1 Procedure No.: SOP-0157 Page: 1 of 6 Preparer: Owner: Approver: Safety Safety Safety 1. PURPOSE The purpose of this procedure is to establish minimum standard practices for the monthly and annual inspection of the fire extinguishers located throughout our Midga Operations. 2. DEFINITIONS Each plant site shall initially place a fire extinguisher in a designated place (within 50 ft. of a fire hazard). As a guide, fire extinguishers should be mounted four feet from the floor. The location of these extinguishers shall be noted on a plant map and a description of the location of each fire extinguisher shall be noted in an appropriate log book. The map must have the name of the hazardous waste coordinator, their phone number, and emergency contact information (911). The extinguishers shall be numbered with a corresponding number placed at its designated location for control of replacement. Monthly Inspections: Each plant site will visually inspect fire extinguishers on a monthly basis and make sure that all of the following items are in compliance: 1) Location of extinguisher is in its adequate place. 2) No obstruction to access or visibility. 3) Operating instructions on nameplate legible and facing outward. 4) Safety seals and tamper indicators not broken or missing. 5) Examination for obvious physical damage, corrosion, leakage, or clogged nozzle. 6) Pressure gauge reading or indicator in the operable range or position. 7) Appropriate month of inspection shall be punched or recorded on fire extinguisher inspection tag. See attached document for above listed items in checklist format. It is recommended that this document be reviewed prior to each monthly inspection to ensure adequate and proper fire extinguisher inspection: 1. Annual Inspections: On an annual basis, each plant site will perform a maintenance check of each fire extinguisher located within that plant site. The following items shall be checked for compliance. 1)A thorough examination will be conducted of the three basic elements of the extinguisher; all mechanical parts, the extinguishing agent (to be determined by weighing the extinguisher and verifying weight is in range of gross weight range on extinguisher), and the means that the extinguishing agent is expelled from the extinguisher (making sure that the extinguisher is under full charge by examining the gauge, and hose is clear).

2 Procedure No.: SOP-0157 Page: 2 of 6 2) If necessary, the tamper seal can be removed by operating the pull pin or locking device. After the applicable maintenance procedures are completed, a new tamper seal shall be installed and any maintenance related items found to be in need of repair shall be replaced. A record shall be kept of each annual inspection of all fire extinguishers to include date of inspection, condition of extinguisher, and any repair or replacement of parts found to be defective and replaced. See attached document for above listed items in checklist format. It is recommended that this document be reviewed prior to each annual inspection to ensure adequate and proper annual extinguisher inspection. An Annual maintenance inspection tag can be placed on the extinguisher and the date and year of the inspection recorded on the tag or documentation maintained showing the inspection has been done on each extinguisher in service, including date inspected and competent person that did inspection, in place of a record list. 3. SCOPE This procedure shall apply to all sites in the Middle Georgia Operations. 4. PROCEDURE NOTE: Each plant site shall establish a location for additional fire extinguishers that can be used in an emergency for fire fighting purposes, or, for replacement of expelled or damaged extinguishers. Each employee shall be trained on the location of these additional fire extinguishers. If a fire extinguisher is found to be inoperable, damaged or in some other way does not meet the inspection standards in any monthly or annual inspection it shall be taken out of service and replaced immediately with an extinguisher of comparable size by the inspecting personnel from this stock of additional extinguishers. The expelled extinguisher shall be transported to the supply room for pick up by our fire extinguisher vendor for refill or service. The ultimate responsibility for the management of the fire extinguisher program within any plant site lies with the Production Superintendents for the Production Areas and the Maintenance Superintendents in the Maintenance Shops. The responsibility for the program within the labs lies with the QC Superintendent over that particular lab. Responsibility for the monthly inspections and annual inspections can be delegated by those listed above to the appropriate personnel of their choice. It is recommended by the Safety Department that this responsibility be shared on a monthly basis by different members of the crew so that as many members on a crew as possible become familiar with where the fire extinguishers are located in their immediate work area. It is recommended that the Annual Inspections be done by a competent person trained by the safety department.

