Certifikat och provningsprotokoll för art och 4511

Size: px
Start display at page:

Download "Certifikat och provningsprotokoll för art och 4511"

Transcription

1 Certifikat och provningsprotokoll för art och 4511 Innehållsförteckning: Declaration of conformity... sid 2 SINTEF Produktdokumentation sid 3 Efectis Nederland BV Brandtestunderlag... sid 7 ELKO AB E-post: info@elko.se Hemsida: VAT/Org.nr: SE Huvudkontor Bryggvägen 16 Box Stockholm Tele Tel: +46 (0) Fax: +46 (0)

2

3

4

5

6

7 Efectis Nederland BV Return address: P.O. Box 1090, 2280 CB Rijswijk, The Netherlands Environmental Seals Ltd Envirograf House Attn: Mr. P. Ackerman-Mond Barfrestone DOVER CT15 7JG Kent United Kingdom Centre for Fire Safety Lange Kleiweg 5 P.O. Box CB Rijswijk T F Subject Preliminary test of ceiling/floor construction with Elko flush mounting boxes 2007-Efectis Nederland-report 2007-Efectis-R Dear Mr. Ackerman-Mond, On behalf of your firm we have performed a preliminary test on a ceiling/floor construction provided with several Elko flush mounting boxes. The test was based on the European standard EN :1999 in compliance with NEN 6069: 2005 and performed on April 24, arjo.lock@efectis.com Direct dialling (015) Direct fax (015) Efectis Nederland BV: a TNO Company The ceiling/floor construction was assembled at our laboratory and consisted of wooden studs with two layers of Fireline plasterboard on the fire side and chipboard on the non fire side. The dimensions of the construction were 1650 x 1650 x 150 mm. On top of the construction there was not any load applied. The test was only performed to check the integrity of the Elko flush mountings boxes with the Envirograf intumescent gaskets. The Standard Conditions for Research Instructions given to Efectis, as filed at he Registry of the District Court and the Chamber of Commerce in The Hague shall apply to all instructions given to TNO; the Standard Conditions will be sent on request. 1 This report is issued by the TNO company Efectis Nederland BV (previously TNO Centre for Fire Research). TNO decided, in response to international developments and requests by customers, to collaborate with two European Egolf partners, both highly experienced in fire safety: the Norwegian Sintef/NBL and the French CTICM. Thus, through scaling up, a more comprehensive service of high quality and a wider range of facilities can be offered. In order to achieve this, the fire safety related activities of the partners involved have been privatised in this collaboration. With respect to TNO this has lead to the privatisation on the 1 st of July of the activities of the TNO Centre for Fire Research via the establishment of the company Efectis Nederland BV.

8 The frame of the construction was made of five wooden studs (timber) and covered with two layers of Fireline plasterboard. The fireside was applied with one joint in the Fireline plasterboard. At the fireside of the construction four Norwegian Flush Mounting Boxes were implemented which were fitted with intumescent gaskets of Envirograf, type 30 which expands during a fire. At the non-fireside a layer of chipboard was used to simulate a floor. 2/13 Specifications of ceiling/floor construction (see drawing 1): - Timber dimension 130 x 50 mm - Fireline Plasterboard thickness 15 mm (2 layers) - Chipboard thickness 25 mm Specification of Flush Mounting Boxes (photo 4): - 2 of product code 32/246 Item No of product code 64/246 Item No Test setup The construction was placed on top of our preliminary furnace which was equipped with three temperature sensors and a pressure device. The ceiling/floor construction was applied with ten surface thermocouples (see figure C1). Observations during the fire test Time Side Observation [min] 0 Start heating 5 N Smoke coming from the construction 10 N Smoke from joint in the floor 22 N Smoke coming from the edge at the backside at position A 32 N More smoke coming from the edges and moist visible at position B 40 N Light deforming of the chipboard at pos. A and more smoke at pos. C 62 N Also smoke at position D and A 70 N More deforming of the chipboard 70 N End of heating

