Technical Design Specificat. Roped Hydraulic Residential Elevator Swing Type Hoistway Doors
|
|
- Silvia Stafford
- 7 years ago
- Views:
Transcription
1 Technical Design Specificat esign Specification Roped Hydraulic Residential Elevator Swing Type Hoistway Doors
2
3 TABLE OF CONTENTS 1. General Description of Work Work to be performed by Others References American National Standards Institute (ANSI) American Society of Mechanical Engineers (ASME A17.1) National Electric Code (NFPA 70) Qualifications A company with no less than (5) years of successful experience in the assembly and erection of similar type elevators and who has adequate product liability insurance shall perform the installation Regulatory Requirements The elevator installer shall verify requirements of the local authority having jurisdiction, obtain and pay for necessary municipal and state permits and inspections as required, and make tests as called for by the regulations of such authorities Submittals Product Data Layout Drawings Product Manufacturer Characteristics Equipment Operation Hydraulic Power Unit Plunger and Cylinder Pipe Rupture Valve Car Frame Construction Platform Construction Suspension Guide Rails Electric Wiring Controller Home Park Feature Emergency Power Lowering and UPS Battery Backup...9 3
4 7.13. Low Oil Control Operating Fixtures Door Interlocks Hoistway Doors Cab Enclosure Car Gate Execution Examination Installation Operating Instructions Maintenance Warranty
5 1. GENERAL 1.1. Description of Work These specifications are intended to cover the complete installation of one (1) CEI-750 or CEI-950 residential elevator. The elevator is to be installed in a first class workmanlike manner and is to include all work and materials in accordance with specifications and installation drawings. The elevator shall be guaranteed for two years against defective manufacturing. It shall be in compliance with the applicable sections of the Safety Code for Elevators and Escalators ASME A17.1 and all local codes having jurisdiction Work to be performed by Others The following preparatory work that must be performed in conjunction with the elevator installation that is to be done by others and is part of the work of other sections Hoistway A suitable-fire rated hoistway of proper size and construction conforming to the applicable building codes and elevator construction drawings. Hoistway shall be plumb within 1/ Provide adequate guide rail supports able to withstand rail forces shown on layout drawings Provide waterproof pit of adequate design to withstand loads shown on layout drawings Provide adequate knockouts and sleeves from elevator hoistway to machine room for oil and electrical lines Provide knockouts for hall stations at each landing Provide all wall patching, painting and grouting required Provide finish painting of hoistway doors and frames Hoistway doors, frames and door hardware by others. (Elevator contractor may furnish) Machine Room A suitable fire rated machine room of proper size with a lockable door, convenience outlet, and light Machine room temperature must be maintained between 60 degrees and 100 degrees F, with relative humidity not to exceed 95% Machine room must be in compliance with ASME A17.1, National EleCode, applicable building codes, and elevator construction drawings Telephone connection in machine room connected to an outside central exchange where required Machine room vents as required by local code. 5
6 Electrical Requirements 1.3. Quality Assurance 2. REFERENCES A 220VAC, single phase service (or optional three phase) with neutral, to a lockable safety disconnect switch, fused with time delay fuses shall be furnished in the machine room in accordance with NFPA 70. A normally open electric interlock contact is required in the switch for battery isolate A 120VAC, single phase, 15AMP service to a lockable fused disconnect switch, or circuit breaker, located in the machine room shall be provided for the cab lighting in accordance with NFPA The elevator shall be designed, manufactured, installed, and inspected in accordance with ANSI/ASME A17.1 standards and all applicable regulations of federal, state, and local codes and ordinances as adopted by local agencies having jurisdiction American National Standards Institute (ANSI) 2.2. American Society of Mechanical Engineers (ASME) 2.3. National Electric Code (NFPA 70) 3. QUALIFICATIONS 3.1. A company with no less than (5) years of successful experience in the assembly and erection of similar type elevators and which has adequate product liability insurance shall perform the installation. 