098 : 2000 CEB STANDARD MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA

Size: px
Start display at page:

Download "098 : 2000 CEB STANDARD MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA"

Transcription

1 098 : 2000 CEB STANDARD MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA

2 Specification for MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS CEB Standard 098 : 2000 CEYLON ELECTRICITY BOARD No. 50, Sir Chittampalam A. Gardener Mawatha, Colombo 2. Sri Lanka Telephone: , Facsimile: cebdp@mega.lk

3 CEB STANDARD 098: 2000 CONTENTS Page 1.0 Scope System Parameters Service Conditions Applicable Standards Technical Requirements Basic Features Additional Requirements Quality Assurance Information to be furnished with the Offer Inspection & Testing Annex. 9 1

4 CEB STANDARD 098: 2000 SPECIFICATION FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS 1.0 SCOPE This Specification covers the general requirements of the design, manufacture, testing, supply and delivery of medium voltage 12kV and 36kV distribution transformers. 2.0 SYSTEM PARAMETERS a) Nominal Voltage - 11kV 33kV b) System highest voltage - 12kV 36kV c) System frequency - 50Hz. 50Hz d) Number of phases e) Type of earthing - Effective Non effective f) System fault level MVA 1000MVA 3.0 SERVICE CONDITIONS a) Annual average ambient temperature - 35 C b) Maximum ambient temperature - 40 C c) Maximum relative humidity - 90% d) Environmental conditions - Humid tropical climate with heavily polluted atmosphere. e) Operational altitude - From MSL to 1900m above MSL f) Isokeraunic (Thunder Day) level - 90 days/year 4.0 APPLICABLE STANDARDS The equipment and the components supplied shall be in accordance with the latest edition of the standards specified below and amendments thereof. However the CEB Specification shall supersede these Standards in the event there is a discrepancy a) IEC (1995) Insulating bushing for alternating voltages above 1 kv b) IEC (1995) Insulating liquids-determination of the breakdown voltage at power frequency test methods c) IEC (1982) Specification for unused minerals insulating oils for transformers and switch-gear d) IEC (1991) Loading guide for oil-immersed transformers e) IEC (1987) Determination of transformer and reactor sound levels f) IEC (1978) Terminal and tapping markings for power Transformers g) IEC (1982) Guide to the lightning impulse and switching impulse testing of power transformers and reactors. 2

5 CEB STANDARD 098: 2000 i) IEC 0076 (1993) Power Transformers j) IEC (1986) Guide for the selection of insulators in respect of polluted conditions k) BS 2562 (1997) Cable boxes for transformers and reactors l) BS 5493 (1997) Protective coating of iron and steel structures against corrosion 5.0 TECHNICAL REQUIREMENTS 5.1 Medium Voltage Characteristics a) Nominal voltage 11kV 33 kv b) Rated voltage 12kV 36 kv d) Rated fault level 1000MVA 1000MVA e) Lightning impulse withstand voltage (peak) 75kV 200kV f) One min power frequency withstand voltage 28kV 70kV g) Off load tapping (Primary side) + 2.5%,0%, -2.5%, -5%, -7.5% h) Insulator creepage distance 290mm 720mm 5.2 Low Voltage a) Nominal system voltage 230/400 V b) Maximum system voltage 254/440 V c) One minute test voltage 3,000 V d) Impulse (1.2/50µ) wave withstand voltage 6,000 V 5.3 Other Performance Characteristics a) Vector group Dyn11 b) System frequency 50Hz c) Cooling type ONAN d) Insulation temperature class (IEC 76). A e) For uninterrupted continuous operation the rated power at 30 0 C ambient, maximum winding temperature rise 60 0 C f) Maximum top oil temperature rise (without conservator) 55 0 C g) Short circuit impedance voltage at 75 0 c between 4.0 p.u. and 5.0 p.u. h) Maximum noise level at 0.3m measured in accordance with IEC 551 [(tolerance 2dB (A))] 65dB(A) i) Short time withstand current duration (Under three phase faults) 2 seconds. j) No load loss and full load loss (corrected at 75 o C) at rated values, shall not exceed the values indicated in Table 1.0 for the respective transformers. 3