3 Procedure No.: SOP-0157 Page: 3 of 6 Hydrostatic Testing: At intervals not exceeding those specified below, fire extinguishers shall be hydrostatically tested. The date of the hydrostatic test is stamped onto the metal shell of the extinguisher. In no case shall an extinguisher be recharged if it is beyond its specified hydrostatic test date. TYPE (Interval) TEST YEAR Carbon Dioxide 5 Dry Chemical, stored pressure, mild steel or aluminum shells 12 On the monthly inspections, any fire extinguisher that is found to be in need of a hydrostatic test should be returned to the storeroom and sent to the fire extinguisher contractor than handles our hydrostatic testing program for retest. NOTE: IF A FIRE IS ENCOUNTERED THAT RAISES ANY DOUBT AS TO WHETHER IT CAN BE CONTROLLED BY A FIRE EXTINGUISHER, IMMEDIATELY CONTACT THE FIRE DEPARTMENT BY PHONING 911, AND CONTACT THE AREA LEADER OR ON CALL PERSON IMMEDIATELY. DO NOT ENDANGER YOUR LIFE OR THE LIVES OF OTHERS TRYING TO CONTROL A FIRE THAT IS TOO INTENSIVE FOR A FIRE EXTINGUISHER.

4 Procedure No.: SOP-0157 Page: 4 of 6 FIRE EXTINGUISHER MONTHLY CHECKLIST The monthly inspection of fire extinguishers shall include a check of the following items. It is recommended that this checklist be reviewed prior to each monthly inspection to ensure adequate and proper inspection of fire extinguishers. 1. Location of extinguisher in its designated place 2. No obstruction to access or visibility 3. Operating instructions on nameplate legible and facing outward 4 Safety seals and tamper indicators not broken or missing 5. Examination for obvious physical damage, corrosion, leakage, or clogged nozzle 6. Pressure gauge reading or indicator in the operable range or position 7. Physically turn fire extinguisher upside down several times to reduce chemical powder packing. 8. Appropriate month of inspection shall be punched or recorded on Monthly fire extinguisher inspection tag.

5 Procedure No.: SOP-0157 Page: 5 of 6 FIRE EXTINGUISHER ANNUAL INSPECTION The annual inspection of fire extinguishers shall include a check of the following items. It is recommended that this checklist be reviewed prior to each annual inspection to ensure adequate and proper inspection and maintenance of fire extinguishers. 1. A thorough examination will be conducted of the three basic elements of the extinguisher; all mechanical parts, the extinguishing agent (to be determined by weighing the extinguisher and verifying weight is in range of gross weight range on extinguisher), and the means that the extinguishing agent is expelled from the extinguisher (making sure that the extinguisher is under full charge by examining the gauge, and hose is clear). 2. If necessary, the tamper seal can be removed to assure the pull pin or locking device is working properly. After the applicable maintenance procedures are completed, a new tamper seal shall be installed, if necessary, and any maintenance related items found to be in need of repair shall be replaced. 3. A record shall be kept of each annual inspection of all fire extinguishers to include date of inspection, condition of extinguisher, and any repair or replacement of parts found to be defective. An Annual maintenance inspection tag can be placed on the extinguisher and the date and year of the inspection recorded on the tag, in place of a record being kept.

6 Procedure No.: SOP-0157 Page: 6 of 6 5. RESPONSIBILITIES Requirements of fire extinguisher inspection of the Mine Safety and Health Administration are as follows: Monthly: Fire extinguishers shall be inspected visually at least once a month to determine that they are fully charged and operable. Annually: At least once every twelve months, maintenance checks shall be made of mechanical parts, the amount and condition of extinguishing agent and expellant, and the condition of the hose, nozzle, and vessel to determine that the fire extinguisher will operate effectively. 6. RELATED DOCUMENTS Section Revision Revised By Date Revised All SOP Revision EM 8/11/2013 All Program Review KMH 8/10/2014

FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES

FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES Fire and Life-Safety Group (FLS) FLS has organized the following information to act as a guideline/checklist for any inspection, maintenance,

More information

Fire Safety Requirements for Rehabilitation Agencies

Fire Safety Requirements for Rehabilitation Agencies DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality/Survey

More information

All You Ever Wanted to Know About Fire Extinguishers...

