1 SUBSTATION SURVEILLANCE USING RADIO FREQUENCY INTERFERENCE (RFI) MEASUREMENTS Eduardo Pabuna WESTCO ELECTRICAL
2 Agenda Introduction. Partial Discharge a precursor to failure. Radio Frequency Interference (RFI) detection - understanding what we are measuring. Complimentary EMI detection techniques using different sensors Case studies Conclusions
3 Key Drivers A successful substation asset management strategy depends heavily on predictive maintenance assessments conducted periodically: Surveillance based techniques to identify potential sites of insulation degradation Followed by more investigative and invasive quantitative techniques Adds value to the maintenance work, selectively identifying and replacing those items of plant that have deteriorated significantly. Identifies HV apparatus that presents a potentially safety hazard to staff and public. Cost effective and non expert use.
4 External discharges Surface discharges caused by pollution on the insulator surfaces. Leakage currents on insulator surfaces. Insulator damage. Corona. Loose connections Internal discharges Voids in the insulation. Poor conductor-insulation interfaces. Metal irregularities/contaminants
5 PDS100 PD Surveyor PD Detection by RFI/EMI
6 Partial Discharge (1) PD occurs when insulation defects exist which produce distorted and enhanced electric field stress. Causes of PD in insulation system: Voids in epoxy resins, polymers, paper Bubbles in liquids/oils Metal depositions/irregularities/contaminants Electrodes and insulation surfaces Poor terminations/loose joints Environmental stresses can act to accelerate the deterioration of the insulation system in HV apparatus.
7 Partial Discharge (2) Can also arise through: Poor design and manufacture Damage of equipment Poor installation processes/workmanship General ageing or deterioration of materials Lightening strikes, transients, overloading
8 Partial Discharge (3) PD is a symptom of degradation Once present it dominates as it s own inherent stress degradation mechanism Precursor to complete insulation failure and breakdown poor preparation erosion traces poor preparation poor preparation Cable Termination Area
9 Detection of partial discharges Detection is based on the energy exchanges that take place during the discharge Dielectric Heat Light losses Electromagnetic Radiation Chemical changes, gases Impulse current pulses Sound/ noise
10 RFI Emissions IEC60270 measurements Quantify apparent charge involved in PD event Integration of current pulse Requires physical connection to measure current pulse RFI measurements Radiated signals depends on the dynamics of charge motion Signals generated when charge is accelerated, e.g. Charge oscillation Charge movement PD current pulse comprises moving charges thus radiation will ensue
11 RFI Case in UK, 1984: Experience of a transformer fire that followed a bushing failure: During 6 months before this failure neighbors were complaining about Radio & TV interference, foretelling what was coming. Since then, RFI surveys are routine.
12 Understanding What We Are Measuring Partial discharge pulse RFI emission frequency spectrum PD current pulse comprises moving charges thus radiation will ensue It emits an impulsive electromagnetic wave that travels in the surrounding media.
13 Understanding What We Are Measuring Detecting and measuring a partial discharge event is analogous to listening for the strike of the hammer on the bell at distance what we hear are the resonant harmonics.
14 RFI propagation discharge source Amplitude of higher frequency emissions drop of quicker with distance Source of discharge may be located to an area or specific item of equipment Discharge pulse propagation Radio frequency, or RF signals, weaken as they travel through free space because of divergence or dispersal, much the same way light travels away from a light bulb.
