1 MONTGOMERY HIGH SCHOOL: FIELD HOUSE
2
3 CAMPUS DATA MONTGOMERY HIGH SCHOOL: FIELD HOUSE Hwy 105 West, Montgomery TX Year Built 2003 Approx. Total Square Footage Grades Served 11,300 n/a Current Enrollment n/a Building Levels 1 1
4 MASTER PLAN 2
5 BUILDING CONDITION: EXTERIOR Building Envelope Brick and Mortar: Brick walls are discolored throughout the building, especially under gutter joints and hose bibs and near the ground. Soffits: Soffits are in fair condition, but have wasp and bird houses that need to be removed. Vents on soffits are corroded. Gutters and Downspouts: Water is leaking at gutter joints throughout the building deteriorating gutter joints and discoloring brick walls below. Doors and Hardware: Exterior doors are in poor condition with finishes damaged and some hardware corroded. Dirt and wasp house residues are accumulated on the exterior side of doors. Storefront: Dirt and wasp house residues are accumulated on the exterior side of storefronts. A metal sill underneath the storefront on the west façade is touching the ground directly and corroding severely. Drinking Fountains: Drinking fountains are not working or in poor condition and need to be replaced. Data: Data outlets and railing next to outlets need to be removed as they are not used any more. Site Conditions Pavement Conditions: Pavements are cracked and stained at several locations. Grade Conditions: The exterior mechanical area on the east façade is not paved and is not graded properly that water is collecting and deteriorating pipe insulations. A concrete curb exists under the gate to the mechanical area, thus trapping water even further. The area should be properly graded or paved in order to drain water away from the mechanical equipment and the building envelope. Plants and Shrubs: Soil is bare without grass at several locations due to ponding. 3
6 BUILDING CONDITION: EXTERIOR 4
7 BUILDING CONDITION: EXTERIOR Downspouts are missing splash blocks causing erosion and water collection near the building envelope at several locations. The signage is damaged. The pipe opening sealant is deteriorated. The bottom brick courses are discolored. The brick is discolored at several locations; especially below gutter joints and hose bibs and at bottom courses. An example of brick discolored below gutter joints throughout the building. An example of brick walls discolored below hose bibs. 5
8 BUILDING CONDITION: EXTERIOR The metal sill underneath the storefront on the west façade is touching the ground directly causing corrosion. The storefront needs to be refinished due to accumulated dirt. A splash block is in disrepair and sloped improperly causing water to collect. Drains are not provided underneath downspouts causing bottom brick courses and pavements to stain. Water is leaking from gutter joints causing gutters to discolor and deteriorate throughout the building. The data outlets left on the west façade should be removed. The guardrail below data outlets need to be removed. 6
9 BUILDING CONDITION: EXTERIOR The drinking fountains are either not working or are in poor condition with corrosion and stains. All four drinking fountains throughout the building need to be replaced. A metal cover is installed at a corner on the east façade and is not sealed properly. The existing light fixtures have dirt accumulated above and need to be cleaned or replaced. Moderate cracks exist on the pavement throughout the building. A downspout on the east façade is damaged and needs to be replaced. The top courses of brick walls at the mechanical area are discolored and mortars are cracked. 7
10 BUILDING CONDITION: EXTERIOR An example image of brick discoloration throughout the building. A concrete masonry unit at the mechanical area is damaged. Improper grading and lack of pavement is causing water to collect within the mechanical area, thus deteriorating insulations around pipes. The concrete curb under the gate is trapping water within the mechanical area. The gate is corroded and scraped and needs to be refinished. An overview of the exterior mechanical area. Vents on soffits are corroded. A filter that is in a different size than the vent is placed. 8
