Installation Instructions - TD3 Case Display. P/N (red LEDs, sealed) P/N (green LEDs, sealed)
|
|
- Bennett Howard
- 7 years ago
- Views:
Transcription
1 TECHNICAL BULLETIN Installation Instructions - TD3 Case Display Introduction P/N (red LEDs, sealed) P/N (green LEDs, sealed) The TD3 is a LonWorks Echelon based refrigeration case display that uses three inputs to monitor discharge air temperature, product probe temperature, and a defrost termination sensor, which can be either a temperature or digital sensor. The TD3 sends information to an Einstein or E2 RX controller (P/N 830-XXXX) via the Echelon Network. The controller can then control refrigeration in the circuit according to the input data. Installation The TD3 is designed to be mounted on the face of a refrigeration display case. Since the unit is sealed, all that is needed for installation is a 1 hole for the wiring harness and two pilot holes (1/ 8 ) for #6 mounting screws. On the back of the unit is a wiring sleeve that is designed to keep moisture from entering the display unit and case through the wiring hole. For programming purposes, be sure that before mounting the unit that you remove the Echelon address sticker off the bottom of the unit. Retain this sticker and record the location of the TD3 from which it came. COMPUTER PROCESS CONTROLS - Page 1
2 Wiring There are five sets of wires that come from the back of the unit. These are to supply power, connect the unit to the network, and to connect the unit to up to three sensors. Power The TD3 requires 4VA power supplied by a 24VAC Class 2 transformer. CPC specs a 10VA 24VAC Class 2 transformer (P/N ) that can power one TD3. If you wish to power multiple TD3s off a single transformer, use one of the transformers listed in Table 1. Xformer P/N VA Rating Input Voltage Center Tap? VA 110 VAC No VA 110 VAC No VA 220 VAC No VA Multi-tap (110/ Yes* 208/220 VAC) VA 110 VAC No VA 220 VAC No VA Multi-tap (110/ 208/220 VAC) Yes* * Refer to Using Center-Tapped Transformers to Power TD3s on page 3 for more information Table 1 - Class 2 Transformers for Echelon Devices COMPUTER PROCESS CONTROLS - Page 2
3 Using Center-Tapped Transformers to Power TD3s The 56VA and 80VA Multi-Tap transformers may only be used to power TD3s if the following three rules are followed: 1. Do NOT connect the black/green TD3 ground wire to the center tap (Earth ground only). 2. Do NOT use the same transformer to power center-tapped devices along with the TD3. Mixing one or more TD3s with a device that requires a center tap connection will destroy the TD3 board. 3. Do NOT ground any side of the secondary. Determining the Correct Wire Gage The wire gage to use when wiring from the transformer to the TD3 depends on the amount of distance required, as well as whether or not you will be powering multiple TD3s from a single transformer. Single-TD3 Transformer Power Wiring If a transformer will be connected to only one TD3, consult Table 2 for the gage of wire to use based on the length of wire you must use. Wire Length from Transformer Wire Gage to TD3 30 feet or less 18AWG feet 16AWG feet 14AWG Table 2 - Wire Gages for Single-TD3 Transformer Installations Multiple Devices Connected to One Transformer When multiple devices are powered by one transformer, the wire gage and length depends on the total number of VA used by all devices. Add up the total number of VA for all devices connected to the transformer (Table 3 lists typical CPC devices and their VA ratings). Controller VA VAC Center Tapped? 16AI 5 24 Yes* 8RO Yes* 4AO Yes* 8DO Yes* 8IO/ARTC No MultiFlex Yes* Table 3 - Class 2 Transformers for Echelon Devices COMPUTER PROCESS CONTROLS - Page 3
4 Use the total VA to calculate the maximum wire length by gage for the TD3 and all other devices connected to this transformer: 14 AWG max length = 1920 / (VA) 16 AWG max length = 1200 / (VA) 18 AWG max length = 738 / (VA) Example: For an 80 VA load, the max wire lengths between TD3 and transformer would be: 14 AWG: 1920 / 80 = 24 feet 16 AWG: 1200 / 80 = 15 feet 18 AWG: 738 / VA = 9.25 feet Power Wiring Connect the Red leads on the TD3 to 24VAC power. Connect the Green/Black wire to earth ground. Secure all wiring in such a way as to prevent foot traffic or moving objects from pulling or damaging the wire. Echelon Network MultiFlex No (Other) ESR No TD No Gateway 5 24 No * Refer to Using Center-Tapped Transformers to Power TD3s on page 3 for more information Table 3 - Class 2 Transformers for Echelon Devices The two blue wires on the cable harness are for connecting