Altivar 78. Variable Speed Drive. Installation Manual APRIL 05. ATV78 variable speed drives. ip00 module installation ATV780C20Y~ATV780C71Y

Size: px
Start display at page:

Download "Altivar 78. Variable Speed Drive. Installation Manual APRIL 05. ATV78 variable speed drives. ip00 module installation ATV780C20Y~ATV780C71Y"

Transcription

1 Altivar 78 Installation Manual Variable Speed Drive APRIL 05 ATV78 variable speed drives ip00 module installation ATV780C20Y~ATV780C71Y

2 2 INDEX 1. GENERAL 3 2. REQUIREMENTS Environmental requirements Cabinet Accessories 5 3. PRODUCT HANDLING Product type designation codes Receipt of delivery Receiving, unpacking and storing the product Lifting the power module Lifting AC chokes 7 4. INSTALLING AC CHOKEs 8 5. INSTALLING THE POWER MODULE Preparing the enclosure Mounting the power module Grounding the power module CONNECTING THE INTERNAL POWER CABLES INSTALLING THE CONTROL UNIT Connecting power supply and internal control cables ATV 780C56Y to ATV780C71Y PREPARING FOR EXTERNAL POWER CONNECTIONS Installing mounting plate and input terminals Installing fuses Installing EMC grounding Understanding the power unit topology Connecting input and output power Mains and motor cables Control of main air flow Arranging ventilation of the enclosure Steering the internal air flow Heat dissipation Temperatures measured during test run APPENDICES Dimensional drawings, Power modules Dimensional drawings, AC chokes Optic fibre cables, signal lists and connections ATV780C56Y to ATV780C71Y 27

3 GENERAL 3 1. GENERAL This manual provides instructions for the installation of ATV780C20Y. C71Y (frames FR10 to FR12) variable speed drives in a cabinet, switchgear, or any other enclosure. ATV780C20Y. C71Y of frames FR10 to FR12 have 1 (FR10 and FR11) or 2 (FR12) power modules. Therefore for frame FR12, you will need twice the number of drive accessories (such as cables, terminals, chokes etc.) unless otherwise stated. Also note that ATV780C50Y requires two chokes mounted in parallel. See Figure 14 The ATV78 C20. C71Y product series comprise the following variable speed drives: Type code Frame size Nominal current Choke type (partial) Voltage range V ATV780C20Y FR10 261A CHK 261 ATV780C25Y FR10 325A CHK 400 ATV780C31Y FR10 385A CHK 400 ATV780C35Y FR11 460A CHK 520 ATV780C45Y FR11 502A CHK 520 ATV780C50Y FR11 590A 2*CHK 400 ATV780C56Y FR12 650A 2*CHK 400 ATV780C63Y FR12 750A 2*CHK 400 ATV780C71Y FR12 820A 2*CHK 400 Table 1. ATV78 C20. C71Y variable speed drives, frames FR10 FR12 The variable speed drives can be installed in any enclosure that fulfils the requirements specified in chapter 2. In the illustrations in this manual, Rittal TS8 is used as an example enclosure. Installing ATV780C20Y. C71Y variable speed drives in an enclosure involves the following steps: Installing the AC choke(s) (chapter 4) Installing and grounding of power module(s) (chapter 5) Connecting internal power cables between the AC choke and the power module (chapter 6) Preparing for input and output power connections (chapter 8) Arranging air-cooling and ventilation (chapter 9). General instructions for product handling are given in chapter 3. Dimensional drawings are found in chapter 10. NOTE: The installation of the variable speed drives must be done by certified electricians. Safety regulations for electrical work must be followed during the installation work. NOTE: NOTE: Safe operation and full service lifetime of the product can be guaranteed only if the installation instructions in this manual are followed. The product warranty is not valid if the product is handled in a way that does not comply with the instructions in this manual and the User's Manual. 1

