Powertech Labs Inc th Ave., Surrey, B.C. Canada V3W 7R7 POWERTECH LABS INC.

Size: px
Start display at page:

Download "Powertech Labs Inc th Ave., Surrey, B.C. Canada V3W 7R7 POWERTECH LABS INC."

Transcription

1 POWERTECH LABS INC. ELECTRICAL ASSESSMENT OF ULTRA HIGH PERFORMANCE FIBRE REINFORCED CEMENTITIOUS COMPOSITE CROSS ARMS FOR 230 KV WOOD POLE TRANSMISSION LINES Project December 2009 January 2009 Prepared for: Lafarge Canada Inc. ABSTRACT: Electrical tests were done on ultra high performance fibre reinforced cementitious composite cross arms for 230 kv wood pole transmission lines. The electrical properties are very comparable to conventional wood cross arms. The one area of concern is the damage to the material during the lightning impulse tests. It was recommended the impact of this damage on the mechanical properties of the material be investigated. Subsequent to the Powertech tests structural tests were carried out by the University of Calgary on the damaged cross arm. A copy of the University of Calgary report is included as Appendix A. Tested by: Prepared by: R.G. Pollock Senior Technologist, High Voltage Lab A.J. Vandermaar, P. Eng. Manager, High Voltage Lab Project No: Page 1 of 24

2 TABLE OF CONTENTS 1.0 SUMMARY BACKGROUND PROJECT OBJECTIVES TEST PROCEDURE Test Setup AC Voltage Partial Discharge Tests AC Voltage Flashover Tests Lightning Impulse Voltage Flashover Tests Dielectric Strength Tests Tracking Wheel Test TEST RESULTS Test Date AC Voltage Partial Discharge Tests AC Voltage Flashover Tests Lightning Impulse Voltage Flashover Tests Dielectric Strength Tests AC Voltage Dielectric Strength Tests Lightning Impulse Voltage Dielectric Strength Tests Tracking Wheel Test DISCUSSION OF RESULTS CONCLUSIONS...22 APPENDIX A University of Calgary Report Project No: Page 2 of 24

3 1.0 SUMMARY Electrical tests were done on 9 m long ultra high performance fibre reinforced cementitious composite cross arms for 230 kv wood pole transmission lines. The cross arms were simultaneously tested in a cross brace configuration. The partial discharge on the test assembly did not exceed 20 pc at 120 % of rated maximum operating voltage (169.7 kv) with and without the hardware (metal parts) grounded. AC flashovers to the surface and across the surface caused no visible damage to the reinforced cementitious composite material. Lightning impulse flashovers across the surface also caused no visible damage to the material. Lightning impulse flashovers to the surface did cause spalling, punctures through the material and visible cracks of unknown depth. It is recommended that the effect of the potential damage that could be done by AC fault currents or lightning impulse on the mechanical strength of the reinforced cementitious composite material be investigated. Subsequent to the Powertech tests structural tests were carried out by the University of Calgary on the damaged cross arm. A copy of the University of Calgary report is included as Appendix A. The power-frequency and the lightning impulse dielectric strength of the reinforced cementitious composite material exceeded the strength of wood samples. The samples passed the tracking and erosion test on the tracking wheel with no damage to the reinforced cementitious composite material. The electrical properties are very comparable to conventional wood cross arms. For structures with un-bonded hardware the slight conductivity of the material is a good feature. This means that under normal operating conditions there will be good voltage grading between the insulators and the transmission line structure. 2.0 BACKGROUND It is proposed to use ultra high performance fibre reinforced cementitious composite cross arms manufactured by Lafarge Canada Inc., on 230 kv Transmission Lines as a replacement for wooden cross arms and potentially to also replace cross braces. The fibre reinforced cementitious cross arms contain no metal. Since the cross arms are exposed to an electric field the effect of the electric field should be considered. The electric field could cause partial discharge within the cross arms. Over an extended period in-service this can cause external or internal damage and eventual failure of the cross arms. There is also concern as to what the impact of AC flashovers and lightning strikes would have on the cross arms. If this material were used as cross braces the same concerns would apply. Project No: Page 3 of 24

4 To study these effects tests were conducted on the fibre reinforced cementitious composite cross arms and on material samples. Figure 1 shows a manufacturer drawing and Figure 2 and 3 show the cross arms tested. Figure 1 Ultra high performance fibre reinforced cementitious composite cross arms Project No: Page 4 of 24

5 Figure 2 Ultra high performance fibre reinforced cementitious composite cross arms Figure 3 Ultra high performance fibre reinforced cementitious composite cross arms Project No: Page 5 of 24

6 3.0 PROJECT OBJECTIVES The objectives of this project were to: Determine if there is damaging internal partial discharge (PD) on the fibre reinforced cementitious concrete members under operating conditions. Evaluate the effect of AC flashovers on the cross arms by initiating low energy flashovers to the cross arms and across the cross arms. Evaluate the effect of lightning impulses applied to the cross arms and across the surface of the cross arms. Evaluate the ability of the ultra high performance fibre reinforced cementitious composite cross arms/cross braces to withstand long term electrical stress over the surface. Evaluate the dielectric strength of the fibre reinforced cementitious members compared to wooden members. 4.1 Test Setup 4.0 TEST PROCEDURE Two 9 m long ultra high performance fibre reinforced cementitious composite cross arms were mounted back to back on 14 x 4 x 38 timbers to simulate the mounting arrangement on a 230 kv wood pole structure. A second pair of ultra high performance fibre reinforced cementitious composite cross arms were used as cross braces on the simulated structure. A 230 kv insulator was suspended from the center of the cross arms to simulate the centre phase of a 230 kv circuit. A conductor was suspended from this insulator at right angles to the cross arms. The complete assembly was suspended from insulators in the High Voltage Laboratory. The test setup is shown in Figure 4 and Figure 5. Project No: Page 6 of 24

