viii TAC I/NET Seven Installation Guide Process Control Unit for TAC I/NET Building Automation Systems TCON /10

Size: px
Start display at page:

Download "viii TAC I/NET Seven Installation Guide Process Control Unit for TAC I/NET Building Automation Systems TCON106. 09/10"

Transcription

1 viii TAC I/NET Seven Installation Guide Process Control Unit 7718 for TAC I/NET Building Automation Systems TCON /10

2 We at Schneider Electric have tried to make the information contained in this manual as accurate and reliable as possible. Nevertheless, Schneider Electric disclaims any warranty of any kind, whether express or implied, as to any matter whatsoever relating to this manual, including without limitation the merchantability or fitness for any particular purpose. Information in this document is based on specifications determined at the time of publication. As we introduce design enhancements, we reserve the right to make changes in specifications and models without obligation to notify the purchaser. In no event shall Schneider Electric be liable for any indirect, special, incidental, or consequential damages arising out of purchase or use of this manual or the information contained herein. The software described in this document is furnished under a license agreement or nondisclosure agreement. The software may be used or copied only in accordance with the terms of the agreement. It is against the law to copy Schneider Electric s TAC I/NET System software onto magnetic tape, disk, or any other medium for any purpose other than the purchaser's personal use. Printed in the United States of America. Document Number: Copyright 2010 Schneider Electric. All rights reserved. On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric; however, there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes.

3 Contents FCC Warning vii Overview Baseboard Input/Output Communication Reset Expansion Board Input/Output Options Physical Description Controller Board Universal Enclosure Power Supply Input/Output Terminals Input Terminations Output Terminations Communication Ports Serial Communication Port LAN Communication Port Memory Expansion Modules E8UI8DO Expansion Module E16UI Expansion Module RS232 Serial Expansion Module Installation Procedures Installing the Setting the Power Line Frequency Setting the 7718 PCU Address Setting the Tap Emulation Setting the Tap Baud Rate Setting the Controller LAN Baud Rate Setting the High Speed Scan Rate Connecting an Expansion Module Board Installing the Input Field Connections Installing Supervised Field Inputs Schneider Electric. All rights reserved. iii

4 Contents PCU 7718 Installation Guide Connecting RTD Sensor Inputs Connecting Lini-Temp Inputs Connecting 0 20 and 4 20 Milliampere Sensors Connecting 0 10 Volt Sensors Connecting Discrete Input Points Setting the Voltage PCU E8UI8DO E16UI Installing Resistors Reducing RC Filtering Installing the Output Field Connections Connecting Discrete Voltage Outputs Connecting Analog Outputs Connecting the Hand Held Console Connecting the LAN Connecting to External Devices Connecting a PC (Direct Connect) Connecting a Modem (Integrated Dial) Installing the Optional RS232 Serial Interface Board Connecting the Power Supply Connecting Power Configuring for Unregulated Power Connecting External Output Power Connecting 24 VAC External Output Power Connecting 24 VDC External Output Power Connecting the E8UI8DO External Output Power Using the 7718 Baseboard AC Power Supply Using an External DC Power Supply Field Hardware Checkout and Addressing Connecting the HHC Setting the 7718 Address Cold Starting the 7718 PCU Checking Out Analog Inputs Check Signal Voltages Check Addresses Checking Out Discrete Inputs Checking Out Discrete Outputs iv 2010 Schneider Electric. All rights reserved.

5 PCU 7718 Installation Guide Contents Set Up and Operation Hardware Inputs Look-Up Tables Selecting Input Type Input LEDs Control Outputs External Output Power Internal Output Power Discrete Voltage Output Terminals Manual Override Analog Output Terminals Communication Ports Communication LEDs RS232 Port Hand Held Console Port RS485 LAN Port Protocol LAN Node Address Data Rate Expansion Ports I/O Expansion Port E8UI8DO Input/Output Expansion Board Universal Inputs Discrete Outputs Power E16UI Expansion Module Universal Inputs RS232 Serial Expansion Module Tap Emulation and Modem Setup Tap Emulation and Beeper Operation Tap Emulation and Pager Operation Modem Switch Settings Auto-dial/Auto-answer Integrated Dial Point Address Summary Inputs Outputs Schneider Electric. All rights reserved. v

6 Resistor Configurations HOA Switch Status Troubleshooting Pinout Chart Baseboard Unit Internal RS RS232 Expansion Module E8UI8DO Expansion Module E16UI Expansion Module Specifications Index

7 PCU 7718 Installation Guide FCC Warning FCC Warning FCC Warning The Federal Communications Commission (FCC) requirements prescribe certification of personal computers and any interconnected peripherals in the FCC rules and regulations. This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: this device may not cause harmful interference, and this device must accept any interference received, including interference that may cause undesired operation. This equipment generates and uses radio frequency (rf) energy for its operation and, if not installed and used in accordance with the installation and operation manual, may cause interference to radio and television reception. It has been found to comply with the limits for a Class A computing device pursuant to the aforementioned regulations. These are designed to provide reasonable protection against such interference when operated in a residential area. Only peripherals (computer input/output devices) certified to comply with the Class A limits may be connected to this device. Operation with noncertified computer peripherals is likely to result in interference with radio and television reception. If this equipment does cause interference to radio or television reception, the user is encouraged to correct the situation by one or more of the following measures. Relocate the receiver with respect to the computer. Move the computer away from the receiver. Plug the equipment into a different outlet, so that the computing device and receiver are on different branch circuits. Disconnect and remove any unused cables that may be acting as a transmission source. Make certain that the computing device is plugged into a grounded outlet receptacle. If necessary, contact Schneider Electric for additional suggestions Schneider Electric. All rights reserved. vii

8 FCC Warning PCU 7718 Installation Guide viii 2010 Schneider Electric. All rights reserved.

9 60 PCU 7718 Installation Guide Overview Overview Baseboard Input/Output The Model 7718 Process Control Unit (PCU) from TAC is a high-speed, fully distributed microprocessor-based controller, which is used with the TAC I/NET integrated network system. The 7718 is designed to connect directly to the controller LAN working with all other controllers and workstations on the TAC I/NET LAN. The 7718 supports over 200 addressable points to provide full adaptive Direct Digital Control (DDC), energy management, and process control in a single controller. The 7718 is based on a monolithic board design that combines processing, memory management, communication, and field input/output functions on a single printed circuit board. The controller features removable terminal blocks, downloadable firmware, on-board modem drivers, and a direct connect RS232 port. The inherent reliability of this monolithic design is further enhanced with extensive transient protection, automatic self-test features, and a fiber optic communication option. The 7718 is capable of supervising and controlling over 200 addressable points. The I/O configuration flexibility provided by the PCU allows it to interface with a variety of industry-standard I/O devices. The 7718 supports the following hardwired I/Os: The eight universal inputs on the base unit can be defined as the following types: Analog Discrete Pulse The eight universal outputs can be defined as the following types: Discrete Voltage Momentary PWM Analog (voltage) Communication The 7718 provides up to four communication ports, as follows: TB3 This port provides a standard synchronous RS485 controller LAN connection on the 7718 baseboard Two asynchronous serial ports on the 7718 baseboard. These ports provide access to external PCs, external modems, and the HC7410 Hand Held Console (HHC). P4 This asynchronous RS232 port allows direct connection to a PC or external auto-answer (Hayes -compatible) modem. These connections allow the 7718 to perform the functions of a 7801 host Tap without consuming a 2010 Schneider Electric. All rights reserved. 1

10 Overview PCU 7718 Installation Guide second LAN address or additional hardware. Refer to TCON101, TAC I/NET Tap and Repeater Installation Guide, for a description of the Direct-connect and Integrated Dial functions of the Tap. The RS232 port s baud rate is set via the connection of a standard TAC HHC. P1 This asynchronous port provides a modular TTL-level interface to a standard HHC and operates at 1200 baud. P2 This port provides an interface to an optional RS232 Serial Expansion Module. This plug-on board provides an RS232 serial port that can be used to connect an external modem (synchronous or asynchronous) or one of several communication multiplexing devices (refer to RS232 Serial Expansion Module on page 8). Reset Expansion Board Input/Output Options Upon power loss/restoration, the PCU executes an automatic reset memory test of RAM and EPROM. The test uses an array of RAM test bytes and a Checksum check on the EPROM, and if the check is successful, control and execution are passed to programmed memory. A manual reset that is started by pressing the reset button executes the same tests. Expanded I/O capability and flexibility are provided via an expansion port that supports the control of additional I/O points providing a number of I/O options. The expansion board modules that are available are: A universal input, discrete voltage output (E8UI8DO) expansion module is available, providing an additional eight inputs and eight outputs. A universal input (E16UI) expansion module is available, providing 16 additional input points Schneider Electric. All rights reserved.

