781N Electric Latch Pullback Controller Installation Instructions

Size: px
Start display at page:

Download "781N Electric Latch Pullback Controller Installation Instructions"

Transcription

1 781N Electric Latch Pullback Controller Installation Instructions INSTALLATION For C-UL Listed applications, the unit shall be installed in accordance with Part 1 of the Canadian Electrical Code. Transformer model BE by Basler Electric and transformer model by Galaxy Transformer and Magnetics have been certified for UL and C-UL applications. Transformer model A A34 by EWC has been certified for UL applications only. The 781N enclosure should be securely fastened to the wall using the four 1/4 inch diameter mounting holes located in the back of the box. Position the enclosure so that the transformer is located on the left-hand side. The 781N must not be installed outdoors. For the 120VAC power input, terminal block TB1 will accommodate up to 12 AWG wire (solid). Conduit must be used to provide an adequate earth ground to the enclosure. NOTE: The maximum input current is 750mA. The 781N is designed to be used with electric latch pullback exit devices. Use the chart below to determine the correct wire gauge per given length of two-conductor cable that will be run from the 781N to each exit device. Do not exceed the maximum length listed with each wire gauge. WIRE GAUGE MAXIMUM LENGTH OF TWO-CONDUCTOR CABLE 16 AWG 40 FEET 14 AWG 60 FEET 12 AWG 100 FEET Up to two devices can be used with the 781N. If only one device is to be used, wire to the "DEVICE ONE" location at TB3, terminals 5 and 6. NOTE: Be sure to observe polarity when connecting devices 1 and 2 to TB3. (Refer to the wiring diagram located on the lid of the controller.)

2 STANDARD OPERATION The 781N provides a choice of two methods of electric latch pullback: Single System or Dual System SINGLE SYSTEM LATCH PULLBACK This method allows one input to control two devices sequentially. A momentary switch closure across terminals 1 and 2 of TB3 will pull back DEVICE ONE first, followed by DEVICE TWO. Use this method for single door applications or on a pair of doors using a device on one or both leaves. The 781N comes from the factory already set up for this method. DUAL SYSTEM LATCH PULLBACK (OPTIONAL) This method allows independent control of DEVICE ONE and DEVICE TWO outputs by their own separate input. A momentary switch closure across terminals 1 and 2 of TB3 will pull back DEVICE ONE only. A momentary switch closure across terminals 7 and 8 of TB3 will pull back DEVICE TWO. No more than one device can be used per output. Use this option for applications requiring two single door systems or two pair door systems using one device on the active leaf of each pair of doors. To change over to the optional dual system latch pullback, move the program jumper PJ1 from between the middle post and the end post, marked "S" (Single System) to between the middle post and the end post, marked "D" (Dual System). NOTE: When using the optional method, DEVICE ONE and DEVICE TWO can never be activated at the same time in the event that both input switches are actuated simultaneously. If this should occur, DEVICE ONE will always activate first, followed by DEVICE TWO. When using a momentary, normally open switch for activating latch pullback, adjust pot R2 (for DEVICE ONE) or pot R4 (for DEVICE TWO) on the p.c. board to the desired latch pullback delay time from 1 to 20 seconds. Turn the pot clockwise to increase the delay time. When using normally open contacts from a keypad or card reader ( with built-in time delay) or a maintain switch, turn pot R2 (or R4) fully counterclockwise to the minimum delay time (approx. 0.5 sec.). A contact closure will activate latch pullback. Upon opening of the timed or maintained contacts, the device will latch within 0.5 second. Each modified exit device contains a pulse module which delivers a pulse at approx. 24VDC to a high current coil inside the exit device every 6 seconds until the latch is finally pulled back all the way. At this point, a control rod passes over a reflective sensor and signals the module to stop pulsing. There is always an initial pulse that occurs at the moment the system is activated. During the period the system remains activated, output voltage is applied to a low current secondary coil. This coil is responsible for holding the latch in the "pulled back" position until instructed to return to the "fail secure" position. (See note 2 on page 5.) 2

