APPENDIX B FREQUENCY OF MAINTENANCE TESTS
|
|
- Malcolm Robbins
- 7 years ago
- Views:
Transcription
1 ANSI/NETA MTS-2007 AMERICAN NATIONAL STANDARD APPENDIX B FREQUENCY OF MAINTENANCE TESTS an excerpt from the ANSI/NETA Standard for Maintenance Testing Specifications for Power Distribution Equipment and Systems 2007 edition 2007 InterNational Testing Association Approved by American National Standards Institute
2 EQUIPMENT RELIABILITY REQUIREMENT APPENDIX B Frequency of Maintenance Tests NETA recognizes that the ideal maintenance program is reliability-based, unique to each plant and to each piece of equipment. In the absence of this information and in response to requests for a maintenance timetable, NETA s Standards Review Council presents the following time-based maintenance schedule and matrix. One should contact a NETA Accredited Testing Company for a reliability-based evaluation. The following matrix is to be used in conjunction with Appendix B,. Application of the matrix is recognized as a guide only. Specific condition, criticality, and reliability must be determined to correctly apply the matrix. Application of the matrix, along with the culmination of historical testing data and trending, should provide a quality electrical preventive maintenance program. MAINTENANCE FREQUENCY MATRIX EQUIPMENT CONDITION POOR AVERAGE GOOD LOW MEDIUM HIGH
3 & 7.1 Switchgear & Switchboard Assemblies Transformers Small Dry-Type Transformers Large Dry-Type Transformers Liquid-Filled Transformers Cables Low-Voltage Cables Medium- and High-Voltage Cables Metal-Enclosed Busways Infrared Only Switches Low-Voltage Air Switches Medium-Voltage Metal-Enclosed Switches Medium- and High-Voltage Open Switches Medium-Voltage Oil Switches Medium-Voltage Vacuum Switches Medium-Voltage SF 6 Switches Cutouts Circuit Breakers Low-Voltage Insulated-Case/Molded-Case CB Low-Voltage Power CB Medium-Voltage Air CB Medium-Voltage Oil CB High-Voltage Oil CB Medium-Voltage Vacuum CB Extra-High-Voltage SF Circuit Switchers Network Protectors
4 & 7.9 Protective Relays Electromechanical and Solid State Microprocessor-Based Instrument Transformers Metering Devices Regulating Apparatus Step-Voltage Regulators Sample Liquid Induction Regulators Current Regulators Load Tap-changers Sample Liquid Grounding Systems Ground-Fault Protection Systems Rotating Machinery AC Induction Motors and Generators Synchronous Motors and Generators DC Motors and Generators Motor Control Low-Voltage Motor Starters Medium-Voltage Motor Starters Low-Voltage Motor Control Centers Medium-Voltage Motor Control Centers Adjustable Speed Drive Systems Direct-Current Systems Batteries Battery Chargers Rectifiers Surge Arresters Low-Voltage Devices Medium- and High-Voltage Devices
5 & 7.20 Capacitors and Reactors Capacitors Capacitor Control Devices Reactors, Dry-Type Reactors, Liquid-Filled Outdoor Bus Structures Emergency Systems Engine Generator Uninterruptible Power Systems Automatic Transfer Switches Telemetry/Pilot Wire SCADA Automatic Circuit Reclosers and Line Sectionalizers Automatic Circuit Reclosers, Oil/Vacuum Sample Automatic Line Sectionalizers, Oil Sample EMF Testing
APPENDIX B FREQUENCY OF MAINTENANCE TESTS
AMERICAN NATIONAL STANDARD APPENDIX B FREQUENCY OF MAINTENANCE TESTS an excerpt from the ANSI/ NETA Standard for Maintenance Testing Specifications for Electrical Power Equipment and Systems Secretariat
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
More informationANSI/NETA ATS-2013 STANDARD FOR ACCEPTANCE TESTING SPECIFICATIONS FOR ELECTRICAL POWER EQUIPMENT AND SYSTEMS
STANDARD FOR ACCEPTANCE TESTING SPECIFICATIONS FOR ELECTRICAL POWER EQUIPMENT AND SYSTEMS AMERICAN NATIONAL STANDARD STANDARD FOR ACCEPTANCE TESTING SPECIFICATIONS for Electrical Power Equipment and Systems
More informationEvaluating Fire- and Heat-Damaged Electrical Equipment
Evaluating Fire- and Heat-Damaged Electrical Equipment www.nema.org 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to heat
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More informationFusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
More informationSchneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing
Scopes of Work for Electrical Acceptance Testing Schneider Electric Services: life-cycle solutions for electrical distribution equipment Make the most of your energy SM Scopes of Work for Electrical Acceptance
More informationELECTRICIAN TRADE REGULATION
Province of Alberta APPRENTICESHIP AND INDUSTRY TRAINING ACT ELECTRICIAN TRADE REGULATION Alberta Regulation 274/2000 With amendments up to and including Alberta Regulation 122/2014 Office Consolidation
More informationGUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT
GUIDELINES FOR HANDLING WATER-DAMAGED ELECTRICAL EQUIPMENT NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 1300 NORTH 17 TH STREET, SUITE 1752 ROSSLYN, VIRGINIA 22209 703 841-3200 703 841-5900 FAX WWW.NEMA.ORG
More informationPROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY
PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY Scope These program criteria apply to programs having titles involving Electrical Engineering Technology including: electrical engineering, electrical
More informationBU Control Technologies, Decathlon TM Product Overview. ABB in the Data Center Overview
BU Control Technologies, Decathlon TM Product Overview ABB in the Data Center Overview Introduction to ABB ABB is a global leader in power and automation technologies that enable utility and industrial
More informationLIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
More informationNational Craft Assessment and Certification Program S P E C I F I C A T I O N S
National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret
More informationUnit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.
Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00 Answers for energy. Unit substation solution with type SIMOSEC primary switches, dry-type transformer
More informationGuide to the China Compulsory Certification System December 2009 OMRON Corporation Industrial Automation Company
Guide to the China Compulsory Certification System December 2009 OMRON Corporation Industrial Automation Company -1- Contents Page 1. What Is CCC? 3 2. Procedure for Judging If a Product Is Subject to
More informationSTANDARD FOR ACCEPTANCE TESTING SPECIFICATIONS for Electrical Power Equipment and Systems
AMERICAN NATIONAL STANDARD STANDARD FOR ACCEPTANCE TESTING SPECIFICATIONS for Electrical Power Equipment and Systems Secretariat InterNational Electrical Testing Association Approved by American National
More informationPredictive Maintenance
PART ONE of a predictive maintenance series Predictive Maintenance Overview Predictive maintenance programs come in all shapes and sizes, depending on a facility s size, equipment, regulations, and productivity
More informationElectrical Distribution Services for Mining and Metals Industries
Electrical Distribution Services for Mining and Metals Industries Solutions to help maximize plant reliability and ensure personnel safety Make the most of your energy SM Electrical Systems are Serious
More informationAsset Management Plans
November 213 Introduction Table of Contents Page # ACS Buildings & Grounds 2 Purpose and Scope ACS Buildings & Seismic 3 The purpose of these ( Plans ) is to demonstrate how we intend to deliver on the
More informationE&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.
SAFETY Industrial DESCRIBE hazards and precautions taken to avoid injury in the workplace. Example #1: All of the following are common PPE used to perform maintenance activities EXCEPT: a. Safety Glasses
More informationFundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
More informationMaintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
More informationElectric Power Distribution Systems Operations
Naval Facilities Engineering Command 200 Stovall Street Alexandria, Virginia 22332-2300 Electric Power Distribution Systems Operations NAVFAC MO-201 April 1990 SN 0525-LP-320-1900 FOREWORD This manual
More informationIEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution
IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January,
More informationThe following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
More informationEmergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
More informationHow To Understand The Electrical Power Supply Of A Power Supply System
17 Circuit diagram symbols E 18 CIRCUIT DIAGRAM SYMBOLS electrical network elements three-phase line or cable single-phase line or cable short circuit earth electrode outgoing feeder supply incoming feeder
More informationEaton Electrical Inc. 1000 Cherrington Parkway Moon Township, PA 15108 United States tel: 1-800-525-2000 www.eatonelectrical.com.
