YORK LINEAR ACTIVE CHILLED BEAMS ENGINEERING GUIDE
|
|
- Leslie Stewart
- 7 years ago
- Views:
Transcription
1 YORK LINEAR ACTIVE CHILLED BEAMS ENGINEERING GUIDE
2 Contents YORK Active Chilled Beams 3 CB-ABL-YK Performance Data 5 CB-ABL-YK Dimensions 10 CB-ALV-YK Performance Data 12 CB-ALV-YK Dimensions 17 CB-ALE-YK Performance Data 18 CB-ALE-YK Dimensions 23 Specifications 24 2
3 YORK Linear Active Chilled Beams Energy Efficiency Delivered YORK linear chilled beams are the air distribution device of choice in high performing energy efficient buildings. Utilizing an integrated sensible cooling coil, active beams reduce the volume of air required for space cooling. A smaller volume of primary air minimizes energy consumed treating outdoor air and nearly eliminates energy wasted by parasitic reheat. When compared to conventional VAV systems a 30% energy savings can be realized. Superior Performance Aerodynamically designed nozzles inject conditioned primary air into the diffuser at high velocity. As the jets of air expand and slow the change in velocity creates a pressure gradient along its boundary. This pressure differential induces room air across the sensible coil within the diffuser. Using Computational Fluid Dynamics (CFD) and extensive laboratory testing the geometry of the YORK linear active chilled beams was refined to maximize induce air flow for optimal energy efficiency. CB-ABL-YK / CB-ALV-YK CB-ALE-YK Low Sound, Low Maintenance Active chilled beams utilize system pressure in their operation, eliminating fans in the space or in the ceiling plenum minimizing overall system noise. With the elimination of fans, active chilled beams have no parts to replace for maintenance. Additionally, since coils are providing sensible cooling only there are no filters to be changed nor drain pans to clean; only periodic vacuuming of the coils to remove lint and dust from the coil and general cleaning of the exposed surfaces. Linear Styling and Flexible Installations The linear design of these beams is such that they can be installed in continuous runs to become a core design feature of a space or project. Perforated or bar grille faces are available to tie into styling of the entire project. Flexible mounting methods allow for direct attachment to the building slab, suspended by hanging wire or by threaded rods. Available border types accommodate standard lay-in, narrow tee and tegular drop face ceiling systems. The CB-ALE-YK is specifically designed for exposed installations with integral coanda plates for ceiling independent air distribution. Available Models: CB-ABL-YK: Standard Linear Active Chilled Beam CB-ALV-YK: Linear Active Chilled Beam with Vertical Coils and condensate tray CB-ALE-YK: Linear Active Chilled Beam for exposed installations 3
4 Standard Features: 2 foot to 10 foot lengths, 1 foot increments Perforated or linear bar induced air grille Left hand or Right hand coil connections Side or top air inlet locations 2-pipe and 4-pipe coil configurations Configured nozzle geometry for capacity optimization Hinged induced air grille for roomside coil access Commissioning port with roomside access for balancing Mounting brackets with adjustments in two directions Durable powder coat finish White or Black ½ Sweat water coil connections Coil air vent Options and Accessories: ½ thick foil-faced external insulation Coil drain valve ½ MNPT water coil connections 12-inch, 18-inch or 24-inch stainless steel braided hoses Lay-in, narrow tee and drop face border types 4
5 CB-ABL-YK: 24-IN WIDTH: PERFORMANCE DATA (4-PIPE COOLING) Nominal Length ft Nozzle Size B2 4 B3 5 B4 6 B3 6 Primary Air Coil Sensible Cooling (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL B ,895 2,354 Induction ratio Throw , , , , ,546 2,656 ft ,594 3,222 3,486 3, ,955 2, , , , , ,627 2, ,693 3,345 3,619 3, ,240 2, , , , , ,009 3, ,096 3,846 4,160 4, ,519 3, , , , , ,384 3, ,482 4,326 4,679 4, ,335 2, , , , , ,137 3, ,241 4,026 4,355 4, ,512 3, , , , , ,375 3, ,465 4,305 4,656 4, ,946 3, , , , , ,958 4, ,051 5,031 5,443 5, ,337 4, , , , , ,484 4, ,584 5,694 6,159 6, ,431 3, , , , , ,267 3, ,591 4,461 4,825 5, ,513 3, , , , , ,376 3, ,735 4,639 5,018 5, ,933 3, , , , , ,941 4, ,350 5,404 5,845 6, ,108 3, , , , , ,176 4, ,707 5,846 6,324 6, ,538 4, , , , , ,753 4, ,889 6,073 6,569 6, ,639 4, , , , , ,890 5, ,064 6,291 6,805 7, ,388 5, , , , , ,896 6, ,037 7,499 8,111 8, ,955 6, , , , , ,658 6, ,817 8,468 9,160 9,
6 CB-ABL-YK: 24-IN WIDTH: PERFORMANCE DATA (4-PIPE HEATING) Nominal Length ft Nozzle Size B2 4 B3 5 B4 6 B3 6 Primary Air Coil Heating (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL B ,945 3,659 Induction ratio Throw , , , , ,957 4,128 ft ,033 5,009 5,418 5, ,039 3, , , , , ,084 4, ,186 5,200 5,625 5, ,482 4, , , , , ,678 4, ,813 5,978 6,466 6, ,916 4, , , , , ,261 5, ,413 6,724 7,273 7, ,107 5, , , , , ,519 5, ,702 7,083 7,661 7, ,419 5, , , , , ,938 6, ,097 7,573 8,192 8, ,183 6, , , , , ,964 7, ,126 8,852 9,575 9, ,680 7, , , , , ,632 7, ,803 9,693 10,485 10, ,278 5, , , , , ,747 5, ,318 7,848 8,489 8, ,421 5, , , , , ,940 6, ,570 8,161 8,828 9, ,161 6, , , , , ,934 7, ,653 9,506 10,283 10, ,290 6, , , , , ,108 7, ,012 9,952 10,765 11, ,224 7, , , , , ,362 8, ,601 10,684 11,557 12, ,402 7, , , , , ,602 8, ,910 11,067 11,972 12, ,720 9,589 10,372 10, , , , , ,620 13,192 14,270 14, ,435 10,478 11,334 11, , , , , ,604 14,415 15,592 16,
