PowerWave Bus System Specification

Size: px
Start display at page:

Download "PowerWave Bus System Specification"

Transcription

1 BUSWAY SYSTEM 1.0 SUMMARY 1.1 This specification covers the electrical characteristics and general requirements for a continuous opening, low voltage vertical or horizontal distribution system (busway). 1.2 System shall be designed primarily as an overhead distributed power distribution center. System shall be designed to be located near critical distribution points to power specific loads, servers and or work stations. Once installed, the completed system will provide a manageable, economical means for the distribution of power and communications. Distribution of power and communications will be made through the adaptation of Tap Off plug-in units mounted securely to the busway rails. 1.3 Tap Off points shall be easily modifiable for phase configuration and be safe for installation and decommissioning while the busway is in its live state. 1.4 System shall be 100% recyclable and be shipped in recyclable containers and packing. 2.0 STANDARDS AND CERTIFICATION 2.1 The low voltage distribution busway shall be manufactured and labeled to the follow standards: 2.1a Underwriters Laboratories Standard, UL 857 The common UL, CSA, and ANSI Standard for Busways that is derived from the fifth edition of CSA Standard C22.2 No. 27, the twelfth edition of UL 857, and the second edition of NMX-J ANSI. 2.1b IEC Standard - Low-voltage switchgear and control gear assemblies - Part 2: Particular requirements for bus bar trunking systems (busways). 2.1c IEC Standard Use of the Busway housing assembly as the protective ground conductor. 2.1d Low Voltage Directive (73/23/EEC) including Amendment (93/68/EEC). 2.1e IEC Standard Requiring that the tap-off units instantly connect loads or secondary runs. 2.1f IEC/EN Standard IEC standard for busway systems with installation standards and regulations for busway with an additional internal conductor with a cross-section equal to half that of the phases. 2.1g Low Voltage Switchgear and Control gear Assemblies, Part 1: Type Tested and partially type tested Assemblies, IEC : Part 2: Particular Requirements for Bus Bar Trunking systems (Busways), IEC : Smiths Power 2015 p.1 Power Distribution, Inc Oakleys Court Richmond, VA 23223

2 2.2 Compliant for: CUL Listing. 2.3 Compliant for: National Electric Code (NEC) Article 364 Busways Compliant: NEMA AB1, Molded Case Circuit Breakers and Molded Case Switches. 2.5 Compliant: NEMA KS-1, Enclosed and Miscellaneous Distribution Equipment Switches (600VAC). 2.6 Compliant: NFPA 70 National Fire Protection Agency. 3.0 SYSTEM DESCRIPTION 3.1 Electrical Requirements: 3.1a Rated system voltage: 208V, 400V, 480V, up to 600V (rating and voltage identified on plans). 3.1b Operating Frequency: 50/60 Hz. 3.1c Ampacity Rating at Full Load: (160), (225), (250), (400), (600), and (800). 3.1d Neutral Capacity: Minimum of 100% of rating (optional 150% - 160A to 800A). 3.1e Short Circuit Rating shall be: (22kAIC, up to 480V; 35kAIC, up to 480V with 400Amp rating, 42kAIC up to 480V with 600 & 800Amp rating). 3.1f Grounding: One piece aluminum housing assembly. 3.1g Conductors: Individual, isolated, and insulated. 3.1h Conductors: 3 Phase Bus, 1 Neutral Bus. 3.1i Conductors shall be silver or tin - plated copper. 3.1j Voltage Drop: Less than 3V per 100' of installed system. 3.1k Operating Temperature: 55 C rise over 40 C / 104 F with no de-rating. 3.1l Position: 100% rating for any horizontal or vertical orientation. Smiths Power 2015 p.2 Power Distribution, Inc Oakleys Court Richmond, VA 23223