11 BUILDING CONDITION: INTERIOR Summary of Conditions Floors: Resinous flooring in the locker rooms have some heavy staining, it is recommended that floors be refinished. Flooring in locker room have some cracks. VCT tiles are used throughout the corridors. Tiles are in fair condition however there are some damaged and broken tiles in the entrance that should be replaced. VCT tiles located in the trainer s room have been severely stained from ice machine dripping water on the floor. It is recommended that all tiles be replaced. Concrete floors located in the concession stand restrooms have stains throughout areas of the floors, all floors should be refinished. Concrete flooring in both coaches locker rooms are cracking in several areas, floors also have minor staining. Walls: Walls throughout the facility are masonry. Masonry walls have cracks in several rooms throughout the facility. It is recommended that walls be refinished, can be determined on a room by room basis. Rubber base should be replaced in the locker rooms. Ceilings: Some ceiling tiles are damaged in locker rooms. Ceiling tiles have water leak stain in several rooms. All tiles with stain should be replaced and area above ceiling should be investigated. Gypsum ceiling is cracking at the corner with masonry wall. Gypsum ceiling is also damaged in one of the locker rooms. Doors and Hardware: Most exterior doors and frames throughout the facility need to be refinished. Several interior door frames have paint chipping off. Frames should be refinishing. Windows: Store front hollow metal frames should be refinished. The window located in room 104 has water leak stains on frame. Window should be resealed to stop water leaks. Hollow metal frame also has corrosion. Casework: Casework located in trainer s room is in poor condition. Water has expanded the wood. Casework in storage room has a cabinet door that does not maintain closed; also casework does not have a finish. Casework in concessions should be refinished, sink is leaking, and base is peeling off. It is recommended that casework in trainer s office and in concessions be replaced. Signage: Some doors are missing signage. Signage does not match from corridor signage to locker room and exterior signage. It is recommended that new signage be installed to have consistency. 9
12 BUILDING CONDITION: INTERIOR 10
13 BUILDING CONDITION: INTERIOR 101 Tiles under ice machine are in poor condition and should be replaced. 101 Damaged case work in trainer's room. 101 Another area of casework damaged in trainer's room. 102 Locker Room Locker has been damaged. 102 Locker Room Floor in locker room has crack. 102 Locker Room ADA bench does not have the adequate clear space. Huckabee 11
14 BUILDING CONDITION: INTERIOR 102 Locker Room Gypsum ceiling has been damaged. Hole should be patched up. 102A Caulking is cracking. 102A Rest room has severe staining. Floor should be refinished. 103 Toilet 18 1/4 From Wall To Center. Height Is Good. Grab Bars Are High From Req. 36 1/2" & 37 1/2" 103 Concrete floor has stains under urinals and sink. 104 Masonry wall has a diagonal crack. Huckabee 12
15 BUILDING CONDITION: INTERIOR 104 Window Frame Has Leak Stain And Corrosion. 105 Toilet Is Compliant. Grab Bars Are Non Compliant, Are 36 3/4" & 37 1/4" 106 Floor has cracks. 106B Ceiling tiles has been heavily stained. 107 Laundry Ceiling tiles are heavily stained. 107A (Storage) Door clearance is obstructed by copy machines. Huckabee 13
16 BUILDING CONDITION: INTERIOR 107A (Storage) Door clear space is being obstructed be an object. 107A (Storage) Cabinet door does not close. 108 Locker Room Locker room has a crack that splits in two. 108 Locker Room Ceiling tile has water leak stains. 108 Locker Room Locker room floor should be refinished. Finish is scraping off. 108 Locker Room ADA bench does not have the adequate clear space. Huckabee 14
17 BUILDING CONDITION: INTERIOR 108 Locker Room Ceiling tile is broken at the corner. 108 Locker Room Drinking fountain is in compliance. 108A Sinks are compliant. 108A Floor has a severe stain. Concession Casework is in poor condition. Counter is warping from water. Concession Closer look at damaged case work. Huckabee 15
18 BUILDING CONDITION: INTERIOR Entr. Hall CVT tiles are damaged. Should be replaced. Entr. Hall Door should be refinished. Has paint chipping off at the edges. Entr. Hall Additional view of VCT tiles that are damaged. Men's RR-B Floor has staining underneath urinals. Floor should be refinished. North Corridor Celling tile has a water leak stain. North Corridor Knee clearance is not compliant. Huckabee 16
19 BUILDING CONDITION: INTERIOR North Corridor Area has VCT tile that has broken off. North Corridor Window frame should be refinished. Fishing has scraped off. North Corridor Ceiling tile has a water leak stain. North Corridor Sealant is cracking should be stripped and replaced. RR-A Wall has a crack. crack travels horizontally and vertically along the mortar. WHall Crack is starting to develop. Huckabee 17