7 Figure 4 Test Setup Project No: Page 7 of 24

8 4.2 AC Voltage Partial Discharge Tests Figure 5 Test Setup The conductor was energized to expose the cross arms to the electric field they would experience in-service. The partial discharge (PD) was measured as a function of the applied voltage. The partial discharge tests were done in three configurations as follows: with all metal hardware floating (not electrically bonded to ground or electrically bonded together), with the lower metal hardware (bolts) on the cross braces electrically connected to ground, with all metal parts (cross brace mounting hardware, cross arm mounting hardware and insulator ground end hardware) electrically connected to ground. Project No: Page 8 of 24

9 The cross arms and cross braces were examined with an image intensifier during the tests for visible external discharge and with an acoustic ultrasonic detector for audible partial discharge. This was done to eliminate external corona as the source of any measured partial discharge. 4.3 AC Voltage Flashover Tests A minimum of twenty AC flashovers were initiated from the energized AC conductor to the cross arms to obtain data on the effect of AC flashovers on the cross arms. The test was done at voltages up to 350 kv. A minimum of twenty AC flashovers were also initiated lengthwise over the surface of one of the cross arm over a distance of 30 cm. For the surface flashover two strips of copper tape were applied to the surface of the crossarms at the 30 cm spacing. One copper strip was energized and the other strip was grounded. Note: The energy available from the AC test source is relatively low so it is expected that the flashovers would cause minimal damage. 4.4 Lightning Impulse Voltage Flashover Tests The previously energized AC conductor was connected to the lightning impulse generator and twenty lightning flashovers (1.1/48 µs waveform) were initiated to the cross arms to obtain data on the effect of lightning on the cross arms. The test was done at voltages up to 1.6 MV. Twenty lightning impulse flashovers were also initiated lengthwise over the surface of one of the cross arms over a distance of 30 cm. This was done over the same surface as used for the AC surface flashovers. 4.5 Dielectric Strength Tests The power-frequency (AC) and lighting impulse material dielectric strength was determined for the ultra high performance fibre reinforced cementitious composite cross arms material. For comparison normal Douglas Fir used for wood pole transmission line structures were also tested. Insulation samples were tested by placing 1 inch diameter electrodes on opposite sides of the test sample. For the AC tests the test voltage was applied to the electrodes and ramped up to sample breakdown. For the lighting impulse test standard 1.2/50 µs waveforms were applied to the test electrodes starting at a voltage below the expected breakdown voltage. The applied impulse voltage was increased in steps up to sample breakdown. 4.6 Tracking Wheel Test Samples of the ultra high performance fibre reinforced cementitious composite cross arms material were tested in accordance with CEA Purchasing Specification LWIWG- Project No: Page 9 of 24

10 03(96), Clause 5.4, tracking and erosion test, with the exception that only the post power frequency test was done i.e. no steep front test. Four 28.5 cm x 9.5 cm x 12 mm samples with 1.9 cm holes drilled in the samples at a 22.9 cm center to center spacing were mounted on the tracking wheel. On one of the samples the cut ends of the sample cut hole edges were sealed with epoxy. This was done to evaluate if sealing cut edges would have any impact on tracking performance. The other three samples were tested as received. Electrodes were attached so the was a distance of 20 cm between the ground and high voltage electrode the samples. The four tested samples were subjected to the aging process on a tracking wheel for 330 hours using Test Method 1. The minimum applied test voltage was 8.1 kv rms (leakage distance of 230 mm and minimum stress of 35 V/mm). The salinity of the water was 0.22 grams/litre. After every four days of testing there was a rest period of 24 hours, when the samples were not sprayed. The total test duration, including the rest periods was 402 hours. Test evaluation: no tracking, no erosion to the core and no coating puncture may occur. 5.0 TEST RESULTS 5.1 Test Date 18 December 2009 to 20 January AC Voltage Partial Discharge Tests Table 1 gives the partial discharge results with all metal hardware floating (not electrically bonded to ground or electrically bonded together). Table 1 Partial Discharge Test with all Metal Hardware Floating Voltage (kv) Partial Discharge (pc) Comments 100 < <1 Rated operating voltage <1 Rated maximum operating voltage x rated operating voltage x rated maximum operating voltage x rated operating voltage x rated maximum operating voltage 236 >1000 inception voltage Extinction voltage Project No: Page 10 of 24

11 Table 2 Partial Discharge Test with the Lower Bolts) on the Cross Braces Electrically Connected to Ground Voltage (kv) Partial Discharge (pc) Comments 100 < Rated operating voltage Rated maximum operating voltage x rated operating voltage x rated maximum operating voltage x rated operating voltage x rated maximum operating voltage 240 >1000 inception voltage extinction voltage Table 3 gives the partial discharge test results with all metal parts (cross brace mounting hardware cross arm mounting hardware and insulator ground end hardware) electrically connected to ground. Table 3 Partial Discharge Test with all Metal Parts Grounded Voltage (kv) Partial Discharge (pc) Comments 100 < Rated operating voltage Rated maximum operating voltage x rated operating voltage x rated maximum operating voltage x rated operating voltage x rated maximum operating voltage 239 >1000 inception voltage extinction voltage The cross arms were examined with an image intensifier for visible external discharge in all the test configurations. No external discharge was observed. 5.3 AC Voltage Flashover Tests The flashover to the surface and across the surface had no visible effect. Figures 6 shows the gap that was used for the flashovers across the surface and figure 7 shows surface flashover. Project No: Page 11 of 24

12 Figure 6 Surface Flashovers Gap Figure 7 Surface Flashover Project No: Page 12 of 24

13 5.4 Lightning Impulse Voltage Flashover Tests The flashovers to the surface caused spalling, punctures and visible cracks on the cross arm web. Figure 8 shows a flashover to the surface. Figures 9 and 10 show the damage caused by the flashovers. The flashovers over the surface had no visible effect. Figure 8 Lightning Impulse Flashover to the Surface Project No: Page 13 of 24

14 Figure 9 Lightning Impulse Flashovers Damage to the Web Figure 10 Lightning Impulse Flashovers Damage to the Web Project No: Page 14 of 24