3 OPERATION WITH AUTOMATIC DOOR OPERATOR The 781N is provided with two outputs (one output associated with DEVICE ONE and the other output associated with DEVICE TWO) for controlling separate automatic door operators. Each output consists of normally open relay contacts that are field wired directly to the "DOOR ACTIVATION" input of the automatic door operator. These outputs are activated within a moment after activation of their corresponding devices to allow time for the doors to be fully unlatched before automatic opening begins. Time delay pots R2 and R4 are factory set at 5 seconds, which are appropriate when using this controller with automatic door operators. When the delay times out, power is removed from the exit device and the signal to the auto door operator input is terminated, thus allowing the operator's "DOOR HOLD OPEN" delay to time out and close the door. NOTE: When using the single system latch pullback method with automatic door operator interface and both devices are being used, the operator control input must be wired to the 781N automatic door operator output for DEVICE TWO (TB3, terminals 9 and 10). OPERATION WITH FIRE ALARM The 781N can be wired to the fire alarm relay normally closed contacts. When a fire alarm occurs, any door that is currently unlatched, whether by momentary time delay or by maintained switch, will immediately latch secure. During the time that the fire alarm is active, electronic control of the automatic door opening system by wall switch, card reader, keypad, etc., is disabled. The door then can only be opened manually. The 781N comes from the factory set up for use without fire alarm interface. If the fire alarm is to be used with this controller, move the program jumper PJ2 from between the middle post and the end post, marked "FA DIS" (Fire Alarm Disabled), to between the middle post and the end post, marked "FA EN" (Fire Alarm Enabled). NOTE: The current drawn through fire alarm relay contacts will be 24VDC AUXILIARY POWER SOURCE OUTPUTS Two constant, power limited auxiliary outputs are provided for powering keypads, motion sensors, annunciator panels, electromagnetic door holders, relays, LEDs, etc. Choose between auxiliary output #1 or auxiliary output #2. Auxiliary Output #1 Range: 26.7V V, Nominal Auxiliary Output #2 Range: 12.6V V, Nominal NOTE: Both auxiliary outputs can be used at the same time for loads requiring different voltages (for a combined maximum load current of 500mA). However, do not tie the aux. output #2 ground (TB3, terminal 18) common to the aux. output #1 ground (TB3, terminal 16). Both of these power sources must be isolated from each other. CAUTION: IT IS RECOMMENDED TO USE OUTPUT #2 WITH EQUIPMENT THAT HAVE INPUTS RATED FOR VOLTS, AC OR DC. CHECK WITH THE MANUFACTURER BEFORE CONNECTING 24VDC RATED EQUIPMENT ACROSS OUTPUT #1 TO ENSURE THE HIGHER VOLTAGE WILL NOT CAUSE ANY DAMAGE. 3

4 TROUBLESHOOTING Before proceeding through the troubleshooting section, ensure that all device latches are not binding against their corresponding strikes. A bound latch can cause sluggish electric pullback or prevent pullback entirely. Power Limited Outputs All outputs to the 781N are power limited. Depending on the output, if a short circuit or an over load condition should occur, the output will either shut off entirely or go into a safe current limiting state. IMPORTANT!: THE MAXIMUM RATED LOAD FOR ALL OUTPUTS COMBINED IS 2.0 AMPS, INCLUDING 250mA (MAX.) FOR EACH AUXILIARY OUTPUT. The outputs to Device One (TB3, terminals 5 & 6) and Device Two (TB3, terminals 11 & 12) will completely shut down to 0 volts when a short circuit across the output occurs or when the load exceeds 5 amps. To reset the output, the short circuit or overload must first be located and removed. Next, momentarily switch off the outputs by opening the contacts across input terminals 1 & 2 or 7 &8, whichever is used. Before switching outputs back on, ensure the load does not exceed the maximum current ratings. Both auxiliary outputs will go into a current limiting state when the load exceeds approximately 2.0 amps or in the event of a short circuit. The current is reduced to a safe level when either of these conditions occur. The output voltage will automatically return to its normal level when the short circuit or overload condition is removed and replaced by a load falling under the maximum current rating. Neither DEVICE ONE or DEVICE TWO pulls back after the control switch is activated. 1. The power limited output to Device 1 or Device 2 (or both) may have shut down.. When this happens, the field wires that are run to the exit device are probably shorted together against the conduit, door frame or electric hinge. 2. The slow blow 4 amp fuse (Littlefuse # ) inside the exit device has blown. The most likely cause would be reversed polarity of the exit device red and black leads: RED = "+"; BLACK = "-". (Refer to the wiring diagram for proper connection.) Other possible causes may be shorted wires in the solenoid assembly or a defective pulse module. 3. An open connection in the field wiring between the power supply and control switch used for activating latch pullback. 4. A defective control switch. 5. An open connection in the field wiring between the power supply and exit device. 4

