How to Specify an Augmented Category 6 Cabling System

Size: px
Start display at page:

Download "How to Specify an Augmented Category 6 Cabling System"

Transcription

1 How to Specify an Augmented Category 6 Cabling System 10GBASE-T - IEEE 802.3an is a specification for the transmission of ten gigabit Ethernet over existing Category 6 copper cables or a new standard of products called Augmented Category 6. It was published in September GBASE-T has a limited capability on existing Category 6 but for new installations the forthcoming Augmented Category 6 or Cat6 A is recommended. These standards come in two groups. The first gives methods of installing and testing cabling to understand their performance relative to 10GBASE-T requirements and the second group are product standards for the new range of Cat6 A products. The product standards are: Draft - ANSI/TIA/EIA-568-B.2-10 Transmission Performance Specifications for 4-pair 100 Ω Augmented Category 6 Cabling. Draft - ISO/IEC Edition 2.1 Information Technology Generic Cabling for Customer Premises. (Draft document number ISO/IEC JTC 1/SC 25 N 755.) Draft EN Amd 1 The test standards are: Draft - ISO/IEC Guidelines for Support of 10GBASE-T over Copper Balanced Pairs of Class E and Class F as per ISO/IEC 11801:2002 and IEEE802.3an. Draft EN ANSI/TIA-TSB-155 Additional Guidelines for 4-pair 100 Ω Category 6 Cabling for 10GBASE-T Applications. March At the time of writing, May 2007, only TSB 155 has been published (March 2007) but all the other product standards are expected before the end of Relevant Articles: Specifying 10 Gigabit Ethernet: Part 1 Specifying 10 Gigabit Ethernet: Part 2 10 Gigabit Ethernet - Questions & Answers

2 System specification The cabling system must be designed according to: EN :2002 Information Technology - Generic Cabling Systems -- Part 1: General Requirements and Office Areas. All components must meet the Category 6 A specification Draft - ANSI/TIA/EIA-568-B The cabling system must meet the Permanent Link and Channel performances defined in the draft standards as Class E A as a minimum. At least one product combination must be externally verified by a competent laboratory. The overall design must take into account any relevant portions of BS 8300 (access for the disabled) e.g. when selecting mounting heights for wall sockets. 2 Components Specification 2.1 Cable The cable must be four-pair Category 6 with a low-flammability sheath The cable must be of the following construction; foil screened pairs with an overall braid screen The cable must be 100% tested by the manufacturer The flammability performance must meet IEC as a minimum. 2.2 Connecting Hardware Patch Panels Must be 19 rack mounting, in exact multiples of 1U (44 mm) in height Cable termination must be Insulation Displacement Connectors (IDC) Front connectors to be 24 x RJ45 style IEC Electrical performance to be Category 6 A All connecting hardware must be shielded with a continuous metal screen Connectors Cable termination must be IDC Connectors to be RJ45 style IEC Electrical performance to be Category 6 A All connecting hardware must be shielded with a continuous metal screen.

3 2.2.3 Patch Leads Must be 27 AWG (STP) stranded, with low flammability sheath to IEC Connectors must be RJ45 style IEC Electrical performance to be Category 6 A. 3 Installation Specification 3.1 The cabling system must be procured from one manufacturer. 3.2 The cabling system must be installed according to the manufacturer s instructions. 3.3 Planning, quality control, documentation and earthing/bonding must be according to EN parts 1 and 2. External cables must be installed according to EN50174 part Earthing and bonding must be according to the manufacturer s instructions and EN , EN and BS % of the installed cables must be tested according to TSB Alien crosstalk testing is not required if screened construction cabling is used % of the test data must be reviewed by the manufacturer and approved by the manufacturer before any warranty certificate is released. 3.8 The Permanent Link must be tested to TSB 155 with a Level III cable tester set to Cat 6 A Permanent Link. A Cat 6 generic interface must be used on the tester. 3.7 Cabling must be tested in both directions and the results stored in an electronic database compatible with the tester manufacturer's cable management programme. 3.8 The cabling must be covered by a manufacturer s product and application warranty and installed by an installer accredited and trained by the manufacturer. Proof of training, which must be less than two years old, must accompany the tender. 3.9 A labelling and administration system must be designed into the cable system in line with EN or ISO or TIA/EIA Separation of power and data cables must be according to EN part 2 and BS 6701 except where local or national electrical safety regulations require a greater separation Mitigation installation techniques are not required due to the use of screened cables and components. 4 LAN Applications 4.1 Any communications protocol designed for use on a 100-ohm (nominal) characteristic impedance Class E A cabling system must operate satisfactorily on the installed cabling system. Satisfactory shall mean better than one in ten-tothe-power-of-ten bit error rate whilst in the presence of up to 3 V/m external interference over 500 MHz for at least thirty minutes.

