Extending the Life of Your Data Centre. Retrofitting with passive water cooling at the rack level.
|
|
- August Thompson
- 7 years ago
- Views:
Transcription
1 Retrofitting with passive water cooling at the rack level blackbox.com
2 Table of Contents Introduction... 3 Build or Renovate Add Heat Density As You Grow... 4 Heat Transfer Door Cooling... 4 Cost Analyses Retrofit Example... 5 University Case Study Summary... 9 About Black Box We re here to help! If you have any questions about your application, our products, or this white paper, contact Black Box Tech Support on or go to and click on Talk to Black Box. You ll be live with one of our technical experts in less than 30 seconds Page 2
3 Introduction The proliferation of new, extended application development in software as a service, as well as new vitualisation technologies, has created a conflict in many data centres between today's outdated capabilities versus tomorrow's growing needs. There is no doubt that the cost of building and managing data centre resources continues to increase yearly. Likewise, the yearly cost to power and cool data centres makes up a majority of operating expenses. Legacy data centres waste at least 50% of the energy they consume managing heat generated by IT systems. Most data centres are not new; they are housed in buildings that are using practices that could be 20 years old and have not yet caught up with the latest trends in IT rack power densities. Fully populated racks can dissipate as much as 7 25 kw per rack. High-end servers can dissipate more than 40 kw per rack. This level of density requires data centres to provide power and cooling densities that exceed typical current capabilities. Furthermore, most legacy data centres have not been designed to use their maximum capabilities, best practices have not been implemented, and the cooling requirements of IT equipment have been considerably less than optimal. This has created a common situation, as identified by the Uptime Institute, where data centres consume 2.0 to 2.6 times the cooling required by the IT equipment, thus wasting energy and power and further reducing the amount of IT that can be housed in the structure. By implementing best practices and optimising the performance of the existing air cooling infrastructure, data centre operators can improve the performance of the specified cooling infrastructure to 70% efficiency. The question data centre owners must ask themselves is if their current air cooling is acceptable at 70% or if they can continue to sustain that performance as computing technologies push power and cooling beyond their current requirements. What can operators expect from their environment if cooling requirements exceed 12 kw to up to 25 kw per rack? Page 3
4 Build or Renovate With the adoption of virtualisation, cloud computing, and consolidation, most data centres that have reached the upper limit of energy consumption essentially have two choices: build new or renovate. New data centres built using performance-enhancing cooling, either with fully optimised air, liquid cooling, or hybrid systems have improved efficiency. But the cost to build a new data centre is prohibitive. According to the Uptime Institute, the total capital expense of building a new data centre ranges from 11,000 to 16,000 or more per kilowatt. The second alternative is renovation. While renovation presents issues with improving existing space and operating a data centre through a rebuilding project, retrofitting allows you to achieve what you want at a fraction of the cost. Add Heat Density As You Grow This paper proposes that by retrofitting existing data centres with passive water cooling at the rack level, data centre operators can increase IT rack power densities at a fraction of the cost of building a new data centre. Furthermore, retrofitting allows data centres to take a deliberate approach to improvement, adding resources on an as-needed basis rather than completing a full build-out of an entire space at one time. This approach using passive water-cooling at the rack level also enables upgrades with no disruption to IT operations while achieving a significant cost savings in energy consumption, not to mention the capital expense of constructing a new data centre. Heat Transfer Door (HTD) Cooling Passive heat transfer doors can neutralise heat directly at the source the rack. These modules replace standard rear doors on IT equipment racks. Server fans draw in air through the chassis, passing the air through the liquid-filled fin-and-tube coil assembly, which removes the heat before reentry into the data centre. An HTD uses specially designed coils that maintain airflow through the rack with a negligible resistance to the airflow. An HTD can sensibly cool up to 35 kw of heat per rack. Taking up a minimum of floor space, the HTD is a flexible, efficient, and space-saving cooling solution for data centres. In a retrofit, an HTD system may be fed by a redundant pumping system, a Coolant Management System (CMS) that creates a secondary loop that controls the heat exchanger temperature to avoid water condensation risks. Being passive, the energy consumed by such a system is negligible, which creates a significant energy savings compared to air-driven cooling. There are also instances where existing facilities can be retrofitted without using a CMS, where the new cooling system can be connected directly to a chiller. Figure 1 shows a typical system layout. This system can remove as much as 35 kw when used at the recommended new American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) conditions. It has been designed to minimise any pressure drop compared to the existing perforated door, resulting in no meaningful temperature rise inside the rack. IT equipment tests by IBM and Dell have shown less than a 1.8 F (1 C) increase in computer CPU junction temperature, which is negligible. Figure Page 4
