1 ELECTROMAGNETIC EFFECTS - Contents 1. Introduction 2. Generation of heat 3. Single-core cables armoured with steel wire or tape not to be used 4. Conductors installed in a ferromagnetic enclosure 5. Conductors entering a ferromagnetic enclosure 1. Introduction Electromagnetic effects from incorrectly installed cables of alternating current (a.c.) circuits can cause heat to be generated in the metal of ferromagnetic enclosures, such as steel conduit or steel equipment housings. To prevent such heat, which may damage cables and other materials, Regulation of BS 7671 calls for the following requirements to be met: (i) Single-core cables armoured with steel wire or tape must not be used for a.c. circuits. (ii) Conductors of a.c. circuits installed in ferromagnetic enclosures (such as steel conduit, trunking or ducting) must be arranged so that the conductors of all phases and the neutral conductor (if any) and the appropriate protective conductor of each circuit are contained in the same enclosure. (iii) Where such conductors enter a ferromagnetic enclosure, they must be arranged so that they are not individually surrounded with ferromagnetic material, or other provision must be made to prevent eddy (induced) currents. Requirements (i), (ii) and (iii) above are explained in items 3, 4 and 5, respectively, of this topic. Item 2 of this topic explains the mechanism by which heat can be generated in ferromagnetic materials surrounding conductors carrying alternating current. 2. Generation of heat When a conductor, such as a single-core cable, carries alternating current, the conductor is encircled by a magnetic field that alternates (changes in magnetic polarity) at the same frequency as the current. Where the conductor is also surrounded with metal, the alternating magnetic flux cuts the metal, inducing voltages in it which in turn cause circulating currents called eddy currents to flow (see Fig 1). The eddy currents produce power in the metal, due to its electrical resistance. In a single-phase or three-phase circuit the magnetic fields cancel each other out unless one or more of the conductors (phase or neutral) is outside the enclosure, in which case eddy currents will be produced. Electrical Safety Council ELECTRICAL SAFETY COUNCIL TECHNICAL MANUAL October of 6

2 Where metal surrounding a conductor (or some of the conductors) of an a.c. circuit is ferromagnetic, such as iron or steel, the power dissipated in the metal as a result of the eddy currents can cause the metal to heat up. This is because, with a ferromagnetic metal, the flux density of the alternating magnetic field is greater than with a non-ferromagnetic metal, such as aluminium or copper, due to the high relative permeabilities of ferromagnetic metals. Hence the eddy currents, and consequently the power dissipated in the metal, are greater if the metal is ferromagnetic, making the metal liable to heat up. If the metal is non-ferromagnetic, no noticeable heating of it due to eddy currents will occur. Metal surrounding a single conductor carrying alternating current Warning! This arrangement is not permitted by BS 7671 where the metal surrounding the conductor is ferromagnetic (such as steel) Metal surrounding conductor (eg tube) Alternating magnetic field Conductor Typical eddy current loop Alternating current Fig 1 Note: Eddy currents (as shown in Fig 1) are still produced if the metal surrounds some, but not all, of the conductors of an a.c. circuit, as the magnetic fields surrounding the conductors do not then cancel each other out. Eddy current heating of metal does not occur if it surrounds all the conductors of an a.c. circuit collectively, even if the metal is ferromagnetic. This is because, in such circumstances, the overall sum of the magnetic fields encircling the conductors is equal to zero. In this context, it should be noted that BS 7671 regards the circuit protective conductor as one of the circuit conductors (unless formed by the enclosing metal, such as conduit), as it has to carry current in certain circumstances. Electrical Safety Council ELECTRICAL SAFETY COUNCIL TECHNICAL MANUAL October of 6

