PLC 21 FILTER PRESS (GBT) SYSTEM SCADA SYSTEM OPERATION MANUAL. Revision 1.0 July 7, 2006

Size: px
Start display at page:

Download "PLC 21 FILTER PRESS (GBT) SYSTEM SCADA SYSTEM OPERATION MANUAL. Revision 1.0 July 7, 2006"

Transcription

1 PLC 21 FILTER PRESS (GBT) SYSTEM SCADA SYSTEM OPERATION MANUAL Revision 1.0 July 7, 2006

2 PLC 21 FILTER PRESS (GBT) SYSTEM SCADA SYSTEM OPERATION MANUAL Revision 1.0 July 7, 2006 Table of Contents 1 Introduction Revision History Conventions Set Points and Process Values Equipment Colors Line sizes and colors Instrument Bubbles New Control Strategies Primary Sludge Flow Control Flow Measurement Flow Control Loop Control Valves Interlocks Sludge Conditioning Polymer System Control Inventory Measurement Polymer Blend Units Interlocks Gravity Belt Thickeners Thickening Recycle Pump Station Level Control Pump Control Interlocks Thickened Sludge Pump Station July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 2 of 31

3 4.5.1 Level Control Pump Control Interlocks Flow Measurement Sample Screens GBT System Overview GBT Navigation Menu Gravity Belt Thickener Primary Sludge Feed Modulating Valve Flow Control Loop Sludge Conditioning Polymer Polymer Blend Unit Pop Up Sludge Polymer Set Points Thickening Recycle Pump Station Recycle Level Control Loop Recycle Pump Pop Up Recycle Set Points Thickened Sludge Pump Station Sludge Level Control Loop Thickened Sludge Pump Pop Up Thickened Sludge Set Points Flow Transmitter Pop Up Weight Transmitter Pop Up July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 3 of 31

4 PLC 21 FILTER PRESS (GBT) SYSTEM SCADA SYSTEM OPERATION MANUAL Revision 1.0 July 7, Introduction This document presents sample SCADA screens and operation description for the Gravity Belt Thickeners (GBTs) at the Stockton Regional Wastewater Control Facility. 2 Revision History The table below shows the history of revisions to this document. Rev. Description By Date 1.0 Issued for customer training Max Hanson/ 07-Jul-06 Imran Saeed 3 Conventions 3.1 Set Points and Process Values Set points appear with a black background inset field and white text. Process values will show an inset field with a white background and blue text. Status indicators also have the white inset field, but the foreground color may change depending upon the conditions and the background will turn yellow for abnormal situations. Status Indicator Text Colors: Text Background Meaning Dark Red White Not called, inactive, off Dark Green White Called, active, on Gray White Not ready, unavailable for PLC control July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 4 of 31

5 Black Yellow Alarm, abnormal condition 3.2 Equipment Colors Symbols for motor-driven equipment are animated with colors to reflect status. Valves symbols are also color-coded. Foreground Red Green Gray Yellow Foreground Red Green Gray Yellow Meaning Not called, inactive, off Called, active, on Not ready, unavailable for PLC control Alarm, abnormal condition Meaning Closed Opened (or called to open if no feedback) Not ready, unavailable for PLC control Alarm, abnormal condition 3.3 Line sizes and colors Where appropriate, major process lines are shown with 3D pipe symbols and are animated to show when fluid is flowing. Minor process lines are shown with a dark gray background and an animated foreground color. Minor process lines do not have 3D appearance and are smaller. Foreground Gray Blue Cyan Yellow Light Green Magenta Pink Light Brown Teal White Dark Brown Meaning No flow is present Plant water Miscellaneous minor process (e.g., scrubbant) Sulfur dioxide Chlorine or sodium hypochlorite Ferric Chloride Polymer Wastewater Storm water Air Sludge July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 5 of 31

6 3.4 Instrument Bubbles Many screens will be arranged to show process flow similar to a Process and Instrumentation Diagram (P&ID). Instrument bubbles will show tag names and will have the relevant process value displayed. These bubbles are animated and will turn yellow when an alarm is present at the instrument represented by the bubble. Clicking on the instrument bubble will open the appropriate pop-up screen (note that these symbols are not used for some existing instruments as the PLC logic does not include all the features necessary to support the pop up screen). 4 New Control Strategies PLC #21 is a new controller that will control operation of the gravity belt thickeners and related processes. 4.1 Primary Sludge Flow Control Two new valves are added to the primary sludge line feeding the gravity thickeners. FV is on the branch leg and controls flow that bypasses the gravity thickeners and flows to the new gravity belt thickeners. FV is on the main leg going to the splitter box for the existing gravity thickeners. These are modulating valves that actuate to achieve a desired primary sludge bypass flow rate. Each valve s position is controlled by a 4-20mA signal from the PLC. The PLC receives signals from a remote switch, a fully opened limit switch and a fully closed limit switch for each valve Flow Measurement A magnetic flow meter, FIT , measures the primary sludge bypass flow rate that goes to the GBTs. The PLC receives this flow rate in the form of a 4-20mA signal. High-high, high, low and low-low alarms are provided with adjustable set points. The low and low-low alarms will only be enabled when the primary sludge pumps are running and the bypass valve is open. A transmitter fail alarm is posted when the signal is out of range. All these alarms have a common delay set point. All alarms for the instrument are disabled by a common disable selector. A resettable flow total is calculated by the PLC in millions of gallons Flow Control Loop A proportional and integral (PI) loop is used to control the primary sludge bypass flow rate. The output from the algorithm is used to control both valves. The loop may also be placed in manual control so that a fixed output can be used Control Valves Operating Modes MANUAL the operator enters the valve position command. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 6 of 31

