1 Fire Alarm Systems FCP 32/FCH 32 Conventional Automatic Fire Detectors FCP 32/FCH 32 Conventional Automatic Fire Detectors High reliability of detection thanks to evaluation electronics Active adjustment of the threshold (drift compensation) if the optical sensor becomes dirty Activation of a remote external detector alarm display possible Mechanical removal lock (can be activated/deactivated) Dust-repellent labyrinth and cap construction The FCP 32/FCH 32 Series Conventional Automatic Fire Detectors set new standards in fire detection technology through a combination of optical, thermal and chemical (gas) sensors and intelligent evaluation electronics. Their most impressive feature is their ability to prevent false alarms, as well as speed and accuracy of detection. The enhanced operating voltage range of 8,5 V DC up to 3 V DC and the two variants with 82 Ω alarm resistor or 47 Ω alarm resistor enables the detector application with nearly all conventional fire panels. System overview Operating mode OC32 OT32 O32 FCH- T32/ T32- FSA Combined x x - - Optical (scattered light measurement) x x x - Thermal max. - x - x Thermal differential - x - x Chemical (gas measurement) Functions x The OC32 and OT32 Multisensor Detectors each combine two detection principles. All sensor signals are analyzed continually by the internal evaluation electronics and are linked with each other. If a signal combination fits the detector's programmed code field, an alarm is automatically triggered. By linking the sensors, the combined detectors can also be used in places where work carried out gives rise to light smoke, steam or dust. Optical sensor (smoke sensor) The optical sensor uses the scattered-light method. An LED transmits light to the measuring chamber, where it is absorbed by the labyrinth structure. In the event of a fire, smoke enters the measuring chamber and the smoke particles scatter the light from the LED. The amount of light hitting the photo diode is converted into a proportional electrical signal.
2 2 FCP 32/FCH 32 Conventional Automatic Fire Detectors Thermal sensor (temperature sensor) A thermistor in a resistance network is used as a thermal sensor; an analog-digital converter measures the temperature-dependent voltage at regular intervals. When the maximum temperature of 54 C is exceeded (thermal maximum), or if the temperature rises by a defined amount within a specified time (thermal differential), the temperature sensor triggers the alarm status. Chemical sensor (CO gas sensor) The main function of the gas sensor is to detect carbon monoxide (CO) generated as a result of a fire, but it will also detect hydrogen (H) and nitrous monoxide (NO). The sensor signal value is proportional to the concentration of gas. The gas sensor delivers additional information to effectively suppress deceptive values. Depending on the service life of the gas sensor, the OC 31 detector switches off the C sensors after five years of operation. The detector will continue to function as an O detector. The detector should then be exchanged immediately in order to be able to keep using the higher reliability of detection of the OC detector. Special features Drift compensation in optical unit Drift compensation in the gas sensor OC32 Certifications and approvals The detectors comply with: OT32 O32 FCH- T32 / T32-FSA x x x - x EN54 5:2/ A1:22 EN54 7:2/ A1:22 OC32 OC32-R47 OT32 OT32-R47 O32 O32-R47 FCH-T32 T32-R471 FCH-T32-FSA Region Certification Germany G 283 FCH-T32_-R47 G 284 FCH-T32-FSA G 281 O32_-R47 Europe CE /FCH-32 G 282 OT32_-R47 G 285 OC32_-R FCH-T32_FCH- T32-R FCH-T32-FSA O32_ O32-R OC32_ OC32-R