7 CB-ABL-YK: 24-IN WIDTH: PERFORMANCE DATA (2-PIPE COOLING) Nominal Length ft Nozzle Size B2 4 B3 5 B4 6 B3 6 Primary Air Coil Sensible Cooling (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL B ,084 2,589 Induction ratio Throw , , , , ,800 2,921 ft ,854 3,545 3,834 4, ,151 2, , , , , ,890 3, ,962 3,680 3,980 4, ,464 3, , , , , ,310 3, ,406 4,230 4,576 4, ,771 3, , , , , ,723 3, ,831 4,758 5,147 5, ,568 3, , , , , ,451 3, ,565 4,429 4,790 4, ,763 3, , , , , ,713 3, ,812 4,735 5,122 5, ,240 4, , , , , ,354 4, ,456 5,535 5,987 6, ,671 4, , , , , ,932 5, ,042 6,263 6,775 7, ,675 3, , , , , ,594 3, ,950 4,907 5,308 5, ,764 3, , , , , ,714 3, ,108 5,103 5,520 5, ,227 4, , , , , ,336 4, ,785 5,944 6,430 6, ,419 4, , , , , ,593 4, ,177 6,431 6,956 7, ,891 4, , , , , ,228 5, ,378 6,680 7,226 7, ,003 4, , , , , ,379 5, ,571 6,920 7,485 7, ,827 5, , , , , ,485 6, ,640 8,248 8,922 9, ,451 6, , , , , ,324 7, ,499 9,315 10,076 10,
8 CB-ABL-YK: 24-IN WIDTH: PERFORMANCE DATA (2-PIPE HEATING) Nominal Length ft Nozzle Size B2 4 B3 5 B4 6 B3 6 Primary Air Coil Heating (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL B ,976 4,939 Induction ratio Throw , , , , ,343 5,573 ft ,444 6,762 7,315 7, ,103 5, , , , , ,513 5, ,651 7,020 7,593 7, ,700 5, , , , , ,315 6, ,497 8,070 8,730 9, ,286 6, , , , , ,102 7, ,308 9,077 9,819 10, ,545 6, , , , , ,451 7, ,698 9,562 10,343 10, ,966 7, , , , , ,016 8, ,230 10,223 11,059 11, ,996 8, , , , , ,401 9, ,620 11,950 12,926 13, ,668 9,525 10,303 10, , , , , ,534 13,085 14,154 14, ,775 7, , , , , ,759 8, ,529 10,595 11,460 11, ,968 7, , , , , ,019 8, ,870 11,017 11,918 12, ,967 8, , , , , ,361 9, ,332 12,834 13,882 14, ,142 8, , , , , ,596 10, ,816 13,435 14,533 15, ,402 10,436 11,289 11, , , , , ,611 14,423 15,601 16, ,643 10,736 11,613 12, , , , , ,028 14,941 16,162 16, ,421 12,945 14,003 14, , , , , ,337 17,809 19,264 20, ,388 14,146 15,301 15, , , , , ,666 19,460 21,049 21,
9 NOTES: 1. All performance data based on test performed in accordance with ASHRAE Standard Inlet diameters shown are nominal. Inlet size designated with a star (*) indicates equivalent oval 3. NC values are based on room absorption of 10 db. A dash (-) indicates an NC value less than Throw values are based on isothermal supply air and represent throw distances to terminal velocities of 150, 100 and 50 fpm respectively 5. DP Coil values in shaded cells indicate use of a two circuit coil. All other values represent a single circuit coil 6. Induction ratio is multiplied by the volume flow rate of primary air to estimate the volume flow rate of room air entrained through the coil Cooling performance: - Cooling capacity listed (qcoil) is the sensible heat removal by the beam s integral coil. It does not include any contribution or offset by the primary air - Capacity is based on 18BF DT between the induced air and the chilled water supply. TABLE 4: CORRECTION FOR (DT) BETWEEN ENTERING AIR AND ENTERING CHILLED WATER Actual DT Multiply Table Value by: - Primary air sensible cooling contribution can be calculated by the following equation: qsenspa = x CFMPA x (TPA - TROOM) - Primary air latent cooling can be calculated by the following equation: qlatent = 0.69 x CFMPA x (WROOM - WPA) where WROOM and WPA are the humidity ratio of the room and primary air respectively expressed in Grains of moisture per pound dry air Heating performance: Heating capacity listed (qcoil) is the sensible heat removal by the beam s integral coil. It does not include any contribution or offset by the primary air - Capacity is based on 50BF DT between the induced air and the chilled water supply. - Primary air sensible heating offset (or contribution) can be calculated by the following equation: qsenspa = x CFMPA x (TPA - TROOM) if the primary air temperature is lower than that of the room, it will offset the coil s heating if the primary air temperature is higher than that of the room, it will contribute to the coil s heating Legend: DP S = Unit Inlet Pressure [in wg] qcoil = Sensible Capacity, Coil [Btu/h] DCoil = Water coil pressure drop [ft wg] qsenspa = Sensible Capacity, Primary Air [Btu/h] CFMPA = Air Flowrate, Primary Air [CFM] TPA = Temperature Primary Air [BF] TROOM = Temperature Room Air [BF] qsenspa = Latent Capacity, Primary Air [Btu/h] 9
10 CB-ABL-YK MODEL SPECIFIC FEATURES & OPTIONS 12 inch and 24 inch widths Condensate tray with drain connection for field plumbing (12 inch version only) DIMENSIONAL INFORMATION CB-ABL-YK (12-INCH) 10
11 DIMENSIONAL INFORMATION CB-ABL-YK (24-INCH) 11