20 BUILDING CONDITION: INTERIOR WHall Bulkhead has a crack at corner. Women's RR A No Turn Radius 4' - 3/8" Huckabee 18
21 BUILDING CODE AND TAS Exterior Conditions Accessible Path: All paths are accessible. Stairs and Ramps: N/A Changes in Level: N/A Door Landings: N/A Interior Conditions Accessible Paths: ADA benches in locker rooms do not have the appropriate clear space needed for a wheel chair. access. Protruding Objects: N/A Door Clearances: All doors have compliant door clearances however, there are several doors clearances that are being obstructed by objects. Doors Hardware: Admin entrance door does not have a key lock set through the inside of the building. Coaches locker room does not have a manual push lock bottom from inside of room. Restrooms: Exterior men s restroom has two urinals that are higher than the allowed height, all other fixtures are compliant. Exterior women s restrooms do not have a turning radius and all sinks do not have mirrors. All other fixtures are compliant.. Grab bars located in both coach s locker rooms and in boys locker are higher than the allowed Grab bars should be lowered to be compliant. Exterior single use restroom is compliant. Many Fixture accessories are corroding throughout the facility s restrooms. Drinking Fountains: Drinking fountains in locker rooms are in ADA compliance. ADA drinking fountain located in the corridor does not have a compliant knee clearance. The drinking fountain is at 26.5 and the minimum allowed is 27. Counters, Sinks and Work Surfaces: Sink located trainer s room is compliant but is in poor condition. Clothes/Book bag Hooks: N/A Room Signage: Some doors are missing signage. It is recommended that new signage be installed. 19
22
23 ENGINEERING REPORT - STRUCTURAL Refer to Structural Engineering Report of Montgomery High School for more information. 21
24
25 ROOFING Montgomery ISD Athletics Facility is a one story structure with a standing seam metal roof system. The standing seam metal roof system is bound by a prefinished perimeter metal. The drainage of the standing seam metal roof system is accomplished by using gutters along all sides of the roof and drains onto the adjoining field. Roof Composition: No cores were taken on the metal roof system. Deficiencies: The roof systems appeared to be in fair condition as numerous deficiencies were observed. 1. Scored standing seam panels showing signs of surface rust./ 11 EA 2. Deteriorated sealant joints./ 4 EA Recommendations: Perform remediation s to the deficiencies listed above. Performing recommended repairs may extend the roof s estimated remaining service life by slowing the deterioration of the roofing system components. 23
26 ROOFING
27 ROOFING General view of the scored roof panels. General view of the scored roof panels. General view of the scored roof panels. General view of the deteriorated sealant joint. 25
Facility Assessment Report, Montgomery Independent School District
THE LEARNING CENTER CAMPUS DATA THE LEARNING CENTER 700 Dr. Martin Luther King Jr. Drive, Montgomery TX 77356 Year Built 1958 Approx. Total Square Footage Grades Served Current Enrollment 22,050 n/a n/a
More information17,280 square feet Overview:
CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The
More information48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No.
Classification: Cluster: Location: Total Area: No. of Stories Aquarium Acreage Owned: Acquired: 1904 Most Recent Improvements: THE AQUARIUM Close to junction of Inselrhue and Loiter Way, Belle Isle Two
More informationInspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
More informationArchitectural Condition Survey
Architectural Condition Survey Santa Fe Railroad / AMTRAK Depot, Lawrence. Kansas for the City of Lawrence, 2002 Survey: (student) PI: William Carswell, Associate Dean, School of Architecture, University
More informationFacility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components
Infrastructure Facility Condition Summary Weighted Avg Condition Score Facility Components Systems Surveyor/ Date Done Comments G Sitework.9 Site Improvements Parking Pedestrian Paving Site Development
More informationMarch 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202
Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request
More informationSODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST
SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS HIGH SCHOOL REPAIRS AND UPGRADES SITE Construction Estimate = $100,000
More information3. Tile used in the toilets is generally in good shape, though somewhat dated looking. The floor tile is slippery when wet.
