Lab 2 Process Control Computer-based Control Systems Flow Control
|
|
- Felicia Wilkins
- 7 years ago
- Views:
Transcription
1 Lab 2 Process Control Computer-based Control Systems Flow Control 1. Aims To operate PC-based instrumentation and control systems To get familiar with open-loop control, ON-OFF, and PID control systems To explain P, PI, PD, and PID control actions To transfer MAN mode to AUTO smoothly. 2. Apparatus Process/Plant: Flow Control Bench consists I/P Converter, Pneumatic Control Valve, Orifice and D/P Cell Transmitters, Pipes and Pump, and Rotameter Computer, LabVIEW 8.6, NI DAQ 6036E Card, Current-to-Voltage converter (4mA-20mA to 1 to 5V) and Voltage-to-Current converter (-10V/+10V to 4mA-20mA). Multimeter, mameter 3 Connection Diagram The connection diagram for control systems is shown in Fig. 1. Pneumatic supply Water supply I/P kpa Valve MI Process (Plant) PV Sensor/s Actuator CS 4-20mA V/I V V I/V MV 4-20mA PC, DAQ PCI 6036E and LabVIEW PC-based controller Figure 1 Connection diagram Schematic diagram for flow control system is shown in Fig. 2 (a & b). 4. Further Information Refer to Chapters 7, 8, 9 (Pressure, Flow and Level), Chapter 12 Actuators and Chapter 13 Basic Control Theory (Direct Acting On-Off Control, PID Control) 1
2 Globe valve ma 4-20mA COMPUTER LABView DAQ 6036E I/V & V/I ma Pneumatic supply kpa Rotameter Q (lpm) Output current I/P Converter Actuator Control valve DC 24V D/P Cell Valve (Open) Gauge 1 Gauge 2 Orifice plate Valve (Closed) Valve (Closed) Pump Water tank Figure 2a Schematic diagram of Flow Control System (Flow Control Bench) Flow Bench D/P Cell kpa Pneumatic supply DC 24V Current 4-20mA (0-30kPa) Orifice plate I/P converter 250R Current 4-20mA kpa (designed) Flow AI channel V Control signal 10V to +10V Control signal 4-20mA COMPUTER DAQ 6036E and LabVIEW V-to-I Figure 2b Connection diagram of the Flow Control System 2
3 Methods 1. Connection and turning on the power Connect the computer, I/V converters, and V/I converter to the process (sensor/s and actuators) by referring to the above scheme/connection diagrams Supply control air (or confirm if the pneumatic supply is done) Turn on the power Log on to the computer 2. Identification of Components and Variables Identify all components and their variable of the process control system (that you have selected) and complete Table 1. Table 1 Components and variables Process system: Component / Model Code No (where applicable) Example: Controller (PC) Input (variable, unit) Process variable: flow [mm, ma, V] Set point [mm, ma, V] Output (variable, unit) Control signal [V, ma] 3. Hands-on Exercises 3.1 Hands-On Exercise 1: Getting Started with Open-Loop Flow Control System Purpose: The purpose of this hands-on exercise is to get familiar with a control system and its components, variables and signals. In the Open Loop Control System there is no comparison of feedback signal to the Set Point. In almost controllers MAN mode is an Open Loop mode. Learning Objectives: Operate the open loop control system Understand components of the control system and their signals 3
4 Explain the principles and functions of the components including process, measurement devices (flow transmitters, pressure gauges), actuators, valves and valve positioners. Procedure Run the LabVIEW On-Off controller program Flow: C:\Documents and Settings\All Users\LabVIEW Data\JEE326_2009\Lab 2\OnOffFlowControlSys\ OnOffFlowControlSys.exe The On-Off controller program looks like... (from D/P cell) SP, PV and CS in ma Manual Controller P and PV in litre/min Diagram Figure 3 On-Off controller program (for flow control) The program is running. If not, click to run the On-Off Controller Program. Make sure that the Auto/Man mode switch is in Man position) Make sure that the Write to File is at Write position and change the path for data files if necessary Enter a minimum value of voltage (Manual Controller), i.e. -10V, write down in Table 2 and Table 3. Change the value of voltage with a step of 2.5 volts and complete Table 2 and Table 3. 4
5 Table 2 Data collection for components and variables of open loop system No Component and/or variable [unit] Examples: Controller (PC), control signal: V: ma Symbol u c u c Volt-to-Curr Converter, control signal [ma] u c I/P converter Output (pressure) kpa P c Control valve Upstream kpa Downstream kpa P 1 P 2 Control valve Output (flowrate) [l/m] D/P Cell Measured flowrate [ma] In PC: Meas flowrate [V] Meas flowrate [ma] Meas flowrate [l/m] Table 3 Ranges of variables No Component / Instrument Open-loop (MAN) Controller 0 Example: Rotameter Input (range, unit) Output (range, unit) Min Max Min Max -10V 10V 4 ma 20mA Flowrate Reading of flowrate on scale 20 l/min 220 l/min 20 l/min 220 l/min 5
6 Label the components, variables and their ranges in the following block diagram. V/I S7 converter Indicators (Virtual Instruments) PC + Controller Air supply Disturbances S1 S2 S3 S4 S5 S6 C1 C2 C3 C4 Figure 4 Block diagram of the open-loop control system (for flow control) 6
7 QUESTION 1 What type is the pneumatic control valve? QUESTION 2 When the Controller Output changes from 0% (4mA) to 50% (12mA) (of span) How much (%) does the Valve Opening change?... How much (%) does the Process Variable change?... Return the Controller Output to the minimum value. Stop the Open-Loop Control System by clicking button. Important: Don t forget to copy data files to your USB flash memory stick! Notes for Hands-on Exercise 1 (Open Loop Control System) 7
8 3.2 Hands-on Exercise 2: Operation of On-Off Flow Control System Purpose The purpose of this hands-on exercise is to get familiar with an On-Off Flow Control System. Learning Objectives To operate the On-Off Flow Control System To perform settings of ON and OFF values to optimize the system response. Introduction The On-Off flow control system is based on the following principle: Error (E) = PV SP SP Error If E > 0 then OFF (large) CLOSE If E < 0 then ON (small) OPEN Controller Output PV Figure 5 On-Off control algorithm for the flow control system The CLOSE and OPEN values of the valve can be set at different values: Fully close: +10 V (in PC) or 20 ma Fully open: -10 V (in PC) or 4 ma SP, PV and CS in ma Manual Controller P and PV in litre/min Diagram Figure 6 On-Off flow control program (Front Panel) 8