5 6. There may be no pulse. To check for pulses, prop the door open and connect a voltmeter across the red and black leads coming from the exit device (red lead is positive). Next, connect a jumper wire across terminals 1 and 2 of TB3 to keep DEVICE ONE in a continuous pulled back state. If the voltmeter measures between 30 and 40 VDC at the moment the jumper wire was installed, but the latch did not budge, then no initial pulse was generated. Check for a series of timed pulses that will occur approximately every six seconds. (Make sure that the control rod is not positioned over the reflective sensor on the pulse module when making this next check.) Wait for about 20 seconds to see if the latch pulls back. If it still does not respond, then it indicates the pulse module is inoperative and the entire solenoid/module assembly must be replaced. When 120 volts is applied to TB1, the exit devices immediately pull back, even though the control switch had not been activated. 1. Field wiring between the power supply and control switch are shorted together against the conduit or switch mounting box. 2. A maintain switch is being used and is in the closed position. 3. A defective control switch. A noticeable buzzing sound at equal intervals is coming from inside the exit device while in its pulled back state. 1. The latch is binding against its corresponding strike and preventing it from pulling back fully, due to misalignment between the latch and strike opening. 2. A defective pulse module. NOTE 1: THIS UNIT IS LISTED AS AN EXIT DEVICE CONTROL UNIT TO UL294 REQUIREMENTS. NOTE 2: THE POWER OUTPUT OF THE CONTROLLER IS OF A FAIL SECURE DESIGN. THE EXIT DEVICE REMAINS LATCHED DURING A COMPLETE POWER FAILURE, BUT ALWAYS ALLOWS FREE MECHANICAL EGRESS. LISTED PANIC HARDWARE MAY BE REQUIRED TO ALLOW EMERGENCY EXIT. CONSULT LOCAL AUTHORITY HAVING JURISDICTION. Any retrofit or other field modification to a fire rated opening can potentially impact the fire rating of the opening, and Yale Locks & Hardware makes no representations or warranties concerning what such impact may be in any specific situation. When retrofitting any portion of an existing fire rated opening, or specifying and installing a new fire-rated opening, please consult with a code specialist or local code official (Authority Having Jurisdiction) to ensure compliance with all applicable codes and ratings. Product Support Tel WIRE (9473) Yale Locks & Hardware is a division of Yale Security Inc., an ASSA ABLOY Group company. Yale is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company. Other products' brand names may be trademarks or registered trademarks of their respective owners and are mentioned for reference purposes only. These materials are protected under U.S. copyright laws. All contents current at time of publication. Yale Security Inc. reserves the right to change availability of any item in this catalog, its design, construction, and/or its materials. Copyright 1998, 2013, Yale Security Inc., an ASSA ABLOY Group company. All rights reserved. Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. 5

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Instructions CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Catalog Number 2100-SD1 Description The Bulletin 2100 smoke detector unit is a 0.5 space factor unit for use in Bulletin

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK Security Door Controls 3580 Willow Lane, Westlake Village, CA 91361-4921 (805) 494-0622 Fax: (805) 494-8861 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP

More information

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal O N DS160/DS161 Installation Guide High Performance Request-to-Exit Sensors 1.0 Description The DS160/161 is a passive-infrared (PIR) detector designed for Request to Exit (REX) interior applications.

