9. Shear Lug Design. 8.2 Calculating Resisting Friction Force The resisting friction force, V f, may be computed as follows: V f.
|
|
- Sarah Lyons
- 7 years ago
- Views:
Transcription
1 TECHNICAL CORRECTION October 2006 PIP STE05121 Anchor Bolt Design Guide will develop friction even when the column or vertical vessel is uplift. This downward load can be considered calculatg frictional resistance. Care shall be taken to assure that the downward load that produces frictional resistance occurs simultaneously with the shear load. In resistg horizontal loads, the friction resistance attributable to downward force from overturng moment may be used. The frictional resistance can also be used combation with shear lugs to resist the factored shear load. The frictional resistance should not be used combation with the shear resistance of anchors unless a mechanism exists to keep the base plate from slippg before the anchors can resist the load (such as weldg the washer to the base plate). Note: If the PIP design STE05121 requires weldg the washer to the base plate, pla washers Anchor steel Bolt Design plate (rather Guide than hardened washers) must be specified PIP - to Oct ensure 2006 that a good weld can be produced. 8.2 Calculatg Resistg Friction Force The resistg friction force, V f, may be computed as follows: V f P μ = μp 9. Shear Lug Design Shear Lug Verification Example = normal compression force = coefficient of friction The materials used and the embedment depth of the base plate determe the value of the coefficient of friction. (Refer to Figure F for a pictorial representation.) a. μ = 0.90 for concrete placed agast as-rolled steel with the contact plane a full plate thickness below the concrete surface. b. μ = 0.70 for concrete or grout placed agast as-rolled steel with the contact plate cocidental with the concrete surface. c. μ = 0.55 for grouted conditions with the contact plane between grout and as-rolled steel above the concrete surface. Normally, friction and the shear capacity of the anchors used a foundation adequately resist column base shear forces. In some cases, however, the engeer may fd the shear force too great and may be required to transfer the excess shear force to the foundation by another means. If the total factored shear loads are transmitted through shear lugs or friction, the anchor bolts need not be designed for shear. A shear lug (a plate or pipe stub section, welded perpendicularly to the bottom of the base plate) allows for complete transfer of the force through the shear lug, thus takg the shear load off of the anchors. The bearg on the shear lug is applied only on the portion of the lug adjacent to the concrete. Therefore, the engeer should disregard the portion of the lug immersed the top layer of grout and uniformly distribute the bearg load through the remag height. Process Industry Practices Page 19 of 24
2 PIP STE05121 TECHNICAL CORRECTION Anchor Bolt Design Guide October 2006 The shear lug should be designed for the applied shear portion not resisted by friction between the base plate and concrete foundation. Grout must completely surround the lug plate or pipe section and must entirely fill the slot created the concrete. When usg a pipe section, a hole approximately 2 ches diameter should be drilled through the base plate to the pipe section to allow grout placement and spection to assure that grout is fillg the entire pipe section. 9.1 Calculatg Shear Load Applied to Shear Lug The applied shear load, V app, used to design the shear lug should be computed as follows: V app = V ua - V f 9.2 Design Procedure for Shear Lug Plate Design of a shear lug plate follows (for an example calculation, see Appendix Example 3, this Practice): a. Calculate the required bearg area for the shear lug: A req = V app / (0.85 * φ * fc ) φ = 0.65 b. Determe the shear lug dimensions, assumg that bearg occurs only on the portion of the lug below the grout level. Assume a value of W, the lug width, on the basis of the known base plate size to fd H, the total height of the lug, cludg the grout thickness, G: H = (A req /W) + G c. Calculate the factored cantilever end moment actg on a unit length of the shear lug: M u = (V app /W) * (G + (H-G)/2) d. With the value for the moment, the lug thickness can be found. The shear lug should not be thicker than the base plate: t = [(4 * M u )/(0.9*f ya )] 0.5 e. Design weld between plate section and base plate. f. Calculate the breakout strength of the shear lug shear. The method shown as follows is from ACI , Appendix B, section B.11: V cb = A Vc *4*φ*[f c ] 0.5 where A Vc = the projected area of the failure half-truncated pyramid defed by projectg a 45-degree plane from the bearg edges of the shear lug to the free edge. The bearg area of the shear lug shall be excluded from the projected area. φ = concrete strength reduction factor = 0.85 Page 20 of 24 Process Industry Practices