11 PCU 7718 Installation Guide Physical Description Physical Description The base 7718 controller is a single printed circuit board. The circuit board is easily installed within a TAC Universal Enclosure. All I/O connections to the 7718 are accomplished via plug-on terminal blocks. Controller Board The controller board measures approximately 10.0" L 8.6" W ( cm). 9.6" (24.38cm) 4.60 " 9" (22.86cm) 4.25 " 8.6" 3.92 (21.8cm) " 7" (17.78cm) 3.41 " TB1 TB2 U1 U2 U3 U4 Resistors For Input Type Selection Output LEDs Input LEDs Communication LEDs SW9 Reset J17 J18 J19 J20 J21 J22 J23 J24 TB6 SW8 10" 4.77 (25.4cm) " J31 J38 SW1 P4 TB " 7.03 (37.47cm) " P1 P2 TB4 J25 P3 J27 J26 F9 Figure Motherboard 2010 Schneider Electric. All rights reserved. 3

12 Physical Description PCU 7718 Installation Guide Universal Enclosure TAC s Universal Enclosure provides a protected environment in locations in which dirt, dust, or other contaminants may exist. TAC Universal Enclosures are available in several sizes designed to house various combinations of TAC control units and interfaces. The model used for the 7718 is the ENCL1813, measuring 18.25" H 13.25" W 4.20" D ( cm) The Universal Enclosure allows both door and back panel mounting, providing additional space for optional equipment such as transformers and electrical junction boxes. The enclosure includes a door key lock. The 7718 board comes already mounted on a baseplate. That baseplate/pcb assembly is then mounted into the Universal Enclosure. If the perforated backplane is used to mount the baseplates, then the size of the baseplates and the enclosure are the limiting factors. Baseplates vary in dimension depending upon the type of controller. All controllers and interface units are attached to a baseplate for mounting in a Universal Enclosure. Universal Enclosures are available in varying capacities and sizes. Table 1. Universal Enclosure Dimensions Model Panel Dimensions Standard Door Mounting Baseplate Qty Perforated Panel Backplane Dimensions H W D H W Panel Backplane w/studs Door Key Lock ENCL1813 W/Knockouts and Gasketed Door 18.25" 13.25" 4.2" 1 Any TAC baseplate unit 16.5" (number 8 32 hardware for Optional Panel mounting) 12.5" Mount one (max.) TAC baseplate unit Options: 1 Transformer 1 Junction box Yes Power Supply Electrical power for the 24 VAC input power enters at TB4, at the lower left side of the controller. The 7718 is powered from a single 24-volt AC 40 VA external transformer. The AC input provides power to five on-board supplies. The power options for the 7718 are shown below and in Table 2. A switching power supply circuit is used to generate the +5 VDC logic power. Four linear power supplies are used to generate the +15 VDC Internal, +15 VDC External, 15 VDC, and +24 VDC External voltages. These supply voltages are used for analog signal processing and RS232 communication. The separate +15 VDC (external) regulator supplies current loop excitation power to avoid loss of communication due to a field sensor wiring problem. The optional external power supply (a separate 24VAC transformer or DC power supply) provides 24 VDC regulated or unregulated VDC to the discrete outputs. Regulated 24 VDC power is limited to a total current output of 0.25 A maximum, and the unregulated DC load (from an external 24VAC supply) is limited to a total of 0.75 A. Use an external 24 VDC power supply to power the outputs on the E8UI8DO Expansion Board, and to provide a higher total (2.0 A maximum) current capacity Schneider Electric. All rights reserved.

13 PCU 7718 Installation Guide Physical Description Selection of regulated or unregulated power is done by moving the plug-on jumper at J25 (refer to Configuring for Unregulated Power on page 25). Power line selection (50/60 Hz) is available using the HHC. The 7718 provides input termination for the connection of an optional external 24 VDC power supply. The optional external power supply must be used to power the output circuits on the E8UI8DO Expansion Board. Use an external DC power supply when you need a higher current capacity than the 0.25 A total provided by the on-board supply. When using the external power supply, the outputs may not exceed a total output current of 2.0 A. Table 2. Discrete Output Power Supply Options Power Supply Available Power (maximum) Power From On-board supply (no connection to external power supply) External AC or DC power supply External DC supply 0.25 A Regulated on-board DC power (+24 VDC) 0.25 A On-board AC power 0.75 A External AC 0.75 A Unregulated on-board DC (31 39 VDC)* 2 A External +24 VDC supply to baseboard outputs 2 A External +24 VDC supply to E8UI8DO expansion board outputs Input/Output Terminals Input Terminations * The unregulated DC voltage available on the discrete outputs depends on the external supply voltage and discrete output loading. Output Terminations The 7718 s input and output terminals are located in different areas of the board. The inputs and outputs do not use the same number of terminals to make up a terminal set. See Figure 23 on page 32 for terminal locations. Signal inputs are provided along the upper left side in two groups of four inputs (TB1 and TB2). Three screw terminations are provided for each input. Two of these terminations are inputs for Signal and Ground. The third terminal is an output for the external field sensor +15/24 V excitation. The inputs (analog, discrete, or pulse) use point addresses 0000 through There are two types of output terminations available on the 7718, Discrete Voltage Output and Analog 0 10 VDC output. Discrete Voltage Outputs Eight universal output terminations are provided along the upper right side of the controller (TB6). An output termination consists of a single output termination screw. A common termination screw is provided on the board for a ground/common return. Each output consists of a voltage sourcing circuit capable of handling 0.25 A at 24 VDC Schneider Electric. All rights reserved. 5

14 Physical Description PCU 7718 Installation Guide Note: The total combined output currents using the on-board, regulated 24 VDC power supply is 0.25 A, and 0.75 A when using the unregulated supply. When using an external 24 VDC supply for the outputs, the total combined output may be increased to a maximum of 2 A (0.25 A per output). Communication Ports Each output provides discrete control of a field contactor or a proportional control through pulse-width modulation (PWM) of the output contact. The discrete outputs use point addresses 0000 through Analog 0 10 VDC Outputs Serial Communication Port The 7718 PCU also has eight 0 10 VDC analog outputs available at TB6 (see Figure 23 on page 32). You may use these analog outputs to replace the corresponding discrete voltage outputs on TB6. This is done by moving the desired jumper (J17 J24) from the A B position (discrete output selection) to the B C position (0 10 VDC analog output selection) for each output to be changed. For example: moving only J17 from position A B to position B C places analog output number 1 onto TB6-1. Terminals 2 through 8 of TB6 remain discrete voltage outputs 2 through 8. The analog outputs use point addresses 3100 through There are three communication ports on the 7718 board, and an optional communication board that can be added as a plug-on daughterboard. All connections to the LAN, modems, external PCs and the HHC are made using these ports. See Figure 23 on page 32 for port locations. The two asynchronous serial ports (on the 7718 baseboard) provide access to external PCs, external modems, and the HHC. Modem and PC Connection The first asynchronous port (P4) provides an RS232 port for direct connection to a PC or external auto-answer (Hayes-compatible) modem. The RS232 port s baud rate is set via the connection of a standard TAC HHC. Hand Held Console Connection LAN Communication Port The second asynchronous port (P1) provides a modular TTL-level interface to the standard HHC and operates at 1200 baud. An RJ11 modular jack is provided along the lower left side of the controller for connection of the TAC HHC. The LAN communication port (TB3) is located along the lower left side of the controller under the input terminal TB2. A 3-pin terminal block provides connection of the RS485 shielded, twisted pair on the standard controller. The normal speed of communication on the controller LAN is 19,200 baud. The controller LAN speed can be lowered to 9600 baud using the HHC in order to accommodate lower grade cable installations Schneider Electric. All rights reserved.

