SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST HIGH PILED COMBUSTIBLE STORAGE

Size: px
Start display at page:

Download "SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST HIGH PILED COMBUSTIBLE STORAGE"

Transcription

1 July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST HIGH PILED COMBUSTIBLE STORAGE Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments; I-Incomplete; D-Denied This Checklist outlines general requirements for High Piled Storage. Information contained herein applies to typical instances and may not address all circumstances. CODE REFERENCES 2007 California Fire Code (CFC) Chapter 23 & California Building Code (CBC) Chapter 4 & NFPA 13 Sprinkler Systems 2003 NFPA 230 Combustible Storage FILE REVIEW REVIEW FILE Is there an alternate method application approved REVIEW PLANS, PLAN NOTES AND FD APPROVAL LETTER REQUIRED INSPECTIONS 1. Fire Department Final - *may include, but are not limited to, inspections of the racks, smoke/heat vents, and access doors. Based on the design of the HPS, inspections may include: Fire Sprinkler Pipe, Rough & Hydro, and Final Inspection Fire Alarm Pre-wire and Final Inspection REQUIRED SUBMITTAL INFORMATION: 2. Permit fees entered in Permits Plus. 3. Three (3) sets of scaled plans and specifications 4. Contractor shall provide, or have on file, a current Contractor s License. 5. Worker s Compensation Insurance certificate. 6. Current Santa Rosa Business Tax Certificate Circadian Way, Santa Rosa, CA Phone: Fax: Page 1 of 10

2 7. Name and address of project 8. Contractor s name, address, and telephone number. PLANS TO INCLUDE (2007 CFC ) 9. A scaled site plan that shows the entire building, including all fire access lanes, fire hydrants, fire department connection, and fire sprinkler risers. 10. A scaled floor plan of the building showing locations and dimensions of the HPS area, location of the racks, and access doors to the storage area. 11. The maximum desired/proposed storage height for each designated storage area per array. This height is measured from the finished floor to the highest point of the commodity stored (not shelve level). 12. The number of tiers within each rack. 13. The commodity clearance between the top of storage and the sprinkler deflector for each storage arrangement. 14. Aisle dimensions between each storage array. Aisles are measured from the actual edge of the commodity to commodity, not rack to rack. 15. Maximum pile volume for each storage array. 16. The location and classification of different commodity classes. 17. The location of commodities that is banded or encapsulated. 18. The dimension and location of the transverse and longitudinal flue spaces. 19. Details on any specialty storage arrangement systems (i.e., automated, carousel, freezer, etc.) NFPA 13, Chapter 12 The sprinkler design requirements based on commodity type, aisle width, and sprinkler temperature rating as outlined in (e.g.,.45/3000 with 286degree heads). A complete sprinkler design shall be submitted under a separate permit NFPA 13, Section The location of all steel columns in relationship to the racks. All steel columns located within a rack flue space or immediately adjacent to a rack in an aisle will require protection. 22. The location, make, model, type, and automatic link temperature of the automatic/manual release smoke vents. Fusible links shall be at least one temperature rating lower than the fire sprinklers (Local Ordinance) SPRINKLERS: Code References from 2002 NFPA 13 unless otherwise noted 23. Total number of each type of sprinkler and their temperatures are noted Minimum temperature for ceiling sprinkler for high-piled storage is 150 deg, Ceiling and roof cross sectional views are provided. Page 2 of 10