3 TECHNICAL CORRECTION October 2006 PIP STE05121 Anchor Bolt Design Guide Example 3 - Shear Lug Plate Section Design PLAN V = 40 K u (ULTIMATE) SECTION Process Industry Practices Page A-25
4 TECHNICAL CORRECTION October 2006 PIP STE05121 Anchor Bolt Design Guide EXAMPLE 3 - Shear Lug Plate Section Design Design a shear lug plate for a 14-. square base plate, subject to a factored axial dead load of 22.5 s, factored live load of 65 s, and a factored shear load of 40 s. The base plate and shear lug have f ya = 36 and f c ' = 3. The contact plane between the grout and base plate is assumed to be 1. above the concrete. A 2-ft 0-. square pedestal is assumed. Ductility is not required. V app = V ua V f = 40 (0.55)(22.5) = 27.6 s Bearg area = A req = V app / (0.85 φ f c ') = 27.6 s / (0.85*0.65*3 ) = On the basis of base plate size, assume the plate width, W, will be 12. Height of plate = H = A req / W + G = / = Use 3. Ultimate moment = M u = (V app / W) * (G + (H G)/2) = (27.6 s / 12.) * (1. + (3.-1.)/2) = 4.61 k-. /. Thickness = t = [(4 * M u )/(φ* f ya )] ½ = ((4* )/(0.9*36 )) ½ = Use This 12-. x 3-. x plate will be sufficient to carry the applied shear load and resultg moment. Design of the weld between the plate section and the base plate is left to the engeer. Check concrete breakout strength of the shear lug shear. Distance from shear lug to edge of concrete = ( ) / 2 = A V = 24 * ( ) (12 * 2) = V cb = A Vc *4*φ*[f c '] 0.5 = 303 * 4 * 0.85 * [3000] 0.5 = lb = 56.4 s > 27.3 s Process Industry Practices Page A-26
5 Engeer: Javier Encas, PE GEOMETRY Column Section... W8X31 Width Length Column... Plate... Concrete Support Wp1 Wp2 Rod Offset... Thickness of Grout Lp Lp FACTORED LOADS (LRFD) Vertical Load P... Bendg Moment M... Horizontal Load V... Design Eccentricity e Design Eccentricity Is < L/6 MATERIALS Plate Steel Strength Fy... Pier Concrete Strength f'c k-ft Cantilever Model Bearg Stress fp... Critical Long m Critical Short n Plate Thickness tp AXIALLY LOADED PLATES Thornton Model Bearg Strength ϕfp... Critical Int λn'. Design Plate... Plate Thickness tp k-/ Blodgett Method Max. Bearg Stress fp... Critical Section Critical Section Moment due to Rod Tension Design Plate... Plate Thickness tp BASE PLATES WITH MOMENT k-/ k-/ k-/ DeWolf Method Max. Bearg Stress fp... Critical Section Critical Section Moment due to Rod Tension Design Plate... Plate Thickness tp k-/ k-/ k-/ 1
6 Engeer: Javier Encas, PE ANCHORAGE DESIGN Rod Material Specification... F (4) Rods, fya = 36.0, futa = 58.0 Anchor Rod Size.. 1" diam. x 12.0 emb. Concrete Is Uncracked at Service Load Level Tension Analysis () Total Tension Force Nug... Tension Force per Rod Nui... No Reforcg Bars Provided Failure Mode ϕ Nn Nu / ϕnn Steel Strength Nsa Rebars Strength Nrg 0.75 N.A. N.A. Conc. Breakout Ncbg Pullout Strength Npn Side Blowout Nsbg 0.70 N.A. N.A. Nu / ϕnn Tension Design Ratio... 0 SUMMARY OF RESULTS Design Plate... Plate Thickness tp... Max. Bearg Stress fp... Bearg Strength ϕfp... fp / ϕfp Design Ratio... DESIGN IS DUCTILE k-/ 4 Shear Analysis () Shear Taken by Shear Lug + Friction Total Shear Force V... 4 Compression Force C... Friction Coefficient... Friction Strength ϕfr... V / ϕfr Shear Friction Ratio... Shear Force Lug... Shear Lug Width Wl... Shear Lug Height Hl... Shear Lug Thickness tl Failure Mode ϕ Vn Vu / ϕvn Conc. Bearg Vcbr Conc. Breakout Vcb V / ϕvn Shear Design Ratio Steel design... Base plate design... Anchorage design... DESIGN CODES AISC (14th Ed.) AISC Design Series # 1 ACI Appendix D 2
7 Engeer: Javier Encas, PE Tension Breakout Shear Breakout 3
8 Engeer: Javier Encas, PE Column Section... Vertical Load P... Width Length Bendg Moment M... k-ft Column... Horizontal Load V... Plate... Design Eccentricity e... Concrete Support Wp1 Wp2 Lp1 Lp2 Design Eccentricity Is < L/6 Rod Offset... Thickness of Grout... Plate Steel Strength Fy... Pier Concrete Strength f'c Bearg stress 22.5 / (14.0 * 14.0) = 0.1 Bearg strength = 0.85 * 3.0 * = 4.4 ACI Under-strength factor ϕ = 0.65 ACI Bearg strength ratio = = * 2.8 = 4 < 1.0 Critical section m = Critical section n = [ 0.5 * ( *8.0) = 3.2 AISC-DG# * ( *8.0) = * 8.0 * 8.0 ] * 4 = 4 AISC-DG# ( )² = + - = 0.20 = = 2.0 Controllg section Plate moment Max (3.2, 3.8, 0.20 * 2.0) = * 3.8² / 2 = 0.8 k-/ Plate thickness = 3.8 * = 0.32 AISC-DG#
9 Engeer: Javier Encas, PE Eccentricity * 12 / 22.5 = < L / 6 = 14.0 / 6 = 2.3 Max bearg stress = * * * * 14.0² = 0.1 M bearg stress = = * * * * 14.0² = 0.1 Bearg at critical section / 14.0 * ( ) = 0.1 Moment due to bearg Mb = 0.1 * 3.2² / 2 * ( ) * 3.2² / 3 = 0.6 k-/ Plate thickness = = 0.27 AISC-DG#