15 PCU 7718 Installation Guide Physical Description Memory The 7718 also provides support for several types of memory with variable amounts of each. The memory is currently organized as follows: Table Memory Socket Amount Memory type U4 32 KB EPROM (stores boot firmware) U1, U2 and U3 96 KB STATIC RAM (stores download software and database. Memory is allocated dynamically.) Static RAM Expansion Modules The 7718 also provides 256 bytes of serial nonvolatile RAM (NOVRAM) memory storage. This memory is used to hold all parameters necessary to establish basic communication with the controller after a long-term power outage (i.e., loss of RAM memory). The software may be downloaded while the 7718 is on the TAC I/NET LAN. The software design and memory organization supports the complete download of all software including revised LAN drivers which are invoked after completion of the download. The downloaded software is held in RAM. When the 7718 is emulating a Tap, it can store the telephone numbers a standard Tap would. Memory is sized to insure accommodation of at least eight telephone numbers of at least twenty-five digits each. The base unit configuration of the 7718 provides a minimum of 96 KB of battery-backed static RAM for software data storage and imbedded 7801, and Tap functions such as message queue, dial telephone numbers, and async/sync communication buffers. Memory Exhaustion Warning The PCU editors provide a warning message when the user adds a point or function that could exceed the available PCU memory. The 7718 can be expanded by adding one or more expansion modules to the controller s expansion ports. The RS232 Serial Expansion Module connects at port P2, the other I/O expansion modules connect to the 7718 motherboard at port P3. Available I/O expansion modules include: E8UI8DO I/O Expansion Module E16UI Expansion Module RS232 Serial Expansion Module E8UI8DO Expansion Module The Eight Point Universal Input/Eight Point Discrete Output (E8UI8DO) Expansion Module provides an additional eight inputs and eight voltage sourcing outputs on an I/O expansion board that attaches to expansion port P3 at the lower end of the controller 2010 Schneider Electric. All rights reserved. 7

16 Physical Description PCU 7718 Installation Guide E16UI Expansion Module RS232 Serial Expansion Module PCB. The expansion module card is 3.25" L 8.60" W ( cm). It attaches on top of the 7718 with standoffs supplied with the module. Signals are passed from the E8UI8DO through a ribbon cable between the terminals of the two boards. The input and output points on the E8UI8DO expansion board occupy point addresses 0100 through The outputs are defined in the database as your choice of analog (PWM) or discrete outputs. The current requirements of the discrete outputs are separate from the maximum values for the motherboard. The inputs are shipped as 0 5 volt, but may be redefined on the expansion module by changing the resistors in resistor strip sockets A, B, and C. Refer to Universal Inputs on page 41 for more information. They are also defined in the database as analog, discrete or pulse. The Sixteen Point Universal Input (E16UI) expansion module provides sixteen universal (analog or contact) inputs. The expansion module card is 3.25"L 8.60" W ( cm). It attaches on top of the 7718 with standoffs supplied with the module. Signals are passed from the E16UI through a ribbon cable between the terminals of the two boards. The input points on the Sixteen Point E16UI Expansion Board occupy point addresses 0100 through 0107 and 0200 through Inputs are shipped as 0 5 V and may be configured as 0 10 V or 0 20 ma current input by inserting precision resistors into resistor strip sockets A, B or C. Refer to Universal Inputs on page 43 for more information. The RS232 Serial Expansion Module provides a fourth serial interface with a full complement of modem control, data and clock signal on an RS232 port. It provides two-way dial or dedicated line communication as currently supplied by TAC s or Tap. The data rate is user-selectable up to 9600 baud. This optional interface can be connected to any of the following devices: External auto-dial/auto-answer (AD/AA) modem When connected to a Hayescompatible AD/AA modem, the 7718 will provide the functionality of the Tap. The following types of modems are supported: Synchronous Use a synchronous modem when the controller is loaded with a TAC I/NET version 4.x or earlier binary file. The controller must also have TAC I/NET version 4.x boot firmware (EPROM). Asynchronous Use an asynchronous modem when the controller is loaded with a TAC I/NET 2000 or later binary file. The controller must also have TAC I/NET 2000 or later boot firmware (EPROM). Note: Ensure that all AD/AA Taps within your TAC I/NET system are configured to use the same communication protocol either synchronous, or asynchronous. Mixing AD/AA protocols will cause communication errors Schneider Electric. All rights reserved.

17 PCU 7718 Installation Guide Physical Description TAC I/NET 2000 is compatible with TAC I/NET version 4.x Tap and controller binary loads. Therefore, when synchronous AD/AA communication is required on a TAC I/NET 2000 system (for example, when using a 78040, 78050, or Tap), you must continue to use TAC I/NET version 4.x Tap and controller binary loads. External synchronous dedicated line modem When connected to an external Hayes-compatible dedicated line modem, the 7718 provides the functionality of a TAC Tap. Refer to TCON101, TAC I/NET Tap and Repeater Installation Guide, for a complete description the Tap function. Another RS232 data communication device Schneider Electric. All rights reserved. 9

18 Installation Procedures PCU 7718 Installation Guide Installation Procedures This section provides: installation instructions field checkout procedures troubleshooting suggestions Installing the 7718 Use the following steps to install the 7718 baseboard. This procedure allows you to set up the 7718 with the proper DCU address, set Tap emulation, baud rate and controller LAN baud rate. 1. Ensure power is disconnected from the 7718 PCU. 2. Disconnect power to all devices that will be connected to the 7718 PCU. Warning: Failure to disconnect power from all interconnected equipment when performing electrical installation may result in damage to the equipment, electrical shock, or burns. 3. Mount universal enclosure on a wall. 4. Bring conduit into box (conduit contains power, sensor cables, etc.). 5. Attach the motherboard PCB/baseplate assembly into the universal enclosure box. 6. Mount any expansion boards, beginning with the RS232 board, on to the The expansion boards mount on top of the 7718 PCU. Table 4. Attachment Instructions Basic 7718 unit Unit with optional RS232 board Unit with expansion board Eight screws support the motherboard/baseplate assembly. Insert the RS232 board onto the top of the 7718 PCB base unit at RS232 option port. Attach the expansion board to the top of the motherboard, then fasten the expansion board s four screws to the extension spacers mounted on the motherboard. Setting the Power Line Frequency 7. Connect the modem or external PC. 1. Connect the power supply to the Connect the HHC to the 7718 and then press [Code]. 3. Enter 92 and press [Enter]. 4. The HHC displays the current power line frequency setting (50 or 60). Select your power line frequency by pressing either [Inc] or [Dec] Schneider Electric. All rights reserved.

19 PCU 7718 Installation Guide Installation Procedures Setting the 7718 PCU Address 5. Press [Enter] to accept your choice. 6. Reconnect power to devices that are connected to the 7718 PCU. 1. Connect the HHC to port P1 and set the 7718 s LAN address. Press [DCU ADDR]. The current 7718 address displays in the two right-most digits of the HHC display. 2. Enter the desired address using the numeric keys. The address displays as it is entered. 3. Press [Enter]. The 7718 RAM is updated with the new address. 4. Terminate wires at PCB. Refer to Installing the Input Field Connections on page 13 and Installing the Output Field Connections on page 21. Setting the Tap Emulation 1. Connect the HHC to port P1. 2. Press [Code]. 3. Enter 90 and press [Enter]. The emulated device type model number (771800, 01, 03, or 06) displays in the readout. Table 5. HHC Tap Emulation Selection Tap Model HHC Display None Note: Selecting 7803 or 7806 also enables the 7801 function. 4. Press [Inc] or [Dec] to toggle through 7801, 7803 or 7806 Tap emulation. 5. Press [Enter] to accept your choice. Setting the Tap Baud Rate 1. Connect the HHC to port P1. 2. Press [Code]. Setting the Controller LAN Baud Rate 3. Enter 91 and press [Enter] to set the Tap baud rate, and press [Enter]. 4. Press [Inc] or [Dec] to toggle through the available PC port baud rates. Typically, the desired rate is Press [Enter] to accept your choice. 1. Connect the HHC to port P1. 2. Press [Code] Schneider Electric. All rights reserved. 11