Page 1 Abstract Adequate space is a concern for electrical installations for several reasons including: Worker safety; Working room; and Adequate clearances for personnel working on energized equipment
More informationGuidelines on the Short Circuit Current Rating for Industrial Control Panels
usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A
More informationSection 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,
More informationUtility generation line card
Utility generation line card Integrated Power Solutions Integrated Power Assembly Integrated Power Assembly Deposit on Base Enclosure Medium Voltage COMPONENTS AND Assemblies VCP-W Switchgear Metal-Clad
More information21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More information7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units
Automotive Powering business worldwide Aerospace Eaton delivers the hundreds of power distribution products that are answering the demands of today s fast changing world. We help our customers worldwide
More informationELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
More informationelectrical services WWW.AU.SGS.COM/INDUSTRIAL
electrical services WWW.AU.SGS.COM/INDUSTRIAL OUR PROFILE SGS offers a full range of electrical engineering services covering the commissioning test of new plant as well as the maintenance and continual
More informationSwitchgear Capabilities. NexGear is a Division of PowerSecure NASDAQ: POWR
Switchgear Capabilities NexGear is a Division of PowerSecure NASDAQ: POWR Discussion Points Introducing PowerSecure Introducing NexGear Solutions Offered Scope of Services Examples of Work Q & A NexGear,
More informationSwitchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
More informationKeeping electrical switchgear safe
Keeping electrical switchgear safe Keeping electrical switchgear safe Health and Safety Failure of electrical switchgear can cause death, serious injury and major damage. If you own or operate this type
More informationMetal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's
Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's Catalogue 2011 Aktif trade mark for Medium voltage switchgears, Switching equipment and Kiosks with high quality and environmentally
More informationSECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationTransmission Related Station Power Use at Substations
Transmission Related Station Power Use at Substations BUSINESS PRACTICE This Business Practice identifies the cost responsibility for energy consumption at substations by American Transmission Company
More informationFive Nines and Infrared (IR) Testing at Data Centers
Five Nines and Infrared (IR) Testing at Data Centers By Gregory R. Stockton 99.999% uptime five nines. That is what IT (information technology) customers are looking for. Uptime or availability at data
More informationELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
More informationHarmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
More informationSquare D Company P. O. Box 729 Houston, Texas 77001 Business Phone: 713-222-9195
JOHN A. GRISWOLD Square D Company P. O. Box 729 Houston, Texas 77001 Business Phone: 713-222-9195 Education Deer Park High School - Deer Park, Texas 1989 Graduate Professional Certifications AVO Training
More informationGeneric PCSR Sub-chapter 15.4 : Electrical Equipment
Form10/00 Document ID : GA91-9101-0101-15004 Document Number : EE-GDA-C284 Revision Number : A Generic Design Assessment Generic PCSR Sub-chapter 15.4 : Electrical Equipment Hitachi-GE Nuclear Energy,
More informationCanadian Technology Accreditation Criteria (CTAC) ELECTRICAL ENGINEERING TECHNOLOGY - TECHNICIAN Technology Accreditation Canada (TAC)
Preamble Canadian Technology Accreditation Criteria (CTAC) ELECTRICAL ENGINEERING TECHNOLOGY - TECHNICIAN Technology Accreditation Canada (TAC) These CTAC are applicable to programs having titles involving
More informationSUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
More informationC.I.8.2 Offsite Power System. C.I.8.2.1 Description
C.I.8 Electric Power The electric power system is the source of power for station auxiliaries during normal operation, and for the reactor protection system and ESF during abnormal and accident conditions.
More informationOccupational Profile: Electrical & Electronics Engineering Technician
Occupational Profile: Electrical & Electronics Engineering Technician A competent Electrical & Electronics Engineering Technician should be able to demonstrate the following skills and competences: 1.
More informationRalf Christian, CEO Low and Medium Voltage. Making Things Right with Totally Integrated Power (TIP)
Ralf Christian, CEO Low and Medium Voltage Making Things Right with Totally Integrated Power (TIP) siemens.com/hannovermesse Making Things Right with Totally Integrated Power (TIP) Trade LV 100 kw Industrial
More informationTransformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS)
Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS) 2 European MEPS for transformers The EU MEPS (European Minimum Energy Performance Standard) Transformers
More information(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS
(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS IS 12729:2004 IEC 60694(2002) 1.1 Scope This International Standard applies to a.c. switchgear and controlgear,
More informationChoosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
More informationProduct Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
More informationIEC PROJETOS EM VOTAÇÃO JULHO E AGOSTO. IEC 60034-1 Ed.13: Rotating electrical machines - Part 1: Rating and performance.
IEC PROJETOS EM VOTAÇÃO JULHO E AGOSTO IEC/TC 2 - Rotating machinery IEC 60034-1 Ed.13: Rotating electrical machines - Part 1: Rating and performance. IEC 60034-12 Ed.3: Rotating electrical machines -
More informationEngineering innovation
Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems
More informationMedium Voltage Motor Control Assemblies
Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................