Architectural Elements Support Facilities A. System Description 1. Architectural support facilities include the lobby, classroom, fitness room, office area, staff toilet/showers, public toilet/lockers,
More informationwww.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
More informationFacility Assessment for. 11801 East Main Street, Huntley, IL
Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested
More informationHow To Check For A Deficiency
UPCS in Pictures The following pictures are not all inclusive nor does it cover every deficiency. The pictures, however are some of the most commonly cited deficiencies on REAC inspections. Erosion The
More informationSelf-Home Inspection Checklist
To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional
More informationCONSERVATION MAINTENANCE WORKSHEET Universal Checklist
3.1 SITE 1 Concrete curbs Check for cracks, spalling, growth from joints X 2 Stone curbs Check for cracks, spalling, growth from joints X 3 Concrete walkways Look for uneven surfaces, ponding, growth from
More informationPresentation Agenda. Introduction. Types of Flooding Identifying Flood Risks Property Improvements Additional Resources.
Presentation Agenda Introduction Types of Flooding Identifying Flood Risks Property Improvements Additional Resources Discussion / Q&A 4 RainReady Home an initiative of RainReady is an initiative of the
More informationInspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com
More informationVision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
More informationRoof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:
More informationVILLAS OF TRADITIONS AT GREY OAKS
Report of Turnover Survey VILLAS OF TRADITIONS AT GREY OAKS Grey Oaks Development Naples, Collier County, Florida Forge Engineering Project Number 2907-001.01 March 2015 Richard P..Lundberg, P.E cn=richard
More informationCLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
More informationBASEMENT FLOODING PART II: Reducing Flooding Risks on Your Property HISTORIC CHICAGO BUNGALOW ASSOCIATION
BASEMENT FLOODING PART II: Reducing Flooding Risks on Your Property HISTORIC CHICAGO BUNGALOW ASSOCIATION HCBA 2 Launched in September, 2000 HCBA is a nonprofit organization whose mission is to help owners
More informationORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT
1. SAFETY, HEALTH, CODE 1.1 Structural Requirements, Seismic Stability 1.1.1 Primary Structure 1.1.2 Ceilings 1.1.2 Water damage in many classrooms. Replace tiles. 1.1.3 Cabinets, Equipment 1.1.4 Portables
More informationBuilding Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
More informationSchool Construction Authority Architecture & Engineering
SCOPING GUIDELINES 1.0 GENERAL GUIDELINES 2.0 BUILDING ENVELOPE SCOPING GUIDELINES 3.0 CATEGORIES AND COMPONENTS: The Flood Elimination/Below Grade Capital Category may include some or all of the following
More informationMURCH ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1929 BUILDING AREA 47,700 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 491 WARD 3 PROPOSED PROGRAM CAPACITY 500 Site Plan MURCH - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationTotal Home Inspection Checklist
Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are
More informationPUBLIC RESTROOMS, DESIGN INTENT
PUBLIC RESTROOMS, DESIGN INTENT 1.01 STRUCTURAL A. Where feasible, metal stud partitions will be constructed on a 6 high concrete curb. 1.02 MECHANICAL A. Restrooms will have a minimum of 15 air changes
More informationBuilding Condition Assessment Report
C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses
More informationBuilding Condition Assessment: 109-111 North Howard Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
More informationEvanston Main Street Station TOD Plan and Study. Appendix A.1: Station Area Existing Conditions
Evanston Main Street Station TOD Plan and Study Appendix A.1: Station Area Existing Conditions EvanstonMainStreetStation TODPlanandStudy A 1 AppendixA.1: ExistingConditions Table of Contents Station Locations