10 Engeer: Javier Encas, PE Rod Material Specification... Anchor Rod Size... 1" diam. x 12.0 emb., Total tension force Nu =, F , Use (4) Rods, fya = 36.0, futa = 58.0 Ase = 0.61 ², Abrg = 1.50 ² # of tension rods = 0, Tension force per rod Nui = ACI D.5 - Steel strength of anchors tension ACI D.5.1 Steel strength * 58.0 = 35.1 ACI Eq. (D-2) Under-strength factor ϕ = 0.75 Steel strength ratio = = 0.75 * 35.1 ACI D.4.3 = 0 < 1.0 ACI D Concrete breakout strength of anchors tension ACI D.5.2 No Reforcg Bars Provided Effective embedment / 1.5 = ACI D Anchor group area Anc = ( ) * ( ) = ² ACI D Sgle anchor area 9 * (11.7)² = ² Eq. (D-5) Sgle anchor strength = 24 = 52.4 Eq. (D-6) Eccentricity factor 1.00 (No eccentric load) ACI D Edge effects factor = = 0.81 ACI D * 11.7 Crackg factor 1.25 (Uncracked concrete at service load level) ACI D Breakout strength * 0.81 * 1.25 * 52.4 = 25.0 Eq. (D-4) Under-strength factor ϕ = 0.70 Breakout strength ratio = = 0.70 * 25.0 ACI D.4.3 = 0 < 1.0 ACI D Breakout strength ratio controls (0 < 0) ACI D Concrete pullout strength of anchors tension ACI D.5.3 Sgle anchor strength 8 * 1.50 * 3.0 = 36.0 ACI Eq. (D-14) Crackg factor 1.25 (Uncracked concrete at service load level) ACI D Pullout strength 1.25 * 36.0 = 50.4 ACI Eq. (D-13) Under-strength factor ϕ = 0.70 Pullout strength ratio = = 0.70 * 50.4 ACI D.4.3 = 0 < 1.0 ACI D
11 Engeer: Javier Encas, PE - Concrete side-face blowout strength of anchors tension ACI D.5.4 Side-face blowout Nsbg = N.A. (Embed < 2.5 Ca₁, 12.0 < 2.5 * 6.5 = 16.3) ACI D Tension Design Ratio = = 0 < 1.0 ACI D Shear resisted by Shear Lug + Friction Total shear force Vu = 4, Compression force C = 22.5, Friction coeff. = 0.20 ACI D.5 Friction strength Friction strength ratio = = 0.75 * 22.5 * 0.20 = = 1.00 <= * 3.4 Shear lug width Wl = 12.0, Shear lug height Hl = 3.0, Shear lug thickness tl = Steel strength of lug flexure Lug moment 36.6 * (1.0 + ( ) / 2) = 73.3 k- Lug flexural strength 12.0 * 36 * 1.0 ² / 4 = k- AISC F.11 Under-strength factor ϕ = 0.90 AISC F.1 Flexural strength ratio = = - Steel strength of lug shear Shear force lug * = 36.6 = 0.75 < 1.0 AISC B3.4 Lug shear strength 0.6 * 36 * 12.0 * 1.0 = AISC Eq. (G2.1) Under-strength factor ϕ = 0.90 AISC G.1 Shear strength ratio = = - Weld strength shear lug * = 0.16 < 1.0 AISC B3.4 Shear lug fillet weld size a = ) (M size = ) NG AISC J2.2a Shear per unit width Tension per unit width 36.6 / (2 * 12.0) = / [( * / 3) * 12.0] = 5.2 Resultant per lug width R = = = Weld stress 0.6 * 70 * ( ) = 63.0 AISC Eq. (J2.5) Weld strength Under-strength factor ϕ = 0.75 Weld strength ratio = = - Concrete bearg strength of lug shear Lug bearg area 63.0 * * * 2 * 12.0 = * AISC J3b.4 = 0.65 < 1.0 AISC B3.3 ( ) * = 24.0 ² Lug bearg strength 1.3 * 3.0 * 24.0 = 93.6 ACI 349 D.4.6 Under-strength factor ϕ = 0.65 ACI Bearg strength ratio = = * 93.6 = 0.60 < 1.0 ACI
12 Engeer: Javier Encas, PE - Concrete breakout strength of lug shear ACI 349 D.11.2 Lug breakout area Avc = ( ) * ( ) = ² Breakout strength = * 4 = 57.8 Under-strength factor ϕ = 0.75 Breakout strength ratio = = * 57.8 ACI D.4.3 = 0.84 < 1.0 ACI D Shear Design Ratio = = 0.84 < 1.0 ACI D Anchorage design is ductile Steel design... Base plate design... Anchorage design... AISC (14th Ed.) AISC Design Series # 1 ACI Appendix D 5
Steel Design Guide Series. Column Base Plates
Steel Design Guide Series Column Base Plates Steel Design Guide Series Column Base Plates Design of Column Base Plates John T. DeWolf Professor of Civil Engineering University of Connecticut Storrs, Connecticut
More informationGuide to the Concrete Capacity Design (CCD) Method Embedment Design Examples
ACI 349.2R-07 Guide to the Concrete Capacity Design (CCD) Method Embedment Design Examples Reported by ACI Committee 349 Ronald J. Janowiak Chair Omesh B. Abhat Werner Fuchs Christopher Heinz * Richard
More informationTZ WEDGE ANCHOR FOR CRACKED AND UNCRACKED CONCRETE
SECTION 2.2 PAGE 1 / 9 l DESCRIPTION UCAN TZ torque controlled mechanical expansion wedge anchors have a Category 1 classification. They are used to resist static, wind and seismic tension and shear loads
More informationTechnical Notes 3B - Brick Masonry Section Properties May 1993
Technical Notes 3B - Brick Masonry Section Properties May 1993 Abstract: This Technical Notes is a design aid for the Building Code Requirements for Masonry Structures (ACI 530/ASCE 5/TMS 402-92) and Specifications
More informationConcrete Design Manual
The Reinforced Concrete Design Manual In Accordance with ACI 318-11 SP-17(11) Vol 2 ACI SP-17(11) Volume 2 THE REINFORCED CONCRETE DESIGN MANUAL in Accordance with ACI 318-11 Anchoring to concrete Publication:
More informationCivilBay Anchor Bolt Design Software Using ACI 318-14 and CSA A23.3-14 Code
CivilBay Anchor Bolt Design Software Using ACI 318-14 and CSA A23.3-14 Code http://asp.civilbay.com CivilBay anchor bolt design software http://asp.civilbay.com is a complete anchorage design software
More informationRISABase. Rapid Interactive Structural Analysis Base Plate and Anchorage Analysis & Design. Version 2.1 - General Reference