5 Figure 2 is a photograph of a Passive HTD. HTD units work with a number of currently available enclosures using transition frames. Each HTD can easily be fitted to an enclosure within minutes without disrupting IT operations. Cost Analyses Figure 3 compares the cost to retrofit a data centre to the cost to build a new one. This analysis is based on data derived from customers and the Uptime Institute. DataSite Orlando is a managed services data centre that is housed in a former telco site. The facility was designed to optimise power and cooling efficiency, using best practices to improve Figure 2 its performance in its conventionally cooled areas. In its higher-density areas DataSite Orlando uses passive liquid cooling, which, in addition to enabling higher density loads, freed up 75 percent of the centre to white space. DataSite now has the ability to cool up to 200 watts per square foot with standard air cooling and up to 600 watts per square foot using passive liquid cooling. DataSite Orlando is the flagship property in BURGES property + company s high-tech real estate portfolio. According to Jeff Burges, president and founder of BURGES property + company, increasing heat density in an existing structure using conventional cooling can be accomplished in a two-step process. First, the existing structure can be upgraded and optimised using best practices. In this example, a 10,000-square-foot, 350-kW datacenter is looking to increase capacity to 1.5 megawatts. Two options exist: Upgrade existing facility and increase density from 35 watts/sf to 150 watts/sf; OR Build a new facility. In an upgrade scenario, the cost to upgrade power and cooling infrastructure supporting the existing 350 kw load is estimated at 700 per kilowatt. The power and cooling infrastructure for the new load of 1,150 kw is estimated at 7,000 per kw (assuming no new space construction cost). The combined cost totals over 8M. In comparison, building a new data centre with an IT load of 1.5 megawatts at a cost of 8,000 would total nearly 12M over 30% more than the cost of retrofitting. In addition, time, planning, and market risk significantly increase under a new build scenario. Retrofit Example Retrofitting and densifying existing facilities is most economical Cheaper and faster Ability to use state-of-the-art cooling at lower cost Current Desired Desired 35W/ft 2 (10,000 ft 2 ) 350 kw 350 kw 125W/ft 2 (10,000 ft 2 ) 900 kw 900 kw 125W/ft 2 (2800 ft 2 ) 125W/ft 2 (7200 ft 2 ) Figure Page 5
6 Figures 4 and 5 illustrate the comparison between each cooling option. An added benefit of using passive, localised liquid cooling is a redistribution of space condensing the space requirement for IT into 25 percent of the existing footprint. Comparisons are based on very conservative estimates. Retrofit Costs Upgrade Existing Power New Power Infrastructure Totals kw addressed Cost to upgrade/add existing power per kw 700 7,000 Total cost 245,000 8,050,000 8,295,000 New Build Costs Retrofit saves approx. Total load (kw) % New power + cooling costs 8,000 over new build. Total P&C costs for new build* 12,000,000 *Excludes cost/kw for non-p&c infrastructure: e.g., land, building, etc. Estimated to be 190/SF Key assumptions Spec new Scenarios Current Target Increase New data centre construction for power + cooling engine (Uptime Institute) 8,000 Local/SF Infrastructure portion of total cost 10% DC critical area 10,000 10,000 Infrastructure cost in pounds 800 Total load (kw) Power + cooling 7,000 Implied kw per rack Existing power reconfiguration cost 315 Cooling retrofit cost 375 } 690 Figure 4 In larger data centres, this comparison is equally compelling as shown in Figure 5: Retrofit Costs Upgrade Existing Power New Power Infrastructure Totals kw addressed Cost to upgrade/add existing power per kw 700 7,000 Total cost 700,000 28,000,000 28,700,000 New Build Costs Retrofit saves Total load (kw) % New power + cooling costs 8,000 over new build. Total P&C costs for new build* 40,000,000 *Excludes cost/kw for non-p&c infrastructure: e.g., land, building, etc. Estimated to be 190/SF Key assumptions Spec new Scenarios Current Target Increase New data centre construction for power + cooling engine (Uptime Institute) 8,000 Local/SF Infrastructure portion of total cost 10% DC critical area 10,000 10,000 Infrastructure cost in pounds 800 Total load (kw) Power + cooling 7,000 Implied kw per rack Existing power reconfiguration cost 315 Cooling retrofit cost 375 } 690 Figure Page 6
7 University Case Study A large midwestern university's advanced computing centre provides high-performance computing and storage for cutting-edge science, engineering, and social science research across the school. It needed additional cooling capacity and power distribution to support a new 1200-node HPC cluster. Data centre power, space, and chilled water capacity constraints eliminated the option of selecting traditional precision air conditioning as an alternative. The university selected passive, liquid cooling using heat transfer door technology as the basis for the cluster expansion cooling solution. The design consisted of 50 rear door heat exchangers, which act as passive radiators to cool the exhaust air from each enclosure. The units were connected by hoses to five 150-kW Coolant Management Systems (CMS), and the CMS transferred the heat to the building s primary chilled water loop. The data centre faced a number of challenges when evaluating cooling methods. First, the facility is housed below-ground, with limited overhead space and shared chiller resources. The centre has only shallow raised floors and therefore the air is delivered from the ceiling. This cooling method was not uniformly distributed. Before increasing the server density, the data centre consumed 500 kw, which did not include the power to run the 12 traditional 20- and 30-ton computer room air conditioners needed to cool the data centre. Once densified, the data centre was able to increase the compute power 888 kw, and eliminate three of the computer room air conditioners from the area where the rear door heat exchangers were installed. Retrofitting the