15 5.5 Dielectric Strength Tests AC Voltage Dielectric Strength Tests The results of the AC dielectric strength tests are given in Tables 5 and 6. Sample No. Table 5 Fibre Reinforced Cementitious Samples Puncture Voltage (kv) Thickness (mm) Dielectric Strength (V/mm) Comments 874-A Smooth surface 874-A Smooth surface 874-A Smooth surface with some roughness 874-A Smooth surface 874-A Smooth surface 874-A Smooth surface with some roughness 874-A Smooth surface 874-A Smooth surface 874-A Rough surface 874-A Rough surface 874-A Smooth surface 874-A Smooth surface Average Table 6 Wood Samples Sample No. Puncture Voltage (kv) Thickness (mm) Dielectric Strength (V/mm) A A A A B B Comments see Note below Old cross arm material tested parallel to the wood grain Old cross arm material tested parallel to the wood grain Old cross arm material tested across the wood grain Old cross arm material tested across the wood grain Old cross arm material tested parallel to the wood grain Old cross arm material tested across the wood grain Project No: Page 15 of 24

16 Sample No. Puncture Voltage (kv) Thickness (mm) Dielectric Strength (V/mm) C Comments see Note below Old cross arm material tested parallel to the wood grain C Old cross arm material tested across the wood grain Average Note: The measured puncture voltage on the wood samples was the maximum voltage reached by the test source before the increasing load current caused the source voltage to collapse Lightning Impulse Voltage Dielectric Strength Tests The results of the lightning impulse dielectric strength tests are given in Tables 7 and 8. Sample No. Table 7 Fibre Reinforced Cementitious Samples Puncture Voltage (kv) Thickness (mm) Dielectric Strength (V/mm) Comments 874-A Smooth surface 874-A Smooth surface Smooth surface with 874-A3 > some roughness 874-A Smooth surface 874-A Smooth surface Smooth surface with 874-A some roughness 874-A7 > Smooth surface 874-A8 > Smooth surface 874-A Rough surface 874-A10 > Rough surface 874-A11 > Smooth surface 874-A Smooth surface Average Project No: Page 16 of 24

17 Sample No. Puncture Voltage (kv) Thickness (mm) Table 8 Wood Samples Dielectric Strength (V/mm) A A A A B B C Comments Old cross arm material tested parallel to the wood grain Old cross arm material tested parallel to the wood grain Old cross arm material tested across the wood grain Old cross arm material tested across the wood grain Old cross arm material tested parallel to the wood grain Old cross arm material tested across the wood grain Old cross arm material tested parallel to the wood grain C Old cross arm material tested across the wood grain Average Tracking Wheel Test The ultra high performance fibre reinforced cementitious composite cross arms material passed the tracking and erosion test with no tracking, no erosion to the core and no coating puncture of the cross arm material. Figures show the samples at the end of the tracking test. Sample B4 (with sealed edges), Figures17 & 18, had carbonization around one of the mounting holes. This damage was on the epoxy used to seal the edges. There was no damage to the tested material. It was observed during the aging on the tracking wheel that the there was considerable heating of the samples. It was found the fibre reinforced cementitious composite material has a slight conductivity. The resistance over a 2.1 m distance was measured to be 6.3 megohm. For comparison a sample of wood was also tested and it measured 5 megohm over a 2.6 m distance. Normally there is a post tracking wheel steep front impulse test, power-frequency flashover test and power-frequency voltage heating test done on the samples. The steep front impulse test and the flashover test is done to determine if there has been water ingress between the fibreglass core and the polymer housing interface on insulators. This does not apply in this case as there is no interface. The power-frequency heating test is done to determine if there has been water absorption into the material. If there is heating of the sample it indicates water absorption. Since the material heated up during the aging test, due to its slight conductivity, the power-frequency heating test would serve no purpose and was not done. Lafarge Canada stated that does not absorb any moisture. Project No: Page 17 of 24

18 Figure 11 Sample 1 Front after Tracking and Erosion Test Figure 12 Sample 1 Back after Tracking and Erosion Test Project No: Page 18 of 24

19 Figure 13 Sample 2 Front after Tracking and Erosion Test Figure 14 Sample 2 Back after Tracking and Erosion Test Project No: Page 19 of 24

20 Figure 15 Sample 3 Front after Tracking and Erosion Test Figure 16 Sample 3 Back after Tracking and Erosion Test Project No: Page 20 of 24

21 Figure 17 Sample 4 Front (with sealed edges) after Tracking and Erosion Test Figure 18 Sample 4 Back (with sealed edges) after Tracking and Erosion Test Project No: Page 21 of 24

22 6.0 DISCUSSION OF RESULTS There is no specification for acceptable partial discharge in the cross arms/cross braces but based on normal requirements for other equipment we would recommend that the internal partial discharge (extinction voltage) should be below 20 pc at 120 % of rated maximum operating voltage (1.2 x kv =169.7 kv). The test structure met this requirement in all test configurations. The AC flashovers to the surface and across the surface caused no visible damage to the fibre reinforced cementitious composite material. The lightning impulse flashovers across the surface also caused no visible damage to the material. The lightning impulse flashovers to the surface did cause spalling, punctures through the cross arm web material and visible cracks on the web of unknown depth. It is recommended that the effect of the potential damage that could be done by AC fault currents or lightning impulse on the mechanical strength of the fibre reinforced cementitious composite material be investigated. The power-frequency and the lightning impulse dielectric strength of the fibre reinforced cementitious composite material exceeded the strength of wood samples. The samples passed the tracking and erosion test on the tracking wheel with no damage to the fibre reinforced cementitious composite material. 7.0 CONCLUSIONS The ultra high performance fibre reinforced cementitious composite cross arms electrical properties are very comparable to conventional wood cross arms. For structures with unbonded hardware the slight conductivity of the material is a good feature. It means that under normal operating conditions there will be good voltage grading between the insulators and the transmission line structure. The one area of concern is the damage to the material during the lightning impulse tests. It is recommended the impact of this damage on the mechanical properties of the material be investigated. Subsequent to the Powertech tests structural tests were carried out by the University of Calgary on the damaged cross arm. A copy of the University of Calgary report is included as Appendix A. Project No: Page 22 of 24

23 APPENDIX A University of Calgary Report Project No: Page 23 of 24

24 Project No: Page 24 of 24

25 Structural Testing of Fibreglass Reinforced Cementitious Composite Cross Arm after being Exposed to Electrical Lightning Impulses Prepared by: Dr. Raafat El-Hacha, PEng University of Calgary Department of Civil Engineering Prepared for: Lafarge Canada Inc. April 2010