6 Table 1.0 CEB STANDARD 098: 2000 Transformer (kva) No Load loss (W) Full load loss (W) 100 kva, 11kV / 415V kva, 11kV / 415V kva, 11kV / 415V kva, 11kV / 415V kva, 33kV / 415V kva, 33kV / 415V kva, 33kV / 415V kva, 33kV / 415V BASIC FEATURES The transformers shall be of hermetically sealed type and suitable for outdoor application. They shall be fully rated at ambient temperature of 35 0 C. and the typical operating characteristics specified in clause 5.0 technical requirements shall apply to all transformers. 6.1 Transformer Construction The transformers shall be double-wound, oil immersed naturally cooled and hermetically sealed fully filled type The transformers for rating upto 250kVA shall be of pole mounted type and the 400 kva shall be of plinth mounted type The core shall be of high grade cold rolled grain oriented silicon sheet steel and securely clamped. The transformer core shall be of three limbs stacked core type The primary and secondary windings shall be constructed from high conductivity E.C. grade copper. All turns of windings shall be adequately supported to prevent movement. The high voltage winding shall be of layered winding and the low voltage winding shall be of foil winding using Copper sheets The core and coil assembly shall have the core and coils rigidly connected. The core/coil assembly shall be mounted on the cover plate so that the assembly could be removed from the tank using the suitably placed lugs provided on the cover plate No material which can be deleteriously affected by the action of oil under the operating conditions of the transformers shall be used in the transformers or leads or bushings To ensure that the core and coils of transformers are seated on the floor of the tank, supporting frames shall be designed to accommodate variations in tank height. The core and coil assembly shall be rigidly connected to the tank and suitably closed lugs shall be provided for removing the core and coil assembly from the tank Construction features shall permit local repairs to be easily carried out in the event of equipment failure. 4

7 CEB STANDARD 098: Transformer Tank The transformer tank shall be fabricated from steel and shall be of robust construction. Care should be taken at the manufacturing stage so as not to have leaks during transportation or when the transformer is continuously operated at rated power With the exception of radiator elements, all external joints shall be seam welded. There shall be only one vertical seam weld for the fin radiator and the other three vertical corner edges of the transformer shall be formed by bending. Corner ribs shall be avoided for the fin radiator. The bearing surface of the tank to which bushings are clamped shall be substantially flat All matching faces of joints shall be made oil tight and finished with a smooth surface to ensure that the gasketing materials make a satisfactory joint Flanges and covers of tanks shall be of sufficient thickness to prevent any depression occurring, which would retain water around the bolts. The horizontal edges of the cover plate shall be bent over the tank flange to facilitate water dripping out of the tank. The bent collar width shall be about 10mm to 15mm All the nut and bolts used shall be hot dip galvanised and spaced at sufficiently close intervals to avoid buckling of either flange or covers and shall provide reasonably uniform compression of the gasket Each transformer shall be provided with a minimum of two closed lifting lugs. The minimum diameter of the hole or width of the slot shall be 25 mm. The two lifting lugs shall be located such that there would be a minimum of 50 mm between the lifting chain and the nearest part of the bushings All transformers shall be suitable for outdoor mounting on pole or plinth platforms and shall have four mounting lugs with 12 mm diameter holes suitable for bolting the transformer to the platform. Bolt hole spacing shall be as specified by the purchaser to suit mounting requirements. 6.3 Transformer Sealing / Gasket The transformers shall be of the hermetically sealed type and provided with a satisfactory lid sealing gaskets The gasket shall of the good quality to maintain the sealing effect through its life span and shall prevent seeping of oil due to ageing and extreme operating temperature Gaskets provided with the transformers shall be suitable for making oil tight joints, and there would be no deleterious effects on either gaskets or oil when the gaskets are continuously in contact with hot oil. No gaskets shall be used in which the material of the gasket is mounted on a textile backing Exterior gaskets shall be of rubberized cork material, weatherproof and shall not be affected by strong sunlight. 5