20 Installation Procedures PCU 7718 Installation Guide 3. Enter 6 and press [Enter] to set the controller LAN baud rate and press [Enter]. 4. Press [Inc] or [Dec] to toggle between the 9600 baud and 19.2 Kbaud rates. 5. Press [Enter] to accept your choice. 6. Connect the 7718 to the LAN. Refer to Connecting the LAN on page Terminate wires at PCB. Refer to Installing the Input Field Connections on page 13 and Installing the Output Field Connections on page Program the PCU from the host PC. Refer to any of the following documents for details: TCON142, TAC I/NET Operator Guide (Windows) TCON207, TAC I/NET 2000 Operator Guide TCON299, TAC I/NET Seven Operator Guide Setting the High Speed Scan Rate 1. Connect the HHC to port P1. 2. Press [Code]. 3. Enter 10 and press [Enter] to set the scan rate and press [Enter]. 4. To set for a pulse rate of 4 per second enter To set for a pulse rate of 20 per second enter Press [Enter] to accept your choice. Note: You must correctly configure the inputs for proper operation at the selected scan rate. Connecting an Expansion Module Board Warning: Ensure that no power is applied to the 7718 when performing these procedures. Failure to disconnect power from all interconnected equipment when performing electrical installation may result in damage to the components, electrical shock, or burns. Mount this option-board on top of the baseboard using the four spacers and screws provided. The E8UI8DO and E16UI use the same standoffs. The RS232 Serial Board connects to port P2 on the 7718 PCU. The inputs and outputs are connected using the same procedures as outlined below for the basic 7718 unit (see Figure 2 on page 13). 1. Insert the four spacer screws into the 7718 PCU. 2. Place the expansion board over the four spacers and secure it using the four screws provided. 3. Connect the ribbon cable from the expansion board port P1 to the 7718 PCU port P Schneider Electric. All rights reserved.

21 PCU 7718 Installation Guide Installation Procedures 7718 PCU J31 5V15V TB3 P4 TBX1 TBX2 AI-5 AI-1 AI-6 AI-2 AI-3 AI-4 AI-7 AI-8 B4 B3 B2 B1 A4 A3 A2 A1 D4 D3 D2 D1 C4 C3 C2 C1 B8 B7 B6 B5 A8 A7 A6 A5 D8 D7 D6 D5 C8 C7 C6 C5 Input 1 2 OFF 3 AUTO J9 7 8 J10 P2 P1 J11 Output OPWR P3 TBX3 CH D08 D07 D06 D05 D04 D03 D02 D01 TBX4 EXT VXT2 VXT1 Installing the Input Field Connections Figure 2. Expansion Board Mounting on the 7718 PCU Ribbon Cable Connecting Expansion Board P1 to 7718 PCU P3. The 7718 supports several types of inputs, each using different field connections. Use the procedures shown below to connect the sensors you use to the Connections to an expansion board are the same for like types of inputs and outputs. Caution: The input, output and power wiring must be routed along the side of the controller. The wiring is not to lay across the controller. Installing Supervised Field Inputs Supervision of inputs may be done on a single Normally Open or Normally Closed contact, or on multiple Normally Open contacts connected in parallel. The contacts may be supervised for line cuts by using a single resistor connected in parallel with the contact. If you want additional supervision for line shorts, add an additional resistor in series with the contact. The resistor value for either shall be 1K ohm, 1 4 W, 5% min, or 1K ohm, 1 4 W 1%. The resident I/O points editor of the TAC I/NET host must be configured for either single resistor supervision, or two resistor supervision (see Figures 3 and 4) Schneider Electric. All rights reserved. 13

22 Installation Procedures PCU 7718 Installation Guide Single resistor supervision with a parallel resistor. Configuration is the same for normally closed switch/contact. Entire circuit is supervised for line cuts ( open wire) Double resistor supervision with a parallel and a series resistor. Entire circuit is supervised for line cuts ( open wire) 1K 1K 1K Parallel Resistor Parallel Resistor Series Resistor Portion of circuit is supervised for jumpers ( shorts in wiring) Normally Open Switch/Contact Figure 3. Supervised Single Switches/Contacts Normally Closed Switch/Contact Note: The components shown inside the dashed boxes should be in close physical proximity. Single resistor supervision with a parallel resistor. Entire circuit is supervised for line cuts ( open wire). Double resistor supervision with a parallel and a series resistor. Entire circuit is supervised for line cuts ( open wire) Parallel Resistor Parallel Resistor Note: The components shown in the dashed box should be in close physical proximity. Series Resistor Portion of circuit is supervised for jumpers ( shorts in wiring) Connecting RTD Sensor Inputs Figure 4. Supervised Multiple Switches/Contacts Signal inputs are provided along the upper left side in two groups of four inputs. Three screw terminations are provided for each input (Signal, Ground and +15/24V) as shown in Figure 5. RTD 1,000 ohm temperature sensors may be connected to the 7718 baseboard, E8UI8DO and E16UI modules in a 2-wire configuration as shown in Figure 5. You must configure the input position for RTD sensors by inserting a resistor in the corresponding resistor position (B1 through B8). See Figure 11 on page 20 for resistor installation. Note: Connection of 100 ohm RTD sensors to the 7718 motherboard, E8UI8DO and E16UI expansion boards are not recommended. 1. Insert a 1K ohm, 1 8 W, 1% resistor in the desired resistor B position for that input. 2. On the 7718 baseboard, jumper the J38 center pin to the +5 V position, allowing the B position plug-in resistor strip to provide 5 V RTD excitation Schneider Electric. All rights reserved.

23 PCU 7718 Installation Guide Installation Procedures RTD TB UI-1 1K ohm, 1/8 W, 1% resistor in B1 for a 1,000 Ohm RTD. On the 7718 baseboard, strap J38 to +5 V. On the E8UI8DO, strap J10 to +5 V. On the E16UI, strap J10 to +5 V for TBx1 and TBx2. Strap J12 to +5 V for TBx3 and TBx4. Figure 5. RTD Sensor Connection Connecting Lini-Temp Inputs 3. On the E8UI8DO Expansion Board, jumper the J10 center pin to the +5 V position to allow 5 V RTD excitation. 4. On the E16UI Expansion Board, jumper the J10 center pin to the +5 V position for TBX1 and TBX2 and jumper the J12 center pin to the +5 V position for TBX3 and TBX4. This allows 5V RTD excitation at these terminals. 5. Connect one lead to a signal (UI-1 through UI-8) terminal on TB1 or TB2. 6. Connect the other lead to the terminal of the input set. Signal inputs are provided along the upper left side in two groups of four inputs. Three screw terminations are provided for each input (Signal, Ground and +15/24 V) as shown in Figure 6. The LTS80 temperature sensors can be connected in a 2-wire or 3-wire configuration as shown in Figure 6. Using the 2-wire configuration requires that you insert a 10K ohm 1 8 W, 0.1% resistor in the corresponding resistor position (A1 through A8). The 3-wire configuration does not require any resistor configuration. See Figure 11 on page 20 for resistor installation. WHT LTS Sensor ORN Typical 2-wire Sensor connection LTS Sensor Typical 3-wire Sensor connection WHT BLU ORN TB A1 2-Wire Connection: 10K ohm, 1/8 W, 0.1% resistor in A1. Strap J31 to 15V. 3-Wire Connection: No resistor required. Strap J31 to 15V. Figure 6. Lini-Temp Input Sensor Connections 1. Connect the white lead to a signal (UI-x) terminal on TB1 or TB2. 2. Connect the orange lead to the terminal of the input set. 3. For 3-wire sensors, connect the blue lead to the terminal (see Figure 6) Schneider Electric. All rights reserved. 15

24 Installation Procedures PCU 7718 Installation Guide Connecting 0 20 and 4 20 Milliampere Sensors 4. For 2-wire sensor connections, place a 10K ohm, 1 8 W, 0.1% resistor in the corresponding resistor A position. 5. Ensure that the variable voltage selection on J31 of the 7718 is set to +15 V (refer to Setting the Voltage on page 18). 6. On the E8UI8DO Expansion Board select the voltage by positioning jumper J9 (refer to Setting the Voltage on page 18) and 4 20 milliampere sensors can be connected as shown in Figure 7. Use a 249 ohm, 1 8 W, 0.1% resistor in the corresponding resistor position (A1 through A8). See Figure 11 on page 20 for resistor installation. 0 20mA, 4 20mA Sensor In Out (+) ( ) 0 20mA, 4 20mA In Out Sensor (+) ( ) Input Power External Power Supply + Output TB1/TB A2 A1 Sensor connected at TB1-1: 249 ohm, 1/8 W, 0.1% resistor in A1 Sensor connected at TB1-2: 249 ohm, 1/8 W, 0.1% resistor in A2 Note: Use external power supply if more than eight 0 20 or 4 20 ma sensors are used. Figure and 4 20 Sensor Connections 1. Connect the output lead from the sensor to SIGNAL (UI-x) terminal on TB1 or TB2. 2. Connect the input lead of the sensor to the terminal of the input set (see Figure 7). 3. Ensure that the variable voltage selection is set on J31 of the 7718 to the appropriate voltage (refer to Setting the Voltage on page 18). 4. On the E8UI8DO Expansion Board select the voltage by positioning jumper J9. On the E16UI Expansion Board set jumpers J9 and J11 (refer to Setting the Voltage on page 18). If more than eight 0 20 ma sensors are connected, or if more than eight 0 20 or 4 20 ma sensors are connected in any combination, use an external power supply and connect as described below. 1. Connect the output ( ) lead from the sensor to SIGNAL terminal on TB1 or TB2. 2. Connect the input (+) lead from the sensor to the positive (+) terminal of the external power supply. 3. Connect the negative ( ) terminal of the external power supply to the terminal (see Figure 7). 4. Install a 249 ohm, 1 8 W, 0.1% resistor in the corresponding resistor A position Schneider Electric. All rights reserved.