4 4.2 LAN operation shall include, but not be limited to, ATM at 155 Mb/s, 622 Mb/s and 1.2 Gb/s. Gigabit Ethernet to IEEE 802.3ab and 10 Gb/s Ethernet to IEEE 802an. 4.3 Delay skew of the Permanent Link shall be better than 20 nanoseconds (typical) to ensure satisfactory video operation. 5 EMC Performance The structured cabling system shall comply with cable balance and EMC requirements of EN and ISO 11801:2002 and will not degrade the EMC performance of any electrical device connected to it. This facility shall be guaranteed by the manufacturer. 6 Reference to Standards BS 6701 Telecommunications Equipment and Telecommunications Cabling. Specification for Installation, Operation and Maintenance (2004). BS 7671 Requirements for Electrical Installations (IEE 16 th Ed). BS 8300 Design of Buildings and their Approaches to Meet the Needs of the Disabled. EN Information Technology, Generic Cabling Systems (2002). EN Information Technology, Cabling Installation. Parts 1, 2 (2000) and Part 3 (2003). EN Application of Equipotential Bonding and Earthing in Buildings with Information Technology Equipment. EN Information Technology - Cabling Installation - Testing of Installed Cabling (2002). EN Electromagnetic Compatibility (EMC) Generic Standards - Emission Standard for Residential, Commercial and Light-Industrial Environments. IEEE 802.3ab Physical Layer Specification for 1000 Mb/s Operation on Four Pairs of Category 5 or Better Balanced Twisted Pair Cable (1000BaseT), July IEEE 802.3an Physical Layer and Management Parameters for 10 Gb/s Operation. ISO/IEC Information Technology - Generic Cabling for Customer Premises. (2002). ISO Information Technology Implementation and Operation of Customer Premises Cabling. Part 1 Administration. Part 2 - Planning and Installation. Part 3 - Testing of Optical Fibre Cabling. IEC Flammability of a Single Vertical Cable. IEC Detail Specification for Connectors, 8 way. Test Methods and Related Requirements for use at Frequencies up to 200 MHz. IEC Generic Specification for Testing of Generic Cabling in Accordance with ISO/IEC Part 1. IEC Halogen Gas Emission. IEC Smoke Corrosivity.

5 IEC Smoke Density and Evolution. ISO 11801:2002 Information Technology Generic Cabling for Customer Premises. TIA/EIA 568-B Commercial Building Telecommunications Cabling Standard (2001 Addendum B2-1). TIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings.

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair Presentation; Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair 5 th April 2010 Paul Mathews MInstSMM, CCNA, MIEEE Global Channel Manager Media Types Physical Layer Cabling;

More information

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling

More information

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8 Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC by Paul Kish NORDX/CDT Chair TIA TR 41.8 Outline Market trends Standards development where we were where we are where we are going Beyond Category

More information

Specifying an IT Cabling System

Specifying an IT Cabling System Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your

More information

PerseveranceWorks. 38 Kingsland Road, London E2 8DD, UK

PerseveranceWorks. 38 Kingsland Road, London E2 8DD, UK PerseveranceWorks 38 Kingsland Road, London E2 8DD, UK Perseverance Works (PW) and Printing House Yard (PHY) are seeking a supplier for the provision of direct fibre access and data transport services

More information

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER Questions to Ask When Planning the Cabling Plant Planning a copper cabling plant to support 10Gbps transmission

More information

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems) Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems) Introduction The purpose of this document is to: 1) provide background information beneficial to specifiers