4 4 REQUIREMENTS 2. REQUIREMENTS 2.1 Environmental requirements Refer to ATV78 User's Manual for information on required operating temperature, humidity, etc. Leave sufficient free space around the enclosure so the air flow is not obstructed. Air is generally sucked in from the front and exhausted upwards leave at least 500 mm free space in front of the enclosure and 200 mm above the enclosure also see section 9.3. NOTE! EN specifies the ambient temperature for enclosed products at 35 C (24h average)/40 C (maximum). The ventilation and cooling of the installation room must be sufficient to keep the temperature below this level. For information on the heat dissipation of the product and the required cooling air, refer to section 9.3 and the User's Manual. 2.2 Cabinet Width: Depth: Height: Mechanical requirements: Protection class: Construction: Ventilation openings: Refer to section 9.1. Table 2. Cabinet data for FR10 Min. 600 mm Min. 600 mm Min mm if the AC choke is installed beneath the power module, otherwise min mm The cabinet must be able to support a total equipment weight of 275 kg (if the power module and the AC choke are installed in the same cabinet). This manual applies to IP21. According to EN Width: Min. 800 mm Depth: See Table 2. Height: See Table 2. Mechanical requirements: The cabinet must be able to support a total equipment weight of 350 kg (if the power module and the AC choke are installed in the same cabinet). Protection class: This manual applies to IP21. Construction: According to EN Ventilation openings: Refer to section 9.1. Table 3. Cabinet data for FR11 Width: Min mm Depth: See Table 2. Height: See Table 2. Mechanical requirements: See Table 2. Protection class: This manual applies to IP21. Construction: According to EN Ventilation openings: Refer to section 9.1. Table 4. Cabinet data for FR12

5 REQUIREMENTS Accessories Accessory Specification Input terminals (optional) See Table 10. Input power cables See User s manual. Internal power cables See Table 8 Output power cables See User s manual. Grounding cable Mounting plates Module mounting rails Fuse switch (optional) See Table 11. EMC grounding PE rail See section 5.3 Table 5. Accessories data for FR10 Cu grounding cable, min. 35mm 2 /power module. The cable must fulfill the local regulations. Must be able to carry a weight of the power module (see Figure 2). Clamp size according to the output cable diameter, see section

6 6 PRODUCT HANDLING 3. PRODUCT HANDLING 3.1 Product type designation codes Product type designation codes are found on the power module and the control unit. For an explanation of the type designation codes, refer to the User's Manual. 3.2 Receipt of delivery The standard delivery includes: Power module(s) with fixing frame(s) and with one integrated control unit AC choke(s) ATV780C56Y to ATV780C71Y units only: optical cable set for internal control connections between power modules IP00 Module Installation manual User's manual. The following optional equipment is delivered on request: Door installation kit VW3A78102 or VW3A78103 for installing the control panel on the enclosure door. AC choke Fibr 24V for A ATV Figure 1. Parts included in delivery: AC choke and power module with integrated control unit and the required cables for ATV780C56Y to ATV780C71Y 3.3 Receiving, unpacking and storing the product The product is delivered packed in a plywood case, which can be recycled or destroyed by burning. Instructions for receiving, handling and storing the product, as well as the general warranty terms can be found in the User s manual.

7 PRODUCT HANDLING Lifting the power module The power module can be lifted by the holes on top of the module. Place the lifting hooks symmetrically in at least two holes. The lifting equipment must be able to carry the weight of the power module. See Figure 2. FR10: 123 kg FR11: 210 kg FR12: 2*123 kg Figure 2. Lifting the power module NOTE! The power module can temporarily rest on the cooling fan assembly, but shocks or nonvertical forces may cause damage to the fans. 3.5 Lifting AC chokes The AC choke can be lifted by the two eyebolts on top of the unit. The weight of the AC choke is 53 kg, 84 kg or 115 kg depending on the type (see Figure 3). Choke CHK0261 CHK0400 CHK0520 Weight 53 kg 84 kg 115 kg Figure 3. Lifting the AC choke 3

8 8 INSTALLING AC CHOKEs 4. INSTALLING AC CHOKES Type code (partial) Frame size Choke type Voltage range V ATV780C20Y FR10 CHK 261 ATV780C25Y FR10 CHK 400 ATV780C31Y FR10 CHK 400 ATV780C35Y FR11 CHK 520 ATV780C45Y FR11 CHK 520 ATV780C50Y FR11 2*CHK 400 ATV780C56Y FR12 2*CHK 400 ATV780C63Y FR12 2*CHK 400 ATV780C71Y FR12 2*CHK 400 Table 6. Choke types The recommended location for the AC choke is the bottom part of the enclosure, where it should be installed close to the rear wall. For a possible later installation of a fuse switch, it may be practical to install the AC choke somewhat to the left. Fasten the choke on an assembly plate or using mounting rails. Figure 4. Installing the AC choke NOTE! An upper support plate must be installed above the choke if the cabinet is transported in a horizontal position. A possible fixed support plate must be equipped with air circulation holes. See Figure 17 on page 21.