9 Procedure (It is supposed that this exercise is started after Exercise 3.1, the On-Off Flow Controller Program is still open). Run the On-Off Flow Controller Program In MAN mode, confirm SP at 220 litre/min (fully open) and the valve is fully opened. Confirm the OPEN value at -10V, and the CLOSE value (fully open) at +10V (fully close). Switch to AUTO mode. The controller is working in the On-Off control mode. Observe the change in PV. Change the SP to 50% of the span, i.e. 120 lit/min (or 12mA), observe the change in PV. Change the OPEN value to -8V and the CLOSE value to +8V, and observe the change in PV. QUESTION 1 How is the system response changing? Select an OPEN value and a CLOSE value so that the system response hunts the set-point with the least oscillation. You may execute several trials to select appropriate valves. QUESTION 2 What are the best values? To stop the On-Off Controller Program click Close the On-Off Controller Program. button. Notes: Don t forget to copy data files to your USB flash memory stick! Notes for Hands-on Exercise 3.2 9
10 3.3 Hands-On Exercise 3: Operation of PID Control System Introduction The PID control system is based on the following principle: Error (E) = SP PV or PV SP SP Error de u PID = K e P + K edt K I + D dt Controller Output PV The PID controller program has the MAN mode similar to that of the On-Off controller program. In AUTO (closed-loop) mode, the PID controller can work in the following control actions: P only control by setting K i = 0 and K d = 0 I only control by setting K p = 0 and K d = 0 (rarely used for this flow system because I control action makes the system unstable) PI control by setting K d = 0 PD control by setting K i = 0 Control gains (Kp, Ki and Kd) are adjusted by on the following formula of the PID Control Algorithm: de VPID = K Pe + K I edt + K D dt Proportional Band is Integral Time: Derivative Time: P I D K T I = K 100% PB = K P P I K T D = K D P. The control signal is computed based 10
11 Figure 7 PID flow control program (Front Panel) Purpose The purpose of this hands-on exercise is to get familiar with the PID Flow Control System. Learning Objectives Operate the PID flow control system with different control actions: o P control o PI control o PD control o PID control Explain the effects of P, I, D, PI, PD and PID on the system response. Switch between the AUTO and MAN modes smoothly. Procedures (It is suggested that you have closed the On-Off Controller Program.) Run the PID Controller Program Confirm the PID Controller Program in MAN mode. Observe the SP, PV, Controller Output and confirm the following values (if not adjust accordingly): Setpoint: 220 lit/min K p = 2, K i = 0, K d = 0 (Proportional Only Control) Controller Output: -10V (4 ma) PV: 20 ma (220 lit/min) 11
12 Switch to the AUTO mode. The controller is working with Proportional Only Control. Proportional Only Control and Effects of Proportional Gains on System Response and Offset Wait until the system response is stable, fill in Table 1 Execute the Trials 1-10 and fill in Table 1. Table 1 Proportional Band Effect on OFFSET TRIAL K P PB SETPOINT MEAS. (PV) + OR - ERROR OUTPUT (Control Signal) QUESTION 1 How does the system response change when the Proportional Gain changes? Proportional and Integral Control Switch to the MAN and confirm the following value: Setpoint: 220 lit/min K p = 2, K i = 0, K d = 0 (Proportional Only Control) Controller Output: 2V (4 ma) PV: 20 ma (220 lit/min) Change the SP to 180 lit/min What is the error? (ma, lit/min) 12
13 What is the P action? (ma) Change K i to What is the I action? (ma) How is the PI action changing? (You can draw a diagram for I action) Stop the PID Controller Program. Start the PID Controller Program. What is the P action? (ma) How is the I action changing? (You can draw a diagram for I action) Change SP to 220 lit/min and K i = 0 (confirm K p = 2.0). Switch to the AUTO mode. Confirm the system is stable at SP of 220 l/min. Change SP to 180 lit/min. Wait until the system is stable. What is offset value? (ma, lit/min) Change K i to Observe the system response (PV). How does the PV change? Is the offset compensated? Change SP to 160 lit/min. Observe the system response (PV). How does the PV change? Change SP to 180 lit/min. Observe the system response (PV). How does the PV change? Change K i to 0.5. Observe the system response (PV). Change SP to 160 lit/min. Observe the system response (PV). How does the PV change? Change the following value: SP to 220 lit/min 13
14 K i to 0.0 K p to 2.0 Switch to the MAN mode. Stop the PID Control Program. Proportional and Derivative Control Run the PID Control Program in MAN mode. Confirm the following: K p = 2 K i = 0.0 K d = 0.0 SP = 220 lit/min Change K d to 2 and SP to 180 lit/min. Change SP to 160 lit/min How does the D action change? (You may change the Sampling Interval to 1 to observe the D action). Draw a diagram showing the D action. Change K d to 2 and SP to 220 lit/min. Wait until the system response is stable. Switch to AUTO Mode PD control Change the SP to 180 l/min, wait until the system response is stable. Change the SP to 160 l/min, wait until the system response is stable. Is the OFFSET compensated by PD control action? Stop the PID Control Program. Proportional plus Integral plus Derivative Control and AUTO/MAN Transfer From previous trial, change the following values: SP = 220 lit/min K p = 2 K i = K d = 2 AUTO/MAN = MAN Run the PID Control Program. Wait until the system is stable. Switch to the AUTO Mode PID Control Action. At this point, you have experienced with the effects of P, I, PI, PD actions. In this section, please do several trials in order to find some values of K p, K i and K d such that the system response has less oscillation and reaches the SP quickly. Change SP to 160 lit/min. How does the PV change? You can do several trials with different sets of K p, K i and K d. 14
15 You can also do several trials with transfer between AUTO/MAN modes when: o SP = PV o SP is different from PV Describe your observations: Conclusion At this point the following LOs have been met: Operate the PID flow control system with different control actions: o P control o PI control o PD control o PID control Explain the effects of P, I, D, PI, PD and PID on the system response. Switch between the AUTO and MAN modes smoothly. Notes: Don t forget to copy data files to your USB flash memory stick! 4. Calculation and Report In your report, do the following tasks (but not restricted to): Introduction Relevant theory on On-Off control Relevant theory on PID control Relevant theories related to level or flow transmitters/sensors and actuators Using AS Standard Drawing Symbols, draw a flow diagram for the above control system you have selected. Draw a block diagram for the closed-loop control system you have selected. Find transfer functions/sensitivities for all components of the systems. Hints: For the level control system the ODE for the tank is Ah & + k vh = q or in A h& + k v h = q in For the flow control system the ODE for the piping system (flow dynamics) is Qout K e Td s = Q Ts + 1 in Find the total feedback transfer function (refer to Chapter 15) Plot sketches and graphs (from data files) Discussions, evaluations and conclusions 15