7 AUTOMATIC The valves modulate when either GBT is running and the primary sludge feed selector switch is set to ON. When the GBTs are off, FV will close and FV will go to 100% open Monitoring SCADA and OIT displays show local / remote, ready, limit switch and position command status information. A valve fail to open alarm is posted if the closed limit switch signal is received when the position command is above 5% for a delay period. Similarly a fail to close alarm will be posted when the open limit switch remains energized and the position command is below 95%. The valve is considered READY if it is in remote mode and has no failure alarms active. Alarms for each valve may be disabled Interlocks The primary sludge pumps (controlled by PLC #4) will be prevented from operation if both FV and FV are fully closed. 4.2 Sludge Conditioning Polymer System Control The polymer system feeds polymer to the sludge immediately upstream of the gravity belt thickeners. A manual isolation valve allows for two modes of operation. If the valve is closed, the operator should select the ISOLATED mode. If the valve is open, the operator should select COMMON mode on the SCADA or OIT Isolated Mode In this normal operating mode, each polymer blend unit (PBU) is dedicated to a single GBT. It will start and stop in response to the operation of the GBT with the same number and it will receive its dose command from that GBT Common Mode If the isolation valve is open, the operator should select the COMMON mode, wherein the discharge of the PBUs is tied together, allowing one PBU to serve both GBTs. When common mode is selected, any PBU that is in automatic mode and ready for PLC control will start when either GBT is ready for sludge. If both GBTs are running the dose requests are averaged to determine the required polymer flow rate. If only one GBT is running, its dose command is used. If two PBUs are running, each will be commanded to provide half the polymer flow. It should be noted that, if operating a single GBT in COMMON mode, the operator should close an isolation valve in the polymer feed line to the GBT that is offline to prevent polymer addition where it is not desired Dose Calculation The target raw polymer flow rate is calculated by the equation below. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 7 of 31

8 Polymer Flow (gph) = 6 x Sludge Flow x Sludge Concentration x Dose Activity x Specific Gravity x 2 x 108 Sludge Flow is the sum of the primary sludge bypass flow rate (FIT ) and the secondary sludge flow rates (FI ~FI ) in gallons per minute. Sludge concentration is the estimated weight of dry sludge in milligrams per milliliter of sludge. Dose is the amount of raw polymer per ton of dry sludge requested by the GBT in pounds per ton. Activity is a polymer activity constant entered by the operator in percent Inventory Measurement Two polymer totes are used to store the raw polymer. These totes are located on scales that transmit 4-20mA signals to the PLC. The outlets of the two totes are tied together to feed the polymer blend units. High-high, high, low and low-low weight alarms are furnished for each tote, as is a weight transmitter failure alarm Polymer Blend Units Operating Modes MANUAL In manual mode, the operator turns the PBU on or off and sets the desired raw polymer flow rate and concentration of diluted polymer solution. AUTOMATIC In automatic mode, the PLC will start and stop the PBU in response to GBT operation and system mode. Desired raw polymer flow rate is calculated as described above. The operator sets the desired concentration for the dilute polymer solution independently for each PBU Monitoring The PBU sends the PLC the following status signals: FAULT shows as a failure alarm on SCADA and OIT screens LOW FLOW low dilution water flow rate REMOTE set to remote control PUMP running or off SPEED pump speed (4-20mA) FLOW RATE dilution water flow rate (4-20mA) The PLC sends the PBU the following commands: July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 8 of 31

9 CALL run command FLOW COMMAND desired raw polymer flow rate (4-20mA) CONCENTRATION desired dilute polymer solution concentration (4-20mA) The PLC tracks run time for the PBU and posts a failure alarm when the fault signal is present or the PBU does not respond with a running signal after being called for a time delay Interlocks A low-low level in both polymer totes prevents automatic operation of the PBUs. A PBU failure alarm is triggered if a PBU faults or fails to run when called to do so. This alarm latches until reset by an operator. A PBU will not be called if it has failed. 4.3 Gravity Belt Thickeners The GBTs are skid-mounted machines that incorporate their own PLC controls. The plant control system interacts with the GBTs in a supervisory manner, issuing start and stop commands and receiving status information. Status signals monitored by PLC #21 and displayed on SCADA and OIT screens include: GENERAL FAULT Fault signal from GBT (shows as failure on SCADA) BELT DRIVE Belt drive running or off THICKENER ON GBT system is active WASH PUMP Wash pump running or off HYDRAULIC POWER UNIT Hydraulic pump running or off READY GBT is ready for sludge (note that this ready signal differs from ready for PLC control signals for other plant equipment) REMOTE GBT in remote auto mode versus local manual POLYMER DOSE Requested polymer dose (4-20mA) PLC #21 generates a failure alarm if the general fault signal is present or the GBT does not respond with a Thickener On signal within a time delay after being called. The PLC also tracks runtime. 4.4 Thickening Recycle Pump Station The thickening recycle pump station receives filtrate and wash water from the GBTs. It pumps this fluid to the influent distribution structure of the primaries. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 9 of 31

