PVS Container Reference Design

Size: px
Start display at page:

Download "PVS Container Reference Design"

Transcription

1 PVS Container Reference Design

2 PVS Container Reference Design Overview Mechanical definitions Material Container design Inverter room design Transformer room design Switchgear room design (optional) Arrangement of components Ventilation (air supply and extraction) Exhaust-air shrouds Air filter Electrical connection... 13

3 PVS Container Reference Design Overview This document contains a description of the design of an inverter station for units in inverter series SINVERT PVS500. The inverter station comprises an inverter room, a transformer room and a medium-voltage room (optional).

4 PVS Container Reference Design Mechanical definitions 2.1 Material Permissible materials for the container are listed below: Steel Concrete The container material must have a guaranteed minimum lifetime of 25 years. 2.2 Container design The container comprises the following components: 2x inverter 1x AC cabinet 1x medium-voltage transformer 1x medium-voltage switchgear (optional) The container dimensions are specified below: Length (external): 6700 mm Width (external): 3000 mm Height (external): 3250 mm Internal height: 2600 mm Minimum height Cable compartment: 300 mm

5 PVS Container Reference Design General design: Degree of protection: Container floor: Base plates: Container false floor: IP54 The floor must have a load-bearing capacity of approximately 10 t inventory. Steel channels at false floor height for cabinet installation, with 4 holes of 16 mm diameter per cabinet The base plates must be coated, removable and lockable. If pressure-relief openings are provided in the false floor, the base plates must be locked to prevent lifting! With false floor, clear height > 170 mm, without thermal insulation Access in aisle via removable base plates Upper edge of aisle flush with mounting surface of cabinets Partitions: 2 partitions as shown in Figure 1 in false floor area cable openings Openings in partitions: Roof: Grounding points / grounding bar: External ground connection: Foundations (for information only) Lightning protection: Supplementary design of steel container: Type of construction: Thermal insulation: Paint finish: Opening in the false floor with aluminum plates between inverter room and transformer room Inverter room: 1 x opening 1200x1214mm for air filter or supply air fan in the inverter room with drill holes and bracing elements provided for mounting. 4 x opening 488x1255 for extracted air above the inverters with external louvers Transformer room: 1x opening 488x488mm for fans MV room: 2x opening 450x500mm for pressure-relief flaps Rainproof, dimensioned for 150 kg/m² 6 grounding points in the container and a grounding bar in the transformer room for 8 connections 2 M12 stainless steel screws, in steel plates, arranged diagonally at two corners of the container frame Strip or post foundations, provided by the customer By means of lightning spikes at every corner of the container Fully welded with trapezoidal plates 4 x ISO corners on the base and 4 x at the top Crane suspension points on the roof By means of PU panels, with galvanized plates, coated with RAL7035, Panel thickness roof = 60 mm Thickness of external/internal coats 120 / 80 µm (Thickness of external coats depending on local environmental conditions)

6 PVS Container Reference Design Inverter room design The inverter room comprises the following components: 2x inverter (WxHxD = 2700mm x 2100 mm x 700 mm / 1965 kg) 1x AC cabinet (WxHxD = 600 mm x 2000 mm x 600 mm / approx. 400 kg) Equipment: Socket outlets on the door Light switch on the door Lighting Luminaires 2 x 2 x 58 W Smoke detector (optional) Thermostatically controlled heater for frost protection 2 kw, 230 V (optional) Container temperature sensor Warning notice: "In order to ensure a safe escape route, do not open the doors of more than one inverter at a time! Door: Width/height, e.g mm/2400 mm clearance dimension (door size suitably dimensioned to allow future replacement of a complete inverter subunit) Single-leaf aluminum door Locking system (with panic lock with knob on outside, latchkey on inside) Doors must open outwards Openings in floor: 1 x 300x300 mm below the AC cabinet 4 x 600x180 mm below the inverters The inverter room dimensions are specified below: Length (internal): Width (internal): Height (internal): Minimum aisle width: 3900 mm 2800 mm 2600 mm 1240 mm

