EMP Effects on Protection and Control Systems
|
|
- Emery Stafford
- 7 years ago
- Views:
Transcription
1 EMP Effects on Protection and Control Systems Copyright SEL 2014
2 Overview EMP description and effects on protection and control systems EMP standards for C4 buildings Present EMC standards and protection for protection and control systems Relays and IEDs in general Panels and Control Houses Cables Possible changes to present design for better EMP protection Testing requirements and preliminary results
3 EMP Threat High Altitude Electromagnetic Pulse (HEMP) Nuclear burst, very high altitude (>30km, effects known since 60 s experiments >400km) High Power Microwave (HMP) or Intentional Electromagnetic Interference (IEMI) Non-explosive weapons, repeatable pulses directed by antennas, much smaller intensity and area
4 EMP Effects and Waveforms Strong Electric and Magnetic Fields Voltages and currents induced on metallic conductors Possible disruption or damage to electric or electronic equipment Simultaneous effects over wide area
5 EMP Effects on Substation Control Houses, Panels and IEDs Similar to harsh electromagnetic events and environments found in power systems Lighting strikes, RFI, HV surge events, strong magnetic fields during short circuits, etc. Possibly higher severity and different frequencies E1 may affect IEDs at the circuit board level and couple with shorter conductors (1-10m), E2 and E3 affects longer conductors and lines (km, several seconds). Biggest concern conductors from substation yard to control building
6 EMP Protection at IED Level Power systems protection and control standards for IEDs are much more robust than commercial or even industrial equipment. Specify highest severity levels listed in present standards Select products that have been designed to exceed these standards
7 SEL-311C Tested at US Army s Picatinny Arsenal in New Jersey RF from 100 MHz to 4 GHz at power levels from 25 to 1000 volts per meter (Mil-Std 461 ask for 50V/m only)
8 SEL-311C at US Army s Picatinny
9 SEL-311C at US Army s Picatinny SEL-311C Analog Measurements During IEMI In Tolerance Out of Tolerance Field Strength (V/m) Frequency (MHz) No damage, out of tolerance may not lead to relay missoperations if applied with best engineering practices
10 Military standards EMP Standards MIL-STD A 1998 High Altitude Electromagnetic Pulse Protection for Ground-Base C4I Facilities Performing Critical Time-Urgent Missions IEC SC 77C
11 EMP Hardening / Enclosure Facility shield / Electromagnetic barrier Faraday Cage: Metallic continuous conductive enclosure closed on all wall, ceiling and floor. Continuously welded, qualified procedures and personal Minimize points of entry (POEs) Equipotential ground plane
12 Control Houses and Systems for EMP SEL has not designed EMP shielded control houses No utility customer requirements IEC standards recently released Present control house design and IED technologies already hardened vs. other types of electromagnetic effects Major design changes would be required to meet HEMP standards Test and validation needs special equipment
13 Present Control Houses Shield Several control house designs provide external metallic shield
14 Present Control Houses Shield Sometimes provide 2 or 3 metallic barriers that attenuate electromagnetic fields (not welded)
15 Control Houses Hardened Shield for EMP Military Std A. Faraday Cage Inside Metal or Concrete Power Core Change of steel gauge and continuously welded
16 EMP Hardening / Enclosure Protection and Control Panels Closed cabinets provide extra shielding for IEDs
17 EMP Hardening / POEs Architectural entryways, two shielded doors, interlocks (or unprotected when open). No windows. Mechanical POE like piping and ventilation Waveguide-below-cutoff
18 EMP Electrical POEs Main threat to substation control rooms, coupling at conductors to yard Each power, communication and control conductor (shielded or unshielded) shall be provided with transient suppression / attenuation devices Surge arresters, filters, non-linear elements, etc Exceptions for conductors on specific conditions of conduit shielding 1-10Amp, 250m (820ft) buried metallic conduit or 31m (102ft) non-buried metallic conduit