10 4.4.1 Level Control An ultrasonic level transmitter measures the level of fluid in the wet well. A PI control loop is used to vary the speed of the operating pump in order to maintain the level at a target set point. High-high, high, low and low-low level alarms with adjustable set points are provided for this instrument. An out of range signal triggers a failure alarm. In addition to the transmitter, high and low level switches also monitor the level. These provide for redundant high and low alarms Pump Control Only one pump runs at a time. The pumps are controlled in an Active / Standby pair. The operator may specify the active pump or the assignment may be set to rotate based upon operating time Operating Modes MANUAL The pump starts and stops in response to pushbuttons. Speed may be set from the operator interface. AUTOMATIC The pump starts and stops in response to system operating conditions. Speed is controlled by the level control loop Monitoring The following status points are monitored and displayed on the operator interface. REMOTE VFD is set for remote (PLC) control rather than local keypad control. READY Pump is ready for PLC control (in remote and not failed) FAULT VFD is reporting a fault condition. FAIL Either a fault has been present for a delay time or the VFD did not return a running status after being called for a delay period. RUNNING Motor is running. CALLED VFD is called to run by the PLC. SPEED COMMAND The speed requested by the PLC (%). SPEED Actual speed at which the VFD is operating (%). CURRENT Current output of the VFD to the motor (Amps). RUNTIME Reported in tenths of an hour Interlocks A low-low level alarm or a low level switch alarm will prevent automatic operation of the thickened sludge pumps. A pump failure alarm is triggered if a VFD faults or fails to run when called to do so. This alarm latches until reset by an operator. A pump will not be called if it has failed. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 10 of 31

11 4.5 Thickened Sludge Pump Station Thickened sludge collects at the thickened sludge pump station between the GBTs. Each GBT has its own wetwell and associated thickened sludge pump. The pumps convey the thickened sludge to the digesters Level Control Each thickened sludge wetwell is equipped with an ultrasonic level transmitter. A PI control loop is used to vary the speed of the operating pump in order to maintain the level at a target set point. High-high, high, low and low-low level alarms with adjustable set points are provided for each instrument. An out of range signal triggers a failure alarm. In addition to the transmitter, high and low level switches also monitor the level in each wetwell. These provide for redundant high and low alarms Pump Control Operating Modes MANUAL The pump starts and stops in response to pushbuttons. Speed may be set from the operator interface. AUTOMATIC The pump starts and stops in response to system operating conditions. Speed is controlled by the level control loop Monitoring The following status points are monitored and displayed on the operator interface. REMOTE VFD is set for remote (PLC) control rather than local keypad control. READY Pump is ready for PLC control (in remote and not failed) FAULT VFD is reporting a fault condition. FAIL Either a fault has been present for a delay time or the VFD did not return a running status after being called for a delay period. RUNNING Motor is running. CALLED VFD is called to run by the PLC. SPEED COMMAND The speed requested by the PLC (%). SPEED Actual speed at which the VFD is operating (%). CURRENT Current output of the VFD to the motor (Amps). RUNTIME Reported in tenths of an hour. HIGH DISCHARGE PRESSURE Monitored by a pressure switch in the discharge piping Interlocks Interlock conditions prevents a piece of equipment from operating. There are several interlocks that will stop a thickened sludge pump. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 11 of 31

12 A pump failure alarm is triggered if a VFD faults or fails to run when called to do so. This alarm latches until reset by an operator. A pump will not be called if it has failed. A pressure switch monitors the discharge pressure for each sludge pump. If high discharge pressure is detected for a delay period, an alarm is posted. Like the pump failure, this alarm latches until reset by an operator Flow Measurement A magnetic flow meter, FIT , measures the thickened sludge flow rate. The PLC will receive this flow rate in the form of a 4-20mA signal. High-high, high, low and low-low alarms are provided with adjustable set points. The low and low-low alarms will only be enabled when the primary sludge pumps are running and the bypass valve is open. A transmitter fail alarm is posted when the signal is out of range. All these alarms have a common delay set point. All alarms for the instrument are disabled by a common disable selector. A resettable flow total is calculated by the PLC in millions of gallons. 5 Sample Screens Sample screens for the GBT system follow. These are screens that will appear on the plant SCADA system. Please note that only simulated process data was present when these screens were generated. This means that process values will show simulated values and operating scenarios that are not actually possible may be shown. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 12 of 31

13 5.1 GBT System Overview This screen presents an overview of the Gravity Belt Thickeners and related systems. Equipment that is running has a green indicator. The GBTs also have arrows that appear showing direction of belt travel. Clicking on a system will open a pertinent detail screen. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 13 of 31

14 5.2 GBT Navigation Menu The navigation menu applies for all the GBT screens. When the mouse is moved to the very left side of the screen this menu will appear, allowing a viewer to quickly navigate to other GBT systems. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 14 of 31

15 5.3 Gravity Belt Thickener The GBT screen presents detailed status information for the GBT and allows an operator to start or stop it. There is no automatic mode for a GBT. When an operator wants to run it, he or she will click the On / Off button and a start command will be sent. When the GBT is ready for sludge, the secondary sludge pumps will be allowed to start pumping as will the primary sludge pumps if they primary sludge bypass mode is active. If the load shed button is selected, the GBT will be stopped during a power outage. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 15 of 31

16 5.4 Primary Sludge Feed In normal operation, the primary sludge goes to the gravity thickeners and the GBTs are used for processing secondary sludge. If Primary Sludge Bypass to GBT is switched to ON, valves FV and FV will modulate so that the target primary sludge flow will go to the GBT system. Clicking on the status fields for the valves will open valve pop-up screens (example follows). Clicking the loop button will open the loop view screen shown below. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 16 of 31

17 5.5 Modulating Valve Clicking either of the status boxes launches the modulating valve pop up screen for the selected valve. If valve is placed in manual mode, the operator may adjust the position command directly. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 17 of 31

18 5.6 Flow Control Loop Clicking the loop button opens the loop view pop up for the flow controller. From this screen the operator can control loop mode and adjust the flow target. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 18 of 31