7 PVS Container Reference Design Transformer room design The MV transformer room must be designed to accommodate an oil-immersed or a cast-resin transformer kva transformer (with casters) Dimensions (approx.): Length: 1,800 mm Width: 990 mm Height: 2,180 mm Total weight: Approx. 4,000 kg Equipment: Light switch on the door Lighting Luminaires 1 x 2 x 58 W Transformer rails with side track limits Removable red warning strip directly behind the door to protect personnel Doors must open outwards Fire protection, water pollution control measures, etc. for oil-immersed transformers (oil drip tray, e.g. made of sheet steel, with oil-tight welds) Door: Width/height, e.g mm/2400 mm clearance dimension (door size suitably dimensioned to allow future replacement of an MV transformer) Single-leaf aluminum door Locking system (with panic lock with knob on outside, latchkey on inside) With ventilation elements Openings in floor: 2 x 500x300 mm The load assumptions for the cable support racks must be taken into account and suitable cable fasteners must be provided. The minimum transformer room dimensions are specified below: Length (internal): Width (internal): Height (internal): 2370 mm 1540 mm The room should be at least 50 cm higher than the maximum height of the transformer.

8 PVS Container Reference Design Switchgear room design (optional) Installation of MV switchgear is optional. The container is capable of accommodating air-insulated or SF6-insulated switchgear, e.g. Siemens 8DJH, 2-4 panels, height 1400mm. Equipment: Socket outlets on the door Light switch on the door Lighting Luminaires 1 x 2 x 58 W Pressure-relief openings with appropriate air ducts, expanded metal grids, etc. must be provided. The dimensions of the necessary pressure-relief openings depend on the type of switchgear and the shortcircuit current. Door: Width/height, e.g mm/2400 mm clearance dimension (door size suitably dimensioned to allow future replacement of switchgear) Locking system (with panic lock) Drilling patterns for MV switchgear (specific to project) Length (internal): Width (internal): Height (internal): specific to project specific to project 2600 mm

9 PVS Container Reference Design Arrangement of components The control cabinets have a predefined geometric arrangement which is determined directly by the ventilation openings. Details can be seen in the sketch below. Figure 1, arrangement of components in the container with MV-Switchgear room (optional) Figure 2, arrangement of components in the container without MV-Switchgear room

10 PVS Container Reference Design Ventilation (air supply and extraction) The air supply and air extraction systems of the inverter room and transformer room are mutually decoupled. Inverter room: Air enters the room through a supply air opening in the container side wall. The air requirement of the inverter room is approximately 13,000 m³/h. Without air-filter: 2 centrifugal fans (K3G 355-AX56-02, supplied by ebmpapst) are required. Supply air opening with supply air fan and external louvers Fan control in the AC cabinet Outlet-air openings above the INV cabinets on side walls (opening 4 x 488 mm x 1255 mm) Exhaust air from the PV INV is transported through fan shrouds to outlet-air openings Fan shrouds and sealing material are available as accessories External louvers for outlet-air openings Order kit: Fan shroud for PVS500 (shrouds, fastening elements and sealing material) With air-filter: 4 centrifugal fans (K3G 355-AX56-02, supplied by ebmpapst) are required. Supply air opening with external air filter with integrated fan Fan control in the AC cabinet Outlet-air openings above the INV cabinets on side walls (opening 4 x 488 mm x 1255 mm) Exhaust air from the PV INV is transported through fan shrouds to outlet-air openings Fan shrouds and sealing material are available as accessories External louvers for outlet-air openings Order kit: Fan shroud for PVS500 (shrouds, fastening elements and sealing material) Figure 3, centrifugal fans Transformer room Air enters the room through supply air opening in the door Exhaust air exits through outlet-air opening in side wall Fan control in the AC cabinet 1 fan, type: W4D315-DP26-35, supplied by ebmpapst External louvers for outlet-air openings

11 PVS Container Reference Design Exhaust-air shrouds DC-exhaust-air shroud AC-exhaust-air shroud Figure 4, Design drawings for fan shrouds

12 PVS Container Reference Design Air filter Opening in side wall 1200 mm x 1214 mm Figure 5, Dimension drawing of air filter housing

13 PVS Container Reference Design Electrical connection The basic interconnection between components can be seen in the circuit diagram below. The power cables in the container are installed either in the cable vault or cable floor (see minimum height of cable vault/floor) Figure 6, electrical connection