OT32_ OT32-R47 18/1 O32 Installation/configuration notes Up to 32 detectors can be connected per primary line. Maximum cable length: 1 m, for J- Y(St) Y n x 2 x.6/.8 Country-specific standards and guidelines must be observed during the planning phase. The detector can be painted (cap and base) and thereby adapted to the surrounding colour scheme. Note the information in the Painting Instructions (Document Number F.1U ). Installation/configuration notes in accordance with /VDE/DIBt Planning for multisensor detectors follows the guidelines for optical detectors, unless a specific planning guideline is available (see DIN VDE 833 Part 2 and VDS 295). The OC and OT types are planned using the guidelines for optical detectors if operated as optical detectors or as combined detectors; see DIN VDE 833 Part 2 and VDS 295. When planning fire barriers according to DIBt, you have to use the FCH-T32-FSA. This detector has the characteristic curve corresponds to class A1R. Parts included Q t y. Components OC32 1 Multisensor Detector Optical/Chemical OT32 1 Multisensor Detector Optical/Thermal O32 1 Optical Smoke Detector
3 3 FCP 32/FCH 32 Conventional Automatic Fire Detectors FCH-T32 1 Heat Detector (Thermal Differential/Thermal Maximum) FCH-T32- FSA Technical specifications Electrical Operating voltage Current consumption Alarm output Indicator output Mechanics 1 Heat Detector for Fire Barriers conforming to DIBt, Quality-controlled (Thermal Differential/ Thermal Maximum) 8.5 V DC to 3 V DC <.12 ma Increase in current (alarm resistance 82 Ωor 47 Ω) Open collector connects V in the event of an alarm over 3.92 kω Maximum installation height OC32, OT32, O32 16 m (Heed local guidelines!) 16 m (Heed local guidelines!) FCH-T32 6 m (Heed local guidelines!) Special features Response sensitivity Optical part <.2 db/m, in line with EN 54 T7 Thermal maximum part Thermal rate-of-rise part (in line with pren 54 5) >54 C FCH-T32: A2R FCH-T32-FSA: A1R Chemical part In ppm range Color code Individual display Dimensions LED red OC32 Blue ring OT32 Black ring Without base Ø 99.5 x 52 mm With base Ø 12 x 63.5 mm Housing material Plastic, ABS Housing color White, similar to RAL 91, matt finish Weight Without / with packaging OC32 Approx. 85 g / approx 13 g OT32 / O32 / FCH-T32 / FCH-T32-FSA Environmental conditions Approx. 8 g / approx. 12 g Protection class as per EN 6529 IP 4, IP 43 with detector base with damp room seal Permissible relative humidity Permissible air speed Permissible operating temperature 95% (non-condensing) 2 m/s OC32-1 C to +5 C OT32-2 C to +5 C O32-2 C to +65 C FCH-T32 / T32-FSA -2 C to +5 C Planning Monitoring area OC32, OT32, O32 Max. 12 m 2 (Heed local guidelines!) O32 No marking FCH-T32 / T32-FSA Red ring Ordering information FCP O32 Optical Smoke Detector conventional technology, with 82 Ohm alarm resistor Order number O32 FCP OT32 Multisensor Detector Optical/Thermal conventional technology, with 82 Ohm alarm resistor Order number OT32 FCP OC32 Multisensor Detector Optical/Chemical conventional technology, with 82 Ohm alarm resistor Order number OC32 FCP OC32 R47 Multisensor Detector Optical/Chemical conventional technology, with 47 Ohm alarm resistor Order number OC32-R47 FCP OT32 R47 Multisensor Detector Optical/Thermal conventional technology, with 47 Ohm alarm resistor Order number OT32-R47 FCP O32 R47 Optical Smoke Detector conventional technology, with 47 Ohm alarm resistor Order number O32-R47 FCH T32 Heat Detector conventional technology, thermal differential/thermal maximum detector, with 82 Ohm alarm resistor Order number FCH-T32 FCH-T32 Max. 4 m 2 (Heed local guidelines!)