19 Cable Entry Protection Mil Std 188
20 Control Houses POEs Modify vents to waveguide-below-cut-off Shielded doors Each conductor protected or each conduit shall be welded to shield Limit number of control conductors entering control building from substation yard
21 Cable Entry Protection Individual Cable EMC protection
22 Transmission Yard Conductors
23 Minimize Electrical Points of Entry Using Fiber Optics Peer to peer technologies available Serial Mirrored Bits / Ethernet GOOSE Process Bus Technologies under development for analog signals (CTs & PTs) Reduce commissioning or substation upgrade time, copper cost, cable trench cost and size and POEs Avoid cable or conduit protection and Current Pulse Injection Test Increase fiber and field cabinet cost, cabinet must be totally closed (NEMA 4) and hardened for EMP with EMC gaskets
24 Hard Wire Process Bus 72 CC for analog inputs 60 CC for discrete inputs Traditional injection testing
25 Fiber Process Bus 7 fiber for analog/discrete or Process bus optional, relays in FTK wired to each CT/PT Traditional injection testing
26 Remote I/O Near Breakers and Transformers
27 Shielding Effectiveness Test
28 Pulse Current Injection Test
29 Cable Entry Protection Testing for conducted current
30 Preliminary Testing to Control House Test with control house as is Only shielding effectiveness test 30 to 40dB average attenuation from 10kHz to 10GHz Conventional doors, cable entries and louvers are the main leakage. 10 to 20db attenuation
31 Summary Understand customer requirements for EMP, review standards for utility applications Use substation hardened IEDs for relays, controls and HMI computers Reduce electrical POEs with fiber optics to reduce yard conduits and their welded connections to control house or individual cable protections Significant costs associated with manufacturing a control building with integrated faraday cage. Specialized test procedure and equipment for MIL standard compliance would be required.
Radio Frequency Interference (RFI) Shielding Principles
Radio Frequency Interference (RFI) Shielding Principles 1.0 Introduction The purpose of this document is to provide Krieger Specialty Products clients and personnel information pertaining to shielding
More informationGS 1 Protecting Data Centers Against Intentional Electromagnetic Interference and High Altitude Electromagnetic Pulse
GS 1 Protecting Data Centers Against Intentional Electromagnetic Interference and High Altitude Electromagnetic Pulse Data Center Facility Infrastructure Threat and Mitigation Considerations 1 GS 1 Protecting
More informationEMP... Electromagnetic Pulse. one of the greatest threats facing technology-driven clients today
EMP... Electromagnetic Pulse one of the greatest threats facing technology-driven clients today Do you remember in the movie Oceans Eleven when Las Vegas was rendered powerless by an EMP event? That could
More informationEMC Standards: Standards of good EMC engineering
Electromagnetic Compatibility (EMC) IEEE Definition Origin, control, and measurement of electromagnetic effects on electronic and biologic systems. IEEE EMC Society Areas of Interest EMC Standards: Standards
More informationRack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
More informationWorkbench EMC Measurements by Henry W. Ott Henry Ott Consultants www.hottconsultants.com
Workbench EMC Measurements by Henry W. Ott Henry Ott Consultants www.hottconsultants.com Workbench EMC measurements are simple, inexpensive precompliance tests that a product designer can perform early
More informationElectromagnetic Compatibility Considerations for Switching Power Supplies
Electromagnetic Compatibility Considerations Characterization of the EMI problem requires understanding the interference source Switching power supplies generate Electromagnetic Interference (EMI) by virtue
More informationScreened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
More informationGrounding Demystified
Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%
More informationDigital C4I Interoperability: The EM Protection Issue
Digital C4I Interoperability: The EM Protection Issue Robert Pfeffer U.S. Army Nuclear and Chemical Agency ATTN: ATNA-NU (R. Pfeffer) 7150 Heller Loop Suite 101 Springfield, VA 22150-3198 Abstract In this
More informationUsing installed Fieldbus Wiring to carry Ethernet Communications
Using installed Fieldbus Wiring to carry Ethernet Communications Modbus Plus, Data Highway, GE Genius, Profibus, ControlNet, DeviceNet, InterbusS and many other RS232 or RS4422 cables Key Issues when upgrading
More informationCable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
More informationApplication Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters
Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters AP-XC-025 Revision B DANGER RISK OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in addition to, and
More informationTelephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
More informationData Transmission. Data Communications Model. CSE 3461 / 5461: Computer Networking & Internet Technologies. Presentation B
CSE 3461 / 5461: Computer Networking & Internet Technologies Data Transmission Presentation B Kannan Srinivasan 08/30/2012 Data Communications Model Figure 1.2 Studying Assignment: 3.1-3.4, 4.1 Presentation
More informationStandard: EN 61000-4-2 :1995, EN 61000-4-3 :1996, ENV 50204 :1993, & EN 61000-4-4 :1995 Solid State Energy Meter
Standard: EN 61000-4-2 :1995, EN 61000-4-3 :1996, ENV 50204 :1993, & EN 61000-4-4 :1995 Model: Solid State Energy Meter Prepared for: Analog Devices, Inc. 804 Woburn Street Wilmington, MA 01887 Date of
More informationSubstation Automation Products Relion 670/650 series IEC and ANSI Hardware
Substation Automation Products Relion 670/650 series IEC and ANSI Hardware ABB Group 1MRG014097 October 2013 Relion 670/650 series hardware Contents Relion 670/650 series Relion Hardware Relion Common
More informationSECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
More informationEMI/RFI Shielded Cable Tray
EMI/RFI Cable Tray Chalfant began supplying industry cable tray in 1948 and designed and developed the first RF Tray for NS in 196 when it became imperative to protect instrument and control cabling from
More informationwith Component Rating A Simple Perspective
Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America
More information40 Years of experience in EMC testing
40 Years of experience in EMC testing Your reference laboratory for tests of generation, propagation and reception of electromagnetic energy in civil, military and industrial applications. CESI has been
More informationElectromagnetic Pulse: Effects on the U.S. Power Grid
Executive Summary The nation s power grid is vulnerable to the effects of an electromagnetic pulse (EMP), a sudden burst of electromagnetic radiation resulting from a natural or man-made event. EMP events
More informationNexus Technology Review -- Exhibit A
Nexus Technology Review -- Exhibit A Background A. Types of DSL Lines DSL comes in many flavors: ADSL, ADSL2, ADSL2+, VDSL and VDSL2. Each DSL variant respectively operates up a higher frequency level.
More informationEECC694 - Shaaban. Transmission Channel
The Physical Layer: Data Transmission Basics Encode data as energy at the data (information) source and transmit the encoded energy using transmitter hardware: Possible Energy Forms: Electrical, light,
More informationMeasurement of RF Emissions from a Final Coat Electronics Corrosion Module
Engineering Test Report No. 37802-02 Rev. A Measurement of RF Emissions from a Final Coat Electronics Corrosion Module For : Canadian Auto Preservation, Inc. 390 Bradwick Drive Concord, Ontario CANADA
More informationfor Communication Systems Protection EMI CD-ROM INCLUDED
Krešimir Malarić EMI Protection for Communication Systems CD-ROM INCLUDED Contents Preface xiii CHAPTER 1 Communications Systems 1 1.1 Components of Communications Systems 1 1.2 Transmitter Systems 2 1.2.1
More informationEMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC) http://www.iec.