8 6.4 Internal and External Finish CEB STANDARD 098: Both internal and external surfaces of the transformer shall be hot dip galvanized in compliance with ISO/BS/EN 1461: The surfaces shall be free of any zinc burrs both inside and outside After galvanizing, the external surface shall be prepared for powder painting by applying a suitable etch primer. The effect of etch primer shall be to avoid powder coating being peeled off from the galvanized surface. The powder shall then be applied and the powder used shall be an epoxy polyester cured with hydroxil alkyl. The powder coating thickness shall not be less than 50μm 6.5 Rating Plate A brass /stainless steel rating plate shall be fitted to each transformer. The information shall be deeply etched including the diagram of the connections of the windings, the vector diagram showing the general phase relations of the transformer, and a diagrammatic plan of the transformer cover showing the terminal positions and marking and other essential particulars The plate shall be mounted in an accessible position and following information shall be clearly and indelibly marked in English language. a) Transformer type b) Manufacturer's name c) Manufacturer's serial number d) Year of manufacture e) Number of phases f) Rated power at 30 O C g) Rated frequency h) Rated voltages i) Rated currents j) Connection symbol k) Mass of insulating oil l) Insulation levels m) Details regarding tapping n) Gross weight o) Impedance voltage at rated current Type of cooling total mass 6.6 Bushings All bushings shall be of porcelain clad, of the highest quality and comply with IEC 137. Creepage distance of the bushing insulator shall be 290mm for 12kV transformer and 720 mm for 36kV transformers. They shall be sealed in a manner to prevent ingress of moisture and to facilitate removal. The neutral bushings and stems shall be identical to those provided for phase terminations. Bushing palms shall be made of brass and be suitable for the bolting of conductor compression lugs The palms shall be suitably dimensioned, to suit the bushing rod and the holes spaced sufficiently apart to enable tightening of bolts using standard spanners and to prevent overlap of lugs. The LV bushing palms shall be as indicated in the drawing No. DS&S/2000/98A. 6.7 Terminal Leads Outgoing leads shall be brought out through bushings, the leads shall be such that the core and coils could be removed with the least possible interference with these leads, and they shall be specially supported inside the transformer to withstand the effects of vibration and short circuits. 6

9 CEB STANDARD 098: The leads shall be so fixed that they do not break at the connection and would not twist and touch each other in case the bushing is turned accidentally. 6.8 Earthing Connections Earthing connections shall be provided with connection facilities for 50mm 2 copper stranded conductor Three bolts of M12 size shall be located on either side of the tank base (two) and on the cover plate (one). 6.9 Off Load Tap Changer Voltage tappings shall be provided on the primary side of each transformer. Tapping step shall be ±2.5%. Number of tappings shall be as stipulated in the Clause 6.0 Technical Requirements The tappings shall be selected by an 'off load' tapping switch with an external hand wheel with provision for locking on to a selected tapping. The shaft shall be adequately sealed so that no seepage of oil occurs under all conditions of service The voltage operating positions, together with tap change positions shall be ` clearly and indelibly marked Surge Arrester Mounting Bracket The surge arrester mounting bracket made of steel shall be provided on the transformer cover plate The bracket shall be hot dip galvanised and suitable to accommodate three Nos. of surge arresters as indicated in the drawing No. DS&S/2000/98B 6.11 Oil All transformers shall be filled to the required level with a new, unused, clean, standard mineral oil in compliance with IEC Pressure Relief Valve The transformer tank shall be fitted with a suitable pressure relief valve to operate when the pressure exceeds 0.3 bars to prevent explosion of the transformer due to internal fault. 7.0 ADDITIONAL REQUIREMENTS 7.1 Terminal Marking All transformers shall have the primary and secondary terminal markings plainly and indelibly marked on the transformer adjacent to the relevant terminal. These markings shall be 25mm in height. 7