9 Assessment We expect that a ceiling/floor construction of timber and covered with Fireline plasterboard on the fireside and chipboard on the non-fireside and provided with Norwegian flush mounting boxes fitted with Envirograf in tumescent gaskets will have a fire resistance according to NEN 6069: 2005 of at least 60 minutes under the conditions: 3/13 the timber has at least the same dimensions, 130 x 50 mm; two layers of Fireline plasterboard is used with a total thickness of 30 mm; the chipboard has a thickness of 25 mm; the boxes are fitted with Envirograf product 30. At the next pages the observations, graphs of the test results and some photographs made during the assemblage and the fire test are enclosed. I hope we have informed you completely with this brief letter report. Yours faithfully, A.J. Lock Dr. Ir G. van den Berg This document has the status of a Efectis Nederland report and is known at Efectis as Efectis-report no Efectis-R0416. No part of this publication may be reproduced and/or published by print, photoprint, microfilm or any other means without the previous written consent of Efectis In case this report was drafted on instructions, the rights and obligations of contracting parties are subject to either the Standard Conditions for Research Instructions given to TNO, or the relevant agreement concluded between the contracting parties. Submitting the report for inspection to parties who have a direct interest is permitted.

10 Sponsor: Environmental Seals Ltd. Projectnumber: /13 Drawing 1: Ceiling/floor construction

11 Sponsor: Environmental Seals Ltd. Projectnumber: Furnace conditions 5/13 Centre for Fire Safety : 24/04/2007 Furnace temperatures Project : Ceiling/floor construction Projectnbr : ISOmax ISOmin TPL1 TPL2 TPL3 Temperature [ C] ===> Time [min] ===> Graph : B1 Centre for Fire Safety : 24/04/2007 Deviation of the fire curve Project : Ceiling/floor construction Projectnbr : ISO+ ISOdev_ISO 10 Deviation [%] ===> Time [min] ===> Graph : B2

12 Sponsor: Environmental Seals Ltd. Projectnumber: Centre for Fire Safety : 24/04/2007 Furnace over pressure 6/13 Project : Ceiling/floor construction Projectnbr : Over pressure [Pa] ===> Time [min] ===> Graph : B3 Figure C1: Positions of thermocouples and observations

13 Sponsor: Environmental Seals Ltd. Projectnumber: Graphs of test result Centre for Fire Safety : 24/04/2007 Surface temperatures (part 1) 7/13 Project : Ceiling/floor construction Projectnbr : Temperature [ C] ===> TC1 TC2 TC3 TC4 TC Time [min] ===> Graph : C2 Centre for Fire Safety : 24/04/2007 Surface temperatures (part 2) Project : Ceiling/floor construction Projectnbr : Temperature [ C] ===> TC6 TC7 TC8 TC9 TC Time [min] ===> Graph : C3

14 Sponsor: Environmental Seals Ltd. Projectnumber: Centre for Fire Safety : 24/04/2007 Ambient temperature 8/13 Project : Ceiling/floor construction Projectnbr : Temperature [ C] ===> Time [min] ===> Graph : C4

15 Sponsor: Environmental Seals Ltd. Projectnumber: Photos 9/13 Photo 1: Assembly of the construction. Photo 2: Holes in Fireline plasterboard for flush mounting boxes.

16 Sponsor: Environmental Seals Ltd. Projectnumber: /13 Photo 3: Flush mounting boxes and fitting used in the construction. Photo 4: Detail of flush mounting box with gaskets.

17 11/13 Photo 5: Fireside of the construction. Photo 6:. Smoke coming from the edge of the construction.

18 Sponsor: Environmental Seals Ltd. Projectnumber: /13 Photo 7: View of ceiling after the test. Photo 8: Fireside after the test.

19 Sponsor: Environmental Seals Ltd. Projectnumber: /13 Photo 9: Detail of ceiling boxes. Photo 10: Detail of two boxes in the ceiling.

