Lab 2 Process Control Computer-based Control Systems Flow Control

Size: px
Start display at page:

Download "Lab 2 Process Control Computer-based Control Systems Flow Control"

Transcription

1 Lab 2 Process Control Computer-based Control Systems Flow Control 1. Aims To operate PC-based instrumentation and control systems To get familiar with open-loop control, ON-OFF, and PID control systems To explain P, PI, PD, and PID control actions To transfer MAN mode to AUTO smoothly. 2. Apparatus Process/Plant: Flow Control Bench consists I/P Converter, Pneumatic Control Valve, Orifice and D/P Cell Transmitters, Pipes and Pump, and Rotameter Computer, LabVIEW 8.6, NI DAQ 6036E Card, Current-to-Voltage converter (4mA-20mA to 1 to 5V) and Voltage-to-Current converter (-10V/+10V to 4mA-20mA). Multimeter, mameter 3 Connection Diagram The connection diagram for control systems is shown in Fig. 1. Pneumatic supply Water supply I/P kpa Valve MI Process (Plant) PV Sensor/s Actuator CS 4-20mA V/I V V I/V MV 4-20mA PC, DAQ PCI 6036E and LabVIEW PC-based controller Figure 1 Connection diagram Schematic diagram for flow control system is shown in Fig. 2 (a & b). 4. Further Information Refer to Chapters 7, 8, 9 (Pressure, Flow and Level), Chapter 12 Actuators and Chapter 13 Basic Control Theory (Direct Acting On-Off Control, PID Control) 1

2 Globe valve ma 4-20mA COMPUTER LABView DAQ 6036E I/V & V/I ma Pneumatic supply kpa Rotameter Q (lpm) Output current I/P Converter Actuator Control valve DC 24V D/P Cell Valve (Open) Gauge 1 Gauge 2 Orifice plate Valve (Closed) Valve (Closed) Pump Water tank Figure 2a Schematic diagram of Flow Control System (Flow Control Bench) Flow Bench D/P Cell kpa Pneumatic supply DC 24V Current 4-20mA (0-30kPa) Orifice plate I/P converter 250R Current 4-20mA kpa (designed) Flow AI channel V Control signal 10V to +10V Control signal 4-20mA COMPUTER DAQ 6036E and LabVIEW V-to-I Figure 2b Connection diagram of the Flow Control System 2

3 Methods 1. Connection and turning on the power Connect the computer, I/V converters, and V/I converter to the process (sensor/s and actuators) by referring to the above scheme/connection diagrams Supply control air (or confirm if the pneumatic supply is done) Turn on the power Log on to the computer 2. Identification of Components and Variables Identify all components and their variable of the process control system (that you have selected) and complete Table 1. Table 1 Components and variables Process system: Component / Model Code No (where applicable) Example: Controller (PC) Input (variable, unit) Process variable: flow [mm, ma, V] Set point [mm, ma, V] Output (variable, unit) Control signal [V, ma] 3. Hands-on Exercises 3.1 Hands-On Exercise 1: Getting Started with Open-Loop Flow Control System Purpose: The purpose of this hands-on exercise is to get familiar with a control system and its components, variables and signals. In the Open Loop Control System there is no comparison of feedback signal to the Set Point. In almost controllers MAN mode is an Open Loop mode. Learning Objectives: Operate the open loop control system Understand components of the control system and their signals 3

4 Explain the principles and functions of the components including process, measurement devices (flow transmitters, pressure gauges), actuators, valves and valve positioners. Procedure Run the LabVIEW On-Off controller program Flow: C:\Documents and Settings\All Users\LabVIEW Data\JEE326_2009\Lab 2\OnOffFlowControlSys\ OnOffFlowControlSys.exe The On-Off controller program looks like... (from D/P cell) SP, PV and CS in ma Manual Controller P and PV in litre/min Diagram Figure 3 On-Off controller program (for flow control) The program is running. If not, click to run the On-Off Controller Program. Make sure that the Auto/Man mode switch is in Man position) Make sure that the Write to File is at Write position and change the path for data files if necessary Enter a minimum value of voltage (Manual Controller), i.e. -10V, write down in Table 2 and Table 3. Change the value of voltage with a step of 2.5 volts and complete Table 2 and Table 3. 4

5 Table 2 Data collection for components and variables of open loop system No Component and/or variable [unit] Examples: Controller (PC), control signal: V: ma Symbol u c u c Volt-to-Curr Converter, control signal [ma] u c I/P converter Output (pressure) kpa P c Control valve Upstream kpa Downstream kpa P 1 P 2 Control valve Output (flowrate) [l/m] D/P Cell Measured flowrate [ma] In PC: Meas flowrate [V] Meas flowrate [ma] Meas flowrate [l/m] Table 3 Ranges of variables No Component / Instrument Open-loop (MAN) Controller 0 Example: Rotameter Input (range, unit) Output (range, unit) Min Max Min Max -10V 10V 4 ma 20mA Flowrate Reading of flowrate on scale 20 l/min 220 l/min 20 l/min 220 l/min 5

6 Label the components, variables and their ranges in the following block diagram. V/I S7 converter Indicators (Virtual Instruments) PC + Controller Air supply Disturbances S1 S2 S3 S4 S5 S6 C1 C2 C3 C4 Figure 4 Block diagram of the open-loop control system (for flow control) 6

7 QUESTION 1 What type is the pneumatic control valve? QUESTION 2 When the Controller Output changes from 0% (4mA) to 50% (12mA) (of span) How much (%) does the Valve Opening change?... How much (%) does the Process Variable change?... Return the Controller Output to the minimum value. Stop the Open-Loop Control System by clicking button. Important: Don t forget to copy data files to your USB flash memory stick! Notes for Hands-on Exercise 1 (Open Loop Control System) 7

8 3.2 Hands-on Exercise 2: Operation of On-Off Flow Control System Purpose The purpose of this hands-on exercise is to get familiar with an On-Off Flow Control System. Learning Objectives To operate the On-Off Flow Control System To perform settings of ON and OFF values to optimize the system response. Introduction The On-Off flow control system is based on the following principle: Error (E) = PV SP SP Error If E > 0 then OFF (large) CLOSE If E < 0 then ON (small) OPEN Controller Output PV Figure 5 On-Off control algorithm for the flow control system The CLOSE and OPEN values of the valve can be set at different values: Fully close: +10 V (in PC) or 20 ma Fully open: -10 V (in PC) or 4 ma SP, PV and CS in ma Manual Controller P and PV in litre/min Diagram Figure 6 On-Off flow control program (Front Panel) 8

9 Procedure (It is supposed that this exercise is started after Exercise 3.1, the On-Off Flow Controller Program is still open). Run the On-Off Flow Controller Program In MAN mode, confirm SP at 220 litre/min (fully open) and the valve is fully opened. Confirm the OPEN value at -10V, and the CLOSE value (fully open) at +10V (fully close). Switch to AUTO mode. The controller is working in the On-Off control mode. Observe the change in PV. Change the SP to 50% of the span, i.e. 120 lit/min (or 12mA), observe the change in PV. Change the OPEN value to -8V and the CLOSE value to +8V, and observe the change in PV. QUESTION 1 How is the system response changing? Select an OPEN value and a CLOSE value so that the system response hunts the set-point with the least oscillation. You may execute several trials to select appropriate valves. QUESTION 2 What are the best values? To stop the On-Off Controller Program click Close the On-Off Controller Program. button. Notes: Don t forget to copy data files to your USB flash memory stick! Notes for Hands-on Exercise 3.2 9