SERVER ROOM CABINET INSTALLATION CONCEPTS

SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS ZPAS 169 EXAMPLES OF SERVER ROOMS PROJECTS WITH ZPAS CABINETS Data Box in the

More information

DIGITUS Network & Server Cabinets. UNIQUE Series

DIGITUS Network & Server Cabinets. UNIQUE Series DIGITUS Network & Server Cabinets UNIQUE Series Benefits - Server Rack 4-Point locking system front door 3-point locking system rear door Swing handle lock with profile zylinder in front and rear door

More information

Climasys Thermal Management System. Schneider Electric Universal Enclosures 2009

Climasys Thermal Management System. Schneider Electric Universal Enclosures 2009 Climasys Thermal Management System Schneider Electric Universal Enclosures 2009 Schneider Electric Universal Enclosures The specialist in sealed equipment What is the mission of Schneider Electric Universal

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

MODEL HSR-007 Direct Drive Rolling Steel

MODEL HSR-007 Direct Drive Rolling Steel MODEL HSR-007 Direct Drive Rolling Steel 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8 Tel: 866-792-9968 or 705-792-9968 Fax: 705-735-9564 www.tnrdoors.com email: info@tnrdoors.com Model HSR-007

More information

BROWACOM PRODUCTS. Our web-pages can be found from: http://www.browacom.fi

BROWACOM PRODUCTS. Our web-pages can be found from: http://www.browacom.fi BROWACOM PRODUCTS manufactures and sells telecom solutions for professional users. Products include CityCabinet-product family, as a service Browacom offers subcontracting services in electromechanical

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

19" Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted.

19 Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted. 19" Data Racks Attractive design and high quality are characteristic. Basic framework is welded from multiple bent metal plate, which assures great rigidity suitable for heavier equipment. All profile

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

Knürr Smaract. Knürr Smaract. CompactRack

Knürr Smaract. Knürr Smaract. CompactRack CompactRack Features Ample space for components and cabling provided in an efficient, compact design. The innovative frame concept with triangular extrusions ensures low weight while maintaining high stability.

More information

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels

More information

RPV - RP - RA air handling units

RPV - RP - RA air handling units APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Material test chamber with mechanical convection

Material test chamber with mechanical convection FP series 400 Material test chambers Material test chamber with mechanical convection A BINDER material test chamber with mechanical convection of the FP series provides reliably short drying times and

More information

Linkeo 19" freestanding cabinets

Linkeo 19 freestanding cabinets 87045 LIMOGES Cedex France Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88 Linkeo 19" freestanding cabinets Page 1. General characteristics....1 2. Range....2 3. Technical characteristics...3

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

AMS 120. EFT Guest Card Terminal & Refund unit

AMS 120. EFT Guest Card Terminal & Refund unit AMS 120 EFT Guest Card Terminal & Refund unit ACCOUNT MANAGEMENT STATIONS Wall mounted kiosk offering Visitor card purchase and refund Card deposit EFT purchase, refund and loading Full statement facilities

More information

Cardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: 0041 22 77 66 051 info@cardok.com

Cardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: 0041 22 77 66 051 info@cardok.com CARDOK CARLIFT Fast access to underground garages Fast, Silent, Discreet, Design, High-Tech Installation to replace an access ramp on private property Dimensions: (Built to measure, all dimensions can

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,

More information

3. Geberit Pluvia Roof Drainage Systems

3. Geberit Pluvia Roof Drainage Systems 3. Geberit Pluvia Roof Drainage Systems Assortment overview: Pluvia Outlets...52 3.1 Roof outlets... 53 3.1.1 Roof outlets up to 25 l/s...53 3.1.2 Roof outlets up to 100 l/s...55 3.2 Roof outlets for gutters...