3 3. Single-core cables armoured with steel wire or tape not to be used Regulation does not permit the use of single-core cables armoured with steel wire or tape for a.c. circuits. Such use would automatically result in conductors being individually surrounded in ferromagnetic material, with the consequent risk of the armouring being heated up as a result of eddy currents. 4. Conductors installed in a ferromagnetic enclosure Where a ferromagnetic enclosure, such as steel conduit, trunking or ducting, is used to contain conductors of a.c. circuits, Regulation requires the conductors of all phases and the neutral conductor (if any) and the appropriate protective conductor of each circuit to be contained in the same enclosure. This is so that the overall sum of the magnetic fields encircling the contained conductors when carrying a.c. current will be zero, so there will be no resulting eddy current heating of the enclosure. The rule may appear to be broken in the case of a steel conduit or other ferromagnetic enclosure taking the cables to a lighting switch position. However, so long as all the associated unswitched and switched phase conductors are contained in the same enclosure, as shown in Fig 2, the magnetic fields add up to zero, and hence no eddy currents (or heat) are produced in the metal of the enclosure. Lighting switch wiring contained in a ferromagnetic enclosure Neutral Ferromagnetic enclosure (eg steel conduit) Phase All associated unswitched and switched phase conductors contained in the same enclosure Luminaires Lighting switch (2 - gang) Fig 2 Electrical Safety Council ELECTRICAL SAFETY COUNCIL TECHNICAL MANUAL October of 6

4 5. Conductors entering a ferromagnetic enclosure Where conductors of an a.c. circuit enter a ferromagnetic enclosure, Regulation requires that one of the following two arrangements is provided: The conductors are arranged so that they are not individually surrounded with ferromagnetic material. An example of this is given in Fig 3, which shows cables supplying an item of switchgear having a ferromagnetic enclosure, entering the enclosure from steel trunking though a single entry hole. Some other provision is made to prevent eddy currents. For example, the conductors may enter the enclosure through separate holes of a plate made of either non-ferromagnetic metal (such as aluminium, brass or some types of stainless steel * ) or non-metallic material (see Fig 4), or through separate holes of a ferromagnetic plate (such as steel) having a slot which joins the holes to each other, so that they effectively form a single hole (see Fig 5). It should be remembered that where a plate containing such a slot is used to protect against contact with live parts (protection against direct contact), the width of the slot must be small enough to meet the requirements of Regulation Group Cables all passing through the same entry hole Item of switchgear having a ferromagnetic enclosure L1 L2 L3 N Steel trunking Fig 3 * Most stainless steels are not ferromagnetic but some are. The application of a magnet will determine whether or not a particular sample is ferromagnetic. The material should be selected to meet the requirements of Regulation for enclosure of connections. To satisfy Regulation Group , the width of a slot must be less than 1 mm (IP4X) if in a readily accessible top surface, or not more than 12 mm (IP2X or IPXXB) if in any other surface. Electrical Safety Council ELECTRICAL SAFETY COUNCIL TECHNICAL MANUAL October of 6

5 Cables passing through separate holes of a non-ferromagnetic metal plate or a non-metallic plate Conductors (sheathed with non-ferromagnetic material) Plate of non-ferromagnetic metal or non-metallic material L1 L2L3 N Ferromagnetic enclosure Fig 4 Cables passing through separate holes of a ferromagnetic metal plate having a slot Conductors (sheathed with non-ferromagnetic material) Slotted ferromagnetic plate L1 L2L3 N Ferromagnetic enclosure Slot joining holes Fig 5 Electrical Safety Council ELECTRICAL SAFETY COUNCIL TECHNICAL MANUAL October of 6

6 Topics referred to in this text: None Topics not referred to in this text, which are related and may be of interest: None listed BS 7671 (Requirements for electrical installations) Some of the most important requirements are found in: electromagnetic effects Electrical Safety Council ELECTRICAL SAFETY COUNCIL TECHNICAL MANUAL October of 6

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations

More information

Theory of Heating by Induction

Theory of Heating by Induction CHAPTER 2 Theory of Heating by Induction INDUCTION HEATING was first noted when it was found that heat was produced in transformer and motor windings, as mentioned in the Chapter Heat Treating of Metal

