HAZARDOUS LOCATION CLASSIFICATIONS

Size: px
Start display at page:

Download "HAZARDOUS LOCATION CLASSIFICATIONS"

Transcription

1 HAZARDOUS LOCATION CLASSIFICATIONS

2 CLASS I: FLAMMABLE GASES, VAPORS OR LIQUIDS Area Classification Comparison Division 1 flammable gases, vapors or liquids can exist all of the time or some of the time under normal operating conditions. Zone 0 flammable gases, vapors or liquids are present continuously or for long periods of time under normal operating conditions. Zone 1 flammable gases, vapors or liquids are likely to exist under normal operating conditions. Division 2 Where ignitable concentrations of flammable gases, vapors or liquids are not likely to exist under normal operating conditions. Zone 2 Where ignitable concentrations of flammable gases, vapors or liquids are not likely to occur under normal operating conditions and if they do occur, will exist only for a short periods of time. Class I, Division 1 A Class I, Division 1 location is a location: In which ignitable concentrations of flammable gases, flammable liquid produced vapors, or combustible liquid produced vapors can exist under normal operating conditions, or In which ignitable concentrations of such flammable gases, flammable liquid produced vapors, or combustible liquids above their flash points may exist frequently because of repair or maintenance operations or because of leakage, or In which breakdown or faulty operation of equipment or processes might release ignitable concentrations of flammable gases, flammable liquid produced vapors, or combustible liquid produced vapors and might also cause simultaneous failure of electrical equipment in such a way as to directly cause the electrical equipment to become a source of ignition.

3 Class I, Division 2 A Class I, Division 2 location is a location: In which volatile flammable gases, flammable liquid produced vapors, or combustible liquid produced vapors are handled, processed, or used, but in which the liquids, vapors, or gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems or in case of abnormal operation of equipment, or In which ignitable concentrations of flammable gases, flammable liquid produced vapors, or combustible liquid produced vapors are normally prevented by positive mechanical ventilation and which might become hazardous through failure or abnormal operation of the ventilating equipment, or That is adjacent to a Class I, Division 1 location, and to which ignitable concentrations of flammable gases, flammable liquid produced vapors, or combustible liquid produced vapors above their flash points might occasionally be communicated unless such communication is prevented by adequate positive -pressure ventilation from a source of clean air and effective A Class I, Zone 0 A Class I, Zone 0 location is a location in which: Ignitable concentrations of flammable gases or vapors are present continuously, or Ignitable concentrations of flammable gases or vapors are present for long periods of time. Class I, Zone 1 A Class I, Zone 1 location is a location: In which ignitable concentrations of flammable gases or vapors are likely to exist under normal operating conditions; or In which ignitable concentrations of flammable gases or vapors may exist frequently because of repair or maintenance operations or because of leakage; or In which equipment is operated or processes are carried on, of such a nature that equipment breakdown or faulty operations could result in the release of ignitable concentrations of flammable gases or vapors and also cause simultaneous failure of electrical equipment in a mode to cause the electrical equipment to become a source of ignition; or That is adjacent to a Class I, Zone 0 location from which ignitable concentrations of vapors could be communicated, unless communication is prevented by adequate positive pressure ventilation from a source of clean air and effective safeguards against ventilation failure are provided.

4 Class I, Zone 2 A Class I, Zone 2 location is a location: In which ignitable concentrations of flammable gases or vapors are not likely to occur in normal operation and, if they do occur, will exist only for a short period; or In which volatile flammable liquids, flammable gases, or flammable vapors are handled, processed, or used but in which the liquids, gases, or vapors normally are confined within closed containers of closed systems from which they can escape, only as a result of accidental rupture or breakdown of the containers or system, or as a result of the abnormal operation of the equipment with which the liquids or gases are handled, processed, or used; or In which ignitable concentrations of flammable gases or vapors normally are prevented by positive mechanical ventilation but which may become hazardous as a result of failure or abnormal operation of the ventilation equipment; or That is adjacent to a Class I, Zone 1 location, from which ignitable concentrations of flammable gases or vapors could be communicated, unless such communication is prevented by adequate positive - pressure ventilation from a source of clean air and effective safeguards against ventilation failure are provided. Gas Group Comparison A (Acetylene) B (Hydrogen) C (Ethylene) D (Propane) IIC (Acetylene & Hydrogen) IIB (Ethylene) IIA (Propane) Division 1 & 2 Gas Groups Group A: Acetylene Group B: Flammable gas, flammable liquid produced vapor, or combustible liquid produced vapor mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value less than or equal to 0.45 mm or a minimum igniting current ratio (MIC ratio) less than or equal to 0.40 Group C: Flammable gas, flammable liquid produced vapor, or combustible liquid produced vapor mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value greater than 0.45 mm and less than or equal to 0.75 mm, or a minimum igniting current ratio (MIC ratio) greater than 0.40 and less than or equal to 0.80