10 3.3 Hands-On Exercise 3: Operation of PID Control System Introduction The PID control system is based on the following principle: Error (E) = SP PV or PV SP SP Error de u PID = K e P + K edt K I + D dt Controller Output PV The PID controller program has the MAN mode similar to that of the On-Off controller program. In AUTO (closed-loop) mode, the PID controller can work in the following control actions: P only control by setting K i = 0 and K d = 0 I only control by setting K p = 0 and K d = 0 (rarely used for this flow system because I control action makes the system unstable) PI control by setting K d = 0 PD control by setting K i = 0 Control gains (Kp, Ki and Kd) are adjusted by on the following formula of the PID Control Algorithm: de VPID = K Pe + K I edt + K D dt Proportional Band is Integral Time: Derivative Time: P I D K T I = K 100% PB = K P P I K T D = K D P. The control signal is computed based 10

11 Figure 7 PID flow control program (Front Panel) Purpose The purpose of this hands-on exercise is to get familiar with the PID Flow Control System. Learning Objectives Operate the PID flow control system with different control actions: o P control o PI control o PD control o PID control Explain the effects of P, I, D, PI, PD and PID on the system response. Switch between the AUTO and MAN modes smoothly. Procedures (It is suggested that you have closed the On-Off Controller Program.) Run the PID Controller Program Confirm the PID Controller Program in MAN mode. Observe the SP, PV, Controller Output and confirm the following values (if not adjust accordingly): Setpoint: 220 lit/min K p = 2, K i = 0, K d = 0 (Proportional Only Control) Controller Output: -10V (4 ma) PV: 20 ma (220 lit/min) 11

12 Switch to the AUTO mode. The controller is working with Proportional Only Control. Proportional Only Control and Effects of Proportional Gains on System Response and Offset Wait until the system response is stable, fill in Table 1 Execute the Trials 1-10 and fill in Table 1. Table 1 Proportional Band Effect on OFFSET TRIAL K P PB SETPOINT MEAS. (PV) + OR - ERROR OUTPUT (Control Signal) QUESTION 1 How does the system response change when the Proportional Gain changes? Proportional and Integral Control Switch to the MAN and confirm the following value: Setpoint: 220 lit/min K p = 2, K i = 0, K d = 0 (Proportional Only Control) Controller Output: 2V (4 ma) PV: 20 ma (220 lit/min) Change the SP to 180 lit/min What is the error? (ma, lit/min) 12

13 What is the P action? (ma) Change K i to What is the I action? (ma) How is the PI action changing? (You can draw a diagram for I action) Stop the PID Controller Program. Start the PID Controller Program. What is the P action? (ma) How is the I action changing? (You can draw a diagram for I action) Change SP to 220 lit/min and K i = 0 (confirm K p = 2.0). Switch to the AUTO mode. Confirm the system is stable at SP of 220 l/min. Change SP to 180 lit/min. Wait until the system is stable. What is offset value? (ma, lit/min) Change K i to Observe the system response (PV). How does the PV change? Is the offset compensated? Change SP to 160 lit/min. Observe the system response (PV). How does the PV change? Change SP to 180 lit/min. Observe the system response (PV). How does the PV change? Change K i to 0.5. Observe the system response (PV). Change SP to 160 lit/min. Observe the system response (PV). How does the PV change? Change the following value: SP to 220 lit/min 13

14 K i to 0.0 K p to 2.0 Switch to the MAN mode. Stop the PID Control Program. Proportional and Derivative Control Run the PID Control Program in MAN mode. Confirm the following: K p = 2 K i = 0.0 K d = 0.0 SP = 220 lit/min Change K d to 2 and SP to 180 lit/min. Change SP to 160 lit/min How does the D action change? (You may change the Sampling Interval to 1 to observe the D action). Draw a diagram showing the D action. Change K d to 2 and SP to 220 lit/min. Wait until the system response is stable. Switch to AUTO Mode PD control Change the SP to 180 l/min, wait until the system response is stable. Change the SP to 160 l/min, wait until the system response is stable. Is the OFFSET compensated by PD control action? Stop the PID Control Program. Proportional plus Integral plus Derivative Control and AUTO/MAN Transfer From previous trial, change the following values: SP = 220 lit/min K p = 2 K i = K d = 2 AUTO/MAN = MAN Run the PID Control Program. Wait until the system is stable. Switch to the AUTO Mode PID Control Action. At this point, you have experienced with the effects of P, I, PI, PD actions. In this section, please do several trials in order to find some values of K p, K i and K d such that the system response has less oscillation and reaches the SP quickly. Change SP to 160 lit/min. How does the PV change? You can do several trials with different sets of K p, K i and K d. 14

15 You can also do several trials with transfer between AUTO/MAN modes when: o SP = PV o SP is different from PV Describe your observations: Conclusion At this point the following LOs have been met: Operate the PID flow control system with different control actions: o P control o PI control o PD control o PID control Explain the effects of P, I, D, PI, PD and PID on the system response. Switch between the AUTO and MAN modes smoothly. Notes: Don t forget to copy data files to your USB flash memory stick! 4. Calculation and Report In your report, do the following tasks (but not restricted to): Introduction Relevant theory on On-Off control Relevant theory on PID control Relevant theories related to level or flow transmitters/sensors and actuators Using AS Standard Drawing Symbols, draw a flow diagram for the above control system you have selected. Draw a block diagram for the closed-loop control system you have selected. Find transfer functions/sensitivities for all components of the systems. Hints: For the level control system the ODE for the tank is Ah & + k vh = q or in A h& + k v h = q in For the flow control system the ODE for the piping system (flow dynamics) is Qout K e Td s = Q Ts + 1 in Find the total feedback transfer function (refer to Chapter 15) Plot sketches and graphs (from data files) Discussions, evaluations and conclusions 15

16 Appendix 1 Flow Control Bench Global Valve Control Valve Rotameter D/P Cell I/O Converter Appendix 2 Block Diagram for On-Off Controller Program (flow control) 16

17 Appendix 3 Block Diagram of the PID Controller Program (flow control) 17

18 Lab 2 Process Control Computer-based Control Systems Level Control 1. Aims To operate PC-based instrumentation and control systems To get familiar with open-loop control, ON-OFF, and PID control systems To explain P, PI, PD, and PID control actions To transfer MAN mode to AUTO smoothly. 2. Apparatus Process/Plant: Process Control Trainer Cart with Level Control Mode of I/P Converter consists of a tank, a pneumatic control valve (with a pneumatic positioned), a D/P level transmitter, an orifice plate and D/P flow transmitter, pipes and pump, and a D/P pressure transmitter (not used in this experiment). Computer, LabVIEW 8.6, NI DAQ 6036E Card, Signal Conditioning SC-2345 (for level control) including a current-to-voltage converter (4mA-20mA to 1 to 5V, with two channels) and a voltage-to-current converter (0V-+10V to 0mA-20mA). A multimeter. 3 Connection Diagram The connection diagram for control systems is shown in Fig. 1 and Fig. 2b. Pneumatic supply Water supply I/P kpa Valve MI Process (Plant) PV Sensor/s Actuator CS 4-20mA V/I V V I/V MV 4-20mA PC, DAQ PCI 6036E and LabVIEW PC-based controller Figure 1 Connection diagram Scheme diagram for level control system is shown in Fig. 2 (also see Appendix 1). 4. Further Information Refer to Chapters 7, 8, 9 (Pressure, Flow and Level), Chapter 12 Actuators and Chapter 13 Basic Control Theory (Direct Acting On-Off Control, PID Control) 1