16 Appendix 1 Flow Control Bench Global Valve Control Valve Rotameter D/P Cell I/O Converter Appendix 2 Block Diagram for On-Off Controller Program (flow control) 16
17 Appendix 3 Block Diagram of the PID Controller Program (flow control) 17
18 Lab 2 Process Control Computer-based Control Systems Level Control 1. Aims To operate PC-based instrumentation and control systems To get familiar with open-loop control, ON-OFF, and PID control systems To explain P, PI, PD, and PID control actions To transfer MAN mode to AUTO smoothly. 2. Apparatus Process/Plant: Process Control Trainer Cart with Level Control Mode of I/P Converter consists of a tank, a pneumatic control valve (with a pneumatic positioned), a D/P level transmitter, an orifice plate and D/P flow transmitter, pipes and pump, and a D/P pressure transmitter (not used in this experiment). Computer, LabVIEW 8.6, NI DAQ 6036E Card, Signal Conditioning SC-2345 (for level control) including a current-to-voltage converter (4mA-20mA to 1 to 5V, with two channels) and a voltage-to-current converter (0V-+10V to 0mA-20mA). A multimeter. 3 Connection Diagram The connection diagram for control systems is shown in Fig. 1 and Fig. 2b. Pneumatic supply Water supply I/P kpa Valve MI Process (Plant) PV Sensor/s Actuator CS 4-20mA V/I V V I/V MV 4-20mA PC, DAQ PCI 6036E and LabVIEW PC-based controller Figure 1 Connection diagram Scheme diagram for level control system is shown in Fig. 2 (also see Appendix 1). 4. Further Information Refer to Chapters 7, 8, 9 (Pressure, Flow and Level), Chapter 12 Actuators and Chapter 13 Basic Control Theory (Direct Acting On-Off Control, PID Control) 1
19 Air supply I/P converter 0-20mA kpa 0-10V AO-0 1-5V AI V Supply liquid 4-20mA Flow transmitter 4-20mA Orifice plate Level transmitter Pneumatic control valve Positioner q in (0-85% square root) Level m DAQ PCI 6036E, PC and LabVIEW AI-10 SC-2345 Isolation valve Valve 1 q out1 Valve 2 q out2 Figure 2a Schematic diagram for level control system I/P converter Air supply 0-20mA kpa (desired) Controller 0-10V AO-0 1-5V AI V FT Supply liquid 4-20mA DC 24V 4-20mA Pneumatic control valve LT Positioner q in (0-85% square root) Level m PC, DAQ PCI 6036E, and LabVIEW AI-10 SC-2345 DC 24V Isolation valve Figure 2b Connection diagram for level control system Valve 1 q out1 Valve 2 q out2 2
20 Methods 1. Connection and turning on the power Connect the computer, I/V converters, and V/I converter to the process (sensor/s and actuators) by referring to the above scheme/connection diagrams Supply control air (or confirm if the pneumatic supply is done) Turn on the power Log on to the computer 2. Identification of Components and Variables Identify all components and their variable of the process control system (that you have selected) and complete the following table. Table 1 Components and variables Process system: No 1 Component / Model Code (where applicable) Example: PC-based controller (Manual Controller) Input (variable, unit) Setpoint level [ma, V, mm] Measured level [ma, V, mm] Output (variable, unit) Control signal: [V] 2 V/I converter (SC-2345) Control signal: [V] Control signal: [ma] Hands-on Exercises 3.1 Hands-On Exercise 1: Getting Started with Open-Loop Level Control System Purpose: The purpose of this hands-on exercise is to get familiar with a control system and its components, variables and signals. In the Open Loop Control System there is no comparison of feedback signal to the Set Point. In almost controllers MAN mode is an Open Loop mode. Learning Objectives: Operate the open loop control system Understand components of the control system and their signals 3
21 Explain the principles and functions of the components including process, measurement devices (flow transmitters, level transmitter, pressure gauges), actuators, valves and valve positioner. Procedure Run the LabVIEW On-Off controller program C:\Documents and Settings\All Users\LabVIEW Data\JEE326_2009\Lab 2\OnOffLevelControl\ OnOffLevelControl01.exe The controller program is running. If not, click MAN (open-loop) mode. The controller program looks like... to run the On-Off Controller Program in Process variable: level Manual controller Flow rate Diagram Drain valves Figure 3 On-Off controller program in the Manual mode (for level control) Make sure that the Auto/Man mode switch is in Man position. Make sure that the Write to File is at Write position and change the path for data files if necessary Enter a minimum value of voltage, i.e. 0V, write down in Table 2 and Table 3. Change the value of voltage to 2V and then with a step of 1 volt and complete Table 2 and Table 3. 4
22 Table 2 Data collection for components and variables of open loop system No 0 1 Component and/or variable [unit] Examples: Controller (PC), control signal: V: ma Sym u c u c 0 0 Volt-to-Curr Converter, control signal [ma] u c I/P converter Air supply pressure kpa Output (pressure) kpa P 1 Positioner Instrument pressure Air supply pressure Output pressure Control valve Flow transmitter Tank P 2 P 3 P c 0 Table 3 Ranges of variables No Component / Instrument Open-loop (MAN) Controller 0 Example: I/P converter Input (range, unit) Output (range, unit) Min Max Min Max 0V 10V 0 ma 20mA Control signal Control pressure 0 20 ma 0 bar 1.2 bar 5
23 Label the components, variables and their ranges in the following block diagram. V/I S7 converter Indicators (Virtual Instruments) PC + Controller Air supply Disturbances S1 S2 S3 S4 S5 S6 C1 C2 C3 C4 Figure 4 Block diagram of the open-loop control system (for level control) 6
24 QUESTION 1 What type is the pneumatic control valve? QUESTION 2 When the Controller Output changes from 0% (4mA) to 50% (12mA) (of span) How much (%) does the Valve Opening change?... How much (%) does the Process Variable change?... Return the Controller Output to the minimum value. Stop the Open-Loop Control System by clicking button. Important: Don t forget to copy data files to your USB flash memory stick! Notes for Hands-on Exercise 1 (Open Loop Control System) 7
25 3.2 Hands-on Exercise 2: Operation of On-Off Level Control System Purpose The purpose of this hands-on exercise is to get familiar with an On-Off Control System. Learning Objectives To operate the On-Off Control System To perform settings of ON and OFF values to optimize the system response. Introduction The On-Off level control system is based on the following principle: Error (E) = SP PV SP Error If E > 0 then ON (large) OPEN If E < 0 then OFF (small) CLOSE Controller Output PV Figure 5 On-Off control algorithm for level control system Confirm ON (OPEN) and OFF (CLOSE) values of the control valve for your control system: ON (OPEN) Fully open: 10 V or 20 ma OFF (CLOSE) Fully close: 0 V or 0 ma Figure 6 Level controller program (Front Panel) 8