More information

Morgue refrigeration unit

Morgue refrigeration unit Morgue refrigeration unit The Morgue refrigeration units are made of sturdy, self-supporting walls, floor and ceiling elements. They are delivered in separate components and are to be assembled on site

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

Server Chassis and Triplet Hardware v1.0

Server Chassis and Triplet Hardware v1.0 Server Chassis and Triplet Hardware v1.0 Author: Steve Furuta, Mechanical Designer 1 Scope This document describes the technical specifications for the custom chassis used in Open Compute Project servers

More information

Liebert DCR Part of the SmartRow Offering. Installation Manual 3-6, Single/Redundant and 5-10 Racks Higher Capacity Cooling Units, 60Hz

Liebert DCR Part of the SmartRow Offering. Installation Manual 3-6, Single/Redundant and 5-10 Racks Higher Capacity Cooling Units, 60Hz Liebert DCR Part of the SmartRow Offering Installation Manual 3-6, Single/Redundant and 5-10 Racks Higher Capacity Cooling Units, 60Hz TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................................1

More information

Secure your IT equipment with confidence... secure with NetClosure

Secure your IT equipment with confidence... secure with NetClosure Secure your IT equipment with confidence... secure with NetClosure SERVER CABINETS NetClosure s REM Series Server Cabinet is the ultimate solution designed and engineered for demanding data center environments.

More information

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency

More information

H45 LED - Direct and indirect pendant

H45 LED - Direct and indirect pendant RAL 01 10 00 IP 20 230V 50/60Hz Specifications Direct and indirect light pendant linear luminaire. Aluminium profile. Diffusers in frosted polycarbonate profile. Driver included. Supplied with clear base,

More information

MAGNUM Original Sauna Stove 6.6 kw 9.0 kw 10.5 kw MAGNUM Cenik and Lite Sauna Stoves 6.6 kw 9.0 kw 10.5 kw Use and Installation

MAGNUM Original Sauna Stove 6.6 kw 9.0 kw 10.5 kw MAGNUM Cenik and Lite Sauna Stoves 6.6 kw 9.0 kw 10.5 kw Use and Installation MAGNUM Original Sauna Stove 6.6 kw 9.0 kw 10.5 kw MAGNUM Cenik and Lite Sauna Stoves 6.6 kw 9.0 kw 10.5 kw Use and Installation With Finlandia and Magnum RC Control Centers Use and installation manual

More information

Cooking at the Speed of light!

Cooking at the Speed of light! Cooking at the Infrared Cooking & Colouring Infrabaker is a modular infrared continuous cooking system developed by Infrabaker International. The machine is designed to cook and/or put colour on a wide

More information

BLADE S-MAX Cabinet for Blade Server

BLADE S-MAX Cabinet for Blade Server Cabinet for Blade Server 1 2 Overview Material specification Corner verticals: 1.5 mm steel End frames: 1.5 mm steel Panel mounts: 2.0 mm steel Panel mount supports: 1.5 mm steel Side panels, door and

More information

Workspace and storage furnishings

Workspace and storage furnishings LISTA Compact Workspace and storage furnishings Test and inspection workstations With its modular test and inspection workstations, LISTA offers optimised solutions for modern quality assurance practices.

More information

Contractors Guide Central Inverter System Installation

Contractors Guide Central Inverter System Installation Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.

More information

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133

More information

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS D E F Y I N G C O N V E N T I O N Congratulations on your new Corner Fridge Your new corner fridge may have different functions

More information

Dimensions (HxDxW) Total Cabinet Area 89.96x 39.69 x 24 in/ 2,285 x 1,008.17 x 612.77 mm 95.47x 48 x 32 in/ 2,425 x 1,219.2 x 812.

Dimensions (HxDxW) Total Cabinet Area 89.96x 39.69 x 24 in/ 2,285 x 1,008.17 x 612.77 mm 95.47x 48 x 32 in/ 2,425 x 1,219.2 x 812. 1 Compaq 10000 Series Racks The 10000 series racks are a family of 1000mm deep racks which are available in 22U, 36U, 42U and 47U 600mm widths. Compaq 10000 Series Racks provides a common, integrated platform

More information

Turnkey Projects, Conversions, Restorations & Property Management. Marsalforn - Gozo APARTMENT FINISHING EXCLUSIVE PACKAGE

Turnkey Projects, Conversions, Restorations & Property Management. Marsalforn - Gozo APARTMENT FINISHING EXCLUSIVE PACKAGE Turnkey Projects, Conversions, Restorations & Property Management Marsalforn - Gozo APARTMENT FINISHING EXCLUSIVE PACKAGE Reg. Office: Karlu Galea Street, Victoria, Gozo Malta. T. 2155 6600 M. 9943 4391