More informationFORENSIC INVESTIGATION QUESTIONNAIRE
FORENSIC INVESTIGATION QUESTIONNAIRE PSE Project Number: - - Project Name: Person(s) Interviewed: Relationship to House: Please answer the following questions to the best of your ability. Exact dates are
More informationBUNKER HILL ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1970 BUILDING AREA 98,200 SF CURRENT PROGRAM CAPACITY 332 ENROLLMENT 2008 387 WARD 5 PROPOSED PROGRAM CAPACITY 750 Site Plan BUNKER HILL - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationTable of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities
Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)
More informationReference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls
Reference: BRM-00220488-A0 July 18 th, 2014 Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Re: 1.0 Introduction Exp Services Inc. (exp) was retained by the Toronto
More informationProtecting Your Home From Water Damage
1 P a g e Protecting Your Home From Water Damage The first signs of water damage might seem trivial. But warnings like water stains on the ceilings or a leak under the kitchen sink can lead to real problems,
More informationORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT
1. SAFETY, HEALTH, CODE 1.1 Structural Requirements, Seismic Stability 1.1.1 Primary Structure 1.1.2 Ceilings 1.1.3 Cabinets, Equipment 1.1.4 Portables 1.2 Fire / Life Safety 1.2.1 Corridor, Separation
More informationArchitectural Inspection Site Structures
0141 Freestanding Shelters Open air shelters not attached to the building. Bike rack shelter with bike racks: This 8'x30' structure is located on the north east side of the building on the wooded landscape
More informationNew Home Walk-Through Package
New Home Walk-Through Package Carrying out a Successful Walk-through Before Closing John MacDonald Architect inc. The Courtyard @ Bonnie Stuart, 141 Whitney Place Suite 101, Kitchener, ON. N2G 2X8 New
More informationProperty Condition Assessment
Property Condition Assessment Business, Wisconsin Inspection Date: 8/2009 Prepared For: Business Owner Report Number: TD999909 Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar
More informationCommon Problems with Walls
Common Problems with Walls Common Problems with Walls There are problems and concerns that are shared by all walls and siding installations. In this article, we will learn about the following commonly
More informationRRIO Checklist. Use of checklist: Definitions: Limitations
CITY OF SEATTLE RENTAL REGISTRATION AND INSPECTION ORDINANCE (RRIO) RRIO Checklist Use of checklist: Property owners will use the RRIO Checklist to confirm that their rental housing properties and units
More informationWASHROOM UPGRADE SIR CHARLES TUPPER BUILDING 2250 RIVERSIDE DRIVE, OTTAWA, ON SIR CHARLES TUPPER BUILDING A0.0 COVER SHEET / DRAWING LIST
0 RIVERSIDE DRIVE, OTTAWA, ON A0.0 COVER SHEET / DRAWING LIST A0. LEGEND AND GENERAL NOTES A0. GENERAL NOTES A0. GENERAL NOTES A0. TYPICAL WASHROOM WALL/SINK SECTION A0. DETAIL - CONTROL JOINT A0. DETAIL
More informationHAMILTON SCHOOL. 1401 Brentwood Parkway, N.E., Washington, DC INITIAL YEAR BUILT 1968 BUILDING AREA
INITIAL YEAR BUILT 1968 BUILDING AREA 187,700 SF CURRENT PROGRAM CAPACITY N/A ENROLLMENT 2008 129 WARD 5 PROPOSED PROGRAM CAPACITY N/A Site Plan HAMILTON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationMemorandum. July 16, 2008. To: Plan Commission City of Madison
Memorandum July 16, 2008 To: Plan Commission City of Madison From: Marc Schellpfeffer Engberg Anderson Re: Structural/Architectural Assessment of Homes for Proposed Demolition Findorff Yards Office Lofts
More informationHow To Plan A Building
State of Nevada Department of Administration Purchasing Division Las Vegas Purchasing Warehouse Facility Condition Analysis LAS VEGAS PURCHASING WAREHOUSE 1054 South Commerce Street Las Vegas, Nevada Site
More informationPROFESSIONAL ENGINEERING INSPECTIONS, INC.