4 4 FCP 32/FCH 32 Conventional Automatic Fire Detectors FCH T32 R47 Heat Detector thermal differential/thermal maximum detector, conventional technology, with 47 Ohm alarm resistor Order number FCH-T32-R47 FCH-T32-FSA Heat Detector, for Fire Barriers conforming to DIBt thermal differential/thermal maximum detector, conventional technology, with 82 Ohm alarm resistor Order number FCH-T32-FSA Accessories MS 4 Detector Base Order number MS 4 MS 4 B Detector Base Bosch-branded detector base for surface mounted and flush-mounted cable feed Order number MS 4 B MSC 42 Additional Base with Damp Room Seal for surface-mounted cable feed Order number MSC 42 MH 4 Detector Heating Element usable at locations where the functional safety of the detector might be impaired by condensation Order number MH 4 SK 4 Protective Basket prevents damage Order number SK 4 SSK 4 Protective Dust Cover (packing unit = 1 units) Order number SSK 4 TP4 4 Support Plate for Detector Identification (packing unit = 5 units) Order number TP4 4 TP8 4 Support Plate for Detector Identification (packing unit = 5 units) Order number TP8 4 MSR 32 Conventional Detector Base with Relay with a change-over relay (Form C) Order number MSR 32 MSD 32 Conventional Detector Base with Diode for Great Britain Order number MSD 32 MSS 3 Detector Base Sounder White Control via C-point of the detector Order number MSS 3 MSS 3-WH EC Detector Base Sounder White Control through fire panel via interface Order number MSS3-WH-EC MSR 32 Conventional Detector Base with Relay with a change-over relay (Form C) Order number MSR 32 MPA External Detector Alarm Display according to DIN the transparent red alarm display conforms to DIN Order number MPA FAA 42 RI Remote Indicator required if the detector is not directly visible or has been mounted in false ceilings or false floors Order number FAA-42-RI Mounting Bracket for Fire Detectors on False Floor Stilts Order number FMX-DET-MB MK 4 Detector Console Console for DIBt compliant mounting of detectors above doors etc., including detector base Order number MK 4
5 5 FCP 32/FCH 32 Conventional Automatic Fire Detectors 32/FCH-32 Conventional Automatic Fire Detectors FCP O32 Optical Smoke Detector FCP OC32 Multisensor Detector Optical/Chemical FCP OT32 Multisensor Detector Optical/Thermal optical optical/chemical optical/thermal Operating voltage 8.5 V DC V DC 8.5 V DC V DC 8.5 V DC V DC Current consumption <.12 ma <.12 ma <.12 ma Protection category IP 4, IP 43 with MSF 4 IP 4, IP 43 with MSF 4 IP 4, IP 43 with MSF 4 Permissible operating temperature -2 C C -1 C C -2 C C Monitoring area max. 12 m² max. 12 m² max. 12 m² Maximum installation height 16 m 16 m 16 m Alarm resistance 82 Ω 82 Ω 82 Ω Color code no marking blue loop black loop For fire barriers conforming to DIBt, quality-controlled FCP O32 R47 Optical Smoke Detector FCP OC32 R47 Multisensor Detector Optical/Chemical FCP OT32 R47 Multisensor Detector Optical/Thermal optical optical/chemical optical/thermal Operating voltage 8.5 V DC V DC 8.5 V DC V DC 8.5 V DC V DC Current consumption <.12 ma <.12 ma <.12 ma Protection category IP 4, IP 43 with MSF 4 IP 4, IP 43 with MSF 4 IP 4, IP 43 with MSF 4 Permissible operating temperature -2 C C -1 C C -2 C C Monitoring area max. 12 m² max. 12 m² max. 12 m² Maximum installation height 16 m 16 m 16 m Alarm resistance 47 Ω 47 Ω 47 Ω Color code no marking blue loop black loop For fire barriers conforming to DIBt, quality-controlled
6 6 FCP 32/FCH 32 Conventional Automatic Fire Detectors FCH T32 Heat Detector FCH T32 R47 Heat Detector FCH-T32-FSA Heat Detector, for Fire Barriers conforming to DIBt thermal differential/thermal maximum thermal differential/thermal maximum thermal differential/thermal maximum Operating voltage 8.5 V DC V DC 8.5 V DC V DC 8.5 V DC V DC Current consumption <.12 ma <.12 ma <.12 ma Protection category IP 4, IP 43 with MSF 4 IP 4, IP 43 with MSF 4 IP 4, IP 43 with MSF 4 Permissible operating temperature -2 C C -2 C C -2 C C Monitoring area max. 4 m² max. 4 m² max. 4 m² Maximum installation height 6 m 6 m 6 m Alarm resistance 82 Ω 47 Ω 82 Ω Color code red loop red loop red loop For fire barriers conforming to DIBt, quality-controlled Represented by: Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina: Bosch Security Systems, Inc. Bosch Security Systems B.V. Robert Bosch (SEA) Pte Ltd, Security Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division 13 Perinton Parkway Fairport, New York, 1445, USA Phone: Fax: security.sales@us.bosch.com P.O. Box BA Eindhoven, The Netherlands Phone: Fax: emea.securitysystems@bosch.com Systems 11 Bishan Street 21 Singapore Phone: Fax: apr.securitysystems@bosch.com 21 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 2335 China Phone Fax: Via Anhanguera, Km 98 CEP Campinas, Sao Paulo, Brazil Phone: Fax: al.securitysystems@bosch.com Bosch Security Systems 212 Data subject to change without notice en, V4, 26. Nov 212