26 Executive Summary The objective of this test is to asses the structural performance and mechanical properties of a cross arm with surface damage created by electrical lightning impulses. A mechanical test was performed on this cross arm in order to asses its structural integrity. The cross arm that was damaged during Powertech s lightning impulse test is shown bellow. Upon visual inspection, the impact caused by the lightning impulse seemed to be on the web s surface and was not larger than 25 mm 2 (1 inch 2 ). The depth of these damage spots did not exceed 3 mm (1/8 of an inch) on both sides of the web. The surface damage seemed to be localized along 500 mm of the cross arm. There was no other apparent damage anywhere on the cross arm. 500 mm Figure 1: Damage due to lightning impulse Page 1 of 8

27 In order to investigate the structural integrity and the mechanical properties of this damaged cross arm, it was decided that a flexural test on the damaged section of the cross arm should be performed with bending about the x-axis. For this reason, the 9,000 mm long cross arm was cut into 3 specimens, each 2550 mm long, labelled specimens S x#1-6.6, S x#2-6.6, and S x# Specimen S x#2-6.6 had the damage area and was cut in a way to have the 500 mm long damaged section located at the mid span for it to be loaded under a 3 point bending test and have the web exposed to maximum stresses.. All specimens were tested in a simply supported configuration under three point bending, with the point load applied at midspan, the ends supports were roller and hinge. The width of the end supports was 100mm. The span centre-to-center between the supports is 2350mm. The shear span (distance between the support reaction and the midspan point load) is 1175mm. Therefore, the shear-span-todepth ratio a/d= 6.6, where d is the effective depth measured from the compression fibre of teh cross arm to the centroid of the bottom tension reinforcement taken equal to 178mm. Figure 2 shows the test-set-up. The specimens were instrumented at midspan using Linear Strain Conversion transducers to measure the vertical deflection and any potential of the occurrence of lateral displacement. The cross arms were loaded on the top flange such that the point load is only applied over the width of the web. Figure 2: Test Set-up for flexural test Figure 3 shows the load versus midspan vertical deflection of the three cross arms. From these curves, it can be concluded that the overall flexural behaviour and capacity of all specimens are similar. The average ultimate load was 31 kn. Page 2 of 8

28 Cross Arm Strong Axis Shear Span-to-Depth Ratio=6.6 Specimens #1, 2 &3 35 Load (kn) S x#1-6.6 S x#2-6.6 (damaged with lightning impulse) S x# Mid-span Deflection (mm) a/h=5.9 (h=200mm) a/d=6.6 (d=178mm) S x#1-6.6: P max = 32.4 kn M max = kn m S x#2-6.6: P max = 30.8kN M max = kn m S x#3-6.6: P max = 30.2 kn M max = 15.1 kn m Figure 3: Load versus midspan deflection of the three specimens The mode of failure of the three specimens was similar and can be described as shear failure followed by longitudinal splitting cracks starting at both ends of the diagonal crack, one (top longitudinal crack) towards the point load and the other (bottom longitudinal crack) towards the support. Figure 4 shows the failure of specimens S x# Figure 5, shows the failure mode of specimen S x# Moreover, it can be seen that the cracks and damaged areas on the cross arm s web caused by the lightning impulses did not promote or attract further cracking or further damage when subjected to the midspan point load from the 3 point bending tests. Moreover, specimens S x#1-6.6, S x#2-6.6, and S x#3-6.6 had comparable results to similar specimens that were cut from undamaged fibreglass reinforced cementitious cross arms and previously tested. The bending test results of these undamaged specimens with the same length reached an average ultimate load of 38 kn with shear as the dominate failure mode accompanied with longitudinal splitting at the bottom flange towards the support. It can be concluded from this test, that the damage caused by the electrical lightning impulse test did not affect the structural performance and mechanical properties of this fibreglass reinforced cementitious composite cross arm. Page 3 of 8

29 S x#1-6.6 S x#1-6.6 Figure 4(a): Cross arm S x#1-6.6 before flexural testing to failure S x#1-6.6 Figure 4(b): Close up view of the left shear-span before flexural testing to failure Page 4 of 8

30 S x#1-6.6 S x#1-6.6 Figure 4(c): Cross arm S x#1-6.6 after flexural testing to failure S x#1-6.6 Figure 4(d): Close up view of the left shear-span after flexural testing to failure Page 5 of 8

31 Figure 5 (a): Cross arm S x#2-6.6: one side of entire length after flexural testing to failure Figure 5 (b): Cross arm S x#2-6.6: close up of the damaged area caused by the lightning impulses (white spots) after flexural testing to failure Figure 5 (c): Cross arm S x#2-6.6: close up of the shear crack (in the right shear span) after flexural testing to failure Page 6 of 8

32 Figure 5 (d): Cross arm S x#2-6.6: close up of left shear span after flexural testing to failure Figure 5 (e): Cross arm S x#2-6.6: other side of entire length after flexural testing to failure Figure 5 (f): Cross arm S x#2-6.6: close up of the damaged area by the lightning impulses (white spots) after flexural testing to failure Figure 5 (g): Cross arm S x#2-6.6: close up of the shear crack after flexural testing to failure Figure 5 (h): Cross arm S x#2-6.6: close up of the cracks on the other shear span after flexural testing to failure Page 7 of 8

33 Figure 5 (i): Cross arm S x#2-6.6: close up of the damaged area by the lightning impulses (white spots) after flexural testing to failure Page 8 of 8

Design Test Report Report No. EU1531-H ANSI C29.18 PROTOTYPE/ CEA LWIWG 02 DESIGN TEST REPORT Silicone Rubber 69 kv Veri*Lite Line Post 80S069

Design Test Report Report No. EU1531-H ANSI C29.18 PROTOTYPE/ CEA LWIWG 02 DESIGN TEST REPORT Silicone Rubber 69 kv Veri*Lite Line Post 80S069 Design Test Report Report No. EU1531-H ANSI C29.18 PROTOTYPE/ CEA LWIWG 02 DESIGN TEST REPORT Silicone Rubber 69 kv Veri*Lite Line Post 80S069 This test report records the results of laboratory tests made