5 Group D: Flammable gas, flammable liquid produced vapor, or combustible liquid produced vapor mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value greater than 0.75 mm or a minimum igniting current ratio (MIC ratio) greater than 0.80 Zone 0, 1 & 2 Gas Groups Group IIC: Atmospheres containing acetylene, hydrogen, or flammable gas, flammable liquid produced vapor, or combustible liquid produced vapor mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value less than or equal to 0.50 mm or minimum igniting current ratio (MIC ratio) less than or equal to 0.45 Group IIB: Atmospheres containing acetaldehyde, ethylene, or flammable gas, flammable liquid produced vapor, or combustible liquid produced vapor mixed with air that may burn or explode, having either maximum experimental safe gap (MESG) values greater than 0.50 mm and less than or equal to 0.90 mm or minimum igniting current ratio (MIC ratio) greater than 0.45 and less than or equal to 0.80 Group IIA: Atmospheres containing acetone, ammonia, ethyl alcohol, gasoline, methane, propane, or flammable gas, flammable liquid produced vapor, or combustible liquid produced vapor mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value greater than 0.90 mm or minimum igniting current ratio (MIC ratio) greater than 0.80 MESG (Maximum Experimental Safe Gap): The maximum clearance between two parallel metal surfaces that has been found, under specified test conditions, to prevent an explosion in a test chamber from being propagated to a secondary chamber containing the same gas or vapor at the same concentration. MIC (Minimum Igniting Current) Ratio: The ratio of the minimum current required from an inductive spark discharge to ignite the most easily ignitable mixture of a gas or vapor, divided by the minimum current required from an inductive spark discharge to ignite methane under the same test conditions. Temperature Class Comparison, F Division 1 and 2 Zone 0, 1 and 2 T1 ( 842 F) T2 ( 572 F) T1 ( 842 F) T2 ( 572 F) T2A, T2B, T2C, T2D ( 536 F, 500 F, 446 F, 419 F) --- T3 ( 392 F) T3 ( 392 F) T3A, T3B, T3C ( 356 F, 329 F, 320 F) --- T4 ( 275 F) T4 ( 275 F) T4A ( 248 F) --- T5 ( 212 F) T6 ( 185 F) T5 ( 212 F) T6 ( 185 F)

6 CLASS II: COMBUSTIBLE DUSTS Area Classification Comparison Division 1 combustible dust can exist all of the time or some of the time under normal operating conditions. Zone 20 combustible dust or ignitable fibers/flyings are present continuously or for long periods of time under normal operating conditions. Zone 21 combustible dust or ignitable fibers/flyings are likely to exist under normal operating conditions. Division 2 combustible dust are not likely to exist under normal operating conditions. Zone 22 combustible dust or ignitable fibers/flyings are not likely to exist under normal operating conditions. Class II, Division 1 A Class II, Division 1 location is a location: In which combustible dust is in the air under normal operating conditions in quantities sufficient to produce explosive or ignitable mixtures, or Where mechanical failure or abnormal operation of machinery or equipment might cause such explosive or ignitable mixtures to be produced, and might also provide a source of ignition through simultaneous failure of electrical equipment, through operation of protection devices, or from other causes, or In which Group E combustible dusts may be present in quantities sufficient to be hazardous. Class II, Division 2 A Class II, Division 2 location is a location: In which combustible dust due to abnormal operations may be present in the air in quantities sufficient to produce explosive or ignitable mixtures; or Where combustible dust accumulations are present but are normally insufficient to interfere with the normal operation of electrical equipment or other apparatus, but could as a result of

7 infrequent malfunctioning of handling or processing equipment become suspended in the air; or In which combustible dust accumulations on, in, or in the vicinity of the electrical equipment could be sufficient to interfere with the safe dissipation of heat from electrical equipment, or could be ignitable by abnormal operation or failure of electrical equipment. Zone 20 A Zone 20 location is a location in which: Ignitable concentrations of combustible dust or ignitable fibers/flyings are present continuously. Ignitable concentrations of combustible dust or ignitable fibers/flyings are present for long periods of time. Zone 21 A Zone 21 location is a location: In which ignitable concentrations of combustible dust or ignitable fibers/flyings are likely to exist occasionally under normal operating conditions; or In which ignitable concentrations of combustible dust or ignitable fibers/flyings may exist frequently because of repair or maintenance operations or because of leakage; or In which equipment is operated or processes are carried on, of such a nature that equipment breakdown or faulty operations could result in the release of ignitable concentrations of combustible dust or ignitable fibers/flyings and also cause simultaneous failure of electrical equipment in a mode to cause the electrical equipment to become a source of ignition; or That is adjacent to a Zone 20 location from which ignitable concentrations of dust or ignitable fibers/flyings could be communicated, unless communication is prevented by adequate positive pressure ventilation from a source of clean air and effective safeguards against ventilation failure are provided. Zone 22 A Zone 22 location is a location: In which ignitable concentrations of combustible dust or ignitable fibers/flyings are not likely to occur in normal operation and, if they do occur, will only persist for a short period; or In which combustible dust or fibers/flyings are handled, processed, or used but in which the dust or fibers/flyings are normally confined within closed containers of closed systems from which they can escape only as a result of the abnormal operation of the equipment with which the dust or fibers/flyings are handled, processed, or used; or That is adjacent to a Zone 21 location, from which ignitable concentrations of dust or fibers/flyings could be communicated, unless such communication is prevented by adequate positive pressure ventilation from a source of clean air and effective safeguards against ventilation failure are provided.