19 Air supply I/P converter 0-20mA kpa 0-10V AO-0 1-5V AI V Supply liquid 4-20mA Flow transmitter 4-20mA Orifice plate Level transmitter Pneumatic control valve Positioner q in (0-85% square root) Level m DAQ PCI 6036E, PC and LabVIEW AI-10 SC-2345 Isolation valve Valve 1 q out1 Valve 2 q out2 Figure 2a Schematic diagram for level control system I/P converter Air supply 0-20mA kpa (desired) Controller 0-10V AO-0 1-5V AI V FT Supply liquid 4-20mA DC 24V 4-20mA Pneumatic control valve LT Positioner q in (0-85% square root) Level m PC, DAQ PCI 6036E, and LabVIEW AI-10 SC-2345 DC 24V Isolation valve Figure 2b Connection diagram for level control system Valve 1 q out1 Valve 2 q out2 2

20 Methods 1. Connection and turning on the power Connect the computer, I/V converters, and V/I converter to the process (sensor/s and actuators) by referring to the above scheme/connection diagrams Supply control air (or confirm if the pneumatic supply is done) Turn on the power Log on to the computer 2. Identification of Components and Variables Identify all components and their variable of the process control system (that you have selected) and complete the following table. Table 1 Components and variables Process system: No 1 Component / Model Code (where applicable) Example: PC-based controller (Manual Controller) Input (variable, unit) Setpoint level [ma, V, mm] Measured level [ma, V, mm] Output (variable, unit) Control signal: [V] 2 V/I converter (SC-2345) Control signal: [V] Control signal: [ma] Hands-on Exercises 3.1 Hands-On Exercise 1: Getting Started with Open-Loop Level Control System Purpose: The purpose of this hands-on exercise is to get familiar with a control system and its components, variables and signals. In the Open Loop Control System there is no comparison of feedback signal to the Set Point. In almost controllers MAN mode is an Open Loop mode. Learning Objectives: Operate the open loop control system Understand components of the control system and their signals 3

21 Explain the principles and functions of the components including process, measurement devices (flow transmitters, level transmitter, pressure gauges), actuators, valves and valve positioner. Procedure Run the LabVIEW On-Off controller program C:\Documents and Settings\All Users\LabVIEW Data\JEE326_2009\Lab 2\OnOffLevelControl\ OnOffLevelControl01.exe The controller program is running. If not, click MAN (open-loop) mode. The controller program looks like... to run the On-Off Controller Program in Process variable: level Manual controller Flow rate Diagram Drain valves Figure 3 On-Off controller program in the Manual mode (for level control) Make sure that the Auto/Man mode switch is in Man position. Make sure that the Write to File is at Write position and change the path for data files if necessary Enter a minimum value of voltage, i.e. 0V, write down in Table 2 and Table 3. Change the value of voltage to 2V and then with a step of 1 volt and complete Table 2 and Table 3. 4

22 Table 2 Data collection for components and variables of open loop system No 0 1 Component and/or variable [unit] Examples: Controller (PC), control signal: V: ma Sym u c u c 0 0 Volt-to-Curr Converter, control signal [ma] u c I/P converter Air supply pressure kpa Output (pressure) kpa P 1 Positioner Instrument pressure Air supply pressure Output pressure Control valve Flow transmitter Tank P 2 P 3 P c 0 Table 3 Ranges of variables No Component / Instrument Open-loop (MAN) Controller 0 Example: I/P converter Input (range, unit) Output (range, unit) Min Max Min Max 0V 10V 0 ma 20mA Control signal Control pressure 0 20 ma 0 bar 1.2 bar 5

23 Label the components, variables and their ranges in the following block diagram. V/I S7 converter Indicators (Virtual Instruments) PC + Controller Air supply Disturbances S1 S2 S3 S4 S5 S6 C1 C2 C3 C4 Figure 4 Block diagram of the open-loop control system (for level control) 6

24 QUESTION 1 What type is the pneumatic control valve? QUESTION 2 When the Controller Output changes from 0% (4mA) to 50% (12mA) (of span) How much (%) does the Valve Opening change?... How much (%) does the Process Variable change?... Return the Controller Output to the minimum value. Stop the Open-Loop Control System by clicking button. Important: Don t forget to copy data files to your USB flash memory stick! Notes for Hands-on Exercise 1 (Open Loop Control System) 7

25 3.2 Hands-on Exercise 2: Operation of On-Off Level Control System Purpose The purpose of this hands-on exercise is to get familiar with an On-Off Control System. Learning Objectives To operate the On-Off Control System To perform settings of ON and OFF values to optimize the system response. Introduction The On-Off level control system is based on the following principle: Error (E) = SP PV SP Error If E > 0 then ON (large) OPEN If E < 0 then OFF (small) CLOSE Controller Output PV Figure 5 On-Off control algorithm for level control system Confirm ON (OPEN) and OFF (CLOSE) values of the control valve for your control system: ON (OPEN) Fully open: 10 V or 20 ma OFF (CLOSE) Fully close: 0 V or 0 ma Figure 6 Level controller program (Front Panel) 8

26 Procedure (It is supposed that this exercise is started after Exercise 3.1, the On-Off Level Controller Program is still open). Run the On-Off Level Controller Program In MAN mode, confirm SP at 400 mm and the valve is fully opened. If not, adjust the Manual Control to 10 V to fill water in the tank up to 400 mm. (Notes: There are two drain valves. One is fully closed, the other is half opened. If the tank is empty you may need to closed the half-opened valve, and then return it back to the half opening position when the water reaches 400 mm.) Confirm the OFF (CLOSE) value (fully close) at 0V, and the ON (OPEN) value (fully open) at 10V. Switch to AUTO mode. The controller is working in the On-Off control mode. Observe the change in PV. Change the SP to 50% of the span, i.e. 200 mm (or 12 ma), observe the change in PV. Change the OFF value to 2V (4 ma) and the ON value to 6V (12 ma), and observe the change in PV. QUESTION 1 How is the system response changing? Select an OPEN value and a CLOSE value so that the system response hunts the set-point with the least oscillation. You may execute several trials to select appropriate valves. QUESTION 2 What are the best values? To stop the On-Off Controller Program click Close the On-Off Controller Program. button. Important: Dot not forget to copy data files to your USB flash memory stick! Conclusion At this point, the learning objectives have been met. You are able to To operate the On-Off Control System To perform settings of ON and OFF values to optimize the system response. Notes for Hands-on Exercise 2 9