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

Numerical modelling of shear connection between concrete slab and sheeting deck

Numerical modelling of shear connection between concrete slab and sheeting deck 7th fib International PhD Symposium in Civil Engineering 2008 September 10-13, Universität Stuttgart, Germany Numerical modelling of shear connection between concrete slab and sheeting deck Noémi Seres

More information

Transmission Silicone Insulators Line Post 69 kv to 161 kv

Transmission Silicone Insulators Line Post 69 kv to 161 kv K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 161 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

Structural Failures Cost Lives and Time

Structural Failures Cost Lives and Time Structural Failures Cost Lives and Time Recent failures of storage bins, silos and other structures highlight the need to increase awareness of hazards associated with these structures. Since 2010, one

More information

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support. www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for

More information

METHOD OF STATEMENT FOR STATIC LOADING TEST

METHOD OF STATEMENT FOR STATIC LOADING TEST Compression Test, METHOD OF STATEMENT FOR STATIC LOADING TEST Tension Test and Lateral Test According to the American Standards ASTM D1143 07, ASTM D3689 07, ASTM D3966 07 and Euro Codes EC7 Table of Contents

More information

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003 MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU

More information

Bending, Forming and Flexing Printed Circuits

Bending, Forming and Flexing Printed Circuits Bending, Forming and Flexing Printed Circuits John Coonrod Rogers Corporation Introduction: In the printed circuit board industry there are generally two main types of circuit boards; there are rigid printed

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

USE OF CFRP LAMINATES FOR STRENGTHENING OF REINFORCED CONCRETE CORBELS

USE OF CFRP LAMINATES FOR STRENGTHENING OF REINFORCED CONCRETE CORBELS International Journal of Civil Engineering and Technology (IJCIET) Volume 6, Issue 11, Nov 2015, pp. 11-20, Article ID: IJCIET_06_11_002 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=6&itype=11

More information

Field Damage Inspection and Static Load Test Analysis of Jiamusi Highway Prestressed Concrete Bridge in China

Field Damage Inspection and Static Load Test Analysis of Jiamusi Highway Prestressed Concrete Bridge in China Advanced Materials Research Vols. 163-167 (2011) pp 1147-1156 Online available since 2010/Dec/06 at www.scientific.net (2011) Trans Tech Publications, Switzerland doi:10.4028/www.scientific.net/amr.163-167.1147

More information

Hardened Concrete. Lecture No. 14

Hardened Concrete. Lecture No. 14 Hardened Concrete Lecture No. 14 Strength of Concrete Strength of concrete is commonly considered its most valuable property, although in many practical cases, other characteristics, such as durability

More information

IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION. Generated: Sergiy Papyshev Engineering. Approved: Don Prysi Manufacturing. Approved: Merzuk Ramic Quality

IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION. Generated: Sergiy Papyshev Engineering. Approved: Don Prysi Manufacturing. Approved: Merzuk Ramic Quality IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION Generated: Sergiy Papyshev Engineering Approved: Don Prysi Manufacturing Approved: Merzuk Ramic Quality Approved: Steven Barnett Administrative DATE DATE DATE

More information

SEISMIC UPGRADE OF OAK STREET BRIDGE WITH GFRP

SEISMIC UPGRADE OF OAK STREET BRIDGE WITH GFRP 13 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 2004 Paper No. 3279 SEISMIC UPGRADE OF OAK STREET BRIDGE WITH GFRP Yuming DING 1, Bruce HAMERSLEY 2 SUMMARY Vancouver

More information

DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,

DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab, DESIGN OF SLABS Dr. G. P. Chandradhara Professor of Civil Engineering S. J. College of Engineering Mysore 1. GENERAL A slab is a flat two dimensional planar structural element having thickness small compared

More information

A Study of a MV Cable Joint

A Study of a MV Cable Joint SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 7, No. 1, May 2010, 1-11 UDK: 621.315.35:537.212 A Study of a MV Cable Joint Radiša Dimitrijević 1, Neda Pekarić-Nađ 2, Miodrag Milutinov 3 Abstract: Construction

More information

Polymer Termination. Mechanical Cracking 2. The reason for polymer termination. What is Polymer Termination? 3

Polymer Termination. Mechanical Cracking 2. The reason for polymer termination. What is Polymer Termination? 3 Polymer Termination An alternative termination material specifically designed to absorb greater levels of mechanical stress thereby reducing capacitor failures associated with mechanical cracking Mechanical

More information

FLEXURAL BEHAVIOUR OF HYBRID FRP-UHPC GIRDERS UNDER STATIC LOADING

FLEXURAL BEHAVIOUR OF HYBRID FRP-UHPC GIRDERS UNDER STATIC LOADING Proceedings of 8 th International Conference on Short and Medium Span Bridge Niagara Falls, Canada 21 FLEXURAL BEHAVIOUR OF HYBRID FRP-UHPC GIRDERS UNDER STATIC LOADING Donna S. M. Chen Department of Civil

More information

The following sketches show the plans of the two cases of one-way slabs. The spanning direction in each case is shown by the double headed arrow.

The following sketches show the plans of the two cases of one-way slabs. The spanning direction in each case is shown by the double headed arrow. 9.2 One-way Slabs This section covers the following topics. Introduction Analysis and Design 9.2.1 Introduction Slabs are an important structural component where prestressing is applied. With increase

More information

bi directional loading). Prototype ten story

bi directional loading). Prototype ten story NEESR SG: Behavior, Analysis and Design of Complex Wall Systems The laboratory testing presented here was conducted as part of a larger effort that employed laboratory testing and numerical simulation

More information

SECTION 02845 GUARDRAILS

SECTION 02845 GUARDRAILS SECTION 02845 GUARDRAILS PART 1 - GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals necessary and repair, replace or install all types of guardrails as specified herein

More information

16. Beam-and-Slab Design

16. Beam-and-Slab Design ENDP311 Structural Concrete Design 16. Beam-and-Slab Design Beam-and-Slab System How does the slab work? L- beams and T- beams Holding beam and slab together University of Western Australia School of Civil