8 Dust Group Comparison Class II, Division 1 and 2 Zone 20, 21 and 22 E (Metals Division 1 only) F (Coal) None G (Grain) Division 1 & 2 Dust Groups Group E: Atmospheres containing combustible metal dusts, including aluminum, magnesium, and their commercial alloys, or other combustible dusts whose particle size, abrasiveness, and conductivity present similar hazards in the use of electrical equipment. Group F: Atmospheres containing combustible carbonaceous dusts that have more than 8 percent total entrapped volatiles (see ASTM D , Standard Test Method for Volatile Matter in the Analysis Sample for Coal and Coke, for coal and coke dusts) or that have been sensitized by other materials so that they present an explosion hazard. Coal, carbon black, charcoal, and coke dusts are examples of carbonaceous dusts. Group G: Atmospheres containing combustible dusts not included in Group E or F, including flour, grain, wood, plastic, and chemicals. Zone 20, 21 & 22 Dust Groups: None Temperature Class Comparison, F Division 1 and 2 Zone 20, 21 and 22 T1 ( 842 F) T2 ( 572 F) T2A, T2B, T2C, T2D ( 536 F, 500 F, 446 F, 419 F) T3 ( 392 F) T3A, T3B, T3C ( 356 F, 329 F, 320 F) None Note: For Zone 20, 21 and 22, equipment shall be marked to show the operating temperature. T4 ( 275 F) T4A ( 248 F) T5 ( 212 F) T6 ( 185 F)

9 CLASS III: IGNITABLE FIBERS & FLYINGS Area Classifications Division 1 Where easily ignitable fibers/flyings are handled, manufactured, or used. Division 2 Where easily ignitable fibers/flyings are stored or handled other than in the process of manufacture. Class III, Division 1 A Class III, Division 1 location is a location in which easily ignitable fibers/flyings are handled, manufactured, or used. Class III, Division 2 A Class III, Division 2 location is a location in which easily ignitable fibers/flyings are stored or handled other than in the process of manufacture. Ignitable Fibers & Flyings Groups Class III, Division 1 and 2 None Division 1 & 2 Fibers & Flyings Groups: None Temperature Class, F Division 1 and 2 None Note: Article 503 of the NEC limits the maximum temperature for Class III equipment to 329 F (equivalent to a T-Code of T3B) for equipment not subject to overloading and to 248 F (equivalent to a T-Code of T4A) for equipment that maybe overloaded (such as motors or power transformers).

5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment

5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment Two Documents are used for the Classification of Combustible Dusts and Hazardous Locations: NFPA 499-Recommended Practices for the Classification of Combustible Dusts and Hazardous Locations for Electrical

More information

Fire Alarm System Accessories

Fire Alarm System Accessories Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer

More information

Classification of Hazardous Atmospheres

Classification of Hazardous Atmospheres Classification of Hazardous s The following pages contain excerpts for your convenience. If more comprehensive information is required, consult with your Western Technology representative. HAZARDOUS LOCATION

More information

Electrical Classification

Electrical Classification Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to

More information

Class/Division Hazardous Location

Class/Division Hazardous Location Table of Contents Introduction............................................................. 3 Basic Requirements for an Explosion.......................................4 What is an explosion?...................................................4

More information

Explosion Protected White Paper Series #1: Imaging Challenges in Explosive Environments

Explosion Protected White Paper Series #1: Imaging Challenges in Explosive Environments Video Systems Explosion Protected White Paper Series Imaging Challenges in Explosive Environments Explosion Protected White Paper Series #1: Imaging Challenges in Explosive Environments Introduction Extraordinary

More information

Electric motors can pose a serious threat when they are

Electric motors can pose a serious threat when they are Back to Basics Choose the Right Electric Motors for Hazardous Locations Uriah van Amerom Zeton Inc. Risks associated with operating an electric motor in hazardous areas range from production downtime to

More information

Basics of Explosion Protection

Basics of Explosion Protection Basics of Explosion Protection INTRODUCTION Understanding Global Explosion Protection Class and Division System Class-Zone System CENELEC Zone System IEC A INTRODUCTION Basics of Explosion Protection Basics

More information

Hazardous Area Classifications and Protections

Hazardous Area Classifications and Protections Hazardous Area Classifications Product Bulletin Hazardous Area Classifications and Protections The intent of this document is to provide a broad overview of hazardous area classifications and the types

More information

Hazardous Area Classifications and Protections

Hazardous Area Classifications and Protections Hazardous Area Classifications Product Bulletin Hazardous Area Classifications and Protections The intent of this document is to provide a broad overview of hazardous area classifications and the types

More information

Article 500. 500.1 Scope Articles 500 Through 504. 500.2 Definitions. VI. Selected Articles from the National Electrical Code 2011

Article 500. 500.1 Scope Articles 500 Through 504. 500.2 Definitions. VI. Selected Articles from the National Electrical Code 2011 VI. Selected Articles from the National Electrical Code 2011 Article 500 Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 Article 500 Informational Note: Text that is followed

More information

HAZARDOUS AREA TECHNICAL GUIDE

HAZARDOUS AREA TECHNICAL GUIDE Page 1 HAZARDOUS AREA TECHNICAL GUIDE The Redapt Hazardous Area Technical Guide provides an overview for the design and use of equipment used within potentially explosive atmospheres created by gases,

More information

Ex q Powder Filling. This is a technique primarily used for oil filled switch-gear. The spark is formed under oil and venting is controlled.