4. REGULATORY REQUIREMENTS 4.1. The elevator installer shall verify requirements of the local authority having jurisdiction, obtain and pay for necessary municipal and state permits and inspections as required, and make tests as called for by the regulations of such authorities. 5. SUBMITTALS 5.1. Product Data Submit manufacturer s literature including product data, elevator car designs, color charts, signal fixtures, and specifications Layout Drawings Layout drawings shall be submitted showing the general arrangement of the elevator equipment including dimensions, clearances, location of machine equipment, and all loads and reactions imposed on pit and building structure. The elevator contractor is to provide general arrangement drawings of the equipment showing the hoistway, pit, and machine room dimensions. Preliminary Drawings are to be properly approved before commencement of fabrication and/or installation. All surface finishes and colors to be selected and returned with approved drawings. 6
7 6. PRODUCT 6.1. Manufacturer The roped hydraulic residential elevator shall be manufactured by Canton Elevator, Inc., North Canton, OH USA, ( Characteristics 7. EQUIPMENT Type: Roped Cantilever Hydraulic Residential Model: CEI-750 [CEI-950] Capacity: 750 lbs [950 lbs] Operation: Single Automatic Push Button Speed: 40 FPM Car Travel: [ ] feet, [ ] inches No. of Landings: [ qty ] No. of Openings: [ qty ] Front, [ qty ] Rear, [ qty ] Side Nominal Car Size: [ ] [ ] Consult factory for custom sizes Power Supply: 220 VAC, Single Phase, 60 Hz 7.1. Operation Operation of the elevator shall be Single Automatic Push Button (SAPB). Momentary pressure on any call button will initiate a call or send command to the elevator to the corresponding landing providing all doors are properly closed Hydraulic Power Unit A power unit especially designed and manufactured for this service shall be furnished. It shall include a constant displacement rotary screw type pump, motor, oil reservoir, hydraulic control unit and oil level gauge. The hydraulic control unit shall include a safety check valve, an UP direction valve with high pressure relief including UP leveling and soft stop features, a lowering valve including DOWN leveling and a manual lowering feature; all enclosed in a compact unit assembly. The control valves shall be solenoid operated and designed to open and close gradually to give smooth starts and stops. All valves shall be readily accessible for adjustments. The power unit shall be located near the hoistway Plunger and Cylinder The plunger shall be manufactured from accurately ground and polished DOM tubing. The bottom of the plunger shall be fitted with a heavy steel disc welded in place and provided with a continuous stop ring that will provide a positive stop designed to prevent the plunger from leaving the cylinder in the UP direction. The top of the plunger shall be provided with an internally welded steel disc drilled and tapped for fastening a U-groove sheave for 1:2 roping application. The cylinder shall be machined from steel 7
8 pipe with a steel flange at the upper end, a heavy steel plug welded in the lower end and a suitable steel fitting for connecting the oil line Pipe Rupture Valve An automatic shut-off valve in the oil supply line at the cylinder inlet will be provided. When there is a drop in no-load operating pressure or an over speed in the DOWN direction, the automatic shut-off valve shall be actuated and immediately stop the elevator Car Frame Construction The car frame and integrated platform support shall be of welded and bolted steel construction of cantilever design. It shall be fitted with the appropriate diameter polyurethane faced roller guide shoes. Solid guide shoes are not acceptable. An instantaneous broken rope car safety and slack cable switch shall be affixed to the car frame which will cut off power to the control valve if a rope should become slack or broken Platform Construction The platform shall be constructed utilizing 13/16 power strut frame with minimum 3/4 plywood subfloor Suspension The