EMC STANDARDS The EMC standards that a particular electronic product must meet depend on the product application (commercial or military) and the country in which the product is to be used. These EMC regulatory
More informationSubstation Grounding Study Specification
Substation Grounding Study Specification Introduction A grounding study is required for name of station, a / / kv substation located in name of location and connected to the following circuits: number
More informationGrounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
More informationReducing Electromagnetic Interference (EMI) With Low Voltage Differential Signaling (LVDS)
Application Report SLLA030C September 2000 Revised June 2002 Reducing Electromagnetic Interference (EMI) With Low Voltage Differential Signaling (LVDS) Elliott Cole High-Performance Analog ABSTRACT This
More informationElectromagnetic Test Facilities at Sandia National Laboratories
IMS 2005 - IEEE International Workshop on Measurement Systems for Homeland Security, Contraband Detection and Personal Safety Orlando, FL, USA, 29-30 March 2005 Electromagnetic Test Facilities at Sandia
More informationMRI RF SHIELDING DESIGN
MRI RF SHIELDING DESIGN Nelco s MRI RF Shielding is specifically designed for the MRI industry. Our engineers have developed a shielded enclosure made entirely of nonmagnetic materials that is unsurpassed
More informationMGL Avionics CAN bus interface for Trig Avionics TT21/TT22 transponders
MGL Avionics CAN bus interface for Trig Avionics TT21/TT22 transponders General The MGL Avionics CAN bus interface for the Trig Avionics TT21 and TT22 transponders provides a simple solution to allow any
More informationNetwork Vulnerability to Electromagnetic Pulse Attacks
Network Vulnerability to Electromagnetic Pulse Attacks Steve Goeringer Jason Rupe Abstract An approach to assessing transport network robustness to single event EMP attacks. 2015 Polar Star Consulting,
More informationApplications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
More informationBuilding Maintenance - Understanding Ground Isolation and Network Safety
TEMPEST Engineering and Hardware Design Dr. Bruce C. Gabrielson, NCE 1998 Power/Ground Isolation and Control in Boxes, Systems, and Facilities Chapter 15 (Note: Much of this chapter is taken from existing
More informationFibre Optic Solutions for your Test and Instrumentation needs
Fibre Optic Solutions for your Test and Instrumentation needs Aerospace Test EMC/EMP Military Industrial Control High Energy Physics Automotive Test Custom www.point2point.co.uk Fibre Optic Solutions for
More information1. Introduction Communication in Substation
WP 1004HE Part 1 1. Introduction Communication in Substation White Paper Data Communication in Substation Automation System (SAS) Introduction of modern substation communication 1.1 What is the Substation
More informationCommon Mode Choke Filtering Improves CMRR in Ethernet Transformer Applications. Application Note. June 2011
Common Mode Choke Filtering Improves CMRR in Ethernet Transformer Applications June 2011 Application Note Common mode chokes provide an effective EMI filtering solution for Ethernet transformer applications.
More informationWhite Paper: Electrical Ground Rules
Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment
More informationSECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
More informationAC and DC Drive System Installation Information
Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS
More information14.5GHZ 2.2KW CW GENERATOR. GKP 22KP 14.5GHz WR62 3x400V
14.5GHZ 2.2KW CW GENERATOR GKP 22KP 14.5GHz WR62 3x400V UTILIZATION OF GKP 22KP GENERATOR With its characteristics of power stability whatever the load, very fast response time at a pulse, low ripple,
More informationAmphenol. High Speed Solutions CABLE ASSEMBLIES
Amphenol High Speed Solutions CABLE ASSEMBLIES amphenol aerospace located in sidney, ny 1 One of the largest manufacturers of interconnect products in the world. WE design manufacture market INTERCONNECT
More informationXPress-Pro SW Series Hardened Ethernet Switches Enabling Communication for the Demanding Industrial Environment
XPress-Pro SW Series Hardened Ethernet Switches Enabling Communication for the Demanding Industrial Environment Part of the device networking family of networkenablement products, XPress-Pro SW series
More informationData Transmission. Raj Jain. Professor of CIS. The Ohio State University. Columbus, OH 43210 Jain@ACM.Org http://www.cis.ohio-state.