Ex q Powder Filling. This is a technique primarily used for oil filled switch-gear. The spark is formed under oil and venting is controlled. Methods of explosion protection for electrical equipment Flammable atmospheres can be ignited by sparks or not surfaces arising from the use of electrical power. Other possible sources of ignition are

More information

Design Safety Standards for Electrical Systems: Hazardous (classified) Locations -- OSHA Standard 1910.307 1

Design Safety Standards for Electrical Systems: Hazardous (classified) Locations -- OSHA Standard 1910.307 1 ABE287 Design Safety Standards for Electrical Systems: Hazardous (classified) Locations -- OSHA Standard 1910.307 1 Carol J. Lehtola, Charles M. Brown, and William J. Becker 2 The Impact of Safety on Florida

More information

SafeSite LED RTO Area Light - UL844. for Indoor and Outdoor Industrial Applications #

SafeSite LED RTO Area Light - UL844. for Indoor and Outdoor Industrial Applications # SafeSite LED RTO Area Light - UL844 for Indoor and Outdoor Industrial Applications # On when it matters most. Products and solutions that protect your business 2 www.dialight.com MDTFSSWRTOX001_J Features

More information

Making sense of Intrinsic Safety and Intrinsically Safe Tools

Making sense of Intrinsic Safety and Intrinsically Safe Tools Making sense of Intrinsic Safety and Intrinsically Safe Tools What is Intrinsically Safe? Intrinsic safety is a protection standard employed in potentially explosive atmospheres. Devices that are certified

More information

Combustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.

Combustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup. Combustible Dust - Things that go Boom W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.net Presentation Objectives After attending this presentation you will: Learn

More information

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES

More information

Assessing the Potential for a Dust Explosion and Navigating the Current Regulatory Environment

Assessing the Potential for a Dust Explosion and Navigating the Current Regulatory Environment Assessing the Potential for a Dust Explosion and Navigating the Current Regulatory Environment Ali Reza, P.E., CFI David Clayton, Ph.D., P.E. Exponent, Inc. 5401 McConnell Avenue Los Angeles, CA 90066

More information

Outline. Background. NFPA 820 Applicability to Wastewater Treatment Facilities. Hazardous Area Classifications. Treatment Plant Area Classifications

Outline. Background. NFPA 820 Applicability to Wastewater Treatment Facilities. Hazardous Area Classifications. Treatment Plant Area Classifications Outline Background NFPA 820 Applicability to Wastewater Treatment Facilities Hazardous Area Classifications Treatment Plant Area Classifications Locations of Concern Background NFPA 820 Standard for fire

More information

Article 505. 505.1 Scope. 505.2 Definitions. Article 505. Class I, Zone 0, 1, and 2 Locations. 52 Cooper Crouse-Hinds Code Digest

Article 505. 505.1 Scope. 505.2 Definitions. Article 505. Class I, Zone 0, 1, and 2 Locations. 52 Cooper Crouse-Hinds Code Digest Informational Note No. 2: In unclassified locations, identification is necessary to ensure that nonintrinsically safe wire will not be inadvertently added to existing raceways at a later date (C) Color

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

Presented by: Rich Perry Marsh Risk Consulting

Presented by: Rich Perry Marsh Risk Consulting Flammable and Combustible Liquids Presented by: Rich Perry Marsh Risk Consulting What s the Big Deal? Flammable and combustible liquids are easily ignited Ignite with explosive force Burn readily and give

More information

Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants

Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants Ram K. Saini, P.E. Principal Engineer, Chuck Emma, P.E. Principal Engineer, Burns and Roe Enterprises,

More information

Zone Hazardous Location

Zone Hazardous Location Table of Contents Introduction............................................................. 3 Basic Requirements for an Explosion.......................................3 What is an explosion?...................................................3

More information

9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration

9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration OSHA Combustible Dust Inspections Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration Overview Background Information OSHA Combustible

More information

NEMA Enclosure Types

NEMA Enclosure Types The purpose of this document is to provide general information on the definitions of NEMA Enclosure Types to architects, engineers, installers, inspectors and other interested parties. [For more detailed

More information

Explosion Prevention

Explosion Prevention Explosion Prevention Question: Many food and industrial products produced by member companies are dry powders or crystals. If mishandled, some of these products may form an explosive mixture of air and

More information

Other OSHA Issues Not Easily Understood

Other OSHA Issues Not Easily Understood Other OSHA Issues Not Easily Understood 399 Combustible Dust Explosion Pentagon Based on the Combustible Dust Explosion Pentagon, five elements are all necessary for a combustible dust explosion to occur.