12 CB-ALV-YK: PERFORMANCE DATA (4-PIPE COOLING) Nominal Length ft Nozzle Size B1 5 B3 6 B1 5 B1 6 B1 6 Primary Air Coil Sensible Cooling (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL ,236 2,777 Induction ratio Throw , , , , ,004 3,134 ft ,923 3,631 3,927 4, , , , , ,029 1,278 1,383 1, ,643 3, , , , , ,551 3, ,486 4,330 4,683 4, ,775 2, , , , , ,385 2, ,463 3,059 3,309 3, ,849 2, , , , , ,484 2, ,489 3,092 3,344 3, ,989 2, , , , , ,673 2, ,662 3,307 3,577 3, ,333 2, , , , , ,135 3, ,112 3,866 4,182 4, ,993 3, , , , , ,022 4, ,989 4,955 5,360 5, ,872 2, , , , , ,515 2, ,697 3,350 3,624 3, ,934 2, , , , , ,599 2, ,804 3,483 3,767 3, ,258 2, , , , , ,034 3, ,266 4,057 4,389 4, ,709 3, , , , , ,640 3, ,999 4,968 5,374 5, ,680 3, , , , , ,601 3, ,638 4,519 4,888 5, ,757 3, , , , , ,704 3, ,768 4,680 5,063 5, ,324 4, , , , , ,467 4, ,493 5,581 6,037 6, ,252 5, , , , , ,713 5, ,746 7,138 7,721 8,
13 CB-ALV-YK: PERFORMANCE DATA (4-PIPE HEATING) Nominal Length ft Nozzle Size B1 5 B3 6 B1 5 B1 6 B1 6 Primary Air Coil Heating (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL ,476 4,317 Induction ratio Throw , , , , ,670 4,872 ft ,544 5,644 6,105 6, ,154 2, , , , , ,894 3, ,984 3,707 4,010 4, ,108 5, , , , , ,520 5, ,418 6,730 7,280 7, ,705 4, , , , , ,978 5, ,140 6,384 6,906 7, ,249 5, , , , , ,709 5, ,720 7,105 7,686 8, ,571 5, , , , , ,142 6, ,118 7,599 8,220 8, ,361 6, , , , , ,204 7, ,152 8,884 9,610 10, ,861 8, , , , , ,219 9, ,145 11,359 12,287 12, ,301 5, , , , , ,779 6, ,198 7,698 8,327 8, ,445 5, , , , , ,972 6, ,443 8,004 8,658 9, ,189 6, , , , , ,972 7, ,506 9,324 10,085 10, ,210 7, , , , , ,344 8, ,168 11,388 12,318 12, ,159 7, , , , , ,275 8, ,360 10,385 11,233 11, ,335 7, , , , , ,512 8, ,659 10,755 11,634 12, ,639 9,489 10,265 10, , , , , ,325 12,825 13,872 14, ,747 12,107 13,096 13, , , , , ,172 16,362 17,698 18,
14 CB-ALV-YK: PERFORMANCE DATA (2-PIPE COOLING) Nominal Length ft Nozzle Size B1 5 B3 6 B1 5 B1 6 B1 6 Primary Air Coil Sensible Cooling (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL ,460 3,055 Induction ratio Throw , ,967 3,36 3, , ,305 3,448 ft ,215 3,994 4,320 4, , ,123 3,36 1, , ,098 1, ,132 1,406 1,521 1, ,907 3, , ,580 3,36 3, , ,906 4, ,834 4,763 5,152 5, ,953 2, , ,691 3,36 2, , ,624 2, ,709 3,365 3,640 3, ,034 2, ,112 1,31 2, , , ,733 2, ,738 3,401 3,679 3, ,188 2, ,242 1,31 2, , , ,940 3, ,928 3,638 3,935 4, ,566 3, ,611 1,31 3, , , ,448 3, ,424 4,253 4,600 4, ,292 4, ,343 1,31 4, , , ,424 4, ,388 5,451 5,896 6, ,059 2, , , , , ,766 2, ,967 3,685 3,986 4, ,128 2, , , , , ,859 2, ,084 3,831 4,144 4, ,484 3, , , , , ,337 3, ,593 4,463 4,828 5, ,980 3, , , , , ,004 4, ,399 5,465 5,911 6, ,948 3, , , , , ,961 4, ,002 4,971 5,377 5, ,033 3, , , , , ,075 4, ,145 5,148 5,569 5, ,657 4, , , , , ,913 5, ,942 6,139 6,640 6, ,677 5, , , , , ,285 6, ,321 7,852 8,493 8,
15 CB-ALV-YK: PERFORMANCE DATA (2-PIPE HEATING) Nominal Length ft Nozzle Size B1 5 B3 6 B1 5 B1 6 B1 6 Primary Air Coil Heating (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL ,692 5,829 Induction ratio Throw , , , , ,305 6,577 ft ,134 7,619 8,242 8, ,908 3, , , , , ,907 4, ,029 5,004 5,413 5, ,546 6, , , , , ,452 7, ,315 9,086 9,828 10, ,002 6, , , , , ,721 7, ,939 8,619 9,323 9, ,736 7, , , , , ,707 8, ,722 9,592 10,375 10, ,172 7, , , , , ,292 8, ,259 10,259 11,097 11, ,238 8, , , , , ,725 10, ,655 11,994 12,973 13, ,262 11,505 12,445 12, , , , , ,345 15,335 16,587 17, ,806 7, , , , , ,801 8, ,367 10,393 11,242 11, ,000 7, , , , , ,062 8, ,699 10,805 11,688 12, ,005 8, , , , , ,412 9, ,133 12,587 13,615 14, ,383 10,413 11,264 11, , , , , ,376 15,373 16,629 17, ,314 10,328 11,171 11, , , , , ,286 14,019 15,165 15, ,553 10,624 11,492 11, , , , , ,689 14,520 15,706 16, ,313 12,811 13,857 14, , , , , ,938 17,313 18,728 19, ,158 16,345 17,680 18, , , , , ,782 22,088 23,893 24,
16 NOTES: 1. All performance data based on test performed in accordance with ASHRAE Standard Inlet diameters shown are nominal. Inlet size designated with a star (*) indicates equivalent oval 3. NC values are based on room absorption of 10 db. A dash (-) indicates an NC value less than Throw values are based on isothermal supply air and represent throw distances to terminal velocities of 150, 100 and 50 fpm respectively 5. DP Coil values in shaded cells indicate use of a two circuit coil. All other values represent a single circuit coil 6. Induction ratio is multiplied by the volume flow rate of primary air to estimate the volume flow rate of room air entrained through the coil Cooling performance: - Cooling capacity listed (qcoil) is the sensible heat removal by the beam s integral coil. It does not include any contribution or offset by the primary air - Capacity is based on 18BF DT between the induced air and the chilled water supply. TABLE 4: CORRECTION FOR (DT) BETWEEN ENTERING AIR AND ENTERING CHILLED WATER Actual DT Multiply Table Value by: - Primary air sensible cooling contribution can be calculated by the following equation: qsenspa = x