27 3.3 Hands-On Exercise 3: Operation of PID Control System Introduction The PID control system is based on the following principle: Error (E) = SP PV SP Error de u PID = K e P + K edt K I + D dt Controller Output PV Figure 7 PID control algorithm for the level control system The PID controller program has the MAN mode similar to that of the On-Off controller program. In AUTO (closed-loop) mode, the PID controller can work in the following control actions: P only control by setting K i = 0 and K d = 0 I only control by setting K p = 0 and K d = 0 (rarely used for this level system because I control action makes the system unstable) PI control by setting K d = 0 PD control by setting K i = 0 Control gains (K p, K i and K d ) are adjusted by on the following formula of the PID Control Algorithm: de VPID = K Pe + K I edt + K D dt Proportional Band is Integral Time: Derivative Time: P I D K T I = K 100% PB = K P P I K T D = K D P. The control signal is computed based Purpose The purpose of this hands-on exercise is to get familiar with the PID Control System. Learning Objectives Operate the PID level control system with different control actions: o P control o PI control o PD control o PID control Explain the effects of P, I, D, PI, PD and PID on the system response. Switch between the AUTO and MAN modes smoothly. 10

28 Figure 8 PID controller program (Front Panel) Procedures (It is suggested that you have closed the On-Off Controller Program.) Run the PID Controller Program Confirm the PID Controller Program in MAN mode. Observe the SP, PV, Controller Output and confirm the following values (if not, adjust accordingly): Setpoint: 200 mm K p = 2, K i = 0, K d = 0 (Proportional Only Control) Controller Output: 0V (0 ma) PV: 12 ma (200 mm) Switch to the AUTO mode. The controller is working with Proportional Only Control. Proportional Only Control and Effects of Proportional Gains on System Response and Offset Wait until the system response is stable, fill in Table 4. Execute the Trials 1-10 and fill in Table 4. 11

29 Table 4 Proportional Band Effect on OFFSET TRIAL K P PB SETPOINT MEAS. (PV) + OR - ERROR OUTPUT (Control Signal) QUESTION 1 How does the system response change when the Proportional Gain changes? Proportional and Integral Control Switch to the MAN and confirm the following value: Set-point: 200 mm K p = 2, K i = 0, K d = 0 (Proportional Only Control) PV: 12 ma (200 mm) (if not, adjust the Manual Control to 10V to fill water up to 200 mm. Switch to the Auto Mode. Wait until the level is stable. What is the error? (V, ma, mm) What is the P action? (V, ma) Change the SP to 180 mm What is the error? (V, ma, mm) What is the P action? (V, ma) Change K i to What is the P action? (ma) How is the PI action changing? (You can draw a diagram for I action) 12

30 Stop the PID Controller Program. Start the PID Controller Program. What is the P action? (ma) How is the I action changing? (You can draw a diagram for I action) Change SP to 200 mm and K i = 0 (confirm K p = 2.0). Switch to the AUTO mode. Wait until the system is stable. Change SP to 180 mm. Wait until the system is stable. What is offset value? (ma, mm) Change K i to Observe the system response (PV). How does the PV change? Is the offset compensated? Change SP to 160 mm. Observe the system response (PV). How does the PV change? Change SP to 180 mm. Observe the system response (PV). How does the PV change? Change K i to 0.5. Observe the system response (PV). Change SP to 160 mm. Observe the system response (PV). How does the PV change? Change the following value: SP to 200 mm K i to 0.0 K p to 2.0 Switch to the MAN mode. Stop the PID Control Program. 13

31 Proportional and Derivative Control Run the PID Control Program in MAN mode. Confirm the following: K p = 2 K i = 0.0 K d = 0.0 SP = 200 mm Change K d to 2 and SP to 180 mm. Change SP to 160 mm How does the D action change? (You may change the Sampling Interval to 1 to observe the D action). Draw a diagram showing the D action. Change K d to 2 and SP to 200 mm. Wait until the system response is stable. Switch to AUTO Mode PD control Change the SP to 180 mm, wait until the system response is stable. Change the SP to 160 mm, wait until the system response is stable. Is the OFFSET compensated by PD control action? Stop the PID Control Program. Proportional plus Integral plus Derivative Control and AUTO/MAN Transfer From previous trial, change the following values: SP = 200 mm K p = 2 K i = K d = 2 AUTO/MAN = MAN Run the PID Control Program. Wait until the system is stable. Switch to the AUTO Mode PID Control Action. At this point, you have experienced with the effects of P, I, PI, PD actions. In this section, please do several trials in order to find some values of K p, K i and K d such that the system response has less oscillation and reaches the SP quickly. Change SP to 160 mm. How does the PV change? You can do several trials with different sets of K p, K i and K d. You can also do several trials with transfer between AUTO/MAN modes when: o SP = PV o SP is different from PV 14

32 Describe your observations: Conclusion Operate the PID level control system with different control actions: o P control o PI control o PD control o PID control Explain the effects of P, I, D, PI, PD and PID on the system response. Switch between the AUTO and MAN modes smoothly. Notes: Don t forget to copy data files to your USB flash memory stick! 4. Calculation and Report In your report, do the following tasks (but not restricted to): Introduction Relevant theory on On-Off control Relevant theory on PID control Relevant theories related to level or level transmitters/sensors and actuators Using AS Standard Drawing Symbols, draw a level diagram for the above control system you have selected. Draw a block diagram for the closed-loop control system you have selected. Find transfer functions/sensitivities for all components of the systems. Hints: For the level control system the ODE for the tank is Ah& + k vh = qin For the flow control system the ODE for the piping system (flow dynamics) is Qout K e Td s = Q Ts + 1 in Find the total feedback transfer function (refer to Chapter 15) Plot sketches and graphs (from data files) Discussions, evaluations and conclusions 15

33 Appendix 1 Process Control Trainer Cart Tank Control valve Microprocessor-based controllers and chart recorders Valve positioner Pressure transmitter Level transmitter Flow transmitter I/P converter Process Control Trainer Cart Appendix 2 Block Diagram for On-Off Controller Program (level control) 16

34 Appendix 3 Block Diagram of the PID Controller Program (level control) 17

Cell Phone Vibration Experiment

Cell Phone Vibration Experiment Objective Cell Phone Vibration Experiment Most cell phones are designed to vibrate. But at what frequency do they vibrate? With an accelerometer, data acquisition and signal analysis the vibration frequency

More information

A Design of a PID Self-Tuning Controller Using LabVIEW

A Design of a PID Self-Tuning Controller Using LabVIEW Journal of Software Engineering and Applications, 2011, 4, 161-171 doi:10.4236/jsea.2011.43018 Published Online March 2011 (http://www.scirp.org/journal/jsea) 161 A Design of a PID Self-Tuning Controller

More information

Control of an industrial process using PID control blocks in automation controller

Control of an industrial process using PID control blocks in automation controller Control of an industrial process using PID control blocks in automation controller by Michel Van Dessel 1 1 Abstract Many continuous industrial processes can be controlled using programmable automation

More information

Industrial Steam System Process Control Schemes

Industrial Steam System Process Control Schemes Industrial Steam System Process Control Schemes This paper was developed to provide a basic understanding of the different process control schemes used in a typical steam system. This is however a fundamental

More information

A Study of Speed Control of PMDC Motor Using Auto-tuning of PID Controller through LabVIEW

A Study of Speed Control of PMDC Motor Using Auto-tuning of PID Controller through LabVIEW A Study of Speed Control of PMDC Motor Using Auto-tuning of PID Controller through LabVIEW Priyanka Rajput and Dr. K.K. Tripathi Department of Electronics and Communication Engineering, Ajay Kumar Garg