Conventional Automatic Detectors FCP-320/FCH-320. Operation Guide
Conventional Automatic Detectors FCP-320/FCH-320 en Operation Guide Conventional Automatic Detectors Table of Contents en 3 Table of Contents 1 Product Description 5 2 System Overview 6 2.1 Configuration
More informationDetector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases
Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases
More informationSmoke detector 500 Series The art of invisible fire detection
Smoke detector 500 Series The art of invisible fire detection 1 2 Tough on protection, invisible to the eye. Fire protection is essential in modern life. Hotels, public buildings and private companies
More information(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently
(68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please
More informationFire detection equipment
PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,
More informationAnalogue addressable devices
Discovery Analogue addressable devices from Channel Safety Systems Discovery Analogue addressable devices Discovery is a range of high-specification, intelligent fire detectors that are developed to meet
More informationAuto-iris Motorized Zoom Lenses
Video Ato-iris Motorized Zoom Lenses Ato-iris Motorized Zoom Lenses www.boschsecrity.com High Qality Optics Reliable, Robst Constrction 1/3- Format with DC-iris Control 1/2- Format with Video-iris Control
More informationProduct Guide Specification
Americas Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: + 1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us Europe, Middle East,
More informationG3A Series AutoDome Indoor Systems
Video G3A Series AutoDome Indoor Systems G3A Series AutoDome Indoor Systems www.boschsecurity.com u Day/Night, color and B/W versions u 26x (Day/Night) or 18x optical zoom range +12x digital zoom u Privacy
More informationMINERVA MX MX Virtual Multi-Sensor Detectors
DATASHEET MINERVA MX MX Virtual Multi-Sensor Detectors Over 20 fire detection modes Tyco MX FASTLOGIC Expert algorithms MX HPO detection Algorithms Up to 250 detectors per loop Optional bi-directional
More informationAlarmSense 2-wire detection and alarm system. Product Guide
AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority
More informationD287/D288/D292/D293A/D293E
D87/D88/D9/D9A/D9E EN Installation Guide Smoke Detector Bases D87/D88/D9/D9A/D9E Installation Guide.0 Overview.0 Overview The D87/D88/D9/D9A/D9E Smoke Detector Bases are designed for use with the D8 Ionization
More informationLBB 442x/xx Power Amplifiers
Commnications Systems LBB 442x/xx Power Amplifiers LBB 442x/xx Power Amplifiers www.boschsecrity.com, 2, 4, or 8 adio otpts (selection from 00 / 70 / 50 V otpts) Adio processing and delay for each amplifier
More informationPremier M Plus & Infinity 8
25 Years of Manufacturing Excellence Premier M Plus & Infinity 8 Conventional Fire Alarm Systems 007 Assessed to ISO 9001: 2008 Certificate number 330 Premier M Plus 8-24 Zone Conventional Fire Alarm Panel
More informationLBC 14x0/x0 MK Volume Controls and LBC 1430/10 Program Selector
Commnications Systems LBC 14x0/x0 MK Volme Controls and LBC 1430/10 Program Selector LBC 14x0/x0 MK Volme Controls and LBC 1430/10 Program Selector www.boschsecrity.com 12 W, 36 W and 100 W versions Available
More informationVG4 Fiber Optic Media Converter
VG4 Fiber Optic Media Converter VG4-SFPSCKT en Installation Guide Fiber Optic Media Converter Table of Contents en iii Table of Contents 1 Important Safety Instructions 1 1.1 Customer Support and Service
More informationInput module, input/output module