19 5.7 Sludge Conditioning Polymer This screen shows the sludge conditioning polymer system. From here the operator may toggle between isolated and common modes depending upon the position of the manual isolation valve. Clicking on the status boxes for the PBUs will open the detailed PBU pop up screen. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 19 of 31

20 5.8 Polymer Blend Unit Pop Up The PBU pop up shows detailed information and allows an operator to control a polymer blend unit. The On/Off button is disabled in automatic mode because the PBU will start and stop in response to GBT ready status. The operator adjusts the desired polymer concentration in either auto or manual mode. In manual mode the operator starts and stops the PBU and sets the desired raw polymer flow rate. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 20 of 31

21 5.9 Sludge Polymer Set Points Clicking the Control Set Points button on the polymer screen opens the polymer set point pop up screen shown to the left. This screen allows the operator to enter parameters affecting the polymer dosage calculations. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 21 of 31

22 5.10 Thickening Recycle Pump Station This screen shows the thickening recycle pump station. It features two variable speed submersible pumps. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 22 of 31

23 5.11 Recycle Level Control Loop Clicking the loop button next to the level transmitter opens the loop view for the level control loop. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 23 of 31

24 5.12 Recycle Pump Pop Up Clicking the status box for one of the pumps opens a variable speed pump pop up for that pump. In manual mode the operator starts and stops the pump and sets its speed command. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 24 of 31

25 5.13 Recycle Set Points The control set points button opens up this screen, showing the level set points for the pump station. The red vertical bar next to the level bar graph indicates the operating range for the active pump. The arrow shows the level control target. Active pump assignment may be fixed or rotating, according to operator selection. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 25 of 31

26 5.14 Thickened Sludge Pump Station The thickened sludge pump station features two wetwells and two progressive-cavity pumps. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 26 of 31

27 5.15 Sludge Level Control Loop Each wetwell has a level control loop that controls level by varying pump speed. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 27 of 31

28 5.16 Thickened Sludge Pump Pop Up Clicking the status box for a pump opens the variable speed pump pop-up. In manual mode the operator starts and stops the pump and sets its speed command. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 28 of 31

29 5.17 Thickened Sludge Set Points Clicking the control set points button on the pump station screen opens the set point window. Control and alarm set points are presented for each wetwell. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 29 of 31

30 5.18 Flow Transmitter Pop Up Typical for new process value transmitters (as opposed to existing ones), clicking on the flow transmitter bubble will open a pop-up where alarm status can be viewed and alarm set points may be adjusted. The bell symbol shows that alarms are currently enabled for this device. A No symbol will cover the bell when alarms are disabled. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 30 of 31

31 5.19 Weight Transmitter Pop Up A polymer weight transmitter pop up is shown as another example. Similar pop ups can be opened for the level transmitters. July 7, 2006 Rev. 1.0 PLC 21 Filter Press (GBT) System SCADA System Operation Manual 31 of 31

PLC 1 SEPTIC SYSTEM SCADA SYSTEM OPERATION MANUAL. Revision 1.0 June 05, 2006

PLC 1 SEPTIC SYSTEM SCADA SYSTEM OPERATION MANUAL. Revision 1.0 June 05, 2006 PLC 1 SEPTIC SYSTEM SCADA SYSTEM OPERATION MANUAL Revision 1.0 June 05, 2006 PLC 1 SEPTIC SYSTEM SCADA SYSTEM OPERATION MANUAL Revision 1.0 June 05, 2006 Table of Contents 1 Introduction... 2 2 Revision

More information

Equipment and Instrument Tagging Requirements

Equipment and Instrument Tagging Requirements Sanitary Sewer Overflow (SSO) Control and Wastewater Facilities Program Equipment and Instrument Tagging Requirements City of Baton Rouge/Parish of East Baton Rouge Department of Public Works Submitted

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030)

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) PART 1 - GENERAL SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) 1.01 SUMMARY This section describes the operation and control of a drip irrigation system. The major components

More information

Programming Logic controllers

Programming Logic controllers Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,

More information

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS Definition: Zone Selective Interlocking (ZSI) - A method which allows two or more ground fault breakers to communicate with each other so that a short circuit or ground fault will be cleared by the breaker

More information

Green = 0,255,0 (Target Color for E.L. Gray Construction) CIELAB RGB Simulation Result for E.L. Gray Match (43,215,35) Equal Luminance Gray for Green

Green = 0,255,0 (Target Color for E.L. Gray Construction) CIELAB RGB Simulation Result for E.L. Gray Match (43,215,35) Equal Luminance Gray for Green Red = 255,0,0 (Target Color for E.L. Gray Construction) CIELAB RGB Simulation Result for E.L. Gray Match (184,27,26) Equal Luminance Gray for Red = 255,0,0 (147,147,147) Mean of Observer Matches to Red=255

More information

Ovation Operator Workstation for Microsoft Windows Operating System Data Sheet

Ovation Operator Workstation for Microsoft Windows Operating System Data Sheet Ovation Operator Workstation for Microsoft Windows Operating System Features Delivers full multi-tasking operation Accesses up to 200,000 dynamic points Secure standard operating desktop environment Intuitive

More information

How To Clean Up A Reactor Water Cleanup

How To Clean Up A Reactor Water Cleanup General Electric Systems Technology Manual Chapter 2.8 Reactor Water Cleanup System TABLE OF CONTENTS 2.8 REACTOR CLEANUP SYSTEM... 1 2.8.1 Introduction... 2 2.8.2 System Description... 2 2.8.3 Component

More information

Real Time Monitor. A Real-Time Windows Operator Interface. DDE Compliant. (for remote data display)

