Optimal neutral ground resistor rating of the medium voltage systems in power generating stations

Size: px
Start display at page:

Download "Optimal neutral ground resistor rating of the medium voltage systems in power generating stations"

Transcription

1 Journal of International Council on Electrical Engineering ISSN: (Print) (Online) Journal homepage: Optimal neutral ground resistor rating of the medium voltage systems in power generating stations Choong-Koo Chang To cite this article: Choong-Koo Chang (2015) Optimal neutral ground resistor rating of the medium voltage systems in power generating stations, Journal of International Council on Electrical Engineering, 5:1, 55-63, DOI: / To link to this article: The Author(s). Published by Taylor & Francis Published online: 20 Nov Submit your article to this journal Article views: 1543 View related articles View Crossmark data Full Terms & Conditions of access and use can be found at Download by: [ ] Date: 02 February 2017, At: 21:12

2 Journal of International Council on Electrical Engineering, 2015 Vol. 5, No. 1, 55 63, Optimal neutral ground resistor rating of the medium voltage systems in power generating stations Choong-Koo Chang* Professor, Department of Nuclear Power Plant Engineering, KEPCO International Nuclear Graduate School (Received 25 August 2015; accepted 19 October 2015) Neutral grounding resistors (NGRs) are used to protect insulation breakdown in faulty electrical equipment. These faults are caused by transient over-voltages produced by arcing ground on ungrounded systems. NGR also reduces mechanical stresses in circuits and apparatus carrying fault currents in solidly grounded systems. In the medium voltage auxiliary power systems of power generating stations, low resistance grounding system is widely used with a NGR. The purpose of this paper is to present the method determining optimal NGR size for the medium voltage systems in power generating stations. Keywords: system grounding; impedance grounding; neutral grounding resistor; phase to ground fault 1. Introduction To determine optimal neutral grounding resistor (NGR) size, many items should be considered. The maximum ground fault current allowed by the resistor has to be large enough to actuate the applied ground fault protection relay. The allowable fault current must be decided in accordance with the protection scheme and nominal current of equipment (generator or transformer). However, the most of literatures related to resistance grounding system design describe only the approximate range of the NGR rating for low and high resistance grounding system. And the only existing standard specific for NGR is the IEEE 32 standards where the allowed temperature rise and time rating are defined. Sophisticated NGR sizing and verification method is not introduced in any literature. Therefore, design, construction and operation engineers in the job field experience difficulties due to the mismatch of NGR rating and ground protection system during commissioning and operation. Throughout this study a procedure for the determination of optimal NGR will be proposed, and it will be verified through a case study. 2. System grounding Power system grounding is very important, particularly because the majority of faults involve grounding. Thus, it has a significant effect on the protection of all the components of the power system. The principal purpose of grounding is to minimize potential transient overvoltages to comply with local, state, and national codes for personnel safety requirements; and to assist in the rapid detection and isolation of trouble or fault areas. In general, system grounding is practiced based on past experience or an extension to the grounding methods in existing installations. There are three types in system grounding: (1) ungrounded, (2) resistance or impedance, and (3) effective or solid grounding. Each has its application in practice, along with advantages and disadvantages. The recommendations are based on general practices and some personal preferences. [1] 2.1. Ungrounded systems An ungrounded system is one in which there is no intentional connection between the conductors and the ground. However, in any system, a capacitive coupling exists between the system conductors and the adjacent grounded surfaces. Consequently, the ungrounded system is, in reality, a capacitively grounded system by virtue of the distributed capacitance. This is shown in Figure 1.[2,3] The voltages and impedances indicated in Figure 2 are as follows: V PN : the applied phase to neutral system voltage (infinite source) Z 1(sys), Z 2(sys), Z 0(sys) : the equivalent positive, negative, and zero sequence source impedance values, respectively Z TX : the transformer impedance (since the return path for the transformer has negligible impedance, the positive, negative, and zero sequence impedance values, for the transformer are all the same) Z 1(line),Z 2(line),Z 0(line) : the impedance values for the line between the transformer secondary terminals and the PG (phase to ground) fault. * ckchang@kings.ac.kr 2015 The Author(s). Published by Taylor & Francis. This is an Open Access article distributed under the terms of the Creative Commons Attribution License ( which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