existing data center dropped the capital expense from a potential 40M for a new data centre to about 625,000 for the retrofit. Since the heat transfer doors operated at above dew point, the selection also eliminated the need for additional pumps and systems to remove condensation. Each CMS expends little energy, consuming no more than 2.5 kw. From a cost perspective, given an electric rate of.003 kwh, the cost to operate the CMS, the data centre saves more than 80,000 in operating expenses over a five-year period. With utility prices increasing, the operating expense savings could top 125,000 in ten years. In addition these examples don t take into account the expense associated with unused cooling capacity or power. Eliminating unused, excess cooling and power, which is typical in many older data centres, makes the financial benefits of the retrofit even more significant. The following charts illustrate a generic example comparing HTD cooling to both non-passive in-row cooling and traditional Computer Room Air Conditioners (CRACs). In many cases, the initial capital cost of the HTD solution is comparable to other solutions. Given the significantly lower power consumption and on-going maintenance of the HTD, operating costs are significantly lower. Therefore, when reviewing the total cost of ownership, the HTD is a very compelling solution. Figures 7 and 8 show a typical example comparing the solutions and the total cost of ownership or TCO, which equals Day 1 capital + cumulative operating expense (OPEX) over the time horizon shown. In this example, the assumed load per rack is 12 kw. The capital expense (CAPEX) costs are likely understated in the CRAC scenario given that containment costs in a 12-kW/rack environment would be more expensive. In addition, a taller raised floor will likely be necessary (most traditional raised floors would not be able to accommodate the airflow needed to cool 12 kw/rack). In addition, the energy cost assumption is today s UK. average of roughly 0.06/kW. Most urban areas are more expensive, and the model does not reflect any energy cost increases in the future years. All this would make CRACs and higher power consuming in-rows even less attractive than shown below. Figure 6: Assumptions/output of generic example: Key assumptions RDHx CRAC In-row, no HACS Number of Racks Cooling Units (RDHx/CRAC/In-rows) CDUs/Manifolds needed 5 5 Cooling equipment footprint (sq. ft.) Cooling equipment power consumption (kw) Total square feet needed if new Power consumption Power draw RDHx/CRAC/In-rows (kw per unit) Power draw CDUs and Manifolds (kw per unit) 2.5 Total power draw all units (total kw) Page 7
8 Figure 7: Capital Expenses and Total Operating Expenses 375,000 CAPEX ANNUAL OPEX 75, ,500 62, ,000 50, ,500 37, ,000 25,000 62,500 12,500 CAPEX 0 $0 OPEX HTD CRAC/CRAH In-row (no HACs) HTD CRAC/CRAH In-row (no HACs) Figure 8: Total Cost of Ownership 625 TCO CAPEX 0 Initial cost Yr 1 Yr 2 Yr 3 Yr 4 HTD CRAC/CRAH In-row (no HACs) Page 8
9 Summary Using passive liquid cooling opens options in retrofitting for optimised performance, a comparable initial cost compared with traditional cooling options, and the opportunity to increase cooling capacity without disrupting operations. Long-term, liquid cooling is significantly more cost-effective to data centre operators. The question of passive liquid cooling isn t if, but when Page 9
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
More informationData Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
More informationData Center Equipment Power Trends
Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data
More informationBlade Server & Data Room Cooling Specialists
SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling
More informationHigh Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
More informationUnified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
More informationIT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
More informationBlade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity
Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face
More informationLiquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
More informationThe New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
More informationElements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
More informationDealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationRittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
More informationAnalysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationIn Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
More informationRittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy
Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and
More informationIncreasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
More informationBytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL
Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration
More informationData Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationManaging Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
More informationEnabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
More informationVISIT 2010 Fujitsu Forum Europe 0
VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00
More informationCIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How
CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch
More informationData Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services
Data Center & IT Infrastructure Optimization Trends & Best Practices Mickey Iqbal - IBM Distinguished Engineer IBM Global Technology Services IT Organizations are Challenged by a Set of Operational Issues
More informationData Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
More informationNational Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
More informationSteps to Achieve Green Data Center
Global Technology Services Oh Bee Joo IBM GTS/ITS - ASEAN-Site and Facilities Services Senior Project Manager, Subject Matter Expert Site and Facilities Services Where IT and the Building Meet Do you know