CFMPA x (TPA - TROOM) - Primary air latent cooling can be calculated by the following equation: qlatent = 0.69 x CFMPA x (WROOM - WPA) where WROOM and WPA are the humidity ratio of the room and primary air respectively expressed in Grains of moisture per pound dry air Heating performance: Heating capacity listed (qcoil) is the sensible heat removal by the beam s integral coil. It does not include any contribution or offset by the primary air - Capacity is based on 50BF DT between the induced air and the chilled water supply. - Primary air sensible heating offset (or contribution) can be calculated by the following equation: qsenspa = x CFMPA x (TPA - TROOM) if the primary air temperature is lower than that of the room, it will offset the coil s heating if the primary air temperature is higher than that of the room, it will contribute to the coil s heating Legend: DP S = Unit Inlet Pressure [in wg] qcoil = Sensible Capacity, Coil [Btu/h] DCoil = Water coil pressure drop [ft wg] qsenspa = Sensible Capacity, Primary Air [Btu/h] CFMPA = Air Flowrate, Primary Air [CFM] TPA = Temperature Primary Air [BF] TROOM = Temperature Room Air [BF] qsenspa = Latent Capacity, Primary Air [Btu/h] 16
17 CB-ALV-YK MODEL SPECIFIC FEATURES & OPTIONS Vertical Water Coil Condensate tray with drain connection for field plumbing DIMENSIONAL INFORMATION CB-ALV-YK 17
18 CB-ALE-YK: 24-IN WIDTH: PERFORMANCE DATA (4-PIPE COOLING) Nominal Length ft Nozzle Size B2 4 B3 5 B4 6 B3 6 Primary Air Coil Sensible Cooling (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL B ,895 2,354 Induction ratio Throw , , , , ,546 2,656 ft ,594 3,222 3,486 3, ,955 2, , , , , ,627 2, ,693 3,345 3,619 3, ,240 2, , , , , ,009 3, ,096 3,846 4,160 4, ,519 3, , , , , ,384 3, ,482 4,326 4,679 4, ,335 2, , , , , ,137 3, ,241 4,026 4,355 4, ,512 3, , , , , ,375 3, ,465 4,305 4,656 4, ,946 3, , , , , ,958 4, ,051 5,031 5,443 5, ,337 4, , , , , ,484 4, ,584 5,694 6,159 6, ,431 3, , , , , ,267 3, ,591 4,461 4,825 5, ,513 3, , , , , ,376 3, ,735 4,639 5,018 5, ,933 3, , , , , ,941 4, ,350 5,404 5,845 6, ,108 3, , , , , ,176 4, ,707 5,846 6,324 6, ,538 4, , , , , ,753 4, ,889 6,073 6,569 6, ,639 4, , , , , ,890 5, ,064 6,291 6,805 7, ,388 5, , , , , ,896 6, ,037 7,499 8,111 8, ,955 6, , , , , ,658 6, ,817 8,468 9,160 9,
19 CB-ALE-YK: 24-IN WIDTH: PERFORMANCE DATA (4-PIPE HEATING) Nominal Length ft Nozzle Size B2 4 B3 5 B4 6 B3 6 Primary Air Coil Heating (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL B ,945 3,659 Induction ratio Throw , , , , ,957 4,128 ft ,033 5,009 5,418 5, ,039 3, , , , , ,084 4, ,186 5,200 5,625 5, ,482 4, , , , , ,678 4, ,813 5,978 6,466 6, ,916 4, , , , , ,261 5, ,413 6,724 7,273 7, ,107 5, , , , , ,519 5, ,702 7,083 7,661 7, ,419 5, , , , , ,938 6, ,097 7,573 8,192 8, ,183 6, , , , , ,964 7, ,126 8,852 9,575 9, ,680 7, , , , , ,632 7, ,803 9,693 10,485 10, ,278 5, , , , , ,747 5, ,318 7,848 8,489 8, ,421 5, , , , , ,940 6, ,570 8,161 8,828 9, ,161 6, , , , , ,934 7, ,653 9,506 10,283 10, ,290 6, , , , , ,108 7, ,012 9,952 10,765 11, ,224 7, , , , , ,362 8, ,601 10,684 11,557 12, ,402 7, , , , , ,602 8, ,910 11,067 11,972 12, ,720 9,589 10,372 10, , , , , ,620 13,192 14,270 14, ,435 10,478 11,334 11, , , , , ,604 14,415 15,592 16,
20 CB-ALE-YK: 24-IN WIDTH: PERFORMANCE DATA (2-PIPE COOLING) Nominal Length ft Nozzle Size B2 4 B3 5 B4 6 B3 6 Primary Air Coil Sensible Cooling (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL B ,084 2,589 Induction ratio Throw , , , , ,800 2,921 ft ,854 3,545 3,834 4, ,151 2, , , , , ,890 3, ,962 3,680 3,980 4, ,464 3, , , , , ,310 3, ,406 4,230 4,576 4, ,771 3, , , , , ,723 3, ,831 4,758 5,147 5, ,568 3, , , , , ,451 3, ,565 4,429 4,790 4, ,763 3, , , , , ,713 3, ,812 4,735 5,122 5, ,240 4, , , , , ,354 4, ,456 5,535 5,987 6, ,671 4, , , , , ,932 5, ,042 6,263 6,775 7, ,675 3, , , , , ,594 3, ,950 4,907 5,308 5, ,764 3, , , , , ,714 3, ,108 5,103 5,520 5, ,227 4, , , , , ,336 4, ,785 5,944 6,430 6, ,419 4, , , , , ,593 4, ,177 6,431 6,956 7, ,891 4, , , , , ,228 5, ,378 6,680 7,226 7, ,003 4, , , , , ,379 5, ,571 6,920 7,485 7, ,827 5, , , , , ,485 6, ,640 8,248 8,922 9, ,451 6, , , , , ,324 7, ,499 9,315 10,076 10,
21 CB-ALE-YK: 24-IN WIDTH: PERFORMANCE DATA (2-PIPE HEATING) Nominal Length ft Nozzle Size B2 4 B3 5 B4 6 B3 6 Primary Air Coil Heating (Btu/h) Flow Sound Inlet Dia. Inlet DPS 0.5 GPM 1.0 GPM 1.5 GPM 2.0 GPM Rate NC Inches CFM (in. H2O) qcoil DCOIL qcoil DCOIL qcoil DCOIL qcoil DCOIL B ,976 4,939 Induction ratio Throw , , , , ,343 5,573 ft ,444 6,762 7,315 7, ,103 5, , , , , ,513 5, ,651 7,020 7,593 7, ,700 5, , , , , ,315 6, ,497 8,070 8,730 9, ,286 6, , , , , ,102 7, ,308 9,077 9,819 10, ,545 6, , , , , ,451 7, ,698 9,562 10,343 10, ,966 7, , , , , ,016 8, ,230 10,223 11,059 11, ,996 8, , , , , ,401 9, ,620 11,950 12,926 13, ,668 9,525 10,303 10, , , , , ,534 13,085 14,154 14, ,775 7, , , , , ,759 8, ,529 10,595 11,460 11, ,968 7, , , , , ,019 8, ,870 11,017 11,918 12, ,967 8, , , , , ,361 9, ,332 12,834 13,882 14, ,142 8, , , , , ,596 10, ,816 13,435 14,533 15, ,402 10,436 11,289 11, , , , , ,611 14,423 15,601 16, ,643 10,736 11,613 12, , , , , ,028 14,941 16,162 16, ,421 12,945 14,003 14, , , , , ,337 17,809 19,264 20, ,388 14,146 15,301 15, , , , , ,666 19,460 21,049 21,