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Sponsor Prepared by Avenue de Catalogne 11300 LIMOUX Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1: 2007

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1: 2007 CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1: 2007 Sponsor Prepared by Fiboveien 2 NO-4580 Lyngdal Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280 CB RIJSWIJK

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007 CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:007 Sponsor Prepared by Qualyline Srl Gewerbezone Reifenstein 18 - Sadrobre I-39040- Freienfeld(BZ), Italy and Stefano Mardegan

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 P.O. Box 1090 - NL-2280 CB Rijswijk Lange Kleiweg 5 - NL-2288 GH Rijswijk +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification

More information

Report Number BTC 17755F

Report Number BTC 17755F Leics. LE NP Tel () 4 Fax () 4 Email btc.testing@saintgobain.com Report Number BTC 77F A FIRE RESISTANCE TEST ON A LOADBEARING TIMBER JOIST FLOOR INCORPORATING 4mm x 7mm x 47mm SOLID JOISTS PROTECTED BY

More information

P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com

P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination according to EN 13381-4:2013 of the contribution to the fire resistance

More information

Fire-resistant barriers: background on requirements and determination method. Reading guide for test reports.

Fire-resistant barriers: background on requirements and determination method. Reading guide for test reports. Fire-resistant barriers: background on requirements and determination method. Reading guide for test reports. Report number C 1395-1E-RA-003 d.d. May 14, 2014 Fire-resistant barriers: background on requirements

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

NATIONAL ASSESSMENT GUIDELINE FOR THE KOMO PROCESS CERTIFICATE FOR THE INSTALLATION OF FACADE CLADDING USING ADHESIVE SYSTEMS

NATIONAL ASSESSMENT GUIDELINE FOR THE KOMO PROCESS CERTIFICATE FOR THE INSTALLATION OF FACADE CLADDING USING ADHESIVE SYSTEMS BRL 4104 01-02-2003 NATIONAL ASSESSMENT GUIDELINE FOR THE KOMO PROCESS CERTIFICATE FOR THE INSTALLATION OF FACADE CLADDING USING ADHESIVE SYSTEMS Accepted by the Harmonisatie Commissie Bouw of the Stichting

More information

CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES

CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES CERTIFICATE OF APPROVAL No CF 5055 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 1 st Industrial Area,

More information

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

Fire-resistance test on fire collars protecting a concrete slab penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Mario Lara Report number: FSP 1614 Date: 14 February 2014 Client:

More information

AUTHOR(S) Are W. Brandt CLIENT(S) STF22 A98833 Unrestricted Arne Johansen, DBE and Joakim Nielsen, SRV

AUTHOR(S) Are W. Brandt CLIENT(S) STF22 A98833 Unrestricted Arne Johansen, DBE and Joakim Nielsen, SRV TITLE SINTEF REPORT SINTEF Civil and Environmental Engineering Norwegian Fire Research Laboratory Address: Location: N-7034 Trondheim, NORWAY Tiller bru, Tiller Telephone: +47 73 59 10 78 Fax: +47 73 59

More information

Check-list for auditors. Audit visit at candidate registered laboratories

Check-list for auditors. Audit visit at candidate registered laboratories Check-list for auditors Audit visit at candidate registered laboratories 1 Contents Introduction Laboratory documentation required by the standard(s), available for inspection by the auditor Items to be

More information

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct

More information

Safety Storage Cabinets

Safety Storage Cabinets Safety Storage Cabinets Safe storage of flammables? The workplace without a fire resistant Safety Storage Cabinet Dangers, risks and your disadvantages... STORAGE ROOM Transport/working time - Increased

More information

REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012

REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.