3 3.2 Optional: Branch Circuit Monitoring System 3.2a Branch Circuit Monitoring System The Branch Circuit Monitoring must be integrated into the busway delivering the measurement and management of the Bus and Tap Off loads to the customer s building management system through Modbus or SNMP protocols. The BCMS option shall be integrated at the factory and shall not require any installer wiring between the End Feeds and Tap Off Boxes. The Branch Circuit Monitoring System shall be capable of monitoring and providing all power calculations for the total input power for each busway run. It is housed on the outside wall of the power input End Feed Box, and shall be able to monitor two independent sources for dual run applications. Voltage (L-L, L-N) for all Three Phases Overvoltage/Undervoltage Alarm Threshold Voltage THD Current Phase, Ground, and Neutral Minimum & Maximum Current Demand and Percent Load Current Crest Factor Warning and Alarm Threshold kw, kva, kvar, Power Factor, kwh 3.2b The Busway Branch Circuit Monitoring System shall be capable of complete integration with PDI s current Branch Circuit Monitoring System (BCMS) Hub. 3.2c Optional BCMS Hub System - this system integrates multiple BCMS devices (up to 240); these devices can be End Feed units or other equipment monitored with installed BCMS. The BCMS Hub includes these features: Modbus RTU Protocol and Modbus TCP/IP Protocol supported simultaneously 10.4" local color touchscreen monitor Embedded web server with IP addressable interface for remote monitoring Graphical representation of all devices including End Feeds, Tap Off Boxes, and other BCMS-monitored equipment with time-stamped alarm log. Software with customization features that includes exporting all points measured into Excel for owner manipulation. Real time load management information through a Modbus RTU or Modbus TCP/IP connection, or web pages. Smiths Power 2015 p.3 Power Distribution, Inc Oakleys Court Richmond, VA 23223

4 3.2d Optional 7 Color Touch Screen Monitoring Display a high-performance, 800 x 480 pixels LED backlit color LCD display with a resistive touch screen interface. It is used with the PowerWave Bus System to provide a graphic display of the detailed power parameter data for the busway. Displays shall not be mounted overhead on end feeds. Eye level display is required. There are two options: 1) End Feed Only Monitoring. 2) End Feed Plus Tap Off Box Monitoring. This monitor can be configured to display the power parameters of up to six End Feeds each with up to fifteen Tap Off Boxes a total of 96 device addresses. The monitor comes standard with Modbus RTU, Modbus TCP via Ethernet is also available as an upgrade. 3.2e This system integrates multiple BCMS devices (up to 96). Up to 6 End Feeds, and up to 15 Plug-in Tap Off units can monitored. 3.3 Optional: Isolated Ground 3.3a Optional isolated ground bus installed in the existing rail channel factory installed and tested. 3.4 Manufacturing Requirements: 3.4a All Busway, fittings and accessories shall be manufactured by Power Distribution Incorporated (PDI) or its sister companies. PDI Corporation 4200 Oakleys Court Richmond VA Smiths Power 2015 p.4 Power Distribution, Inc Oakleys Court Richmond, VA 23223

5 4.0 SUBMITTALS 4.1 Submittals shall be in accordance with specified procedures. A line by line compliance is required and deviations to the specification are to be explained. Submit shop drawing and product data for record and approval prior to shipment. 4.2 All submittals shall include construction details; dimensions, weights, clearances, connection details and component layout. Include submittals for all Tap Off units including but not limited to breaker, communication, cabling and lengths as well as Tap Off unit schedules. 4.3 All submittals shall include connection details for configurations, document the integrated BCMS option if selected, show external power wiring and connections, as well as the size and location of all conduit connections and terminations. 4.4 Submittal shall include documentation regarding, transportation, handling and installation requirements. 5.0 WARRANTY 5.1 The Busway manufacturer shall guarantee the entire system against defective material and workmanship for a period of one(1) year from installation or eighteen (18) months from shipment with optional extended warranty periods of two (2) and three (3) years. Smiths Power 2015 p.5 Power Distribution, Inc Oakleys Court Richmond, VA 23223

6 6.0 COMPONENTS 6.1 Housing Construction 6.1a Housing shall be of a single piece extruded aluminum designed to act as a 100% ground conductor. Standard lengths must include 5, 6, 10, and 12 foot. Bus bar conductor must not extend beyond the housing. 6.1b The extruded housing must accommodated the direct insertion of hanger assemblies which attach directly to the housing assembly. 6.1c Hanger assemblies shall include the option for ceiling mount, side wall mount and must not interfere or obstruct the housing opening intended for the installation of Tap Off units. 6.1d The complete assembly shall be of the continuous opening design and shall have a slotted opening on one side of the bus to accommodate the insertion of the Tap Off units. 6.1e The busway shall be constructed to allow any individual section to be removed and replaced without disruption to adjacent sections. 6.1f All the bus systems shall be finger safe IP2X rated and tested. 6.2 Conductor and Conductor Assemblies 6.2a All phase and neutral conductors shall be made of silver plated copper with a minimum of 98.9% electrical grade purity and sized to handle a minimum of 100% of the continuously rated current with ambient temperatures at or below 40 C/104 F. All conductors shall be electrically isolated from the housing using a Class H (220), C (302 0 F) fiberreinforced Glastic material with non-propagating properties. All insulators must be UL recognized. 6.2b All critical power junction points must have redundant connection points, or contact springs when relying on spring force to maintain the connection to avoid the fatigue or failure of a single spring force junction from comprising the critical load. Smiths Power 2015 p.6 Power Distribution, Inc Oakleys Court Richmond, VA 23223