15 How? RFI from PD source radiates intermittently PDS100 scans VHF/UHF in steps of 6 MHz for ms (set by user) Captures RF energy by amplitude
16 Scanning for RFI emissions
17 How? 1. Establish baseline outside substation or switch room 2. Walk from point to point inside substation in service 3. Look for changes in amplitude of the RF-activity 4. If indications of PD approach the apparatus and see if the activity increases
18 Typical RFI spectrum without discharge source (frequency sweep mode)
19 Compare Background signal with signal next to source
20
21 Frequency Range Contributions 1) Corona in air around sharp metal will be dominant up to 10 MHz but will go as high as ~250 MHz 1) Surface discharge on dirty porcelains will dominate from 10 to 250 MHz. Heavily influenced by time of year, rain washing etc. 3) PD will extend RFI up to 1GHz on the PDS100 (but actually can go much higher). The higher the frequency the greater the attenuation Localization of PD requires the using the attenuation to your advantage! The closer you get to the source of PD the more sensitive (elevated) the higher frequencies
22 Fault Characterization Measured impulse events from an arcing discharge source (time resolved mode)
23 Case Study 1 Survey of Switchyard revealed high RFI in vicinity of Isolator The time resolved plot shows a typical arcing type discharge Deviations from Background (Black) becoming larger when approaching the isolator
24 Case Study 1 Survey of Switchyard revealed high RFI in vicinity of Isolator It was recommended to pay particular attention to the isolator and to look for floating metal parts. Several Cu braids and springs were found to be burned off and just lying in the centre pole enclosure of the isolator. In addition the insulators on the load end (CSBP) were replaced due to glazing damage of the surface due to a previous flashover. A repeat test after repair of the isolator showed no significant deviation from background for all HV plant in this switchyard.
25 Case Study 2 11KV switchboard During a routine Survey some RFI activity was found in front of only one 11kV switchgear panel.
26 Case Study 4 400/275/22kV 800MVA Transformer RFI scans performed on places indicated by red dots L2 L11 L12 L13 Radiator 400 kv 275 kv L3 L4 L5 L1 Tapchanger L7 L6 L10 L9 L8
27 Case Study 4 400/275/22kV 800MVA Transformer The PD scans at location L3 and the baseline is shown. The PD measurements showed increases in amplitudes when compared with the baseline measurement indicating evidence of discharge activity.
28 Case Study 4 400/275/22kV 800MVA Transformer
29 Case Study 4 400/275/22kV 800MVA Transformer RFI scan at L8 (TDM at arrow 790MHz) Time domain mode at 780MHz Pos. L8
30 Case Study 4 400/275/22kV 800MVA Transformer Clear signs of severe PD The transformer failed 2 weeks after this survey
31 Case Study 4 132kV CT Strong RFI emissions were detected in the range of 750 to 900 MHz indicating significant PD activity in the oil dielectric. Further interrogation of RF signals were done in time domain mode at different PD frequencies.
32 Case Study 4 132kV CT Time Resolved Mode showing correlation with system voltage DGA results confirm internal PD C & TD Test data of CT s insulation measured Tan Delta at 3.0%.
33 Case kv - Surge Arrester RFI measurement was carried out during routine substation survey. Very high amplitudes at the highest frequencies indicated serious PD. Other arresters in the same switchyard followed the baseline.
34 Other decoupling options TEV Joint Metal Cladding HV Busbar EM Wave PD EM Wave EM Wave TEV Probe Far-Field Propagation PDS 100 Photo showing the deployment of a TEV probe Graphic Showing Transient Earth Voltage Detection of Partial Discharge Activity.
35 Other Sensors: High Frequency CT s
36 UHF Transformer Sensors UHF Plate Sensors (Mounted in Hatch) UHF Drain Valve Sensors
37 Use of Complementary EMI Couplers Frequency plot of injected pulse Using a UHF coupler on a GIS Substation. Time resolved 810 MHz
38 Example of a Detected GIS Defect Frequency trace for a floating particle UHF 2.5 GSs -1 Time resolved 871 MHz; -repetition rate 1 s -1
39 Summary Impulsive broadband emissions are a characteristic of insulation defects in HV substations. The PDS100 instrument platform is specifically designed for substation surveillance and can greatly assist in early stage recognition and reporting of PD. RFI offers a routine non-invasive and costeffective surveillance technique.