All You Ever Wanted to Know About Fire Extinguishers... All You Ever Wanted to Know About Fire Extinguishers... There are basically four different types or classes of fire extinguishers, each of which extinguishes specific types of fire. Newer fire extinguishers

More information

STORED PRESSURE STAINLESS STEEL

STORED PRESSURE STAINLESS STEEL STORED PRESSURE STAINLESS STEEL WATER FIRE EXTINGUISHERS Model 240-2-1/2 Gallon OWNER'S SERVICE MANUAL NO. 05601 INSPECTION, MAINTENANCE AND RECHARGE All fire extinguishers should be installed, inspected

More information

RISK MANAGEMENT QUARTERLY BUILDING REPORT Fire Safety Self -Inspection Checklist

RISK MANAGEMENT QUARTERLY BUILDING REPORT Fire Safety Self -Inspection Checklist RISK MANAGEMENT QUARTERLY BUILDING REPORT Fire Safety Self -Inspection Checklist Quarter: Year Fall Building: Phone: Winter Spring Safety Coordinator: Date: Summer Use the Checklist to conduct your own

More information

Six Monthly Servicing of Fire Extinguisher on Commercial Vessels.

Six Monthly Servicing of Fire Extinguisher on Commercial Vessels. Marine Safety Notice to Industry Number: 34 Date of Issue: 17 January 2012 Six Monthly Servicing of Fire Extinguisher on Commercial Vessels. This Notice to Industry is to clarify the requirements for the

More information

Inspection, Testing and Maintenance

Inspection, Testing and Maintenance Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information

More information

INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303

INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303 WATER MIST HAND PORTABLE FIRE EXTINGUISHERS Model B270 ¾ Gallon Model B272 2 ½ Gallon INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 6303 All fire extinguishers should be installed, inspected

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

Model Safety Program

Model Safety Program Model Safety Program DATE: SUBJECT: Fire Extinguisher Program REGULATORY STANDARD: OSHA 29 CFR 1910.157 NFPA 10 RESPONSIBILITY: The company Safety Officer is. He/she is solely responsible for all facets

More information

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS 1.0 PURPOSE 1.1 To provide an overview of fire extinguisher use

More information

Minnesota State Department of Public Safety

Minnesota State Department of Public Safety Minnesota State Department of Public Safety 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us Inspection

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use. Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections

More information

To: All Shipowners, Ship Managers, Ship Masters and Classification Societies

To: All Shipowners, Ship Managers, Ship Masters and Classification Societies 海 事 處 船 舶 事 務 科 香 港 中 環 統 一 碼 頭 道 38 號 海 港 政 府 大 樓 ---------- 香 港 郵 箱 4155 號 MARINE DEPARTMENT Shipping Division Harbour Building 38 Pier Road, Central, Hong Kong ----------- G.P.O.Box 4155 網 站 Website

More information

Formal Interpretation NFPA 10. Portable Fire Extinguishers. 2013 Edition

Formal Interpretation NFPA 10. Portable Fire Extinguishers. 2013 Edition Reference: 5.5.5 and 6.6.1 F.I. No.: 10-02-2 Background:, subsection 5.5.5 requires that fire extinguishers be provided for the protection of cooking appliances that use combustible cooking media (vegetable

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Fire Protection Systems, Appliances and Compressed Gas Cylinders Periodic Maintenance, Inspection and Testing

Fire Protection Systems, Appliances and Compressed Gas Cylinders Periodic Maintenance, Inspection and Testing Fire Protection Systems, Appliances and Compressed Gas Cylinders Periodic Maintenance, Inspection and Testing Notice to Shipowners, Ship Operators, Managers, Masters, Owners Representatives and Recognised

More information

Fire Extinguishers. A Health and Safety Guideline for Your Workplace. Fire Extinguishing Methods. Introduction. Types of Extinguishers

Fire Extinguishers. A Health and Safety Guideline for Your Workplace. Fire Extinguishing Methods. Introduction. Types of Extinguishers A Health and Safety Guideline for Your Workplace Introduction Fire extinguishers are designed to put out or control small fires. A small fire, if not checked immediately, will soon spread out of control.