More information

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable June 10, 2010 Contributors: Yinglin (Frank) Yang CommScope, Inc. Charles Seifert Ixia Ethernet Alliance 3855 SW 153 rd

More information

Accelerating Light. Copper Cabling Solutions. Category 6A

Accelerating Light. Copper Cabling Solutions. Category 6A Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity

More information

Specification SFTP CAT6 Network Cable 23AWG CU

Specification SFTP CAT6 Network Cable 23AWG CU Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)

More information

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems Asef Baddar, RCDD Principal Engineer / Applications Engineering Supervisor Leviton Network Solutions C/7 - #1928 Table of Contents Background

More information

Cabling for 10GBASE-T and Beyond - A Tangled Web

Cabling for 10GBASE-T and Beyond - A Tangled Web Augmented Category 6 Category 6 A CLC TR 50173-99-1 TIA/EIA-TSB-155 TIA/EIA-568-B.2-10 ISO/IEC 11801 A1.1 Class E A Class F A ISO/IEC 11801 A1.2 Category 7 A ISO/IEC TR 24750 ISO/IEC 11801 Cabling for

More information

10 Gigabit Ethernet over copper: Unshielded, unprotected?

10 Gigabit Ethernet over copper: Unshielded, unprotected? Technical Article 10 Gigabit Ethernet over copper: Unshielded, unprotected? Copyright 2005 Reichle & De-Massari AG (R&M). All rights reserved. Transmission and reproduction of this publication or parts

More information

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks HIGHSPEED ETHERNET THE NEED FOR SPEED Jim Duran, Product Manager - Americas WHITE PAPER Molex Premise Networks EXECUTIVE SUMMARY Over the years structured cabling systems have evolved significantly. This

More information

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications 3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition

More information

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Introduction When network managers decide on a cabling system,

More information

Structured Cabling, Earthing & Equipotential Bonding

Structured Cabling, Earthing & Equipotential Bonding White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,

More information

CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE

CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE ORTRONICS : UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE Cindy Montstream, RCDD/NTS, EE, CPLP Director of elearning and Standards DATA COMMUNICATIONS Legrand, North America

More information

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module R&Mfreenet Advanced R&Mfreenet Advanced Cat 6 A Connection Module The R&Mfreenet Cat 6 A unshielded connection modules, part of the Advanced cabling system, are ideal for voice, fast data transmissions

More information

with Component Rating A Simple Perspective

with Component Rating A Simple Perspective Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America

More information

The Next Generation of Cable Technology. A technology primer from NORDX/CDT By, Eric d Allmen

The Next Generation of Cable Technology. A technology primer from NORDX/CDT By, Eric d Allmen A technology primer from NORDX/CDT By, Eric d Allmen Foreword The Telecommunications Industry Association (TIA) and the International Standards Organization (ISO/IEC) are actively engaged in the development

More information

Cabling Standards Update 2014

Cabling Standards Update 2014 Cabling Standards Update 2014 Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of Greek National Committee, CENELEC

More information

Innovative Connectivity Solution for Maximum Performance and Security

Innovative Connectivity Solution for Maximum Performance and Security Innovative Connectivity Solution for Maximum Performance and Security Financial Institutions Supports high performance backbone which enables transfer of real-time financial information through voice,

More information

The High Cost of a Low-Cost Cable Certification Tester

The High Cost of a Low-Cost Cable Certification Tester The High Cost of a Low-Cost Cable Certification Tester How much does it cost? That is typically the first question a cabling contractor or network owner asks when considering a new certification tester

More information

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4. Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s

More information

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI) within the Unified Physical Infrastructure SM (UPI) www.panduit.com WP-11 April 2007 Introduction With the ratification of the IEEE 802.3an 10GBASE-T copper standard, end users now have more media options

More information

How to Choose the Right Cable Category

How to Choose the Right Cable Category How to Choose the Right Cable Category Why do I need a different category of cable? Not too long ago, when local area networks were being designed, each work area outlet typically consisted of one Category

More information

HARTING Ethernet Cabling 4-poles Overview

HARTING Ethernet Cabling 4-poles Overview Overview RJ45 Connectors [on page 8] System cables [on page 10] Distribution modules and Outlets [on page 20] HARTING PushPull Connectors [on page 22] System cables [on page 24] Panel feed-throughs [on