10 7.2 Radio Interference CEB STANDARD 098: 2000 When operated at voltage even up to 10% in excess of the normal system rating, transformers shall be substantially free from partial discharges (i.e. corona discharges in either internal or external insulation) which are likely to cause interference with radio or telephone communication. 7.3 Routine Tests The following routine tests as per IEC : 1993 shall be carried out on all the distribution transformers ordered and the routine test reports shall be made available for the observation of the CEB Inspector at the time of inspection. a) Measurement of winding resistance b) Measurement of voltage ratio and check of voltage vector relationship c) Measurement of impedance voltage, short-circuit impedance and load loss d) Measurement of no-load loss and current e) Dielectric routine tests f) Oil breakdown test g) Pressure test at 0.25 bar above atmospheric 7.4 Spare Parts and Tools The supplier shall specify the spare parts required for proper and continuos functioning of the transformers. The supplier shall also specify if any special tools are required for the maintenance of transformers other than those conventional for transformers. A schedule of prices and quantities of spare parts and special tools shall be given by the supplier. 7.5 Outline Drawings, Maintenance Manual and Packing Outline drawings and other necessary drawings baring an effect on customers' installation shall be provided with each transformer and a comprehensive maintenance manual shall also provided. 8.0 QUALITY ASSURANCE The manufacturer shall posses ISO 9001 Quality Assurance Certification for the manufacture of distribution transformers for the plant where the manufacture of distribution transformers is done. Bidders shall furnish a copy of the ISO certificate certified as true copy of the original by the manufacturer, along with the offer. 9.0 INFORMATIONS TO BE FURNISHED WITH THE OFFER 9.1 The following Information shall be furnished the offer a) Particulars requested in annex - A. b) Constructional features and materials used for components c) Separate explanatory drawings and dimensions of tap changer. d) Overall dimensional drawings e) Drawing of Rating plate to scale incorporating the particulars called for. f) Certified copy of the quality assurance conforming to ISO

11 CEB STANDARD 098: Type Tests Certificates The following Certificates of Type tests as per IEC by an internationally recognised independent testing authority shall be furnished with the offer a) Lightning Impulse withstand voltage test b) One minute wet power frequency withstand voltage test c) Temperature-rise test d) Acoustic sound level measurements e) Short-circuit tests The Type Test Certificates for short circuit tests shall be from one of the following testing authorities who are the members of the European Organization for Testing and Certification for Short Time Current Test and Short Circuit Breaking / Making Tests i) ASTA Certification Services - (ASTA) UK ii) Centro Electtrotecnico Sperimentale Italiano S. P. A. - ( CESI) Italy iii) Ensemble Des Stations D Essais a Grande Puissance Francaises (ESEF) - France iv) B.V. KEMA - (KEMA) - Netherlands v) Gesellschaft for Elektrische Hochleistungsprufungen - PEHLA- Germany vi) Scandinavian Association for Testing of Electrical Power Equipment - (SATS) - Scandinavia vii) Short Circuit Testing Liasion North America - (STLNA) - North America viii) Central Short-Circuit Testing Committee - (JSTC) - Japan Offers of Bidders who failed to provide above particulars in full shall be rejected INSPECTION AND TESTING 10.1 Inspection The selected Bidder shall make necessary arrangements for inspection of the equipment by an Engineer appointed by the Purchaser and also to carry out in his presence necessary Acceptance / sample tests of the materials and equipment, offered Acceptance /Sample Tests The following Acceptance/Sample tests conforming to IEC (1993) shall be witnessed by the Engineer. Extra copies of these Test Certificates shall also be supplied with the equipment. a) Measurement of winding resistance b) Measurement of voltage ratio and check of voltage vector relationship c) Measurement of impedance voltage, short-circuit impedance and load loss d) Measurement of no-load loss and current e) Dielectric routine tests f) Oil breakdown test g) Pressure test at 0.25 bar above atmospheric 11.0 ANNEX A - B - C - Details of Flag for 250A / 630A Bushings Surge Arrester Mounting Bracket Schedule of guaranteed technical particulars - To be filled by the Bidder 9

12 CEB STANDARD 098: 2000 ANNEX - C SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS To be filled by the Bidder for each rating (kv & kva) offered 1. Name of manufacturer & country of origin - 2. Applicable Standard - 3. Voltage rating kv/v - 4. Capacity kva - 5. Vector group - 6. Frequency Hz - 7. Cooling type - 8. Insulation temperature class - 9 Maximum winding temperature rise at Uninterrupted continuous operation, at rated power and at ambient temperature of 30 0 C 10. Maximum top oil temperature rise 0 C - 0 C Short circuit impedance voltage at 75 0 C pu Maximum noise level at 0.3m as per IEC 551 db No load Loss at 75 0 C W Full load Loss at 75 0 C W Lightning impulse withstand voltage (peak) kv Wet power frequency withstand voltage kv LV (1min) power frequency withstand voltage V LV impulse withstand voltage V Total creepage distance of the bushings mm Tap changer steps (number of steps) % Total weight kg - 10