7 6.3 Conductive Fittings and Components 6.3a All conductive fittings including Tees, Crosses, and Elbows etc. shall be of the same material from the same manufacturer. All insulating material shall be a Class H (220), C (302 0 F) fiber-reinforced Glastic material. All insulators must be UL recognized. 6.4 Plug-in Tap Units 6.4a Plug-in Tap Off units shall be polarity matched to the busway system. 6.4b Plug-in Tap Off units shall use (Square D or approved equal, MG Schneider circuit breakers or equal) for branch circuit protection. The breakers shall compliment AIC rating of the application. 6.4c Plug-in Tap Off units shall permit inherently safe two step insertion and removal, and shall allow mechanically securing and then energizing contact with the bus rail conductors in isolated, sequential steps. Plug-in Tap Off units shall make ground contact prior to full insertion in the bus system. The two step insertion and removal process compliments safety and change procedures at Mission Critical sites. 6.4d Plug-in Tap Off units must be able to be repositioned on busway without de-energizing the busway system. 6.4e Plug-in Tap Off units requiring a cord assembly shall be manufactured with cord grips and receptacles as specified in the drawings. 6.4f All Tap Off Boxes will be equipped to provide current/voltage information for optional Branch Circuit Monitoring System and Branch Circuit Monitoring Hub devices. When equipped with the BCMS option the Tap Off Boxes shall be plug and play. No installer wiring shall be required. Smiths Power 2015 p.7 Power Distribution, Inc Oakleys Court Richmond, VA 23223

8 7.0 INSTALLATION 7.1 Busway Runs will consist of specific factory manufactured straight lengths and fittings as shown on the approval drawings. 7.2 Suspension System Using supplied mounting hardware the busway will be hung from the ceiling using threaded rod. Contractor shall be responsible for the connections on the supporting structure. Maximum hanger spacing will be no more than 10' maximum on center see Installation Manuals for recommendations for contractor. Height and plane changes of the busway system will be evaluated and submitted prior to release of final approval drawings. 7.3 Connecting Busway Sections The installer will follow all manufacturers installation details. Specifications for the cam-operated splice joint will include the alignment of the position indicators on each joint in a straight line. The splice joints shall not have any visible sag when installed per factory instructions. 7.4 End of Runs End pieces and end caps will be provided to install at the ends of each run. 7.5 Closure Components The bottom opening of the bus system can be closed at any point along the system with the addition of the optional closure. Closure hardware can be field modified for length and fit. Smiths Power 2015 p.8 Power Distribution, Inc Oakleys Court Richmond, VA 23223

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

Cable/Conduit Conversion

Cable/Conduit Conversion Cable/Conduit Conversion Busway can be used in many applications where cable and conduit are more commonly used. The question arises, Why use busway instead of conventional cable and conduit? Benefits

More information

MAJORSINE Power Inverter

MAJORSINE Power Inverter MAJORSINE Power Inverter Product Features: 24, 48, 130 V 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Low EMI/RFI Emissions

More information

Installation Instructions

Installation Instructions H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

SECTION 16911 WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM

SECTION 16911 WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM PART 1 GENERAL 01 02 03 04 SCOPE This section describes the metering, communications, and visualization requirements for a modular, scalable Web-based Power

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

SWITCHGEAR. EGP Switchgear

SWITCHGEAR. EGP Switchgear SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,

More information

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

Power Commander Power Distribution Units from Wiremold/Legrand offer

Power Commander Power Distribution Units from Wiremold/Legrand offer Power Commander Power Distribution Units Rack Power Distribution Solutions for IT/Network Environments Power Commander Power Distribution Units from Wiremold/Legrand offer comprehensive power distribution