Data Transmission Professor of CIS Columbus, OH 43210 Jain@ACM.Org http://www.cis.ohio-state.edu/~jain/ 2-1 Overview Time Domain and Frequency Domain Bit, Hertz Decibels Data vs Signal Attenuation, Delay
More informationData Communications Competence Center
Importance of Cable Balance For Improving Noise Susceptibility Data Communications Competence Center DCCC03101702 July 11, 2007 Summary In a study of category 5e and category 6 UTP cables, a strong correlation
More informationUpon completing this chapter, you will be able to: Describe the primary types and uses of twisted-pair cables Describe the primary types and uses of
Upon completing this chapter, you will be able to: Describe the primary types and uses of twisted-pair cables Describe the primary types and uses of coaxial cables Describe the primary types and uses of
More informationGood EMC Design Principles: cable routing
Good EMC Design Principles: cable routing Keith Armstrong describes three important techniques for cable routing in metal cabinets, whether the cables are bundles of individual wires, or individual or
More informationTIMING SIGNALS, IRIG-B AND PULSES
TIMING SIGNALS, IRIG-B AND PULSES Document No. PD0043200B July 2013 Arbiter Systems, Inc. 1324 Vendels Circle, Suite 121 Paso Robles, CA 93446 U.S.A. (805) 237-3831, (800) 321-3831 http://www.arbiter.com
More informationMicrowave Photonic Systems Inc. Joshua L. Korson & Richard J. Stewart
Fiber Optic Communications Equipment Provides Backhaul Infrastructure for Critical Satellite Based Continuity of Communications Solutions: IRIDUIM, INMARSAT, GEO SATCOM Microwave Photonic Systems Inc.
More informationCellular Wireless Antennas
Cellular Wireless Antennas A Technical Brief GarrettCom Inc., November 2010 Overview The Cellular Wireless Antenna Technical brief is provided to assist with the design and deployment of the DX940 Cellular
More informationRadiated Emission and Susceptibility
Radiated Emission and Susceptibility Tzong-Lin Wu, Ph.D. EMC Lab Department of Electrical Engineering National Taiwan University Differential-Mode v.s. Common-mode Currents 1 Differential-Mode v.s. Common-mode
More informationSeparation of power and information technology cabling
Technical bulletin Separation of power and information technology cabling Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based on the current
More informationVerizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012
Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012 CHANGE CONTROL RECORD: Version Date Action* Reason for Revision
More informationILB, ILBB Ferrite Beads
ILB, ILBB Ferrite Beads Electro-Magnetic Interference and Electro-Magnetic Compatibility (EMI/EMC) avid B. Fancher Inductive Products ivision INTROUCTION Manufacturers of electrical and electronic equipment
More informationTest Report #: 1981-3 Date: April 8, 2005
Test Report #: 1981-3 Date: April 8, 2005 CERTIFICATE #2316.01 Issued To: Bill Burks American Power Conversion 85 Rangeway Road North Billerica, MA 01862 USA 978-670-2440 Product Name/Description Model
More informationRated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W
14713221 001 Seite 2 von 37 Page 2 of 37 Model List: No Model Rated Voltage(V) 1. EG-LED0827-01 Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 4. EG-LED1040-01 AC 100-240V, 10W 5. EG-LED1027-02
More informationA Beginners Guide to EMC. Presented by Andy Lawson Technical Supervisor, Industry EMC, TÜV SÜD Product Service
A Beginners Guide to EMC Presented by Andy Lawson Technical Supervisor, Industry EMC, TÜV SÜD Product Service EMC Issues In The Real World What Actually is EMC? EMC Standards and Legislation The Need For
More informationAN96-07. Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x
TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x On January 1, 1996, exports into Europe began facing some tough transient immunity standards. The International Electrotechnical Commission (IEC), a worldwide
More information4-Port 10/100Mbps with PoE + 1-Port 100FX Industrial Ethernet Switch Wide Temperature
4-Port 10/Mbps with + 1-Port FX Industrial Ethernet Switch Wide Temperature 15 F Fiber Optic Link Capability for Flexible Distance Extension The series equips one Base-FX port that provides more flexibility
More informationDDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
More informationCPS 100 480Y S K CPS 100 480Y S C
Ref. No. 1299 Visor Series Ordering Guidelines Table.1-4. Retrofit Surge Protection Products TVSS General Description Clipper Power System Visor Series CPS 100 480Y S K.1-9 Surge Ratings 100 = /phase 120
More informationSimulation électromagnétique 3D et câblage, exemples dans l'automobile et aéronautique :
Simulation électromagnétique 3D et câblage, exemples dans l'automobile et aéronautique : CST, Christophe Morin 1 www.cst.com Agenda - Présentation CST - Simulation câblage dans modèle 3D - Exemples automobile
More informationFor emission and immunity testing according to IEC 61000-4-20
EMC GTEM 500 Gtem Cell For emission and immunity testing according to IEC 61000-4-20 Theory of operation GTEM-cells (Giga-hertz Transversal Electro-Magnetic cells) are waveguide structures intended for
More informationHarmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
More information1. Franklin Rod Performance 2. LEC/DAS Performance
THREE ESSENTIALS OF LIGHTNING PROTECTION: BONDING, GROUNDING AND SURGE PROTECTION by Richard Kithil, President and Orlando Alzamora, Vice-President National Lightning Safety Institute (NLSI) 1.0 Summary.