3 (12) For each type of sprinkler the K factor and temperature rating are provided , Table (c and d) Each sprinkler coverage area is within its square footage and dimension limitations in accordance with its listing and Control mode specific application, large drop, early suppression fast response sprinklers installation design comply with the standard and listing limitations. LARGE DROP SPRINKLERS: Code References from 2002 NFPA 13 unless otherwise noted Large drop sprinkler coverage area and maximum spacing is in accordance with Table The minimum area of protection for large drop sprinklers is 80 sq. ft Maximum perpendicular distance to the walls shall be in accordance with ft. is the minimum spacing between sprinklers Large drop sprinklers installed in a building of unobstructed construction shall be in accordance with and a cross sectional view is provided Large drop sprinklers installed in a building of obstructed construction shall be in accordance with and a cross sectional view is provided Sprinkler position in relation to the roof or hanging obstructions shall comply with For obstructions 8 in. or less, sprinklers are positioned in accordance with Depending on the diameter of the branch lines, large drop sprinklers shall be located in accordance with Sprinkler position when more than 24 in. directly above the bottom of an obstruction shall be in accordance with For obstructions running parallel with a branch line, the sprinkler placement shall be in compliance with Sprinklers deflectors shall be located at least 3 ft. above the top of storage, Sprinkler position when above an obstruction more than 24 in. wide complies with Table and Figure , GENERAL STORAGE REQUIREMENTS: Code References from 2002 NFPA 13 unless otherwise noted When a structure has two or more hazard areas or design methods that are nonseparated and are located adjacent to each other, the most hydraulic demanding area shall be extended as required by section Page 3 of 10

4 Dry pipe and pre-action system design areas shall be increased 30 percent but shall not exceed the design area specified in This does not apply to pre-action system designed in accordance with Ceiling slope is detailed, cross sectional view provided, and does not exceed a 2 in 12 slope When adjustments are made to the design area, the designer shall provide an analysis explaining how the adjustments were made Design for idle pallets is in accordance with and Table Miscellaneous and Class I through IV commodity storage up to 12 ft. and Group A plastic, rolled paper, tires shall be protected accordance with Figure and Table GENERAL IN-RACK STORAGE REQUIREMENTS: In-rack sprinklers are ordinary temperature and the K factor, orientation, temperature rating and type complies with and The area limitation for in-rack sprinkler systems is limited to 40,000 sq. ft. of floor area, When adjacent to a heat source the sprinkler temperature rating is in accordance with When in-rack sprinklers are required for Class I IV commodities, water shields are provided when required by section When required for plastics storage, water shields are provided for in-rack sprinklers when required by When in-rack sprinklers are required for miscellaneous storage, the number of sprinklers calculated and the discharge pressure complies with section Sprinklers K-factors for storage applications; rack, tire, roll paper, and baled cotton are in compliance with based on the required discharge density. PALLETIZED, SOLID PILE, BIN BOX, SHELF STORAGE FOR CLASS I-IV COMMODITIES: Hose connections are provided for storage exceeding 12 ft., The minimum design area/density for wet and for dry systems complies with The design for area/density using ordinary or high temperature sprinklers is based on Figures and respectively, and If the density is adjusted due to storage height, it is in accordance with Figure and calculations are provided. Page 4 of 10

5 PALLETIZED AND SOLID PILE FOR CLASS I-IV COMMODITIES: 59. Large drop sprinklers protecting palletized or solid-pile Class I IV commodities is in accordance with Tables (a) and (b), The number of large drop sprinklers calculated for ordinary hazard and miscellaneous storage for the different types of systems complies with Large drop and control mode specific application sprinklers protecting open wood joist construction shall be in accordance with Large drop or control mode specific application sprinkler placement and branch line diameter limitations comply with ESFR sprinklers protecting palletized or solid-pile Class I IV commodities are in accordance with Table The number of ESFR sprinklers calculated for the most hydraulically demanding design area and the number of calculated branch lines complies with ESFR sprinklers installed above and below obstructions are hydraulically calculated in accordance with PALLETIZED, SOLID PILE, BIN BOX, SHELF STORAGE FOR PLASTIC AND RUBBER COMMODITIES: 66. Sprinkler design protecting plastics stored up to 25 ft. are selected in accordance with Figure The designer has provided design information for solid pile storage: closed or open array, clearance between storage, clearance between storage and the roof, pile height, and stable or unstable piles, and Class B, free-flowing Group A, and Class C plastics are protected as the commodity specified in and Design area and density are based on Table and Figure , When determining the design area, the designer provided a calculations illustrating how the design area adjustments were made, Large drop or control mode sprinklers K factor, storage height coverage, number of design sprinklers, and hose stream demand are in accordance with Table (a) or (b), Large drop or control mode sprinklers for open wood joist construction, large drop sprinkler pressure, design area, and hose stream demand are in compliance with Branch line diameters comply with ESFR sprinklers protection design is in accordance with Table The number of ESFR sprinkler for most hydraulically demanding design area and the number of branch lines calculated complies with ESFR sprinklers installed above and below obstructions are hydraulically calculated in accordance with , Page 5 of 10