3 56 C.-K. Chang Figure 1. Ungrounded system Solidly grounded systems There is no intentional impedance between the system neutral and ground as shown in Figure 3. The voltage and impedance values indicated in Figure 4 are the same as those defined originally for Figure 2. In terms of the applied voltage and the system impedance values given, the bolted PG fault current magnitude would be determined as follows: I PG ¼ ½2Z 1ðsys 3V PN Þ þ 3Z TX þ 2Z 1ðlineÞ þ Z 0 line ð ÞŠ (3) 2.3. Resistance grounding There are two broad categories of resistance grounding: low resistance and high resistance. In both types of grounding, the resistor is connected between the neutral of the transformer secondary as shown in Figure 5 or the generator winding and the earth ground. The voltage and impedance values indicated in the resistance grounding system are the same as those defined originally for ungrounded system except neutral ground impedance R N inserted between transformer neutral and ground. In terms of the applied voltage and the system impedance values given, the bolted PG fault current magnitude would be determined as follows: Figure 2. Sequence network model for phase to ground fault on an ungrounded system. The equal positive and negative sequence components of the total distributed shunt capacitive reactance (X C1 and X C2 ), shown in Figure 2, are so large compared to the system impedances parallel to them that they can be neglected.[2] In terms of the applied voltage and the system impedance values given, the bolted PG fault current magnitude would be determined as follows: I PG ¼ ½2Z 1ðsys 3V PN Þ þ 3Z TX þ 3Z N þ 2Z 1ðlineÞ þ Z 0 line ð ÞŠ (4) In general, other impedances than the neutral impedance are negligible. Since the neutral impedance is in a residual portion of the zero sequence current circulation path, its impedance value is modelled as three times its actual value and X C0 is negligible in low resistance grounding system. For this reason, the PG fault current magnitude is determined by the neutral impedance value used: I PG ¼ 3V PN 3Z N ¼ V PN Z N ffi V PN R N (5) 3V PN I PG ¼ (1) ½2Z 1ðsysÞ þ 2Z TX þ 2Z 1ðlineÞ þ Z 0ðlineÞ þ X C0 Š Because X C0 dwarfs the other system impedance values, the simplified Equation 1 gives a close approximation: I PG ¼ 3V PN (2) X C0 As a result, the PG fault current on an ungrounded system has a very small magnitude, very small for overcurrent relaying to be used for detecting ground faults. Figure 3. Delta/grounded-wye transformer connection.

4 Journal of International Council on Electrical Engineering 57 To reduce the arc blaster flash hazard to personnel who may have accidentally caused or who happen to be in close proximity to the ground fault. High resistance grounding typically uses ground fault current levels of 10 A or less, although some specialized systems in the 15 kv voltage class may have higher ground fault current levels. On the other hand, low resistance grounding typically uses ground fault current levels of at least 100 A, with currents in the A range being more usual.[4,5] 3. System grounding practice in a nuclear power generating stations The following is a brief description of the system grounding practice in nuclear power generating stations and Figure 6 shows the conceptual diagram of the system grounding. Figure 4. Sequence network model for a bolted PG fault on the solidly grounded system Main generator and transformer The main generator should always be high resistance grounded and the main transformer for the generating plant should always be solidly grounded at the high side. Low side connected to the generator is always delta connected. No special equipment is required for high side grounding.[6] 3.2. Unit auxiliary transformers Unit auxiliary transformers (UAT) connected to the generator leads should always have the high side delta connected. Low side of the UAT is generally wye connection and should be low resistance grounded allowing a maximum of 2000 A ground fault current. Grounding resistor directly connected to the neutral should have a minimum of 10 sec rating. Figure 5. Resistance grounded system. The reasons for limiting the current by resistance grounding may be one or more of the following: To reduce the burning and melting effects in faulted electric equipment, such as switchgear, transformers, cables, and rotating machines. To reduce mechanical stresses in circuits and apparatus carrying fault currents. To reduce electric-shock hazards to personnel caused by stray ground-fault currents in the ground return path Standby auxiliary transformers Standby auxiliary transformers (SAT), when used, may have wye connection for high and low side winding with delta connection tertiary winding. For high side, wye connection, neutral should be solidly grounded. For low side wye connection, neutral should be low resistance grounded allowing a maximum of 2000 A ground fault current to flow. Rating of this equipment should have a minimum of 10 sec rating Load centre transformers Transformer feeding low voltage load centre should be delta/wye connection with neutral solidly grounded, unless specifically required by the client to be different.