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest
More informationINDIAN HEAD ELEMENTARY SCHOOL
ROOF ASSESSMENT REPORT INDIAN HEAD ELEMENTARY SCHOOL NOVEMBER 08, 2010 PREPARED FOR: FACILITIES DEPARTMENT WHITMAN HANSON REGIONAL SCHOOL DISTRICT 1. Purpose This Roofing Assessment Report provides a summary
More informationEAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
More informationVOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10
VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10 SECTION B1: PREPARATION GUIDE B1.1 INTRODUCTION... B1-1
More informationSun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
More informationCONDITION OF QUALITY ITEMS
CONDITION OF QUALITY ITEMS FOUNDATION Always look for moisture problems and any bulges or irregularities in the walls. Lines on the walls or floors may indicate water problems. Have these been cured? If
More informationHow to report a repair
How to report a repair for repairs to your home? We are committed to making sure your home is in a good state of repair. To meet our legal responsibilities we will: Keep the exterior (eg roof, walls, doors,
More informationBasement & Foundation Damage
Basement & Foundation Damage Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case
More informationReport Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10
Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 PROPERTY DESCRIPTION PROPERTY INSPECTED: INSPECTION ADDRESS: 4722 Baltimore Avenue
More informationESTIMATE ORIG. ESTIMATE: TOTAL: $204,249 DATE: 01/15/08 DESCRIPTION OF WORK QUANTITY DIVISION TOTAL
PARTITIONS REGULAR WALLS 9' HIGH 214 LF TENANT DEMISING WALL 150 LF INTERIOR FURRED WALLS 9' 86 LF OFFICE DEMISING WALL 98 LF DOUBLE FRAME RADIUS WALL 18 LF RADIUS SOFFITS 172 LF SOFFIT 76 LF FINISH NEW
More informationGeorgia Home Inspection Services
Cover Page Property Inspection Report My street, Anytown GA, 30000 Inspection prepared for: John Doe Inspection Date: 7/18/2011 Time: 5pm Age: 25+ Size: >1500 Weather: Clear This ranch style home is in
More informationSimplify. Homeownership
Simplify Homeownership Home Pulse An Innovative Program To Maintain Your Home. The Home Pulse Preventive Maintenance Plan will keep your home looking great, dramatically slow the deterioration process
More informationIntegrating Healthy Housing Considerations into Weatherization Inspections. Jim LaRue
Cleveland Cuyahoga County Healthy House Project Training Integrating Healthy Housing Considerations into Weatherization Inspections Jim LaRue Joint inspections for housing health hazards Weatherization
More informationOPTIMUS WORK CLASSIFICATION LIST ENTER ALL THAT APPLY
Cost Code # Description Cost Code # Description 01 00 00.001 General Requirements 02 00 00.001 Existing Conditions 01 31 19.13.001 Preconstruction Meetings 02 21 00.001 Surveys 01 32 33.001 Photographic
More informationPEPPER VINER HOMES WARRANTY GUIDELINES
PEPPER VINER HOMES WARRANTY GUIDELINES All non-emergency warranty and customer service requests MUST be made in writing. This provides you with documentation and allows Pepper Viner to operate efficiently.
More informationAPPLICANT: ORANGE COUNTY, NEW YORK
Figure 1 Div 1 3 rd Flr Leakage in County Executives Office Figure 2 Div 1 3 rd Flr Location 067 approximately 2 SF of visible mold growth above entrance to Room 341 Figure 3 Div 1 3 rd Flr Location 067
More informationG. Common Defects in Buildings - Leakage
F. Common Defects in Buildings - Structural 32. Recently, some concrete chips have fallen from the ceiling in my kitchen. There are rusty steel bars and the area in question measures about 300 x 400mm.
More informationCOST OF WORK FORM. Abbreviations: ea = each, LF = linear feet, SF = square feet, HSF = square feet of living area (including garage conversion space)
COST OF WORK FORM All costs shown are estimates using base grade materials, taxes, and labor. For houses where a higher quality is indicated, the costs should be increased for work requiring upgraded materials.
More informationDate: March 7, 2006 Report for [removed]
Date: March 7, 2006 Report for [removed] The Preservation Resource Center Of New Orleans, in conjunction the National Trust for Historic Preservation, has conducted a condition survey of your property.
More informationNARRATIVE REPORT. The Asbestos Bulk Sample Results Table includes asbestos sampling data.