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

INTRUSION DETECTION SYSTEM Section 281600

INTRUSION DETECTION SYSTEM Section 281600 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual Master Time Clock MTC-200 MTC-400 MTC-600 Users Manual Toll Free (888)713-0373 Phone (972)987-4408 FAX (877)720-9291 www.midwest-time.com sales@midwest-time.com TABLE OF CONTENTS TOPIC PAGE GENERAL DESCRIPTION

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

TS93 EMR T/PT/TDE. Surface applied door closer

TS93 EMR T/PT/TDE. Surface applied door closer TS EMR T/PT/TDE Surface applied door closer Installation instructions: Pull side track mount door closer with smoke detector (EMR T) Push side track mount door closer with smoke detector (EMR PT) Double

More information

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output

More information

e-ask electronic Access Security Keyless-entry

e-ask electronic Access Security Keyless-entry e-ask electronic Access Security Keyless-entry e-fob Keyless-entry entry System Full-Function Function Installation Manual FCC ID: TV2EFOB1 (UM20 ~ 22793-02) Table of Contents Introduction... 1 e-fob Operation

More information

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY 7320 Ashcroft, Suite 104 Houston, Texas 77081 p: 713-772-1404 f: 713-772-7360 e: info@juicegoose.com www.juicegoose.com 06-06 CONGRATULATIONS

More information

ETZGAR CONVEYOR COMPANY Controls Section v12.05

ETZGAR CONVEYOR COMPANY Controls Section v12.05 Section 7 Controls Page Description 7-1 Controls Index 7-2 Motor Data, Enclosure Rating and Abbreviations 7-3 Controls Safety Guidelines 7-4 Fixed Speed Controls Packages 7-5 Three Phase AC Variable Speed

More information

GLOLAB Two Wire Stepper Motor Positioner

GLOLAB Two Wire Stepper Motor Positioner Introduction A simple and inexpensive way to remotely rotate a display or object is with a positioner that uses a stepper motor to rotate it. The motor is driven by a circuit mounted near the motor and

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

Analog Control Wiring & Adjustment Manual for Gyro Tech Swing Door Operators

Analog Control Wiring & Adjustment Manual for Gyro Tech Swing Door Operators NABCO ENTRANCES Inc. S82 W18717 Gemini Drive Muskego, WI 53150 Phone: 877-622-2694 Fax: 888-679-3319 Technical Assistance: 866-622-8325 www.nabcoentrances.com Email: info@nabcoentrances.com Analog Control

More information

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E SENS part no: 101314 Document revision: F DCN No. 106811 Date 8/3/15 1840 Industrial Circle Longmont, CO 80501 Fax: (303) 678-7504

More information

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &

More information

INSTALLATION/PROGRAMMING INSTRUCTIONS 928 ENTRYCHECK

INSTALLATION/PROGRAMMING INSTRUCTIONS 928 ENTRYCHECK 3580 Willow Lane, Westlake Village, CA 91361-4921 (805) 494-0622 Fax: (805) 494-8861 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION/PROGRAMMING INSTRUCTIONS 928 ENTRYCHECK INTRODUCTION

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

EQUIPMENT SPECIFICATIONS

EQUIPMENT SPECIFICATIONS EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power) MODEL NUMBER: ISC910-1-0-GB-XX ISC911-5-0-GB-XX IXP20 CONTROLLER SPECIFICATIONS Working Environment Plastic Housing... Power ImproX IXP20 Controller INSTALLATION MANUAL Designed to work in an indoor (dry)

More information

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting

More information

Speed Control Relays SX2

Speed Control Relays SX2 SX2 File 850 CONENS Description.....................................................Page General Information................................................ 2-3 SX2DV General Information...........................................