More information

Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk

Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk Introduction At the IEEE 802.3 Working Group meeting in July of 2012, the Next Generation BASE-T Call for

More information

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and

More information

SMARTen 24 STP Patch Panels

SMARTen 24 STP Patch Panels Features Support 24 ports per 1U High performance, supportable bandwidth up to 500MHz supporting IEEE 802.3an 10Gbps application Conform to ANSI/TIA/EIA-568-B.2-10, ISO/IEC 11801 2.1 edition and CENELEC

More information

HARTING Ethernet Cabling 8-poles Overview

HARTING Ethernet Cabling 8-poles Overview Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs

More information

White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?

White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care? White Paper Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? TABLE OF CONTENTS 1. Introduction...3 2. Component Standards

More information

SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS

SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS STRUCTURED CABLING SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS INTRODUCTION In recent years, communications have taken on a crucial role in development for businesses. Communications

More information

Flexible and safe solutions, for decades. Cables for alarmand safety systems

Flexible and safe solutions, for decades. Cables for alarmand safety systems Flexible and safe solutions, for decades. Cables for alarmand safety systems 2 We offer the widest range of cables on the market for every kind of installation. It s all about reliability. It is always

More information

Gigabit Ethernet on Copper Cabling Infrastructures

Gigabit Ethernet on Copper Cabling Infrastructures Gigabit Ethernet on Copper Cabling Infrastructures Overview of Gigabit Ethernet (1000Base-T) Ethernet was developed by the Xerox Corporation in the early 1970 s and has emerged as the dominant networking

More information

AXIS T81B22 DC 30W Midspan

AXIS T81B22 DC 30W Midspan INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial

More information

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings Focus on the IBDN System 4800LX from NORDX/CDT Table of Contents Introduction... 3 Bandwidth and Information

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

Data Communications Competence Center

Data Communications Competence Center Importance of Cable Balance For Improving Noise Susceptibility Data Communications Competence Center DCCC03101702 July 11, 2007 Summary In a study of category 5e and category 6 UTP cables, a strong correlation

More information

BICSI :Building Industry Consulting Service International

BICSI :Building Industry Consulting Service International BICSI :Building Industry Consulting Service International - Lead the information and communications technology community with excellence in publications, education and knowledge assessment. - Advance our

More information

Screened cable and data cable segregation

Screened cable and data cable segregation December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;

More information

EN 50174-1 and EN 50174-2: 2008 Integrated standards for telecommunications cabling installation

EN 50174-1 and EN 50174-2: 2008 Integrated standards for telecommunications cabling installation EN 50173-1 EN 50173-2 EN 50173-3 EN 50173-4 EN 50173-5 EN 50346 EN 50174-1 EN 50174-2 EN 50174-3 DESIGN INSPECTION TESTING PLANNING INSTALLATION National Standards National Regulations EN 50174-1 and EN

More information

What are the requirements for a Home Network?

What are the requirements for a Home Network? What are the requirements for a Home Network? Setting up a computer network in your home is not rocket science but it pays to think about what you want/need before you start buying equipment or drilling

More information

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify

More information

SMARTen 24 UTP Patch Panels

SMARTen 24 UTP Patch Panels Features High density, 24 ports per 1U High performance, supportable bandwidth up to 500MHz supporting IEEE 802.3an 10Gbps application Special cap design for minimizing Alien Cross-Talk Conform to ANSI/TIA/EIA-568-B.2-10,

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61156-5 First edition 2002-03 Multicore and symmetrical pair/quad cables for digital communications Part 5: Symmetrical pair/quad cables with transmission characteristics up

More information

White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems

White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems Originally ratified by IEEE in 1999 and 2003 respectively, gigabit Ethernet (1000BASE-T) and power over Ethernet

More information

Category 6 UTP - Cabling System

Category 6 UTP - Cabling System AMP NETCONNECT Category 6 UTP Cabling System...... real Category 6 Performance, both on Component as well as on System level! Owing to the extreme high performance of the AMP NETCONNECT Category 6 UTP

More information

How To Get 40G Over Copper (Wired) And 40G On Coaxian (Wireless) Cable (Wired Coaxian) (Wired Cable) (Wireline) (Powerline) And 50G Over Coaxian Cable (Wire Coaxian