More information

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors www.static-control.in 1 Introduction The detection or monitoring of flue gases and or hazardous gases has been a complex subject

More information

12.85 Enforcement and Consultation Guidance for Combustible Dust Hazards December 30, 2008

12.85 Enforcement and Consultation Guidance for Combustible Dust Hazards December 30, 2008 DOSH DIIRECTIIVE Deeppaarrt tmeennt t oof f LLaabboorr aanndd Inndduusst I trri ieess Divvi issi ioonn oof f Occccuuppaat tioonnaal l Saaf feet tyy aanndd Heeaal lthh Keeping WA workers safe. 12.85 Enforcement

More information

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION Page No: 1 of 7 6.0 PURPOSE (192.751) All possible precautions shall be exercised to prevent the accidental escape and ignition of gas. Whenever possible, potential sources of ignition should be eliminated

More information

Today's world of increasing

Today's world of increasing Applying Intrinsic Safety Today's world of increasing process control in potentially explosive atmospheres has forced designers and engineers to specify more efficient and effective ways of protecting

More information

Intrinsically Safe Barrier Relays NY2 and 8501TO

Intrinsically Safe Barrier Relays NY2 and 8501TO Intrinsically Safe Barrier Relays NY2 and 8501TO Class/File 8501 CONTENTS Description.....................................................Page NY2 General Information..............................................

More information

During Various Aluminum Fabricating Operations

During Various Aluminum Fabricating Operations Guidelines for Handling Aluminum Fines Generated During Various Aluminum Fabricating Operations F-1 Guidelines for Handling Aluminum Fines Generated During Various Aluminum Fabricating Operations SCOPE

More information

ATEX Fans 08/02/2008. Data subject to change without prior notice

ATEX Fans 08/02/2008. Data subject to change without prior notice ATEX Fans Introduction 1. What is ATEX? 1 2. Zones 1 3. Groups and Categories 2 3.1. Group I 2 3.2. Group II 2 3.2.1. Group II, Category 1 2 3.2.2. Group II, Category 2 3 3.2.3. Group II, Category 3 3

More information

COMBUSTION. In order to operate a heat engine we need a hot source together with a cold sink

COMBUSTION. In order to operate a heat engine we need a hot source together with a cold sink COMBUSTION In order to operate a heat engine we need a hot source together with a cold sink Occasionally these occur together in nature eg:- geothermal sites or solar powered engines, but usually the heat

More information

Combustible Dust: - The Basics You Need to Know. Presented by: Mary Ann Heaney, CIH, CSP ohsm, llc.

Combustible Dust: - The Basics You Need to Know. Presented by: Mary Ann Heaney, CIH, CSP ohsm, llc. Combustible Dust: - The Basics You Need to Know Presented by: Mary Ann Heaney, CIH, CSP ohsm, llc. Why the Current Focus? 2003-3 catastrophic dust explosions January - 7 Fatalities, 38 injured 2006 US

More information

STORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders

STORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders STORE HAZARDOUS SUBSTANCES SAFELY Suitable containers incompatibles gas cylinders Oxy-Acetylene welding flammable substances 35 36 STORE HAZARDOUS SUBSTANCES SAFELY STORE HAZARDOUS SUBSTANCES SAFELY Storing

More information

COMBUSTIBLE DUST EXPLOSIONS

COMBUSTIBLE DUST EXPLOSIONS COMBUSTIBLE DUST EXPLOSIONS Most people would not think that dust made up of ordinary materials such as food could explode, but under certain circumstances it can. On 7 February 2008, a violent explosion

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

COMBUSTIBLE DUST in the WOOD PRODUCTS INDUSTRY

COMBUSTIBLE DUST in the WOOD PRODUCTS INDUSTRY COMBUSTIBLE DUST in the WOOD PRODUCTS INDUSTRY Produced by NWCEP, Inc. This material was produced under grant SH23597SH2 from the Occupational Safety and Health Administration, U.S. Department of Labor.

More information

Combustible Dust. Overview

Combustible Dust. Overview Combustible Dust Michael Wacker Industrial Hygienist Madison, WI Area OSHA Office Overview History of Combustible dust What is combustible dust Some recognized hazards OSHAs Combustible Dust NEP What does

More information

Is This Combustible Dust?

Is This Combustible Dust? 1 of 5 8/6/2012 1:16 PM Is This Combustible Dust? Thursday, 19 July 2012 Dust explosions and fires are serious hazards in the process industries that have lead to loss of life, injury to plant personnel

More information

Explosion Protected Electrical Apparatus in the Russian Federation

Explosion Protected Electrical Apparatus in the Russian Federation Legislation, Standards and Technology Explosion Protected Electrical Apparatus in the Russian Federation Adaptations of National Standards to International Standards, deviations and peculiarities by Vitaly

More information

Combustible Dust Booklet

Combustible Dust Booklet Introduction In general, over 70% of organic dusts are explosible if given an adequate ignition source and appropriate dust/air concentration. Unless the material is combustible and finely divided (generally

More information

AIHA Professional Development Conference by Daniel Brechko, Managing Consultant

AIHA Professional Development Conference by Daniel Brechko, Managing Consultant AIHA Professional Development Conference by Daniel Brechko, Managing Consultant 952-334-9580 dan@sangwinsolutions.com Basics: Fire vs. Explosion OSHA NEP and NFPA 654 What is a combustible dust? Hazard

More information

Controlling fire and explosion risks in the workplace

Controlling fire and explosion risks in the workplace Controlling fire and explosion risks in the workplace A brief guide to the Dangerous Substances and Explosive Atmospheres Regulations Introduction to DSEAR This leaflet provides a brief introduction to

More information

Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute

Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute Grounding and Bonding Against Static Electricity Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute Objectives Identify Sources of Ignition. Identify Hazards associated

More information

Professional Series ATEX Portable Radios

Professional Series ATEX Portable Radios Systemcom A/S jon.otterskred@nordialog.no +47 900 20 366 Professional Series ATEX Portable Radios Product Launch, July 2005 Professional Series ATEX Objectives Provide our customers with best-in-class

More information

Certain specific properties of compressed gases make them highly useful in various research activities.