the TD3 to the Echelon cable that leads back to its parent Einstein. The only Echelon network cable to be used with CPC networks is Level IV, shielded, stranded, twisted pair 22 AWG (available from CPC, P/N non-plenum, P/N plenum). Before attempting to wire the TD3 to the Echelon network, you should consult the chapter in the Einstein RX User s Guide (P/N ) or E2 User s Guide (P/N ) regarding structuring an Echelon network. Using a Stub to Network the TD3 Since TD3s are typically mounted at the top of a case, the easiest way to daisy-chain TD3s on the Echelon network is to use a stub. As demonstrated in Figure 1, a stub is a length of special Echelon wire with two twisted pair leads instead of one pair, leading from (1) the TD3 cable harness to (2) the kickplate at the bottom of the case. This will allow field technicians to (3) connect the COMPUTER PROCESS CONTROLS - Page 4
5 TD3s to the Echelon network by crimping the Echelon cable leads to the stub leads at the kickplate. Figure 1 - Using a Stub with TD3 Stub Wire Type and Part Number The wire type necessary for the stub is Level IV, shielded, stranded, two pair 22 AWG (CPC P/N ). Connecting the TD3 to the Stub The Echelon stub should have two twisted pair leads: one colored blue and white/blue, and the other colored orange and white/orange. As shown in Figure 2, snap the connector end of the stub into the Molex connector at the end of the BLUE leads on the TD3 wiring harness. Figure 2 - Connecting the Stub to the TD3 Cable Harness Wiring the Stub to The Echelon Network The other end of the Echelon wire stub will be used to connect the TD3 to the Echelon network. This end of the stub should extend into the kickplate of the case for easy access to wiring. COMPUTER PROCESS CONTROLS - Page 5
6 Note: Use only CPC-approved Super B Wire Connectors from Dolphin Components Corp (P/N ) for all Echelon wire crimping connections. Never use wire nuts or terminal blocks for Echelon wiring. Figure 3 - Field Wiring TD3s to Echelon Network 1. Connect the signal-carrying wires from the incoming Echelon cable to either the BLUE & BLUE/WHITE or ORANGE & ORANGE/WHITE pairs of leads on the stub. 2. Connect the signal-carrying wires from the outgoing Echelon cable to the remaining pair of leads on the stub. 3. Crimp the SHIELD wires of all Echelon cables (including the stub) together (keeping the lengths of the exposed shield wire from the cable jacket to the connector as short as possible), and connect them to an earth ground. It is recommended you crimp the shield wires to a length of 14AWG wire (no longer than six inches) and terminate the other end of this wire to a lug somewhere on the case chassis. Note: When using stubbed TD3s on an Echelon network, count the length of each stub twice when determining the total length of Echelon network cable. Terminating a Daisy Chain (When TD3 Is On the End) If a TD3 is at the end of a daisy chain network segment, you will need to terminate the Echelon network at the TD3. To do this, you will need a Daisy Chain Termination Block (CPC P/N ). Wire the Daisy Chain Termination Block to one pair of the TD3 stub leads, as shown in Figure 4. Crimp the shield wires of the incoming Echelon daisy-chain and the TD3 stub together and ground them to an Earth ground; do not connect them to the middle terminal of the termination block. COMPUTER PROCESS CONTROLS - Page 6
7 Sensors Figure 4 - Terminating the TD3 at the End of a Daisy Chain The three sets of wires with connector ends are for connecting sensors to the unit. The Green pair is for a standard discharge air temperature sensor (P/N ). The White pair is for a product probe sensor (P/N ). The Orange pair is for either an analog or digital defrost termination sensor. All sensors are supplied by CPC and come fitted with compatible connector ends. Wiring TD3 For High Moisture Areas If the TD3 is to be mounted and wired in an area with exposure to large amounts of moisture (for example, near water sprays), it is strongly recommended you clip the Molex connectors off the TD3 wiring pigtail (for both sensors and Echelon) and instead crimp the wires with water-resistant wire connectors (CPC P/N , Super B Wire Connectors from Dolphin Components Corp.). These connectors should be used for all wire splices that must occur within the high-moisture area. Failing to do this can result in moisture being drawn up through the sensor wiring and/ or Echelon wiring, depositing itself within the TD3, and causing damage. Contact CPC for more information about these connectors or to