25 PCU 7718 Installation Guide Installation Procedures Connecting 0 10 Volt Sensors A 0 10 V sensor may use three leads to connect to the 7718 if powered by the 7718 PCU. It also requires a 100K ohm, 1 8 W, 1% resistor installed in the corresponding C resistor position. Connection is identical for the 7718, and the E16UI and E8UI8DO Expansion Boards V Sensor Signal Out In TB C1 Sensor connected at TB1-1: 100K ohm, 1/8 W, 1% resistor in C1. Strap to +15 V or +24 V as required. Connecting Discrete Input Points Figure Volt Sensor Connections 1. Connect the signal out lead of the 0 10 V sensor to a signal (UI-x) terminal. 2. Connect the negative lead of the sensor to the terminal of the Connect the lead of the sensor to the terminal on the 7718 (see Figure 8). 4. Install a 100K ohm, 1 8 W, 1% resistor in the corresponding resistor C position. 5. Ensure that the variable voltage selection is set on J31 of the 7718 to the appropriate voltage (refer to Setting the Voltage on page 18). 6. On the E8UI8DO Expansion Board select the voltage by positioning jumper J9 (refer to Setting the Voltage on page 18). 7. On the E16UI Expansion Board select the voltage by positioning jumper J9 for TBX1 and TBX2 and J11 for TBX3 and TBX4 (refer to Setting the Voltage on page 18). For contact sensing on the 7718 PCU, the E8UI8DO Expansion Board, or the E16UI Expansion Board, either DI or PI, the excitation current for the field contact is achieved by placing a 1K ohm, 1 4 W, 5% resistor in the appropriately numbered B position. The B position provides a pull-up on the input to +5 VDC for dry contact excitation. Dry Contact For DI or PI Note: Contact closed = logical 1st or 2nd of state description pair. TB B1 Dry Contact connected at TB1-1: 1K ohm, 1/4 W, 5% resistor in B1 Figure 9. Dry Contact Connections 2010 Schneider Electric. All rights reserved. 17

26 Installation Procedures PCU 7718 Installation Guide 1. Connect one lead from the contact to the signal (UI-x) terminal. 2. Connect the other lead of the sensor to the terminal of the 7718 (see Figure 9). 3. Install a 1K ohm, 1 4 W, 5% resistor in the corresponding resistor B position. 4. On the 7718 position the jumper on J38 on posts B and C for +5 V pull-up. 5. On the E8UI8DO Expansion Board, jumper the J10 center pin to +5 V to supply the +5 V pull-up 6. On the E16UI Expansion Board, jumper the J10 center pin to +5 V for TBX1 and TBX2, and jumper the J12 center pin to +5 V for TBX3 and TBX4, to provide the +5 V pull-up. Setting the Voltage PCU7718 E8UI8DO E16UI You may select whether to provide +15 or +24 volts with a maximum load of 160 ma to sensors connected to the 7718 PCU. When using Lini-Temps (which require +15 V) and 0 20 ma sensors that require 24 V, or if more than eight 0 20 ma sensors are used, then an external power supply must be used. You must also configure jumper J31 for 15 V or 24 V power. All terminals on the input connection blocks TB1 and TB2 on the 7718 PCU baseboard will be set to the +15 V or +24 V selection. You may select either +15 or +24 volt power provided by the 7718 PCU to a connected sensor by positioning a jumper on J31 (see Figure 23 on page 32). To achieve +15 volts, position the jumper on posts B and C. Position the jumper on posts A and B to achieve +24 volts. You may select either +15 or +24 volt power provided by the E8UI8DO by positioning a jumper on J9 (see Figure 30 on page 41). To achieve +15 volts, position the jumper on posts A B. Position the jumper on posts B C to achieve +24 volts. Jumper position J10 is used to select the pull-up voltage used by the B resistor positions. When using J10 the pull-up voltage may be set to 5 V or 15 V. On the E16UI Expansion Board jumper J9 is used for TBX1 and TBX2, while jumper J11 is used for TBX3 and TBX4. To achieve +15 volts, position the jumper on posts A B of the respective jumper. Position the jumper on posts B C of the respective jumper for +24 volts. Jumpers J9 and J11 select the voltage for sensor excitation. Jumpers J10 and J12 select the setting for pull-up voltage (+15 V or +5 V) through B resistor strips. Table 6. Variable Voltage Summary Function Jumper Configuration +15 V power on 7718 PCU J31 jumper B to C +24 V power on 7718 PCU J31 jumper A to B +15 V power on E8UI8DO J9 jumper center pin to +15 V +24 V power on E8UI8DO J9 jumper center pin to +24 V Schneider Electric. All rights reserved.

27 PCU 7718 Installation Guide Installation Procedures Table 6. Variable Voltage Summary (Continued) Function Jumper Configuration +15 V power on E16UI J9 jumper center pin to +15V +24 V power on E16UI J9 jumper center pin to +24 V Installing Resistors Caution: The available 160 ma at (either +15 or +24 VDC) applies to the Expansion Boards also. The combined current drain for base inputs and expansion inputs cannot exceed 160 ma total when using the on-board supply. The eight inputs on the E8UI8DO Expansion Board and the 7718 PCU baseboard, and the sixteen inputs on the E16UI Expansion Board, are shipped in a 0 5 volt configuration. The position numbers (A1 A8) correspond to the inputs UI-1 through UI-8. Alternate positions labeled B, C and D are also provided (see Figure 10). TB1 TB UI-1 A1 A2 A3 A4 B1 B2 B3 B4 UI-2 UI-3 UI-4 UI-5 UI-6 UI-7 UI-8 A5 A6 A7 A8 B5 B6 B7 B8 C1 C2 C3 C4 D1 D2 D3 D4 C5 C6 C7 C8 D5 D6 D7 D8 Figure 10. Input Configuration Resistors The A positions provide a pull-down to DC ground on the input signal for analog input current sensing. The B positions provide a pull-up on the input to 5 volts DC for excitation of discrete contact inputs. The B position also is also used to excite an RTD sensor configured in 2-wire mode. The C positions provide a resistance divider for achieving a 0 10 V input span. Note: The +15 volt J38 selection (with the appropriate resistor value in the corresponding B position) allows the use of non-standard resistive temperature resistors Schneider Electric. All rights reserved. 19

28 Installation Procedures PCU 7718 Installation Guide The plug-in resistor positions allow you to perform the following input reconfigurations. Position the jumpers to support the configuration, as shown in Table 7. Table PCU Input Jumper Configuration Function Jumper Configuration +5 V Pull Up for DI Points J38 jumper center pin to +5 V +15 V Pullup J38 jumper center pin to +15 V +15 V Sensor Power J31 jumper B to C +24 V Sensor Power J31 jumper A to B For 0 20 ma, insert a 249 ohm, 1 8 W, 0.1% current sensing resistor in the corresponding resistor position (A1 through A8). For 2-wire Lini-Temp, install a 10K ohm, 1 8 W, 0.1% resistor in an A position. For 0 10 V, install a 100K ohm, 1 8 W, 1% resistor in a C position. For dry contact (DI or PI) inputs, install a 1K ohm, 1 4 W, 5% resistor in a B position. For RTD 1000 ohm inputs, install a 1K ohm, 1 8 W, 1% resistor in a B position. See Figure 11 on page 20 for details of installation. A1 A2 A3 A4 B1 B2 B3 B4 C1 C2 C3 10 K ohm, 1 /8 W, 0.1% for Two-wire Lini-Temp (P/N ) 249 ohm, 1 /8 W, 0.1% for 0 20 ma Input (P/N ) 1 K ohm, 1 /4 W, 5% for Dry Contact Input: DI or PI (P/N ) 1 K ohm, 1 /8 W, 1% for RTD Excitation (P/N ) 10 K ohm, 1 /8 W, 0.1% for Thermistor (P/N ) 100 K ohm, 1 /8 W, 1% for 0 10 V Input (P/N ) Reducing RC Filtering Figure 11. Resistor Installation In order to accept fast pulse input rates (>5 Hz and < 20 Hz), reduce the RC filtering by inserting a 1K ohm, 1 4 W, 5% resistor in the desired E position for that input (see Table 12 on page 21). This will reduce the RC filter by a factor of 100. Select the high speed scan rate using Code 10 through the HHC. Refer to Setting the High Speed Scan Rate on page Schneider Electric. All rights reserved.