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY

THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY Office of Deputy Commissioner of Maritime Affairs THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY Marine Notice FIR-001 Rev. 06/12 TO: SUBJECT: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT

More information

FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie

FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion

More information

APPENDIX 2-3 PCAPP EDS INSPECTION LOG SHEETS

APPENDIX 2-3 PCAPP EDS INSPECTION LOG SHEETS APPENDIX 2-3 PCAPP EDS INSPECTION LOG SHEETS Pueblo Chemical Depot Pueblo Chemical Depot (This page intentionally left blank.) PCAPP EDS Daily (When in Use) Operational Inspection Checklist EXAMPLE Inspected

More information

SERVICE MANUAL NO. 14425 for AMEREX HALOTRON I HAND PORTABLE CLEAN AGENT FIRE EXTINGUISHERS (FOR NON-RESIDENTIAL APPLICATIONS)

SERVICE MANUAL NO. 14425 for AMEREX HALOTRON I HAND PORTABLE CLEAN AGENT FIRE EXTINGUISHERS (FOR NON-RESIDENTIAL APPLICATIONS) SERVICE MANUAL NO. 14425 for AMEREX HALOTRON I HAND PORTABLE CLEAN AGENT FIRE EXTINGUISHERS (FOR NON-RESIDENTIAL APPLICATIONS) * * * HAVE EXTINGUISHERS RECHARGED IMMEDIATELY AFTER ANY USE * * * All fire

More information

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These

More information

REPUBLIC OF ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT SHIPS, AND RECOGNIZED ORGANIZATIONS

REPUBLIC OF ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT SHIPS, AND RECOGNIZED ORGANIZATIONS REPUBLIC OF Marine Notice THE MARSHALL ISLANDS No. 2-011-14 OFFICE OF THE MARITIME ADMINISTRATOR Rev. 2/12 TO: SUBJECT: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT SHIPS, AND RECOGNIZED

More information

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book:

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book: Fire Safety Log Book Premises Name: Premises Address: Date From: Date To: Location of Log Book: CONTENTS PART 1 FIRE SAFETY ADVICE 1 PART 2 FIRE PRECAUTIONS 2 Section 1 Guidance on Fire Risks and Preventative

More information

Emergency Evacuation Plan: 232 King St.

Emergency Evacuation Plan: 232 King St. Emergency Evacuation Plan: 232 King St. Effective Date: July 2003 Revisions: 0 Approved on: April 20, 2004 Table of Contents 1.0 Building Resources... 1 2.0 Human Resources... 2 3.0 Definitions... 3 4.0

More information

PANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-281

PANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-281 PANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-281 PanCanal Building Albrook, Panama City Republic of Panama Tel: (507) 501-5355 jortega@segumar.com To: Ship-owners/Operators, Company Security

More information

CANTON FIRE DEPARTMENT

CANTON FIRE DEPARTMENT CANTON FIRE DEPARTMENT Dean Floyd Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES FIRE PREVENTION CHECKLIST- To review prior to your inspection. 1. Is the address of your property

More information

TECHNICAL ADVISORY BULLETIN

TECHNICAL ADVISORY BULLETIN RISK CONTROL AND CLAIM ADVOCACY PRACTICE TECHNICAL ADVISORY BULLETIN November 2014 www.willis.com FIRE PUMP TESTING Fire pumps are a critical part of a fire protection system, especially when they are

More information

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES Reference: National Fire Protection Association (NFPA) Pamphlet No. 58 Liquefied Petroleum Gas Code, 2001, Chapter 11 Type of Facility: Petroleum