steel car frame shall be attached to and suspended by two (2) 10mm diameter 8 19 IWRC Steel Core Rope. The cables shall be fastened to the pit structure on one end and pass over the U-groove sheave to shackles attached to the car frame and safety device. Should one or more cables break or slacken, a broken rope safety mechanism shall apply two cams to wedge against the elevator guide rails and bring the car to a complete stop Guide Rails The car guide rails shall consist of (2) machined steel tee sections, no less than 8 lbs. per foot, securely fastened to the hoistway structure with steel brackets. The ends of all guides shall be tongue and groove, forming matched joints and shall be connected with steel splice plates. Formed rails or channels are not acceptable Electric Wiring Furnish and install all wiring necessary for a complete installation commencing at the machine room disconnect switch and connecting the controller and power unit to all electrical devices. All wiring is to be in accordance with the requirements of the applicable building codes and the National Electric Code. The traveling cables between the car and the controller shall have a flame retarding and moisture resisting outer cover. They shall be flexible and suitably suspended to relieve strain in the individual conductor Controller An automatic two-way leveling device shall be provided so that the car will approach a landing stop at reduced speed from either direction of travel. The leveling device shall, within its zone, be entirely independent of the operating device and shall automatically stop and maintain the car approximately level, plus or minus 1/4 with the landing, regardless of the change in load. 8
9 7.11. Home Park Feature The elevator shall automatically return to a field programmable designated landing after one minute without use Emergency Power Lowering and UPS Battery Backup An automatic emergency-lowering feature shall be incorporated into the power unit and control system. In the event of the loss of normal power to the elevator, the emergency light output EL will activate and the buzzer output BZ will pulse for 1 second every 15 seconds. The elevator will respond as follows: Power loss during an UP run, the destination call will be dropped and the unit will automatically lower itself to the next lowest floor. If that floor is not the lowest landing, car can be moved to a lower landing by pressing the selected floor button Power loss during a DOWN run, the destination call will be dropped and the unit will automatically lower itself to the next lowest floor. If that floor is not the lowest landing, car can be moved to a lower landing by pressing the selected floor button Power loss while at a floor, unit will stay at the floor level. If a call is placed to a lower floor, and all normally required safety circuits are in the correct state, the unit will lower to the requested floor The EL and BZ output will disable themselves 30 sec after the lower terminal floor had been reached The car will maintain 110 Volt power for approximately four hours (i.e. cab lighting, auto gate operator, etc.) Batteries are to have an automatic charging system. The power supply shall be arranged and sufficiently sized to illuminate cab lighting, operate power gate operator (if supplied), and power emergency alarm Low Oil Control A low oil control feature shall be provided which is designed to automatically cause an UP traveling car to descend to the lowest terminal landing if the system does not have a sufficient reservoir of oil Operating Fixtures Car Operating Panel shall consist of light-up floor call buttons, a red emergency stop button, an alarm button, a light switch, and an optional digital position indicator Hall stations will contain a call button with acknowledge light. One hall station shall be located adjacent to each landing hoistway door Faceplate Style: Standard Faceplate GA: Minimum 1/8 thick Fixture Finish: Brushed Stainless Steel Phone: Integral phone device with Car Operating Panel Security Options: Keyed Car Station, Keyed Hall Stations 9