More information

5.1. Smoke Sealing. General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1.

5.1. Smoke Sealing. General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1. v8 5.1 General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1. The performance criteria for smoke sealed doorsets is given by reference to BS5588 (and BS9999)

More information

Rockwool Flexi Insulation Application Guide

Rockwool Flexi Insulation Application Guide Pitched roof Rafters InterMediate floors INTERNAL partitions external Framed walls separating floors Separating Walls Rockwool Flexi Insulation Application Guide Ground floor The perfect fit for any framed

More information

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS INFORMATION PAPER IP 21/10 FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS Tom Lennon and Danny Hopkin The use of Structural Insulated Panel (SIP) systems in construction in the UK has increased

More information

Code of Practice for fire resisting metal doorsets

Code of Practice for fire resisting metal doorsets COP 1005 Code of Practice for fire resisting metal doorsets Scope The aim of this document is to provide guidance on the best practice for, and a better understanding of, hinged or pivoted fire resisting

More information

SMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC #100-2949-1 TESTED: MAY 23, 2008 REVISION

SMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC #100-2949-1 TESTED: MAY 23, 2008 REVISION SMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC #100-2949-1 TESTED: MAY 23, 2008 REVISION 2.0: OCTOBER 14, 2008 October 14, 2008 Client: Attn: Subject:

More information

(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark

(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This

More information

P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com

P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination according to EN 13381-4:2013 of the contribution to the fire resistance

More information

ENVIRONMENTAL INFORMATION APR 1200 products are made from glass mineral wool, one of the most environmentally friendly insulants available.

ENVIRONMENTAL INFORMATION APR 1200 products are made from glass mineral wool, one of the most environmentally friendly insulants available. APR 1200 Acoustic Partition Roll CI/Sfb Ref: APR002 Glass mineral wool roll designed to provide high levels of sound insulation in walls and floors to meet Part E (England & Wales) and Section 5 (Scotland)

More information

Tremco Fire Protection Systems Group Technical Bulletin

Tremco Fire Protection Systems Group Technical Bulletin Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,

More information

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method

More information

English Version. Fire safety storage cabinets - Part 2: Safety cabinets for pressurised gas cylinders

English Version. Fire safety storage cabinets - Part 2: Safety cabinets for pressurised gas cylinders EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM EN 14470-2 August 2006 ICS 13.220.40; 71.040.10 English Version Fire safety storage cabinets - Part 2: Safety cabinets for pressurised gas cylinders

More information

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01. Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice

More information

Approval Standard for Plastic Suspended Ceiling Panels

Approval Standard for Plastic Suspended Ceiling Panels Approval Standard for Plastic Suspended Ceiling Panels Class Number 4651 February 1978 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that

More information

Test Report No. C829QPEN

Test Report No. C829QPEN Institut für Solartechnik Hochschule für Technik Rapperswil Oberseestrasse 10, CH 8640 Rapperswil Tel +41 55 222 48 21, Fax +41 55 222 48 44 www.solarenergy.ch Ordered by: Westech Components Wuxi Co.,

More information

BS 476: Part 7: 1997. Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Eco-Sol Ltd. Document Reference: 304043

BS 476: Part 7: 1997. Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Eco-Sol Ltd. Document Reference: 304043 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification

More information

ISO 13845 INTERNATIONAL STANDARD

ISO 13845 INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 13845 First edition 2000-04-15 Plastics piping systems Elastomeric-sealing-ring-type socket joints for use with unplasticized poly(vinyl chloride) (PVC-U) pipes Test method for

More information

CERTIFICATE OF APPROVAL No CF 388 ALLEGION (UK) LIMITED

CERTIFICATE OF APPROVAL No CF 388 ALLEGION (UK) LIMITED CERTIFICATE OF APPROVAL No CF 88 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Bescot Crescent, Walsall,

More information

Universal systems for frameless doors

Universal systems for frameless doors EN Universal systems for frameless doors Xinnix Door Systems designs, creates and manufactures systems for internal doors. With our construction elements, it is possible to obtain easily an elegant and

More information

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of

More information

P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com

P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Investigation into the fire in the Heinenoordtunnel on 21 May 2014 Report no.