More information

Screened cable and data cable segregation

Screened cable and data cable segregation December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

Power Separation Guidelines for SYSTIMAX Installations

Power Separation Guidelines for SYSTIMAX Installations SYSTIMAX Solutions Power Separation Guidelines for SYSTIMAX Installations Design and installation guidelines August 2011 www.commscope.com 1.0 General These guidelines are based on extensive testing and

More information

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor. DC Generators DC generators are widely used to produce a DC voltage. The amount of voltage produced depends on a variety of factors. EO 1.5 LIST the three conditions necessary to induce a voltage into

More information

PHYS 222 Spring 2012 Final Exam. Closed books, notes, etc. No electronic device except a calculator.

PHYS 222 Spring 2012 Final Exam. Closed books, notes, etc. No electronic device except a calculator. PHYS 222 Spring 2012 Final Exam Closed books, notes, etc. No electronic device except a calculator. NAME: (all questions with equal weight) 1. If the distance between two point charges is tripled, the

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters 8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

PROTECTION AGAINST ELECTRIC SHOCK by John Ware 16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Pyrotenax SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Contents Introduction This section provides an overview of general circuit design considerations and installation guidelines for a Pyrotenax System

More information

Chapter 7. Magnetism and Electromagnetism ISU EE. C.Y. Lee

Chapter 7. Magnetism and Electromagnetism ISU EE. C.Y. Lee Chapter 7 Magnetism and Electromagnetism Objectives Explain the principles of the magnetic field Explain the principles of electromagnetism Describe the principle of operation for several types of electromagnetic

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

chapter6 Basic electrical circuitry and applications Unit 2 Outcome 3

chapter6 Basic electrical circuitry and applications Unit 2 Outcome 3 Basic electrical circuitry and applications chapter6 Unit 2 Outcome 3 The primary role of an electrician is the installation of electrical circuits and applications. In order to install any type of application,

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

Inductors & Inductance. Electronic Components

Inductors & Inductance. Electronic Components Electronic Components Induction In 1824, Oersted discovered that current passing though a coil created a magnetic field capable of shifting a compass needle. Seven years later, Faraday and Henry discovered

More information

H45 LED - Direct and indirect pendant

H45 LED - Direct and indirect pendant RAL 01 10 00 IP 20 230V 50/60Hz Specifications Direct and indirect light pendant linear luminaire. Aluminium profile. Diffusers in frosted polycarbonate profile. Driver included. Supplied with clear base,

More information

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE

More information

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question. MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question. 1) If the voltage at a point in space is zero, then the electric field must be A) zero. B) positive.

More information

Cable Size Selection for Energy Efficiency

Cable Size Selection for Energy Efficiency Cable Size Selection for Energy Efficiency Introduction The traditional method for determining the appropriate cable size for a particular installation involves the selection of the smallest size conductor

More information

Edmund Li. Where is defined as the mutual inductance between and and has the SI units of Henries (H).

Edmund Li. Where is defined as the mutual inductance between and and has the SI units of Henries (H). INDUCTANCE MUTUAL INDUCTANCE If we consider two neighbouring closed loops and with bounding surfaces respectively then a current through will create a magnetic field which will link with as the flux passes

More information

Estimation results on the location error when using cable locator

Estimation results on the location error when using cable locator Estimation results on the location error when using cable locator HITOSHI KIJIMA TOMOHIKO HATTORI Tokaigakuin University 5-68 Naka Kirino Kagamigahara, Gifu 504-8511 JAPAN kijima@tokaigakuin-u.ac.jp, spiezswiss@yahoo.co.jp

More information

The Do s and Don ts of Pressure Transducers

The Do s and Don ts of Pressure Transducers The Do s and Don ts of Pressure Transducers ABSTRACT When specifying a pressure transducer for a process measurement, a number of items have to be considered. Some of the more important ones are discussed