10 7.15. Door Locks A combination unit system contact and lock shall be furnished for each hoistway entrance. The interlock device shall prevent elevator operation unless all doors are closed and locked and prevent opening of a door when the car is not at rest at that landing. The door interlock shall be designed to mechanically open by cam actuation only when the elevator is positioned at the hoistway landing Hoistway Doors The general contractor or owner is to furnish (elevator contractor may furnish) and install hoistway doors, frames, and hinges and passage sets at each landing. The type and installation of the doors and frames must comply with ASME A17.1, all local codes and per manufacturer s layout drawings. Special attention should be given to ASME A17.1, Part 5.3., Para requiring that for safety reasons, the space between the hoistway door and the car gate does not exceed 5, and that the clearance between the hoistway landing door and the edge of the landing sill does not exceed Cab Enclosure The cab enclosure shall be constructed of 3/4 substrate material. Cab floor to be prepared for floor covering to be supplied and installed by others. Each cab opening shall be equipped with a horizontal sliding manually or power operated accordion type folding gate Wall Finish: Stain-grade sliced veneer or decorative plastic laminate from manufacturer s standard species, stain and color selections Ceiling Material: Minimum 1 thick substrate material Ceiling Finish: White plastic laminate or 12ga white powder coated steel Cab Height: 80 minimum / 96 maximum Cab Lighting: (1) surface mounted chandelier, (2) 120v LED down light fixtures, (1) 3-light LED track light, (4) low voltage LED lights or fixtures by others Handrail: One (1) 3/ Entry Columns: Two (2) for each cab entrance Cab Trim: Brushed Stainless Steel Car Sill: Clear Anodized Extruded Aluminum Car Gate The elevator cab shall be furnished with accordion style, folding gates. Scissor style gates are not acceptable Car Gate Material and Finishes: Vinyl Laminate, Hardwood or Aluminum selected from manufacturer s standard species and color selections Car Gate Vision Panels: Available in all clear or tinted assembly or 3-panel sections in clear or tinted. 10
11 8. EXECUTION 8.1. Examination Elevator installer shall verify dimensions of hoistway, pit, machine room, and inspect conditions of supports and structure prior to installation Installation The elevator shall be installed in accordance with the manufacturer s instructions and shall conform to ASME A17.1 and all state and local code requirements Operating Instructions Upon completion of the installation, the owner shall be instructed on the elevator s operation, safety precautions, and maintenance requirements. The owner shall be supplied with an owner s manual to retain for reference Maintenance The elevator shall be maintained in accordance with the manufacturer s recommendations and all applicable codes Warranty All materials furnished by elevator contractor shall be guaranteed for a period of two (2) years against defects in workmanship during manufacturing. Please see manufacturer s Standard Terms and Conditions for details. 11
12 2575 Greensburg Road North Canton, OH Ph: Fax:
Roped Hydraulic Residential Elevator Specifications
January 1, 2004 Roped Hydraulic Residential Elevator Specifications P.O. Box 749, 5191 Stump Rd., Plumsteadville, PA 18949 Toll Free: 888-443-2800, Phone: 215-766-3380, Fax: 215-766-3385 CONTENTS Part
More informationP.A.L. S SPECIFICATIONS
PART 1- GENERAL 1.1 SCOPE To furnish all labor, materials and equipment necessary or required to complete the installation of the lift as indicated on the Drawings and Specifications. This specification
More informationV1504 Vertical Platform Lift OWNER S MANUAL
V1504 Vertical Platform Lift OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 000692 01-m03-2016 2 IMPORTANT Ensure that only an authorized Savaria Dealer
More informationV1504 Vertical Platform Lift OWNER S MANUAL
V1504 Vertical Platform Lift OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 000692 03-m12-2013 2 IMPORTANT Ensure that only an authorized Savaria Dealer
More informationSECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
More informationSECTION 14 20 10 - FREIGHT & PARKING GARAGE ELEVATORS PART I - GENERAL
SECTION 14 20 10 - FREIGHT & PARKING GARAGE PART I - GENERAL 1.1 SECTION INCLUDES [NOTE to AE: The following lists requirements that are specific to freight elevators. These requirements are in addition
More informationLOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.
LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and
More informationCITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS
Subject: SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS Reference: Denver Fire Code Section 105.7.29 Approved: Joseph L. Gonzales, Division Chief, Fire Prevention Division Number: 105-1 Effective
More informationCLEAR-DIVISIONS APERTO
CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the
More informationCLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
More informationCLEAR-DIVISIONS VARIOFOLD
CLEAR-DIVISIONS VARIOFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS VARIOFOLD moveable The yellow highlighted areas in the
More informationMobile Home Pre-Inspection Checklist
Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING
More informationSECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationUtility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
More informationPUBLIC VERTICAL PLATFORM LIFT PLANNING GUIDE
Multilift PUBLIC VERTICAL PLATFORM LIFT PLANNING GUIDE Applicable Codes: ASME A17.1 ASME A18.1 CSA B613 CSA B355-09 19-m01-2015 Part No. 000790 Copyright 2015 Savaria Corporation All rights reserved. Printed
More informationITEM DESCRIPTION SPECIFICATION TENDER OFFER
TECHNICAL SPECIFICATIONS PL1 & PL2 PLEASE TICK IF YOU COMPLY. SPECIFY YOUR OPTION IF YOU DON'T. ITEM DESCRIPTION SPECIFICATION TENDER OFFER Make (please specify) 1.0 Type Duplex Passenger Lift 2.0 Minimum
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
More informationBLADDER SURGE CONTROL SYSTEM
PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures
More informationPlanning Information. Passenger and Freight Elevators.
A company of ThyssenKrupp Elevator Thyssen Aufzüge tk This planning information will give you an overview of the most important planning criteria of passenger and freight elevators. However you should
More informationOPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationMODEL HSR-007 Direct Drive Rolling Steel
MODEL HSR-007 Direct Drive Rolling Steel 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8 Tel: 866-792-9968 or 705-792-9968 Fax: 705-735-9564 www.tnrdoors.com email: info@tnrdoors.com Model HSR-007
More informationSECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
More informationSECTION 11014 WINDOW WASHING SYSTEMS
SECTION 11014 WINDOW WASHING SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes, but is not limited to, design and furnishing portable davits, davit sleeves, dvit bases, four (4) removable outriggers,
More informationDENVER MODEL 30 X 30 SPECIFICATIONS
DENVER MODEL 30 X 30 SPECIFICATIONS Dimensions: Roof Dimensions 30-0 x 30-0 (4) Columns (Center to Center) 25-6½ x 25-6½ Minimum Clearance 8-0 Roof Height @ Peak Dependent on Col. Ht. Hip Roof 4:12 pitch
More informationGenerator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
More informationELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
More informationSPECIFICATIONS FOR BOON EDAM TOMSED MODEL TUT-65TMB
SPECIFICATIONS FOR BOON EDAM TOMSED MODEL TUT-65TMB PRODUCT DESCRIPTION: BOON EDAM TOMSED MODEL TUT-65TMB STAINLESS STEEL BARCODE SCANNING ELECTRONIC REGISTERING TURNSTILE SCOPE OF OPERATION: A. The TUT-65TMB
More informationPump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationCOLORADO MODEL. 35 x 65 SPECIFICATIONS
COLORADO MODEL 35 x 65 SPECIFICATIONS Dimensions: Roof Dimensions 35-0 x 65-0 Column Dimensions (center to center) 31-0 x 30-6 Minimum Clearance 14-0 Roof Height @ Peak ±18-8 Curved Roof ±42-6 radius Square
More informationAutomatic Door Selection Guide
Automatic Door Selection Guide AAADM 1300 Sumner Avenue Cleveland, OH 44115 P: 216-241-7333 F: 216-241-0105 aaadm@aaadm.com Automatic Door Selection Guide General: The members of AAADM manufacture an assortment
More informationINSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks
Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 techsupport@securitron.com in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate
More informationSECTION 6. Glass Storefront Doors:
SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail
More informationDESIGN CLARIFICATION (DC)
DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:
More informationHOW TO ORDER SAFETY PRODUCTS/SAFETY CONTROL SYSTEMS ELECTRICAL SAFETY CONTROLS
HOW TO ORDER SAFETY PRODUCTS/SAFETY CONTROL SYSTEMS PNEUMATIC SAFETY CONTROLS BASIC CONTROLS SC3000 - SELF CONTAINED 2 HAND CONTROL - STAND ALONE MODEL SC3300 - SELF CONTAINED 2 HAND CONTROL - PRESS READY
More informationB. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related
More informationVOYAGER 570G. 744A Sprayer Control
VOYAGER 570G 744A Sprayer Control U S E R M A N U A L U S E R M A N U A L Table of Contents CHAPTER 1 - INTRODUCTION...1 SYSTEM CONFIGURATIONS...1 KIT CONTENTS...3 CONTROL HOUSING ASSEMBLY...5 CHAPTER
More informationDesign & Construction Standards, Revised January 2013 5.21.30-1
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.