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2013
European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started
More informationMetering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk
Metering and Managing University of Sheffield Data Centres Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk Summary ICT Electricity Use Footprint Data Centre Electricity Use European
More informationAPC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
More informationEnclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
More informationData Center Colocation Build vs. Buy
Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for
More informationChallenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
More informationPaul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
More informationAIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
More informationData Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
More informationCANNON T4 MINI / MICRO DATA CENTRE SYSTEMS
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly
More informationStrategies for Deploying Blade Servers in Existing Data Centers
Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling
More informationHow to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
More informationAPC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
More informationWhite Paper Rack climate control in data centres
White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC
More informationDOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and
More informationData Center Facility Basics
Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern
More informationData Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
More informationAirflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
More informationImproving Data Center Efficiency with Rack or Row Cooling Devices:
Improving Data Center Efficiency with Rack or Row Cooling Devices: Results of Chill-Off 2 Comparative Testing Introduction In new data center designs, capacity provisioning for ever-higher power densities
More informationDataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
More informationHot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationData Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
More informationCooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
More informationAdaptive Cooling in Data Centers. Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009
Adaptive Cooling in Data Centers Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009 Maximizing Cooling Efficiency in a Concurrently Maintainable and Fault
More informationThe Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
More informationVirginia Tech. Background. Case Summary. Results
Background Virginia Tech When Virginia Tech initiated plans to build a supercomputer by clustering hundreds of desktop computers, it had ambitious goals for the performance of the new system and a very
More informationServer Room Thermal Assessment
PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...
More informationIMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
More informationHow To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
More informationAlcatel-Lucent Modular Cooling Solution
T E C H N O L O G Y W H I T E P A P E R Alcatel-Lucent Modular Cooling Solution Redundancy test results for pumped, two-phase modular cooling system Current heat exchange methods for cooling data centers
More informationManaging Today s Data Centers Avoiding the Impending Crisis
Managing Today s Data Centers Avoiding the Impending Crisis Steven Yellen Aperture Research Institute EXECUTIVE SUMMARY Organizations are facing an impending data center management crisis. The constant
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
More informationImplementing Energy Efficient Data Centers
Implementing Energy Efficient Data Centers By Neil Rasmussen White Paper #114 Executive Summary Electricity usage costs have become an increasing fraction of the total cost of ownership (TCO) for data
More informationSmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity
SmartDesign Intelligent, Integrated Infrastructure For The Data Center Solutions For Business-Critical Continuity Prepare Your Data Center For What s Next Efficiency. Availability. Capacity. Control. One
More informationRecovering Stranded Capacity in the Data Center. Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09
Recovering Stranded Capacity in the Data Center Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09 2 Recovering Stranded Data Center Capacity most data centers are overcooled & inefficient
More informationState of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
More informationIntroduction to Datacenters & the Cloud
Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview
More informationThe Advantages of Row and Rack- Oriented Cooling Architectures for Data Centers
The Advantages of Row and Rack- Oriented Cooling Architectures for Data Centers By Kevin Dunlap Neil Rasmussen White Paper #130 Executive Summary Room cooling is an ineffective approach for next-generation
More informationHow High Temperature Data Centers and Intel Technologies Decrease Operating Costs
Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features
More informationData center TCO; a comparison of high-density and low-density spaces
White Paper Data center TCO; a comparison of high-density and low-density spaces M.K. Patterson, D.G. Costello, & P. F. Grimm Intel Corporation, Hillsboro, Oregon, USA M. Loeffler Intel Corporation, Santa
More informationLeveraging Radware s ADC-VX to Reduce Data Center TCO An ROI Paper on Radware s Industry-First ADC Hypervisor
Leveraging Radware s ADC-VX to Reduce Data Center TCO An ROI Paper on Radware s Industry-First ADC Hypervisor Table of Contents Executive Summary... 3 Virtual Data Center Trends... 3 Reducing Data Center
More informationBICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.