NARRATIVE REPORT 1.0 BUILDING INFORMATION The original date of construction for Construction Management Engineering was not immediately available; the building has had no major renovations. Construction
More informationMUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION
REPORT NO. PR-019-15 MUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION TO: Mayor and Members of Council FROM: Liz Murray Recreation and Facilities Manager DATE: July 13, 2015
More informationBuilding Foundation and Structure
Building Foundation and Structure Overview The construction of the Hall of Waters building began in 1936, and was constructed over the original site of the Siloam and Sulpho-Saline Springs. The original
More informationHistoric Preservation Certification Application Part 2 343-345 Main Street West South Haven, Vermont NPS Project No. 12345
Exterior Features 1 site and drainage 2 foundation 3 wood siding and trim 4 exterior doors 5 windows / storm windows 6 porches front and rear 7 chimneys 8 roofing Interior Features 9 frame 10 basement
More informationFacilities Operations Customer Service Standards WORK ORDER PRIORITIES
Facilities Operations Customer Service Standards WORK ORDER PRIORITIES In order to provide fair and consistent maintenance service to all University faculty, staff and students, a work priority system
More informationWORK SUMMARY April 17, 2015
1 A Roof Damaged condenser fins at CU-1, CU-1A, and CU-2A. Rake all condenser fins at CU-1, CU-1A, and CU-2A. 66 3 units 2 A Roof Unacceptable/damaged paint finish at sheet metal parapet Sand/re-paint
More informationTundra Series Windows January 2016
Tundra Series Windows January 2016 New Construction Installation Instructions Nail Fin, J-Fin and Brickmold Aplications product. ATTENTION! Read and understand all installation instructions before installing
More informationSTRUCTURAL ASSESSMENT
STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha
More informationU.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live!
U.S. Department of Housing and Urban Development Office of Public and Indian Housing A Good Place to Live! Introduction Having a good place to live is important. Through your Public Housing Agency (or
More informationSUMMARY REPORT THE BOTTOM LINE. Electrical. Report Number: 1860. Inspection Date: Saturday, February XX, XXXX
SUMMARY REPORT Report Number: 1860 Inspection Date: Saturday, February XX, XXXX Property Address: XX XXXXX XXX Toronto, ON XXX XZX Client Name: Xxxx Xxxxxxxxxxxxx Prepared by: Andrew Marioselva BSc,CHI
More informationEstimator: Miami Estimates Business: (305) 395-4362. Date Entered: 04/30/2008
Insured: Property: Claim Rep.: Business: Estimator: Miami Estimates Business: (305) 395-4362 Claim Number Policy Number Type of Loss Deductible Dates: Date of Loss: 10/24/2005 Dwelling $0.00 Other structures
More informationDRAPER ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1953 BUILDING AREA 54,000 SF CURRENT PROGRAM CAPACITY 250 ENROLLMENT 2008 84 WARD 8 PROPOSED PROGRAM CAPACITY 325 Site Plan DRAPER - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationReport for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
More informationIMPROVEMENT COST ESTIMATE powered by HomeFixers
IMPROVEMENT COST ESTIMATE powered by HomeFixers 123 Main St, Anytown, USA 12345 2000 SF $ 45,041.06 100.0% $22.52 per sq. ft. Stage 1: Pre-Construction $ 1,461.00 3.2% 1 House Secured $ 106.00 0.2% Lockbox
More informationDIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
More informationMequon - Thiensville School District Long Range Facilities Plan Monthly Project Schedule
Mequon - Thiensville School District Long Range Facilities Plan Monthly Project Schedule Homestead HS Sept.'15 Oct'15 Nov'15 Dec'15 Jan'16 Feb'16 Repair Asphalt @ Main Garage Replace Exterior Hollow Metal
More informationThis handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
More informationVJ ASSOCIATES 1825 K STREET NW, #1100 WASHINGTON, DC - 20006 TEL: (202) 609-7480 INITIAL PROJECT COST ANALYSIS
VJ ASSOCIATES 1825 K STREET NW, #1100 WASHINGTON, DC - 20006 TEL: (202) 609-7480 INITIAL PROJECT COST ANALYSIS January 7, 2014 0 BASIS OF ESTIMATE The estimate is based on the drawings and documents received
More informationOrlando Home Inspection Services
PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com
More information1. Maintenance. Mechanical, Electrical & Plumbing Improve ligh>ng control an sensoring $230,239
1. Maintenance Building Component Detail Est. Cost. Alkali Building Envelope Replace windows $40,425 Replace worn and rippling carpet $81,335 Improve ligh>ng control an sensoring $230,239 Repair and replace
More informationAdditions and Alterations
Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal
More informationAll substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.