More information

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331) Lab 5: Single-phase transformer operations. Objective: to examine the design of single-phase transformers; to study the voltage and current ratios of transformers; to study the voltage regulation of the

More information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to

More information

Network Standard Advice No. 1420C 9/6/2011

Network Standard Advice No. 1420C 9/6/2011 Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides

More information

ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1

ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1 ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1 Design and Planning Specification for New Low Voltage Installations for Housing Developments 1. SCOPE This appendix to ENA

More information

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80 Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the

More information

Homework #11 203-1-1721 Physics 2 for Students of Mechanical Engineering

Homework #11 203-1-1721 Physics 2 for Students of Mechanical Engineering Homework #11 203-1-1721 Physics 2 for Students of Mechanical Engineering 2. A circular coil has a 10.3 cm radius and consists of 34 closely wound turns of wire. An externally produced magnetic field of

More information

Application Note AN:005. FPA Printed Circuit Board Layout Guidelines. Introduction Contents. The Importance of Board Layout

Application Note AN:005. FPA Printed Circuit Board Layout Guidelines. Introduction Contents. The Importance of Board Layout FPA Printed Circuit Board Layout Guidelines By Paul Yeaman Principal Product Line Engineer V I Chip Strategic Accounts Introduction Contents Page Introduction 1 The Importance of 1 Board Layout Low DC

More information

Alternating Current and Direct Current

Alternating Current and Direct Current K Hinds 2012 1 Alternating Current and Direct Current Direct Current This is a Current or Voltage which has a constant polarity. That is, either a positive or negative value. K Hinds 2012 2 Alternating

More information

Grounding & Bonding Why it is done And How to Install Properly

Grounding & Bonding Why it is done And How to Install Properly Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.

More information

Grounding Demystified

Grounding Demystified Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%

More information

ScottishPower Distribution Cables & Equipment. Metal Theft

ScottishPower Distribution Cables & Equipment. Metal Theft ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated

More information

Lab 14: 3-phase alternator.

Lab 14: 3-phase alternator. Lab 14: 3-phase alternator. Objective: to obtain the no-load saturation curve of the alternator; to determine the voltage regulation characteristic of the alternator with resistive, capacitive, and inductive

More information

DEGREE: Bachelor's Degree in Industrial Electronics and Automation COURSE: 1º TERM: 2º WEEKLY PLANNING

DEGREE: Bachelor's Degree in Industrial Electronics and Automation COURSE: 1º TERM: 2º WEEKLY PLANNING SESSION WEEK COURSE: Physics II DEGREE: Bachelor's Degree in Industrial Electronics and Automation COURSE: 1º TERM: 2º WEEKLY PLANNING DESCRIPTION GROUPS (mark ) Indicate YES/NO If the session needs 2

More information

Magnetic proximity switches

Magnetic proximity switches Magnetic proximity switches Magnetic proximity switches Overview Page 38 Functional principle and installation Page 39 Cylindrical designs Page 41 Rectangular designs Page 42 37 Kurzübersicht Magnetoresistive

More information

Slide 1 / 26. Inductance. 2011 by Bryan Pflueger

Slide 1 / 26. Inductance. 2011 by Bryan Pflueger Slide 1 / 26 Inductance 2011 by Bryan Pflueger Slide 2 / 26 Mutual Inductance If two coils of wire are placed near each other and have a current passing through them, they will each induce an emf on one

More information

C03D Group. Magnetic Fields of Underground Cables. 10/24/2011 ICC Fall 2011 Meeting, Denver 24 October - 1 -

C03D Group. Magnetic Fields of Underground Cables. 10/24/2011 ICC Fall 2011 Meeting, Denver 24 October - 1 - C03D Group Magnetic Fields of Underground Cables Jicable'11 Digest of Papers about EMF Frédéric LESUR 10/24/2011 ICC Fall 2011 Meeting, Denver 24 October - 1 - Impact of electromagnetic fields on current