More informationDisplay hidden notes to specifier. (Don't know how? Click Here) A. Advanced Upcoiling Security Grilles, power operated.
SECTION 08333 ADVANCED UPCOILING SECURITY GRILLE MODEL 600 ADV Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Advanced Upcoiling Security Grilles,
More informationIntroduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual
Operation and Maintenance Manual Introduction Read all instructions thoroughly. Installation of the OilTector must comply with all Federal, State and Local Codes, Regulations and Practices. The OilTector
More information(B613) VERTICAL PLATFORM LIFT PLANNING GUIDE
Multilift (B613) VERTICAL PLATFORM LIFT PLANNING GUIDE Applicable Codes: CSA B613 01-m06-2011 Part No. 000790 Copyright 2011 Savaria Corporation All rights reserved. Printed in Canada Purpose of this guide
More informationDEPARTMENT OF CORRECTIONS
Elevator Consulting, LLC. Post Office Box 464 Mequon, WI 53092-0464 Voice/Fax: 262-242-3077 Mobile No: 262-853-1054 E-mail: PerformElevCons@wi.rr.com DEPARTMENT OF CORRECTIONS MILWAUKEE SECURE DETENTION
More informationORIONTM LIMITED USE / LIMITED APPLICATION ELEVATOR
ORIONTM LIMITED USE / LIMITED APPLICATION ELEVATOR Planning Guide Limited Use / Limited Application Elevator Applicable Codes: ASME A17.1, Section 5.2 CAN/CSA B44, Section 5.2 Part No. 000682 10-m03-2016
More informationTECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)
TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless
More informationDORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationJames M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationMETER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
More informationBUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
More informationLift and Escalator Installations
Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-29 Lift and Escalator Installations Building Works Requirements The
More information2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
More informationMorgue refrigeration unit
Morgue refrigeration unit The Morgue refrigeration units are made of sturdy, self-supporting walls, floor and ceiling elements. They are delivered in separate components and are to be assembled on site
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationSapa: SECTION 05520 ARCHITECTURAL ALUMINUM HANDRAILS AND RAILINGS
PART 1 GENERAL Sapa: SECTION 05520 ARCHITECTURAL ALUMINUM HANDRAILS AND RAILINGS 1.1 SECTION INCLUDES A. Aluminum and Glass Handrails B. Aluminum Railings 1.2 RELATED SECTIONS A. Section 05700 - Ornamental
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationLight Duty Commercial Electric Water Heater
Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and
More informationBERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
More informationContractors Guide Central Inverter System Installation
Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.
More informationglass & Glazing Products
glass & Glazing Products WallMaker Create an unlimited variety of bright, beautiful and secure interior environments with the easy-to-install Stylmark WallMaker glass wall system. This versatile system
More informationGas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard
LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled
More informationDIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS
DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including general and supplementary conditions and other Division 1
More informationTroubleshooting Guide for Jacks Down LED Lights
Troubleshooting Guide for Jacks Down LED Lights Equalizer Systems Auto-Level systems manufactured after 2005 feature a pressure switch system that monitors the retracted state of leveling jacks and any
More informationProcurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier
Procurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier A. Requirement This document is to be used to specify the physical and operational
More informationSECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
More informationInstallation Instructions
READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:
More informationCHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.