9 INSTALLING THE POWER MODULE 9 5. INSTALLING THE POWER MODULE 5.1 Preparing the enclosure To facilitate a possible future replacement of boards as well as other service work, it is recommended that the power module be mounted on rails. Fasten mounting rails to the sides of the cabinet at distances given under F (from the top) and G (from the bottom) in the table below. Leave a space (A) between the module and the walls on both sides for the internal cooling air circulation. A A E B C F D G Figure 5. Preparing the enclosure for the power module The power module should be fastened to the rear side of the enclosure as shown in Figure 6. For this purpose, install two fixing bars on the rear wall of the cabinet at appropriate levels. Note the following dimensions that are essential for placing the power module. All dimensions in mm: A B C D E F G 50* (290) (590) Table 7. A = Minimum distance to the side walls or adjacent components. * = Note that the two cabinets, in which the modules of ATV780C56Y to ATV 780C71Y are installed, require no clearance between them. B = Minimum distance from the top of the cabinet; This space is needed for the power cables (see Figure 9). C = Module height 5

10 10 INSTALLING THE POWER MODULE D = Minimum distance from the bottom of the enclosure if the AC choke is installed at the bottom of the enclosure. If the choke is installed in another location, the distance must not, however, be smaller than what is given in parentheses E = Minimum distance from the cabinet door. F = Minimum distance from the mounting rails to top of the cabinet. G = Minimum distance from the mounting rails to the bottom of the cabinet. If the choke is installed in another location, the distance must not, however, be smaller than what is given in parentheses See also the dimensional drawings in chapter Mounting the power module NOTE! If the space around the power module is narrow, lead the internal power cables along the wall and fasten them in brackets before mounting the power module. See chapter 6. Fasten the power module to the rear wall of the enclosure utilising the fixing holes in the frame. Figure 6. Mounting the power module NOTE! If the power module is installed before the AC choke, the centre of gravity is very high at this stage. Make certain that the enclosure does not fall over during the assembly.

11 INSTALLING THE POWER MODULE Grounding the power module Install a PE rail, for instance at the bottom front of the enclosure. Connect a grounding cable from the grounding connector at the lower right hand side of the power module frame to the PE rail of the enclosure. Use a copper grounding cable with a cross-sectional area of at least 35 mm 2 per power module, which obeys the local regulations for grounding cables. See Figure 7 on page 11. NOTE! The PE rail must be connected to external ground at the installation site according to local regulations. Grounding cable PE rail Figure 7. Grounding the power module 5

12 12 CONNECTING THE INTERNAL POWER CABLES 6. CONNECTING THE INTERNAL POWER CABLES Power board L1 L2 L3 B- B+/R+ R- U V W BR (option) L1* L2* L3 M 3~ Figure 8. Connecting the power cables to ATV780C20Y to ATV780C50Y. For ATV780C56Y to ATV780C71Y the connection is to both the units. Connect three power cables according to Figure 9 to the output terminals of the AC choke and the input terminals of the power module. It is recommended to use cables designed for 90 C. Connect the L1 cable from the L1 terminal of the AC choke to the L1 input terminal of the power module, the L2 cable to the L2 terminal, and the L3 cable to the L3 terminal. NOTE! NOTE! The choke has two sets of output terminals designed for different voltages/frequencies. Use the upper set for 500V/50Hz, 525V/50Hz, 600V/60Hz, and 690V/50Hz The connections for the external brake resistor are located at the top of the unit, beside the L1-L3 power input terminals