More information

Process Control Primer

Process Control Primer Process Control Primer At the onset of the Industrial Revolution, processes were controlled manually. Men turned valves, pulled levers or changed switches based on the need to turn devices on or off. As

More information

Introduction to LabVIEW for Control Design & Simulation Ricardo Dunia (NI), Eric Dean (NI), and Dr. Thomas Edgar (UT)

Introduction to LabVIEW for Control Design & Simulation Ricardo Dunia (NI), Eric Dean (NI), and Dr. Thomas Edgar (UT) Introduction to LabVIEW for Control Design & Simulation Ricardo Dunia (NI), Eric Dean (NI), and Dr. Thomas Edgar (UT) Reference Text : Process Dynamics and Control 2 nd edition, by Seborg, Edgar, Mellichamp,

More information

Lab 3: Introduction to Data Acquisition Cards

Lab 3: Introduction to Data Acquisition Cards Lab 3: Introduction to Data Acquisition Cards INTRODUCTION: In this lab, you will be building a VI to display the input measured on a channel. However, within your own VI you will use LabVIEW supplied

More information

Data Acquisition Using NI-DAQmx

Data Acquisition Using NI-DAQmx Instructor s Portion Data Acquisition Using NI-DAQmx Wei Lin Department of Biomedical Engineering Stony Brook University Summary This experiment requires the student to use NI-DAQmx to acquire voltage

More information

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE HITACHI INVERTER SJ/L1/3 SERIES PID CONTROL USERS GUIDE After reading this manual, keep it for future reference Hitachi America, Ltd. HAL1PID CONTENTS 1. OVERVIEW 3 2. PID CONTROL ON SJ1/L1 INVERTERS 3

More information

Microcontroller-based experiments for a control systems course in electrical engineering technology

Microcontroller-based experiments for a control systems course in electrical engineering technology Microcontroller-based experiments for a control systems course in electrical engineering technology Albert Lozano-Nieto Penn State University, Wilkes-Barre Campus, Lehman, PA, USA E-mail: AXL17@psu.edu

More information

Servo Motors (SensorDAQ only) Evaluation copy. Vernier Digital Control Unit (DCU) LabQuest or LabPro power supply

Servo Motors (SensorDAQ only) Evaluation copy. Vernier Digital Control Unit (DCU) LabQuest or LabPro power supply Servo Motors (SensorDAQ only) Project 7 Servos are small, relatively inexpensive motors known for their ability to provide a large torque or turning force. They draw current proportional to the mechanical

More information

INSTRUMENTATION AND CONTROL TUTORIAL 3 SIGNAL PROCESSORS AND RECEIVERS

INSTRUMENTATION AND CONTROL TUTORIAL 3 SIGNAL PROCESSORS AND RECEIVERS INSTRUMENTATION AND CONTROL TUTORIAL 3 SIGNAL PROCESSORS AND RECEIVERS This tutorial provides an overview of signal processing and conditioning for use in instrumentation and automatic control systems.

More information

PID control - Simple tuning methods

PID control - Simple tuning methods - Simple tuning methods Ulf Holmberg Introduction Lab processes Control System Dynamical System Step response model Self-oscillation model PID structure Step response method (Ziegler-Nichols) Self-oscillation

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

QNET Experiment #06: HVAC Proportional- Integral (PI) Temperature Control Heating, Ventilation, and Air Conditioning Trainer (HVACT)

QNET Experiment #06: HVAC Proportional- Integral (PI) Temperature Control Heating, Ventilation, and Air Conditioning Trainer (HVACT) Quanser NI-ELVIS Trainer (QNET) Series: QNET Experiment #06: HVAC Proportional- Integral (PI) Temperature Control Heating, Ventilation, and Air Conditioning Trainer (HVACT) Student Manual Table of Contents

More information

Gas Custody Transfer Calibration

Gas Custody Transfer Calibration Gas Custody Transfer Calibration Using multi variable temperature / pressure calibrators for flowmeter calibration 2013 Introduction Gas custody transfer flow computers require special calibration to perform

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

SECTION 5 Examples of Function Block Combinations

SECTION 5 Examples of Function Block Combinations SECTION 5 Examples of Function Block Combinations 5-1 BASIC EXAMPLES OF CONTROL... 152 5-1-1 Simple Control... 152 5-1-2 Multi-channel Control... 153 5-1-3 Control for Switching Multiple Set Points...

More information

T0118 T2118 T3118. Instruction Manual

T0118 T2118 T3118. Instruction Manual Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity

More information

OEM-EP Pressure Controllers

OEM-EP Pressure Controllers Pressure Controllers Typical Applications Carrier Gas Pressure Control Air over Liquid Control Mass Spectrometer Process Gas Supply Pressure Control Miniature ler The Miniature ler converts a variable

More information

8500 Installation/Start-up/Operation Lit # 8500 OP

8500 Installation/Start-up/Operation Lit # 8500 OP 8500 Installation/Start-up/Operation Lit # 8500 OP K SYSTEM CORPORATION INVENTORY SYSTEM GENERAL DESCRIPTION The K SYSTEM TANK INVENTORY CONTROL SYSTEM, #8600C Series, provides an extremely accurate method

More information

Instrumentation and Process Control. Boiler Control. Courseware Sample 85993-F0

Instrumentation and Process Control. Boiler Control. Courseware Sample 85993-F0 Instrumentation and Process Control Boiler Control Courseware Sample 85993-F0 A INSTRUMENTATION AND PROCESS CONTROL BOILER CONTROL Courseware Sample by the staff of Lab-Volt Ltd. Copyright 2010 Lab-Volt

More information

Temperature Transmitter TTX300

Temperature Transmitter TTX300 coo Interface Description COM/TTX300/FF-EN Temperature Transmitter TTX300 FOUNDATION Fieldbus Contents Blinder Text Temperature Transmitter TTX300 Interface Description COM/TTX300/FF-EN 01.2010 Manufacturer:

More information

Lab 4 - Data Acquisition

Lab 4 - Data Acquisition Spring 11 Lab 4 - Data Acquisition Lab 4-1 Lab 4 - Data Acquisition Format This lab will be conducted during your regularly scheduled lab time in a group format. Each student is responsible for learning

More information

Implementing PID Temperature Control Using LabVIEW. Abstract. Introduction

Implementing PID Temperature Control Using LabVIEW. Abstract. Introduction Implementing PID Temperature Control Using LabVIEW Carlton Prewit, Rafic Bachnak Department of Computing and Mathematical Sciences Texas A&M University Corpus Christi Session XXXX Abstract Feedback control

More information

Positioner Versions. Remote feed-back. Local display, Electric / Hydraulic. Remote feed-back Electric / Hydraulic. Embedded Control Positioner

Positioner Versions. Remote feed-back. Local display, Electric / Hydraulic. Remote feed-back Electric / Hydraulic. Embedded Control Positioner Quick Stepper 3G ECP Positioner Versions Mechanical feed-back Pneumatic Remote feed-back Local display, Pneumatic Remote feed-back Local display, Electric / Hydraulic Remote feed-back Electric / Hydraulic

More information

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.