5 58 C.-K. Chang Figure 6. System grounding of a nuclear power generating station Diesel generators Diesel generators, when provided, should be low resistance grounded at the medium voltage and solidly grounded at low voltage distribution. Low resistance grounding should allow a maximum of 1000 A ground fault current. Grounding resistor directly connected to the neutral should have a minimum of 10 sec rating. 4. Determination of NGR rating for medium voltage network For the purpose of this study, a design and verification process of Figure 7 has been developed. Every factor affecting the rating of NGR are reviewed and cross checked in the process to confirm the suitability of NGR rating. In the last, the NGR ratting is verified through the ground fault protection relay coordination check. The line-to-ground capacitance associated with system components determines the magnitudes of zero sequence charging current. The resistor must be sized to ensure that the ground fault current limit is greater than the system s total capacitance-to-ground charging current. If not, then transient overvoltages can occur.[3] Furthermore, NGR selection is a comprehensive task which involves many aspects of power system as shown in Figure 7. The following items are mainly considered when selecting NGRs:[7,8] Charging current Allowable maximum fault current for network Transient overvoltage and insulation level of equipment Fault current withstand time and temperature rise Ground fault protection and coordination Charging current and fault current level The charging current of a system can be calculated by summing the zero-sequence capacitance or determining capacitive reactance of all the cable and equipment connected to the system. The system charging current in normal operation condition is as follows, where C 0 is the zero-sequence capacitance in μf (microfarad) per phase and kv is the line-to-line voltage (see Figure 8): Capacitive reactance, X CO ¼ 106 xc o Ohm per phase, where x ¼ 2 p f (6) Charging current in Amps at 60 Hz: 3I CO ¼ x C 0 kv p 3 ¼ 0:652 C 0 kv (7) 1000 Typical values of system-capacitance data are available from the cable manufacturer catalogue or Westinghouse design guide [9] and the GE Data Book.[10] On the other hand, it is preferable to measure the magnitude of the charging current on existing power

6 Journal of International Council on Electrical Engineering 59 Figure 8. systems. Ground fault current path in resistance grounding systems. High resistance grounding systems are designed to meet the criterion of Rg Xco/3 or R O X CO to limit the transient overvoltages due to arcing ground faults. Where, Rg is the grounding resistance as seen from the system being grounded and R 0 is the per-phase zero-sequence resistance of the system. Xco is the capacitive reactance-to-ground per phase and includes the capacitance of all cables, motor windings, transformer windings, surge or shunt capacitors, and other equipment connected to the system.[5,11] Total fault current is the vector sum of capacitive charging current and resistor current: I f ¼ p fi 2 R þ ð 3I C0Þ 2 g (8) Figure 7. Flow diagram of NGR determination and ground fault relay setting. systems for correct grounding equipment selection. The measured values must be adjusted to obtain the maximum current if all the system components were not in operation during the tests.[3] For safe measuring of neutral point capacitor current, measurement from the secondary side of grid is proposed. Also different frequency injection method is widely used for the measurement of capacitive current.[8] In a resistance grounded system, the resistance must be low enough to allow the system capacitance to discharge relatively quickly. The level of fault current is commonly thought to be 10 A or less in ungrounded So, if I R =3I C0, then I F = I R Total fault current must not exceed the value for which the system is braced. However, in many cases, the system is already braced for the three-phase fault current which is much higher than the single line-ground fault current of a resistance grounded system.[12] In low resistance grounding, ground fault detecting current relays are sometimes connected in the common or residual circuit of current transformers. Where selective tripping is to be accomplished, the fault current is typically limited to a value equal to the primary current rating of the largest current transformers. This practice usually results in the maximum ground fault current being approximately equal to the full load rated current of the power supply transformer. Justification for this is based on the 5 A secondary rating of the current transformers. With an overcurrent relay having a minimum available setting of 0.5 A, the grounding resistance selected would permit 10 times the relay pickup current during a zero impedance fault. This will assure reliable relay performance.[11] Typical current values used range from 400 A on modern systems using sensitive toroid or core balance current transformer ground sensor relaying