More information

FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England

FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England Fire is a life-threatening and destructive force, which if unchecked, can spread rapidly through a building. Every year,

More information

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch

More information

Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012

Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012 Medicine Hat Fire Department Special Event Requirements August 202 medicinehat.ca/fire The following is a standard guide for event organizers to ensure occupant safety and compliance with the Alberta Fire

More information

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory

More information

Test Report. Nr. 1370-001-12 dated 16.02.2012. Sound Absorption Coefficient in the Reverberation Room. Lammengatan 2 SE-360 30 Lammhult Sweden

Test Report. Nr. 1370-001-12 dated 16.02.2012. Sound Absorption Coefficient in the Reverberation Room. Lammengatan 2 SE-360 30 Lammhult Sweden Test Report Nr. 1370-001-12 dated 16.02.2012 Sound Absorption Coefficient in the Reverberation Room Customer: Abstracta AB Lammengatan 2 SE-360 30 Lammhult Sweden Test Object: Arrangement of Acoustic Panels

More information

Fire Doors Explained. Presented by - Peter Barker

Fire Doors Explained. Presented by - Peter Barker Fire Doors Explained Presented by - Peter Barker Objectives and Outline 1. The role of fire resisting doors 2. Proving the performance of fire resisting doors 3. Common problems and solutions The Role

More information

Installation Handbook. Interactive Fire Alarm System Release 3. Repeater Panel BU-320 / Information Panel BV-320

Installation Handbook. Interactive Fire Alarm System Release 3. Repeater Panel BU-320 / Information Panel BV-320 Interactive Fire Alarm System Release 3 Installation Handbook Repeater Panel BU-320 / Information Panel BV-320 Protecting life, environment and property... P-ASAFE/RI/DE Rev. A, 010531 COPYRIGHT This publication,

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13

More information

SCHOTT PYRANOVA Planline System

SCHOTT PYRANOVA Planline System Schott_050_Pyranova_E_RZ.fh8.07.005 0:50 Uhr Seite HOME T E C H The Planline system The patented glass fixing method is a clear multi- is based on a fire resistant double glazed allows quick and easy replacement

More information

ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape

ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape ModuSec Secure and efficient IT room solutions Turnkey Modular Construction Fast clean build to any size or shape Room in room Standalone external build Transportable Modusec SR Options Modusec SR Options

More information

CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED

CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED CERTIFICATE OF APPROVAL No CF 291 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.

More information

FIRE RATED GLAZING System Guide

FIRE RATED GLAZING System Guide SYSTEM GUIDE Issue date: 05-05-2015 Expiry date: 31-12-2016 System Guide Introduction Pyropanel Developments are specialists in fire rated glazing solutions, and our systems are designed for easy installation

More information

Plaisance 24. Sliding Systems. Sapa Building System

Plaisance 24. Sliding Systems. Sapa Building System Plaisance 24 Sliding Systems Sapa Building System Plaisance 24 is Sapa s noninsulated sliding system for windows and doors. Available as one-, two-, three- and fourrail solution. Among its features, there

More information

Product Data Sheet PDS050: ArmourFX polished plaster and decorative paint panels

Product Data Sheet PDS050: ArmourFX polished plaster and decorative paint panels PDS050: ArmourFX polished plaster and decorative paint panels Page 1 of 5 Document: 9070.12 Collection: 106: Product Data Sheets (PDS) Modified: 20/05/2016 16:42 Created: 04/04/2016 12:54 Armourcoat Ltd

More information

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized

More information

Confort 26. Sliding Systems. Sapa Building System

Confort 26. Sliding Systems. Sapa Building System Confort 26 Sliding Systems Sapa Building System Confort 26 is Sapa s thermally insulated sliding system for windows and doors. Available as two- and three-rail solution. Among its features, there are

More information

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration

More information

Fire testing procedure for concrete tunnel linings

Fire testing procedure for concrete tunnel linings P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Ministry of Infrastructure and the Environment (Rijkswaterstaat) Report no.