More information

USB-500 Series Stand-Alone, Low-Cost Data Loggers

USB-500 Series Stand-Alone, Low-Cost Data Loggers Stand-Alone, Low-Cost Data Loggers Features Stand-alone, remote data loggers Measure temperature, humidity, voltage, or current 1 or 2 channels Low cost, small size Battery powered Software Included, easy-to-use

More information

Cod. Documento: RT2014-0515a Title: Fimer Plant Controller Description. Rev. Data Redatto Approvato. 00 15-9-2014 S.Sidoti A.

Cod. Documento: RT2014-0515a Title: Fimer Plant Controller Description. Rev. Data Redatto Approvato. 00 15-9-2014 S.Sidoti A. Pag 1 di 19 SCOPE The main purpose of the Fimer Plant Controller is make possible to the Grid Operator both remote and local control capability over an entire PV plant from a single control point The Fimer

More information

EVAL-UFDC-1/UFDC-1M-16

EVAL-UFDC-1/UFDC-1M-16 Evaluation Board for Universal Frequency-to- Digital Converters UFDC-1 and UFDC-1M-16 EVAL-UFDC-1/UFDC-1M-16 FEATURES Full-Featured Evaluation Board for the Universal Frequency-to-Digital Converters UFDC-1

More information

Device Management Jonas Berge Emerson Process Management

Device Management Jonas Berge Emerson Process Management Device Management Jonas Berge Emerson Process Management 1 Topics What is intelligent device management? Integrated operations Why do I need a handheld field communicator? With fieldbus, I can do everything

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

Terminology and Symbols in Control Engineering

Terminology and Symbols in Control Engineering Technical Information Terminology and Symbols in Control Engineering 1 Part 1 Fundamentals Technical Information Part 1: Fundamentals Part 2: Self-operated Regulators Part 3: Control Valves Part 4: Communication

More information

Automotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim

Automotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim Automotive sensor simulator Operating manual AutoSim Contents Introduction.. page 3 Technical specifications.... page 4 Typical application of AutoSim simulator..... page 4 Device appearance... page 5

More information

SHENZHEN JUNSI ELECTRONIC CO.,LTD

SHENZHEN JUNSI ELECTRONIC CO.,LTD Cell Voltage Monitor&Logger USER S MANUAL SHENZHEN JUNSI ELECTRONIC CO.,LTD Thank you for purchasing the. Please read the entire User s Manual completely and attentively as it contains a wide variety of

More information

Lab 2 Sensor Modeling Introduction to the Wiimote and the Wiimote LABVIEW Interface

Lab 2 Sensor Modeling Introduction to the Wiimote and the Wiimote LABVIEW Interface Lab 2 Sensor Modeling Introduction to the Wiimote and the Wiimote LABVIEW Interface 1. Objective In this lab, you will: i. Become familiar with the Wiimote ii. Understand the LABVIEW Bluetooth interface

More information

A simple method to determine control valve performance and its impacts on control loop performance

A simple method to determine control valve performance and its impacts on control loop performance A simple method to determine control valve performance and its impacts on control loop performance Keywords Michel Ruel p.eng., Top Control Inc. Process optimization, tuning, stiction, hysteresis, backlash,

More information

Indicators. and Alarm Units. World class accuracy with clear, user friendly, operator interfaces. Control Optimise Simplify

Indicators. and Alarm Units. World class accuracy with clear, user friendly, operator interfaces. Control Optimise Simplify Indicators and Alarm Units World class accuracy with clear, user friendly, operator interfaces Control Optimise Simplify Control Optimise Simplify Easy to use technology so powerful it s simple 2 Indicators

More information

Universal Simple Control, USC-1

Universal Simple Control, USC-1 Universal Simple Control, USC-1 Data and Event Logging with the USB Flash Drive DATA-PAK The USC-1 universal simple voltage regulator control uses a flash drive to store data. Then a propriety Data and

More information

High Power Programmable DC Power Supplies PVS Series

High Power Programmable DC Power Supplies PVS Series Data Sheet High Power Programmable DC Power Supplies The PVS10005, PVS60085, and PVS60085MR programmable DC power supplies offer clean output power up to 5.1 kw, excellent regulation, and fast transient

More information

Electro-Pneumatic Bus Door Control Mechanism

Electro-Pneumatic Bus Door Control Mechanism Electro-Pneumatic Bus Door Control Mechanism Application and Feature 1. Pneumatic Door Mechanism actuates the open/close movements of bus door through two double acting cylinders and two linkages with

More information

Conversion Between Analog and Digital Signals

Conversion Between Analog and Digital Signals ELET 3156 DL - Laboratory #6 Conversion Between Analog and Digital Signals There is no pre-lab work required for this experiment. However, be sure to read through the assignment completely prior to starting

More information

Contents. Document information

Contents. Document information User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB

More information

GRUNDFOS INSTRUCTIONS. CR Monitoring. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. CR Monitoring. Installation and operating instructions GRUNDFOS INSTRUCTIONS CR Monitoring Installation and operating instructions Declaration of Conformity We Grundfos declare under our sole responsibility that the product CR Monitor, to which this declaration

More information

How to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers.

How to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers. How to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers. OMEGALOG Help Page 2 Connecting Your Data Logger Page 2 Logger Set-up Page 3 Download Data Page 8 Export Data Page 11 Downloading

More information

Inwall Room Temperature Unit

Inwall Room Temperature Unit Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall

More information

Guidelines for operation of minimum flow control valves

Guidelines for operation of minimum flow control valves Guidelines for operation of minimum flow control valves Holter Regelarmaturen GmbH & Co KG Helleforthstr. 58-60 D-33758 Schloß Holte-Stukenbrock 05/2005 List of contents I. Minimum flow control valves...

More information

System Modeling and Control for Mechanical Engineers

System Modeling and Control for Mechanical Engineers Session 1655 System Modeling and Control for Mechanical Engineers Hugh Jack, Associate Professor Padnos School of Engineering Grand Valley State University Grand Rapids, MI email: jackh@gvsu.edu Abstract

More information

GENERAL SCIENCE LABORATORY 1110L Lab Experiment 6: Ohm s Law

GENERAL SCIENCE LABORATORY 1110L Lab Experiment 6: Ohm s Law GENERAL SCIENCE LABORATORY 1110L Lab Experiment 6: Ohm s Law OBJECTIVES: To verify Ohm s law, the mathematical relationship among current, voltage or potential difference, and resistance, in a simple circuit.