2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other
More informationPoint Auditorium Design Narrative PROJECT NAME: Point Auditorium DATE: 06/25/15 TO: Lance Francis FROM: Leslie Ellsworth
INTRODUCTION: Kronberg Wall Architects is pleased to present the Design Narrative for the Point University Auditorium conversion from the existing warehouse space. General Project Description: This project
More informationBUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
More informationA comfortable house is a great source of happiness. - Sydney Smith. Home Maintenance Guide
A comfortable house is a great source of happiness. - Sydney Smith Home Maintenance Guide HOME GUIDE By conducting regular maintenance checks, you can prevent small inexpensive repairs from becoming more
More informationA0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET
POYNTZ AVENUE, STE 9 MANHATTAN, KS 0..0..9 FAX WEST th STREET JUNCTION CITY, KS.... FAX 0, Bruce McMillan AIA, Architects, P.A. HERITAGE TRUST FUND GRANT PROJECT NO. 0-0 ROOF REPAIR OF THE 00 LOCUST STREET
More informationSECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
More informationNovember 3, 2015 Bond and District Additional Assistance Election Information
November 3, 2015 Bond and District Additional Assistance Election Information Proposition 432 - $22 million General Obligation Bond 150+ facility projects across all schools Building renovations and improvements
More informationUNIVERSITY OF CALIFORNIA, SAN DIEGO
UNIVERSITY OF CALIFORNIA, SAN DIEGO UCSD BERKELEY DAVIS IRVINE LOS ANGELES MERCED RIVERSIDE SAN DIEGO SAN FRANCISCO SANTA BARBARA SANTA CRUZ UNIVERSITY CENTERS - 0076 PHONE: (858) 822-4987 9500 GILMAN
More informationLITITZ MUTUAL INSURANCE COMPANY 2 North Broad Street Lititz, Pennsylvania - MAIN OFFICE -
The original section of this building was constructed in 1941. The exterior walls are built of good quality stone. In the early 1980 s a similar addition was added to the north elevation. The exterior
More informationOctober 6, 2009. (B) the vantage point from which the crawl space was inspected; and
535.228. Standards of Practice: Minimum Inspection Requirements for Structural Systems (a) Foundations. The inspector shall: (1) inspect slab surfaces, foundation framing components, subflooring, and related
More informationHow To Prevent Water Damage To A Home
Having inspected about 800 homes in the last four years, I have seen a lot of problems with many homes. Most of these problems are minor; however, there are some problems that are quite serious. One of
More informationHEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
More informationRental Property Safety Inspection Checklist
PLANNING AND COMMUNITY DEVELOPMENT DEPARTMENT Rental Registration and Safety Inspection Program 210 Lottie Street, Bellingham, WA 98225 Telephone: (360) 778-8361 Fax: (360) 778-8302 TTY: (360) 778-8382
More informationMold Inspection Report (Initial Assessment)
Morlin Home Services, LLC 4435 Nanticoke Court Sw Lilburn, GA. 30047 Phone: (770) 564-1505 Fax: (770) 564-1575 Cell: (770) 344-7416 InspectorRick@Bellsouth.net www.morlinpropertyinspections.com Mold Inspection
More information7.0 REHABILITATION /RESTORATION / MAINTENANCE PLAN
7.0 REHABILITATION /RESTORATION / MAINTENANCE PLAN This section will detail and outline the rehabilitation, restoration, and maintenance plan for the 418 South June Street residence. Future work shall
More information