Sinteso / Cerberus PRO Input module, input/output module FDCI221, FDCIO221 Input module and input/output module for the automatically addressed detector line Input module FDCI221: Monitorable contact input
More informationMIC-WKT and MIC-WKT-IR
MIC-WKT and MIC-WKT-IR Installation Manual Bosch Security Systems EN Installation and Operation Manual MIC-WKTI and MIC-WKT-IR Installation Manual EN 2 MIC-WKT and MIC-WKT-IR Washer Pump Drive Card Kits
More informationDBS720 / FDS221-R / FDS221-W Sounder base, Alarm sounders
DBS720 / FDS221-R / FDS221-W Sounder base, Alarm sounders For the automatic addressable detector bus C-NET Cerberus PRO Sounder base DBS720 11 selectable tones, 2 programmable activation levels Sound intensity
More informationSmoke exhaust systems
1 Fire zone, e.g. hall 2 Smoke exhaust zone, separated by smoke curtains Natural and mechanical smoke extraction General information 3 Natural smoke and heat exhaust vent 4 Air inlet opening or wake max.
More informationFire Detection Product Range
Fire Detection Product Range World Leading Fire Detection Products from the NITTAN group Issue 1.0 Business Overview The Nittan Group has been at the forefront of the fire protection industry since 1954
More informationProduct and Application Description
Technical Product - Information Product and Application Description The room temperature controller UP 237K and UP 252K are available in the following colors, matching the design of the wall switch design
More informationProduct Information Fire alarm panel 8000 C
Product Information Fire alarm panel 8000 C Fire alarm panel 8000 C, basic configuration In common with all modern Esser panels, the 8000 C fire alarm panel is based on high-performance ringbus technology.
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More information2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal
O N DS160/DS161 Installation Guide High Performance Request-to-Exit Sensors 1.0 Description The DS160/161 is a passive-infrared (PIR) detector designed for Request to Exit (REX) interior applications.
More informationPolyGard Carbon Monoxide CO Transmitter ADTX3 1110
PolyGard Carbon Monoxide CO Transmitter ADTX3 1110 DESCRIPTION CO transmitter including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air
More informationHow To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
More informationDigital Pressure Measuring Instrument MDR480
Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm
More informationCB200 1 8 Zone Conventional Control Panel
CB200 1 8 Zone Conventional Control Panel > features Built-in detector removal indication facility From 1 to 8 zones 4 Alarm circuits on 4-8 zone panels Conforms to the requirements of EN54-2 User-friendly
More informationRosemount 333 HART Tri-Loop
Product Data Sheet Rosemount 333 Rosemount 333 HART Tri-Loop HART-TO-ANALOG SIGNAL CONVERTER Convert a digital HART signal into three additional analog signals Easy to configure and install Accessory product
More informationRosemount 333 HART Tri-Loop
Product Data Sheet September 2014 00813-0100-4754, Rev GA Rosemount 333 HART Tri-Loop HART-to-Analog Signal Converter Convert a digital HART signal into three additional analog signals Easy to configure
More informationIPThermo206G. Offline/online data collector, SMS alarm sender, watchdog terminal for IPThermo Pro network
IPThermo206G Offline/online data collector, SMS alarm sender, watchdog terminal for IPThermo Pro network IPThermo 206G is the central data handling terminal of the IPThermo Pro measurement network. This
More informationW 260: Standard photoelectric switch series for a broad range of applications
W 0 Photoelectric switches Photoelectric proximity switches, BGS Photoelectric proximity switches, energetic Photoelectric reflex switches W 0: Standard photoelectric switch series for a broad range of
More informationLTC 8900 Series Allegiant Matrix/Control Systems - Modular
Video LTC Series Allegiant Matrix/Control Systems - Modular LTC Series Allegiant Matrix/Control Systems - Modular www.boschsecurity.com u u u u u Camera by monitor switching Modular construction Powerful
More informationDLO1191 Linear smoke detector
DLO1191 Linear smoke detector collective/synoline600, interactive AlgoRex Synova Reliable smoke detection in large-volume rooms (inside application) Detection distance from 5 100 Meter Efficient signal