6 RACK STORAGE OF COMMODITIES: 77. Structural columns that are within storage racks are protected when required by Solid shelving with an area of 20 sq. ft. up to 64 sq. ft., is protected by automatic sprinklers in accordance with Solid shelving with an area exceeding 64 sq. ft. or the storage level exceeds 6 ft. with solid shelves; sprinkler protection is in compliance with Where in-rack sprinklers protect a higher commodity hazard and the rack contains mixed commodities the in-rack sprinkler design shall comply with When required horizontal barriers within the rack shall comply with section For storage 25 ft. or less a longitudinal flue is not required in double and multi-row racks so long as solid shelves are not present. Transverse flues required in single, double, and multi-row racks are provided and detailed or noted, RACK STORAGE OF CLASS I THROUGH IV COMMODITIES STORED UP TO 25 FT.: 83. The density/area design for miscellaneous storage is in accordance with The density/area design for storage exceeding the height of miscellaneous storage is in accordance with The sprinkler design for single or double-row racks is derived from Table using Figures (a)-(g), If aisles are less than 3.5 ft. consider the racks as multiple-row racks. 87. The sprinkler design for multiple-row racks 16 ft. or less in depth and with aisles 8 ft. or wider is derived from Table using Figures (a)-(g), The sprinkler design for multiple-row racks more than 16 ft in depth and with aisles less than 8 ft. is derived from Table using Figures (a)-(g), If the design density curve requirements are adjusted, the designer provided calculations explaining how the design area adjustments were made in accordance with Hose stream demands were added to the hydraulic calculations in accordance with Table Large drop and specific application control mode sprinklers shall be calculated is in accordance with Table (a) or (b), When in-rack sprinklers are required by Table (a) or (b) the in-rack sprinkler design criteria is in accordance with Large drop or control mode sprinklers under open wood joist construction shall operate at a minimum pressure specified in (A). 94. Large drop K-11.2 sprinklers installed in open wood joist channel construction shall comply with, (B). Page 6 of 10

7 95. The branch line diameter for pre-action automatic sprinklers shall comply with ESFR sprinkler orientation, K-factor, and minimum pressure design for single, double, and multiple-row racks without solid shelves is in accordance with Table , ESFR sprinklers are not used with solid shelves or combustible open-top cartons, The number of ESFR sprinkler for most hydraulically demanding design area and the number of calculated branch lines complies with ESFR sprinklers installed above and below obstructions are hydraulically calculated in accordance with In-rack sprinklers are provided for single and double-row racks without solid shelves when required by Table , In-rack sprinklers are provided for multiple-row rack less than 16 ft. deep and aisles 8 ft. wide or greater when required by Table , In-rack sprinklers are provided for multiple-row rack more than 16 ft. deep and aisles up to 8 ft. wide when required by Table , In-rack sprinklers for only one level are positioned at the first tier level at or above the halfway height of the storage, In-rack sprinklers for only two levels are positioned at the first tier storage level at or above 1/3 and 2/3 the height of the storage, In-rack maximum horizontal sprinkler spacing for single and double-row racks protecting nonencapsulated and encapsulated products are in accordance with In-rack maximum horizontal sprinkler spacing and area limitations for multiple-row racks protecting non-encapsulated and encapsulated products are in compliance with At least 6 in. of vertical clearance is detailed between the in-rack sprinkler deflector and the top of the tier of storage, The in-rack water demand has been calculated based on the quantity of sprinklers specified for its storage conditions in accordance with section , and the in-rack sprinkler discharge pressure is in compliance with RACK STORAGE OF PLASTICS STORED UP TO 25 FT. AND CEILING CLEARANCES UP TO 10 FT.: 109. Control mode sprinkler design for single, double, and multiple-row racks for aisles 3.5 ft. wide or greater is in accordance with the decision tree in Figure For control mode sprinklers, the ceiling water design density/area demand for Group A plastics packaged in cartons, encapsulated or not in single, double, or multiple-row racks are determined from Figures (a)-(f) and the designer has provided design rationale and plan details, For control mode sprinkler design requirements protecting plastic commodities stored in single, double, or multiple-row racks at varying heights and ceiling clearances, Figures (a) (f) have been used as specified in sections through Page 7 of 10