RISABase Rapid Interactive Structural Analysis Base Plate and Anchorage Analysis & Design Version 2.1 - General Reference 26632 Towne Centre Drive, Suite 210 Foothill Ranch, California 92610 (949) 951-5815
More informationBasics of Reinforced Concrete Design
Basics of Reinforced Concrete Design Presented by: Ronald Thornton, P.E. Define several terms related to reinforced concrete design Learn the basic theory behind structural analysis and reinforced concrete
More informationHilti KWIK HUS-EZ I (KH-EZ I) Internally Threaded Carbon Steel Screw Anchor
Hilti KWIK HUS-EZ I (KH-EZ I) Internally Threaded Carbon Steel Screw Anchor Supplement to Hilti North American Product Technical Guide Volume 2: Anchor Fastening Technical Guide 2011 Edition 3.3. KWIK
More informationHUS-H Screw Anchor. Technical data. Seismic design data. HUS-H Carbon steel screw anchor. HUS-H diameter 8, 10, 14. Seismic design data
Technical data HUS-H Carbon steel screw anchor HUS-H diameter 8, 10, 14 10 / 011 Version 011-10 1 HUS-H screw anchor seismic design data Anchor version Carbon steel screw Benefits - Quick and easy setting
More informationSPECIFICATIONS, LOADS, AND METHODS OF DESIGN
CHAPTER Structural Steel Design LRFD Method Third Edition SPECIFICATIONS, LOADS, AND METHODS OF DESIGN A. J. Clark School of Engineering Department of Civil and Environmental Engineering Part II Structural
More informationSLAB DESIGN. Introduction ACI318 Code provides two design procedures for slab systems:
Reading Assignment SLAB DESIGN Chapter 9 of Text and, Chapter 13 of ACI318-02 Introduction ACI318 Code provides two design procedures for slab systems: 13.6.1 Direct Design Method (DDM) For slab systems
More informationDraft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI 318-14
Draft Table of Contents Building Code Requirements for Structural Concrete and Commentary ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318 14) Chapter 1 General 1.1 Scope of ACI 318
More informationThank you for joining our live webinar today. We will begin shortly. Please standby. Thank you. Need Help? Call ReadyTalk Support: 800.843.
Thank you for joining our live webinar today. We will begin shortly. Please standby. Thank you. Need Help? Call ReadyTalk Support: 800.843.9166 Today s audio will be broadcast through the internet. Alternatively,
More informationSubmittal Information
Wedge SPECIFIED FOR ANCHORAGE INTO CONCRETE Wedge anchs feature a stainless steel expansion clip, threaded stud body, nut and washer. Anch bodies are made of plated carbon steel, hot-dipped galvanized
More informationThe following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.
The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16. Please refer to the publication in its entirety for complete details on this product
More informationFOOTING DESIGN EXAMPLE
County: Any Design: BRG Date: 10/007 Hwy: Any Ck Dsn: BRG Date: 10/007 FOOTING DESIGN EXAMPLE Design: Based on AASHTO LRFD 007 Specifications, TxDOT LRFD Bridge Design Manual, and TxDOT Project 0-4371
More informationResidential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
More informationHilti, Inc. 5400 South 122 nd East Avenue Tulsa, OK 74146. 1-800-879-8000 www.hilti.com
Attached are page(s) from the 2014 Hilti North American Product Tech Guide. For complete details on this product, including data development, product specifications, general suitability, installation,
More informationFOUNDATION DESIGN. Instructional Materials Complementing FEMA 451, Design Examples
FOUNDATION DESIGN Proportioning elements for: Transfer of seismic forces Strength and stiffness Shallow and deep foundations Elastic and plastic analysis Foundation Design 14-1 Load Path and Transfer to
More informationDetailing of Reinforcment in Concrete Structures
Chapter 8 Detailing of Reinforcment in Concrete Structures 8.1 Scope Provisions of Sec. 8.1 and 8.2 of Chapter 8 shall apply for detailing of reinforcement in reinforced concrete members, in general. For
More informationHilti, Inc. 5400 South 122 nd East Avenue Tulsa, OK 74146. 1-800-879-8000 www.hilti.com
Attached are page(s) from the 2014 Hilti North American Product Tech Guide. For complete details on this product, including data development, product specifications, general suitability, installation,
More informationSTRUCTURAL CALCULATIONS Pipe Supports and AST Anchorage
STRUCTURAL CALCULATIONS Pipe Supports and AST Anchorage Riverside Transit Agency 1825 E. 3 rd Street Riverside, CA January 21, 2013 Project No. 12117 Prepared by: Paul Truong, P.E., Structural Engineer
More informationPage 1 of 18 28.4.2008 Sven Alexander Last revised 1.3.2010. SB-Produksjon STATICAL CALCULATIONS FOR BCC 250
Page 1 of 18 CONTENT PART 1 BASIC ASSUMPTIONS PAGE 1.1 General 1. Standards 1.3 Loads 1. Qualities PART ANCHORAGE OF THE UNITS.1 Beam unit equilibrium 3. Beam unit anchorage in front..1 Check of capacity..