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SDC200039B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of

More information

Rack Power Distribution

Rack Power Distribution The Rack PDU Selector is located at: www.apc.com/tools/selector/pdu Test drive a metered or switched Rack Power Distribution Rack PDU at testdrive.apc.com 132 Fairgrounds Road West Kingston, RI 02892 Phone:

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

BASIC NEC CODE RULES AND DESIGN PRACTICE

BASIC NEC CODE RULES AND DESIGN PRACTICE BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,

More information

Utility Distribution Systems

Utility Distribution Systems Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date

More information

ATS Overhead Table Shelf System INSTRUCTION MANUAL

ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship

More information

MCC Ratings. Voltage Rating

MCC Ratings. Voltage Rating MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control

More information

Intersection Preassembled 19-inch Rack

Intersection Preassembled 19-inch Rack Intersection Preassembled 19-inch Rack The intersection preassembled 19-inch rack comes fully assembled, wired and ready to be installed in a server rack. The rack provides communications, power conversion

More information

Applications. Remote Display Mounting Kits

Applications. Remote Display Mounting Kits June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge

More information

Uninterruptible Power Supply

Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features

More information

CRITICAL POWER MONITORING CPM20/CPM21 DETAILS

CRITICAL POWER MONITORING CPM20/CPM21 DETAILS CRITICAL POWER MONITORING CPM20/CPM21 DETAILS The Starline Critical Power Monitor (CPM) is a distributed data acquisition system that enables Current and Power monitoring in busway systems. Each phase

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

PowerCommand iwatch 100

PowerCommand iwatch 100 PowerCommand iwatch 100 Remote Network Monitoring Description The PowerCommand iwatch 100 system provides convenient means for remotely monitoring generator sets and transfer switches that are interconnected

More information

B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.

B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems. SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related

More information

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1 Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

ED1259R5 Updated April 2011 For latest specs visit www.legrand.us/wiremold

ED1259R5 Updated April 2011 For latest specs visit www.legrand.us/wiremold Rack Power Distribution Solutions for IT/Network Environments Wiremold Power Commander Power Distribution Units offer comprehensive power distribution solutions for IT environments from networking solutions

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior

More information

Low Voltage Transformers Sealed, General Purpose, Dry Type

Low Voltage Transformers Sealed, General Purpose, Dry Type Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................

More information

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140) 9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity

More information

1 & 2 CIRCUIT. Architectural grade ISO 9001 quality JIT availability Open architecture ready for your fixtures now!

1 & 2 CIRCUIT. Architectural grade ISO 9001 quality JIT availability Open architecture ready for your fixtures now! L I G H T I N G T R A C K S Y S T E M S & CIRCUIT Architectural grade ISO 900 quality JIT availability Open architecture ready for your fixtures now! Your lighting track source. Nordic Aluminium is the

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Electric Vehicle Charging Station Products EVoReel Charge Cable Management Solutions

Electric Vehicle Charging Station Products EVoReel Charge Cable Management Solutions Self-Retracts 30 ft. Charge Cable Length Electric Vehicle Charging Station Products EVoReel Charge Cable Management Solutions Safe, Convenient & Clean EV Charging The EVoReel cable management solutions

More information

Buck - Boost Transformers

Buck - Boost Transformers Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,

More information

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the

More information

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4 How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work Table of Contents Section 1 Introduction page 3 Section 2 Types of Methods of Measurements page 4 Section 3 Project Specific

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a

More information

Addendum #2 Contract UK-11-13

Addendum #2 Contract UK-11-13 Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

Machine Safety Switches

Machine Safety Switches Machine Switches SI-LS31H Series 31 mm Limit-Switch-Style with Hinged Lever Actuators Features Limit switch design (EN 50047) For use on doors or flaps Positive opening safety contacts (IEC 60947-5-1)

More information

Panduit Infrastructure Management Software for Data Centers and Enterprises

Panduit Infrastructure Management Software for Data Centers and Enterprises Panduit Infrastructure Management Software for Data Centers and Enterprises SmartZone Rack Energy Kits Energy and Environmental Monitoring for Small Data Centers SmartZone Rack Energy Kits Features: Simple

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility

EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility Catalog 2800CT1001 2014 Class 2800 CONTENTS Description............................................ Page 2 Outdoor

More information

Understanding Emergency Power Off (EPO)

Understanding Emergency Power Off (EPO) Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

Distributing Power to Blade Servers

Distributing Power to Blade Servers Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

Low Voltage Switchboards The Best Technical Solution for Your Ship

Low Voltage Switchboards The Best Technical Solution for Your Ship The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V

Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79

More information

Power Management Module 2. Installation

Power Management Module 2. Installation Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...