8 112. Large drop and specific control mode sprinkler design quantity and minimum operating pressure for single, double, and multiple-row racks without solid shelves for unexpanded plastics is as specified in Tables (a) or (b) and when required in-rack sprinklers are hydraulically designed and positioned in accordance with , Large drop K-11.2 sprinklers positioned under open wood joist construction operate at a minimum pressure specified in ESFR sprinkler orientation, K-factor, and minimum pressure design for single, double, and multiple-row racks without solid shelves for plastics are in accordance with Table , ESFR sprinklers are not used with solid shelves or combustible open-top cartons, The number of ESFR sprinkler for most hydraulically demanding design area and the number of branch calculated lines complies with ESFR sprinklers installed above and below obstructions are hydraulically calculated in accordance At least 6 in. of vertical clearance is provided between the in-rack sprinkler deflector and the top of the tier of storage, In-rack sprinklers are provided for single and double-row racks without solid shelves when required by Table , In-rack horizontal sprinkler spacing is provided and detailed on the plans as specified in Figures (a) and (f), The in-rack water demand calculations are provided and based on the number of sprinklers for each tier and the discharge pressure complies with Page 8 of 10

9 Page 9 of 10

10 Page 10 of 10

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13? NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued

More information

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2)

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Formally part of NFPA 231 12.2.1 General 12.2.2 Protection of Class I - IV Commodities 12.2.3 Protection of Plastic & Rubber Commodities

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12 Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.

More information

AON SPRINKLER CERTIFICATION

AON SPRINKLER CERTIFICATION Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or

More information

Warehouse Checklist. Warehouse Construction

Warehouse Checklist. Warehouse Construction PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage

More information

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

FIRE SPRINKLER SYSTEM DESIGN, ENGINEERING EXEMPTION POLICY FOR (Effective April 1, 2006)

FIRE SPRINKLER SYSTEM DESIGN, ENGINEERING EXEMPTION POLICY FOR (Effective April 1, 2006) State of Tennessee Department of Commerce and Insurance Board of Architectural and Engineering Examiners 500 James Robertson Parkway Nashville, TN 37243 1142 800 256 5758 615 741 3221 (Nashville Area)

More information

FireLock LP-46 Storage Sprinkler V4601 Pendent FM Approved, culus Listed See Submittal Publication 40.95

FireLock LP-46 Storage Sprinkler V4601 Pendent FM Approved, culus Listed See Submittal Publication 40.95 .61 FireLock Storage Design Guide This Firelock Storage Design Guide (the "Guide") illustrates the performance characteristics of the full offering of Victaulic Storage s based upon selected design criteria

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

HIGH-PILED COMBUSTIBLE STORAGE

HIGH-PILED COMBUSTIBLE STORAGE CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION 2301 GENERAL 2301.1 Scope. High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the