More information

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the

More information

FIRE PREVENTION PLAN

FIRE PREVENTION PLAN FIRE PREVENTION PLAN 1 FIRE PREVENTION PLAN OSHA s Fire Prevention Plan regulation, found at 29 CFR 1910.38(b) and 29 CFR 1926.24, requires Northern Clearing, Inc. to have a written fire prevention plan

More information

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety

More information

PANAMA MARITIME AUTHORITY

PANAMA MARITIME AUTHORITY PANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-226 PanCanal Building Albrook, Panama City Republic of Panama Tel: (507) 501-5000 segumar@segumar.com To: Ship-owners/Operators, CSO, Legal Representatives

More information

FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES

FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES Insert Picture of Building FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES Address: Lock Box Location: Fire Safety Plan Location: Approved: Fire Department (dd /mm/yyyy) Building Owner (dd /mm/yyyy) Reviewed

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND

More information

Automatic fire-extinguishing systems for commercial cooking

Automatic fire-extinguishing systems for commercial cooking Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and

More information

PERFORMANCE AT HAND. RED LINE Hand Portable Fire Extinguishers

PERFORMANCE AT HAND. RED LINE Hand Portable Fire Extinguishers PERFORMANCE AT HAND RED LINE Hand Portable Fire Extinguishers MODEL 5 The Model 5 has a slim design for use on vehicles and machinery where space is limited. Typical applications include small trucks,

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect

More information

Portable Fire Extinguisher Presentation

Portable Fire Extinguisher Presentation Slide 1 Fire Extinguisher Training A requirement of all Clemson University Employees as mandated by OSHA: Portable fire extinguishers. - 1910.157 Welcome to the Clemson University Online Fire Extinguisher

More information

SODIUM CHLORIDE FOR COMBUSTIBLE METAL FIRES FACTORY MUTUAL APPROVED RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE

SODIUM CHLORIDE FOR COMBUSTIBLE METAL FIRES FACTORY MUTUAL APPROVED RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE OWNERS SERVICE MANUAL NO. 08220 INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS for AMEREX MODEL 570/B570 30 POUND (3.6 KG) CLASS D STORED PRESSURE FIRE EXTINGUISHER SODIUM CHLORIDE FOR COMBUSTIBLE

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

LIFE CYCLE COST ANALYSIS OF ELECTRONIC C58655 Page 1 MONITORING OF PORTABLE EXTINGUISHERS January 3, 2013 DRAFT FINAL

LIFE CYCLE COST ANALYSIS OF ELECTRONIC C58655 Page 1 MONITORING OF PORTABLE EXTINGUISHERS January 3, 2013 DRAFT FINAL LIFE CYCLE COST ANALYSIS OF ELECTRONIC C58655 Page 1 MONITORING OF PORTABLE EXTINGUISHERS January 3, 2013 DRAFT FINAL LIFE CYCLE COST ANALYSIS OF ELECTRONIC MONITORING OF PORTABLE FIRE EXTINGUISHERS LIFE

More information

A Self-Audit of Your Current Campus Security Systems

A Self-Audit of Your Current Campus Security Systems A Self-Audit of Your Current Campus Security Systems Security Solutions for Education, Business & Public Safety Free Consultations on ID Card Systems, Access Control, Call Recording, Video Surveillance,

More information

Safety & Risk Management Policies and Procedures

Safety & Risk Management Policies and Procedures Safety & Risk Management Policies and Procedures Title: Emergency Eye Wash & Shower Policy Date: August 2013 Rationale: The Occupational Safety and Health Administration (OSHA 29CFR 1910.151) requires

More information

Commercial Fire Inspections

Commercial Fire Inspections Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated

More information

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder. Page 1 of 5 COMPRESSED GASES A compressed gas is defined as any mixture of gases in a container with a pressure exceeding 40 psi. at 70 o F, or 104 psi. at 130 o F; or any flammable liquid with an absolute