TAC I/NET. Installation Guide. Seven. Process Control Unit TCON127. 09/10. for TAC I/NET Building Automation Systems

TAC I/NET. Installation Guide. Seven. Process Control Unit TCON127. 09/10. for TAC I/NET Building Automation Systems vi TAC I/NET Seven Installation Guide Process Control Unit 5 for TAC I/NET Building Automation Systems TCON. 0/0 We at Schneider Electric have tried to make the information contained in this manual as

More information

TAC I/NETTM. Process Control Unit

TAC I/NETTM. Process Control Unit TAC I/NETTM 7756 Process Control Unit TAC s 7756 Process Control Unit (PCU), part of the TAC I/NETTM family of products, provides direct control and monitoring of process functions from a Peer-to-Peer

More information

TAC I/NET. Installation Guide. Seven. LAN Interface Unit 7790A TCON109. 09/10. for TAC I/NET Building Automation Systems

TAC I/NET. Installation Guide. Seven. LAN Interface Unit 7790A TCON109. 09/10. for TAC I/NET Building Automation Systems vi TAC I/NET Seven Installation Guide LAN Interface Unit 7790A for TAC I/NET Building Automation Systems TCON109. 09/10 We at Schneider Electric have tried to make the information contained in this manual

More information

TAC I/NETTM MR-AHU-HP. Application Specific Controller

TAC I/NETTM MR-AHU-HP. Application Specific Controller TAC I/NETTM MR-AHU-HP Both the MR-AHU and MR-HP controllers are application specific controllers (ASCs). The intention of the design is to reduce total install cost through pre-engineered control algorithms

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

CONSOLE REMOTE I /O AC 9V

CONSOLE REMOTE I /O AC 9V CONSOLE CONSOLE REMOTE I /O AC 9V AC 9V REMOTE I /O User Manual CE-220 Read this guide thoroughly and follow the installation and operation procedures carefully in order to prevent any damage to the units

More information

2100 POS System. 2100 User Guide

2100 POS System. 2100 User Guide 2100 POS System 2100 User Guide Thank you for selecting UTC RETAIL s innovative Model 2100 Point of Sale solution! This guide is designed to acquaint you with the features and functionality of the 2100

More information

EDI Distributor Control Interface Wiring and Setup Instructions

EDI Distributor Control Interface Wiring and Setup Instructions Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls

More information

BroadBand PowerShield. User Manual

BroadBand PowerShield. User Manual BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains

More information

AXIS 291 1U Video Server Rack Installation Guide

AXIS 291 1U Video Server Rack Installation Guide AXIS 291 1U Video Server Rack Installation Guide About This Document This document describes how to install Axis blade video servers in the AXIS 291 1U Video Server Rack. Updated versions of this document

More information

8-Port HDMI Switch USER MANUAL VS0801H

8-Port HDMI Switch USER MANUAL VS0801H 8-Port HDMI Switch USER MANUAL VS0801H FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits

More information

Fire Fighter Phone System Installation Instructions

Fire Fighter Phone System Installation Instructions Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the Fire Fighter s Phone on a 4100U or a 4100ES Fire Alarm Control Panel (FACP).

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

110244-003. PrintPAD CN3/4/3e/4e. User Guide

110244-003. PrintPAD CN3/4/3e/4e. User Guide 110244-003 PrintPAD CN3/4/3e/4e User Guide TABLE OF CONTENTS PrintPAD CN3/4 & PrintPAD CN3e/4e Printer Views...1 Open View...1 Closed View...1 Using Batteries: General Guidelines...1 Installing and/or

More information

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX INSTALLATION INSTRUCTIONS Step 1. Determine the position for the Hands-free phone in the elevator phone

More information

Web Site: www.parallax.com Forums: forums.parallax.com Sales: sales@parallax.com Technical: support@parallax.com

Web Site: www.parallax.com Forums: forums.parallax.com Sales: sales@parallax.com Technical: support@parallax.com Web Site: www.parallax.com Forums: forums.parallax.com Sales: sales@parallax.com Technical: support@parallax.com Office: (916) 624-8333 Fax: (916) 624-8003 Sales: (888) 512-1024 Tech Support: (888) 997-8267

More information

M68EVB908QL4 Development Board for Motorola MC68HC908QL4

M68EVB908QL4 Development Board for Motorola MC68HC908QL4 M68EVB908QL4 Development Board for Motorola MC68HC908QL4! Axiom Manufacturing 2813 Industrial Lane Garland, TX 75041 Email: Sales@axman.com Web: http://www.axman.com! CONTENTS CAUTIONARY NOTES...3 TERMINOLOGY...3

More information

EQUIPMENT SPECIFICATIONS

EQUIPMENT SPECIFICATIONS EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only

More information

HDMI Matrix Switch USER MANUAL VM0404H

HDMI Matrix Switch USER MANUAL VM0404H HDMI Matrix Switch USER MANUAL VM0404H FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits

More information

Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W)

Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Table of Contents Introduction.. Power Over Ethernet (PoE) & Features.... Unpacking and

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Troubleshooting and Diagnostics

Troubleshooting and Diagnostics Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem

More information

USER MANUAL VS92A / VS94A / VS98A

USER MANUAL VS92A / VS94A / VS98A Video Splitter USER MANUAL VS92A / VS94A / VS98A FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

USB 2.0 Peripheral Switch USER MANUAL US221A / US421A

USB 2.0 Peripheral Switch USER MANUAL US221A / US421A USB 2.0 Peripheral Switch USER MANUAL US221A / US421A FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.

More information

BACnet Automation Interface Module (Network Version)

BACnet Automation Interface Module (Network Version) Sense +V Tx Rx LAN LINK Over ARCNET KBaud BACnet Rx BACnet Tx Archive Valid Port S Tx Port S Rx Low Battery Network- Enhanced Access Default MSTP PTP = Download Required on Rnet and Port S IP Address IP

More information

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported PCIe Cards 1.2 PACKAGE

More information

9,'(2 #6(3$5$725 8VHU V#0DQXDO 96043;

9,'(2 #6(3$5$725 8VHU V#0DQXDO 96043; 9,'(2 #6(3$5$725 8VHU V#0DQXDO 96043; Introduction 3 Features 3 Specifications 4 Installation 4 Stand-Alone Installation 4 Daisy-Chain Installation 5 Preventing Radio & TV Interference 6 Limited Warranty

More information

8-Port PoE Network Switch

8-Port PoE Network Switch Page 1 of 12 8-Port PoE Network Switch User s Guide Document Number 91I00-1 Rev A August, 2009 FCC Warning: Page 2 of 12 This devices has been tested and found to comply with the regulations for Class

More information

User Manual IC-485AI 2002-09-27

User Manual IC-485AI 2002-09-27 User Manual IC-485AI Note: This equipment has been tested and found to comply ith the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable

More information

VS-0202 VS-0204. User Manual

VS-0202 VS-0204. User Manual User Manual VS-0202 VS-0204 Read this guide thoroughly and follow the installation and operation procedures carefully in order to prevent any damage to the units and/or any devices that connect to them.

More information

HDMI Switch USER MANUAL VS481A

HDMI Switch USER MANUAL VS481A HDMI Switch USER MANUAL VS481A FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions

4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions 4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the 4100U/4100ES to TFX Fire Fighter s Phone card used to

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The

More information

If anything is damaged or missing, contact your dealer.