More information

HIGH-PILED COMBUSTIBLE STORAGE

HIGH-PILED COMBUSTIBLE STORAGE CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION FC 2301 GENERAL 2301.1 Scope. This chapter shall govern high-piled combustible storage, and the design, installation, operation and maintenance of any

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration

Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration Balanced Risk Engineering Solutions Storage Fires Understanding the Risk Many of the most costly fires occur in warehouses and storage areas, where often a high fire risk is combined with high values and/or

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes. 1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,

More information

Extended Coverage Sprinklers

Extended Coverage Sprinklers Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible

More information

Risk Guidance Note 03. Management of In-Rack Automatic Sprinklers (IRAS)

Risk Guidance Note 03. Management of In-Rack Automatic Sprinklers (IRAS) Risk Guidance Note 03 Management of In-Rack Automatic Sprinklers (IRAS) Overview In-rack automatic sprinklers (IRAS) are often a fundamental part of the fire protection solution for racked storage areas.

More information

Automatic Fire Sprinkler System Checklist

Automatic Fire Sprinkler System Checklist Fire Prevention rd Location: 701 E. 3 Avenue Mail to: P.O. Box 1579 Moses Lake, WA 98837 (509) 765-2204 www.ci.moses-lake.wa.us Automatic Fire Sprinkler System Checklist Please print in Black or Blue ink

More information

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

Certification: Building Plans Examiner. Exam ID: B3

Certification: Building Plans Examiner. Exam ID: B3 Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire

More information

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Waste Treatment and Immobilization Plant (WTP) Project U.S. Department

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional

More information

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

WINDOW AND DOOR REPLACEMENT REQUIREMENTS

WINDOW AND DOOR REPLACEMENT REQUIREMENTS WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.

More information

EFSN Training i Module 1. 90 Minutes

EFSN Training i Module 1. 90 Minutes Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler

More information

F.Y.I. Specifying Fire Protection Systems Using Division 13

F.Y.I. Specifying Fire Protection Systems Using Division 13 F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

Bath Planning Guidelines With Access Standards

Bath Planning Guidelines With Access Standards Bath Planning Guidelines With s 1: Door/Entry The clear opening of a doorway should be at least 32. This would require a minimum 2-10 door. If the existing structure precludes changing the opening then

More information

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE

More information

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire

More information

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:

More information

National Archives and Records Administration (NARA) Facility Standards for Federal Records Storage Facilities

National Archives and Records Administration (NARA) Facility Standards for Federal Records Storage Facilities National Archives and Records Administration (NARA) Facility Standards for Federal Records Storage Facilities A quick overview of what Federal Records Officers need to know about: What the Records Storage

More information

#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist

#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist #506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the

More information

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013 Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have

More information

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM

More information

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44

More information

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations

More information

City of Elk River BASEMENT Office Use Only

City of Elk River BASEMENT Office Use Only City of Elk River BASEMENT Office Use Only Fire and Building Safety Division (FABS) Building Permit Application Notes Scan Permit Total Date Permit # PID # $ Site Address Suite/Unit Structure Type Single

More information

HATFIELD TOWNSHIP DRY CLEANING PLANT PERMIT APPLICATION PROCEDURES

HATFIELD TOWNSHIP DRY CLEANING PLANT PERMIT APPLICATION PROCEDURES HATFIELD TOWNSHIP DRY CLEANING PLANT PERMIT APPLICATION PROCEDURES A Dry Cleaning Plant Operational Permit is required to engage in the business of dry cleaning or to change to a more hazardous cleaning

More information

Walking and Working Surface Checklist:

Walking and Working Surface Checklist: Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:

More information

Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

Single Family Residential Basement Finish

Single Family Residential Basement Finish How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete

More information

The following definitions apply with regard to requirements specified in this document:

The following definitions apply with regard to requirements specified in this document: GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved

More information

CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST

CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST CITY OF BERKELEY DETAILED CHECKLIST This checklist will assist you in preparing plans for submittal with a building permit application. Alterations, additions and remodeling projects may not require all

More information

Builder Specifications for Solar Ready Homes

Builder Specifications for Solar Ready Homes Builder Specifications for Solar Ready Homes This document specifies the essential elements required to make a new home ready for the future installation of roof-mounted solar domestic hot water and photovoltaic

More information

Errata has been identified as follows:

Errata has been identified as follows: 2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page

More information

CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau

CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction

More information

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for

More information

The replacement or modification of existing windows shall comply with the following requirements:

The replacement or modification of existing windows shall comply with the following requirements: City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)

More information

The Accord on Fire and Building Safety in Bangladesh Building Standard

The Accord on Fire and Building Safety in Bangladesh Building Standard The Accord on Fire and Building Safety in Bangladesh Building Standard December 30, 2013 TABLE OF CONTENTS 1 Part 1 Scope and Definitions... 1 2 Part 2 Administration and Enforcement... 5 3 Part 3 General

More information

city of edmonds development information

city of edmonds development information #B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit

More information

Errata NFPA 1. Fire Code. 2015 Edition

Errata NFPA 1. Fire Code. 2015 Edition Errata NFPA 1 Fire Code 2015 Edition Reference: 2.2, Table 6.1.14.4.1(a) and (b), 13.3.1.6, 13.7.2.13.2.1, 14.11.3.3, 18.5.2, 18.5.3, 20.1.2, 20.1.5.12, 25.1.1, 25.3, 25.4, A.3.3.164.2, and A.13.3.2.9.1

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

How To Build A Basement House

How To Build A Basement House Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International

More information

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

In accordance with NFPA 30, these containers are not to store Class I flammable liquids. In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing

More information

(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark

(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This

More information

Exhaust Calculation Booklet

Exhaust Calculation Booklet Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: techsupport@amdry.com ADC Part No. 450450 Exhaust

More information

Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet

Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet 1. Definitions a. AHJ Authority Having Jurisdiction. The Fire Chief or Fire Marshal of a given Fire District

More information

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-

More information

Installation Instructions

Installation Instructions Installation Instructions Pedestal Models FS 500 LE FS 800 LE Insert Models IS 500 LE IS 800 LE Pecan Engineering Pty Ltd 13 Acorn Road Dry Creek South Australia 5094 Email info@pecan-eng.com.au Phone:

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

Residential Decks. Planning and Development Services Department

Residential Decks. Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks

More information

SECTION 15410 GROUND WATER STORAGE TANKS

SECTION 15410 GROUND WATER STORAGE TANKS SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design

More information

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

C I T Y O F S E L M A F I R E D E P A R T M E N T

C I T Y O F S E L M A F I R E D E P A R T M E N T C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

IBC Tote Containment Sumps

IBC Tote Containment Sumps IBC Tote Containment Sumps DENIOS Provides More Models- and More Variety of IBC Totes Sumps than any other Manufacturer Painted, Galvanized, Stainless Steel, and Poly models available Models provide storage

More information

HATFIELD TOWNSHIP. FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES

HATFIELD TOWNSHIP. FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES HATFIELD TOWNSHIP FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES A flammable and combustible liquids permit is required to store, transport on site, dispense, use or handle flammable and

More information

Basement Development Construction requirements for the development of basements in residential dwellings.

Basement Development Construction requirements for the development of basements in residential dwellings. PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Basement Development Construction requirements for the development of basements in residential dwellings. June 2009 contents GENERAL INFORMATION 3 BUILDING

More information

Number of Sides Required to Have a Handrail

Number of Sides Required to Have a Handrail Excerpt from 2012 B.C. Building Code HANDRAILS & GUARDS 9.8.7. Handrails 9.8.7.1. Required Handrails 1) Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and ramps in accordance

More information