Certain specific properties of compressed gases make them highly useful in various research activities. GAS CYLINDER SAFETY Introduction Certain specific properties of compressed gases make them highly useful in various research activities. These gases, however, can be dangerous if not handled in an appropriate

More information

WEEKLY SAFETY MEETING All Euramax Subsidiaries COMBUSTIBLE DUST. Safety Meeting Contents. Meeting Notice. Leaders Guide.

WEEKLY SAFETY MEETING All Euramax Subsidiaries COMBUSTIBLE DUST. Safety Meeting Contents. Meeting Notice. Leaders Guide. Safety Meeting Contents Meeting Notice Leaders Guide Employee Handout Employee Quiz Meeting Sign-In Sheet Employee Puzzle PRIOR TO THE WEEKLY MEETING: - Post the meeting notice by the timeclock - Read

More information

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED Preparation: Safety Mgr Authority: Dennis Johnston Issuing Dept: Safety Page: Page 1 of 9 Purpose The purpose of the Electrical Safety program is to set forth procedures for the safe use of electrical

More information

SAFETY AND HEALTH PROGRAM

SAFETY AND HEALTH PROGRAM PROGRAM NUMBER NO. PAGES 05-005 10 REVISION ISSUE DATE Revision 2 11/1/2005 SAFETY AND HEALTH PROGRAM Confined Space Entry 1.0 INTRODUCTION Confined Space Entry is a serious workplace hazard, capable of

More information

Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A.

Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A. Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A. Properties of hydrogen Hydrogen is an odorless, colorless gas. With molecular

More information

The Status of Combustible Dust Regulation

The Status of Combustible Dust Regulation The Status of Combustible Dust Regulation Mark Haskins, CSP Practical Safety Solutions, LLC For CBIA Wellness Health and Safety Conference March 31, 2011 Learning Objectives During this presentation you

More information

Failure Analysis Associates. Cell Phone Usage At Gasoline Stations

Failure Analysis Associates. Cell Phone Usage At Gasoline Stations Failure Analysis Associates Cell Phone Usage At Gasoline Stations Cell Phone Usage At Gasoline Stations Prepared for Motorola Corporation 2001 N. Division St. Harvard, IL 60033 Prepared by Exponent Failure

More information

OSHA Office of Training and Education 1

OSHA Office of Training and Education 1 Flammable and Combustible Liquids OSHA Office of Training and Education 1 Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and

More information

Natural Gas Emergencies

Natural Gas Emergencies Natural Gas Emergencies Purpose To protect the personnel within the department, and citizens from the hazards involved in a natural gas emergency. The Incident Commander is to use his/her best judgment

More information

General Confined Space Awareness

General Confined Space Awareness Confined Spaces General Confined Space Awareness Confined spaces can be found in many industrial settings, from steel mills to paper mills, from shipyards to farms, and from public utilities to the construction

More information

How To Protect An Explosion

How To Protect An Explosion The basics of explosion protection preface It is a fact that gases, vapours and mists escape during the production, processing, transportation and storage of flammable substances in the chemical and petrochemical

More information

exit routes and fire protection

exit routes and fire protection exit routes and fire protection OSHA 11 Exit Routes and Fire Protection Osha 11 Exit Routes and Fire Protection Exit routes and fire protection Learning Objectives By the end of this lesson, students will

More information

Hazardous Substance Class Definitions & Labels

Hazardous Substance Class Definitions & Labels Hazardous Substance Class Definitions & Labels In the IMDG Code, substances are divided into 9 classes. A substance with multiple hazards has one 'Primary Class' and one or more 'Subsidiary Risks'. Some

More information

Ethanol Vehicle and Infrastructure Codes and Standards Citations

Ethanol Vehicle and Infrastructure Codes and Standards Citations Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,

More information

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 paul@occsev.com OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update

More information

Combustible Dust Ensuring Safety and Compliance. Brian Edwards, PE Conversion Technology Inc. ENVIRONMENTAL & SAFETY CONSULTING ENGINEERS

Combustible Dust Ensuring Safety and Compliance. Brian Edwards, PE Conversion Technology Inc. ENVIRONMENTAL & SAFETY CONSULTING ENGINEERS Combustible Dust Ensuring Safety and Compliance Prepared for: REGION IV VPPPA Presented by: Brian Edwards, PE Conversion Technology Inc. ENVIRONMENTAL & SAFETY CONSULTING ENGINEERS 1 Scope of Discussion

More information

SafeSite LED High Bay - UL 844 for Indoor and Outdoor Hazardous Applications

SafeSite LED High Bay - UL 844 for Indoor and Outdoor Hazardous Applications SafeSite LED High Bay - UL 844 for Indoor and Outdoor Hazardous Applications On when it matters most. Products and solutions that protect your business 2 www.dialight.com MDTFHZCHB001_Q Features & Benefits