More information

BS 476: Part 7: 1997. Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Gurit (UK) Ltd. Document Reference: 312304

BS 476: Part 7: 1997. Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Gurit (UK) Ltd. Document Reference: 312304 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification

More information

WHI TEST REPORT #630-104800 FIRE RATED DOORS

WHI TEST REPORT #630-104800 FIRE RATED DOORS 8000 Whitepine Rd. Richmond, VA 23237 Tel: 800-446-7325 Fax: 800-448-2908 E-mail: weatherseal@sealeze.com WHI TEST REPORT #630-104800 FIRE RATED DOORS REPORT OF TEST OF GASKETING FOR RESISTANCE TO AIR

More information

Installation Guide. DEVIreg 530. Electronic Thermostat. www.devi.com

Installation Guide. DEVIreg 530. Electronic Thermostat. www.devi.com Installation Guide DEVIreg 530 Electronic Thermostat www.devi.com The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive

More information

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Kai Sirén and Ala Hasan Helsinki University of Technology, Finland Corresponding email: kai.siren@tkk.fi

More information

European Organisation for Technical Approvals

European Organisation for Technical Approvals Warrington Certification Limited, Holmesfield Road, Warrington, WA1 2DS Tel. +44 (0) 1925-646777 Fax +44 (0) 1925-646667 Member of EOTA Authorised and notified according to Article 10 of the Council Directive

More information

WTW SWANTM. Linear slot air diffusers of wall-to-wall design for ceilings

WTW SWANTM. Linear slot air diffusers of wall-to-wall design for ceilings SWANTM WTW Linear slot air diffusers of wall-to-wall design for ceilings Quick facts Wall-to-wall installation Diffuser face of light aluminium design 2, 3 or slots Horizontal/vertical air distribution

More information

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in 891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1181: PART 1: ISSUE 1.1 Series of Fire Growth Tests for LPCB Approval and Listing of Construction Product Systems Part One: Requirements and Tests for Built-up Cladding and

More information

How to measure absolute pressure using piezoresistive sensing elements

How to measure absolute pressure using piezoresistive sensing elements In sensor technology several different methods are used to measure pressure. It is usually differentiated between the measurement of relative, differential, and absolute pressure. The following article

More information

UX-30 PERFORMANCE TESTING SUMMARY REPORT Revision 0

UX-30 PERFORMANCE TESTING SUMMARY REPORT Revision 0 UX-30 PERFORMANCE TESTING SUMMARY REPORT Revision 0 Prepared By: Patrick L. Paquin, EnergySolutions Date Reviewed By: Mirza I. Baig, EnergySolutions Date Approved By: Thomas F. Dougherty, Columbiana Hi

More information

EN 14904. Export Manager Pulastic Sports Surfaces The Netherlands www.descol.nl

EN 14904. Export Manager Pulastic Sports Surfaces The Netherlands www.descol.nl Introduction by : Peter Minnée Export Manager Pulastic Sports Surfaces The Netherlands www.descol.nl Co-operation between European test institutes and standardization institutes formalized in 1961 Construction

More information

Fire safety in buildings and implementation of European fire test standards

Fire safety in buildings and implementation of European fire test standards Fire safety in buildings and implementation of European fire test standards Dr Debbie Smith OBE Chair of CEN TC127 Fire Safety BRE Global Ltd, UK 18 th June 2014 Part of the BRE Trust Construction Products

More information

Test Report: ICL/H11/979. BS 7837: 1996 Flammability performance for textiles used in the construction of marquees and similar textile structures.

Test Report: ICL/H11/979. BS 7837: 1996 Flammability performance for textiles used in the construction of marquees and similar textile structures. Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk

More information

Flexible Circuits and Interconnection Solutions

Flexible Circuits and Interconnection Solutions Flexible Circuits and Interconnection Solutions Introduction Our "Mission" is "to demonstrate through our unrivalled capability and service that Teknoflex sets the standard in the design, manufacture and

More information

Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests. Project report number 204505. Dr Corinne Williams and R Harrison

Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests. Project report number 204505. Dr Corinne Williams and R Harrison Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests Project report number 2455 Dr Corinne Williams and R Harrison February 24 Section 4: Benchmark tests Contents 4 Benchmark

More information

Installation Instructions

Installation Instructions Installation Instructions READ BEFORE INSTALLING UNIT For Low Profile Window Air Conditioner INSTALLATION WARNINGS AND CAUTION Carefully read the installation manual before beginning. Follow each step