26 Procedure (It is supposed that this exercise is started after Exercise 3.1, the On-Off Level Controller Program is still open). Run the On-Off Level Controller Program In MAN mode, confirm SP at 400 mm and the valve is fully opened. If not, adjust the Manual Control to 10 V to fill water in the tank up to 400 mm. (Notes: There are two drain valves. One is fully closed, the other is half opened. If the tank is empty you may need to closed the half-opened valve, and then return it back to the half opening position when the water reaches 400 mm.) Confirm the OFF (CLOSE) value (fully close) at 0V, and the ON (OPEN) value (fully open) at 10V. Switch to AUTO mode. The controller is working in the On-Off control mode. Observe the change in PV. Change the SP to 50% of the span, i.e. 200 mm (or 12 ma), observe the change in PV. Change the OFF value to 2V (4 ma) and the ON value to 6V (12 ma), and observe the change in PV. QUESTION 1 How is the system response changing? Select an OPEN value and a CLOSE value so that the system response hunts the set-point with the least oscillation. You may execute several trials to select appropriate valves. QUESTION 2 What are the best values? To stop the On-Off Controller Program click Close the On-Off Controller Program. button. Important: Dot not forget to copy data files to your USB flash memory stick! Conclusion At this point, the learning objectives have been met. You are able to To operate the On-Off Control System To perform settings of ON and OFF values to optimize the system response. Notes for Hands-on Exercise 2 9
27 3.3 Hands-On Exercise 3: Operation of PID Control System Introduction The PID control system is based on the following principle: Error (E) = SP PV SP Error de u PID = K e P + K edt K I + D dt Controller Output PV Figure 7 PID control algorithm for the level control system The PID controller program has the MAN mode similar to that of the On-Off controller program. In AUTO (closed-loop) mode, the PID controller can work in the following control actions: P only control by setting K i = 0 and K d = 0 I only control by setting K p = 0 and K d = 0 (rarely used for this level system because I control action makes the system unstable) PI control by setting K d = 0 PD control by setting K i = 0 Control gains (K p, K i and K d ) are adjusted by on the following formula of the PID Control Algorithm: de VPID = K Pe + K I edt + K D dt Proportional Band is Integral Time: Derivative Time: P I D K T I = K 100% PB = K P P I K T D = K D P. The control signal is computed based Purpose The purpose of this hands-on exercise is to get familiar with the PID Control System. Learning Objectives Operate the PID level control system with different control actions: o P control o PI control o PD control o PID control Explain the effects of P, I, D, PI, PD and PID on the system response. Switch between the AUTO and MAN modes smoothly. 10
28 Figure 8 PID controller program (Front Panel) Procedures (It is suggested that you have closed the On-Off Controller Program.) Run the PID Controller Program Confirm the PID Controller Program in MAN mode. Observe the SP, PV, Controller Output and confirm the following values (if not, adjust accordingly): Setpoint: 200 mm K p = 2, K i = 0, K d = 0 (Proportional Only Control) Controller Output: 0V (0 ma) PV: 12 ma (200 mm) Switch to the AUTO mode. The controller is working with Proportional Only Control. Proportional Only Control and Effects of Proportional Gains on System Response and Offset Wait until the system response is stable, fill in Table 4. Execute the Trials 1-10 and fill in Table 4. 11
29 Table 4 Proportional Band Effect on OFFSET TRIAL K P PB SETPOINT MEAS. (PV) + OR - ERROR OUTPUT (Control Signal) QUESTION 1 How does the system response change when the Proportional Gain changes? Proportional and Integral Control Switch to the MAN and confirm the following value: Set-point: 200 mm K p = 2, K i = 0, K d = 0 (Proportional Only Control) PV: 12 ma (200 mm) (if not, adjust the Manual Control to 10V to fill water up to 200 mm. Switch to the Auto Mode. Wait until the level is stable. What is the error? (V, ma, mm) What is the P action? (V, ma) Change the SP to 180 mm What is the error? (V, ma, mm) What is the P action? (V, ma) Change K i to What is the P action? (ma) How is the PI action changing? (You can draw a diagram for I action) 12
30 Stop the PID Controller Program. Start the PID Controller Program. What is the P action? (ma) How is the I action changing? (You can draw a diagram for I action) Change SP to 200 mm and K i = 0 (confirm K p = 2.0). Switch to the AUTO mode. Wait until the system is stable. Change SP to 180 mm. Wait until the system is stable. What is offset value? (ma, mm) Change K i to Observe the system response (PV). How does the PV change? Is the offset compensated? Change SP to 160 mm. Observe the system response (PV). How does the PV change? Change SP to 180 mm. Observe the system response (PV). How does the PV change? Change K i to 0.5. Observe the system response (PV). Change SP to 160 mm. Observe the system response (PV). How does the PV change? Change the following value: SP to 200 mm K i to 0.0 K p to 2.0 Switch to the MAN mode. Stop the PID Control Program. 13
31 Proportional and Derivative Control Run the PID Control Program in MAN mode. Confirm the following: K p = 2 K i = 0.0 K d = 0.0 SP = 200 mm Change K d to 2 and SP to 180 mm. Change SP to 160 mm How does the D action change? (You may change the Sampling Interval to 1 to observe the D action). Draw a diagram showing the D action. Change K d to 2 and SP to 200 mm. Wait until the system response is stable. Switch to AUTO Mode PD control Change the SP to 180 mm, wait until the system response is stable. Change the SP to 160 mm, wait until the system response is stable. Is the OFFSET compensated by PD control action? Stop the PID Control Program. Proportional plus Integral plus Derivative Control and AUTO/MAN Transfer From previous trial, change the following values: SP = 200 mm K p = 2 K i = K d = 2 AUTO/MAN = MAN Run the PID Control Program. Wait until the system is stable. Switch to the AUTO Mode PID Control Action. At this point, you have experienced with the effects of P, I, PI, PD actions. In this section, please do several trials in order to find some values of K p, K i and K d such that the system response has less oscillation and reaches the SP quickly. Change SP to 160 mm. How does the PV change? You can do several trials with different sets of K p, K i and K d. You can also do several trials with transfer between AUTO/MAN modes when: o SP = PV o SP is different from PV 14