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire) FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control

More information

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation. This quick start guide provides, basic installation information, drawings, first time power-on instructions, and short descriptions of key terms and concepts for installing the EntraGuard Platinum Telephone

More information

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142

More information

FIRERAY 2000 Installation Guide

FIRERAY 2000 Installation Guide FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description

More information

98371000 REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 2011 ELKHART BRASS MFG. CO., INC.

98371000 REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 2011 ELKHART BRASS MFG. CO., INC. 81471067 Electric Monitor Motor Control Panel For use with Model 8394059 SPIT-FIRE Monitor Installation, Operation, and Maintenance Instructions FOR ATEX APPLICATIONS 1302 WEST BEARDSLEY AVENUE P.O. BOX

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The

More information

INSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS

INSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS INSTALLATION MANUAL Before you begin the installation Read the INSTRUCTIONS! Always use a multi-meter when verifying vehicle wiring. Before mounting the

More information

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

Model 201 Wiegand Touchpad Reader Installation Guide

Model 201 Wiegand Touchpad Reader Installation Guide Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without

More information

Control Panels D9412GV3/D7412GV3/D7212GV3. UL Installation Instructions

Control Panels D9412GV3/D7412GV3/D7212GV3. UL Installation Instructions Control Panels D9412GV3/D7412GV3/D7212GV3 en UL Installation Instructions Control Panels Table of Contents en 3 Table of Contents 1 Installation 4 1.1 Installation Preparation 4 1.2 Enclosure Options

More information

conventional system operation

conventional system operation conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than

More information

APOLLO Gate Operators, Inc.

APOLLO Gate Operators, Inc. APOLLO Gate Operators, Inc. Model 7200ETL Post Mounted Residential & Heavy Duty Commercial Slide Gate Operator INSTALLATION MANUAL 04/11 CONTENTS IMPORTANT SAFETY INSTRUCTIONS... 3 Applications... 4 Pre-Installation

More information

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER (PWM Input, 1.2A or 2A Output, Metal Box or PCB) PCB Board - P/N: PWMC-PCB-2A, PWMC-PCB-1.2A Packaged Driver (metal box with 1.5 m (5 ft.) cable)

More information

Section 1 Overview of Heavy-Duty Auto Throttle Controls. Heavy Duty Auto Throttle Applications

Section 1 Overview of Heavy-Duty Auto Throttle Controls. Heavy Duty Auto Throttle Applications Section 1 Overview of Heavy-Duty Auto Throttle Controls Heavy Duty Auto Throttle Applications Utility and Maintenance Vehicles Increases engine RPM to provide full current output of the alternator when

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access CSP Combined Series Telephone Door Entry with Proximity Keyfob Access PD-094 Issue 3 General Description The CSP series systems are combined Door Entry Telephone and Proximity Access Systems. The entrance

More information

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 techsupport@securitron.com in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

8900 EMR (WITH DETECTOR)

8900 EMR (WITH DETECTOR) 00 EMR (WITH ) GENERAL DESCRIPTION Each 00 EMR series unit contains a door closer, hold open electromagnet and smoke detector. The unit can be used as a single installation or as a series of singles powered

More information

DUCT SMOKE DETECTOR D4120

DUCT SMOKE DETECTOR D4120 Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity

More information

Secure Keypads for access control

Secure Keypads for access control torm Secure Keypads for access control Strike Master Read this manual carefully before attempting to install, program or operate the STORM AXS Strike Master Keypad. After installation the Command Summary

More information

PAC1 Door Access Controller

PAC1 Door Access Controller PAC1 Door Access Controller Series 2 IMPORTANT DIFFERENCES FROM SERIES 1 1. A PACDL data logger revision 4.0 or higher attached to the DLOG terminal is able to program all features (i.e. times, relay type,

More information

EMBEDDED ACCESS CONTROL Hardware Installation Guide

EMBEDDED ACCESS CONTROL Hardware Installation Guide EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel

More information

VARIO PROX CARD READER INSTALLATION MANUAL

VARIO PROX CARD READER INSTALLATION MANUAL VARIO PROX CARD READER INSTALLATION MANUAL TABLE OF CONTENTS 1.0 INTRODUCTION...2 1.1 Legend...3 1.2 Terminology...4 2.0 MOUNTING...5 3.0 WIEGAND CONNECTION...6 4.0 AUX BUTTON INPUT...7 5.0 INSTALLER PROGRAMMING...8