More informationSystem. Stability. Security. Integrity. 150 Helical Anchor
Model 150 HELICAL ANCHOR System PN #MBHAT Stability. Security. Integrity. 150 Helical Anchor System About Foundation Supportworks is a network of the most experienced and knowledgeable foundation repair
More informationDesign of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. The design of any foundation consists of following two parts.
8.7. Design procedure for foundation The design of any foundation consists of following two parts. 8.7.1 Stability analysis Stability analysis aims at removing the possibility of failure of foundation
More information[TECHNICAL REPORT I:]
[Helios Plaza] Houston, Texas Structural Option Adviser: Dr. Linda Hanagan [TECHNICAL REPORT I:] Structural Concepts & Existing Conditions Table of Contents Executive Summary... 2 Introduction... 3 Structural
More informationNational Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination
Structural Effective Beginning with the April 2011 The structural engineering exam is a breadth and exam examination offered in two components on successive days. The 8-hour Vertical Forces (Gravity/Other)
More information1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona
for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety
More informationDesign and Construction of Cantilevered Reinforced Concrete Structures
Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-68 Design and Construction of Cantilevered Reinforced Concrete Structures
More informationICC-ES Evaluation Report
ICC-ES Evaluation Report ESR-2369 Reissued May 1, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
More information6 RETROFITTING POST & PIER HOUSES
Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This
More informationA transverse strip of the deck is assumed to support the truck axle loads. Shear and fatigue of the reinforcement need not be investigated.
Design Step 4 Design Step 4.1 DECK SLAB DESIGN In addition to designing the deck for dead and live loads at the strength limit state, the AASHTO-LRFD specifications require checking the deck for vehicular
More informationETABS. Integrated Building Design Software. Concrete Shear Wall Design Manual. Computers and Structures, Inc. Berkeley, California, USA
ETABS Integrated Building Design Software Concrete Shear Wall Design Manual Computers and Structures, Inc. Berkeley, California, USA Version 8 January 2002 Copyright The computer program ETABS and all
More informationCHAPTER J DESIGN OF CONNECTIONS
J-1 CHAPTER J DESIGN OF CONNECTIONS INTRODUCTION Chapter J of the addresses the design and heking of onnetions. The hapter s primary fous is the design of welded and bolted onnetions. Design requirements
More informationDiameter. Swift Lift Round Recess Plug. Note: The diameter of the narrow recess plug is the same as the diameter of the round recess plug.
P-5 The P-5 is hot forged from carbon steel. The formed head provis spherical seating that the Lifting Eye engages, while a disc-shaped foot is embedd in the concrete. Due to its being a forged part, the
More informationPOST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
More informationChapter 3 FOUNDATIONS AND FOUNDATION WALLS
Chapter 3 FOUNDATIONS AND FOUNDATION WALLS This chapter discusses foundations and foundation walls constructed using the two most common foundation materials concrete and masonry. Although the IRC permits
More informationSECTION 5 ANALYSIS OF CONTINUOUS SPANS DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: BRYAN ALLRED
SECTION 5 ANALYSIS OF CONTINUOUS SPANS DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: BRYAN ALLRED NOTE: MOMENT DIAGRAM CONVENTION In PT design, it is preferable to draw moment diagrams
More informationTECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION
TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006
More informationFormwork for Concrete
UNIVERSITY OF WASHINGTON DEPARTMENT OF CONSTRUCTION MANAGEMENT CM 420 TEMPORARY STRUCTURES Winter Quarter 2007 Professor Kamran M. Nemati Formwork for Concrete Horizontal Formwork Design and Formwork Design
More informationTECHNICAL MEMORANDUM SUMMARY REPORT:
Texas Transportation Institute The Texas A&M University System 3135 TAMU College Station, TX 77843-3135 979-845-6375 Fax: 979-845-6107 http://tti.tamu.edu TECHNICAL MEMORANDUM Contract No.: T4541-AO Test
More informationDESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,
DESIGN OF SLABS Dr. G. P. Chandradhara Professor of Civil Engineering S. J. College of Engineering Mysore 1. GENERAL A slab is a flat two dimensional planar structural element having thickness small compared
More informationReport on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars
Report on Wind Resistance of Signs supported by Glass Fiber Reinforced Concrete (GFRC) Pillars Prepared for US Sign and Fabrication Corporation January, 2006 SUMMARY This study found the attachment of
More informationSECTION 3 DESIGN OF POST TENSIONED COMPONENTS FOR FLEXURE
SECTION 3 DESIGN OF POST TENSIONED COMPONENTS FOR FLEXURE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: TREY HAMILTON, UNIVERSITY OF FLORIDA NOTE: MOMENT DIAGRAM CONVENTION In PT design,
More informationInternational Nursing and Rehab Center Addition 4815 S. Western Blvd. Chicago, IL
PROJECT International Nursing and Rehab Center Addition 4815 S. Western Blvd. Chicago, IL EXP. 11/30/2014 STRUCTURAL CALCULATIONS July 24, 2014 BOWMAN, BARRETT & ASSOCIATES INC. CONSULTING ENGINEERS 312.228.0100
More informationStructural Design Calculation For Pergola
Structural Design Calculation For Pergola Revision :5 Prepared by :EC Date : 8/10/009 CONTENTS 1. Introduction... Design Code and Reference 3. Design Synopsis 4. Design Parameters 4.1 Design Load. 4. Design
More informationANALYSIS FOR BEHAVIOR AND ULTIMATE STRENGTH OF CONCRETE CORBELS WITH HYBRID REINFORCEMENT
International Journal of Civil Engineering and Technology (IJCIET) Volume 6, Issue 10, Oct 2015, pp. 25-35 Article ID: IJCIET_06_10_003 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=6&itype=10
More informationCover. When to Specify Intermediate Precast Concrete Shear Walls. 10.10 Rev 4. White Paper WP004
Cover Introduction In regard to precast concrete systems, the addition of two new categories of Seismic Force Resisting Systems (SFRS) in IBC 2006 has created some confusion about whether to specify intermediate
More informationTABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.