More informationMedia Conversion in Video Security and Surveillance Systems
The Conversion Technology Experts Media Conversion in Video Security and Surveillance Systems Worldwide Headquarters 6475 City West Parkway Eden Prairie, MN 55344 USA tel 952.941.7600 toll free 800.526.9267
More informationCAN Bus Transceivers Operate from 3.3V or 5V and Withstand ±60V Faults
CAN Bus Transceivers Operate from 3.3V or 5V and Withstand ±6 Faults Ciaran Brennan design features The LTC2875 is a robust CAN bus transceiver that features ±6 overvoltage and ±25kV ESD tolerance to reduce
More informationCommercial Cable Installation Philadelphia PA
Commercial Cable Installation Philadelphia PA About Us Squid Wire is a low voltage cabling company which is dedicated to providing solid, reliable technology advice and solutions to support our clients
More informationInterfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13
Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified
More informationGrounding and Shield Termination. Application Note 51204
Grounding and Shield Termination Application Note 51204 DEFINITIONS This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this
More informationWaveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
More informationSUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
More informationEMC Basics. Speaker : Alain Lafuente. Alain.lafuente@we-online.com
EMC Basics Speaker : lain Lafuente lain.lafuente@we-online.com WHT IS EMC? 2 CE Marking With the formation of the single European market, standardization was required to remove technical barriers to trade.
More informationPower network telecommunication
www.siemens.com Power network telecommunication Teleprotection Answers for infrastructure and cities. Binary I/O The best protection against high-voltage grid failures When it comes to managing power networks,
More informationFranz Hirtenfelder and Stephen Murray, CST Computer Simulation Technology and W. L. Gore and Associates (Gore) March 5, 2015
1 of 7 3/17/2015 9:38 AM Home Franz Hirtenfelder and Stephen Murray, CST Computer Simulation Technology and W. L. Gore and Associates (Gore) March 5, 2015 Editor s Note: A cable that leaks electromagnetic
More informationVideo Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
More informationIEEE Electromagnetic Compatibility Standards (Active & Archive) Collection: VuSpec
IEEE Electromagnetic Compatibility Standards (Active & Archive) Collection: VuSpec This value-packed VuSpec CD-ROM represents the most complete resource available for professional engineers looking for
More informationTrial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
More informationFIBRE TO THE BTS IMPROVING NETWORK FLEXIBILITY & ENERGY EFFICIENCY
FIBRE TO THE BTS IMPROVING NETWORK FLEXIBILITY & ENERGY EFFICIENCY (Study Paper by FLA Division) Ram Krishna Dy. Director General (FLA) TEC New Delhi, DoT, Govt. of India. E-mail: ddgfla.tec@gov.in Mrs.