22 NOTES: 1. All performance data based on test performed in accordance with ASHRAE Standard Inlet diameters shown are nominal. Inlet size designated with a star (*) indicates equivalent oval 3. NC values are based on room absorption of 10 db. A dash (-) indicates an NC value less than Throw values are based on isothermal supply air and represent throw distances to terminal velocities of 150, 100 and 50 fpm respectively 5. DP Coil values in shaded cells indicate use of a two circuit coil. All other values represent a single circuit coil 6. Induction ratio is multiplied by the volume flow rate of primary air to estimate the volume flow rate of room air entrained through the coil Cooling performance: - Cooling capacity listed (qcoil) is the sensible heat removal by the beam s integral coil. It does not include any contribution or offset by the primary air - Capacity is based on 18BF DT between the induced air and the chilled water supply. TABLE 4: CORRECTION FOR (DT) BETWEEN ENTERING AIR AND ENTERING CHILLED WATER Actual DT Multiply Table Value by: - Primary air sensible cooling contribution can be calculated by the following equation: qsenspa = x CFMPA x (TPA - TROOM) - Primary air latent cooling can be calculated by the following equation: qlatent = 0.69 x CFMPA x (WROOM - WPA) where WROOM and WPA are the humidity ratio of the room and primary air respectively expressed in Grains of moisture per pound dry air Heating performance: Heating capacity listed (qcoil) is the sensible heat removal by the beam s integral coil. It does not include any contribution or offset by the primary air - Capacity is based on 50BF DT between the induced air and the chilled water supply. - Primary air sensible heating offset (or contribution) can be calculated by the following equation: qsenspa = x CFMPA x (TPA - TROOM) if the primary air temperature is lower than that of the room, it will offset the coil s heating if the primary air temperature is higher than that of the room, it will contribute to the coil s heating Legend: DP S = Unit Inlet Pressure [in wg] qcoil = Sensible Capacity, Coil [Btu/h] DCoil = Water coil pressure drop [ft wg] qsenspa = Sensible Capacity, Primary Air [Btu/h] CFMPA = Air Flowrate, Primary Air [CFM] TPA = Temperature Primary Air [BF] TROOM = Temperature Room Air [BF] qsenspa = Latent Capacity, Primary Air [Btu/h] 22
23 CB-ALE-YK MODEL SPECIFIC FEATURES & OPTIONS Integral coanda plates for ceiling independent air distribution pattern 1-way or 2-way air distribution pattern DIMENSIONAL INFORMATION CB-ALE-YK 23
24 Guide Specification: CB-ABL-YK Active Chilled Beams 24-inch Width PART 1- GENERAL 1.01 Summary This section describes the active chilled beams Submittals Submit product data for all items complete with the following information: 1. Operating weights and dimensions of all unit assemblies. 2. Performance data, including sensible and latent cooling capacities, nozzle types, primary and total supply (primary plus induced) airflow rates, chilled (and where applicable hot) water flow rates, noise levels in octave bands, air and water side pressure losses and maximum discharge air throw values. 3. Construction details including manufacturers recommendations for installation, mounting and connection. PART 2- PRODUCTS 2.01 General Materials and products required for the work of this section shall not contain asbestos, polychlorinated biphenyls (PCB) or other hazardous materials identified by the engineer or owner Design 1. Furnish and install YORK CB-ABL-YK series two slot active chilled beams of sizes and capacities as indicated on the drawings and within the mechanical equipment schedules. The quantity and length of the beams shall be as shown on the drawings, without EXCEPTION. The beams shall be constructed and delivered to the job site as single units. 2. The face of the beam shall consist of a room air induction section of 50% free area perforated (optional linear bar type) induction section flanked by linear supply slots. The face section shall include hinged fastening on each side that allows the face to be swung opened from either direction for coil cleaning. Faces that are designed to be lifted out are NOT ACCEPTABLE. The entire visible face sections and all visible internal surfaces shall be finished in white powder coat paint or as specified by the architect. 3. Beams shall be provided with side and end details which will allow its integration into the applicable (nominal 24 inch wide) acoustical ceiling grid as specified by the architect. 4. The beams shall consist of a minimum 20 gauge galvanized steel housing encasing the integral sensible cooling coil and a plenum feeing a series of induction nozzles. A single duct connection shall be provided on either the side or top of the unit. The use of multiple duct connections is NOT ACCEPTABLE. 