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

Installation and Operation Guide for PD4000 Series Power Control Center

Installation and Operation Guide for PD4000 Series Power Control Center Extended warranties are available for purchase at www.progressivedyn.com Installation and Operation Guide for PD4000 Series Power Control Center Member Thank you for selecting Progressive Dynamics as your

More information

InHome Water Leak Detection Package

InHome Water Leak Detection Package InHome Water Leak Detection Package For Model Numbers ILD10A-L and ILD10A-B Installation Guide / Wiring Diagram For Creating Water Leak Detection-based Events with Line-Powered or Battery-Powered Sensors

More information

ASSA ABLOY Factory Training Adams Rite HES Securitron Course Offerings

ASSA ABLOY Factory Training Adams Rite HES Securitron Course Offerings ASSA ABLOY Factory Training Adams Rite HES Securitron Course Offerings ADAMS RITE HES SECURITRON ASSA ABLOY is proud to offer the following educational courses covering Adams Rite, HES and Securitron product

More information

Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P

Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P Distributed in the U.S.A. and Canada by CHENG USA, INC. Sales (574) 294-8997 Warranty Service (877) 294-8997

More information

AUTODIALLER / QUICKDIALLER - SA132

AUTODIALLER / QUICKDIALLER - SA132 AUTODIALLER / QUICKDIALLER - SA132 INSTRUCTION LEAFLET ENGLISH www.thermomax-group.com CONTENTS 1 SETUP AT A GLANCE... 2 2 FOREWORD....... 3 3 INSTALLATION...... 4 4 KEYPAD AND INDICATORS...... 5 SETTING

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The

More information

ACTIVE 5 ENGINEERING MANUAL

ACTIVE 5 ENGINEERING MANUAL ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features

More information

Load Cell Amplifier Module. Instruction Manual LCA210-000

Load Cell Amplifier Module. Instruction Manual LCA210-000 Load Cell Amplifier Module Instruction Manual LCA210-000 Table of Contents 1. General Description...3 2. Specifications...3 2.1 Electrical...3 2.2 Physical...4 3. Installation...4 3.1 Wiring Guidelines...4

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

MDC151-024031 Series

MDC151-024031 Series MDC151-024031 Series 24V, 3A Brushless DC Controller User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.com (714) 992-6990 fax: (714)

More information

User Guide. Model 380260 Insulation Tester / Megohmmeter

User Guide. Model 380260 Insulation Tester / Megohmmeter User Guide Model 380260 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380260 provides three test ranges plus continuity

More information

Automatic Voltage Regulator User s Manual

Automatic Voltage Regulator User s Manual Resp. dept. R&D We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. Copyright

More information

Reference & Installation Manual

Reference & Installation Manual & Versions 4.4 (728ULT) & 4.1 (738ULT) 728ULT 738ULT Reference & Installation Manual Table of Contents Introduction... 1 About This Manual... 1 New Features... 1 Main Features... 1 Specifications... 1

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence

More information

INSTALLATION GUIDE. www.security.soundstream.com FCC ID NOTICE

INSTALLATION GUIDE. www.security.soundstream.com FCC ID NOTICE AL.1 AUTO SECURITY SYSTEM INSTALLATION GUIDE www.security.soundstream.com FCC ID NOTICE This device complies with Part 15 of the FCC rules. Operation is subject to the following conditions: 1. This device

More information

White Papers: Delayed Egress Hardware

White Papers: Delayed Egress Hardware www.sdcsecurity.com service@sdcsecurity.com [t] 800.413.8783 805.494.0622 [f] 805.494.8681 801 Avenida Acaso, Camarillo CA 93012 PO Box 3670, Camarillo CA 93011-3670 www.sdcsecurity.com White Papers: Delayed

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Model 2300DR Installation Guide

Model 2300DR Installation Guide Model 2300DR Installation Guide POWER ACCESS CORPORATION P.O. BOX 1050 170 MAIN STREET NEW HARTFORD, CT 06057 800-344-0088 WEBSITE: www.power-access.com EMAIL: salesinfo@power-access.com 1 STANDARD PARTS