purchase them. Programming Programming the unit is as simple as setting up the Einstein controller to read the unique Echelon address (see Einstein RX Refrigeration Controller User s Guide, P/N , or E2 User s Guide, P/N ) and commissioning the TD3 by pressing the Commissioning Button. If the unit can not be commissioned at the TD3 (for instance, if the TD3 is far from the Einstein, or if you are programming alone) the Einstein controller can accept the unique Echelon address number typed in. The address number is located on the back of the unit. Make sure to either remove the address sticker or make a copy of it before mounting the unit. For more details on how to program the TD3, refer to the Einstein or E2 documentation. COMPUTER PROCESS CONTROLS - Page 7
8 Operation The numeric display of the TD3 has five features: The TD3 by default displays discharge air temperature. Press the function button once ( Pr will flash for one second) and the temperature value for the product probe is displayed. This value will be displayed for ten seconds and then go back to display the discharge air temperature. Press the function button again (within ten seconds of the first press) and df will flash for one second. Then either the defrost termination temperature (for an analog sensor) or the defrost or the defrost status (for a digital sensor, open, closed) will be displayed. Again, after ten seconds the display will go back to discharge air temperature. Press the function button one more time and either C or F will flash, and then the discharge air temperature will display again. When the case is in defrost mode, def will be displayed by default. If you wish to display the discharge or product temperature instead of the def message, you may do so by changing a setting in the Einstein Standard Circuit application to which the TD3 belongs. If a sensor failure is detected, or a sensor is absent from and input, will be displayed for that particular sensor mode. Status LED The LED on the front of the TD3 is a status light that is controlled by the Einstein. If the status light is green, conditions are normal. A red status light indicates an alarm condition. The TD3 sends information from the connected sensors to the Einstein controller and the Einstein compares the data to alarm parameters that have been programmed in the Einstein (refer to the Einstein or E2 documentation for more information). COMPUTER PROCESS CONTROLS - Page 8
E2 Controller Wiring Practices. 026-1903 Rev 4 19-APR-2010
E2 Controller Wiring Practices 026-1903 Rev 4 19-APR-2010 3240 Town Point Drive NW Suite 100 Kennesaw, GA 30144 Phone: 770-425-2724 Fax: 770-425-9319 ALL RIGHTS RESERVED The information contained in this
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationIMS ALARM 3 PORT RS485 EXPANSION BOX
Price $.00 IMS ALARM 3 PORT EXPANSION BOX OPERATING INSTRUTIONS READ THOROUGHLY BEFORE INSTALLING EQUIPMENT 920147.fm TABLE OF ONTENTS GENERAL SPEIFIATIONS... 3 INTRODUTION... 4 RS232 ONNETION... 4 OMPATIBILITY...
More informationINSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
More information026-1704 Rev 6 06-APR-10. MultiFlex I/O Board Installation and Operation Manual
026-704 Rev 6 06-APR-0 MultiFlex I/O Board Installation and Operation Manual 3240 Town Point Drive NW Suite 00 Kennesaw, GA 3044, USA Phone: 770-425-2724 Fax: 770-425-939 ALL RIGHTS RESERVED. The information
More informationAutomatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811
Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The
More informationProcessor. Installation Guide
Processor Installation Guide Land Instruments International Dronfield, S18 1DJ England Telephone: (01246) 417691 Facsimile: (01246) 410585 Email: infrared.sales@landinst.com Internet: www.landinst.com
More informationHSG Engineering Tech Bulletin
Specifications subject to change OCT 2013; Rev. 1.3 HSG Engineering Tech Bulletin Recommended RS-485 Wiring for NetAXS-4/NetAXS-123 Loops Overview This document provides the recommended RS-485 wiring for
More informationQSE-CI-DMX Control Interface
Control Interface 369372c 1 04.05.16 Description The operates either in a standalone QS system or a Quantum system. It performs different functions depending on the system in which it is operating. QS
More informationModular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
More informationSchneider Automation Modbus Plus Network Installing Clustered Node Devices 31000939 00 Version 2.0