Pages identified with the NMBS Logo as shown above, have been produced by NMBS to assist specifiers and consumers in the application of New Millennium Building Systems Deck products. Pages identified with
More information16. Beam-and-Slab Design
ENDP311 Structural Concrete Design 16. Beam-and-Slab Design Beam-and-Slab System How does the slab work? L- beams and T- beams Holding beam and slab together University of Western Australia School of Civil
More informationABSTRACT 1. INTRODUCTION 2. DESCRIPTION OF THE SEGMENTAL BEAM
Ninth LACCEI Latin American and Caribbean Conference (LACCEI 11), Engineering for a Smart Planet, Innovation, Information Technology and Computational Tools for Sustainable Development, August 3-, 11,
More informationMETHOD OF STATEMENT FOR STATIC LOADING TEST
Compression Test, METHOD OF STATEMENT FOR STATIC LOADING TEST Tension Test and Lateral Test According to the American Standards ASTM D1143 07, ASTM D3689 07, ASTM D3966 07 and Euro Codes EC7 Table of Contents
More informationSECTION 3 DESIGN OF POST- TENSIONED COMPONENTS FOR FLEXURE
SECTION 3 DESIGN OF POST- TENSIONED COMPONENTS FOR FLEXURE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: TREY HAMILTON, UNIVERSITY OF FLORIDA NOTE: MOMENT DIAGRAM CONVENTION In PT design,
More informationHPM Rebar Anchor Bolt. For bolted connections. Technical Manual. European Technical Approval ETA-02/0006. Version: Peikko Group 01/2015
HPM Rebar Anchor Bolt For bolted connections European Technical Approval ETA-02/0006 Version: Peikko Group 01/2015 Technical Manual HPM Anchor Bolt For bolted connections System benefits Standardized and
More informationChapter - 3 Design of Rectangular Beams and One-way Slabs
Rectangular Beams and One-way Slabs Page 1 of 9 Chapter - 3 Design of Rectangular Beams and One-way Slabs 12 h A 12 strip in a simply supported one-way slab h b=12 L Rectangular Beams and One-way Slabs
More informationSite Summit Tower Foundation Report
Site Summit Tower Foundation Report For: Blaine Sears Project Manager, PTC, Telecom By: Andrew P. Adams, PE Consulting Engineer Date Prepared: 7/17/15 July 17, 2015 Blaine Sears Project Manager, PTC, Telecom
More informationTECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE
TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION PART 8000 - PRECAST CONCRETE TABLE OF CONTENTS Item Number Page 8100 PRECAST CONCRETE CONSTRUCTION - GENERAL 8-3 8101 General
More informationMETHODS FOR ACHIEVEMENT UNIFORM STRESSES DISTRIBUTION UNDER THE FOUNDATION
International Journal of Civil Engineering and Technology (IJCIET) Volume 7, Issue 2, March-April 2016, pp. 45-66, Article ID: IJCIET_07_02_004 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=7&itype=2
More informationCOMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
More informationAPE T CFRP Aslan 500
Carbon Fiber Reinforced Polymer (CFRP) Tape is used for structural strengthening of concrete, masonry or timber elements using the technique known as Near Surface Mount or NSM strengthening. Use of CFRP
More informationEUROPEAN ORGANISATION FOR TECHNICAL APPROVALS
E TA TECHNICAL REPORT Design of Bonded Anchors TR 29 Edition June 27 EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS TABLE OF CONTENTS Design method for bonded anchors Introduction..4 1 Scope...2 1.1 Type
More informationDIVISION: 31 00 00 EARTHWORK SECTION: 31 63 00 BORED PILES REPORT HOLDER: HUBBELL POWER SYSTEMS, INC.