40 Thank You! QUESTION?
Condition Monitoring of equipment to improve quality of supply to customers by averting failures
Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract
More informationLastest Development in Partial Discharge Testing Koh Yong Kwee James, Leong Weng Hoe Hoestar Group
Lastest Development in Partial Discharge Testing Koh Yong Kwee James, Leong Weng Hoe Hoestar Group INTRODUCTION Failure of High Voltage insulation is the No 1 cause of High voltage system failures with
More informationHigh Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd
High Voltage Electrical Equipment Failure Diagnosis Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd High Voltage Electrical Equipment Failure Diagnosis Definition of High Voltage
More informationElectrical Predictive and Preventative Maintenance
Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types
More informationELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
More informationPD Monitor GIS. 24/7 Partial Discharge (PD) monitoring system for Gas Insulated Switchgear. Benefits NEW PRODUCT
NEW PRODUCT PD Monitor GIS 24/7 Partial Discharge (PD) monitoring system for Gas Insulated Switchgear For automatic, continuous monitoring of mission critical GIS assets Benefits The most cost effective
More informationEffective Condition Assessment of Medium Voltage Switchgear
Effective Condition Assessment of Medium Voltage Switchgear Abstract There is a general trend within electricity distribution companies and operators of large private electricity networks to extend maintenance
More informationMiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
More informationNON INTRUSIVE TECHNIQUES FOR DETECTING PARTIAL DISCHARGE IN HV AND EHV SWITCHGEAR
NON INTRUSIVE TECHNIQUES FOR DETECTING PARTIAL DISCHARGE IN HV AND EHV SWITCHGEAR Volume 1of 1 Graham Dennis A thesis submitted for the Degree of Master of Philosophy University of Bath Department of Electronic
More informationEVALUATING WAVE FILES TO DETERMINE THE SEVERITY OF THE ULTRASONIC EMISSIONS
EVALUATING WAVE FILES TO DETERMINE THE SEVERITY OF THE ULTRASONIC EMISSIONS We are often asked at which voltages and on what type of equipment is ultrasound most effective. The answer is not simple since
More informationEnhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
More informationRated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W
14713221 001 Seite 2 von 37 Page 2 of 37 Model List: No Model Rated Voltage(V) 1. EG-LED0827-01 Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 4. EG-LED1040-01 AC 100-240V, 10W 5. EG-LED1027-02
More information21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
More informationHarmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
More informationSIEMENS Transmission and Distribution
TITLE Long Term Maintenance and Care for S36A E. C. Wright 02/09/04 This document is to be used in conjunction with Installation, Operation and Maintenance Schedule IOMS 635. Its aim is to provide guidance
More informationCable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
More informationXVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011
XVII International Symposium on High Voltage Engineering, Hannover, Germany, August -6, 11 UHF AND ACOUSTIC PARTIAL DISCHARGE LOCALISATION IN POWER TRANSFORMERS S. Coenen 1*, A. Müller 1, M.Beltle 1 and
More informationCharged cable event. 1 Goal of the ongoing investigation. 2 Energy sources for the CDE. Content
Charged cable event David Pommerenke, david_pommerenke@hp.com, 916 785 4550 Last update: Feb.23, 2001 Content Goal Energy sources, which may lead to CDE. Complexity of the different discharge modes. Possible
More informationMOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD
MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationGrounding Demystified
Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%
More informationHow To Test For Safety On A Power Cable
T H E M A G A Z I N E O F 7 x 2 4 E X C H A N G E I N T E R N AT I O N A L A Green Approach to Building a Superior Data Center S P R I N G 0 9 BUILD FOR TODAY. EXPAND ON DEMAND. Modularity in the data
More informationUltrasound Condition Monitoring
Ultrasound Condition Monitoring Whitepaper Alan Bandes UE Systems, Inc. Abstract: Instruments based on airborne/structure borne ultrasound technology offer many opportunities for reducing energy waste
More informationEMC Standards: Standards of good EMC engineering
Electromagnetic Compatibility (EMC) IEEE Definition Origin, control, and measurement of electromagnetic effects on electronic and biologic systems. IEEE EMC Society Areas of Interest EMC Standards: Standards
More informationVideo Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
More informationemployed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
More informationHigh-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv
High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage
More informationWorld Leader in HV Testing Technology
World Leader in HV Testing Technology Cable Fault Locators w/tdr Oil/Fluid Dielectric Testers Very Low Frequency AC Technology W/TD & PD Diagnostics Portable AC Hipots ---------------------------------
More informationwith Component Rating A Simple Perspective
Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America
More informationDDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
More informationStudy of RF Spectrum Emissions in High Pressure Sodium and Metal Halide Lamps. Lawrence P. Glaister VE7IT, Automation Engineer.