Real Time Monitor. A Real-Time Windows Operator Interface. DDE Compliant. (for remote data display) Real Time Monitor A Real-Time Windows Operator Interface DDE Compliant (for remote data display) TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 INSTALLATION...2 1.2 FIRST START UP - DDE CONFIGURE...2 1.3 AUTO-STARTUP...2

More information

SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS)

SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS) SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS) PART 1: GENERAL 1.01 SCOPE OF WORK A. Under this section of the specifications, the contractor shall furnish and install a shop-fabricated 4X4 Dispersal

More information

Safety Requirements Specification Guideline

Safety Requirements Specification Guideline Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se -1- Summary Safety Requirement

More information

ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES

ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES by Kazuhiro Takeda Research Manager, Research and Development Center and Kengo Hirano Instrument and Control Engineer,

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

2011, The McGraw-Hill Companies, Inc. Chapter 5

2011, The McGraw-Hill Companies, Inc. Chapter 5 Chapter 5 5.1 Processor Memory Organization The memory structure for a PLC processor consists of several areas, some of these having specific roles. With rack-based memory structures addresses are derived

More information

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142

More information

Appendix S Pump Station Evaluation

Appendix S Pump Station Evaluation Appendix S Pump Station Evaluation Technical Memorandum Date: October 12, 2001 To: Re: Orange County Utilities Task 6.4 Raw Wastewater Pump Stations 1.0 Summary In accordance with Task 6.4 of the Orange

More information

How to read this guide

How to read this guide How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information

More information

PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator

PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator 3.635.5275.251 IM-P486-19 CH Issue 2 PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator Installation, Start-up and Operation Manual 1. Safety information 2. General product information 3.

More information

PowerWorld Simulator

PowerWorld Simulator PowerWorld Simulator Quick Start Guide 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com Purpose This quick start guide is intended to

More information

Features. Emerson Solutions for Abnormal Situations

Features. Emerson Solutions for Abnormal Situations Features Comprehensive solutions for prevention, awareness, response, and analysis of abnormal situations Early detection of potential process and equipment problems Predictive intelligence network to

More information

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety

More information

Rockwell Software Online Demo System

Rockwell Software Online Demo System Rockwell Software Online Demo System Table of Contents TABLE OF CONTENTS 1 ROCKWELL SOFTWARE ONLINE DEMO SYSTEM 3 ABOUT THIS SCRIPT 3 HOW TO USE THIS SCRIPT 3 BEFORE YOU BEGIN 4 NAVIGATION 5 DEMO WATER

More information

E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT

E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL 1.1. SCOPE OF WORK A. Under this item the Contractor shall furnish and install a sodium hypochlorite solution metering system complete with all accessories

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Description of the Water Conserv II Facility

Description of the Water Conserv II Facility Description of the Water Conserv II Facility Introduction The Water Conserv II (WCII) Water Reclamation Facility provides service to a majority of the southwest section of Orlando. The WCII facility has

More information

GPD 506/P5 Start-up Procedure and Checklist

GPD 506/P5 Start-up Procedure and Checklist GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass

More information

Recognizing and understanding schematic symbols will enable you to comprehend a circuit s function.

Recognizing and understanding schematic symbols will enable you to comprehend a circuit s function. Schematic symbols are used to identify and graphically depict the function of fluid power components. Recognizing and understanding schematic symbols will enable you to comprehend a circuit s function.

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace. SAFETY Industrial DESCRIBE hazards and precautions taken to avoid injury in the workplace. Example #1: All of the following are common PPE used to perform maintenance activities EXCEPT: a. Safety Glasses

More information

Chemical Feed System Operation and Design Considerations

Chemical Feed System Operation and Design Considerations PNWS AWWA MAY 7, 2014 EUGENE, OREGON Chemical Feed System Operation and Design Considerations Kevin Batridge Lake Oswego Tigard Water Partnership Austin Peters MWH Global Chemical Delivery and Storage

More information

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS WG2 Dimensions: LxHXW: 26 x 14.5 x 29.5 cm INTERNAL Alarm Terminals EXTERNAL Alarm Terminals WG2 Control Unit WaterGuard

More information

Twido Simulator - Online Help Scope What's in this Part? Twido Simulator Overview What's in this Chapter? How to Use Twido Simulator

Twido Simulator - Online Help Scope What's in this Part? Twido Simulator Overview What's in this Chapter? How to Use Twido Simulator Page 1 of 10 Scope This is the Online Help for the Twido Simulator. The Twido Simulator is a feature of TwidoSuite which allows you to test, run and a debug a program by simulating a connection between

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around

More information

Procidia Control Solutions Dedicated Backup in a Single Variable Control Loop

Procidia Control Solutions Dedicated Backup in a Single Variable Control Loop APPLICATION DATA AD353-109 Rev 3 April 2012 Procidia Control Solutions Dedicated Backup in a Single Variable Control Loop In critical control applications, a dedicated backup controller can provide increased

More information

Model SETR-50 and SETR-51 Trim Tab Control

Model SETR-50 and SETR-51 Trim Tab Control Model SETR-50 and SETR-51 Trim Tab Control Pictured above is the SETR-50 with black switches on a gray background. The SETR-51 is identical except for the color, wherein it has black switches on a black

More information

Transmitter Interface Program

Transmitter Interface Program Transmitter Interface Program Operational Manual Version 3.0.4 1 Overview The transmitter interface software allows you to adjust configuration settings of your Max solid state transmitters. The following

More information

A descriptive definition of valve actuators

A descriptive definition of valve actuators A descriptive definition of valve actuators Abstract A valve actuator is any device that utilizes a source of power to operate a valve. This source of power can be a human being working a manual gearbox