0 ICC ES Report ICC ES (800) 4 6587 (56) 699 054 www.icc es.org 000 Most Widely Accepted and Trusted ESR 794 Reissued 05/05 This report is subject to renewal 05/06. DIVISION: 00 00 EARTHWORK SECTION: 6
More informationPerformance of Existing Reinforced Concrete Columns under Bidirectional Shear & Axial Loading
Performance of Existing Reinforced Concrete Columns under Bidirectional Shear & Axial Loading Laura M. Flores University of California, San Diego REU Institution: University of California, Berkeley REU
More informationINSTRUCTIONS FOR USE
2/2013 ANCHOR BOLTS INSTRUCTIONS FOR USE - Threaded rebars ATP, AHP, AJP - Threaded high strength steel bolts ALP-L, ALP-P, AMP ATP AHP ALP-L ALP-P AMP Eurocode design according to EN1993-1-8 (2005) &
More informationStructural welding is a process by which the parts that are to be connected are heated and
CHAPTER 6. WELDED CONNECTIONS 6.1 INTRODUCTORY CONCEPTS Structural welding is a process by which the parts that are to be connected are heated and fused, with supplementary molten metal at the joint. A
More informationDesign Parameters for Steel Special Moment Frame Connections
SEAOC 2011 CONVENTION PROCEEDINGS Design Parameters for Steel Special Moment Frame Connections Scott M. Adan, Ph.D., S.E., SECB, Chair SEAONC Structural Steel Subcommittee Principal Adan Engineering Oakland,
More informationREINFORCED CONCRETE. Reinforced Concrete Design. A Fundamental Approach - Fifth Edition. Walls are generally used to provide lateral support for:
HANDOUT REINFORCED CONCRETE Reinforced Concrete Design A Fundamental Approach - Fifth Edition RETAINING WALLS Fifth Edition A. J. Clark School of Engineering Department of Civil and Environmental Engineering
More informationDesign of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig. 7.21 some of the trusses that are used in steel bridges
7.7 Truss bridges Fig. 7.21 some of the trusses that are used in steel bridges Truss Girders, lattice girders or open web girders are efficient and economical structural systems, since the members experience
More informationOptimising plate girder design
Optimising plate girder design NSCC29 R. Abspoel 1 1 Division of structural engineering, Delft University of Technology, Delft, The Netherlands ABSTRACT: In the design of steel plate girders a high degree
More informationB.TECH. (AEROSPACE ENGINEERING) PROGRAMME (BTAE) Term-End Examination December, 2011 BAS-010 : MACHINE DESIGN
No. of Printed Pages : 7 BAS-01.0 B.TECH. (AEROSPACE ENGINEERING) PROGRAMME (BTAE) CV CA CV C:) O Term-End Examination December, 2011 BAS-010 : MACHINE DESIGN Time : 3 hours Maximum Marks : 70 Note : (1)
More informationModule 5 (Lectures 17 to 19) MAT FOUNDATIONS
Module 5 (Lectures 17 to 19) MAT FOUNDATIONS Topics 17.1 INTRODUCTION Rectangular Combined Footing: Trapezoidal Combined Footings: Cantilever Footing: Mat foundation: 17.2 COMMON TYPES OF MAT FOUNDATIONS
More informationPPM High-Strength Anchor Bolt
PPM High-Strength Anchor Bolt For bolted connections Version: Peikko Group 05/2015 Technical Manual PPM High-Strength Anchor Bolt For bolted connections Standardized, tested and widely approved high-strength
More informationThe following sketches show the plans of the two cases of one-way slabs. The spanning direction in each case is shown by the double headed arrow.
9.2 One-way Slabs This section covers the following topics. Introduction Analysis and Design 9.2.1 Introduction Slabs are an important structural component where prestressing is applied. With increase
More informationMATERIALS AND MECHANICS OF BENDING
HAPTER Reinforced oncrete Design Fifth Edition MATERIALS AND MEHANIS OF BENDING A. J. lark School of Engineering Department of ivil and Environmental Engineering Part I oncrete Design and Analysis b FALL
More informationHUS-A 6 / HUS-H 6 / HUS-I 6 / HUS-P 6 Screw anchor in precast prestressed hollow core slabs
HUS-A 6 / HUS-H 6 / HUS-I 6 / HUS-P 6 Screw anchor in precast Anchor version HUS-A 6 Screw with hex head HUS-H 6 Screw with hex head HUS-I 6 Screw with hex head Benefits - Quick and easy setting - Low
More informationFero Angle Support Technology TECHNICAL REPORT. Yasser Korany, Ph.D., P.Eng. Mohammed Nazief
FAST TM SYSTEM Fero Angle Support Technology TECHNICAL REPORT Prepared by: Yasser Korany, Ph.D., P.Eng. Mohammed Nazief August 2013 Executive Summary In this report, the new angle support system developed
More informationHow to Design Helical Piles per the 2009 International Building Code
ABSTRACT How to Design Helical Piles per the 2009 International Building Code by Darin Willis, P.E. 1 Helical piles and anchors have been used in construction applications for more than 150 years. The
More informationLOAD-CARRYING CAPACITY OF AXIALLY LOADED RODS GLUED-IN PERPENDICULAR TO THE GRAIN
LOAD-CARRYING CAPACITY OF AXIALLY LOADED RODS GLUED-IN PERPENDICULAR TO TE GRAIN Prof. Dr.-Ing..J. Blaß, Dipl.-Ing. B. Laskewitz Universität Karlsruhe (T), Germany Abstract Glued-in rods have been used
More informationSEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:
SEISMIC DESIGN Various building codes consider the following categories for the analysis and design for earthquake loading: 1. Seismic Performance Category (SPC), varies from A to E, depending on how the