If anything is damaged or missing, contact your dealer. User Manual CS-62 Read this guide thoroughly and follow the installation and operation procedures carefully in order to prevent any damage to the units and/or any devices that connect to them. This package

More information

UniPi technical documentation REV 1.1

UniPi technical documentation REV 1.1 technical documentation REV 1.1 Contents Overview... 2 Description... 3 GPIO port map... 4 Power Requirements... 5 Connecting Raspberry Pi to UniPi... 5 Building blocks... 5 Relays... 5 Digital Inputs...

More information

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to

More information

xpico Wi-Fi Embedded Device Server Evaluation Kit Quick Start Guide

xpico Wi-Fi Embedded Device Server Evaluation Kit Quick Start Guide xpico Wi-Fi Embedded Device Server Evaluation Kit Quick Start Guide Part Number 900-685 Revision A June 2013 Copyright and Trademark Contacts 2013 Lantronix, Inc.. All rights reserved. No part of the contents

More information

PagePac PAGEPAL V-5335700

PagePac PAGEPAL V-5335700 PagePac Issue 3 by PAGEPAL V-5335700 INTRODUCTION The PagePal unit interfaces most telephone systems (PBX, KTS, Centrex) to virtually any public address audio system. In addition, PagePal furnishes inputs

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

InnoMedia ESBC 9580-4B. Quick Install Guide. www.innomedia.com 1

InnoMedia ESBC 9580-4B. Quick Install Guide. www.innomedia.com 1 InnoMedia ESBC 9580-4B Quick Install Guide www.innomedia.com 1 Table of Contents Introduction 2 Package Contents 2 CAUTION 2 Installation 3 Wall-Mounting Instructions 5 Troubleshooting 6 Appendix A. LED

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

F2400 FOM II Series Fiber Optic Modem Technical Manual

F2400 FOM II Series Fiber Optic Modem Technical Manual F2400 FOM II Series Fiber Optic Modem Technical Manual T1 Revision B Copyright April 2003 VERSITRON, Inc. 83 Albe Drive / Suite C Newark, DE 19702 www.versitron.com A030430283T PROPRIETARY DATA All data

More information

TAC I/NETTM. Intrusion Alarm System

TAC I/NETTM. Intrusion Alarm System TAC I/NETTM Intrusion Alarm System The TAC I/NET intrusion alarm system (IAS) consists of a mix of security control products that can be combined and configured to provide intruder detection and alarm

More information

How To Use A 1232 On A 1236 On A Computer Or A Cell Phone

How To Use A 1232 On A 1236 On A Computer Or A Cell Phone 12-36-1000 Autodialler and Relay Telephone Interface 1.0 INTRODUCTION 12-36-1000 I/O Telephone Interface with AutoDialer The 12-36-1000 is a autodialer and telephone interface that can be used autonomously

More information

Laser Barcode Scanner

Laser Barcode Scanner Laser Barcode Scanner User s Manual FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are

More information

USER MANUAL. Model 6103 3U ForeFront Alarm Card SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007. An ISO-9001 Certified Company

USER MANUAL. Model 6103 3U ForeFront Alarm Card SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007. An ISO-9001 Certified Company USER MANUAL Model 6103 3U ForeFront Alarm Card An ISO-9001 Certified Company Part# 07M6103 Doc# 123011U Rev. A Revised 7/15/03 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007 CONTENTS 1.0

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

GSM-EXT Cable Assembly Installation Guide

GSM-EXT Cable Assembly Installation Guide GSM-EXT Cable Assembly Installation Guide For Documentation and Online Support: http://www.security.honeywell.com/hsc/resources/mywebtech General Information The GSM-EXT cable assembly is used to connect

More information

User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M)

User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M) Document code: MN67038-2_ENG Revision 1.400 Page 1 of 25 User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M) for

More information

DVI Video Splitter USER MANUAL VS-162 / VS-164

DVI Video Splitter USER MANUAL VS-162 / VS-164 DVI Video Splitter USER MANUAL VS-162 / VS-164 FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These

More information

Personal Assistance System Owner's Guide

Personal Assistance System Owner's Guide Owner's Guide PSC07 READ THIS FIRST This equipment generates and uses radio frequency energy, and if not installed and used properly, that is, in strict accordance with the manufacturers instructions,

More information

EVGA Z97 Classified Specs and Initial Installation (Part 1)

EVGA Z97 Classified Specs and Initial Installation (Part 1) User Guide EVGA Z97 Classified Specs and Initial Installation (Part 1) - 1 - Table of Contents Before you Begin 3 Parts Not in the kit.4 Intentions of the kit 4 Motherboard Specifications 5 Unpacking and

More information

DMX USB PRO. User Manual. www.enttec.com

DMX USB PRO. User Manual. www.enttec.com DMX USB PRO User Manual www.enttec.com Firmware V1.43 February 2007 Package Contents Your DMX USB PRO package should contain these items: DMX USB PRO (Part No. 70304) Driver for Windows software on the

More information

USBSPYDER08 Discovery Kit for Freescale MC9RS08KA, MC9S08QD and MC9S08QG Microcontrollers User s Manual

USBSPYDER08 Discovery Kit for Freescale MC9RS08KA, MC9S08QD and MC9S08QG Microcontrollers User s Manual USBSPYDER08 Discovery Kit for Freescale MC9RS08KA, MC9S08QD and MC9S08QG Microcontrollers User s Manual Copyright 2007 SofTec Microsystems DC01197 We want your feedback! SofTec Microsystems is always on

More information

LDG DTS-4/4R Desktop Coaxial Switch / Remote

LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 ldg@ldgelectronics.com www.ldgelectronics.com

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

AC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134

AC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134 AC 800M EtherNet/IP DeviceNet Linking Device LD 800DN SP1134 Power and productivity for a better world TM AC 800M EtherNet/IP DeviceNet Linking Device LD 800DN NOTICE This document contains information

More information

MANUAL FOR RX700 LR and NR

MANUAL FOR RX700 LR and NR MANUAL FOR RX700 LR and NR 2013, November 11 Revision/ updates Date, updates, and person Revision 1.2 03-12-2013, By Patrick M Affected pages, ETC ALL Content Revision/ updates... 1 Preface... 2 Technical

More information

ELK-MM443. Magic Module Automation Controller

ELK-MM443. Magic Module Automation Controller ELK-MM443 Magic Module Automation Controller Features Re-Programmable Logic Controller Four (4) supervised inputs with analog or digital sensing. Four (4) dry contact SPDT relay outputs. Two relay outputs

More information

ECR Shelf System Installation Guide Centralized Rack Mount Call Recording

ECR Shelf System Installation Guide Centralized Rack Mount Call Recording Hardware & Installation Guide Algo Communication Products Ltd. Customer Support and Sales Tel: 1.877.884.2546 Fax: 604.437.5726 Email: sales@algosolutions.com support@algosolutions.com www.algosolutions.com

More information

XTEND 900 MHZ WIRELESS MODEM For use with VEEDER-ROOT EMR³ DATALINK INSTALLATION INSTRUCTIONS Manual 577013-859, Rev. B

XTEND 900 MHZ WIRELESS MODEM For use with VEEDER-ROOT EMR³ DATALINK INSTALLATION INSTRUCTIONS Manual 577013-859, Rev. B INTRODUCTION This Installation Guide Contains the necessary information to Connect the Wireless Modems to the EMR³ Interconnect Box and the Office Computer for running the EMR³ Datalink Program. For Specific

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

RC2200DK Demonstration Kit User Manual

RC2200DK Demonstration Kit User Manual Demonstration Kit User Manual Table of contents TABLE OF CONTENTS... 1 QUICK INTRODUCTION... 2 INTRODUCTION... 3 DEMONSTRATION BOARD... 4 POWER SUPPLY SECTION... 5 RS-232 INTERFACE... 6 CONNECTORS... 7

More information

On/Off Relay Switch and 3-Way Switch Kit

On/Off Relay Switch and 3-Way Switch Kit 45637/45638 Wireless Lighting Control On/Off Relay Switch and 3-Way Switch Kit marthome Control the On/Off status of permanently installed lighting, fans and more! www.lowes.com/iris 2012 JASCO Made in

More information

Beckhoff onboard SATA-RAID

Beckhoff onboard SATA-RAID Installation and operating instructions for Beckhoff onboard SATA-RAID Version: 1.3 Date: 2009-07-24 Table of contents Table of contents 1. 2. 3. 4. 5. 6. 7. General notes 2 Notes on the documentation

More information

USER MANUAL. PingBrother EPIW104 managed passive poe switch & IP watchdog

USER MANUAL. PingBrother EPIW104 managed passive poe switch & IP watchdog USER MANUAL PingBrother EPIW104 managed passive poe switch & IP watchdog CONTENT Content... 2 Chapter 1... 3 1.1 Preface... 3 1.2 CE mark warning... 3 1.3 FCC warning... 4 Chapter 2... 5 2.1 Physical description...