Schneider Automation Modbus Plus Network Installing Clustered Node Devices 3000939 00 Version.0 Modbus Plus devices must be installed as specified in a network layout plan, showing each device s mounting
More informationINSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
More informationElectronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
More informationFN2001-A1 Network module (SAFEDLINK) Mounting Installation
FN00-A Network module (SAFEDLINK) Mounting Installation A6V050_f_en_-- 05-0-6 Building Technologies Division Legal notice Legal notice Technical specifications and availability subject to change without
More informationVOT-320. VOT-320V0xxL VOT-320V0xxH. Quick Installation Guide
VOT-320 VOT-320V0xxL VOT-320V0xxH en Quick Installation Guide VOT-320 Table of Contents en 3 Table of Contents 1 General information 4 2 Parts included 5 3 Unpacking 6 4 Installing and connecting 7 4.1
More informationRMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
More informationPower Supply and Cabling Options. SmartTrak 100/101/140
Power Supply and Cabling Options SmartTrak 00/0/40 2 Power Supply and Cabling Options SmartTrak 00/0/40 Table of Contents Power Supplies... Communication Cables... Accessory Options... Appendix A Communication
More informationINSTALLATION GUIDE OWNER S GUIDE
INSTALLATION GUIDE OWNER S GUIDE KEYLESS ENTRY MODELS KE100 / KE150 / 1702 CONTENTS System Features... 1 System Components... 1 Technical Assistance... 1 Before You Begin... 1 Precautions... 1-2 Making
More information400 Series - Mini USB Buccaneer
IP68 Sealed IP68 rated USB V2.0 performance Plug and play capability Shielded system Overmoulded cables Screw coupling PCB versions Dust and waterproof to EN60529 Data rates up to 480Mbs Hot pluggable,
More informationwww.sebury.com.cn Digital Keypad Use s Manual
K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4
More information12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST
12VDC MAGNETIC ED DIMMABE POER SUPPIES SPEC SEET DIGEST TM-30-DIM TM-50-DIM T-60-DIM TM100-DIM TM200-DIM TM300-DIM iring Diagram for TM-50-DIM and TM-100-DIM ED 12VDC MAGNETIC DIMMABE 30 POER SUPPY Smallest
More informationApplied Electronics. Commercial Dimming System UPDATE NOTICE
REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with
More information5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...
More informationINSTALLATION INSTRUCTIONS
Rear Vision System Tailgate Handle Camera Mirror Display 2004-2014 Ford F-150 and 2008-2015 Ford Super Duty (Kit part numbers 9002-9521) Kit Contents: Mirror Tailgate Handle with camera and harness Interior
More informationZlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION
Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature
More informationQSE-CI-NWK-E Control Interface
QSE-CI-NWK-E Control Interface 369373e 1 04.05.16 The QSE-CI-NWK-E is a versatile integration access point for Lutron QS-based systems. Through either RS232 or TCP / IP over Ethernet, third-party devices
More informationwith MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
More informationNOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.
This quick start guide provides, basic installation information, drawings, first time power-on instructions, and short descriptions of key terms and concepts for installing the EntraGuard Platinum Telephone
More informationBACnet Automation Interface Module (Network Version)
Sense +V Tx Rx LAN LINK Over ARCNET KBaud BACnet Rx BACnet Tx Archive Valid Port S Tx Port S Rx Low Battery Network- Enhanced Access Default MSTP PTP = Download Required on Rnet and Port S IP Address IP
More informationTable of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7
THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationSingle Station Remote Alarm
ADI 5106G Certified ISO 9001:2000 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation
More informationInstruction Manual. Cable Splicing. Models 4500-9, 4500-9-HDF1, 4500-9-HDF2 4500-9-SS1
Instruction Manual Cable Splicing Models 4500-9, 4500-9-HDF1, 4500-9-HDF2 4500-9-SS1 No part of this instruction manual may be reproduced, by any means, without the written consent of Geokon, Inc. The
More informationCM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way
More informationSecure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual
Secure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual Section 1: Introduction SECURITY WARNING: New SEG's shipped after April 2008 will have Telnet setup option enabled by
More informationLighting Controls ! WARNING RISK OF ELECTRIC SHOCK. Installation Instructions DESCRIPTION