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

On-Line Fire Extinguisher Training

On-Line Fire Extinguisher Training On-Line Fire Extinguisher Training The USC Fire Safety Office is delighted you have chosen to take the on-line version of our fire extinguisher training. This power-point presentation will give you some

More information

Contingency Plan. Facility Name

Contingency Plan. Facility Name Contingency Plan Facility Name This plan is reviewed annually and amended whenever changes occur that will significantly affect the ability of this facility to respond to an emergency situation. This includes

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

FIRE SAFETY RECORD OF TESTS LOGBOOK

FIRE SAFETY RECORD OF TESTS LOGBOOK FIRE SAFETY RECORD OF TESTS LOGBOOK PREMISES ADDRESS: Responsible person AN INTRODUCTION TO YOUR LOG BOOK The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for a premises to

More information

Civil Engineering Sector Labour-Management Health and Safety Committee

Civil Engineering Sector Labour-Management Health and Safety Committee PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION SITES Civil Engineering Sector Labour-Management Health and Safety Committee July 2008 PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION

More information

Mobile Equipment Safety

Mobile Equipment Safety Mobile Equipment Safety PLANNING THE JOB Hazard Assessment DO YOU HAVE THE RIGHT EQUIPMENT? ARE THERE HAZARDS TO BE AVOIDED? IS THE GROUND AREA STRONG ENOUGH TO SUPPORT THE EQUIPMENT? ARE THERE ANY UNUSUAL

More information

SAFETY - LIFE SAVING RULES MECHANICAL ISOLATION CAT A-1 SOP #3

SAFETY - LIFE SAVING RULES MECHANICAL ISOLATION CAT A-1 SOP #3 SUNCOR ENERGY PRODUCTS DISTRIBUTION TERMINAL OPERATING MANUAL STANDARD OPERATING PROCEDURE SAFETY - LIFE SAVING RULES Verify isolations of hazardous energy before any work begins. Date Issued: February

More information

Maintaining Fire Protection Systems

Maintaining Fire Protection Systems Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars

More information

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority

More information

(1) Acceptable means having been inspected by the Commissioner or his/her representative and approved for the intended usage.

(1) Acceptable means having been inspected by the Commissioner or his/her representative and approved for the intended usage. RULES AND REGULATIONS FOR INSTALLATION, INSPECTION, RECHARGING, REPAIRING, SERVICING AND TESTING OF PORTABLE FIRE EXTINGUISHERS OR FIRE SUPPRESSION SYSTEMS CHAPTER 120-3-23 TABLE OF CONTENTS 120-3-23-.01

More information

Town of Bellingham Fire Department

Town of Bellingham Fire Department Town of Bellingham Fire Department OFFICE OF THE Fire Prevention Division Captain Robidoux- jrobidoux@bellinghamma.org Lieutenant Bangma- jbangma@bellinghamma.org Fire Safety Inspection Guidelines for

More information

Greater Manchester Fire and Rescue Service

Greater Manchester Fire and Rescue Service Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY

More information

TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007

TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007 TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES 301.010 ANNUAL SERVICE TEST FOR FIRE HOSE EFFECTIVE: OCTOBER 2007 The Department will test all fire hose annually. The testing of fire hose determines its serviceability.

More information

Pharmaceutical Wholesaler Site Inspection Checklist

Pharmaceutical Wholesaler Site Inspection Checklist Pharmaceutical Wholesaler Site Inspection Checklist Date and time of inspection: Legal business name and plant name: Location (address): Phone number: Fax number: Email address: Web site URL: Contact Person:

More information

Kroger Manufacturing Trailer Seal Policy Revised 09/03/10

Kroger Manufacturing Trailer Seal Policy Revised 09/03/10 Kroger Manufacturing Trailer Seal Policy Revised 09/03/10 1 Inbound Supplier After the product is loaded and the trailer doors are closed, the supplier (or shipping warehouse) is responsible for affixing