5. Each beam shall be provided with a pressure tap that may be used to measure the pressure differential between the primary air plenum and the room. Airflow calibration charts that relate this pressure differential reading with the primary and beam supply airflow rates shall be furnished with the beams. 6. Beams shall be provided with connections for either 2 or 4 pipe water connections as indicated on plans and schedules. Four pipe configurations shall require separate supply and return connections for chilled and hot water. The coil shall be mounted horizontally and shall be manufactured with seamless copper tubing (½ outside diameter) with minimum.016 inch wall thickness 24
25 mechanically fixed to aluminum fins. The aluminum fins shall be limited to no more than ten (10) fins per inch. The coil shall have a working pressure of at least 300 PSI, and be factory tested for leakage at a minimum pressure of 360 PSI. Each chilled beam shall be provided with factory integrated manual air vents. (OPTIONAL, coil shall be provided with factory integrated drain fittings.) Unless otherwise specified, coil connections shall be bare copper for field sweating to the water supply circuit. Connections shall face upwards, be located near the left end of the beam (when viewing into the primary air connection). (OPTIONAL, the chilled water coil shall be provided with NPT male threaded fittings. These fittings must be suitable for field connection to a similar NPT female flexible hose spigot and shall be at least 1½ long to facilitate field connection (by others). 7. Beams shall be delivered clean, flushed and capped to prevent ingress of dirt 2.03 Performance 1. All performance shall be in compliance with that shown on the equipment schedule. Acoustical testing shall have been performed in accordance with ASHRAE Standard Coils shall be rated in accordance with AHRI Standard 410, but their cooling and heating capacities shall be established in accordance to ASHRAE Standard for the specific application on the inlet side of the submitted chilled beam. 3. Chilled water flow rates to the beams shall be limited to that which results in a maximum ten (10) foot head loss. Water flow velocities through the beam shall not exceed 4 FPS. PART 3- EXECUTION 3.02 Installation 1. Coordinate the size, tagging and capacity of the beams to their proper location. 2. Chilled beams up to six feet in length shall be independently suspended from the structure above by a four (4) threaded rods of 3/8 diameter (provided by the installing contractor). For beams beyond six feet in length, six (6) threaded rods of 3/8 diameter shall be used. The upper end of the rods shall be suspended from strut channels that are a) mounted perpendicular to the beam length and b) at least four inches wider than the beam to facilitate relocation of the threaded rods along their length. The beam shall then be positioned above the acoustical ceiling grid and lowered into the grid module by adjusting the nuts connecting the threaded rods to the beam. 3. Before connecting the supply water system(s) to the beams, contractor shall flush the piping system(s) to assure that all debris and other matter have been removed. 4. Contractor shall perform connection of beams to the chilled water circuit by method specified (hard connection using sweated connection or connection using flexible hoses). 5. Flexible connector hoses shall be furnished by others (optionally by the manufacturer). Hoses shall be twenty four (12, 18, or 24) inches in length and suitable for operation with a bend radius as small as five (5) inches. Connector hoses shall consist of a PTFE lined hose with a wire braided jacket. The hoses shall be suitable for operation in an environment between -40 and 200BF, rated for a least 300 PSI and tested for leakage at a minimum pressure of 360 PSI. Contractor shall assure that the chilled water supplying the beams has been 25
plenum slot diffusers
light powered Redefine your comfort zone. www.titus-hvac.com dual-function smart logic light powered energy solutions Table of Contents PLENUM SLOT IFFUSERS products Plenum Slot iffusers Products... 4
More informationChilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
More informationBasic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
More informationM SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
More informationVertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water
2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationInstallation Manual CLIFC Fan & Coil Variable Speed
Installation Manual CLIFC Fan & Coil Variable Speed General Description GENERAL DESCRIPTION FANS EQUIPMENT Totally Factory assembled within the unit all piping, wiring, and required controls for operation
More informationSECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution.