More information

PowerPatch Sealant Tests

PowerPatch Sealant Tests American Polywater s A Publication for Engineers Involved in Cable Installations Subject: PowerPatch Sealant Tests Background and Purpose: The PowerPatch Paste Sealant is a two-part, rapid-cure, resin

More information

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta? TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing

More information

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig. 7.21 some of the trusses that are used in steel bridges

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig. 7.21 some of the trusses that are used in steel bridges 7.7 Truss bridges Fig. 7.21 some of the trusses that are used in steel bridges Truss Girders, lattice girders or open web girders are efficient and economical structural systems, since the members experience

More information

Condition Monitoring of equipment to improve quality of supply to customers by averting failures

Condition Monitoring of equipment to improve quality of supply to customers by averting failures Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract

More information

Detailing of Reinforcment in Concrete Structures

Detailing of Reinforcment in Concrete Structures Chapter 8 Detailing of Reinforcment in Concrete Structures 8.1 Scope Provisions of Sec. 8.1 and 8.2 of Chapter 8 shall apply for detailing of reinforcement in reinforced concrete members, in general. For

More information

SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS

SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS Fracture Mechanics of Concrete Structures Proceedings FRAMCOS-3 AEDIFICA TIO Publishers, D-79104 Freiburg, Germany SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS H.

More information

MECHANICS OF SOLIDS - BEAMS TUTORIAL 1 STRESSES IN BEAMS DUE TO BENDING. On completion of this tutorial you should be able to do the following.

MECHANICS OF SOLIDS - BEAMS TUTORIAL 1 STRESSES IN BEAMS DUE TO BENDING. On completion of this tutorial you should be able to do the following. MECHANICS OF SOLIDS - BEAMS TUTOIAL 1 STESSES IN BEAMS DUE TO BENDING This is the first tutorial on bending of beams designed for anyone wishing to study it at a fairly advanced level. You should judge

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

Chapter 2 Basis of design and materials

Chapter 2 Basis of design and materials Chapter 2 Basis of design and materials 2.1 Structural action It is necessary to start a design by deciding on the type and layout of structure to be used. Tentative sizes must be allocated to each structural

More information

Design Test Report Veri*Lite Suspension Insulators Catalog Numbers: 405003, 405004, 405005, 405006

Design Test Report Veri*Lite Suspension Insulators Catalog Numbers: 405003, 405004, 405005, 405006 Design Test Report Veri*Lite Suspension s Catalog Numbers: 0003, 000, 000, 000 This design test report records the results of laboratory tests made on the Ohio Brass Veri*Lite Suspension s. Test performed

More information

In-situ Load Testing to Evaluate New Repair Techniques

In-situ Load Testing to Evaluate New Repair Techniques In-situ Load Testing to Evaluate New Repair Techniques W.J. Gold 1 and A. Nanni 2 1 Assistant Research Engineer, Univ. of Missouri Rolla, Dept. of Civil Engineering 2 V&M Jones Professor, Univ. of Missouri

More information

Electrical tests on PCB insulation materials and investigation of influence of solder fillets geometry on partial discharge

Electrical tests on PCB insulation materials and investigation of influence of solder fillets geometry on partial discharge , Firenze, Italy Electrical tests on PCB insulation materials and investigation of influence of solder fillets geometry on partial discharge A. Bulletti, L. Capineri B. Dunn ESTEC Material and Process

More information

Formwork for Concrete

Formwork for Concrete UNIVERSITY OF WASHINGTON DEPARTMENT OF CONSTRUCTION MANAGEMENT CM 420 TEMPORARY STRUCTURES Winter Quarter 2007 Professor Kamran M. Nemati Formwork for Concrete Horizontal Formwork Design and Formwork Design

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

Use of Strain Gauge Rosette to Investigate Stress concentration in Isotropic and Orthotropic Plate with Circular Hole

Use of Strain Gauge Rosette to Investigate Stress concentration in Isotropic and Orthotropic Plate with Circular Hole Use of Strain Gauge Rosette to Investigate Stress concentration in Isotropic and Orthotropic Plate with Circular Hole Mr.V.G.Aradhye 1, Prof.S.S.Kulkarni 2 1 PG Scholar, Mechanical department, SKN Sinhgad

More information

June 2007 CHAPTER 7 - CULVERTS 7.0 CHAPTER 7 - CULVERTS 7.1 GENERAL

June 2007 CHAPTER 7 - CULVERTS 7.0 CHAPTER 7 - CULVERTS 7.1 GENERAL 7.0 7.1 GENERAL For the purpose of this manual, culverts are defined as structures that are completely surrounded by soil and located below the surface of the roadway parallel to the general direction

More information

Cathode Ray Tube. Introduction. Functional principle

Cathode Ray Tube. Introduction. Functional principle Introduction The Cathode Ray Tube or Braun s Tube was invented by the German physicist Karl Ferdinand Braun in 897 and is today used in computer monitors, TV sets and oscilloscope tubes. The path of the

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS

MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS May 29, 2013 Revision B Structural Guideline for Design and Installation Holes in Composite Floor Slab Terminal 3, Departure Level

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Optimising plate girder design

Optimising plate girder design Optimising plate girder design NSCC29 R. Abspoel 1 1 Division of structural engineering, Delft University of Technology, Delft, The Netherlands ABSTRACT: In the design of steel plate girders a high degree

More information

APE T CFRP Aslan 500

APE T CFRP Aslan 500 Carbon Fiber Reinforced Polymer (CFRP) Tape is used for structural strengthening of concrete, masonry or timber elements using the technique known as Near Surface Mount or NSM strengthening. Use of CFRP

More information

SMA Interface Mating Dimensions (Per MIL-STD-348)

SMA Interface Mating Dimensions (Per MIL-STD-348) SMA Series SMA 6 SMA Interface Mating Dimensions (Per MIL-STD-348) SMA Interface Dimensions MALE Inches/Millimeters 3 Minimum Nominal Maximum LTR in. mm in. mm in. mm A.250 6.35.263 6.68.. B.1790 4.55.1808