More information

15GAL STEEL OIL DRAIN WITH 110V PUMP

15GAL STEEL OIL DRAIN WITH 110V PUMP 15GAL STEEL OIL DRAIN WITH 110V PUMP OWNER S MANUAL WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety

More information

CHAPTER 120-3-23 TABLE OF CONTENTS

CHAPTER 120-3-23 TABLE OF CONTENTS THE RULES OF THE SAFETY FIRE COMMISSIONER ARE HEREBY FURTHER AMENDED BY ADDING A NEW CHAPTER 120-3-2 3 E N T I T L E D RULES AND REGULATIONS FOR INSTALLATION; INSPECTION; RECHARGING, REPAIRING, SERVICING

More information

Fire Safety Risk Assessment Checklist for Residential Care Premises

Fire Safety Risk Assessment Checklist for Residential Care Premises Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

External Visual Inspection Form

External Visual Inspection Form Tank ID Code Part 1 (a): Information on Registered Facility Name of Registered Facility: Address: Town: Postal Code: Province: Phone Number: Person Conducting the Inspection: Transport Canada Facility

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

Safety Manual For Overhead Crane Operators

Safety Manual For Overhead Crane Operators Safety Manual For Overhead Crane Operators Contents Forward ---------------------------------------------------------------1 Qualifications---------------------------------------------------------1 Certification

More information

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1 Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers

More information

OSHA & Restaurants: Top 10 Frequently Cited Violations from October 2008 September 2009 for SIC Code 5812 Eating and Drinking Places

OSHA & Restaurants: Top 10 Frequently Cited Violations from October 2008 September 2009 for SIC Code 5812 Eating and Drinking Places OSHA & Restaurants: Top 10 Frequently Cited Violations from October 2008 September 2009 for SIC Code 5812 Eating and Drinking Places www.marsh.com Discussion Frequently Cited OSHA Regulations Current Penalty

More information

UCLA - Compressed Gas Cylinder Storage and Handling

UCLA - Compressed Gas Cylinder Storage and Handling UCLA - Compressed Gas Cylinder Storage and Handling Purpose UCLA is committed to provide safety guidelines concerning the handling and use of portable compressed gas cylinders. Compressed gases represent

More information

Contingency Plan. Community College of Denver - Auraria Campus Facility Name

Contingency Plan. Community College of Denver - Auraria Campus Facility Name Contingency Plan Community College of Denver - Auraria Campus Facility Name This plan is reviewed annually and amended whenever changes occur that will significantly affect the ability of this facility

More information

Inspection and Testing Program Fire Protection Equipment

Inspection and Testing Program Fire Protection Equipment I. Introduction Inspection and Testing Program Fire Protection Equipment State of Minnesota Emergencies seldom give warning before they strike. Thus, it is essential that fire protection equipment be inspected,

More information

Texas Department of Insurance. Fire Safety. Provided by. Workers Health & Safety. Pub. No. HS01-028D (7-08)

Texas Department of Insurance. Fire Safety. Provided by. Workers Health & Safety. Pub. No. HS01-028D (7-08) Texas Department of Insurance Provided by Workers Health & Safety Pub. No. HS01-028D (7-08) A fire safety plan is an essential part of any workplace safety program. In fact, the Occupational Safety and

More information

This program is listed as a mandatory inspection item on the MnOSHA Investigation Checklist, Item 7D.

This program is listed as a mandatory inspection item on the MnOSHA Investigation Checklist, Item 7D. Standard: Summary: Coverage: Workplace Accident and Injury Reduction Program RESOLUTION NO# 0809-88 Minnesota Statutes 182.653, A Workplace Accident and Injury Reduction Program Minnesota Rules 5205.1500,

More information

PPG SUPPLIER DEVELOPMENT ASSESSMENT

PPG SUPPLIER DEVELOPMENT ASSESSMENT Supplier: Address: Products: Assessment Date: Assessment Team: Certification: Supplier Contacts Position E-mail Phone General Comments: Assessment Results Summary Sections Non-conformity Action Point Quality