SECTION EG Air Distribution Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. Space Air Diffusion AIR DISTRIBUTION ENGINEERING GUIDE Proper selection of air diffusion
More informationMethods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update
More informationsecurity products metric sizes Redefine your comfort zone. www.titus-hvac.com
metric sizes secure lethal objects monitoring areas suicide deterrent Redefine your comfort zone. www.titus-hvac.com humid areas prevents corrosion minimum security medium security maximum security Table
More information1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None
1-Way Chilled Water Cassettes KCO 60, 90 & 120 Technical Brochure TM KCO-W.1GB Date : November 2005 Supersedes : None General Features Control valve (optional) Air vent In-tube electric heating elements
More informationResidential/Commercial Gas Condensing High Efficiency Tankless Water Heaters
Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger
More informationInnovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationT 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ
TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size
More informationCEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
More informationA. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
More informationAABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
More informationSECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
More informationDSRQ - DSRSQ - DSRSQ-THERM
DSRQ - DSRSQ - DSRSQ-THERM Specification item: Variable geometry diffuser on 597x597 mm panel developed for rooms with high ceilings where a long throw and a high induction ratio are required. Made up
More informationPIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant
More informationActive & Passive Beams
Active & Passive Beams Active & Passive Beams Introduction Beam systems are an alternative to traditional all-air conditioning systems. Beams use water to move energy through a building and service the
More informationCOIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here.
COIL INPUT SCREENS Example of a Water Coil Input Screen: (*please see the appendix for an example of an Evaporator, Steam or Condenser Coil input screen) PHYSICAL DATA ITEM NUMBER: Always use a 1 through?
More informationSECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
More informationWTW SWANTM. Linear slot air diffusers of wall-to-wall design for ceilings
SWANTM WTW Linear slot air diffusers of wall-to-wall design for ceilings Quick facts Wall-to-wall installation Diffuser face of light aluminium design 2, 3 or slots Horizontal/vertical air distribution
More informationflowbar Redefine your comfort zone. www.titus-hvac.com
open ceiling Redefine your comfort zone. www.titus-hvac.com woodgrains metric sizes Table of ontents products FlowBar Products... 2 overview linear Overview... 6 Application Icons Key... 6 HighThrow...
More informationAPC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
More informationFIRE DAMPER APPLICATION GUIDE
FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire
More informationROOF TOP MOUNTED Air Handler Specification
ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor
More informationLight Duty Commercial Electric Water Heater
Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and
More informationLH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_001_071015. Products that provide lasting solutions.
LH and GH/GL Series UNIT COOLERS Technical Bulletin: LHGH_001_07101 Products that provide lasting solutions. LH Series Unit Coolers Dual Discharge Low Hite Series At 9 1/ maximum height, the LH Series
More informationSubpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationREGULATORS 175/153 Series
175/153 Series 175 HEATING 153 COOLING Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2002 Watson McDaniel Company Revised 7/2002 175 / 153 Screwed
More informationAIR DISTRIBUTION FOR COMFORT AND IAQ
AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant
More informationDehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationUnder sill units. Type FSL-B-ZAS
.1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationASME Packaged Indirect Fired Water Heater
Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining
More informationChilled Water Fan Coil Unit. Model:HFCA Size 03~14
Chilled Water Fan Coil Unit Model:HFCA Size 03~4 The Best Choice for Comfort =The Best Results Quiet Comfort Slope coil avoid air flow perpendicular impact Low noise permanent split capacitor motor Metal
More informationAll work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationSPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
More informationTechnical Concept. Filter Fan Unit COMPACT. Type COMPACT AC Type COMPACT EC
Technical Concept Filter Fan Unit COMPACT Type COMPACT AC Type COMPACT EC Ultra Filter Fan Unit COMPACT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide
More informationLocal Dealer: www.cebrands.com
Local Dealer: C.E. LLC - Miami, FL USA www.cebrands.com Res2012-Rev2 QUALITY YOU CAN FEEL Residential Product Line >TCA7,9 Tempstar SmartComfort TXT + Air Conditioner Featuring The Observer Communication
More informationDefining Quality. Building Comfort. Heating and Cooling Coils
Defining Quality. Building Comfort. Heating and Cooling Coils Heating and Cooling Coils Heating and Cooling Coils For over 20 years, AAON has supplied the coil needs of industrial and commercial HVAC customers.