More information

Combustible dust. How to use this guide. Combustible Dust

Combustible dust. How to use this guide. Combustible Dust INDUSTRIAL HYGIENE Combustible dust How to use this guide The purpose of this guide is to provide an overview of the dangers of combustible dust explosions along with tools and resources to recognize,

More information

Fire Safety in Laboratories. University of Tennessee Environmental Health and Safety

Fire Safety in Laboratories. University of Tennessee Environmental Health and Safety Fire Safety in Laboratories University of Tennessee Environmental Health and Safety Fire Safety in Laboratories Fire Prevention is a vital aspect of laboratory safety. Requires knowledge and constant vigilance

More information

of Protecting Professionals through Innovative Lighting

of Protecting Professionals through Innovative Lighting of Protecting Professionals through Innovative Lighting TABLE OF CONTENTS Koehler Bright Star LLC is located in Hanover Township, Pennsylvania, USA and is a member of the Marmon Group/ Berkshire Hathaway

More information

Safe Operating Procedure

Safe Operating Procedure Safe Operating Procedure HAZARDS OF FLAMMABLE GASES, LIQUIDS & AEROSOLS & RISK MINIMIZATION (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) (1/13) Background

More information

Minimum Ignition Temperature of Hybrid Mixtures Of Burnable Dusts and Gases

Minimum Ignition Temperature of Hybrid Mixtures Of Burnable Dusts and Gases 25 th ICDERS August 2 7, 2015 Leeds, UK Minimum Ignition Temperature of Hybrid Mixtures Of Burnable Dusts and Gases Emmanuel Kwasi Addai, Dieter Gabel, Ulrich Krause Otto-von-Guericke-Universität, Institute

More information

BUILDING A WORLD OF DIFFERENCE. Safe work in confined spaces

BUILDING A WORLD OF DIFFERENCE. Safe work in confined spaces Health & Safety Training Safe work in confined spaces Agenda Introduction What is a confined space? What are the hazards? Safe system of work Emergency arrangements Summary of pre-entry checks Questions

More information

Group A/B Dust Explosion Classification Chilworth Hazard and Risk Profile (CHARP) - Standard package of tests

Group A/B Dust Explosion Classification Chilworth Hazard and Risk Profile (CHARP) - Standard package of tests Item Description Item Remarks Explosion severity analysis (20L sphere): Triplicate test Explosion severity analysis (20L sphere): Single series screening test Explosion severity analysis (20L sphere):

More information

Flammable Liquids 29 CFR 1910.106

Flammable Liquids 29 CFR 1910.106 Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,

More information

Flammable and Combustible Liquids. Slide 1 (of 23)

Flammable and Combustible Liquids. Slide 1 (of 23) Flammable and Combustible Liquids Slide 1 (of 23) Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids

More information

Safety Data Sheet Aluminium profiles Apply for alloys Sapa EN AW 6060, 6063, 6005, 6005A, 6082, yellow chromated, with or without powder coating.

Safety Data Sheet Aluminium profiles Apply for alloys Sapa EN AW 6060, 6063, 6005, 6005A, 6082, yellow chromated, with or without powder coating. Apply for alloys Sapa EN AW 6060, 6063, 6005, 6005A, 6082, yellow chromated, with or without powder coating. 1. Identification of the Substance/Preparation and Company Product name: (Alloys, Sapa EN AW

More information

ATEX INDUSTRIAL VACUUM SOLUTIONS AND SAFETY SYSTEMS

ATEX INDUSTRIAL VACUUM SOLUTIONS AND SAFETY SYSTEMS ATEX INDUSTRIAL VACUUM SOLUTIONS AND SAFETY SYSTEMS INTRODUCTION Safety is an integral component of Nilfisk philosophy in the development of industrial vacuum cleaners, pneumatic conveyors and centralized

More information

METHOD 511.4 EXPLOSIVE ATMOSPHERE

METHOD 511.4 EXPLOSIVE ATMOSPHERE EXPLOSIVE ATMOSPHERE NOTE: Tailoring is essential. Select methods, procedures, and parameter levels based on the tailoring process described in Part One, paragraph 4.2.2, and Appendix C. Apply the general

More information

Hazmat Materials Training Fact Sheet Module 2 Classification. The classification of hazardous materials is based on three key factors:

Hazmat Materials Training Fact Sheet Module 2 Classification. The classification of hazardous materials is based on three key factors: Hazmat Materials Training Fact Sheet Module 2 Classification The classification of hazardous materials is based on three key factors: Accident history Physical and chemical properties International hazard

More information

SURVIVE INSIDE: Employee Safety in Confined Spaces

SURVIVE INSIDE: Employee Safety in Confined Spaces SURVIVE INSIDE: Employee Safety in Confined Spaces This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the

More information

Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems

Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems Technical Bulletin Gas & Air Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems 1. Introduction Norit GL 50 is a powdered activated carbon widely used for the removal of

More information

Commercial Garages, Repair, and Storage

Commercial Garages, Repair, and Storage ARTICLE 511 Commercial Garages, Repair, and Storage Introduction to Article 511 Commercial Garages, Repair, and Storage Article 511 covers locations used for the service and repair of vehicles which use

More information

Class A - Wood, paper, cloth, trash, plastics Solid combustible materials that are not metals. (Class A fires generally leave an Ash.