7 60 C.-K. Chang and up to perhaps 2000 A in the larger systems using residually connected ground overcurrent relays.[4] 4.2. Transient overvoltage and insulation level An ungrounded system with no intentional conductive path to ground has a path for alternating currents to flow between the phase conductors and ground through the distributed capacitance to ground of circuits and equipment windings and any surge capacitors or power factor correction capacitors connected to ground. This capacitance is a significant factor in the generation of transient overvoltage during an arcing ground fault. Restriking arcs after current interruption in the breaker or in the fault can result in large destructive overvoltages in ungrounded systems. This phenomenon is illustrated in Figure 9. In the capacitive system, the current leads the voltage by nearly 90. When the current is interrupted or the arc is extinguished at or near its zero value, the voltage will be at or near its maximum value. With the breaker open, this voltage remains on the capacitor to decay at a time constant of the capacitive system. In the source system, it continues as demonstrated by V S. Thus, in a half cycle, the voltage across the open contact is almost twice the normal peak value. If a restrike occurs (switch closed in Figure 9), the basic +1 pu voltage of the capacitive system will shift to the system voltage of 1 pu, but because of the system inductance and inertia, it will overshoot to a maximum possibility of 3 pu. If the arc goes out again near current zero (switch open) but restrikes (switch closed) again, the system voltage will try to shift to +1 pu, in succession another time overshoot, this time to a potential maximum of +5 pu. This could continue to 7 pu, meanwhile, the system insulation would no doubt break down, causing a major fault. Thus, ungrounded systems should be used with caution, and applied at the lower voltages, where the system insulation levels are higher.[1] For resistance grounding systems at 15 kv and below, such overvoltages will not ordinarily be of a serious nature if the resistance value lies within the following boundary limits: R 0 X C0, R 0 2X 0. Where, X 0 is zero-sequence reactance. The corresponding ground-fault current is far less than is normally used for low-resistance grounding, but is the design criterion for high-resistance grounding.[5] 4.3. Fault withstand time and temperature rise Normally, protective relaying will trip within a few cycles. IEEE 32 defines standard resistor on times. Lowest rate is 10 seconds, but could potentially go less in order to save material/space. It can go as high as 30 or 60 seconds as required (rare). Extended or continuous ratings are almost never used in this application due to the relatively high fault currents. Coefficient of resistivity typically increases with temperature of the material, thus resistance of the NGR increases while the unit runs. As resistance increases, current decreases.[12] Therefore, the time rating and resistivity coefficient of resistor should be confirmed when make a ground fault relay setting calculation. Figure 9. Transient overvoltage on an ungrounded system. Figure 10. Ground fault protection scheme of the class 1E MV switchgear fed from unit aux. transformer.