More information

Supplier/ Vendor Evaluation Form

Supplier/ Vendor Evaluation Form . Dated 1. General: Supplier/ Vendor Evaluation Form i. Name of Supplier/ Vendor: i Address of Supplier/ Vendor: Contact Person: Phone. v. Fax. v vi ix. Email: Web Address: Year of Establishment: Facility

More information

Emergency Eyewash and Drench Shower Program

Emergency Eyewash and Drench Shower Program Emergency Eyewash and Drench Shower Program Document Number: Effective Date: Revision Date: 7-24-14 1.0 Purpose and Applicability 1.1 The purpose of this program is to ensure that all safety eyewashes

More information

COLUMBUS STATE COMMUNITY COLLEGE EMPLOYEE SAFETY MANUAL

COLUMBUS STATE COMMUNITY COLLEGE EMPLOYEE SAFETY MANUAL COLUMBUS STATE COMMUNITY COLLEGE EMPLOYEE SAFETY MANUAL HAZARDOUS MATERIAL MANAGEMENT Effective October 15, 1995 Page 1 of 4 Updated August, 2008 Revised August, 2009 A. Columbus State Community College

More information

Routine and Emergency Boiler Operation

Routine and Emergency Boiler Operation Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here

More information

FIRE EXTINGUISHER TRAINING

FIRE EXTINGUISHER TRAINING FIRE EXTINGUISHER TRAINING Fire safety, at its most basic, is based upon the principle of keeping fuel sources and ignition sources separate. Three things must be present at the same time to produce fire:

More information

Restaurant & café guide

Restaurant & café guide 'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers

More information

QuickAir - 5, - 10 Minute Emergency Escape Breathing Apparatus. Operating Manual

QuickAir - 5, - 10 Minute Emergency Escape Breathing Apparatus. Operating Manual QuickAir - 5, - 10 Minute Emergency Escape Breathing Apparatus Operating Manual Table of Contents 1 General... 2 1.1 Purpose... 2 1.2 Description... 2 2 Operation... 3 2.1 Pre-donning Inspection... 3 2.1.1

More information

Machine/Woodworking Shop The Basic Rules

Machine/Woodworking Shop The Basic Rules Machine/Woodworking Shop The Basic Rules 1. Eye protection or face shields are required when working in the shop. A selection of protective goggles and safety glasses are available in the shop. The eyeglasses

More information

MONARCH FIRE PROTECTION DISTRICT

MONARCH FIRE PROTECTION DISTRICT MONARCH FIRE PROTECTION DISTRICT 13725 OLIVE BLVD., CHESTERFIELD, MO 63017 314-514-0900, EXT. 309 fireprevention@monarchfpd.org www.monarchfpd.org TENT / BOOTH REQUIREMENTS To help insure the safety, health

More information

Code Compliance Guideline: Swimming Pool Chemicals

Code Compliance Guideline: Swimming Pool Chemicals A publication of Fairfax County, Virginia CODE COMPLIANCE GUIDELINE SWIMMING POOL CHEMICALS AND FIRE SAFETY REQUIREMENTS RELATED TO POOL OPERATIONS This publication outlines the Fire Prevention Code requirements

More information

Waste Management Log Book

Waste Management Log Book Waste Management Log Book Web address: www.ehs.psu.edu Designated Accumulation Area: Building & Room Number Location in Room Supervisor: E-mail Individual designated to ensure procedures are followed:

More information

Office of the State Fire Marshal. Fire Rated Doors

Office of the State Fire Marshal. Fire Rated Doors Office of the State Fire Marshal Fire Rated Doors Fire Rated Doors These doors serve a purpose. They are manufactured in a way that is to help reduce the spread of fire and smoke. Fire rated doors allow

More information

Fire Prevention Plan for Flynn Hall 1648 Musketeer Drive

Fire Prevention Plan for Flynn Hall 1648 Musketeer Drive Audit and Risk Management and Xavier Police Fire Prevention Plan for Flynn Hall 1648 Musketeer Drive Xavier University October 12, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Fire Prevention

More information

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-

More information