More information

EFFECTS OF CORONA RING DESIGN ON ELECTRIC FIELD INTENSITY AND POTENTIAL DISTRIBUTION ALONG AN INSULATOR STRING

EFFECTS OF CORONA RING DESIGN ON ELECTRIC FIELD INTENSITY AND POTENTIAL DISTRIBUTION ALONG AN INSULATOR STRING EFFECTS OF CORONA RING ESIGN ON ELECTRIC FIEL INTENSITY AN POTENTIAL ISTRIUTION ALONG AN INSULATOR STRING Suat İlhan Aydoğan Özdemir e-mail: ilhan@elk.itu.edu.tr e-mail: ozdemir@elk.itu.edu.tr Electrical

More information

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences

More information

Medium voltage insulator

Medium voltage insulator Medium voltage insulator Line post insulators type R-ET Commercial designation LPI 24 N ET 1) LPI 24 L ET/5 1)2) LPI 24 L ET/6 1)2) LPI 38 L ET 1) esignation acc. to IEC 720 R 12,5 ET 125 N R 12,5 ET 125

More information

PC-Concrete Injectable Concrete Anchoring and Repair System

PC-Concrete Injectable Concrete Anchoring and Repair System PC-Concrete Injectable Concrete Anchoring and Repair System DESCRIPTION: PC-Concrete is a two component (1:1 ratio), 100% solids, high modulus, structural epoxy paste. PC-Concrete is a solvent free, no

More information

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO LED PORTFOLIO LUXEON LEDs Circuit Design and Layout Practices to Minimize Electrical Stress Introduction LED circuits operating in the real world can be subjected to various abnormal electrical overstress

More information

Single Channel Loop Detector

Single Channel Loop Detector Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop

More information

White Paper. Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards.

White Paper. Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards. Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards White Paper Introduction Optocouplers and alternative isolation technologies

More information

Installation Instructions For Slider Casement Air Conditioners

Installation Instructions For Slider Casement Air Conditioners Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT

More information

DEHN + SÖHNE. DEHNconductor System No Problems with Proximities

DEHN + SÖHNE. DEHNconductor System No Problems with Proximities DEHN + SÖHNE DEHNconductor System No Problems with Proximities DEHNconductor System - New Possibilities for controling Proximities. For preventing dangerous flashovers among parts of external lightning

More information

NUMERICAL ANALYSIS OF GLULAM BEAMS WITHOUT AND WITH GFRP REINFORCEMENT

NUMERICAL ANALYSIS OF GLULAM BEAMS WITHOUT AND WITH GFRP REINFORCEMENT 10th International Conference on Composite Science and Technology ICCST/10 A.L. Araújo, J.R. Correia, C.M. Mota Soares, et al. (Editors) IDMEC 2015 NUMERICAL ANALYSIS OF GLULAM BEAMS WITHOUT AND WITH GFRP

More information

WWW.CABLEJOINTS.CO.UK THORNE & DERRICK UK TEL 0044 191 490 1547 FAX 0044 477 5371 TEL 0044 117 977 4647 FAX 0044 977 5582 WWW.THORNEANDDERRICK.CO.

WWW.CABLEJOINTS.CO.UK THORNE & DERRICK UK TEL 0044 191 490 1547 FAX 0044 477 5371 TEL 0044 117 977 4647 FAX 0044 977 5582 WWW.THORNEANDDERRICK.CO. able leats Section 6 able leats for Power Transmission ables Glass reinforced composite cable cleats general information type able cleat U type able cleat (channel mounted) T type able cleat (trefoil configuration)

More information

An Overview of Lapp Insulator High Voltage Bushing Design

An Overview of Lapp Insulator High Voltage Bushing Design An Overview of Lapp Insulator High Voltage Bushing Design W.A. Young Lapp Insulator Company LeRoy, NY 14482 USA INTRODUCTION High voltage bushings are devices designed to transmit electric energy through

More information

FINAL FAILURE INVESTIGATION WESTCHESTER NORTH LAGOON BRIDGE. Anchorage, Alaska

FINAL FAILURE INVESTIGATION WESTCHESTER NORTH LAGOON BRIDGE. Anchorage, Alaska FINAL FAILURE INVESTIGATION WESTCHESTER NORTH LAGOON BRIDGE Anchorage, Alaska August 2014 Prepared for: Municipality of Anchorage Project Management and Engineering P.O. Box 196650 Anchorage, Alaska 99519-6650

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

AC and Pulse Film Foil Capacitors KP Radial Potted Type

AC and Pulse Film Foil Capacitors KP Radial Potted Type AC and Pulse Film Foil Capacitors KP Radial Potted Type 0.5 L max. W max. Marking H max. FEATURES 5 mm lead pitch, supplied loose in box taped in ammopack or reel Material categorization: for definitions

More information

Flex Circuit Design and Manufacture.

Flex Circuit Design and Manufacture. Flex Circuit Design and Manufacture. Hawarden Industrial Park, Manor Lane, Deeside, Flintshire, CH5 3QZ Tel 01244 520510 Fax 01244 520721 Sales@merlincircuit.co.uk www.merlincircuit.co.uk Flex Circuit

More information

Chapter 5 Bridge Deck Slabs. Bridge Engineering 1

Chapter 5 Bridge Deck Slabs. Bridge Engineering 1 Chapter 5 Bridge Deck Slabs Bridge Engineering 1 Basic types of bridge decks In-situ reinforced concrete deck- (most common type) Pre-cast concrete deck (minimize the use of local labor) Open steel grid

More information

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2

More information

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or

More information

MATERIALS AND MECHANICS OF BENDING

MATERIALS AND MECHANICS OF BENDING HAPTER Reinforced oncrete Design Fifth Edition MATERIALS AND MEHANIS OF BENDING A. J. lark School of Engineering Department of ivil and Environmental Engineering Part I oncrete Design and Analysis b FALL

More information

BEHAVIOR OF SHORT CONCRETE COLUMNS REINFORCED BY CFRP BARS AND SUBJECTED TO ECCENTRIC LOAD

BEHAVIOR OF SHORT CONCRETE COLUMNS REINFORCED BY CFRP BARS AND SUBJECTED TO ECCENTRIC LOAD International Journal of Civil Engineering and Technology (IJCIET) Volume 6, Issue 10, Oct 2015, pp. 15-24 Article ID: IJCIET_06_10_002 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=6&itype=10