32 Describe your observations: Conclusion Operate the PID level control system with different control actions: o P control o PI control o PD control o PID control Explain the effects of P, I, D, PI, PD and PID on the system response. Switch between the AUTO and MAN modes smoothly. Notes: Don t forget to copy data files to your USB flash memory stick! 4. Calculation and Report In your report, do the following tasks (but not restricted to): Introduction Relevant theory on On-Off control Relevant theory on PID control Relevant theories related to level or level transmitters/sensors and actuators Using AS Standard Drawing Symbols, draw a level diagram for the above control system you have selected. Draw a block diagram for the closed-loop control system you have selected. Find transfer functions/sensitivities for all components of the systems. Hints: For the level control system the ODE for the tank is Ah& + k vh = qin For the flow control system the ODE for the piping system (flow dynamics) is Qout K e Td s = Q Ts + 1 in Find the total feedback transfer function (refer to Chapter 15) Plot sketches and graphs (from data files) Discussions, evaluations and conclusions 15
33 Appendix 1 Process Control Trainer Cart Tank Control valve Microprocessor-based controllers and chart recorders Valve positioner Pressure transmitter Level transmitter Flow transmitter I/P converter Process Control Trainer Cart Appendix 2 Block Diagram for On-Off Controller Program (level control) 16
34 Appendix 3 Block Diagram of the PID Controller Program (level control) 17
Cell Phone Vibration Experiment
Objective Cell Phone Vibration Experiment Most cell phones are designed to vibrate. But at what frequency do they vibrate? With an accelerometer, data acquisition and signal analysis the vibration frequency
More informationA Design of a PID Self-Tuning Controller Using LabVIEW
Journal of Software Engineering and Applications, 2011, 4, 161-171 doi:10.4236/jsea.2011.43018 Published Online March 2011 (http://www.scirp.org/journal/jsea) 161 A Design of a PID Self-Tuning Controller
More informationControl of an industrial process using PID control blocks in automation controller
Control of an industrial process using PID control blocks in automation controller by Michel Van Dessel 1 1 Abstract Many continuous industrial processes can be controlled using programmable automation
More informationIndustrial Steam System Process Control Schemes
Industrial Steam System Process Control Schemes This paper was developed to provide a basic understanding of the different process control schemes used in a typical steam system. This is however a fundamental
More informationA Study of Speed Control of PMDC Motor Using Auto-tuning of PID Controller through LabVIEW
A Study of Speed Control of PMDC Motor Using Auto-tuning of PID Controller through LabVIEW Priyanka Rajput and Dr. K.K. Tripathi Department of Electronics and Communication Engineering, Ajay Kumar Garg
More informationProcess Control Primer
Process Control Primer At the onset of the Industrial Revolution, processes were controlled manually. Men turned valves, pulled levers or changed switches based on the need to turn devices on or off. As
More informationIntroduction to LabVIEW for Control Design & Simulation Ricardo Dunia (NI), Eric Dean (NI), and Dr. Thomas Edgar (UT)
Introduction to LabVIEW for Control Design & Simulation Ricardo Dunia (NI), Eric Dean (NI), and Dr. Thomas Edgar (UT) Reference Text : Process Dynamics and Control 2 nd edition, by Seborg, Edgar, Mellichamp,
More informationLab 3: Introduction to Data Acquisition Cards
Lab 3: Introduction to Data Acquisition Cards INTRODUCTION: In this lab, you will be building a VI to display the input measured on a channel. However, within your own VI you will use LabVIEW supplied
More informationData Acquisition Using NI-DAQmx
Instructor s Portion Data Acquisition Using NI-DAQmx Wei Lin Department of Biomedical Engineering Stony Brook University Summary This experiment requires the student to use NI-DAQmx to acquire voltage
More informationHITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE
HITACHI INVERTER SJ/L1/3 SERIES PID CONTROL USERS GUIDE After reading this manual, keep it for future reference Hitachi America, Ltd. HAL1PID CONTENTS 1. OVERVIEW 3 2. PID CONTROL ON SJ1/L1 INVERTERS 3
More informationMicrocontroller-based experiments for a control systems course in electrical engineering technology
Microcontroller-based experiments for a control systems course in electrical engineering technology Albert Lozano-Nieto Penn State University, Wilkes-Barre Campus, Lehman, PA, USA E-mail: AXL17@psu.edu
More informationServo Motors (SensorDAQ only) Evaluation copy. Vernier Digital Control Unit (DCU) LabQuest or LabPro power supply
Servo Motors (SensorDAQ only) Project 7 Servos are small, relatively inexpensive motors known for their ability to provide a large torque or turning force. They draw current proportional to the mechanical
More informationINSTRUMENTATION AND CONTROL TUTORIAL 3 SIGNAL PROCESSORS AND RECEIVERS
INSTRUMENTATION AND CONTROL TUTORIAL 3 SIGNAL PROCESSORS AND RECEIVERS This tutorial provides an overview of signal processing and conditioning for use in instrumentation and automatic control systems.
More informationPID control - Simple tuning methods
- Simple tuning methods Ulf Holmberg Introduction Lab processes Control System Dynamical System Step response model Self-oscillation model PID structure Step response method (Ziegler-Nichols) Self-oscillation
More informationOperational Overview and Controls Guide
DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)
More informationQNET Experiment #06: HVAC Proportional- Integral (PI) Temperature Control Heating, Ventilation, and Air Conditioning Trainer (HVACT)
Quanser NI-ELVIS Trainer (QNET) Series: QNET Experiment #06: HVAC Proportional- Integral (PI) Temperature Control Heating, Ventilation, and Air Conditioning Trainer (HVACT) Student Manual Table of Contents
More informationGas Custody Transfer Calibration
Gas Custody Transfer Calibration Using multi variable temperature / pressure calibrators for flowmeter calibration 2013 Introduction Gas custody transfer flow computers require special calibration to perform
More informationAutomation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
More informationSECTION 5 Examples of Function Block Combinations
SECTION 5 Examples of Function Block Combinations 5-1 BASIC EXAMPLES OF CONTROL... 152 5-1-1 Simple Control... 152 5-1-2 Multi-channel Control... 153 5-1-3 Control for Switching Multiple Set Points...