More information

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power: PHOTOVOLTAIC (PV) solar panels Electricity - CE & ISO 9000 certified Photovoltaic solar panels convert sunlight into useful electricity. ZEDfabric supplies high quality mono-crystalline silicon cell PV

More information

Technical Information

Technical Information Technical Information This section of the catalogue provides technical information that will help specify, install and maintain Surelock McGill devices and components. The topics are listed below: Blast

More information

NetXtend Flex Series Integrated Outdoor Enclosure Solution. Outside Plant for Business-Critical Continuity

NetXtend Flex Series Integrated Outdoor Enclosure Solution. Outside Plant for Business-Critical Continuity NetXtend Flex Series Integrated Outdoor Enclosure Solution Outside Plant for Business-Critical Continuity Features & Benefits Full flexibility and scalability one enclosure for various telecommunication

More information

Reduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U

Reduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U Reduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U Applications The High Density Cabinets are suitable for Central Offices and can be used as fiber nodes and termination points

More information

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility

More information

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

ORAY PREFABRICATED GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS

ORAY PREFABRICATED GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS ~GSM SHELTER CONTAINERS ARE PROCUDED ACCORDING TO THE DEMANDED SIZE.~ (W x L x H) Page1 GENERAL FEAUTURES Environmental Conditions : Maximum outdoor temperature

More information

Product and Application Description

Product and Application Description Technical Product - Information Product and Application Description The room temperature controller UP 237K and UP 252K are available in the following colors, matching the design of the wall switch design

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT 2003-2014 CHEVROLET/GMC VANS FOR

INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT 2003-2014 CHEVROLET/GMC VANS FOR INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT 2003-2014 CHEVROLET/GMC VANS FOR (For NEW 2007 ALL WHITE KWIK-KITS ONLY) Warning do not attempt to install A/C units unless you are experienced with servicing

More information

Défumair XR. ventilation and cmv. fire grade - label CE. smoke-extraction fan extraction casing for kitchen at F400-120. advantages.

Défumair XR. ventilation and cmv. fire grade - label CE. smoke-extraction fan extraction casing for kitchen at F400-120. advantages. Défumair XR smoke-extraction fan extraction casing for kitchen at F400-120 Personalisation : - Phonic insulation version by insulated double-skin panels through 25 mm glass wool, class M1. advantages Originally

More information

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR

More information

InForm Mobile Units. Selection. Equipment trolley, filing trolley Printer/PC trolley Overhead/demo trolley

InForm Mobile Units. Selection. Equipment trolley, filing trolley Printer/PC trolley Overhead/demo trolley Selection Equipment trolley, filing trolley Printer/PC trolley Overhead/demo trolley Basic mobile unit Basic mobile with vertical profiles Installation options Functional shelf, low Functional shelf, inclinable

More information

CNC Tool Storage Solutions

CNC Tool Storage Solutions Solutions CNC TOOL STORAGE SOLUTIONS Thanks to the flexibility of the CNC line, your tools will be protected during regular handling, transportation and storage. The Rousseau CNC tool rack distinguishes

More information

Procurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier

Procurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier Procurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier A. Requirement This document is to be used to specify the physical and operational

More information

INSTRUCTION FOR ASSEMBLY. 150x180 v Traditional sauna cabin

INSTRUCTION FOR ASSEMBLY. 150x180 v Traditional sauna cabin INSTRUCTION FOR ASSEMBLY 150x180 v Traditional sauna cabin 1. SAUNA PLAN 1800 LIGHT UNDER THE BENCH VENTILATION OUTLET UPPER BENCH 600 1500 LOWER BENCH 400 700 1656 956 HEATER 366 381 690 815 Light switch

More information

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER PSUM These technical specifications determinate a range of manufactured sizes and models of fire shutters (further only shutters)

More information

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design .8 Ex-Recess-mounted, ceiling emergency light fittings in compact metal design RLF/RLF-INOX 50 18-58 W / RLF/RLF-INOX 50... N 18-36 W (Zone 1,, 1, ) The explosion-protected lighting concept for clean rooms

More information

Incubator with mechanical convection

Incubator with mechanical convection BF series 400 Incubators and cooling incubators Incubator with mechanical convection The BINDER incubator of the BF series with mechanical convection is suitable for all gentle incubation applications,