Study of RF Spectrum Emissions in High Pressure Sodium and Metal Halide Lamps Lawrence P. Glaister VE7IT, Automation Engineer May 2010 Abstract: This research was performed in collaboration with the City
More informationOnline Transformer Insulation Monitoring System BushingGard Product Focus. Maximizing Transformer Uptime and Reliability
Online Transformer Insulation Monitoring System BushingGard Product Focus Maximizing Transformer Uptime and Reliability Critical Energy Transfer... Large power transformers are found around the world at
More information13 common causes of motor failure
13 common causes of motor failure Application Note What to look for and how to improve asset uptime Motors are used everywhere in industrial environments and they are becoming increasingly complex and
More informationelectrical services WWW.AU.SGS.COM/INDUSTRIAL
electrical services WWW.AU.SGS.COM/INDUSTRIAL OUR PROFILE SGS offers a full range of electrical engineering services covering the commissioning test of new plant as well as the maintenance and continual
More informationDigital C4I Interoperability: The EM Protection Issue
Digital C4I Interoperability: The EM Protection Issue Robert Pfeffer U.S. Army Nuclear and Chemical Agency ATTN: ATNA-NU (R. Pfeffer) 7150 Heller Loop Suite 101 Springfield, VA 22150-3198 Abstract In this
More informationDDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
More informationMSAN-001 X-Band Microwave Motion Sensor Module Application Note
1. Introduction HB Series of microwave motion sensor module are X-Band Mono-static DRO Doppler transceiver front-end module. These modules are designed for movement detection, like intruder alarms, occupancy
More informationCONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services
CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services SpecialistS IN ELECTRICAL SUPPORT SERVICES TO MINING, UTILITIES & industry Ampcontrol is committed to supporting our customers to maintain efficient
More informationCellular Wireless Antennas
Cellular Wireless Antennas A Technical Brief GarrettCom Inc., November 2010 Overview The Cellular Wireless Antenna Technical brief is provided to assist with the design and deployment of the DX940 Cellular
More informationLUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO
LED PORTFOLIO LUXEON LEDs Circuit Design and Layout Practices to Minimize Electrical Stress Introduction LED circuits operating in the real world can be subjected to various abnormal electrical overstress
More informationDrayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
More informationWhite Paper. Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards.
Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards White Paper Introduction Optocouplers and alternative isolation technologies
More informationUFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
More informationExperiment 5. Lasers and laser mode structure
Northeastern University, PHYS5318 Spring 2014, 1 1. Introduction Experiment 5. Lasers and laser mode structure The laser is a very important optical tool that has found widespread use in science and industry,
More informationWhy Buy HVI VLF Products?
Very Low Frequency AC Hipots AC testing of cables and electrical apparatus is now easier than ever. Since the introduction of the High Voltage, Inc. line of portable and affordable VLF hipots, there is
More informationSubstation Grounding Study Specification
Substation Grounding Study Specification Introduction A grounding study is required for name of station, a / / kv substation located in name of location and connected to the following circuits: number
More informationMylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness
Product Information Mylar polyester film Electrical Properties Mylar offers unique design capabilities to the electrical industry due to the excellent balance of its electrical properties with its chemical,
More informationComplete Solar Photovoltaics Steven Magee. Health and Safety
Health and Safety Health and safety around solar photovoltaic systems is very important. In the DC circuit you will find up to 600 volts in residential and commercial systems. In utility systems you may
More informationCable Condition Monitoring to Improve Reliability
Cable Condition Monitoring to Improve Reliability by Hilary Marazzato, Ken Barber, Mark Jansen, and Graeme Barnewall Olex Australia Page 1-1 - Cable Condition Monitoring of Improve Reliability Hilary Marazzato,
More informationIntroduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
More informationDEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD OF INSERTION LOSS MEASUREMENT
INCH-POUND MIL-STD-220C 14 May 2009 SUPERSEDING MIL-STD-220B 24 January 2000 DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD OF INSERTION LOSS MEASUREMENT AMSC N/A FSC EMCS FOREWORD 1. This standard
More informationSpecifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
More informationTroubleshooting accelerometer installations
Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.
More informationMEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
More informationTRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
More informationCase Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives
Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives G.C. Stone, I. Culbert, H.G. Sedding Qualitrol-Iris Power Mississauga, Ontario, Canada Abstract On-line partial discharge
More informationProduct Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer
Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment Scott Aldous, Compliance Engineer What is Insulation Coordination? From IEC 60664-1, Edition 1.2: So what does that mean
More informationPhysical Science Study Guide Unit 7 Wave properties and behaviors, electromagnetic spectrum, Doppler Effect
Objectives: PS-7.1 Physical Science Study Guide Unit 7 Wave properties and behaviors, electromagnetic spectrum, Doppler Effect Illustrate ways that the energy of waves is transferred by interaction with
More informationUSB 3.0* Radio Frequency Interference Impact on 2.4 GHz Wireless Devices
USB 3.0* Radio Frequency Interference Impact on 2.4 GHz Wireless Devices White Paper April 2012 Document: 327216-001 INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE,
More informationSF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
More informationPower Quality for Information Technology System
Power Quality for Information Technology System ITS OBVIOUS THE TOLERANCE IS DIFFRENT But What isn t Tobvious? HOW MANY OF YOU HAVE : A COMPUTER AT HOME? = Computers are not screens and Keyboards COMPUTERS
More informationTransformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
More informationOMICRON Monitoring Solutions
OMICRON Monitoring Solutions Partial discharge monitoring of high voltage assets M/G Extending the service life of high-voltage assets Why monitoring? Insulation degradation in critical high-voltage (HV)
More informationTHE VALUE OF POWER FACTOR TESTING
THE VALUE OF POWER FACTOR TESTING Nov 1, 2005 12:00 PM by John Bleyer and Phillip Prout, National Grid NATIONAL GRID DISCOVERED A HIGH POWER FACTOR DURING ACCEPTANCE TESTING of a new 40-MVA transformer
More informationElectromagnetic Compatibility Considerations for Switching Power Supplies
Electromagnetic Compatibility Considerations Characterization of the EMI problem requires understanding the interference source Switching power supplies generate Electromagnetic Interference (EMI) by virtue
More informationOur brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
More informationHigh Frequency Power Quality
High Frequency Power Quality Dr. Ing. Jos Knockaert, MSc jos.knockaert@ugent.be CE-ABLE Seminar 21st June 2016-1 Project: TETRA HFPQ funded by Dec 2014 Nov 2016 Main goals: - How to measure? - What are
More informationApplication Note: Spread Spectrum Oscillators Reduce EMI for High Speed Digital Systems
Application Note: Spread Spectrum Oscillators Reduce EMI for High Speed Digital Systems Introduction to Electro-magnetic Interference Design engineers seek to minimize harmful interference between components,
More information(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS
(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS IS 12729:2004 IEC 60694(2002) 1.1 Scope This International Standard applies to a.c. switchgear and controlgear,
More informationFundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
More informationHigh Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance
Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety
More informationTransmission Silicone Insulators Line Post 69 kv to 161 kv
K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 161 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines
More informationPower transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
More informationWHAT IS INFRARED (IR) THERMOGRAPHY
WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical
More informationStandard: EN 61000-4-2 :1995, EN 61000-4-3 :1996, ENV 50204 :1993, & EN 61000-4-4 :1995 Solid State Energy Meter
Standard: EN 61000-4-2 :1995, EN 61000-4-3 :1996, ENV 50204 :1993, & EN 61000-4-4 :1995 Model: Solid State Energy Meter Prepared for: Analog Devices, Inc. 804 Woburn Street Wilmington, MA 01887 Date of
More informationThe Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
More informationWIRE AND CABLE ENGINEERING GUIDE
Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime
More informationA Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
More informationAnalysis of Immunity by RF Wireless Communication Signals
64 PIERS Proceedings, Guangzhou, China, August 25 28, 2014 Analysis of Immunity by RF Wireless Communication Signals Hongsik Keum 1, Jungyu Yang 2, and Heung-Gyoon Ryu 3 1 EletroMagneticwave Technology
More informationA comparison of radio direction-finding technologies. Paul Denisowski, Applications Engineer Rohde & Schwarz
A comparison of radio direction-finding technologies Paul Denisowski, Applications Engineer Rohde & Schwarz Topics General introduction to radiolocation Manual DF techniques Doppler DF Time difference
More informationGrounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
More informationResidual life aspects on GIS with the focus on SF 6
Residual life aspects on GIS with the focus on SF 6 Speaker: Karsten Pohlink 25. March 2015 The presentation refers to CIGRÉ WORKING GROUP B3.17 RESIDUAL LIFE CONCEPTS APPLIED TO HV GIS CIGRE Technical
More informationfor Communication Systems Protection EMI CD-ROM INCLUDED
Krešimir Malarić EMI Protection for Communication Systems CD-ROM INCLUDED Contents Preface xiii CHAPTER 1 Communications Systems 1 1.1 Components of Communications Systems 1 1.2 Transmitter Systems 2 1.2.1
More informationTEST REPORT EN 55014-2 (1997) +A1 (2001)
Page 1 of 23 TEST REPORT EN 55014-2 (1997) +A1 (2001) Electromagnetic compatibility - Requirements for household appliances, electric tools and similar apparatus Part 2: Immunity Report Reference No....
More informationPower surges can also be generated by equipment in your facility such as:
Power Quality Surge Suppressors What is Surge Protection A surge suppressor can be the first and best defense against the instant or gradual destruction of electrical equipment. Compared to the replacement
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
More informationRegulation IO-6.0: Electrical Safety Regulations
Regulation IO-6.0: Electrical Safety Regulations 6.1 Workmanship & Material 6.2 Electrical Conductors 6.3 Overcurrent Protective Devices 6.4 Precautions against Earth Leakage and Earthfault Currents 6.5
More informationST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
More informationTransformer Fleet Management with e-terraassetcare
Transformer Fleet Management with e-terraassetcare Jean-Michel AGNIER jean-michel.agnier@alstom.com Alstom-Grid - http://www.alstom.com/ Asset Management Development Director Alstom Group Thermal Power
More informationAvaya WLAN 9100 External Antennas for use with the WAO-9122 Access Point
Avaya WLAN 9100 External Antennas for use with the WAO-9122 Access Point Overview To optimize the overall performance of a WLAN in an outdoor deployment it is important to understand how to maximize coverage
More informationVoltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
More informationCalculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi
Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi One of the most common errors uncovered by product safety engineers stems from manufacturers and designers failing to fully
More informationClamp Filters that Suppress Emission Noise Provide Immunity Against Surge Noise
TDK EMC Technology Product Section Clamp Filters that Suppress Emission Noise Provide Immunity Against Surge Noise TDK Shonai Corporation Satoru Saito Reduce Emission Noise from Cables Even if an electronic
More informationGrounding and Shield Termination. Application Note 51204
Grounding and Shield Termination Application Note 51204 DEFINITIONS This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this
More informationAdvantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
More informationTIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationCHAPTER 6 INSTRUMENTATION AND MEASUREMENTS 6.1 MEASUREMENTS
CHAPTER 6 INSTRUMENTATION AND MEASUREMENTS 6.1 MEASUREMENTS Atmospheric electricity is a field that is very easy to get into because it does not require a large capital investment for measuring equipment.
More informationGLOBAL COLLEGE OF ENGINEERING &TECHNOLOGY: YSR DIST. Unit VII Fiber Optics Engineering Physics
Introduction Fiber optics deals with the light propagation through thin glass fibers. Fiber optics plays an important role in the field of communication to transmit voice, television and digital data signals
More information