How To Get 40G Over Copper (Wired) And 40G On Coaxian (Wireless) Cable (Wired Coaxian) (Wired Cable) (Wireline) (Powerline) And 50G Over Coaxian Cable (Wire Coaxian Copper for Beyond 10GBASE-T David Zambrano Agenda Market Drivers Standards Cabling and Ethernet Field Test Considerations Agenda Market Drivers Standards Cabling and Ethernet Field Test Considerations

More information

Standard Buccaneer - Ethernet

Standard Buccaneer - Ethernet IP6 rated compliant PUR jacket on cable Shielded system shielded coupler Shroud on RJ45 Screw coupling Rewireable flex connector PCB mounted panel connector IDC termination panel connector Earth lead version

More information

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware for CAT 6A Connecting Hardware Written by: Antoine Pelletier Engineer, Global Cabling Products Intertek www.intertek-etlsemko.com 1-800-WORLDLAB Introduction The telecommunication industry recently achieved

More information

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,

More information

Category-6 / Class-E Cabling

Category-6 / Class-E Cabling Category-6 / Class-E Cabling IEEE 802 Tutorial July 7, 1998 San Diego, CA by: Luc Adriaenssens SYSTIMAX Systems Applications Director Bell Labs of Lucent Technologies How were the ISO Cat-6 Targets set?

More information

6000 Series Buccaneer

6000 Series Buccaneer Robust, instant connections for harsh environments 6000 Series Buccaneer - circular connectors that combine the ease of use of a push/pull coupling mechanism with proven environmental sealing. Available

More information

108-93018 05 APR 2016 Rev M

108-93018 05 APR 2016 Rev M Product Specification 108-93018 05 APR 2016 Rev M Copper LAN Cable 1. SCOPE 1.1. Content This specification describes the general requirements for CommScope copper LAN cable. 2. APPLICABLE DOCUMENTS The

More information

DEPARTMENTAL REGULATION

DEPARTMENTAL REGULATION U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies

More information

New Technology Developments and How They Impact Your Structured Wiring Choices

New Technology Developments and How They Impact Your Structured Wiring Choices New Technology Developments and How They Impact Your Structured Wiring Choices Author: Rob Wessels Vice President of Engineering Structured wiring has come a long way since the days when Category 3 and

More information

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard. WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of

More information

Gigabit Ethernet over fiber optic cable.

Gigabit Ethernet over fiber optic cable. 1000BaseT 1000BaseFX 100BaseTX 100BaseFX 100BaseLX 100BaseSX 100BaseT2 100BaseT4 100BaseTX 10Base2 10Base5 10BaseT ACR 1000 Mbps, 1 Billion bits per second data transmission over copper cabling. All four

More information

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

Industry Standards Activity Overview

Industry Standards Activity Overview Industry Standards Activity Overview TIA Most Recent Plenary Meeting: June 13-17, 2016 in Tigard, OR Updated: July 18, 2016 TR-42.1 Commercial Building Cabling: TSB-185 Environmental Classification (MICE)

More information

Security & Surveillance Cabling Systems

Security & Surveillance Cabling Systems Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.

More information

HARTING Ethernet Cabling 4-poles Overview

HARTING Ethernet Cabling 4-poles Overview Ethernet Cabling 4-poles Overview RJ45 Connectors [on page 8] System cables [on page 10] Distribution modules and Outlets [on page 20] Connectors [on page 22] System cables [on page 24] Panel feed-throughs

More information

Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council

Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Date: 6/19/2013 Version: 1.0 Prepared by: Gregory Cotten Department of General Services District

More information

428 MY HOME Structured cabling system for the home sector

428 MY HOME Structured cabling system for the home sector 428 MY HOME Structured cabling system for the home sector CONTENTS MY HOME Structured cabling system for the home sector General features. 384 General rules for installation. 400 Wiring diagrams. 404 Structured

More information

Cat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards.