More information

Installation Guide. DEVIreg 530. Electronic Thermostat. www.devi.com

Installation Guide. DEVIreg 530. Electronic Thermostat. www.devi.com Installation Guide DEVIreg 530 Electronic Thermostat www.devi.com The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive

More information

SMARTY 160 POWER page 4-5 SMARTY 180 / 220 XL page 4-6 SMARTY TX 250 page 4-7. SMARTY TX 160 Alu page 4-8 SMARTY TX 220 Alu page 4-9

SMARTY 160 POWER page 4-5 SMARTY 180 / 220 XL page 4-6 SMARTY TX 250 page 4-7. SMARTY TX 160 Alu page 4-8 SMARTY TX 220 Alu page 4-9 CHAPTER TIG welding Introduction pages - & - WELDING POWER SOURCES DC power sources SMARTY 60 POWER page -5 SMARTY 80 / 0 XL page -6 SMARTY TX 50 page -7 AC/DC power sources SMARTY TX 60 Alu page -8 SMARTY

More information

Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille

Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille Text example Compile and tender according to requirements. Please refer to technical data below for respective

More information

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and

More information

Accessories for GF and RA machines

Accessories for GF and RA machines Orbital cutting & beveling machines for high-purity process piping www.orbitalum.com Accessories for GF and RA machines A brand of ITW Orbital Cutting & Welding 23 www.orbitalum.com Orbital cutting & beveling

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

Cooktop Low-Profile Ventilation Hoods

Cooktop Low-Profile Ventilation Hoods INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............

More information

RRV934. Multi-controller. Synco living

RRV934. Multi-controller. Synco living s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard

More information

IT infrastructure Efficiency-boosting solutions. nextlevel. for data centre

IT infrastructure Efficiency-boosting solutions. nextlevel. for data centre IT infrastructure Efficiency-boosting solutions nextlevel for data centre 2 Rittal IT infrastructure The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind,

More information

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table

More information

Cable Trays Technical Instructions & Specifications

Cable Trays Technical Instructions & Specifications Cable Trays Technical Instructions & Specifications Products Catalogue Objective and Structure The company s main objective is the supply of quality products, with respect to: practical design increased

More information

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems Content Introduction Preventing unauthorized access by perimeter surveillance Monitoring unauthorized access by indoor surveillance

More information

Installation information. METTLER TOLEDO MultiRange DW150 / DW150T wall scale

Installation information. METTLER TOLEDO MultiRange DW150 / DW150T wall scale Installation information METTLER TOLEDO MultiRange DW150 / DW150T wall scale DW150 / DW150T wall scale Contents Contents Page 1. Installation... 2 1.1 Preparatory work... 2 1.2 Installing the wall plates

More information

Switchboard system. NorLine 800

Switchboard system. NorLine 800 Switchboard system NorLine 800 NorLine 800 SWITCHBOARD SYSTEM 2 NorLine 800 Switchboard system Table of contents Subject Page Table of contents 2 Overview 2-3 NorLine 800 technical specifications 4 Structural

More information

Containment Solutions

Containment Solutions Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA

More information

SERVICE MANUAL. Domestic Air Conditioner. Model. Feature HW-05LN03

SERVICE MANUAL. Domestic Air Conditioner. Model. Feature HW-05LN03 Domestic Air Conditioner SERVICE MANUAL Model HW-05LN03 Feature Anti-mold filter Mechanical control Easy clean filters Slide chassis 4-way airflow direction 2 cool settings, 2 fan settings Serial Number:

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Installation Instructions For Slider Casement Air Conditioners

Installation Instructions For Slider Casement Air Conditioners Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT

More information

Services Enclosures and Protected Shafts - Maintaining Compartmentation

Services Enclosures and Protected Shafts - Maintaining Compartmentation Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping

More information

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: info@switchgearcompany.eu

More information

Knürr Miracel. Knürr Miracel. 19 Network and Server Rack Platform 1.12 to 1.22 1.11

Knürr Miracel. Knürr Miracel. 19 Network and Server Rack Platform 1.12 to 1.22 1.11 Knürr Miracel 19 Network and Server Rack Platform 1.12 to 1.22 1.11 19" Server Rack: Knürr Miracel Strong points 1.13 Knürr Miracel ASP ASP/Server Rack 1.16 Knürr Miracel Server Rack 1.18 Knürr Miracel

More information

Customized Server Cabinets

Customized Server Cabinets GOING GREEN WITH CUSTOMIZABLE CABINETS AND RACKS Designed to provide industry leading airflow, CyrusOne s cabinets and rack solutions promote optimal cooling and contribute to reduced power consumption.