More information

2.24. Pump Controller 704. Data Sheet

2.24. Pump Controller 704. Data Sheet Pump Controller 704 2.24 There are several reasons to choose an MJK pump controller. Pump controller 704, as described in this data sheet, was introduced in 1989. It has been updated several times with

More information

Operation Manual TPOP MINI. Doc No. OM-1213424-0101. 2.212134240101fro.fm

Operation Manual TPOP MINI. Doc No. OM-1213424-0101. 2.212134240101fro.fm OM Operation Manual Tetra Alcip 10 TPOP MINI 2.212134240101fro.fm This document is valid for: Series No/ Machine No OM Operation Manual 2.212134240101fro.fm Issue 2002-01 Tetra Pak Dairy & Beverage Systems

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4 Present sample project 1 HMI configuration 2 SIMATIC Getting Started Insert HMI device from libraries 3 Configuring HMI connection 4 Configuring system diagnostics 5 Simulating an HMI device 6 05/2014

More information

Software version 1.1 Document version 1.0

Software version 1.1 Document version 1.0 Software version 1.1 Document version 1.0 1 RDNET PROTOCOL OVERVIEW... 2 1.1 Network description... 2 1.2 Connection topology... 2 2 SOFTWARE BASIC OPERATIONS... 3 2.1 Main View elements... 3 2.2 Scanning

More information

City of West Palm Beach makes Water Treatment Plant Improvements by Implementing Priority Projects

City of West Palm Beach makes Water Treatment Plant Improvements by Implementing Priority Projects October 13, 2014 Tulsa, OK City of West Palm Beach makes Water Treatment Plant Improvements by Implementing Priority Projects Ron Cass Gert-Jan Schers Location West Palm Beach 2 Consent Order - 2008 Source

More information

Cod. Documento: RT2014-0515a Title: Fimer Plant Controller Description. Rev. Data Redatto Approvato. 00 15-9-2014 S.Sidoti A.

Cod. Documento: RT2014-0515a Title: Fimer Plant Controller Description. Rev. Data Redatto Approvato. 00 15-9-2014 S.Sidoti A. Pag 1 di 19 SCOPE The main purpose of the Fimer Plant Controller is make possible to the Grid Operator both remote and local control capability over an entire PV plant from a single control point The Fimer

More information

CGC s Hybrid System Loop Control

CGC s Hybrid System Loop Control verview The CGC Group Hybrid Heat Pump System does NT operate with the same fluid loop temperatures as a conventional reversing Water Source Heat Pump system. The CGC system differs from a WSHP system

More information

Jump Start: Aspen HYSYS Dynamics V7.3

Jump Start: Aspen HYSYS Dynamics V7.3 A Brief Tutorial (and supplement to training and online documentation) Glenn Dissinger, Product Director, Aspen Technology, Inc. Julie Levine, Associate Product Marketing Professional, Aspen Technology,

More information

STEP 7 MICRO/WIN TUTORIAL. Step-1: How to open Step 7 Micro/WIN

STEP 7 MICRO/WIN TUTORIAL. Step-1: How to open Step 7 Micro/WIN STEP 7 MICRO/WIN TUTORIAL Step7 Micro/WIN makes programming of S7-200 easier. Programming of S7-200 by using Step 7 Micro/WIN will be introduced in a simple example. Inputs will be defined as IX.X, outputs

More information

Color Balancing Techniques

Color Balancing Techniques Written by Jonathan Sachs Copyright 1996-1999 Digital Light & Color Introduction Color balancing refers to the process of removing an overall color bias from an image. For example, if an image appears

More information

Industrial Steam System Process Control Schemes

Industrial Steam System Process Control Schemes Industrial Steam System Process Control Schemes This paper was developed to provide a basic understanding of the different process control schemes used in a typical steam system. This is however a fundamental

More information

Measuring, Controlling and Regulating with labworldsoft

Measuring, Controlling and Regulating with labworldsoft Kai-Oliver Linde IKA-Werke Staufen Neumagenstraße 27 79219 Staufen Measuring, Controlling and Regulating with labworldsoft Rapid and easy networking of lab devices from different manufacturers The user

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

White Noise Help Guide for iphone, ipad, and Mac

White Noise Help Guide for iphone, ipad, and Mac White Noise Help Guide for iphone, ipad, and Mac Created by TMSOFT - www.tmsoft.com - 12/08/2011 White Noise allows you to create the perfect ambient sound environment for relaxation or sleep. This guide

More information

e-ask electronic Access Security Keyless-entry

e-ask electronic Access Security Keyless-entry e-ask electronic Access Security Keyless-entry e-fob Keyless-entry entry System Full-Function Function Installation Manual FCC ID: TV2EFOB1 (UM20 ~ 22793-02) Table of Contents Introduction... 1 e-fob Operation

More information

Introduction To SCADA and Telemetry

Introduction To SCADA and Telemetry Introduction To SCADA and Telemetry Joe Mullaney Senior I&C Engineer MSE Technology Applications, Inc. Tetragenics Division joe.mullaney@mse-ta.com Overview Definitions What is SCADA? What is Telemetry?