More information

Dr. Yeffry Handoko Putra, S.T., M.T

Dr. Yeffry Handoko Putra, S.T., M.T Tuning Methods of PID Controller Dr. Yeffry Handoko Putra, S.T., M.T yeffry@unikom.ac.id 1 Session Outlines & Objectives Outlines Tuning methods of PID controller: Ziegler-Nichols Open-loop Coon-Cohen

More information

Vibration Monitoring System Adash 3600

Vibration Monitoring System Adash 3600 " User's guide Application: Vibration Monitoring System Adash 3600! Vibration diagnostics, monitoring and protective on-line system! On-line vibration monitoring system of engines, fans, pumps, gearboxes,

More information

Event recording (or logging) with a Fluke 287/289 Digital Multimeter

Event recording (or logging) with a Fluke 287/289 Digital Multimeter Event recording (or logging) with a Fluke 287/289 Digital Multimeter Application Note One of the major features of the Fluke 280 Series digital multimeters (DMM) with TrendCapture is their ability to record

More information

NOVA MULTI-MONITORING SOFTWARE. Instruction Manual

NOVA MULTI-MONITORING SOFTWARE. Instruction Manual NOVA MULTI-MONITORING SOFTWARE REMOTE OPERATION Precision Digital Corporation s Nova Multi-Monitoring software allows for the operation of common Nova control features remotely from a PC. Up to 30 Nova

More information

Measurement Products. PID control theory made easy Optimising plant performance with modern process controllers

Measurement Products. PID control theory made easy Optimising plant performance with modern process controllers Measurement Products PID control theory made easy Optimising plant performance with modern process controllers 1. What are the main types of control applications? Introduction Accurate control is critical

More information

USB-500 Series Low-Cost Data Loggers and Accessories

USB-500 Series Low-Cost Data Loggers and Accessories Low-Cost Data Loggers and Accessories Features Stand-alone, remote data loggers and portable logger assistant Measure temperature, humidity, voltage, current, or event/state change 1 or 2 channels Low

More information

T-BOXN12R. First steps with T-BOXN12R. You can make it wireless. Date: 2004-07-16 Version 1.0

T-BOXN12R. First steps with T-BOXN12R. You can make it wireless. Date: 2004-07-16 Version 1.0 T-BOXN12R You can make it wireless First steps with T-BOXN12R Date: 2004-07-16 Version 1.0 Content 1. Purpose of this document... 3 2. T-BoxN12R overview... 4 3. First step... 5 3.1. Preparing your workshop

More information

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions RVR Hybrid System Controller Installation Instructions 1 Introduction to Hybrid Systems The RVR Hybrid system uses a combination of the Immergas Audax range of heat pumps with gas or oil boilers to create

More information

UM-X Field display for continous level sensors

UM-X Field display for continous level sensors Technical Documentation Field display for continous level sensors 10/2007 Edition: 1 Item No.: 207120 FAFNIR GmbH Bahrenfelder Str. 19 D-22765 Hamburg Telephone: +49 (0)40-39 82 07-0 Fax: +49 (0)40-3 90

More information

Transmitter Interface Program

Transmitter Interface Program Transmitter Interface Program Operational Manual Version 3.0.4 1 Overview The transmitter interface software allows you to adjust configuration settings of your Max solid state transmitters. The following

More information

PID Control. Chapter 10

PID Control. Chapter 10 Chapter PID Control Based on a survey of over eleven thousand controllers in the refining, chemicals and pulp and paper industries, 97% of regulatory controllers utilize PID feedback. Desborough Honeywell,

More information

Chilled Water Valves: Resizing and Tuning for Peak Performance. IDEA Conference Feb. 2008 Jay Russell, PE University of Michigan

Chilled Water Valves: Resizing and Tuning for Peak Performance. IDEA Conference Feb. 2008 Jay Russell, PE University of Michigan Chilled Water Valves: Resizing and Tuning for Peak Performance IDEA Conference Feb. 2008 Jay Russell, PE University of Michigan Overview Introduction Discussion of Chilled Water (CHW) Control Valve Selection

More information

PC Software for VAV compact and modular controllers

PC Software for VAV compact and modular controllers s 5 854 OpenAir PC Software for VAV compact and modular controllers ACS941 for use with GDB/GLB/ASV181 For Version 3.02 The ACS941 software is used for setting and displaying the parameter values with

More information

Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual

Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual Ⅰ. Warn Warning of connection Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual If the controller fails to operate or error occurs, the system will bring fault for it, please

More information

FUNDAMENTALS OF CONTROL ENGINEERING

FUNDAMENTALS OF CONTROL ENGINEERING EQUIPMENT FOR ENGINEERING EDUCATION EQUIPMENT FOR ENGINEERING EDUCATION ENGINEERING MECHANICS & MACHINE ELEMENTS Statics Strength of Materials Dynamics Fundamentals of Engineering Design Machinery Diagnosis

More information

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C F4 Process Controller Installation and Operation Guide SAFETY ALERTS The symbols below are used on the equipment and throughout this document to draw the user s attention to important operational and safety

More information

Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015

Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015 Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) The standard tuning values used in ADVANCED Motion Controls drives are conservative and work well in over 90%

More information

GETTING STARTED. 6. Click the New Specimen icon.

GETTING STARTED. 6. Click the New Specimen icon. BD FACSDiva Software Basic Experiment Guide Please note, this guide is not intended to take the place of in-person training but is to be used as a reference as needed after completing training with Unified

More information

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

Schematic Symbols Chart (Design Hydraulic and Pneumatic circits)

Schematic Symbols Chart (Design Hydraulic and Pneumatic circits) Page 1 of 6 (Home) Symbols / Visit us on: Fluid Power, Automation and Motion Control for all Industries About Us Products Services Catalogs Place an Order Training & Information Contact Us Employee Access

More information

PID Controller Tuning: A Short Tutorial

PID Controller Tuning: A Short Tutorial PID Controller Tuning: A Short Tutorial Jinghua Zhong Mechanical Engineering, Purdue University Spring, 2006 Outline This tutorial is in PDF format with navigational control. You may press SPACE or, or

More information

Computer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC

Computer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC Technical Teaching Equipment Computer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC Teaching Technique used EDIBON SCADA System 2 Control Interface Box 5 Cables and Accessories 6 Manuals 3

More information

Automation and Systems Technology. LABCONTROL TFM/TPM User Manual TroxMConnect Operating Software. 1. Introduction 1. 2. Software Installation 2

Automation and Systems Technology. LABCONTROL TFM/TPM User Manual TroxMConnect Operating Software. 1. Introduction 1. 2. Software Installation 2 1. Introduction 1 2. Software Installation 2 2.1 System Requirements 2 2.2 TroxMConnect Installation 2 2.3 Connection to the PC 3 3. TroxMConnect Description 4 3.1 Starting the Software 4 3.2 Layout 4

More information

Controller Design using the Maple Professional Math Toolbox for LabVIEW

Controller Design using the Maple Professional Math Toolbox for LabVIEW Controller Design using the Maple Professional Math Toolbox for LabVIEW This application demonstrates how you can use the Maple Professional Math Toolbox for LabVIEW to design and tune a Proportional-Integral-Derivative

More information

Evaluation copy. Build a Temperature Sensor. Project PROJECT DESIGN REQUIREMENTS

Evaluation copy. Build a Temperature Sensor. Project PROJECT DESIGN REQUIREMENTS Build a emperature Sensor Project A sensor is a device that measures a physical quantity and converts it into an electrical signal. Some sensors measure physical properties directly, while other sensors

More information

Industrial Automation Training Academy. PLC, HMI & Drives Training Programs Duration: 6 Months (180 ~ 240 Hours)

Industrial Automation Training Academy. PLC, HMI & Drives Training Programs Duration: 6 Months (180 ~ 240 Hours) nfi Industrial Automation Training Academy Presents PLC, HMI & Drives Training Programs Duration: 6 Months (180 ~ 240 Hours) For: Electronics & Communication Engineering Electrical Engineering Instrumentation

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue

More information

Multi-Range Programmable DC Power Supplies 9115 Series

Multi-Range Programmable DC Power Supplies 9115 Series Data Sheet 1200 W Multi-Range DC Power Supplies Features & Benefits Any 9115 series model can replace several supplies on your bench or in your rack. Unlike conventional supplies with fixed output ratings,

More information

REMOTE LABORATORY PLANT CONTROL

REMOTE LABORATORY PLANT CONTROL REMOTE LABORATORY PLANT CONTROL HALÁS Rudolf, ĎURINA Pavol Institute of Information Engineering, Automation and Mathematics Faculty of Chemical and Food Technology Slovak University of Technology in Bratislava,

More information

BEIJING EPSOLAR TECHNOLOGY CO.,LTD.