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

E-PDD Duct Smoke Detector Installation Sheet

E-PDD Duct Smoke Detector Installation Sheet E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating

More information

Electrical Wiring Technical Bulletin

Electrical Wiring Technical Bulletin Electrical Wiring Technical Bulletin Overview In general, SIP construction is easier and more cost effective when things are planned and thought out before the panels are manufactured. This process will

More information

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow

More information

Installation Instructions

Installation Instructions Installation Instructions READ BEFORE INSTALLING UNIT For Low Profile Window Air Conditioner INSTALLATION WARNINGS AND CAUTION Carefully read the installation manual before beginning. Follow each step

More information

19 DYNAmax Free Standing Server C A B I N E T s

19 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server Cabinets FAMILY W=mm and W=800mm DYNAmax Series Free Standing Server Cabinets DYNAmax series Servering Enclosures, provide

More information

Modular Access Floor for Data Center. From Rack to Row to Room to Building

Modular Access Floor for Data Center. From Rack to Row to Room to Building Modular Access Floor for Data Center From Rack to Row to Room to Building Why using Scneider Electric modular access floor in Data Centers The evolution of modern Data Centers emphasizes specific exigencies

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Summary of Preliminary Assessment on Structural, Fire and Electrical Safety

Summary of Preliminary Assessment on Structural, Fire and Electrical Safety Name of the Factory Address of the Factory Present Status of the Factory Structural Assessment Conducted by : Galaxy Stitch Ltd. : BSCIC Industrial Estate, Plot no. A102, Tongi Gazipur Bangladesh : Under

More information

P 602. This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

P 602. This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001. This generator set has been designed to meet ISO 88 regulation. This generator set is manufactured in facilities certified to ISO 900. This generator set is available with CE certification. Enclosed product

More information

19 DYNAmax Free Standing Server C A B I N E T s

19 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server Cabinets FAMILY W=600mm and W=800mm DYNAmax Series Free Standing Server Cabinets DYNAmax series Servering Enclosures, provide

More information

understanding medium frequency induction melting furnace and its components

understanding medium frequency induction melting furnace and its components understanding medium frequency induction melting furnace and its components 9 Spruce Street, Jersey City, NJ 07306 USA sales@electroheatinduction.com INDUCTION MELTING FURNACE AND ITS COMPONENTS The purpose

More information

Spetec Laminar Flow Systems. Operating Instructions

Spetec Laminar Flow Systems. Operating Instructions Spetec Laminar Flow Systems Operating Instructions 1 Spetec Laminar Flow Systems Operating Instructions Thank you for your trust in the Spetec clean room systems! Your chosen system is ideally suited for

More information

DCF Optimized Rack System

DCF Optimized Rack System Integrated Cabinet Solutions For Business-Critical Continuity DCF Optimized Rack System User Manual IMPORTANT SAFETY GUIDELINES SAVE THESE INSTRUCTIONS This manual contains important instructions that

More information

6. BILLS OF QUANTITIES

6. BILLS OF QUANTITIES 6. BILLS OF QUANTITIES HOUSING BUILDINGS Item Unit Measu Number of General note: This BoQ shall include the delivery of materials stated under the individual items and all miscellaneous unspecified material

More information

Installation Instructions

Installation Instructions READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:

More information

Decree of the Ministry of the Environment on fire safety of ventilation systems

Decree of the Ministry of the Environment on fire safety of ventilation systems THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18

More information

Data Centre Solutions

Data Centre Solutions Issue 6 Data Centre Solutions RACKS POWER COOLING MONITORING SECURITY SERVICE & SUPPORT The simple route to the perfect data centre Data centres are complex systems. Software, hardware and IT infrastructure

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information