More informationT0118 T2118 T3118. Instruction Manual
Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity
More informationOEM-EP Pressure Controllers
Pressure Controllers Typical Applications Carrier Gas Pressure Control Air over Liquid Control Mass Spectrometer Process Gas Supply Pressure Control Miniature ler The Miniature ler converts a variable
More information8500 Installation/Start-up/Operation Lit # 8500 OP
8500 Installation/Start-up/Operation Lit # 8500 OP K SYSTEM CORPORATION INVENTORY SYSTEM GENERAL DESCRIPTION The K SYSTEM TANK INVENTORY CONTROL SYSTEM, #8600C Series, provides an extremely accurate method
More informationInstrumentation and Process Control. Boiler Control. Courseware Sample 85993-F0
Instrumentation and Process Control Boiler Control Courseware Sample 85993-F0 A INSTRUMENTATION AND PROCESS CONTROL BOILER CONTROL Courseware Sample by the staff of Lab-Volt Ltd. Copyright 2010 Lab-Volt
More informationTemperature Transmitter TTX300
coo Interface Description COM/TTX300/FF-EN Temperature Transmitter TTX300 FOUNDATION Fieldbus Contents Blinder Text Temperature Transmitter TTX300 Interface Description COM/TTX300/FF-EN 01.2010 Manufacturer:
More informationLab 4 - Data Acquisition
Spring 11 Lab 4 - Data Acquisition Lab 4-1 Lab 4 - Data Acquisition Format This lab will be conducted during your regularly scheduled lab time in a group format. Each student is responsible for learning
More informationImplementing PID Temperature Control Using LabVIEW. Abstract. Introduction
Implementing PID Temperature Control Using LabVIEW Carlton Prewit, Rafic Bachnak Department of Computing and Mathematical Sciences Texas A&M University Corpus Christi Session XXXX Abstract Feedback control
More informationPositioner Versions. Remote feed-back. Local display, Electric / Hydraulic. Remote feed-back Electric / Hydraulic. Embedded Control Positioner
Quick Stepper 3G ECP Positioner Versions Mechanical feed-back Pneumatic Remote feed-back Local display, Pneumatic Remote feed-back Local display, Electric / Hydraulic Remote feed-back Electric / Hydraulic
More informationTLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR
TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.
More informationUSB-500 Series Stand-Alone, Low-Cost Data Loggers
Stand-Alone, Low-Cost Data Loggers Features Stand-alone, remote data loggers Measure temperature, humidity, voltage, or current 1 or 2 channels Low cost, small size Battery powered Software Included, easy-to-use
More informationCod. Documento: RT2014-0515a Title: Fimer Plant Controller Description. Rev. Data Redatto Approvato. 00 15-9-2014 S.Sidoti A.
Pag 1 di 19 SCOPE The main purpose of the Fimer Plant Controller is make possible to the Grid Operator both remote and local control capability over an entire PV plant from a single control point The Fimer
More informationEVAL-UFDC-1/UFDC-1M-16
Evaluation Board for Universal Frequency-to- Digital Converters UFDC-1 and UFDC-1M-16 EVAL-UFDC-1/UFDC-1M-16 FEATURES Full-Featured Evaluation Board for the Universal Frequency-to-Digital Converters UFDC-1
More informationDevice Management Jonas Berge Emerson Process Management
Device Management Jonas Berge Emerson Process Management 1 Topics What is intelligent device management? Integrated operations Why do I need a handheld field communicator? With fieldbus, I can do everything
More informationDigital inductive conductivity transmitter
Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
More informationTerminology and Symbols in Control Engineering
Technical Information Terminology and Symbols in Control Engineering 1 Part 1 Fundamentals Technical Information Part 1: Fundamentals Part 2: Self-operated Regulators Part 3: Control Valves Part 4: Communication
More informationAutomotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim
Automotive sensor simulator Operating manual AutoSim Contents Introduction.. page 3 Technical specifications.... page 4 Typical application of AutoSim simulator..... page 4 Device appearance... page 5
More informationSHENZHEN JUNSI ELECTRONIC CO.,LTD
Cell Voltage Monitor&Logger USER S MANUAL SHENZHEN JUNSI ELECTRONIC CO.,LTD Thank you for purchasing the. Please read the entire User s Manual completely and attentively as it contains a wide variety of
More informationLab 2 Sensor Modeling Introduction to the Wiimote and the Wiimote LABVIEW Interface
Lab 2 Sensor Modeling Introduction to the Wiimote and the Wiimote LABVIEW Interface 1. Objective In this lab, you will: i. Become familiar with the Wiimote ii. Understand the LABVIEW Bluetooth interface
More informationA simple method to determine control valve performance and its impacts on control loop performance
A simple method to determine control valve performance and its impacts on control loop performance Keywords Michel Ruel p.eng., Top Control Inc. Process optimization, tuning, stiction, hysteresis, backlash,
More informationIndicators. and Alarm Units. World class accuracy with clear, user friendly, operator interfaces. Control Optimise Simplify
Indicators and Alarm Units World class accuracy with clear, user friendly, operator interfaces Control Optimise Simplify Control Optimise Simplify Easy to use technology so powerful it s simple 2 Indicators
More informationUniversal Simple Control, USC-1
Universal Simple Control, USC-1 Data and Event Logging with the USB Flash Drive DATA-PAK The USC-1 universal simple voltage regulator control uses a flash drive to store data. Then a propriety Data and
More informationHigh Power Programmable DC Power Supplies PVS Series
Data Sheet High Power Programmable DC Power Supplies The PVS10005, PVS60085, and PVS60085MR programmable DC power supplies offer clean output power up to 5.1 kw, excellent regulation, and fast transient
More informationElectro-Pneumatic Bus Door Control Mechanism
Electro-Pneumatic Bus Door Control Mechanism Application and Feature 1. Pneumatic Door Mechanism actuates the open/close movements of bus door through two double acting cylinders and two linkages with
More informationConversion Between Analog and Digital Signals
ELET 3156 DL - Laboratory #6 Conversion Between Analog and Digital Signals There is no pre-lab work required for this experiment. However, be sure to read through the assignment completely prior to starting
More informationContents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
More informationGRUNDFOS INSTRUCTIONS. CR Monitoring. Installation and operating instructions
GRUNDFOS INSTRUCTIONS CR Monitoring Installation and operating instructions Declaration of Conformity We Grundfos declare under our sole responsibility that the product CR Monitor, to which this declaration
More informationHow to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers.
How to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers. OMEGALOG Help Page 2 Connecting Your Data Logger Page 2 Logger Set-up Page 3 Download Data Page 8 Export Data Page 11 Downloading
More informationInwall Room Temperature Unit
Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall
More informationGuidelines for operation of minimum flow control valves
Guidelines for operation of minimum flow control valves Holter Regelarmaturen GmbH & Co KG Helleforthstr. 58-60 D-33758 Schloß Holte-Stukenbrock 05/2005 List of contents I. Minimum flow control valves...