More informationAccessory Packages for the Allegiant
Video Accessory Packages for the Allegiant Accessory Packages for the Allegiant www.boschsecurity.com The Allegiant accessory products provide many optional features to the base Allegiant Video Switcher/
More informationCross-beam scanning system to detect slim objects. 100 mm 3.937 in
891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC
More informationAnalogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001
Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.
More informationFIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
More informationRM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
More informationFire & Security DETECTORS
Fire & Security DETECTORS Smoke Sensitivity 0.98 ~.0%/ft Obscuration Ceiling Spacing 50 foot rating for heat sensor Temperature Range 10ºC to 50ºC Humidity 0 to 95% RH, no condensation or icing Dimensions
More informationFACTORY AUTOMATION EXPERTISE AND SERVICE OPEN DOORS RADAR SENSORS FROM PEPPERL+FUCHS
FACTORY AUTOMATION EXPERTISE AND SERVICE OPEN DOORS RADAR SENSORS FROM PEPPERL+FUCHS RADAR MOTION SENSORS FROM PEPPERL+FUCHS A FAMILY OF RADAR SENSORS THAT IS EQUAL TO ANY CHALLENGE Since radar sensors
More informationABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems
ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems Content Introduction Preventing unauthorized access by perimeter surveillance Monitoring unauthorized access by indoor surveillance
More informationDM1101, DM1103, DM1104 DM1103-L, DM1103-S Manual call points Manual release button and emergency stop button
DM1101, DM1103, DM1104 DM1103-L, DM1103-S Manual call points Manual release button and emergency stop button collective/synoline600 AlgoRex Synova Manual call point to all fire detection system control
More informationClimasys Thermal Management System. Schneider Electric Universal Enclosures 2009
Climasys Thermal Management System Schneider Electric Universal Enclosures 2009 Schneider Electric Universal Enclosures The specialist in sealed equipment What is the mission of Schneider Electric Universal
More informationRRV934. Multi-controller. Synco living
s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard
More informationDifferential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
More informationTechnical data. General specifications. Indicators/operating means. Electrical specifications Operating voltage U B Power consumption P 0 Interface
Release date: 06-0- 09: Date of issue: 06-0- 009_eng.xml Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service
More informationwelcome to our world fire alarm systems - series 600 www.staticsystems.co.uk
Static Systems Group PLC Heath Mill Road, Wombourne Staffordshire WV5 8AN. United Kingdom. Tel: +44 (0) 1902 895551 Fax: +44 (0) 1902 324969 www.staticsystems.co.uk welcome to our world In line with our
More informationSeries AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter
FEATURES: Click on Series name for product info on aimtec.com Models Single output Model Max Output Power (W) 1 AC-DC Constant Current or Constant Over temperature protection Voltage LED Driver Over current
More informationFDCI222, FDCIO222, FDCIO224 Input module Input/output modules
FDCI222, FDCIO222, FDCIO224 Input module Input/output modules addressable (FDnet/C-NET) Sinteso Cerberus PRO Input module FDCI222 with 4 monitored contact inputs for the acknowledgement of technical states
More informationDRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
More informationACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
More informationMitel DECT Base Stations
Mitel DECT Base Stations On-site Mobility for Professionals The Mitel BS300 range of base stations offers a variety of coverage patterns to suit different situations. By choosing the right mix of base
More informationDräger Alcotest 9510 Evidential Alcohol Measuring Device
Dräger Alcotest 9510 Evidential Alcohol Measuring Device The Dräger Alcotest 9510 is an advanced breath alcohol measuring instrument for evidential applications. It is designed to comply with national
More informationTLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR
TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.