13 22. Whether the offered transformers fully conform with CEB STANDARD 098: 2000 a) Clause Transformer Construction Yes/No. - b) Clause Transformer Tank Yes/No. - c) Clause Transformer Sealing Yes/No. - d) Clause 6.4 Internal & External Finish Yes/No. - e) Clause 6.5 Rating Plate Yes/No. - f) Clause 6.6 Bushings Yes/No. - g) Clause 6.7 Terminal Leads Yes/No. - h) Clause Earthing Connections Yes/No. - i) Clause 6.9 On Load Tap hanger Yes/No. - j) Clause Arrester Mounting Bracket Yes/No. - k) Clause 6.11 Oil Yes/No. - l) Clause 6.12 Pressure Relief Valve Yes/No. - m) Clause 7.1 Terminal Marking Yes/No. - n) Clause 7.2 Radio Interference Yes/No. - o) Clause 7.3 Routine Tests Yes/No Indicate the particulars of Spares to be supplied with each transformers Whether the Type Test Certficates as per Clause 9.2 are furnished Yes/no Whether the Acceptance /Sample Tests as per Clause 10.2 will be carried out Yes/No Whether the certificate of ISO 9001 quality Assurance furnished. Yes/No. - I/We certify that the above data are true and correct SEAL AND SIGNATURE OF THE MANUFACTUER / DATE Distribution transformers 11

14

15

16 Amendment Slip No. 01 Effective from 02 nd December 2004 To CEB Standard 098 : 2000 Specification for Medium Voltage Distribution Transformers REVISED TEXT December 2004 THE PROPOSED AMENDMENT TO CEB STANDARD 098 : 2000 SPECIFICATION FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS Clause 9.2 of the CEB Standard is amended to read as follows. 9.2) Type Test Certificates The following Certificates to Type Tests as per IEC by an internationally recognized independent testing authority shall be furnished with the offer. a) Lighting Impulse withstand voltage test b) Short-Circuit Tests The Type Test Certificates for short circuit tests shall be from one of the following testing authorities who are the members of the European Organization for Testing and Certification for Short Time Current Test and Short Circuit Breaking/Making Tests. i) ASTA Certification Servgices (ASTA) UK ii) Centro Electtrotecnico Sperimentale Italiano S.P.A. (CESI) Italy iii) Ensemble Des Stations D Essais a Grande Puissance Francaises (ESEF)-France iv) B.V.KEMA (KEMA) Netherlands v) Gessellschaft for Elektrische Hochleistungsprufungen PEHLA- Germany vi) Scandinavian Association for Testing of Electrical Power Equipment SATS)-Scandinavia vii) Short Circuit Testing Liasion North America (STLNA)-North America viii) Central Short-Circuit testing Committee (JSTC)-Japan The following Type Test Certificates shall also be provided from independent Testing Authorities. a) One minute wet power frequency withstand voltage test b) Temperature rise test c) Acoustic sound level measurements All type test certificates under clause 9.2 shall be furnished for 33kV/LV, 100kVA or 33kV/LV 160kVA or 33kV/LV 250 kva Transformers Offers of Bidders who failed to comply with the above in full shall be rejected. Amd. Slip 98

17 Amendment Slip No. 02 Effective from 07 th July 2005 To CEB Standard 098 : 2000 Specification for Medium Voltage Distribution Transformers REVISED TEXT July 2005 THE PROPOSED AMENDMENT TO CEB STANDARD 098 : 2000 SPECIFICATION FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS Following Clause shall be added as Clause ) Manufacturing Experience The bidder should have a minimum experience of ten years of design, manufacture and supply of Transformers similar to the requirements of the bidding documents. Amd. Slip 98

18 Amendment Slip General Amendments to CEB Specification Effective from REVISED TEXT 1. Tender form, Schedule of Prices, Letter of Authorization, Power of Attorney documents shall be signed in Blue Ink. Name of the persons signing shall be clearly indicated and their official stamp has to be put in. 2. Bidders shall include with their offer the Type Tests Report/Certificates in accordance with the Standard specified, obtained from an accredited independent test laboratory acceptable to the CEB. Proof of accreditation by a national/international authority shall also be forwarded with the offer. Test Reports shall be complete including all the pages as issued by the Testing Authority. Parts of the Test Report shall not be acceptable. R\slip.LF

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before

More information

Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva

Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic.