GE Lighting Installation Instructions Lighting Controls Centralized Lighting Control Panel Interior Catalog Number CLCINTxx DESCRIPTION The Centralized Lighting Control System is a small network of relay
More informationETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
More information3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE
4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement
More information1978-83 Malibu 1978-87 Monte Carlo 1978-87 El Camino
Important facts about this kit. 1. The dash panel used in this picture is used by permission of Covan's Classic. 2. This kit requires some modification to your original under dash wiring harness. It is
More informationTR21, TR22, TR23, and TR24 Wall Modules
TR21, TR22, TR23, and TR24 Wall Modules FEATURES INSTALLATI INSTRUCTIS The TR21, TR22, TR23, and TR24 family of wall modules include: Models with setpoint adjustment. Models with humidity output. Models
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationDS 10.210A 07/99 MN MI I/A SERIES MICRONET INTERFACE APPLICATION SPECIFICATION
DS 10.210A 07/99 MN MI WIRING AND COMMISSIONING INFORMATION FOR I/A SERIES MICRONET INTERFACE APPLICATION Order Type: MNN-Ml-100 MicroNet NCP Interface The I/A Series MicroNet Interface (MI) provides network-level
More information12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar
More informationPart Name/Description Part Number Quantity. Power Cable 4000950-5 1
Note: Indented items indicate parts included in an assembly listed above Part Name/Description Part Number Quantity Power Cable 4000950-5 1 Raven Harness Adapter Kit 4100525 1 Installation Instructions
More informationTEMPERATURE CONTROLS/ THERMOMETER/TIMERS
TEMPERATURE CONTROLS/ THERMOMETER/TIMERS 117 118 NOTES TEMPERATURE CONTROLS/ THERMOMETER/TIMERS Temperature Control Repairs 119 HOW TO DIAGNOSE STEP 1 - Control must operate within its pre-calibrated range
More informationTAC1 Telephone Entry System Installation and Programming Manual
TAC Telephone Entry System 4 7 3 6 8 9 Installation and Programming Manual The Chamberlain Group 84 Larch Ave. Elmhurst, IL 66-96 www.liftmaster.com TABLE OF CONTENTS SPECIFICATIONS 3 Cable Requirements
More informationComm5 Wiring Installation
Comm5 Wiring Installation This wiring information applies to the following Trane products: Tracer Summit systems (Comm5 communications, Version 12.0 and higher) Tracker systems (BMTK models) Tracer loop
More informationSquare D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
More information73 Chevy C10 Ammeter to Volt Gauge Conversion Mark and Michael Olson 2013 Rev 1.0
73 Chevy C10 Ammeter to Volt Conversion Mark and Michael Olson 2013 Rev 1.0 The ammeter in my son s 73 Chevy C10 did not work, so we decided to convert it to a more modern volt gauge. We made a number
More informationSystem Wiring Design Guide
System Wiring Design Guide This guide will help demonstrate the various types of wiring solutions available when connecting video surveillance cameras to EZ Watch Pro and Armor Pro Digital Video Recorders.
More informationHP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
More information* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2
COMMERCIAL INSTALL GUIDE 2 Contents How to Use This Guide: The first section of this guide is designed to assist you with the installation of your DECK Monitoring hardware. The revenue grade meter and
More informationInstallation and Operation Guide PD4600 Series Converter Replacement
Installation and Operation Guide PD4600 Series Converter Replacement Extended warranties are available for purchase at www.progressivedyn.com Member Thank you for selecting Progressive Dynamics as your
More informationInstallation instructions for Series NRX INCOM communications adapter module
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply
More informationA99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
More informationVroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR
Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions
More informatione-ask electronic Access Security Keyless-entry
e-ask electronic Access Security Keyless-entry e-fob Keyless-entry entry System Full-Function Function Installation Manual FCC ID: TV2EFOB1 (UM20 ~ 22793-02) Table of Contents Introduction... 1 e-fob Operation
More informationStep 1. Item 6. Item 1
Voltage Regulators QD3/T350 Motor Replacement Kit Kit Number 57A63675100B Service Information S225-50-35 Contents General..................................... 1 Parts Supplied...............................