More informationFIRE ALARM SYSTEM. reliable fire detection and alarm signalling system
FIRE ALARM SYSTEM reliable fire detection and alarm signalling system Satel fire alarm devices allow to implement reliable and modern systems responsible for fire safety. A combination of 20-year experience
More informationFire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
More informationCombi B Alarm box. Mounting instructions
Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power
More informationXUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm
Characteristics XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm Complementary Detection system Kit composition [EAA] effective aperture angle Emission Main Range of product Product or
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 15 mm
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element
More informationUML Series 42- and 55-inch High Performance HD LED Monitors
Video UML Series 42- and 55-inch High Performance HD LED Monitors UML Series 42- and 55-inch High Performance HD LED Monitors www.boschsecrity.com Fll HD 1920 x 1080 resoltion Precise color reprodction
More informationPIEZOMETER AIRFLOW MEASURING RING
PIEZOMETER AIRFLOW MEASURING RING M.K. Plastics is pleased to introduce The Piezometer Airflow Measuring Ring, now available as an accessory for our steel Axijet fans. The system consists of a Piezometer
More informationFlameproof Audible Signal 115 db (A) Series YA90
Clifford Snell www.stahl.de > Max sound output 115 db (A) / 1 m > 2 stage alarm, independently selectable 2nd stage > IP66 rated as standard > 32 selectable tones meeting international regulations > Light
More informationBusch-Watchdog Presence EIB Type: 6131-74-102-500
Type: 6131-74-102-500 Contents Technical data 2-2 Application programs (List) 2-3 Circuit diagrams 2-3 in combination with Bus coupler FM (6120-102): Switch Value Cyclic Monitoring /3 2-4 Switch Value
More informationPower Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN
Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit
More informationIS3016A Passive Infrared Motion Sensor with Anti-Mask - Installation Instructions
IS3016A Passive Infrared Motion Sensor with Anti-Mask - Installation Instructions QUICK LINKS Mounting Location Guidelines Open the Sensor Mount the Sensor Sensor Components and Settings Wire the Sensor
More informationTechnical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5
Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis
More informationD7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors
D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH
More informationMIC-BP4 Bi-Phase Converter Card For the MIC400 series camera
MIC-BP4 Bi-Phase Converter Card for the MIC400 PTZ Camera Series Bosch Security Systems EN Installation and Operation Manual BP4 Bi-phase card Installation and Operation Manual AAAEN 2 MIC-BP4 Bi-Phase
More informationFire Alarm System Accessories
Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer
More informationABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
More informationSERIES 65 ENGINEERING PRODUCT GUIDE
SERIES 65 ENGINEERING PRODUCT GUIDE Wide Voltage Conventional Detectors www.apollo-fire.co.uk Series 65 incorporates well-proven sensing technologies, including an Integrated Circuit based on that used
More informationTMS TANK MANAGEMENT SYSTEM
TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS
More informationPRODUCT PROFILE FEATURES
PRODUCT PROFILE Pressure Transmitters & Pneumatic Transducer Airflow Transmitter, Differential Air Pressure Transmitter and Differential & Gauge Liquid/Gas Pressure Transmitter FEATURES AIRFLOW TRANSMITTER
More informationIntroduction. Refrigerant Leak Detecting System. Feature and Benefits
PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for
More informationBS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
More informationOperating Instructions. Room temperature controller
Operating Instructions 1. Area of application The room temperature controller is used to regulate the temperature in closed rooms such as flats, schools, function suites, workshops, etc. Safety instructions
More informationVacuum drying oven for non-flammable solvents
VD series 53 Vacuum drying ovens Vacuum drying oven for non-flammable solvents A BINDER vacuum drying oven of the VD series is impressive while gently drying with its homogeneous temperature distribution.