More information

Current, Resistance and Electromotive Force. Young and Freedman Chapter 25

Current, Resistance and Electromotive Force. Young and Freedman Chapter 25 Current, Resistance and Electromotive Force Young and Freedman Chapter 25 Electric Current: Analogy, water flowing in a pipe H 2 0 gallons/minute Flow Rate is the NET amount of water passing through a

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

chapter8 Testing and commissioning Unit 2 outcome 2

chapter8 Testing and commissioning Unit 2 outcome 2 Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law. 260 17-1 I. THEORY EXPERIMENT 17 QUALITATIVE STUDY OF INDUCED EMF Along the extended central axis of a bar magnet, the magnetic field vector B r, on the side nearer the North pole, points away from this

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

CURRENT RATINGS MORE THAN A CABLE

CURRENT RATINGS MORE THAN A CABLE CURRENT RTINGS Updated for the 17th Edition of the IEE Wiring Regulations MORE THN CBLE C O M P N Y EI CBLES, DURHM ROD, BIRTLEY, CO DURHM. DH3 2R Tel: +44 (0)191 410 3111 Fax: +44 (0)191 410 8312 E-mail:

More information

Introduction to Electricity & Magnetism. Dr Lisa Jardine-Wright Cavendish Laboratory

Introduction to Electricity & Magnetism. Dr Lisa Jardine-Wright Cavendish Laboratory Introduction to Electricity & Magnetism Dr Lisa Jardine-Wright Cavendish Laboratory Examples of uses of electricity Christmas lights Cars Electronic devices Human body Electricity? Electricity is the presence

More information

Chapter 11. Inductors ISU EE. C.Y. Lee

Chapter 11. Inductors ISU EE. C.Y. Lee Chapter 11 Inductors Objectives Describe the basic structure and characteristics of an inductor Discuss various types of inductors Analyze series inductors Analyze parallel inductors Analyze inductive

More information

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers 25 januari 2012 Topics - Theory of current transformers (CTs) - Equivalent Circuit for

More information

5. Measurement of a magnetic field

5. Measurement of a magnetic field H 5. Measurement of a magnetic field 5.1 Introduction Magnetic fields play an important role in physics and engineering. In this experiment, three different methods are examined for the measurement of

More information

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

MASTER ELECTRICIAN CODE EXAMINATION EXAMINATION REFERENCE MATERIAL AND CONTENT OUTLINE. Answers to sample questions: CONTENT OUTLINE

MASTER ELECTRICIAN CODE EXAMINATION EXAMINATION REFERENCE MATERIAL AND CONTENT OUTLINE. Answers to sample questions: CONTENT OUTLINE Answers to sample questions: Question Answer Reference 1 4 Section 362.12(6) 2 2 Table 310-16; 310.15(B)(2)(a) 3 4 Table. 250-66 4 2 Table 430.250 & 430.52 5 2 American Electrician Handbook, Figure 7-159

More information

Session 14 Cable Support Systems

Session 14 Cable Support Systems Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load

More information

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the

More information

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao. x x. x x. Figure 10: Cross sectional view

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao. x x. x x. Figure 10: Cross sectional view 4 Armature Windings Main field Commutator & Brush Compole field haft v Compensating winding Armature winding Yoke Figure 10: Cross sectional view Fig. 10 gives the cross sectional view of a modern d.c.

More information

Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features

Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features Metallic and Non-Metallic Air Conditioning Disconnects A Complete Family of Disconnects with Exclusive Time Saving Features Enclosed Molded Case Disconnect Switch Not-Fusible The preferred molded case

More information

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49 Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large

More information

April 1. Physics 272. Spring 2014 http://www.phys.hawaii.edu/~philipvd/pvd_14_spring_272_uhm.html. Prof. Philip von Doetinchem philipvd@hawaii.