More information

The risk assessment of fire damper installations

The risk assessment of fire damper installations The risk assessment of fire damper installations June 2010 Paul White OVERVIEW OVERVIEW The purpose of this presentation is to highlight that fire dampers form a key part of the passive fire protection

More information

fr fire retardant MARMOLEUM

fr fire retardant MARMOLEUM MARMOLEUM fr fire retardant MARMOLEUM fr 63038 63173 63174 sahara van gogh caribbean 63120 63163 63164 indian summer opera rosato 63182 63055 63030 blue fresco blue lapponia 63032 63146 63048 graphite

More information

EBDSPIR-PRM, EBDSPIR-PRM-IP

EBDSPIR-PRM, EBDSPIR-PRM-IP Product Guide EBDSPIR-PRM, EBDSPIR-PRM-IP Ceiling PIR presence/absence detector Overview The EBDSPIR-PRM PIR (passive infrared) presence detector provides automatic control of lighting loads with optional

More information

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER PSUM These technical specifications determinate a range of manufactured sizes and models of fire shutters (further only shutters)

More information

PCR: NPCR010 Building boards

PCR: NPCR010 Building boards ENVIRONMENTAL DECLARATION, ISO 14025 & ISO 21930 Gyproc Plasterboard 12,5 mm, GN13 NEPD NO: 223E Approved according to ISO14025, 8.1.4: 11.11.2011 Valid until : 11.11.2016 Verification of data: Independent

More information

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19

More information

ITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name.

ITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name. ITE Indirect calorifier ITE - 400/500/600/750/1000 0310 117 Installation, User and Service Manual Innovation has a name. Read this manual carefully Warning Read this manual carefully before starting the

More information

Structural fire design Eurocode 5-1.2 Timber structures

Structural fire design Eurocode 5-1.2 Timber structures Background and Applications Brussels, 18-20 February 2008 Dissemination of information workshop 1 Structural fire design Eurocode 5-1.2 Timber structures Jochen Fornather Austrian Standards Institute jochen.fornather@on-norm.at

More information

fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors

fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors Roxul Safe n Sound Sound Control and Fire Safety From One Batt Insulation Roxul

More information

Environmental Product Declaration EPD

Environmental Product Declaration EPD Environmental Product Declaration EPD May 2014 EPD The company Europrofil AB, founded 1982, is the leading producer of light gauge steel profiles for the building construction industry. Headquarters and

More information

Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual

Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual BR BO-01-02 Effective from June 1, 2000 Revision: March 26, 2002 Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual (Unofficial Manual) Technical Appraisal Department, Building

More information

Plaisance 50. Windows and doors. Sapa Building System

Plaisance 50. Windows and doors. Sapa Building System Plaisance 50 Windows and doors Sapa Building System Plaisance 50 is a non-thermally broken system for aluminium windows and doors with a building depth. The system offers a wide range of inward and outward

More information

HOSCH. Sprung blade scraper with heating system. Documentation Type B6C/H

HOSCH. Sprung blade scraper with heating system. Documentation Type B6C/H HOSCH Sprung blade scraper with heating system Documentation Type B6C/H 1 HOSCH Sprung blade scraper Type B6-C/H with heating system Table of contents 1 Intended use Page 3 1.1 Use 1.2 General operating

More information

Composite Panel Firewall Systems

Composite Panel Firewall Systems Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.

More information

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test

More information

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency

More information

Waterproofing of exterior walls at 7 Anderson Place, Queenstown

Waterproofing of exterior walls at 7 Anderson Place, Queenstown Waterproofing of exterior walls at 7 Anderson Place, Queenstown 1 The parties and the matter to be determined 1.1 This is a determination under Part 3 Subpart 1 of the Building Act 2004 ( the Act ) made

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1581: Issue 2.1 Requirements and tests for LPCB approval of nonload This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information

More information

VdS 2100-09en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS 2100-09en : 2011-05 (01)