More informationDivar - Digital Video Recorder
CCTV Divar - Digital Video Divar - Digital Video 6, 9, and 16-channel versions Bilinx communication optional Simultaneous recording, playback & archiving AutoDome control Smart motion search Authenticated
More informationBar Code Reader Series BCL 20 A flexible reader for a variety of applications
Bar Code Reader Series BCL 20 A flexible reader for a variety of applications PRODUCT INFORMATION The benchmark for flexibility. Laser scanners of the BCL 20 series as variable as your requirements demand.
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationFIREDEX 2200. Conventional Fire Panels
68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationPreset Counter signo 721
Most simple handling Impressive, clearly readable display in 48x48 mm Input frequency up to 60 khz Easy installation due to pluggable terminals TECHNICAL DATA GENERAL Display Height of digits Supply voltage
More informationRVL470. Heating Controller. Building Technologies HVAC Products. Series B
2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones
More informationFire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
More informationThermal flow sensors TA10-ZG8c and TA10-ZG9c for exact and stable, long-term measuring of lower flow velocities (Laminar Flow)
Thermal flow sensors TA10-ZG8c and TA10-ZG9c for exact and stable, long-term measuring of lower flow velocities (Laminar Flow) Drawing 8c Drawing 9c U391_TA10C_DoP_e_150421 www.hoentzsch.com 1 of 5 Measured
More informationW 36: Mastering complex tasks reliably
Lichtschranken W Photoelectric Baureihe switches WL - Photoelectric proximity switches, BGS Photoelectric reflex switches W : astering complex tasks reliably Through-beam photoelectric switches for temperatures
More informationRittal TopTherm fan-and-filter unit
Rittal TopTherm fan-and-filter unit System Climate Control More pressure. Higher air flow rates. 2 Assembly without tools Straightforward assembly, exchange and maintenance with no need for tools of any
More informationThe supplier and installer of the system should be approved by the local civil defence authority.
ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer
More informationVario-Series Accessories
Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates
More informationFrequency Converter Fv
2 Bosch Rexroth AG Electric Drives and Controls Documentation Brake chopper with up to 30 kw continuous braking power Easy to operate and service (detachable fan, LCD operating panel with copy function)
More informationShunt lock function 3066
Version: January 2004 Contents Alarm System Activation unit Deactivation unit Digital locking cylinder or Smart Relay 1.0 Method of Operation 4 1.1 General 4 1.2 Turning the Alarm System On 4 1.3 Turning
More informationIS76 Beacon with Ferrite Antenna Installation Manual
IS76 Beacon with Ferrite Antenna Installation Manual Edition: July 2009 Document N : 953-26a Page 1 of 9 Document No 953.26a IS76 Beacon with Ferrite Antenna: Installation Manual Edition: July 2009 Editor:
More informationFire alarm system EBL512 G3
Fire alarm system EBL512 G3 An analog addressable fire alarm system for early detection - without any unwanted alarms. Generation three G3. Internet: pesn.panasonic.se 2011-03-24 Page 1 of 6 The demands
More informationintelligent solutions
Lichtschranken W 8- Photoelectric Baureihe switches WL - Photoelectric proximity switches, BGS Photoelectric reflex switches Through-beam photoelectric switches W 8-: Integrated stateof-the-art technology
More informationJ TB/TW Temperature limiter, temperature monitor
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
More informationCOOL Shelf Quick Connect
Refrigeration equipment Shelf lighting High efficiency COOL QCS Quick-Connection-System Dimmable Various lengths Neutral White Warm White Pasta & Cheese Fresh Meat Packed Meat 1 A COOL Shelf Quick Connect
More informationModular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
More information