April 1. Physics 272. Spring 2014 http://www.phys.hawaii.edu/~philipvd/pvd_14_spring_272_uhm.html. Prof. Philip von Doetinchem philipvd@hawaii. Physics 272 April 1 Spring 2014 http://www.phys.hawaii.edu/~philipvd/pvd_14_spring_272_uhm.html Prof. Philip von Doetinchem philipvd@hawaii.edu Phys272 - Spring 14 - von Doetinchem - 164 Summary Gauss's

More information

Circuit Electrical Testing

Circuit Electrical Testing Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

SYMMETRIC 1A POWER SUPPLY K8042

SYMMETRIC 1A POWER SUPPLY K8042 SYMMETRIC 1A POWER SUPPLY K8042 Low cost universal symmetric power supply ILLUSTRATED ASSEMBLY MANUAL H8042IP-1 Features & Specifications Features low cost universal symmetric power supply just add a suitable

More information

Typical TIG-plasma solutions

Typical TIG-plasma solutions Typical -plasma solutions 2228-005 2003-670 Boilers maker solutions 2004-257 1210-064 1210-067 64 3638-008 2008-400 1415-014 2000-169 2003-204 1467-003 2000-343 2000-160 Pipework solutions or plasma welded

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

Lecture 22. Inductance. Magnetic Field Energy. Outline:

Lecture 22. Inductance. Magnetic Field Energy. Outline: Lecture 22. Inductance. Magnetic Field Energy. Outline: Self-induction and self-inductance. Inductance of a solenoid. The energy of a magnetic field. Alternative definition of inductance. Mutual Inductance.

More information

NATIONAL COIR RESEARCH AND MANAGEMENT INSTITUTE (NCRMI) KUDAPPANAKUNNU.P.O, THIRUVANANTHAPURAM NOTICE INVITING LIMITED QUOTATION

NATIONAL COIR RESEARCH AND MANAGEMENT INSTITUTE (NCRMI) KUDAPPANAKUNNU.P.O, THIRUVANANTHAPURAM NOTICE INVITING LIMITED QUOTATION NATIONAL COIR RESEARCH AND MANAGEMENT INSTITUTE (NCRMI) KUDAPPANAKUNNU.P.O, THIRUVANANTHAPURAM NOTICE INVITING LIMITED QUOTATION NCRMI/LIB/ELE001/15 4.09.2015 Competitive sealed quotations are invited

More information

INTRODUCTION TO CHAPTER 3 WIRING METHODS AND MATERIALS

INTRODUCTION TO CHAPTER 3 WIRING METHODS AND MATERIALS CHAPTER 3 WIRING METHODS AND MATERIALS INTRODUCTION TO CHAPTER 3 WIRING METHODS AND MATERIALS Chapter 2 provided the general rules for wiring and protection of conductors, and was primarily concerned with

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

1. The diagram below represents magnetic lines of force within a region of space.

1. The diagram below represents magnetic lines of force within a region of space. 1. The diagram below represents magnetic lines of force within a region of space. 4. In which diagram below is the magnetic flux density at point P greatest? (1) (3) (2) (4) The magnetic field is strongest

More information

Motor Fundamentals. DC Motor

Motor Fundamentals. DC Motor Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical

More information

Transformer Calculations

Transformer Calculations Transformer Calculations Transformers Transformers are one of the most basic yet practical devices used today. No matter where you are there is always a transformer nearby. They are used throughout alternating-current

More information

ElectroMagnetic Induction. AP Physics B

ElectroMagnetic Induction. AP Physics B ElectroMagnetic Induction AP Physics B What is E/M Induction? Electromagnetic Induction is the process of using magnetic fields to produce voltage, and in a complete circuit, a current. Michael Faraday

More information

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

FREQUENTLY ASKED QUESTIONS

FREQUENTLY ASKED QUESTIONS September 2011 FREQUENTLY ASKED QUESTIONS Wiring Rules The new edition of the Australian/New Zealand Standard for Wiring Rules (AS/NZS 3000:2007) was released in November 2007 and revised by Amendment