More informationSystem Modeling and Control for Mechanical Engineers
Session 1655 System Modeling and Control for Mechanical Engineers Hugh Jack, Associate Professor Padnos School of Engineering Grand Valley State University Grand Rapids, MI email: jackh@gvsu.edu Abstract
More informationGENERAL SCIENCE LABORATORY 1110L Lab Experiment 6: Ohm s Law
GENERAL SCIENCE LABORATORY 1110L Lab Experiment 6: Ohm s Law OBJECTIVES: To verify Ohm s law, the mathematical relationship among current, voltage or potential difference, and resistance, in a simple circuit.
More informationDr. Yeffry Handoko Putra, S.T., M.T
Tuning Methods of PID Controller Dr. Yeffry Handoko Putra, S.T., M.T yeffry@unikom.ac.id 1 Session Outlines & Objectives Outlines Tuning methods of PID controller: Ziegler-Nichols Open-loop Coon-Cohen
More informationVibration Monitoring System Adash 3600
" User's guide Application: Vibration Monitoring System Adash 3600! Vibration diagnostics, monitoring and protective on-line system! On-line vibration monitoring system of engines, fans, pumps, gearboxes,
More informationEvent recording (or logging) with a Fluke 287/289 Digital Multimeter
Event recording (or logging) with a Fluke 287/289 Digital Multimeter Application Note One of the major features of the Fluke 280 Series digital multimeters (DMM) with TrendCapture is their ability to record
More informationNOVA MULTI-MONITORING SOFTWARE. Instruction Manual
NOVA MULTI-MONITORING SOFTWARE REMOTE OPERATION Precision Digital Corporation s Nova Multi-Monitoring software allows for the operation of common Nova control features remotely from a PC. Up to 30 Nova
More informationMeasurement Products. PID control theory made easy Optimising plant performance with modern process controllers
Measurement Products PID control theory made easy Optimising plant performance with modern process controllers 1. What are the main types of control applications? Introduction Accurate control is critical
More informationUSB-500 Series Low-Cost Data Loggers and Accessories
Low-Cost Data Loggers and Accessories Features Stand-alone, remote data loggers and portable logger assistant Measure temperature, humidity, voltage, current, or event/state change 1 or 2 channels Low
More informationT-BOXN12R. First steps with T-BOXN12R. You can make it wireless. Date: 2004-07-16 Version 1.0
T-BOXN12R You can make it wireless First steps with T-BOXN12R Date: 2004-07-16 Version 1.0 Content 1. Purpose of this document... 3 2. T-BoxN12R overview... 4 3. First step... 5 3.1. Preparing your workshop
More informationRVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions
RVR Hybrid System Controller Installation Instructions 1 Introduction to Hybrid Systems The RVR Hybrid system uses a combination of the Immergas Audax range of heat pumps with gas or oil boilers to create
More informationUM-X Field display for continous level sensors
Technical Documentation Field display for continous level sensors 10/2007 Edition: 1 Item No.: 207120 FAFNIR GmbH Bahrenfelder Str. 19 D-22765 Hamburg Telephone: +49 (0)40-39 82 07-0 Fax: +49 (0)40-3 90
More informationTransmitter Interface Program
Transmitter Interface Program Operational Manual Version 3.0.4 1 Overview The transmitter interface software allows you to adjust configuration settings of your Max solid state transmitters. The following
More informationPID Control. Chapter 10
Chapter PID Control Based on a survey of over eleven thousand controllers in the refining, chemicals and pulp and paper industries, 97% of regulatory controllers utilize PID feedback. Desborough Honeywell,
More informationChilled Water Valves: Resizing and Tuning for Peak Performance. IDEA Conference Feb. 2008 Jay Russell, PE University of Michigan
Chilled Water Valves: Resizing and Tuning for Peak Performance IDEA Conference Feb. 2008 Jay Russell, PE University of Michigan Overview Introduction Discussion of Chilled Water (CHW) Control Valve Selection
More informationPC Software for VAV compact and modular controllers
s 5 854 OpenAir PC Software for VAV compact and modular controllers ACS941 for use with GDB/GLB/ASV181 For Version 3.02 The ACS941 software is used for setting and displaying the parameter values with
More informationTemperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual
Ⅰ. Warn Warning of connection Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual If the controller fails to operate or error occurs, the system will bring fault for it, please
More informationFUNDAMENTALS OF CONTROL ENGINEERING
EQUIPMENT FOR ENGINEERING EDUCATION EQUIPMENT FOR ENGINEERING EDUCATION ENGINEERING MECHANICS & MACHINE ELEMENTS Statics Strength of Materials Dynamics Fundamentals of Engineering Design Machinery Diagnosis
More informationInput signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C
F4 Process Controller Installation and Operation Guide SAFETY ALERTS The symbols below are used on the equipment and throughout this document to draw the user s attention to important operational and safety
More informationCurrent Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015
Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) The standard tuning values used in ADVANCED Motion Controls drives are conservative and work well in over 90%
More informationGETTING STARTED. 6. Click the New Specimen icon.
BD FACSDiva Software Basic Experiment Guide Please note, this guide is not intended to take the place of in-person training but is to be used as a reference as needed after completing training with Unified
More informationABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
More informationHow To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
More informationSchematic Symbols Chart (Design Hydraulic and Pneumatic circits)
Page 1 of 6 (Home) Symbols / Visit us on: Fluid Power, Automation and Motion Control for all Industries About Us Products Services Catalogs Place an Order Training & Information Contact Us Employee Access
More informationPID Controller Tuning: A Short Tutorial
PID Controller Tuning: A Short Tutorial Jinghua Zhong Mechanical Engineering, Purdue University Spring, 2006 Outline This tutorial is in PDF format with navigational control. You may press SPACE or, or
More informationComputer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC
Technical Teaching Equipment Computer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC Teaching Technique used EDIBON SCADA System 2 Control Interface Box 5 Cables and Accessories 6 Manuals 3
More informationAutomation and Systems Technology. LABCONTROL TFM/TPM User Manual TroxMConnect Operating Software. 1. Introduction 1. 2. Software Installation 2
1. Introduction 1 2. Software Installation 2 2.1 System Requirements 2 2.2 TroxMConnect Installation 2 2.3 Connection to the PC 3 3. TroxMConnect Description 4 3.1 Starting the Software 4 3.2 Layout 4
More informationController Design using the Maple Professional Math Toolbox for LabVIEW
Controller Design using the Maple Professional Math Toolbox for LabVIEW This application demonstrates how you can use the Maple Professional Math Toolbox for LabVIEW to design and tune a Proportional-Integral-Derivative
More informationEvaluation copy. Build a Temperature Sensor. Project PROJECT DESIGN REQUIREMENTS
Build a emperature Sensor Project A sensor is a device that measures a physical quantity and converts it into an electrical signal. Some sensors measure physical properties directly, while other sensors
More informationIndustrial Automation Training Academy. PLC, HMI & Drives Training Programs Duration: 6 Months (180 ~ 240 Hours)
nfi Industrial Automation Training Academy Presents PLC, HMI & Drives Training Programs Duration: 6 Months (180 ~ 240 Hours) For: Electronics & Communication Engineering Electrical Engineering Instrumentation
More informationOperational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives
DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)
More informationWEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK
WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue
More informationMulti-Range Programmable DC Power Supplies 9115 Series
Data Sheet 1200 W Multi-Range DC Power Supplies Features & Benefits Any 9115 series model can replace several supplies on your bench or in your rack. Unlike conventional supplies with fixed output ratings,
More informationREMOTE LABORATORY PLANT CONTROL
REMOTE LABORATORY PLANT CONTROL HALÁS Rudolf, ĎURINA Pavol Institute of Information Engineering, Automation and Mathematics Faculty of Chemical and Food Technology Slovak University of Technology in Bratislava,
More informationBEIJING EPSOLAR TECHNOLOGY CO.,LTD.