More informationAutomatic Door Openers and ADA Devices Rev. 0 Bid # 48240056. Scope of Work
Scope of Work I. Scope of Solicitation II. Instructions to Offerors III. Scope of Work / Specifications IV. Terms and Conditions - Special I. SCOPE OF SOLICITATION Clemson is seeking to initiate a turnkey
More informationOHIO MEDICAL CORPORATION. Medical Gas Panel. Installation and Maintenance Manual
OHIO MEDICAL CORPORATION Medical Gas Panel Installation and Maintenance Manual P/N 255105 (Rev.5) 08/2005 P/N 255105 (Rev.5) 08/2005 PAGE 2 OHIO MEDICAL CORPORATION PAGE 3 1.0 User Responsibilities The
More informationTown House 11265 Center Highway North Huntingdon, PA 15642
APPENDIX C SPECIFICATIONS FOR THE CONSTRUCTION OF BUILDING LATERAL SANITARY SEWERS DECEMBER 2004, INCLUDING AMENDMENTS ADOPTED ON FEBRUARY 6, 2008 AND APRIL 2, 2008; EFFECTIVE ON MAY 1, 2008 Town House
More informationDIAMOND Retractable Rodding Robot Model SPRAYROD-R
2004-12-21 2 1 (23) DIAMOND Retractable Rodding Robot Model SPRAYROD-R 2004-12-21 2 2 (23) Table of contents 1 TECHNICAL DESCRIPTION...4 1.1 MAIN DETAILS...5 1.2 COMPONENTS DESCRIPTION...5 1.2.1 Pneumatic
More informationSECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS
1 SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and
More informationCONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
More informationArchitectural Casework 06400-01. 1.01 Description of Work
06400-01 1.01 Description of Work A. Extent of each type of architectural millwork and casework as indicated on drawings. Types of architectural casework shall include both stained and plastic laminated
More informationPLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.
More informationSECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationGUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationPERMITS REQUIRED & PERMIT EXEMPTIONS
PERMITS REQUIRED & PERMIT EXEMPTIONS This guideline is intended to assist the applicant in determining what types of construction work require a permit. The 1997 California Uniform Administrative Code,
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationwith MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
More informationMODEL 300505 INSTALLATION INSTRUCTIONS
WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 info@burcam.com Your pump has been carefully packaged at the factory to prevent damage during shipping.
More informationHydraulic Jack Units. Contact Us! 888-577-EECO (3326) Delivery & Lead Times
Hydraulic Jack Units Elevator Equipment Corporation (EECO) has been manufacturing hydraulic elevator equipment since 1946, and is one of the leading suppliers in the industry for hydraulic jack units and
More information2. Division 05 Structural Steel Framing for steel framework requirements
SECTION 131200 - CLIMBING WALLS PART 1 GENERAL 1.1 SUMMARY A. This section includes the following: 1. GFRC Rock Realistic Climbing Wall System B. Related Sections 1. Division 04 Unit Masonry 2. Division
More informationOPERATING INSTRUCTIONS
PIPELINE INSPECTION COMPANY LTD. OPERATING INSTRUCTIONS Wet Sponge Holiday Detectors 670,673, and MSRB Wet Sponge Holiday Detectors Portable and In-Plant Detectors Table of Contents General Information.......................3
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationUBC Technical Guidelines Division 14 2016 Edition CONVEYING EQUIPMENT Page 1 of 1 INDEX. Section 14 40 00
UBC Technical Guidelines Division 14 2016 Edition CONVEYING EQUIPMENT Page 1 of 1 INDEX Section 14 20 00 Section 14 40 00 Elevators Lifts Page 1 of 14 1.0 GENERAL 1.1 Related UBC Guidelines.1 Division
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationCommercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
More information-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
More informationSECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationSingle Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
More informationHYDRAULIC LIFT TABLE CART 2200-LB.
HYDRAULIC LIFT TABLE CART 2200-LB. OWNER S MANUAL WARNING: Read carefully and understand all MACHINE ADJUSTMENT AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other
More informationInstallation Instructions For Slider Casement Air Conditioners
Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT
More information