More informationRehabilitation of Existing Foundation Building to Resist Lateral and Vertical Loads
International Journal of Current Microbiology and Applied Sciences ISSN: 2319-7706 Volume 3 Number 12 (2014) pp. 950-961 http://www.ijcmas.com Original Research Article Rehabilitation of Existing Foundation
More informationC E L CONSULTING A D I V I S I O N O F C O N S O L I D A T E D E N G I N E E R I N G FOR THE
A D I V I S I O N O F C O N S O L I D A T E D E N G I N E E R I N G REPORT OF MAXI-BOLT ANCHOR TESTING FOR THE HANFORD RIVER PROTECTION PROJECT WASTE TREATMENT PLANT TESTING ACCORDING TO BECHTEL NATIONAL,
More informationCONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION
CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION General 7 www.meadowburke.com 877-518-7665 MB1109 CONCRETE FLOOR SLAB AND CASTING BED CONSTRUCTION Quality Construction Begins at Ground Level Everything
More informationDesign of reinforced concrete columns. Type of columns. Failure of reinforced concrete columns. Short column. Long column
Design of reinforced concrete columns Type of columns Failure of reinforced concrete columns Short column Column fails in concrete crushed and bursting. Outward pressure break horizontal ties and bend
More informationReinforced Concrete Design Project Five Story Office Building
Reinforced Concrete Design Project Five Story Office Building Andrew Bartolini December 7, 2012 Designer 1 Partner: Shannon Warchol CE 40270: Reinforced Concrete Design Bartolini 2 Table of Contents Abstract...3
More informationATLAS RESISTANCE Pier Foundation Systems
ATLAS RESISTANCE Pier Foundation Systems Foundation Repair Systems for Civil Construction Applications: Residential, Commercial, Industrial Atlas Resistance Piers have been used to restore and/or stabilize
More informationDesign for Nonstructural Components
14 Design for Nonstructural Components Robert Bachman, S.E., John Gillengerten, S.E. and Susan Dowty, S.E. Contents 14.1 DEVELOPMENT AND BACKGROUND OF THE REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS... 3
More informationOptimum proportions for the design of suspension bridge
Journal of Civil Engineering (IEB), 34 (1) (26) 1-14 Optimum proportions for the design of suspension bridge Tanvir Manzur and Alamgir Habib Department of Civil Engineering Bangladesh University of Engineering
More informationJoist. Reinforcement. Draft 12/7/02
Joist Reinforcement Draft 12/7/02 1 JOIST REINFORCING The purpose of this CSD Design Aid is to provide procedures and suggested details for the reinforcement of open web steel joists. There are three basic
More informationThe Effects of Hole Cleaning on Post-Installed Anchor Systems in Concrete
The Effects of Hole Cleaning on Post-Installed Anchor Systems in Concrete A Major Qualifying Project proposal to be submitted to the faculty of Worcester Polytechnic Institute in partial fulfillment of
More informationConnection Solutions
Connection Solutions DESIGN BUILD SYSTEM Connection Solutions for Cold formed Steel Construction Complies with; AS/NZS 4600:2005 AISI S100:2007 AS/NZ 1397 ASTM A653 DESIGN & BUILD SYSTEM FRAMECAD Construction
More informationTechnical handbook Panel Anchoring System
1 Basic principles of sandwich panels 3 Design conditions 4 Basic placement of anchors and pins 9 Large elements (muliple rows) 10 Small elements (two rows) 10 Turned elements 10 Slender elements 10 Cantilevering
More informationCE591 Fall 2013 Lecture 26: Moment Connections
CE591 Fall 2013 Lecture 26: Moment Connections Explain basic design procedure for moment (FR) connections Explain considerations for connections in momentresisting frames for seismic demands Describe problems
More informationLong-term serviceability of the structure Minimal maintenance requirements Economical construction Improved aesthetics and safety considerations
Design Step 7.1 INTEGRAL ABUTMENT DESIGN General considerations and common practices Integral abutments are used to eliminate expansion joints at the end of a bridge. They often result in Jointless Bridges
More informationTension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-02
ENGINEERING DATA REPORT NUMBER 51 Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-02 A SERVICE OF THE CONCRETE REINFORCING STEEL INSTITUTE Introduction Section 1.2.1 in the
More informationCITY OF LOS ANGELES CALIFORNIA
BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS INTERIM PRESIDENT E. FELICIA BRANNON JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI MAYOR
More informationGUIDELINES FOR TESTING FRESH SELF-COMPACTING CONCRETE
Growth Contract No. GRD2-2000-30024 GUIDELINES FOR TESTING FRESH SELF-COMPACTING CONCRETE Principal author: G. DE SCHUTTER September 2005 European Research Project: MEASUREMENT OF PROPERTIES OF FRESH SELF-COMPACTING
More information4B-2. 2. The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.
Shear Walls Buildings that use shear walls as the lateral force-resisting system can be designed to provide a safe, serviceable, and economical solution for wind and earthquake resistance. Shear walls
More informationWisconsin Building Products Evaluation
Safety & Buildings Division 201 West Washington Avenue P.O. Box 2658 Madison, WI 53701-2658 Evaluation # 200813-O Wisconsin Building Products Evaluation Material Best Management Standards for Foundation
More information