BICSInews m a g a z i n e july/august 2012 Volume 33, Number 4 plus + Industrial-grade Infrastructure and Equipment + I Say Bonding, You Say Grounding + Data Center Containment & design deployment The
More informationCooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
More informationAPC by Schneider Electric
APC by Schneider Electric Energy Efficiency - The Green Power Solution James Taylor Business Development manager, UK APC by Schneider Electric The Efficient Enterprise Components Close Coupled Cooling
More informationReducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
More informationEnergy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
More informationBenefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationBest Practices. for the EU Code of Conduct on Data Centres. Version 1.0.0 First Release Release Public
Best Practices for the EU Code of Conduct on Data Centres Version 1.0.0 First Release Release Public 1 Introduction This document is a companion to the EU Code of Conduct on Data Centres v0.9. This document
More informationRaised Floor Data Centers Prepared for the Future
Raised Floor Data Centers Prepared for the Future Raised Floors Protect My Investment by Providing a Foundation for Current and Future Technologies. Creating the Future Proof Data Center Environment The
More informationCase Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
More informationEUROPEAN COMMISSION DIRECTORATE-GENERAL JOINT RESEARCH CENTRE Institute for Energy and Transport Renewable Energy Unit. 2013 Best Practices
EUROPEAN COMMISSION DIRECTORATE-GENERAL JOINT RESEARCH CENTRE Institute for Energy and Transport Renewable Energy Unit 201 Best Practices for the EU Code of Conduct on Data Centres Version 4.0.5 1 Document
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationRittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
More informationDataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
More information2010 Best Practices. for the EU Code of Conduct on Data Centres. Version 2.0.0 Release Public Review Public
2010 Best Practices for the EU Code of Conduct on Data Centres Version 2.0.0 Release Public Review Public 1 Document Information 1.1 Version History Version 1 Description Version Updates Date 2.0.0 2010
More informationW H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers
W H I T E P A P E R Computational Fluid Dynamics Modeling for Operational Data Centers 2 Executive Summary Improving Effectiveness of CFD Technology in Cooling of Data Centers IT managers continue to be
More informationIBM Portable Modular Data Center Overview for Critical Facilities Round Table
Brian Canney Global Services Executive, IBM GTS Site and Facilities Services April 2011 IBM Portable Modular Data Center Overview for Critical Facilities Round Table 2009 IBM Corporation Key messages Containers
More informationHow To Find A Sweet Spot Operating Temperature For A Data Center
Data Center Operating Temperature: The Sweet Spot A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL
More informationEnergy and Cost Analysis of Rittal Corporation Liquid Cooled Package
Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package Munther Salim, Ph.D. Yury Lui, PE, CEM, LEED AP eyp mission critical facilities, 200 west adams street, suite 2750, Chicago, il 60606
More informationPresented at ISA Summit - Stockholm, Sweden. March 19, 2009 Dean Nelson Sr. Director, Global Lab & Datacenter Design Services (GDS)
Presented at ISA Summit - Stockholm, Sweden March 19, 2009 Dean Nelson Sr. Director, Global Lab & Datacenter Design Services (GDS) 1 Unique Challenge 2 Demand and Capacity Are Colliding......And Data Centers
More informationI-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 4, Lancaster University, 2 nd July 2014 Background Data centres estimated to use 2-3% of total electricity consumption in the UK and generate
More information