BEIJING EPSOLAR TECHNOLOGY CO.,LTD. WITH TWO BATTERY CHARGING EPSOLAR s duo-battery charging solar controller, For RVs, Caravans,and boats. Adjust options: 1. Battery type selection. 2. Two battery charging priority(from 0-100%) 3. Charging

More information

D-MAX WEB GUIDE CONTROLLER WITH OPERATOR INTERFACE PANEL QUICK START SETUP MANUAL

D-MAX WEB GUIDE CONTROLLER WITH OPERATOR INTERFACE PANEL QUICK START SETUP MANUAL 1/1 D-MAX.D1 1A Manual S1 D-MAX OPERATOR INTERFACE (Application Home Screen Is Shown) D-MAX CONTROLLER 04/14/2008 2008 Fife Corporation. All rights reserved. Figure Sheet 2-249 This page is intentionally

More information

6.2.2 TECHNICAL ARGUMENTS FOR OWN SCADA AND OWN SCADA WITH PID CONTROL.

6.2.2 TECHNICAL ARGUMENTS FOR OWN SCADA AND OWN SCADA WITH PID CONTROL. 1/9 www.edibon.com Ref: 6.2.2 TECHNICAL ARGUMENTS FOR OWN SCADA AND OWN SCADA WITH PID CONTROL. About 600 units in EDIBON product range are considered as advanced units. Why do we consider them advanced

More information

INDUSTRIAL AUTOMATION Interactive Graphical SCADA System INSIGHT AND OVERVIEW. IGSS Online Training. Exercise 8: Creating Templates

INDUSTRIAL AUTOMATION Interactive Graphical SCADA System INSIGHT AND OVERVIEW. IGSS Online Training. Exercise 8: Creating Templates INDUSTRIAL AUTOMATION Interactive Graphical SCADA System INSIGHT AND OVERVIEW IGSS Online Training Exercise 8: Creating Templates Exercise: Create Templates and Template Based Objects Purpose Learn how

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information

Inwall 4 Input / 4 Output Module

Inwall 4 Input / 4 Output Module Inwall 4 Input / 4 Output Module IO44C02KNX Product Handbook Product: Inwall 4 Input / 4 Output Module Order Code: IO44C02KNX 1/27 INDEX 1. General Introduction... 3 2. Technical data... 3 2.1 Wiring Diagram...

More information

Product data sheet. JUMO MIDAS Pressure Transmitter. Sales No. Order code JUMO AS 40.1001 401001/000-459-405-502-20-601-61

Product data sheet. JUMO MIDAS Pressure Transmitter. Sales No. Order code JUMO AS 40.1001 401001/000-459-405-502-20-601-61 Produktdatenblatt - JUMO MIDAS Pressure Transmitter JUMO AS Street address: Solheimveien 50, 1470 Lørenskog, Norway Phone: +47 67 97 37 10 Delivery address: Solheimveien 50, 1470 Lørenskog, Norway Fax:

More information

Implementation of Fuzzy and PID Controller to Water Level System using LabView

Implementation of Fuzzy and PID Controller to Water Level System using LabView Implementation of Fuzzy and PID Controller to Water Level System using LabView Laith Abed Sabri, Ph.D University of Baghdad AL-Khwarizmi college of Engineering Hussein Ahmed AL-Mshat University of Baghdad

More information

Measuring, Controlling and Regulating with labworldsoft

Measuring, Controlling and Regulating with labworldsoft Kai-Oliver Linde IKA-Werke Staufen Neumagenstraße 27 79219 Staufen Measuring, Controlling and Regulating with labworldsoft Rapid and easy networking of lab devices from different manufacturers The user

More information

Process controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line

Process controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line BT. 2.9 M/E Process controller programmer /6 DIN - 48 x 48 mm gammadue series M line Advanced features, customizable and process adaptable High speed data aquisition and signal management. Efficent information

More information

Rackmount Intelligent Pressure Scanners

Rackmount Intelligent Pressure Scanners Rackmount Intelligent Pressure Scanners NetScanner System 9816/98RK-1 FEATURES ±0.05% Accuracy 100 Hz EU Throughput Autonegotiating 10/100/1G Base T Ethernet - TCP and UDP Protocol Pressure Ranges up to

More information

Lambda Tuning the Universal Method for PID Controllers in Process Control

Lambda Tuning the Universal Method for PID Controllers in Process Control Lambda Tuning the Universal Method for PID Controllers in Process Control Lambda tuning gives non-oscillatory response with the response time (Lambda) required by the plant. Seven industrial examples show

More information

Phocos CXCOM for CX and CXN Instruction Manual

Phocos CXCOM for CX and CXN Instruction Manual Phocos CXCOM for CX and CXN Instruction Manual Contents 1. System Requirements...3 2. Setting up the Phocos CX/CXN Charge Controller Menu... 4 3. Installing the Drivers for the Phocos CXI... 6 4. Installing

More information

R001. Room Control Unit TG650. Summary. Control functions. Orders. Planning. Installation

R001. Room Control Unit TG650. Summary. Control functions. Orders. Planning. Installation R001 Room Control Unit TG650 Summary TG650 Microprocessor Room Control Unit is designed to manage and control hotel room services. The Room Unit automatically manages the electric system validation on

More information

VP23, 3-way proportional pressure control valves Seat valve with μp-driven pressure control

VP23, 3-way proportional pressure control valves Seat valve with μp-driven pressure control VP, -way proportional pressure control valves > > Port size: G/... G/ > > All-digital control electronics > > Variable pressure control > > Optional actuation via fieldbus (separate datasheet on request)

More information

USB-AD16f Data acquisition system (USB)

USB-AD16f Data acquisition system (USB) Data acquisition system (USB) Measurement & Control. Extremely powerful. Precisely record and output signals with the USB-AD16f: The high-performance USB data acquisition system accomodated in a stable

More information

Instruction Manual. T3111 T3111L T3111P T3111Ex

Instruction Manual. T3111 T3111L T3111P T3111Ex www.cometsystem.cz Instruction Manual T3111 T3111L T3111P T3111Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with external probe and 4-20 ma outputs

More information

Lab 5 Getting started with analog-digital conversion

Lab 5 Getting started with analog-digital conversion Lab 5 Getting started with analog-digital conversion Achievements in this experiment Practical knowledge of coding of an analog signal into a train of digital codewords in binary format using pulse code

More information

Split Controller. User Manual SM-SS-F 2009/01/04

Split Controller. User Manual SM-SS-F 2009/01/04 Split Controller SM-SS-F User Manual 2009/01/04 Table of contents 1. Parts illustration.... 1 2. Electrical technical data...... 2 3. Electrical connection...3 4. Assemble parts...4 4.1 Assemble the fixed

More information