More information

Disclaimers. Important Notice

Disclaimers. Important Notice Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means,

More information

InnoMedia ESBC 9380-4B. Quick Install Guide. www.innomedia.com 1

InnoMedia ESBC 9380-4B. Quick Install Guide. www.innomedia.com 1 InnoMedia ESBC 9380-4B Quick Install Guide www.innomedia.com 1 Table of Contents Introduction 2 Package Contents 2 CAUTION 2 Installation 3 Wall-Mounting Instructions 5 Troubleshooting 6 Appendix A. LED

More information

3M Wrist Strap and Footwear Tester 740. User s Guide

3M Wrist Strap and Footwear Tester 740. User s Guide 3M Wrist Strap and Footwear Tester 740 User s Guide Table of Contents Section Page Safety Information...3 1.0 General...4 2.0 Description...4 3.0 Operation...5 4.0 Wall Mounting...5 5.0 Wrist Strap Test...6

More information

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...

More information

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES AC averaging technique used to rectify, amplify, and filter 50 Hz to 400 Hz sine-wave signals. Accepts inputs of between 20 mv to 550 V rms to give

More information

Mini Breakout-Board. CNC Interface for LPT Port. Installation Manual Version 4

Mini Breakout-Board. CNC Interface for LPT Port. Installation Manual Version 4 Mini CNC Interface for LPT Port Version 4 Product Brief This breakout-board is designed to connect up to four stepper or servo drives to the parallel port of a PC. This requires the use of a CNC controller

More information

Perle Protocol Transparent Media Converter Modules

Perle Protocol Transparent Media Converter Modules Perle Protocol Transparent Media Converter Modules Installation Guide C-4GPT-DSFP CM-4GPT-DSFP Part# 5500335-10 Overview This document contains instructions necessary for the installation and operation

More information

In regard to calculating system power requirements, refer to DBK Basics located near the front of this manual.

In regard to calculating system power requirements, refer to DBK Basics located near the front of this manual. DBK42 16-Slot 5B Signal Conditioning Module Overview 1 Hardware Setup 2 DBK42 Connection 2 DBK42 Configuration 2 5B Module Connection 2 Power Considerations 2 Terminal Block Connections 3 DaqBoard/2000

More information

DK40 Datasheet & Hardware manual Version 2

DK40 Datasheet & Hardware manual Version 2 DK40 Datasheet & Hardware manual Version 2 IPC@CHIP DK40 Evaluation module Beck IPC GmbH http://www.bcl.de page 1 of 11 Table of contents Table of contents... 2 Basic description... 3 Characteristics...

More information

Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)

Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet) Installation and Maintenance Manual IM 963-1 Group: Controls Part Number: IM 963 Date: July 2010 Supercedes: IM 963 Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)

More information

UniStream CPU-for-Panel

UniStream CPU-for-Panel UniStream CPU-for-Panel Installation Guide USC-P-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

CM6700 Matrix Switcher/Controller

CM6700 Matrix Switcher/Controller CM6700 Matrix Switcher/Controller Installation/ Operation Manual C523M-H (6/05) Pelco 3500 Pelco Way Clovis, CA 93612-5699 USA www.pelco.com In North America and Canada: Tel (800) 289-9100 FAX (800) 289-9150

More information

SYSTEM 4C. C R H Electronics Design

SYSTEM 4C. C R H Electronics Design SYSTEM 4C C R H Electronics Design SYSTEM 4C All in one modular 4 axis CNC drive board By C R Harding Specifications Main PCB & Input PCB Available with up to 4 Axis X, Y, Z, A outputs. Independent 25

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

TM Advanced Tracking Technologies, Inc. 2003 ATTI All rights reserved

TM Advanced Tracking Technologies, Inc. 2003 ATTI All rights reserved TM Advanced Tracking Technologies, Inc. 2003 ATTI All rights reserved Copyright 2003, Advanced Tracking Technologies, Inc. All rights reserved. No part of this publication may be reproduced or transmitted

More information

EMBEDDED ACCESS CONTROL Hardware Installation Guide

EMBEDDED ACCESS CONTROL Hardware Installation Guide EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel

More information

NetScanner System. Toronto: 416 754 7008, Montreal: 514 695 5147, Toll Free:1888 754 7008, Email: sales@a-tech.ca; www.a-tech.ca

NetScanner System. Toronto: 416 754 7008, Montreal: 514 695 5147, Toll Free:1888 754 7008, Email: sales@a-tech.ca; www.a-tech.ca Networking Solutions NetScanner System 9IFC/90DB/90DC FEATURES Ethernet Interface for NetScanner System Modules Provides Power and Hardware Trigger Interface 10/100 Base-T Auto-Negotiating Universal AC

More information

Measuring Temperature withthermistors a Tutorial David Potter

Measuring Temperature withthermistors a Tutorial David Potter NATIONAL INSTRUMENTS The Software is the Instrument Application Note 065 Measuring Temperature withthermistors a Tutorial David Potter Introduction Thermistors are thermally sensitive resistors used in

More information

USER S GUIDE. EE210 - Humidity and Temperature Transmitter for demanding Climate Control Applications GENERAL CAUTION CONNECTION DIAGRAM

USER S GUIDE. EE210 - Humidity and Temperature Transmitter for demanding Climate Control Applications GENERAL CAUTION CONNECTION DIAGRAM USER S GUIDE EE210 - Humidity and Temperature Transmitter for demanding Climate Control Applications GENERAL The EE210 transmitter, available for wall or duct mounting, is designed for the highly accurate

More information

USB-to-Serial RS-232 Hub USB-to-Serial RS-422/485 Hub USER MANUAL UC2322 / UC2324 / UC4852 / UC4854

USB-to-Serial RS-232 Hub USB-to-Serial RS-422/485 Hub USER MANUAL UC2322 / UC2324 / UC4852 / UC4854 USB-to-Serial RS-232 Hub USB-to-Serial RS-422/485 Hub USER MANUAL UC2322 / UC2324 / UC4852 / UC4854 FCC Information This equipment has been tested and found to comply with the limits for a Class B digital

More information

PCAN-MicroMod Universal I/O Module with CAN Interface. User Manual. Document version 2.1.0 (2014-01-16)

PCAN-MicroMod Universal I/O Module with CAN Interface. User Manual. Document version 2.1.0 (2014-01-16) PCAN-MicroMod Universal I/O Module with CAN Interface User Manual Document version 2.1.0 (2014-01-16) Products taken into account Product Name Part number Model PCAN-MicroMod IPEH-002080 with firmware

More information

AXIS T81B22 DC 30W Midspan

AXIS T81B22 DC 30W Midspan INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial

More information

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input

More information

Operation and Installation Manual

Operation and Installation Manual Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control

More information

User s Manual. Home CR-H212. 2.5 2-BAY RAID Storage Enclosure

User s Manual. Home CR-H212. 2.5 2-BAY RAID Storage Enclosure User s Manual Home CR-H212 2.5 2-BAY RAID Storage Enclosure 1 Introduction 1.1 Features - 2-Bay Bus Powered Portable RAID Enclosure -Works with SATA HDD or SSD -Supports Big (JBOD), RAID0, RAID1, and Normal

More information

9,'(2 #6(3$5$725 8VHU V#0DQXDO

9,'(2 #6(3$5$725 8VHU V#0DQXDO 9,'(2 #6(3$5$725 8VHU V#0DQXDO 960435 960437 Introduction 3 Features 3 Specifications 4 Installation 4 Stand-Alone Installation 4 Daisy-Chain Installation 5 Preventing Radio & TV Interference 6 Limited

More information

DT105X / PB105 Series

DT105X / PB105 Series DT105 / Series Cash Drawer Trigger & Printer Beeper User's Manual TM951031-05 Contents Information... 1 Technical And Operational Description... 3 Connections Load Test Specifications......... 5 7 8 Communication

More information