8 Journal of International Council on Electrical Engineering (a) Lack of coordination (b) Better coordination Figure 11. Ground fault protection coordination curve for MV switchgear. 61

9 62 C.-K. Chang 4.4. Ground fault relay coordination CTs and relays must be designed such that system will trip on a fault of the magnitude of the ground fault current, but not on transient events such as large motor startup. Figure 10 is an example of the ground fault protection scheme for the Class 1E 4.16kV Switchgear fed from Unit Auxiliary Transformer (UAT) in a nuclear power plant. Secondary side neutral of the UAT is grounded with the NGR. In this example system, NGR rating is Ω and maximum fault current is 1200 A. The maximum fault current was decided to a value equal to the rated current of X winding at ONAN rating. X and Y windings use the same size of resistance for the convenience of design and maintenance. Figure 11 is the time current characteristic curves of ground protection relays showing the coordination between upstream and downstream relays. The time overcurrent relay (51G) installed on the grounded neutral of a transformer is set to minimum values of current pickup but not less than 10% of NGR rating and time delay to be selective with downstream feeder ground fault relays. Accordingly, about 160 A is appropriate to set 51G relay to make coordination with the 4.16 kv SWGR branch feeder ground fault relays which are set at 20 A and 120 A as explained in below. The ground protection relays installed on the incoming feeder of switchgears are residual type (51N). In Figure 11(a), the 51N relay of the Class 1E 4.16kV SWGR was set at 120 A for the coordination with the transformer neutral ground protection relay 51G. In that case, 51N(R2) relay s setting value is only 4% of the CT rating (3000 A) and it may cause undesired tripping of the ground relay due to CT error. Relay must not be set to pick up at less than CT accuracy class. In general, accuracy of the IEEE type protection CT is 10%. Coordination between 51G(R1) of the UAT neutral and 51N(R2) of the 4.16 kv SWGR incoming feeder can be sacrificed. However, coordination between 51N (R2) and downstream relays (R3 and R4) should be maintained as shown in Figure 11(b). Motor feeders are protected with instantaneous ground overcurrent relay (50G) connected to a core balance CT. 50G(R4) for motor feeder is set at lowest tap and typical pick-up value is A. In the case of an outgoing feeder for subsidiary 4.16 kv Non Class 1E SWGR, 51N (R3) device is used and it must coordinate with upstream and downstream ground overcurrent relay. The 51N(R3) is set at 120 A. 120 A is 10% of the CT primary rating of 1200 A. As a result, the 51N(R3) relay properly coordinates with the upstream relays. Therefore, Figure 11(b) is better protection coordination than Figure 11(a). current and ground fault level, transient overvoltage and insulation level, fault withstand time and temperature rise, and ground fault relay coordination. In the high resistance grounding system, NGR must be sized to flow resistive ground fault current that is greater than capacitive charging current and the system is not subject to destructive transient overvoltage. On the other hand, in the low resistance grounding system, ground fault current level and selectivity of ground fault relays are more critical to determine NGR rating than other parameters. In the case study, system ground fault relay (51G) was set at 13.3% (160 A) of the NGR rating and selective tripping was possible through the coordination with branch feeder s relay of the 4.16 kv SWGR. Therefore, the NGR rating satisfies the requirements specified in Sections The transformer neutral CT is 1200/ 400 multi-ratio type and 400 A CT is preferred for reference system for more reliable protection. If the NGR rating is greater than 1200 A, it is inevitable to allow higher ground fault current in the circuit. However, if the NGR rating is smaller than 1200 A, coordination between downstream 51N relays are difficult or fault detection in high impedance ground fault is insensitive. 6. Conclusion Usually the importance of NGR rating is overlooked because NGR is ordered in the early stage of the project with the power transformer which is long lead time equipment. As a result, in many cases, the rating of NGR already installed is not suitable for the proper setting and coordination of ground fault protection relays. Consequently it results in unsatisfactory coordination of ground fault protection system. Optimal NGR rating determination procedure and verification method proposed in this paper will contribute to the design of the reliable and safe ground protection systems for power generating stations. Additionally, as the power system design progresses and data becomes available, the grounding system and NGR design should be reviewed and re-evaluated when necessary to ensure that the system will perform within the established criteria and design margins. This re-evaluation may be required when transformer with NGR proposal is evaluated to check whether the rating proposed by the manufacturer is acceptable. A final re-evaluation is necessary after NGR test data and ground protection relay information are available. Acknowledgements This research was supported by the 2015 Research Fund of the KEPCO International Nuclear Graduate School (KINGS). 5. Results and discussion NGR rating in a resistance grounding system must be decided considering the above mentioned charging ORCID Choong-Koo Chang