More informationPrimary Electric Distribution for Industrial Plants
PDH Course E242 Primary Electric Distribution for Industrial Plants Adolph A. Biss, P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
More informationPower Quality Issues, Impacts, and Mitigation for Industrial Customers
Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing
More informationUL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL
UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL Definition of Terms / Explanations Overview of Basic Devices Construction Types acc. to UL 508 Self-Protected Combination Motor Controller
More informationDATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
More informationMEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV
MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects
More informationProduct brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms
Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity
More informationATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only
ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category
More informationStatement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Thermography Assessment Data Center Thermography Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits
More informationFederal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
More informationThe following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
More informationCertification Awarded to ABB LTDA. AV. DOS AUTONOMISTAS, 1496, VILA CAMPESINA, 06020-902 - OSASCO/SP BRAZIL
Certification Bureau Veritas Certification certifies that the Management System of the above organization has been assessed and found to be in accordance with the requirements of the standard detailed
More informationHow the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse
How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission
More informationOur goal ABB. ABB Avangard
Our goal is transforming from being a traditional supplier to be a market partner with the intention to offer broad customised services not exclusively focusing on product sales Retrofit Upgrading existing,
More informationUnit 33 Three-Phase Motors
Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation
More informationMEDIUM VOLTAGE METAL CLAD SWITCHGEAR
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES
More informationUL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved.
UL 508A Industrial Control Panels Power Distribution and Control Lunch & Learn Training 2002 Eaton Corporation. All rights reserved. Agenda Who is UL and what role do they play? What is the UL 508A Standard?
More informationMulti-Faceted MANUFACTURING
98 DECEMBER ISSUE 2013 Multi-Faceted MANUFACTURING Adria Manufacture, based in Rouyn-Noranda, Quebec, designs and fabricates industrial electrical equipment including portable substations, industrial control
More informationSECTION 16341 MEDIUM VOLTAGE SWITCHGEAR
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed
More informationTypical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
More informationEssPro Energy Storage Grid Substation The power to control energy
EssPro Energy Storage Grid Substation The power to control energy EssPro Grid gives you the power to control energy helping to keep smart grids in balance Maximizing the value and performance of energy
More informationMonitoring of electrical equipment failure indicators and zero-planned outages: past, present, and future maintenance practices
White Paper WP083006EN Monitoring of electrical equipment failure indicators and zero-planned outages: past, present, and future maintenance practices G. J. Paoletti, P.E. Senior Member, IEEE Eaton G.
More informatione 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
More informationABB LTDA. Av. dos Autonomistas, 1496, Vila Campesina, 06020-902 - Osasco/SP Brazil
Av. dos Autonomistas, 1496, Vila Campesina, 06020-902 - Osasco/SP Brazil Bureau Veritas Certification certify that the Management System of the above organization has been audited and found to be in accordance
More informationCahier technique no. 196
Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for
More informationMIT510/2, MIT520/2 and MIT1020/2
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com MIT510/2, MIT520/2 and MIT1020/2 Line supply or battery operated Digital/analog
More informationMEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
More informationMedium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation
Medium Voltage (MV) & High Voltage (HV) Training Module 6 Date of the presentation Electrical System Basics MV vs. HV - Definitions Differences between USA and the rest of the world IEC define a high voltage
More informationNATIONAL CERTIFICATE (VOCATIONAL)
NATIONAL CERTIFICATE (VOCATIONAL) SUBJECT GUIDELINES ELECTRICAL PRINCIPLES AND PRACTICE NQF Level 4 September 2007 ELECTRICAL PRINCIPLES AND PRACTICE LEVEL 4 CONTENTS INTRODUCTION 1 DURATION AND TUITION
More informationUNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS
UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS Automobile Electrical Structure 3.1 Introduction Objectives 3.2 Ignition System 3.3 Requirement of an Ignition System 3.4 Types of Ignition 3.4.1 Battery or Coil Ignition
More informationParalleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
More informationFukushima Daini Nuclear Power Station: Progress Status Based on the Recovery Plan (As of the End of April 2013)
Attachment 1 Progress milestone dates are defined as follows: : The date when an equipment is removed power station: The date when an equipment is carried into the relevant building within the premises
More informationService Power Technologies. Retrofitting A future-oriented concept in lifecycle management
Retrofitting A future-oriented concept in lifecycle management Retrofit solutions for gas-insulated switchgear > 50 kv to 170 kv ABB-supplied high-voltage substations generally have a service life of approx.
More informationPowerChain Management solutions. PowerChain Management Solutions for Data Centers
PowerChain Management solutions PowerChain Management Solutions for Data Centers PowerChain Management keeps your data center open for business Your data center and the network that supports it form the
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationSECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
More informationSWITCHGEAR. EGP Switchgear
SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all
More information