More informationWIND ALARM. Wind Speed Alarm. Wind Speed. Set Point 2. Set Point 1 NEW BEDFORD, MA 02745 USA
Thank you for purchasing the Maximum wind speed alarm. The Maximum wind speed alarm is a dual set point wind speed indicator with a two digit LED display. It contains a yellow light to display one set
More informationK9 Heat Alarm Owners Manual HA-1520
K9 Heat Alarm Owners Manual HA-1520 Your K9 Heat Alarm is a state of the art product designed and developed by ACEK9.COM a division of Radiotronics, Inc. It is a unique blend of positive features taken
More informationMounting Plate / Screwdriver. Alignment Stickers Screws / Desiccant Bag / Double-sided Tape / Rubber Seal Plug / Rubber Washer
5000020G Warning Before Installation English Power off the Network Camera as soon as smoke or unusual odors are detected. Do not place the Network Camera on unsteady surfaces. Do not insert sharp or tiny
More informationHow To Wire Wireline Cable To A Cell Phone (New Zealand)
Installation Guide EnerNOC Site Server - S2 Installation Guide - AUS, NZ v 1.7 EnerNOC New Zealand Limited 2 Collina Terrace PO Box 12-202 Thorndon Wellington NZ 6144 +64 4 909 7546 1 Table of Contents
More informationWxGoos-1 Climate Monitor Installation Instructions Page 1. Connections. Setting an IP Address
Instructions Page 1 Connections The WxGoos-1 is a self-contained web server and requires 6vdc of power at 300ma. A center-positive 2.1 mm plug is used. There are five ports: 1. 10/100 Ethernet RJ-45 receptacle
More informationPC Tab INSTALLATION MANUAL SECURE-IT, INC. EAST LONGMEADOW, MA 01028. 800-451-7592 / 413-525-7039 (fax) 413-525-8807 http://www.secure-it.
PC Tab INSTALLATION MANUAL SECURE-IT, INC. EAST LONGMEADOW, MA 01028 800-451-7592 / 413-525-7039 (fax) 413-525-8807 http://www.secure-it.com IMPORTANT READ ENTIRE MANUAL BEFORE STARTING!!! System Overview
More informationRain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English. 1-800- RAIN BIRD (800-724-6247) or visit www.rainbird.
Rain+Birdt Simple To Set r (SST) Setup & Operation Instructions English Installation...2 Tools and Supplies Needed...2 Step 1. Mount r...2 Step 2. Connect Power...2 Indoor r...2 Outdoor r...2 Step 3. Connect
More informationREAD THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
More informationModel 201 Wiegand Touchpad Reader Installation Guide
Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without
More informationMAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS
MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.
More informationData Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.
Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring
More informationEDI Distributor Control Interface Wiring and Setup Instructions
Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls
More informationI NTERFACE CABLE ADAPTER MODULE
I NTERFACE CABLE ADAPTER MODULE The Interface Cable Adapter Module (ICAM) has two basic uses. First, it enables you to run shielded cable between the industrial sensor interface module (SIM) and the weather
More informationMTX-D Ethanol Content and Fuel Temperature Gauge User Manual
MTX-D Ethanol Content and Fuel Temperature Gauge User Manual P/N 3912 kit does not include flex fuel sensor. The ECF-1 is compatible with GM P/Ns 13577429 and 13577379 1. Installation... 2 1.1 Gauge Mounting...
More informationMCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
More informationABB Drives. User s Manual HTL Encoder Interface FEN-31
ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions
More informationi ChatterBox! Motorcycle Security
i Before you Start the Installation * Please read this manual to become familiar with the requirements necessary to complete the installation. * Use a high quality multi-meter to test all wires before
More informationSECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationSSW-iLM Keypad. Wire Harness Configuration. Note: This product is designed to be installed and serviced by security and lock industry professionals
SSW-iLM Keypad Note: This product is designed to be installed and serviced by security and lock industry professionals Specifications Case dimensions: 6 1/2 L x 1 3/4 W x 1 1/8 D Electrical: 5-12VDC Only
More information12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
More informationhttp://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html TECHNICAL SERVICE DEPARTMENT Removal, Cleaning, & Reinstallation of the Burner Assembly For models 74 & GT199 Required tools -
More informationLMU-5000. Hardware and Installation Guide
LMU-5000 Hardware and Installation Guide Plan The Installation Verify Power, Ground and Ignition. Be sure to check each source (power, ground and ignition) to ensure that the proper signaling exists. This