More information

SECTION 02612 NONREINFORCED CONCRETE SEWER PIPE

SECTION 02612 NONREINFORCED CONCRETE SEWER PIPE SECTION 02612 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Furnishing and installing nonreinforced concrete sewer pipe. Provide concrete sewer pipe less than 12 inches in diameter, and in other sizes

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety

More information

Installation Instructions

Installation Instructions READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

Guidelines for Earthquake Bracing of Residential Water Heaters

Guidelines for Earthquake Bracing of Residential Water Heaters Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)

More information

LOAD-CARRYING CAPACITY OF AXIALLY LOADED RODS GLUED-IN PERPENDICULAR TO THE GRAIN

LOAD-CARRYING CAPACITY OF AXIALLY LOADED RODS GLUED-IN PERPENDICULAR TO THE GRAIN LOAD-CARRYING CAPACITY OF AXIALLY LOADED RODS GLUED-IN PERPENDICULAR TO TE GRAIN Prof. Dr.-Ing..J. Blaß, Dipl.-Ing. B. Laskewitz Universität Karlsruhe (T), Germany Abstract Glued-in rods have been used

More information

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors Size 1206, 0805, 0603, 0402 *Contents in this sheet are subject to change without prior notice. Page 1 of 8 ASC_WWxxX_V12 Nov.- 2011

More information

Session 3: Guardrail Design and Sitespecific. Considerations

Session 3: Guardrail Design and Sitespecific. Considerations FHWA Roadway Departure Technology Transfer Roadside Safety Systems Installer Training : Guardrail Design and Sitespecific Installation Considerations 3-1 Course Topics Session 2 Testing Requirements and

More information

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-...

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-... Installation guide for the SafeLine type anchorage device Tested in compliance with EN 795: 1996 No.: SE-... Version: 09.10.2008 SE 67 Subject to technical alterations! Contents 1. General information

More information

Structural Axial, Shear and Bending Moments

Structural Axial, Shear and Bending Moments Structural Axial, Shear and Bending Moments Positive Internal Forces Acting Recall from mechanics of materials that the internal forces P (generic axial), V (shear) and M (moment) represent resultants

More information

B.TECH. (AEROSPACE ENGINEERING) PROGRAMME (BTAE) Term-End Examination December, 2011 BAS-010 : MACHINE DESIGN

B.TECH. (AEROSPACE ENGINEERING) PROGRAMME (BTAE) Term-End Examination December, 2011 BAS-010 : MACHINE DESIGN No. of Printed Pages : 7 BAS-01.0 B.TECH. (AEROSPACE ENGINEERING) PROGRAMME (BTAE) CV CA CV C:) O Term-End Examination December, 2011 BAS-010 : MACHINE DESIGN Time : 3 hours Maximum Marks : 70 Note : (1)

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

4 SENSORS. Example. A force of 1 N is exerted on a PZT5A disc of diameter 10 mm and thickness 1 mm. The resulting mechanical stress is:

4 SENSORS. Example. A force of 1 N is exerted on a PZT5A disc of diameter 10 mm and thickness 1 mm. The resulting mechanical stress is: 4 SENSORS The modern technical world demands the availability of sensors to measure and convert a variety of physical quantities into electrical signals. These signals can then be fed into data processing

More information

SECTION 22 LIGHTNING PROTECTION SYSTEM

SECTION 22 LIGHTNING PROTECTION SYSTEM SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for

More information

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment Scott Aldous, Compliance Engineer What is Insulation Coordination? From IEC 60664-1, Edition 1.2: So what does that mean

More information

DC Film Capacitors MKT Radial Potted Type

DC Film Capacitors MKT Radial Potted Type DC Film Capacitors MKT Radial Potted Type FEATURES 15 mm to 27.5 mm lead pitch. Supplied loose in box and taped on reel Material categorization: for definitions of compliance please see www.vishay.com/doc?99912

More information

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before

More information

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of

More information

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance Dennis W. Lenk, Fellow, IEEE Abstract-- This paper examines performance

More information

Fixed and Portable Ladders- A Guide to OSHA Rules

Fixed and Portable Ladders- A Guide to OSHA Rules Fixed and Portable Ladders- A Guide to OSHA Rules Introduction Working on and around stairways and ladders is hazardous. Stairways and ladders are major sources of injuries and fatalities among construction

More information

Free piston Stirling engine for rural development

Free piston Stirling engine for rural development Free piston Stirling engine for rural development R. Krasensky, Intern, Stirling development, r.krasensky@rrenergy.nl W. Rijssenbeek, Managing director, w.rijssenbeek@rrenergy.nl Abstract: This paper presents

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES

SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES SnoTrace Surface Snow and Ice Melting INSTALLATION PROCEDURES SnoTrace INSTALLATION PROCEDURES Refer to the SnoTrace Cable Testing Report for required recording of test data and circuit information. Upon

More information

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court

More information

Quality Regulations for Profiles

Quality Regulations for Profiles Quality Regulations for Profiles September 2010 Quality Regulations for Profiles Page 2/42 Contents Preface... 4 1. Terms and Definitions... 5 1.1 Third parties... 5 1.2 Independent laboratories... 5 1.3

More information

REPAIR AND STRENGTHENING OF HISTORICAL CONCRETE BRIDGE OVER VENTA RIVER IN LATVIA

REPAIR AND STRENGTHENING OF HISTORICAL CONCRETE BRIDGE OVER VENTA RIVER IN LATVIA 1 REPAIR AND STRENGTHENING OF HISTORICAL CONCRETE BRIDGE OVER VENTA RIVER IN LATVIA Verners Straupe, M.sc.eng., Rudolfs Gruberts, dipl. eng. JS Celuprojekts, Murjanu St. 7a, Riga, LV 1024, Latvia e-mail:

More information

Silicone Rubber Thermal Interface Materials: Applications and Performance Considerations

Silicone Rubber Thermal Interface Materials: Applications and Performance Considerations Silicone Rubber Thermal Interface Materials: Applications and Performance Considerations David C. Timpe Jr. Arlon Silicone Technologies Division 1100 Governor Lea Road, Bear, DE 19701 P: 800-635-9333 F:

More information