More informationDoc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
More informationUNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS
Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com hott@ieee.org Page 2 THE BASIC
More informationElectromagnetic (EMI) shielding
Electromagnetic (EMI) shielding 1.1. The mechanism of Electromagnetic Interference (EMI) The definition of EMC The council of the European Union defines EMC in Article 4 of their "council directive on
More informationDEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD OF INSERTION LOSS MEASUREMENT
INCH-POUND MIL-STD-220C 14 May 2009 SUPERSEDING MIL-STD-220B 24 January 2000 DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD OF INSERTION LOSS MEASUREMENT AMSC N/A FSC EMCS FOREWORD 1. This standard
More information10 Gigabit Ethernet over copper: Unshielded, unprotected?
Technical Article 10 Gigabit Ethernet over copper: Unshielded, unprotected? Copyright 2005 Reichle & De-Massari AG (R&M). All rights reserved. Transmission and reproduction of this publication or parts
More informationThe following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
More informationTest Report. Prepared for: Technologic Systems, Inc. Model: TS-8820
Test Report Prepared for: Technologic Systems, Inc. Model: TS-8820 Description: Single Board Computer with Analog and Digital Inputs and Outputs, Relays, and RS-232/485 Ports To IEC 61000-6-1 (2005-03)
More informationQuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA - 12859 North America Version 5 August 22, 2008 Page 1
Overview It's getting harder to manage a data center efficiently, with rising utility bills and ever-increasing demands due to processor power and server density increases. Growing user requests mean heavier
More informationSPECIAL SPECIFICATION 6819 Wireless Ethernet Microwave Radio
2004 Specifications CSJ 2266-02-127 SPECIAL SPECIFICATION 6819 Wireless Ethernet Microwave Radio 1. Description. Furnish and install Wireless Ethernet Microwave Radio (WEMR) as shown on the plans, as detailed
More informationModule 11: Conducted Emissions
Module 11: Conducted Emissions 11.1 Overview The term conducted emissions refers to the mechanism that enables electromagnetic energy to be created in an electronic device and coupled to its AC power cord.
More informationRICHARD T ELL ASSOCIATES,INC.
RICHARD T ELL ASSOCIATES,INC. An Evaluation of Test Measurement Data Obtained on the KW-Gard RF Protective Suit March 30, 1998 Prepared for Euclid Garment Manufacturing Company 333 Martinel Drive Kent,
More informationPXL-250: Network Wiring
This document provides the network wiring requirements for a PXL-250 access control network. Network Requirements The PXL-250 uses a half-duplex, RS-485 communication bus. Per the RS-485 specification,
More informationDATA SHEET DVI - HDCP Extension Cable
DATA SHEET DVI - HDCP Extension Cable Contents Description Features Absolute Maximum Ratings Recommended Operating Conditions Electrical Power Supply Characteristics Receiver Electrical Interface Specifications
More informationFundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
More informationPredicting radiated emissions from cables in the RE02/RE102/DO- 160/SAE J113-41 test set up, using measured current in NEC and simple TX equations.
Predicting radiated emissions from cables in the RE02/RE102/DO- 160/SAE J113-41 test set up, using measured current in NEC and simple TX equations. D. A. Weston RE02Tx.rep 14-6-2004 NARTE Certified EMC
More informationIndustrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
More informationInvestigation of the Risk of Electromagnetic Security on Computer Systems
Investigation of the Risk of Electromagnetic Security on Computer Systems Changlin Zhou, Member, IACSIT, IEEE, Qun Yu, and Litao Wang Abstract Electromagnetic environmental effects (E3) and compromising
More informationNetworks. The two main network types are: Peer networks
Networks Networking is all about sharing information and resources. Computers connected to a network can avail of many facilities not available to standalone computers: Share a printer or a plotter among
More informationZero-Variable Wireless Infrastructure Deployment. Datasheet. Models: BM2HP, BM5HP. Completely integrated Radio
Zero-Variable Wireless Infrastructure Deployment Models: BM2HP, BM5HP Completely integrated Radio Directly plugs into any Antenna that has a Type N female connector Robust Weatherproof Design Overview
More information