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

Installation and Operation Guide for PD4100 Series Power Control Centers

Installation and Operation Guide for PD4100 Series Power Control Centers Installation and Operation Guide for PD4100 Series Power Control Centers Extended warranties are available for purchase at www.progressivedyn.com Member Thank you for selecting Progressive Dynamics as

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

Service Information CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS NOTE

Service Information CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS NOTE Service Information Calibration & Adjustments CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS Part Number DYN1-10752-000-0-12/24 DYN1-10752-001-0-12/24* DYN1-10753-000-0-12/24

More information

12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST

12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST 12VDC MAGNETIC ED DIMMABE POER SUPPIES SPEC SEET DIGEST TM-30-DIM TM-50-DIM T-60-DIM TM100-DIM TM200-DIM TM300-DIM iring Diagram for TM-50-DIM and TM-100-DIM ED 12VDC MAGNETIC DIMMABE 30 POER SUPPY Smallest

More information

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

More information

SAGEON SITE MONITOR (SSM) Application Note AN103-4012-00

SAGEON SITE MONITOR (SSM) Application Note AN103-4012-00 SAGEON SITE MONITOR (SSM) Application Note AN103-4012-00 AN 103-4012-00, Issue 2a sageon_sm-an.pdf www.unipowerco.com SALES: +1-800-440-3504 HEAD OFFICE: +1-954-346-2442 EUROPE: +44 (0)1903 768200 SAGEON

More information

www.sebury.com.cn Digital Keypad Use s Manual

www.sebury.com.cn Digital Keypad Use s Manual K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4

More information

JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator

JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator The Janus Pantheon mini operator does not typically require the provision of any additional site requirements other than

More information

Industrial Control Power Transformers

Industrial Control Power Transformers Class MT Features Epoxy-encapsulated (50 5000); Completely seals the transformer coils against moisture, dust, dirt and industrial contaminants for maximum protection in hostile and industrial environments

More information

7200 series Electromechanical Closer/Holder

7200 series Electromechanical Closer/Holder 7200 series Electromechanical Closer/Holder introduction The 7200 Series Electromechanical Closer/Holders combine the functions of an electromechanical door holder with the 7700 series door closer. The

More information

PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE

PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE MODEL HAA51 PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE OPERATING MANUAL HAA51 PASSIVE INFRARED INTRUDER DETECTOR INTRODUCTION HAA51 Passive Infrared

More information

12 Volt 30 Amp Digital Solar Charge Controller

12 Volt 30 Amp Digital Solar Charge Controller 12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

ANTI-THEFT SYSTEM. 1995 Volvo 850 DESCRIPTION & OPERATION BASIC ALARM. 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems

ANTI-THEFT SYSTEM. 1995 Volvo 850 DESCRIPTION & OPERATION BASIC ALARM. 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems ANTI-THEFT SYSTEM 1995 Volvo 850 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems 850 DESCRIPTION & OPERATION WARNING: Deactivate air bag system before performing any service operation. For 1995

More information

SYSTEM 4C. C R H Electronics Design

SYSTEM 4C. C R H Electronics Design SYSTEM 4C C R H Electronics Design SYSTEM 4C All in one modular 4 axis CNC drive board By C R Harding Specifications Main PCB & Input PCB Available with up to 4 Axis X, Y, Z, A outputs. Independent 25

More information

D287/D288/D292/D293A/D293E

D287/D288/D292/D293A/D293E D87/D88/D9/D9A/D9E EN Installation Guide Smoke Detector Bases D87/D88/D9/D9A/D9E Installation Guide.0 Overview.0 Overview The D87/D88/D9/D9A/D9E Smoke Detector Bases are designed for use with the D8 Ionization

More information

Ω POWEROHM RESISTORS, INC. Braking Resistors for Variable Frequency Drives APPLICATION SELECTING A STANDARD DESIGN CUSTOM RATINGS

Ω POWEROHM RESISTORS, INC. Braking Resistors for Variable Frequency Drives APPLICATION SELECTING A STANDARD DESIGN CUSTOM RATINGS Braking Resistors for Variable Frequency Drives APPLICATION AC variable frequency drives are commonly used with a general purpose AC induction motor to form a reliable variable speed drive system. For

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information