10 Journal of International Council on Electrical Engineering 63 References [1] Blackburn J. Lewis, Domin Thomas J. Protective relaying principles and applications. CRC Press Taylor & Francis Group, NW, 2007, p.221. [2] Johnson Gerald, Schroeder Mark, Dalke Gerald. A review of system grounding methods. Proceedings of the Protective Relay Engineers 61st Annual Conference; [3] Post Glover TM, Ground fault protection technical guide, converting ungrounded systems to high resistance grounding. 2013;2 6. [4] IEEE Std IEEE recommended practice for electric power distribution for industrial plants, pp [5] IEEE Std IEEE recommended practice for grounding of industrial and commercial power systems, pp [6] IEEE Std C IEEE guide for generator ground protection, pp [7] Izadfar Hamid R, Farsad MR, Davood Andavari, Shokri S. Design and calculation of 66 kv neutral grounding resistor for main transformers in Bandar Imam Petrochemical Complex (BIPC) power station located in south west of Iran. Electrical Machines and Systems, ICEMS Proceedings of the Eighth International Conference, 2005, September 27 29, pp [8] Siming Hua, Hua Zhang, Feng Qian, Chunjie Chen, Meixia Zhang. The research on neutral grounding scheme of Fengxian 35 kv and 10 kv power grid, Energy and Power Engineering. 2013;5:898. [9] Westinghouse. System neutral grounding and ground fault protection. Publication PRSC-4B-1979, Westinghouse, 1979, pp [10] General Electric Co. GE industrial power systems data book. Schenectady, NY: General Electric; [11] IEEE Std IEEE design guide for electric power service systems for generating stations, pp [12] GloverTM Post. Grounding for electrical power systems (low resistance and high resistance design). IEEE Baton Rouge May;8:11 16.

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan claudio.mardegan@engepower.com www.engepower.com Phone: 55 3579-8777

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Earth Fault Detection Basics in Theory

Earth Fault Detection Basics in Theory Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering

More information

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

Grounding of AC generators and switching the neutral in emergency and standby power systems

Grounding of AC generators and switching the neutral in emergency and standby power systems Power topic #6006 Part 2 of 2 Technical information from Cummins Power eneration rounding of AC generators and switching the neutral in emergency and standby power systems > White paper By Lawrence A.

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

ASK THE EXPERTS. Resistance Grounding Q&A. with industry experts

ASK THE EXPERTS. Resistance Grounding Q&A. with industry experts ASK THE EXPERTS Resistance Grounding Q&A with industry experts system grounding system grounding system grounding system grounding system grounding System Grounding Definition and Different Types What

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

4.5 Transformer Connections

4.5 Transformer Connections ELECTRIC POWER SYSTEMS IN COMMERCIAL BUILDINGS IEEE Std 241-1990 5) Flat Billing Ñ Certain applications involve service to the load of a Þxed characteristic. For such loads, the supplying utility may offer

More information

Paralleling Power Sources Which Share a Common Neutral

Paralleling Power Sources Which Share a Common Neutral Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Application of Four-Pole Circuit Breakers within Data Centers

Application of Four-Pole Circuit Breakers within Data Centers Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

FIT TIER 2 Application

FIT TIER 2 Application FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:

More information

Residual Current Circuit Breaker

Residual Current Circuit Breaker Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

Shunt Capacitor Bank Fundamentals and Protection

Shunt Capacitor Bank Fundamentals and Protection 2003 Conference for Protective Relay Engineers - Texas A&M University April 8-10, 2003, College Station (TX) Shunt Capacitor Bank Fundamentals and Protection Gustavo Brunello, M.Eng, P.Eng Dr. Bogdan Kasztenny