More information

Harmonics in your electrical system

Harmonics in your electrical system Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses

More information

DIOCESE OF LINCOLN GUIDELINES

DIOCESE OF LINCOLN GUIDELINES DIOCESE OF LINCOLN GUIDELINES FOR ELECTRICAL INSTALLATIONS INSIDE CHURCHES Diocesan Advisory Committee for the Care of Churches Revised March 2006 Electrical Installations inside Churches As with all

More information

HARMONISATION OF WIRING COLOUR CODES Practical Guidelines

HARMONISATION OF WIRING COLOUR CODES Practical Guidelines HARMOISATIO OF WIRIG COLOUR CODES Practical Guidelines Acknowledgments: We are grateful to the IEE for their permission to reproduce sections of BS 7671 and The Electrician s Guide to the Building Regulations.

More information

Indoor Environment Electromagnetic Radiation

Indoor Environment Electromagnetic Radiation Indoor Environment Electromagnetic Radiation Purpose: To increase the students awareness of the sources of electric and magnetic fields and the potential for adverse health effects from prolonged exposure

More information

Introduction to Data Centre Design

Introduction to Data Centre Design Introduction to Data Centre Design Barry Elliott BSc RCDD MBA CEng Earthing, grounding and bonding November 09 Earthing what s the point Safety from electrical hazards Reliable signal reference within

More information

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET

More information

2. Permanent Magnet (De-) Magnetization 2.1 Methodology

2. Permanent Magnet (De-) Magnetization 2.1 Methodology Permanent Magnet (De-) Magnetization and Soft Iron Hysteresis Effects: A comparison of FE analysis techniques A.M. Michaelides, J. Simkin, P. Kirby and C.P. Riley Cobham Technical Services Vector Fields

More information

Tutorial One: Calculation of leakage inductance of transformer using FEM. 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No.

Tutorial One: Calculation of leakage inductance of transformer using FEM. 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No. Tutorial One: Calculation of leakage inductance of transformer using FEM Consider a transformer with the following rating: 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No. of HV turns = 980 Although

More information

13 ELECTRIC MOTORS. 13.1 Basic Relations

13 ELECTRIC MOTORS. 13.1 Basic Relations 13 ELECTRIC MOTORS Modern underwater vehicles and surface vessels are making increased use of electrical actuators, for all range of tasks including weaponry, control surfaces, and main propulsion. This

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

AN INTRODUCTION TO MAGNETIC AND UTILITY LOCATING BASICS

AN INTRODUCTION TO MAGNETIC AND UTILITY LOCATING BASICS AN INTRODUCTION TO MAGNETIC AND UTILITY LOCATING BASICS TABLE OF CONTENTS AN INTRODUCTION TO PIPE AND CABLE LOCATING BASICS how to apply signal.................1 power levels.......................1 conductive

More information

Chapter 24. Three-Phase Voltage Generation

Chapter 24. Three-Phase Voltage Generation Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

Separation of power and information technology cabling

Separation of power and information technology cabling Technical bulletin Separation of power and information technology cabling Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based on the current

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin January 2016 CEC-10 [rev-9] Page 1 of 8 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and Bonding Rule 10-204 Grounding Connections for Alternating-Current

More information

AC Motor Speed. n s = synchronous speed (in RPM), f = frequency (in Hz), and p = the number of poles

AC Motor Speed. n s = synchronous speed (in RPM), f = frequency (in Hz), and p = the number of poles AC Induction Motors Simplest and most rugged electric motor Consists of wound stator and rotor assembly AC in the primary member (stator) induces current in the secondary member (rotor) Combined electromagnetic

More information

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design .8 Ex-Recess-mounted, ceiling emergency light fittings in compact metal design RLF/RLF-INOX 50 18-58 W / RLF/RLF-INOX 50... N 18-36 W (Zone 1,, 1, ) The explosion-protected lighting concept for clean rooms

More information