More informationPART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual
PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code
More informationbba - Balboa Bluetooth Audio (AMP) Installation & User Guide
bba - Balboa Bluetooth Audio (AMP) Installation & User Guide Bluetooth Integration CONNECT YOUR SMART DEVICE TO YOUR HOT TUB With Bluetooth connection you can now play all your favorite songs directly
More informationPXL-250: Network Wiring
This document provides the network wiring requirements for a PXL-250 access control network. Network Requirements The PXL-250 uses a half-duplex, RS-485 communication bus. Per the RS-485 specification,
More informationRC8021 Indoor Camera Installation Guide
RC8021 Indoor Camera Installation Guide P/N: 957YL502GJ Document Version: 1.0 Copyright 2011. All Rights Reserved. All trademarks and trade names are the properties of their respective owners i Package
More informationTSn SERIES Surge Protective Device
Page: 1 of 8 TSn SERIES Surge Protective Installation & Operation Manual 3621 Saunders Avenue www.systems.us Ph 804.355.1100 Richmond, VA 23227 4354 Sales@Systems.us Fax 804.355.8900 Page: 2 of 8 Quick
More informationAssembly Instruction CAI- Connector with universal Endbell
CANNON STANDARD Seite 1 von 17 CAI- Connector with universal Endbell Shell size 10 to 36 with APK contact / Trident T2P - contact Illustration and assembly exemplary of CAI Layout 20-0306 with APK / Trident
More informationModel: LCDM40 4.0 LCD Rear Vision Mirror Monitor Installation Manual Features
Model: LCDM40 4.0 LCD Rear Vision Mirror Monitor Installation Manual Features Mirror with built in 4.0 LCD Monitor Low Profile, Slim Design High Resolution TFT LCD Built in Speaker Two video inputs Fully
More informationINSTRUCTIONS FOR THE INSTALLATION AND OPERATION OF ACTIVATOR II
INSTRUCTIONS FOR THE INSTALLATION AND OPERATION OF ACTIVATOR II ELECTRONIC TRAILER BRAKE CONTROL 5500 FOR 2, 4, 6 & 8 BRAKE SYSTEMS IMPORTANT: READ AND FOLLOW THESE INSTRUCTIONS CAREFULLY. KEEP THESE INSTRUCTIONS
More informationSERVICE MANUAL REFRIGERATION
SERVICE MANUAL REFRIGERATION ELECTROLUX HOME PRODUCTS S.p.A. Publication no. Spares Operations Italy 599 36 16-90 Corso Lino Zanussi, 30 031117 I - 33080 PORCIA / PN (ITALY) ITZ/SERVICE/AA Fax +39 0434
More informationINSTALLATION GUIDE OWNER S GUIDE
INSTALLATION GUIDE OWNER S GUIDE SECURITY SYSTEM PRO-SERIES 5002 CONTENTS System Features... 1-2 System Components... 2 Technical Assistance... 2 Before You Begin... 2 Precautions... 2-3 Making Connections...
More informationI Click on a link tab to jump to that page. Cover Page
Publication, Duplication, or Retransmission Of This Document Not Expressly Authorized n Writing By The nstall Doctor s Prohibited. Protected By U.S. Copyright Laws. 1997,1998,1999,2000. Factory Radio Other
More informationSealed Industrial Ethernet Circular IP67 Cat. 5e RJ45 Connector System
Revised Sept--22-2009 Sealed Industrial Ethernet Circular IP67 Cat. 5e RJ45 Connector System Description The sealed circular RJ45 connector system is designed for use in harsh environments. The connector
More informationDetector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases
Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases
More informationKVT-729DVD INSTALLATION MANUAL
MONITOR WITH DVD RECEIVER KVT-729DVD INSTALLATION MANUAL B54-4516-00/00 (EV) Accessories 1 0...1...1 2!...1...2 3...1 4 5...1...1 6...2 7...4 8...4 9...2 2 KVT-729DVD Installation Procedure 1. To prevent
More informationUser Manual for CH-PFC76810
AA Portable Power Corp www.batteryspace.com, Email: Sales@batteryspace.com User Manual for CH-PFC76810 1. Overview The CH-PFC76810 charger is suitable for charging lithium ion battery packs such as those
More informationThe power module is Feature Number 8800-F2-901.
Hotwire 8820 GranDSLAM AC to DC Power Supply Installation Instructions Document Number 8800-A2-GZ41-00 AC to DC Power Supply The AC to DC Power Supply consists of a power supply chassis and one or two
More informationIntroduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual
Operation and Maintenance Manual Introduction Read all instructions thoroughly. Installation of the OilTector must comply with all Federal, State and Local Codes, Regulations and Practices. The OilTector
More informationVOIP-500 Series Phone Quick Installation Guide
I. Introduction This provides instructions for installation of the VOIP-500 Series Phone. It is recommended to read this instruction set completely before starting any installation. II. Contents Please
More information=============================== WARNING
=============================== WARNING EXPLANATION OF GRAPHICAL SYMBOLS This symbol is intended to alert the user to the presence of unprotected dangerous voltage" within the product's enclosure that
More information