More information

AQUAPRO INDUSTRIAL CO.,LTD. Reverse Osmosis Parts Introduction

AQUAPRO INDUSTRIAL CO.,LTD. Reverse Osmosis Parts Introduction Reverse Osmosis Parts Introduction Reverse Osmosis Flow Chart AQUAPRO INDUSTRIAL CO.,LTD Triple Membrane WATER IMPROVER WATER IMPROVER 2 Reverse Osmosis Electrical Diagram AC-220V Power (2.0 point) (W)

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

Fleet Manager Quick Guide (Non Maintenance Mode)

Fleet Manager Quick Guide (Non Maintenance Mode) Fleet Manager Quick Guide (Non Maintenance Mode) Launch Fleet Manager: Open the Fleet Manager Application by: 1. Double clicking the icon located on the desktop - or 2. Via Start > Programs > MobileView

More information

Shadow TX(A) Shadow RX

Shadow TX(A) Shadow RX Shadow TX(A) Shadow RX Asset Management and RFID Transmitter Tags Asset Management Receiver The Shadow TX(A) and Shadow RX wireless asset management system is a standalone wireless asset tracking system

More information

MC4-50 Feeding System

MC4-50 Feeding System MC4-50 Feeding System Dry Calcium Hypochlorite For Municipal Applications The smarter way to water quality PATENTED SPRAY TECHNOLOGY DELIVERS UNPARALLELED CONSISTENT RESULTS The Constant Chlor Plus MC4-50

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Power consumption (kw)

Power consumption (kw) OS Series Series description LIT OS systems are applied to wastewater disinfection. The models of this series were developed on base of high-efficiency low-pressure amalgam lamps and have all components

More information

9452/9453 Installation and User Guide

9452/9453 Installation and User Guide 9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and

More information

Electrical Systems - IQAN Digital Control System. IQAN Control System Components... 5.1.3

Electrical Systems - IQAN Digital Control System. IQAN Control System Components... 5.1.3 Section 5.1 Electrical Systems - IQAN Digital Control System IQAN Control System Components........................... 5.1.3 IQAN Operational Description: At Machine Startup.....................................

More information

SCADA System Fundamentals

SCADA System Fundamentals SCADA System Fundamentals Course No: E01-007 Credit: 1 PDH Tracy Adams, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Programming A PLC. Standard Instructions

Programming A PLC. Standard Instructions Programming A PLC STEP 7-Micro/WIN32 is the program software used with the S7-2 PLC to create the PLC operating program. STEP 7 consists of a number of instructions that must be arranged in a logical order

More information

Job Scheduler User Guide IGSS Version 11.0

Job Scheduler User Guide IGSS Version 11.0 Job Scheduler User Guide IGSS Version 11.0 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained therein.

More information

Maxi Pressurisation Units (Maxi, Maxi Plus & HP)

Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Installation and Maintenance Instructions Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5

More information

How To Control A Car Alarm On A Car With A Remote Control System

How To Control A Car Alarm On A Car With A Remote Control System MODEL CA100 REMOTE CONTROL AUTO ALARM SYSTEM INSTALLATION & OPERATION INSTRUCTIONS WIRING DIAGRAM Black Antenna Wire 6 Pin 6 Pin Mini Connector Valet Switch Blue LED Indicator Blue Wire: (-) 200mA Unlock

More information

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits: Variable Frequency Drives (or VFDs) are becoming almost standard part of aquatics equipment room packages. Most VFDs are fairly simple to install and operate however, they are quite complex with respect

More information

Technical Training Module ( 30 Days)

Technical Training Module ( 30 Days) Annexure - I Technical Training Module ( 30 Days) Section 1 : Programmable Logic Controller (PLC) 1. Introduction to Programmable Logic Controller - A Brief History, Need and advantages of PLC, PLC configuration,

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

Fault Diagnosis and Maintenance for CNC Machine. Based on PLC

Fault Diagnosis and Maintenance for CNC Machine. Based on PLC Fault Diagnosis and Maintenance for CNC Machine Based on PLC Deng Sanpeng [1, 2] Xu Xiaoli [2, 3] Chen Tao [2] 1.Tianjin University of Technology and Education,300222; 2. Beijing Institute of Technology,100081;

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

Controller Automation, Model II+

Controller Automation, Model II+ Controller Automation Page 2 of 2 Automation with the RADAK II+ power controller II+ I/O Points: Inputs 5 Programmable Digital inputs 2 Dedicated digital inputs (Channel select and External SCR control

More information

8500 Installation/Start-up/Operation Lit # 8500 OP

8500 Installation/Start-up/Operation Lit # 8500 OP 8500 Installation/Start-up/Operation Lit # 8500 OP K SYSTEM CORPORATION INVENTORY SYSTEM GENERAL DESCRIPTION The K SYSTEM TANK INVENTORY CONTROL SYSTEM, #8600C Series, provides an extremely accurate method

More information

Smoke Density Monitor application documentation

Smoke Density Monitor application documentation Smoke Density Monitor application documentation Navigating the User interface Fig. 1 Screen shot of the application layout. Description Graphical Monitor Data Browser Trending Graph Alarm View Create Report

More information

SD Memory Card Recorder Instructions. ver 110516.01

SD Memory Card Recorder Instructions. ver 110516.01 SD Memory Card Recorder Instructions ver 110516.01 Contents 1. SD CARD RECORDER MAIN UNIT 3 2. REMOTE CONTROL FOR SD CARD RECORDER 4 3. TURNING ON THE RECORDER: 5 4. HOW TO RECORD: 6 5. HOW TO TAKE A PICTURE:

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

Elite Monitoring System Installation and Operation

Elite Monitoring System Installation and Operation Elite Monitoring System Installation and Operation 750-353 Elite Monitoring System 750-353 2 750-353 Elite Monitoring System Contents Product Overview and Definitions........................................4

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

ER-1 Emergency Response System INSTALLATION & PROGRAMMING GUIDE

ER-1 Emergency Response System INSTALLATION & PROGRAMMING GUIDE Emergency Response System INSTALLATION & PROGRAMMING GUIDE Copyright micron 2005 Contents Product Description 3 Console Operation Overview 4 Console Wiring Diagram 5 User Manual 6 Transmitter Assembly

More information

Infinity 2020 Perimeter Intrusion Detection System

Infinity 2020 Perimeter Intrusion Detection System Infinity 2020 Perimeter Intrusion Detection System User Guide: Network Application Your First Line of Defense 1 Infinity 2020 Perimeter Intrusion Detection System Table of Contents Section 1: Getting Started...