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

CT Application Guide for the 489 Generator Management Relay

CT Application Guide for the 489 Generator Management Relay g GE Power Management Technical Notes CT Application Guide for the 489 Generator Management Relay GE Publication No. GET-8402 Copyright 2002 GE Power Management Introduction A protection scheme operates

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear. OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

Grounding and Electrical Safety of Shore Power Supply and DC Stinger System Design

Grounding and Electrical Safety of Shore Power Supply and DC Stinger System Design Grounding and Electrical Safety of Shore Power Supply and DC Stinger System Design Dev Paul AECOM 2101 Webster Street, Suite 1900, Oakland, Ca 94612 dev.paul@aecom.com; (510) 419 6448 Abstract: To enhance

More information

Transformers. Special transformers Reactors products

Transformers. Special transformers Reactors products Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having

More information

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr. Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley

More information

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection

More information

Electrical Predictive and Preventative Maintenance

Electrical Predictive and Preventative Maintenance Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

Power Quality Paper #3

Power Quality Paper #3 The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production

More information

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6 Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of

More information

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems by Reza Tajali, P.E. Square D Company, Power Systems Engineering Group 295 Tech Park Drive LaVergne, Tennessee 37086

More information

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008 CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand

More information

Fault Characteristics in Electrical Equipment

Fault Characteristics in Electrical Equipment 1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid

More information

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it

More information

A Practical Guide to Dielectric Testing

A Practical Guide to Dielectric Testing Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions

More information

Loading Considerations When Paralleling Transformers

Loading Considerations When Paralleling Transformers Application Guide 7400DB0701 02/2007 Nashville, TN, USA Loading Considerations When Paralleling Transformers Class 7400 Retain for future use. Introduction Principles of Paralleling This application guide

More information

Ground Fault Protection on Ungrounded and High Resistance Grounded Systems

Ground Fault Protection on Ungrounded and High Resistance Grounded Systems > the power to protect Ground Fault Protection on Ungrounded and High Resistance Grounded Systems Application Guide www.i-gard.com table of contents SUBJECT PAGE 1. Introduction...1 2. Ungrounded Systems...1

More information

Radial Distribution Test Feeders

Radial Distribution Test Feeders Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

New standardized approach to arc flash protection

New standardized approach to arc flash protection New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200

More information

TABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4

TABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4 Page: 1 of 14 KEY BULLETIN POINTS: THIS GUIDE OUTLINES MINIMUM REQUIREMENTS FOR CONNECTION OF CUSTOMER-OWNED EMERGENCY AND STANDBY (ESG) TO THE GEORGIA POWER COMPANY (GPC) DISTRIBUTION SYSTEM. THESE ARE

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

Electrical Safety Tester Verification

Electrical Safety Tester Verification Ensuring Validity of Regulatory Tests Verification of electrical safety testing equipment is a procedure that is often overlooked by manufacturers. Running test verification is crucial to ensuring that

More information

However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.

However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence. Application note for Inrush Current Limiters (ICL) Turning on electrical devices generally cause high inrush currents which can damage electronic components and cause interruption of the line voltage if

More information

The electrical energy produced at the gen

The electrical energy produced at the gen 300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012 INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably

More information

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS Bachelor's Thesis Electrical Engineering June 2014 SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS MD FARUQUL ALAM SALMAN SAIF HAMID ALI School of Engineering Blekinge Tekniska

More information

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Guidelines on the Short Circuit Current Rating for Industrial Control Panels usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A

More information

Electrical Shore Connections / Cold Ironing

Electrical Shore Connections / Cold Ironing STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version

More information

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters

More information

Impact of Distributed Resources on Distribution Relay Protection

Impact of Distributed Resources on Distribution Relay Protection Impact of Distributed Resources on Distribution Relay Protection A report to the Line Protection Subcommittee of the Power System Relay Committee of The IEEE Power Engineering Society prepared by working

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Transfer Equipment Controls

Transfer Equipment Controls Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment

More information

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011 AM 5-202 BASIC ELECTRONICS AC CIRCUIT ANALYSIS December 2011 DISTRIBUTION RESTRICTION: Approved for Pubic Release. Distribution is unlimited. DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT

More information

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how

More information

Errors Due to Shared Leadwires in Parallel Strain Gage Circuits

Errors Due to Shared Leadwires in Parallel Strain Gage Circuits Micro-Measurements Strain Gages and Instruments Errors Due to Shared Leadwires in Parallel Strain Gage Circuits TN-516 1. Introduction The usual, and preferred, practice with multiple quarterbridge strain

More information

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents

More information

Corner-Grounded Delta (Grounded B Phase) Systems

Corner-Grounded Delta (Grounded B Phase) Systems Data Bulletin 2700DB0202R03/12 09/2012 Replaces 2700DB0202R2/09 dated 02/2009 Corner-Grounded Delta (Grounded B Phase) Systems Class 2700 Retain for future use. Introduction Corner-grounded delta systems

More information

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward

More information

WINDING RESISTANCE TESTING

WINDING RESISTANCE TESTING WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991

More information

ACCURACY OF POTENTIALTRANSFORMERS

ACCURACY OF POTENTIALTRANSFORMERS 8 VOLTAGE TRANSFORMERS Two types of voltage transformer are used for protective-relaying purposes, as follows: (1) the "instrument potential transformer," hereafter to be called simply "potential transformer,"

More information

Switchgear Application Issues for Mission Critical Power Systems, Part One

Switchgear Application Issues for Mission Critical Power Systems, Part One Switchgear pplication Issues for Mission Critical Power Systems, Part One BSTRCT With the advent of high reliability data centers and telecommunication facilities, designers of commercial power face new

More information

Pilot-wire differential relay for lines with two or more terminals

Pilot-wire differential relay for lines with two or more terminals Pilot-wire differential relay for lines with two or more terminals Page 1 Issued: March 2003 Revision: A Data subject to change without notice Pilot-wire differential relay with RXHL 401 Features Phase

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc. Short-circuit, Protective Device Coordination & Arc Flash Analysis By Albert Marroquin Operation Technology, Inc. Agenda Short-circuit Calculations for Arc Flash Analysis Protection and Coordination Principles

More information

Power System Analysis

Power System Analysis PDHonline Course E194 (15 PDH) Power System Analysis Instructor: Timothy L. O'Hearn, PE 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question

More information

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE INTRODUCTION In all kinds of manufacturing, it is very common to have equipment that has three phase motors for doing different

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY 2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium

More information

Engineering Series Ratings: Is It Practical?

Engineering Series Ratings: Is It Practical? Engineering Series Ratings: Is It Practical? By the National Electrical Manufacturers Association The 2005 National Electrical Code (NEC) introduces a change regarding series ratings for circuit breakers

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

MIT510/2, MIT520/2 and MIT1020/2

MIT510/2, MIT520/2 and MIT1020/2 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com MIT510/2, MIT520/2 and MIT1020/2 Line supply or battery operated Digital/analog

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

GE Multilin technical note

GE Multilin technical note Digital Energy Multilin GE Multilin technical note eutral voltage unbalance function at grounded wye capacitor banks GE publication number: GET-8544 Copyright 00 GE Multilin eutral voltage unbalance function

More information

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...

More information

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits.

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits. IAV Time Delay Voltage For A and D circuit applications. Features and Benefits Frequency compensation (optional) Target seal-in unit (most units) Instantaneous units (optional) Applications A Generators

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.

More information

PowerFlex Dynamic Braking Resistor Calculator

PowerFlex Dynamic Braking Resistor Calculator Application Technique PowerFlex Dynamic Braking Resistor Calculator Catalog Numbers 20A, 20B, 20F, 20G, 22A, 22B Important User Information Solid-state equipment has operational characteristics differing

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES

DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES Edward P. Rafter, P. E. Principal Tier IV Consulting Group Lee s Summit, Missouri 64064 INTRODUCTION There are concerns among owners

More information

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...

More information