More information

James M. Pleasants Company

James M. Pleasants Company James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:

More information

SECTION 16461 DRY-TYPE TRANSFORMERS

SECTION 16461 DRY-TYPE TRANSFORMERS SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

CLAMPS CONNECTORS & EQUIPOTENTIAL RING

CLAMPS CONNECTORS & EQUIPOTENTIAL RING CLAMPS CONNECTORS & EQUIPOTENTIAL RING March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata

More information

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO. SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.

More information

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide 1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under: REQUIREMENT : The equipment offered shall be highly reliable suitable to operate satisfactorily in hot humid and polluted climate. The equipments offered shall work satisfactorily within temperature range

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide 1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003 MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

Explosion proof enclosures

Explosion proof enclosures 1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

V47 Series Temperature Actuated Modulating Water Valves

V47 Series Temperature Actuated Modulating Water Valves V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate

More information

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support. www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

Transformer oil cooler ALFA A02

Transformer oil cooler ALFA A02 A02 Transformer oil cooler ALFA Transformer oil cooler ALFA The transformer oil cooler ALFA is used to cool power transformers by means of forced air and oil flow. The oil in the cooler is circulated using

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY

More information

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer 168-08 TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE APPARATUS A three-phase outdoor oil-immersed distribution transformer DESIGNATION 1000 kva SERIAL No. 1-08-112-01-0001 Rated power Rated voltage

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Presentation of the France Transfo factories

Presentation of the France Transfo factories Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15

More information

OLI. Oil level indicator

OLI. Oil level indicator OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

CRN5-5 A-FGJ-G-E-HQQE 3x230/400 50HZ

CRN5-5 A-FGJ-G-E-HQQE 3x230/400 50HZ GRUNDFOS DATA BOOKLET CRN5-5 A-FGJ-G-E-HQQE 3x23/4 5HZ Grundfos Pump 96517184 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn5/96517184/crn-5-5-a-fgj-g-e-hqqe.html

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR)

TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR) TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR) (SPECIFICATION NO. DIST/MM-II/03/2005) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION

More information

CRN32-2-2 A-F-G-E-HQQE 3x400D 50 HZ

CRN32-2-2 A-F-G-E-HQQE 3x400D 50 HZ GRUNDFOS DATA BOOKLET CRN32-2-2 A-F-G-E-HQQE 3x4D 5 HZ Grundfos Pump 96122352 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn32/96122352/crn-32-2-2-a-f-g-e-hqqe.html

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC) APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines

More information

Low Voltage Transformers Sealed, General Purpose, Dry Type

Low Voltage Transformers Sealed, General Purpose, Dry Type Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

Compact pressure switch Flameproof enclosure Ex d Model PCA

Compact pressure switch Flameproof enclosure Ex d Model PCA Mechatronic pressure measurement Compact pressure switch Flameproof enclosure Ex d Model PCA WIKA data sheet PV 33.31 for further approvals see page 4 Process Compact Series Applications Pressure monitoring

More information

SECTION 22 LIGHTNING PROTECTION SYSTEM

SECTION 22 LIGHTNING PROTECTION SYSTEM SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for

More information

4. Combi valves. 7. Fire hydrants. 8. Check valves. 9. Air valves

4. Combi valves. 7. Fire hydrants. 8. Check valves. 9. Air valves 1. General company and product information 2. Flanged gate valves for water 3. Other gate valves for water 4. Combi valves 5. Service connection valves for water 6. Valves and fittings for gas 7. Fire

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60076-1 Edition 2.1 2000-04 Edition 2:1993 consolidated with amendment 1:1999 Power transformers Part 1: General This English-language version is derived from the original bilingual

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

22 kv ISOLATORS & ISOLATOR CUM EARTHING SWITCHES

22 kv ISOLATORS & ISOLATOR CUM EARTHING SWITCHES GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATION FOR 22 kv ISOLATORS & ISOLATOR CUM EARTHING SWITCHES GETCO/E/022TS ISO/R1

More information

Technical catalogue About KOLEKTOR ETRA has been acting as transformer manufacturer over more than 75 years. Specializing in the manufacturing of power transformers rating up to 500 MVA and 420 kv the