VdS 2100-09en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS 2100-09en : 2011-05 (01) VdS Guidelines for water extinguishing systems VdS 2100-09en Requirements and test methods VdS 2100-09en : 2011-05 (01) Publishing house: VdS Schadenverhütung GmbH Amsterdamer Str. 172-174 50735 Köln,

More information

Basic Fire Door Requirements

Basic Fire Door Requirements TECHNICAL DATA SERIES S D I 118-01 Basic Fire Door Requirements 2001 Steel Door Institute STEEL DOOR INSTITUTE 30200 DETROIT ROAD - CLEVELAND, OHIO 44145 Technical Data Series SDI 118-2001 Basic Fire Door

More information

FAKRO SMART ATTIC LADDERS

FAKRO SMART ATTIC LADDERS SMART ATTIC LADDERS FAKRO SMART ATTIC LADDERS Applications Do you have any unused attic space that you can t get to? Get access to your attic quickly! Utilize the storage space that you are currently wasting

More information

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength. INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS Multi-Layer Technology provides increased strength. Specifically designed for interior applications. Compatible with most internal

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Effects of water mist on real large tunnel fires: Experimental determination of BLEVE-risk and tenability during growth and suppression

Effects of water mist on real large tunnel fires: Experimental determination of BLEVE-risk and tenability during growth and suppression Efectis Nederland BV Efectis Nederland report 28-Efectis-R425 Effects of water mist on real large tunnel fires: Experimental determination of BLEVE-risk and tenability during growth and suppression Efectis

More information

NATIONAL ASSESSMENT DIRECTIVE FOR THE PRODUCT CERTIFICATE FOR WOODEN SCAFFOLDING BOARDS

NATIONAL ASSESSMENT DIRECTIVE FOR THE PRODUCT CERTIFICATE FOR WOODEN SCAFFOLDING BOARDS BRL 9923 dd. 2004-10-01 NATIONAL ASSESSMENT DIRECTIVE FOR THE KOMO PRODUCT CERTIFICATE FOR WOODEN SCAFFOLDING BOARDS Technical area E2 Accepted by the Committee of Experts of SKH dd. 15 th September 2004

More information

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing Substrate, structural panel, bonded waterproofing The universal substrate for tiles Perfect covering No matter whether you work with mosaics or large format tiles, an absolutely level substrate with straight

More information

fischer Test Report Fixing Tests for Wienerberger Porotherm blocks

fischer Test Report Fixing Tests for Wienerberger Porotherm blocks fischer Test Report Fixing Tests for Wienerberger Porotherm blocks CONTENTS. Test Parameters... Substrates Tested Wienerberger Porotherm 90 &. Fixings Products Tested... Fischer Nylon UX Plug... Fischer

More information

BYG DTU. Thermal properties of window frame Type 1 Sheet: 1. Type: Side, top and bottom profile. Source file: Format: dwg/dxf bmp

BYG DTU. Thermal properties of window frame Type 1 Sheet: 1. Type: Side, top and bottom profile. Source file: Format: dwg/dxf bmp Thermal properties of window frame Type 1 Sheet: 1 Type: Side, top and bottom profile Profile: Frame profile made of wood and a GRP profile mounted with a sealed triple glazing unit. Materials: Wood GRP

More information

Liebert DCR Part of the SmartRow Offering. Installation Manual 3-6, Single/Redundant and 5-10 Racks Higher Capacity Cooling Units, 60Hz

Liebert DCR Part of the SmartRow Offering. Installation Manual 3-6, Single/Redundant and 5-10 Racks Higher Capacity Cooling Units, 60Hz Liebert DCR Part of the SmartRow Offering Installation Manual 3-6, Single/Redundant and 5-10 Racks Higher Capacity Cooling Units, 60Hz TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................................1

More information

Linear thermal transmittance of the assembly of the glazing and the frame in windows

Linear thermal transmittance of the assembly of the glazing and the frame in windows Linear thermal transmittance of the assembly of the glazing and the frame in windows Svend Svendsen,Professor, Technical University of Denmark; ss@byg.dtu.dk; www.byg.dtu.dk Jacob B. Laustsen, Assistant

More information