More information

Teacher References archived classes and resources

Teacher References archived classes and resources Archived Classes At the end of each school year, the past year s academic classes are archived, meaning they re still kept in finalsite, but are put in an inactive state and are not accessible by students.

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

Cam switches. Page. Overview 4-2. ON-OFF switches, main switches, maintenance switches 4-3. Changeover switches, reversing switches 4-5

Cam switches. Page. Overview 4-2. ON-OFF switches, main switches, maintenance switches 4-3. Changeover switches, reversing switches 4-5 Eaton Wiring Manual / Page Overview - ON-OFF switches, main switches, maintenance switches - Changeover switches, reversing switches - (Reversing) star-delta switches - Multi-Speed Switches - Interlock

More information

11. FLOWCHART BASED DESIGN

11. FLOWCHART BASED DESIGN plc flowchart - 11.1 Topics: Describing process control using flowcharts Conversion of flowcharts to ladder logic Objectives: Ba able to describe a process with a flowchart. Be able to convert a flowchart

More information

14 Failover and Instant Failover

14 Failover and Instant Failover 14 Failover and Instant Failover 14.1 Failover Introduction ACP uses specific terms to cover different topics that are concerned with keeping data viable during computer failure. Replacement: If a terminal

More information

Cooking at the Speed of light!

Cooking at the Speed of light! Cooking at the Infrared Cooking & Colouring Infrabaker is a modular infrared continuous cooking system developed by Infrabaker International. The machine is designed to cook and/or put colour on a wide

More information

PROGRAMMABLE LOGIC CONTROLLERS Unit code: A/601/1625 QCF level: 4 Credit value: 15

PROGRAMMABLE LOGIC CONTROLLERS Unit code: A/601/1625 QCF level: 4 Credit value: 15 UNIT 22: PROGRAMMABLE LOGIC CONTROLLERS Unit code: A/601/1625 QCF level: 4 Credit value: 15 ASSIGNMENT 3 DESIGN AND OPERATIONAL CHARACTERISTICS NAME: I agree to the assessment as contained in this assignment.

More information

REGTRONIC OPERATING INSTRUCTIONS

REGTRONIC OPERATING INSTRUCTIONS REGTRONIC OPERATING INSTRUCTIONS 1.FEATURES Electrical connection: M12 8-pin connector Preset pressure range 0.05-10 bar with possible full scale regulation. 10 100 mbar adjustable deadband Supply pressure:

More information

CHAPTER 1 - EXECUTIVE SUMMARY

CHAPTER 1 - EXECUTIVE SUMMARY Chapter Page CHAPTER 1 - EXECUTIVE SUMMARY 1.1 Background 1-1 1.2 Purpose/ Objectives 1-1 1.3 Flow, Condition and Operation Assessment 1-3 1.4 Class A Biosolids 1-4 1.5 Summary of Recommendations 1-4 CHAPTER

More information

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel ABC DEF GHI JKL MNO PQR STU YZ WXY FA-300 Series LCD Fire Alarm Control Panel Advanced Life Safety Solutions System Normal 10:36AM WED 2003-10-01 SYSTEM RESET A.C. ON ALARM SUPV TRBL CPU FAIL SIGNAL SILENCE

More information

Ann Arbor Wastewater Treatment Plant Facilities Renovations Project September 2015

Ann Arbor Wastewater Treatment Plant Facilities Renovations Project September 2015 Ann Arbor Wastewater Treatment Plant Facilities Renovations Project September 2015 The Facilities Master Plan was completed in 2004 and identified the need for improvements to the City of Ann Arbor s Wastewater

More information

SiCam Systems Guide. Alarms. Description: Guide for setting up alarms, including linking them to PLCs. (1017 REV 1)

SiCam Systems Guide. Alarms. Description: Guide for setting up alarms, including linking them to PLCs. (1017 REV 1) SiCam Systems Guide Alarms (1017 REV 1) Description: Guide for setting up alarms, including linking them to PLCs. Sicam Systems Guide - Alarms 1017 2 Revision History # Date By Comments 001 June 16, 2011

More information

Introduction to LogixPro - Lab

Introduction to LogixPro - Lab Programmable Logic and Automation Controllers Industrial Control Systems I Introduction to LogixPro - Lab Purpose This is a self-paced lab that will introduce the student to the LogixPro PLC Simulator

More information

Corsair Link v2.4 Manual. Initial Set-up. Placing devices within the chassis

Corsair Link v2.4 Manual. Initial Set-up. Placing devices within the chassis Corsair Link v2.4 Manual Initial Set-up Placing devices within the chassis When you first start up Corsair Link, there will be a list of auto-detected devices on the left column. You can drag and drop

More information

FUNDAMENTALS OF CONTROL ENGINEERING

FUNDAMENTALS OF CONTROL ENGINEERING EQUIPMENT FOR ENGINEERING EDUCATION EQUIPMENT FOR ENGINEERING EDUCATION ENGINEERING MECHANICS & MACHINE ELEMENTS Statics Strength of Materials Dynamics Fundamentals of Engineering Design Machinery Diagnosis

More information