WITH TWO BATTERY CHARGING EPSOLAR s duo-battery charging solar controller, For RVs, Caravans,and boats. Adjust options: 1. Battery type selection. 2. Two battery charging priority(from 0-100%) 3. Charging
More informationD-MAX WEB GUIDE CONTROLLER WITH OPERATOR INTERFACE PANEL QUICK START SETUP MANUAL
1/1 D-MAX.D1 1A Manual S1 D-MAX OPERATOR INTERFACE (Application Home Screen Is Shown) D-MAX CONTROLLER 04/14/2008 2008 Fife Corporation. All rights reserved. Figure Sheet 2-249 This page is intentionally
More information6.2.2 TECHNICAL ARGUMENTS FOR OWN SCADA AND OWN SCADA WITH PID CONTROL.
1/9 www.edibon.com Ref: 6.2.2 TECHNICAL ARGUMENTS FOR OWN SCADA AND OWN SCADA WITH PID CONTROL. About 600 units in EDIBON product range are considered as advanced units. Why do we consider them advanced
More informationINDUSTRIAL AUTOMATION Interactive Graphical SCADA System INSIGHT AND OVERVIEW. IGSS Online Training. Exercise 8: Creating Templates
INDUSTRIAL AUTOMATION Interactive Graphical SCADA System INSIGHT AND OVERVIEW IGSS Online Training Exercise 8: Creating Templates Exercise: Create Templates and Template Based Objects Purpose Learn how
More informationRDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
More informationInwall 4 Input / 4 Output Module
Inwall 4 Input / 4 Output Module IO44C02KNX Product Handbook Product: Inwall 4 Input / 4 Output Module Order Code: IO44C02KNX 1/27 INDEX 1. General Introduction... 3 2. Technical data... 3 2.1 Wiring Diagram...
More informationProduct data sheet. JUMO MIDAS Pressure Transmitter. Sales No. Order code JUMO AS 40.1001 401001/000-459-405-502-20-601-61
Produktdatenblatt - JUMO MIDAS Pressure Transmitter JUMO AS Street address: Solheimveien 50, 1470 Lørenskog, Norway Phone: +47 67 97 37 10 Delivery address: Solheimveien 50, 1470 Lørenskog, Norway Fax:
More informationImplementation of Fuzzy and PID Controller to Water Level System using LabView
Implementation of Fuzzy and PID Controller to Water Level System using LabView Laith Abed Sabri, Ph.D University of Baghdad AL-Khwarizmi college of Engineering Hussein Ahmed AL-Mshat University of Baghdad
More informationMeasuring, Controlling and Regulating with labworldsoft
Kai-Oliver Linde IKA-Werke Staufen Neumagenstraße 27 79219 Staufen Measuring, Controlling and Regulating with labworldsoft Rapid and easy networking of lab devices from different manufacturers The user
More informationProcess controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line
BT. 2.9 M/E Process controller programmer /6 DIN - 48 x 48 mm gammadue series M line Advanced features, customizable and process adaptable High speed data aquisition and signal management. Efficent information
More informationRackmount Intelligent Pressure Scanners
Rackmount Intelligent Pressure Scanners NetScanner System 9816/98RK-1 FEATURES ±0.05% Accuracy 100 Hz EU Throughput Autonegotiating 10/100/1G Base T Ethernet - TCP and UDP Protocol Pressure Ranges up to
More informationLambda Tuning the Universal Method for PID Controllers in Process Control
Lambda Tuning the Universal Method for PID Controllers in Process Control Lambda tuning gives non-oscillatory response with the response time (Lambda) required by the plant. Seven industrial examples show
More informationPhocos CXCOM for CX and CXN Instruction Manual
Phocos CXCOM for CX and CXN Instruction Manual Contents 1. System Requirements...3 2. Setting up the Phocos CX/CXN Charge Controller Menu... 4 3. Installing the Drivers for the Phocos CXI... 6 4. Installing
More informationR001. Room Control Unit TG650. Summary. Control functions. Orders. Planning. Installation
R001 Room Control Unit TG650 Summary TG650 Microprocessor Room Control Unit is designed to manage and control hotel room services. The Room Unit automatically manages the electric system validation on
More informationVP23, 3-way proportional pressure control valves Seat valve with μp-driven pressure control
VP, -way proportional pressure control valves > > Port size: G/... G/ > > All-digital control electronics > > Variable pressure control > > Optional actuation via fieldbus (separate datasheet on request)
More informationUSB-AD16f Data acquisition system (USB)
Data acquisition system (USB) Measurement & Control. Extremely powerful. Precisely record and output signals with the USB-AD16f: The high-performance USB data acquisition system accomodated in a stable
More informationInstruction Manual. T3111 T3111L T3111P T3111Ex
www.cometsystem.cz Instruction Manual T3111 T3111L T3111P T3111Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with external probe and 4-20 ma outputs
More informationLab 5 Getting started with analog-digital conversion
Lab 5 Getting started with analog-digital conversion Achievements in this experiment Practical knowledge of coding of an analog signal into a train of digital codewords in binary format using pulse code
More informationSplit Controller. User Manual SM-SS-F 2009/01/04
Split Controller SM-SS-F User Manual 2009/01/04 Table of contents 1. Parts illustration.... 1 2. Electrical technical data...... 2 3. Electrical connection...3 4. Assemble parts...4 4.1 Assemble the fixed
More information