More informationIn-Line Air Separators
Air Elimination & Control In-Line Air Separators The AC models of air separators deliver all the quality and performance you expect from Taco products. They are built to last with shell, heads and ANSI
More informationIndirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
More informationStainless Steel Single and Dual Circulation Kits
Instruction Sheet P/N 160780 01 Stainless Steel Single and Dual Circulation Kits Introduction The single and dual high-pressure circulation kits allow you to vary and control the circulation rate of coating
More informationMUELLER FALLING FILM CHILLERS
MUELLER FALLING FILM CHILLERS MUELLER FALLING FILM CHILLERS ARE DESIGNED TO COOL ANY FLUID TO WITHIN 2 F OF ITS FREEZE POINT. The primary application for Mueller s falling film chiller is to cool food-grade
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationGas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard
LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled
More informationSECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationNEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More informationLow Profile Unit Cooler
Super-Flo Now available with EC Motors High Efficiency / High Reliability Low Profile Unit Cooler Publication No. 411.4 November, 2008 S A N I T A T I O N F O U N D A T I O N A L N A T I O N Air Defrost
More informationDESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System
TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: MC, PC, FC, HD, UC 600-2000 CFM 1.5-5 TON COILS UPFLOW/DOWNFLOW FULL CASED FC UPFLOW PARTIAL CASED PC UPFLOW UNCASED
More informationAdvances in Gas Cooler Design and the New Gas Cooler Product Selector
Advances in Gas Cooler Design and the New Gas Cooler Product Selector Simon Jones Engineering Manager Sean Armitage Sales Manager Introduction GEA Searle Over 90 years experience in the design and manufacture
More informationGlossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
More informationContents and Nomenclature
DX Coils Contents and Nomenclature Nomenclature... 1 Evaporator Coil Types EN... 2 EF... 2 ER... 2 EJ... 3 EK... 3 Evaporator Construction Connections... 4 Tubing... 4 Headers... 5 Tube Supports... 5 Coil
More informationCommercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
More informationInstallation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
More informationCoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
More informationNAVIEN AMERICA INC. 17855 FITCH AVENUE
Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:
More informationInstallation and Operating Instructions Installation Instructions for SS EPE-316L Series
INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This
More informationSECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
More informationPerformance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
More informationRadiant Panels and Chilled Sails. www.price-hvac.com
Radiant Panels and Chilled Sails www.price-hvac.com Radiant Panels and Chilled Sails Introduction Radiant panels use thermal radiation to modify surface temperatures in order to provide sensible cooling
More informationDuct Design. Presented by Dave Janquart
Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length
More informationANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals
ANSI/AHRI Standard 880 (I-P) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:
More informationSelect Radiators Installation Guide
Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall
More informationSIMPLAIR PIPING. www.irtools.com 1-800-376-TOOL
SIMPLAIR PIPING INGERSOLL-RAND SIMPLAIR PIPING With push-in fittings and lightweight anodized aluminum pipe, a SimplAir system provides ideal connection throughout your entire air distribution system.
More informationDr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationChilled Water Fan Coil Unit
Chilled Water Fan Unit Model: HFCF02~HFCF14 Airflow Range: 200~2400m 3 /h Features and Benefits The Best Choice for Comfort The Best Results - Quiet Comfort Low noise permanent split capacitor motor. Metal
More informationAPPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
More informationIMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.
QUIET-ONE Environmental Products 2000 Kickspace Heater Series Models: KS 2004, KS 2006 KS 2008, KS 2010 INSTALLATION OPERATING MAINTENANCE Please read these instructions thoroughly before beginning your
More informationHVAC Characteristics. Test Space HVAC Characteristics
HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,
More informationExplosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
More informationA. Section includes air conditioning units, controls and control panels.
SECTION 23 81 23 - COMPUTER-ROOM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes air conditioning units, controls and control panels. 1.2 REFERENCES A. Air-Conditioning, Heating, and
More informationSanitary Type Electronic Flow Switches
Industries Pharmaceutical Sanitary Type Electronic Flow Switches Food and Beverage Biotechnology Semiconductor Water Treatment S Series Ameritrol, Inc. Instruments and Controls Features No Moving Parts
More informationINSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)
CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage
More informationCeiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
More informationTABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)
CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.
More informationCooling/Heat Pump Convertible Air Handlers
Cooling/Heat Pump Convertible Air Handlers 2/4TEC3F18-60A1000A 1½ 5 Ton PUB. NO. 22-1774-01-0905 (EN) Features and Benefits 13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way
More informationDIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
More informationPump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationCased/Uncased Coils For Gas And Oil Furnaces
Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFL- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,900 CFM [283-897 L/s] Rheem Indoor Coils are designed for use
More informationFilter Fan Unit SILENT. Type SILENT AC Type SILENT EC
Technical Concept Filter Fan Unit SILENT Type SILENT AC Type SILENT EC Filter Fan Unit SILENT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide clean
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationSPACE COOLERS. P.O. Box 956 Paoli, PA 19301 (800) 523-7590 FAX (610) 251-0805 www.coilcompany.com. The leader in packaged Space Cooling.
SPACE COOLERS P.O. Box 956 Paoli, PA 19301 (800) 523-7590 FAX (610) 251-0805 www.coilcompany.com The leader in packaged Space Cooling. 2 Table of Contents Description Space Cooler from Coil Company. A
More informationNITROUS TRANSFER PUMP INSTRUCTIONS
NITROUS TRANSFER PUMP INSTRUCTIONS SAFETY TIPS Never directly inhale nitrous oxide. When inhaled in large quantities, nitrous oxide can cause respiratory ailments or in extreme cases, death by suffocation.
More informationSERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
More informationARMSTRONG AIR HEAT PUMPS www.armstrongair.com
INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7
More informationChilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
More informationB. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationEquivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409
Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationBOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.
SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION
More information