Class A - Wood, paper, cloth, trash, plastics Solid combustible materials that are not metals. (Class A fires generally leave an Ash. Not all fires are the same, and they are classified according to the type of fuel that is burning. If you use the wrong type of fire extinguisher on the wrong class of fire, you can, in fact, make matters

More information

FDNY C14 Certificate of Fitness Quiz

FDNY C14 Certificate of Fitness Quiz FDNY C14 Certificate of Fitness Quiz Name: Date: 1. Who issues a New York City laboratory permit? a) Department of Environmental Protection (DEP) b) Department of Environmental Conservation (DEC) c) Occupational

More information

Safety Data Sheet for Whole Grain

Safety Data Sheet for Whole Grain SECTION 1: IDENTIFICATION Safety Data Sheet for Whole Grain PRODUCT NAME: SDS NUMBER: WHOLE GRAIN GRAIN SYNONYMS/OTHER MEANS OF IDENTIFICATION: INTENDED USE: FOOD MANUFACTURER: (company name) EMERGENCY

More information

EzFlex Combustible Gas Leak Detector Model EZ40

EzFlex Combustible Gas Leak Detector Model EZ40 User's Guide EzFlex Combustible Gas Leak Detector Model EZ40 Introduction Congratulations on your purchase of the Extech EZ40 Combustible Gas Leak Detector. The EZ40 detects the presence of combustible

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600 OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done

More information

Explosion Protection. Industrial Automation and Drive Technologies. Products and systems for use in hazardous areas. Brochure November 2010

Explosion Protection. Industrial Automation and Drive Technologies. Products and systems for use in hazardous areas. Brochure November 2010 Industrial Automation and Drive Technologies Products and systems for use in hazardous areas Brochure November 2010 Explosion Protection Answers for industry. The hazardous area completely under control

More information

FIRE PREVENTION PLAN

FIRE PREVENTION PLAN FIRE PREVENTION PLAN 1 FIRE PREVENTION PLAN OSHA s Fire Prevention Plan regulation, found at 29 CFR 1910.38(b) and 29 CFR 1926.24, requires Northern Clearing, Inc. to have a written fire prevention plan

More information

EXPLOSION SAFETY DOCUMENT FOR THE ATEX 137 DIRECTIVE NEW NAME FOR A FIRE AND EXPLOSION HAZARD ASSESSMENT?

EXPLOSION SAFETY DOCUMENT FOR THE ATEX 137 DIRECTIVE NEW NAME FOR A FIRE AND EXPLOSION HAZARD ASSESSMENT? EXPLOSION SAFETY DOCUMENT FOR THE ATEX 137 DIRECTIVE NEW NAME FOR A FIRE AND EXPLOSION HAZARD ASSESSMENT? Dr. Richard L. Rogers, Dr. Bernd Broeckmann, Nigel Maddison* INBUREX Consulting GmbH, Hamm, Germany,

More information

List of Frequently Utilized Storage Tank Standards and Practices

List of Frequently Utilized Storage Tank Standards and Practices List of Frequently Utilized Storage Tank Standards and Practices Below is a list of frequently used storage tank standards and practices from organizations that are referenced in 25 PA Code, Chapter 245.

More information

Compressed Gas Cylinder Safety

Compressed Gas Cylinder Safety Compressed Gas Cylinder Safety I. Background. Due to the nature of gas cylinders, special storage and handling precautions are necessary. The hazards associated with compressed gases include oxygen displacement,

More information

Compressed Gas Cylinder Storage and Handling Guide

Compressed Gas Cylinder Storage and Handling Guide Overview Compressed gas cylinders are used in many workplaces to store gases that vary from extremely flammable (acetylene) to extremely inert (helium). Many compressed gas cylinders are stored at extremely

More information

STORAGE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS

STORAGE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS Page 1 of 10 STORAGE AND HANDLING OF These guidelines provide requirements for all University faculty, staff, and students using, handling, or storing flammable and combustible liquids. These requirements

More information

IP Rating Chart. 910 East Orangefair Lane Anaheim, CA 92801 USA. www.anaheimautomation.com 714-992-6990 714-992-0471, Fax

IP Rating Chart. 910 East Orangefair Lane Anaheim, CA 92801 USA. www.anaheimautomation.com 714-992-6990 714-992-0471, Fax IP, NEMA and UL Rating Codes The International Protection Rating, sometimes referred to as an Ingress Protection rating, is a set of codes used to define specific levels of protection. These codes consist

More information

FIRE EXTINGUISHER TRAINING

FIRE EXTINGUISHER TRAINING FIRE EXTINGUISHER TRAINING Fire safety, at its most basic, is based upon the principle of keeping fuel sources and ignition sources separate. Three things must be present at the same time to produce fire:

More information

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type

More information

Hazard Warning Signage Guidelines

Hazard Warning Signage Guidelines Fire Department 401 Oak Street, #402 Roseville, California 95678-2649 Hazard Warning Signage Guidelines Where hazardous materials are stored in quantities that require a permit pursuant to CFC Table 105.6.20,

More information