More information

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100J Diesel Engine Fire Pump Controllers Product Description Description Firetrol combined automatic and manual Mark

More information

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

QuickSpecs. HP 480/277 Volt Solutions. Overview

QuickSpecs. HP 480/277 Volt Solutions. Overview Overview As the quest for efficiency continues it becomes apparent that what worked in the past needs improvement. More and more data center managers are looking at alternate power plans to distribute

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

Job Aid Pre-Installation Information S8500 Media Server

Job Aid Pre-Installation Information S8500 Media Server Required information Job Aid Pre-Installation Information S8500 Media Server This job aid provides the information, hardware requirements, and computer hardware and software specifications necessary for

More information

Power Distribution Considerations for Data Center Racks

Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical

More information

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 01 (January. 2014), V6 PP 01-12 www.iosrjen.org Paper on Basbar Trunking System for Electrical Supply to Industrial

More information

QuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA - 12859 North America Version 5 August 22, 2008 Page 1

QuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA - 12859 North America Version 5 August 22, 2008 Page 1 Overview It's getting harder to manage a data center efficiently, with rising utility bills and ever-increasing demands due to processor power and server density increases. Growing user requests mean heavier

More information

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings

More information

2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes

2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 1) Tamper resistant receptacles. 2009 CEC Required in dwelling units 2012 CEC Expanded to child care facilities First introduced in the 2009

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

Table of Contents. TransformerIQ FAQs 1

Table of Contents. TransformerIQ FAQs 1 [12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is

More information

QuickSpecs. HP Fixed Cord PDUs & Extension Bars (Zero-U/1U Modular PDUs) Overview

QuickSpecs. HP Fixed Cord PDUs & Extension Bars (Zero-U/1U Modular PDUs) Overview Overview Fixed Cord PDUs and Extension Bars have a unique architecture designed specifically for 1U fixed rail servers (HP ProLiant DL360, HP ProLiant DL320, HP ProLiant DL140). This new design consists

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

Emergency lighting units EM powerled

Emergency lighting units EM powerled M BASIC 1 W Combined emergency lighting Driver 1 4 W Product description Emergency lighting Driver for manual testing SEV for output voltage < 60 V DC ow-profile casing (21 x 30 mm cross-section) 5-year

More information

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. Power Max Level 2 Charging Station en Installation and Operating Instructions This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the

More information

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module

More information

Rack Power Distribution. Worldwide

Rack Power Distribution. Worldwide Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data

More information

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing

More information

PLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 Series Features: Color coding and pin configuration makes it physically impossible to mate plugs and receptacles of different voltages and current ratings (per IEC 60 309-2). Interlocked switch mechanism

More information

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80 Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

Installation Guide Content for P250xV-240 microinverters

Installation Guide Content for P250xV-240 microinverters A C M o d u l e Installation Guide Content for P250xV-240 microinverters May 15, 2012 2011-2012 SolarBridge Technologies, Inc. All Rights Reserved. No part of this publication may be reused in any manner

More information

LOW-VOLTAGE CURRENT TRANSFORMERS

LOW-VOLTAGE CURRENT TRANSFORMERS LOWVOLTAGE CURRENT TRANSFORMERS 5 A Power network meters ND0 and ND type. N4Z and N5Z Tel: (+48 68) 45 75 39; 45 75 305; 45 75 3; 45 75 368; email: export@lumel.com.pl ul. Słubicka 657 Zielona Góra CONTENTS

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

Bullet Camera. Installation Guide. Hangzhou Hikvision Digital Technology Co., Ltd. http://www.hikvision.com

Bullet Camera. Installation Guide. Hangzhou Hikvision Digital Technology Co., Ltd. http://www.hikvision.com Bullet Camera Installation Guide Hangzhou Hikvision Digital Technology Co., Ltd. http://www.hikvision.com 1 Thank you for purchasing our product. If there are any questions, or requests, please do not

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information