Cat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards. Cat 5, 6 or 7? A University Standard for Structured Wiring. Background isolutions recently formed Incorporates all IT service providers within the University. Focus on all ICT needs of the user and the

More information

Trends and Standards In Cabling Systems

Trends and Standards In Cabling Systems Trends and Standards In Cabling Systems Agenda Trends and Standards in Intelligent Buildings And Data Center Trends Update RJ45 supports 10BASE T to 40GBASE T Enterprise LAN trends BYOD (Bring Your Own

More information

01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS

01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS . HARTING RJ INDUSTRIAL ETHERNET CONNECTORS Ethernet is is coming up to standard industrial interface. Therefore, automation devices such as controllers, sensors and actuators feature possess on one or

More information

TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report

TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report Peter L. Pondillo Standards Committee Chairman Corning Incorporated March 2012 Liz to update Fiber Optics LAN Section Overview: Part

More information

Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka

Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka What is a network? A computer network is two or more computers connected together using a telecommunication system for the purpose

More information

Implementing Fast Ethernet

Implementing Fast Ethernet Implementing Fast Ethernet R The Next Generation of Ethernet Fast Ethernet (also known as IEEE 802.3u or 100BASE-T) is quickly becoming the successor to Ethernet as the network topology of choice. Fast

More information

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission

More information

Cable Sharing in Commercial Building Environments

Cable Sharing in Commercial Building Environments Cable Sharing in Commercial Building Environments Reducing Cost, Simplifying Cable Management, and Converging Applications onto Twisted-Pair Media Cable sharing describes the practice of running more than

More information

Rutenbeck Network Connection Box Cat. 5, shielded. Cable installation. UAE Connection Box Cat. 5 Operating Instructions.

Rutenbeck Network Connection Box Cat. 5, shielded. Cable installation. UAE Connection Box Cat. 5 Operating Instructions. Rutenbeck Network Connection Box Cat. 5, shielded 1-gang, 1 x 8-pole Order No.: 0180 00 2-gang, 2 x 8-pole Order No.: 0178 00 1-gang, (especially for channel construction) Order No.: 0802 00 2-gang, (especially

More information

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Paul Vanderlaan Product Development Engineer Belden Presented at BICSI January 20, 1999 Introduction New Parameters involving

More information

SHEET 5 CABLE TELEVISION SYSTEM

SHEET 5 CABLE TELEVISION SYSTEM SHEET 5 CABLE TELEVISION SYSTEM TRADITIONAL TELEVISION AND IPTV INTRODUCTION Access to full digital, as an inevitable technological development, clearly demonstrates the place of Digital Communication

More information

Outdoor Carrier Class Shielded Ethernet Cable. Datasheet. Models: PRO, CARRIER, Connectors. Increase Performance. Extreme Weatherproof

Outdoor Carrier Class Shielded Ethernet Cable. Datasheet. Models: PRO, CARRIER, Connectors. Increase Performance. Extreme Weatherproof Datasheet Outdoor Carrier Class Shielded Ethernet Cable Models: PRO, CARRIER, Connectors Increase Performance Extreme Weatherproof ESD Damage Protection Extended Cable Support 1 2Datasheet Protect your

More information

Networks. The two main network types are: Peer networks

Networks. The two main network types are: Peer networks Networks Networking is all about sharing information and resources. Computers connected to a network can avail of many facilities not available to standalone computers: Share a printer or a plotter among

More information

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor... 1 CONTENTS 1000 GENERAL OVERVIEW

More information

Total Solutions Verification

Total Solutions Verification Total Solutions Verification 3rd Party Electrical Performance Testing Author: Tom Boucino Applications Engineer Uniprise Solutions CommScope has always designed cables with connectivity in mind. Our engineers

More information

Introduction to Data Centre Design

Introduction to Data Centre Design Introduction to Data Centre Design Barry Elliott BSc RCDD MBA CEng Earthing, grounding and bonding November 09 Earthing what s the point Safety from electrical hazards Reliable signal reference within

More information

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

AMP CO Plus Insert for Cat. 6 A Applications

AMP CO Plus Insert for Cat. 6 A Applications Product Specification 108-93039 10/Mar/2011 Rev F AMP CO Plus Insert for Cat. 6 A Applications 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP* CO Plus