More information

Power Transformers 10 to 100 MVA

Power Transformers 10 to 100 MVA Power Transformers 10 to 100 MVA Transformer technology at a glance An extensive transmission system with efficient transformers is indispensable to ensure a reliable supply of power. Consequently Siemens

More information

Electrical Practices for Construction Work

Electrical Practices for Construction Work 1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

COATING & WRAPPING OF UNDERGROUND PIPING

COATING & WRAPPING OF UNDERGROUND PIPING CONSTRUCTION STANDARD SPECIFICATION DOCUMENT NO :SEC-PJ-000-SPC-PI-008 TOTAL PAGES : 8 Page 1 of 8 CONTENTS 1. SCOPE 2. DEFINITION 3. CODES AND STANDARDS 4. MATERIALS Page 2 of 8 1. SCOPE This specification

More information

ISORIA. Centered disc butterfly valves with AMRING elastomer liner. 240 PSI: 1½ to8. 150 PSI : 10 to 24

ISORIA. Centered disc butterfly valves with AMRING elastomer liner. 240 PSI: 1½ to8. 150 PSI : 10 to 24 Type series booklet 8448.1/2-EN--US ISORIA Centered disc butterfly valves with AMRING elastomer liner 240 PSI: 1½ to8 150 PSI : 10 to 24 Design in accordance with ISO 10631 Manual, electrical, pneumatical

More information

RUBBER SLEEVE KNIFE GATE VALVE

RUBBER SLEEVE KNIFE GATE VALVE RUBBER SLEEVE KNIFE GATE VALVE The model knife gate is a wafer valve designed for a wide range of industrial applications. The double-seated design provides bi-directional shut off. The design of the valve

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS

GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS 13.1 13.2 2006 Edition SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS GENERAL

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION PART 8000 - PRECAST CONCRETE TABLE OF CONTENTS Item Number Page 8100 PRECAST CONCRETE CONSTRUCTION - GENERAL 8-3 8101 General

More information

Sports and High Mast Lighting Poles Phone: (866) 474-7200 Fax: (817) 924-7049

Sports and High Mast Lighting Poles Phone: (866) 474-7200 Fax: (817) 924-7049 Sports and High Mast Lighting Poles 4 High Mast Lighting Poles General American LitePole offers a raising and lowering system that allows for ease of maintaining the lighting system at ground level. Ideal

More information

SPECIFICATIONS FOR TENDER NO: PSNR/SCP/VKS/E 1635 ANNEXURE I TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST

SPECIFICATIONS FOR TENDER NO: PSNR/SCP/VKS/E 1635 ANNEXURE I TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST ANNEXURE I Sl.No. Description for BHEL Requirement Offered Deviation Scope of supply, erection and commissioning: 1 The scope of this specification covers

More information

TARIFF CODE and updates standard

TARIFF CODE and updates standard TARIFF CODE and updates standard No HS CODE AHTN CODE PRODUCT DESCRIPTION PRODUCT TYPE STANDARDS IDENTIFIED 7207 Semi finished products of iron or non alloy steel Containing by weight less than 0.25% of

More information

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD)

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Note: This guidance document is a translation of official Chinese document which is issued by CQC (China Quality Certification Center) on

More information

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 01 (January. 2014), V6 PP 01-12 www.iosrjen.org Paper on Basbar Trunking System for Electrical Supply to Industrial

More information

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx DSF..10.**.HV Ex ATEX Operating Instructions 374E-64368 Valid from lot nr. 0103 General Function Use in potentially explosive environment

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

SECTION 15410 GROUND WATER STORAGE TANKS

SECTION 15410 GROUND WATER STORAGE TANKS SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

Data Sheet VITOSOL 100. Flat collectors for the utilisation of solar energy. Vitosol 100. Part nos. and prices: see price list

Data Sheet VITOSOL 100. Flat collectors for the utilisation of solar energy. Vitosol 100. Part nos. and prices: see price list VITOSOL 100 Flat collectors for the utilisation of solar energy Data Sheet Part nos. and prices: see price list File in: Vitotec 1 Manual, Index 16 Vitosol 100 Type s 1.7 Vitosol 100 Type s 2.5 Vitosol

More information

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1 Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader

More information

Waterproof Connectors for Outdoor Use

Waterproof Connectors for Outdoor Use Waterproof Connectors for Outdoor Use HR41A Series Mated condition diagram Nut-tightening rear mount type (panel thickness=mm) 70.5 Features 1. Waterproof connector designed for outdoor use Light-weight

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

Isover HVAC Application Handbook Installing fire protection insulation to metal ductwork

Isover HVAC Application Handbook Installing fire protection insulation to metal ductwork Isover HVAC Application Handbook Installing fire protection insulation to metal ductwork HVAC - Fire protection of metal ductwork Fire protection Thermal insulation Isover ULTIMATE TM Protect - Fire protection

More information

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in 891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC

More information

a Nexans company Catalogue 2014

a Nexans company Catalogue 2014 a Nexans company Catalogue 2014 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated

More information

AMPSEAL* Automotive Plug Connector and Header Assembly

AMPSEAL* Automotive Plug Connector and Header Assembly AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2

More information

SECTION 15140 - PIPE HANGERS AND SUPPORTS

SECTION 15140 - PIPE HANGERS AND SUPPORTS Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the

More information

TRANSFORMATORY DYSTRYBUCYJNE I MOCY POWER AND DISTRIBUTION TRANSFORMERS POL ENG

TRANSFORMATORY DYSTRYBUCYJNE I MOCY POWER AND DISTRIBUTION TRANSFORMERS POL ENG TRANSFORMATORY DYSTRYBUCYJNE I MOCY POWER AND DISTRIBUTION TRANSFORMERS POL ENG O Nas About us 1969 ze Starting activity in Tezze Trafo Elettro Service srl has specialized in the design and production

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Ergo-Pro Single Line Solar Station Installation and Operating Instructions Rp 3/4 Ergo-Pro Single Line Solar Station Installation and Operating Instructions Item No Pump type 677.21.70 WILO ST 15/6 13 2 4 11 Technical Specifications Max. operating pressure: 6 bar Max. operating

More information

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE

PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE FORM A PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE The following suggested specifications are written as a guide to assist the specifier in writing his own specifications. Specific circumstances

More information

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless

More information

PivotLoc Ladder Systems

PivotLoc Ladder Systems N25 ACCESS AND SAFETY EQUIPMENT SPECIFICATION CLAUSES PivotLoc Ladder Systems To be read with The Main Contract Preliminaries, General Conditions, Sub-Contract Preliminaries. MINIMUM CONTRACTOR STANDARD

More information

Site Planning Guide Aug 2011

Site Planning Guide Aug 2011 Site Planning Guide Aug 2011 Document Number : Phoenix Site Planning Guide Aug 2011 (2).docx Table of Contents 1. INTRODUCTION... 2 2. SERVICES REQUIRED... 3 3. ENVIRONMENTAL REQUIREMENTS... 5 4. SAMPLE

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

This section applies to the design and installation of transformers.

This section applies to the design and installation of transformers. ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies

More information

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics

More information

HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001

HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001 NEW POL DEPOT AT HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & S GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001 TECHNICAL SPECIFICATION OF XLPE, FRLS LT CABLES

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

3/2-way Solenoid Valve, direct-acting, NC or NO

3/2-way Solenoid Valve, direct-acting, NC or NO 3/2-way Solenoid Valve, direct-acting, NC or NO Electrical connection cable plug, Form A With or without manual override as standard Threaded port and sub-base s Impulse optional Type 6014 can be combined

More information

SERIES NG 1800 STRUCTURAL STEELWORK

SERIES NG 1800 STRUCTURAL STEELWORK MANUAL OF CONTRACT DOCUMENTS FOR HIGHWAY WORKS VOLUME 2 NOTES FOR GUIDANCE ON THE SPECIFICATION FOR HIGHWAY WORKS SERIES NG 1800 STRUCTURAL STEELWORK Contents Clause Title Page NG 1800 (08/14) General

More information

TRANSFORMER FITTINGS & ACCESSORIES

TRANSFORMER FITTINGS & ACCESSORIES TRANSFORMER FITTINGS & ACCESSORIES CONTENTS 1. Low Voltage transformer bushing clamps... 3 1.1. TOGA type clamps... 5 1.1.1. TOGA 1 type clamps... 5 1.1.2. TOGA 2 type clamps... 6 1.1.3. TOGA 3 type clamps...

More information