More information

The Quality Connection. Industrial IT cabling ISO/IEC 24702 / EN 50 173-3

The Quality Connection. Industrial IT cabling ISO/IEC 24702 / EN 50 173-3 The Quality Connection Industrial IT cabling ISO/IEC 24702 / EN 50 173-3 LEONI Kerpen & HARTING worldwide LEONI Kerpen and HARTING... For more than 85 years now, LEONI Kerpen as one of the leading companies

More information

Simpler all over. Simpler all round. 500 MHz. 10 GB ether. fully shielded. Poe+ Cat.6 A. Data Voice. MFP8 Cat.6 A Field assembly RJ45 plug

Simpler all over. Simpler all round. 500 MHz. 10 GB ether. fully shielded. Poe+ Cat.6 A. Data Voice. MFP8 Cat.6 A Field assembly RJ45 plug Simpler all over. Simpler all round. No special tools required for field ASSEMBLY Cat.6 A 10 GB ether. 500 MHz fully shielded Poe+ Data Voice MFP8 Cat.6 A Field assembly RJ45 plug Less fuss. More flexibility.

More information

CCNA Discovery Chapter Four

CCNA Discovery Chapter Four CCNA Discovery Chapter Four By Chief Eng. Amna Ahmed Institute of Telecommunication amna_ahmed28@yahoo.com Modified by Vincenzo Bruno Hacklab Cosenza Chapter 4 Explain what the internet is Every day millions

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

Wireless and Wired Networking Specifications

Wireless and Wired Networking Specifications ImproMed LLC Wireless and Wired Networking Specifications For ImproMed Software Packages Revised May 22, 2013 2013 ImproMed, LLC. All rights reserved. No part of this publication may be reproduced, transmitted,

More information

Category 8 Cabling Standards Update

Category 8 Cabling Standards Update White Paper Category 8 Cabling Standards Update TIA TR42.7 Study Group for Class II Limits Contents 1 Background 3 2 Impact of this approval on Category 7 A cabling 3 3 Differences between Class I and

More information

WHITE PAPER December, 2001

WHITE PAPER December, 2001 Is Superior Essex Outside Plant Copper Cable Rated Category 3? The applicability of the Category 3 specification to outside plant cables is sometimes misunderstood. This white paper examines that issue,

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

Enhanced Category 5 Cabling System Engineering for Performance

Enhanced Category 5 Cabling System Engineering for Performance Engineering for Performance Table of Contents 2 Introduction 2 Where Did It Come From? 2 Enhanced Category 5 Performance What to Test The Link The Channel Don t Forget the Cable Assembly 4 Performance

More information

FIA FIA. Installation Standards - 2004. e-ready Building Next Generation IT infrastructures. ϕ The Cabling Partnership AGENDA

FIA FIA. Installation Standards - 2004. e-ready Building Next Generation IT infrastructures. ϕ The Cabling Partnership AGENDA Installation Standards - 2004 January 2004, Issue 1 Mike Gilmore Standards Activities Member: ISO/IEC JTC1 SC25 WG3: Generic Cabling ISO/IEC JTC1 SC25 Project Team: SOHO Convenor: ISO/IEC JTC1 SC25 WG3

More information

RTEX Cable 2015/10/1. Motor Business Unit Automotive & Industrial Systems Company Panasonic Corporation

RTEX Cable 2015/10/1. Motor Business Unit Automotive & Industrial Systems Company Panasonic Corporation RTEX Cable 2015/10/1 Motor Business Unit Automotive & Industrial Systems Company Panasonic Corporation Cable and Connector Page 2 2015/10/1 Rev. 5 Motor Business Unit, AIS Company The Kind of Ethernet

More information

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew jew@j-and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards

More information

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the

More information

IT Services Converged Network Installation Specification:

IT Services Converged Network Installation Specification: IT Services Converged Network Installation Specification: Author: Phil Gregory Status: Published Last Modified: 21 August 2015 Last Modified by: Phil Gregory Updates: Version Date (Initial) Comments 1.1401

More information

LAN Installation Handbook

LAN Installation Handbook ] LAN Installation Handbook LAN Installation Handbook Central Information Management Unit Office of the Prime Minister Version 1.0 April 2003 Contents Section 1 Introduction...1 Section 2 LAN Installation...3

More information

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs

More information