13 CONNECTING THE INTERNAL POWER CABLES 13 L3 L2 L1 L1 L2 L3 L1L2 L3 L1 L2 L3 Voltage / Frequency 500V/50Hz 525V/50Hz 575V/60Hz 690V/50Hz L1 L2 L3 L1 L2 L3 Figure 9. Connecting the power cables between the AC choke and the power unit Product Temp. rating Cable size, mm 2 per phase Cu cables Specification ATV780C20Y ATV780C25Y 90 C 2*70 GENELEC HD 21.7 H07V2-K ATV780C31Y 70 C 2*95 Standard ATV780C35Y 90 C 2*95 GENELEC HD 21.7 H07V2-K ATV780C45Y 70 C 2*120 Standard ATV780C50Y ATV780C56Y 90 C 2*2*70 GENELEC HD 21.7 H07V2-K ATV780C63Y ATV780C71Y 70 C 2*2*95 Standard Table 8. Required cable sizes for the internal power cables (90 o C rating recommended)

14 14 CONNECTING THE INTERNAL POWER CABLES L3 L2 L1 L3 L2 L1 DC- DC+ R- L1 L2 L3 DC- DC+ R- L1 L2 L3 L1L2 L3 L1L2L3 Fuses L1 L2 L3 L1 L2 L3 Figure 10. Connecting the DC links together when the brake chopper of ATV780C56Y to A TV780C71Yis used Product Fuse ratings Recomm. fuse types Current [A] Voltage (or equivalent) ATV780C56Y V Bussmann 170M6202 (2 pcs) ATV780C63Y V Bussmann 170M6202 (2 pcs) ATV780C71Y V Bussmann 170M6202 (2 pcs) Table 9. Fuse recommendations The cable used to connect the DC bus must be at least 90 mm2.

15 INSTALLING THE CONTROL UNIT INSTALLING THE CONTROL UNIT NOTE! The ATV78 variable speed drive is delivered with the control unit mounted on the power unit 7.1 Connecting power supply and internal control cables NOTE! Only ATV780C56Y to ATV780C71Y require connecting of cables by the customer ATV 780C56Y to ATV780C71Y The control unit uses 24 VDC supplied from the ASIC board, which is located on the left side of the power unit 1. To access the board, remove the protective cover in front of the power module. Connect the power supply cable to the X10 connector on the ASIC board and to the X2 connector on the rear side of the control unit. Min bending radius 50 mm Power module 1 ASIC board X10 FB board X2 Power module 2 ASIC board Star coupler board Figure 11. Connecting the power supply and control cables to the control unit, ATV 780C56Y to ATV780C71Y Each fibre optic cable has a number and marked on the cable shield at both cable ends. Connect each cable to the connectors marked with the same number on the ASIC board and on the rear side of the control unit. Additionally, you may have to connect the 4 fibre cables from the fieldbus board to the star coupler board. The list of the optic signals can be found in chapter

16 16 PREPARING FOR EXTERNAL POWER CONNECTIONS 8. PREPARING FOR EXTERNAL POWER CONNECTIONS 8.1 Installing mounting plate and input terminals For further installation of other devices (breakers, fuses, EMC grounding), it is recommended that an installation plate be mounted in front of the AC choke, leaving the bottom part open for air circulation. Install input terminals on the plate and connect them to the input terminals (the uppermost terminals) of the AC choke using busbars or flexible busbars according to Table 10. Voltage range V Product ATV780C20Y... ATV780C31Y ATV780C35Y...ATV780C50Y ATV780C56Y...ATV780C71Y Table 10. Copper busbars Cu busbar, size 30*6 mm 40*6 mm 2 pcs 30*6 mm L1 L2 L3 Figure 12. Power input terminals 7

17 PREPARING FOR EXTERNAL POWER CONNECTIONS Installing fuses The power module contains no internal fuses. To protect the device and allow the installation of a main switch in the enclosure, it is recommended that a fuse switch be installed. Use ar type fuses according to Table 11, and install them in the same enclosure as the frequency converter, or in another enclosure in the immediate vicinity. Product Fuse ratings Recomm. fuse types Current [A] Voltage I 2 t at U n Size (or equivalent) ATV780C20Y V Bussmann 170M5813 (3 pcs) ATV780C25Y V Bussmann 170M5813 (3 pcs) ATV780C31Y V Bussmann 170M5813 (3 pcs) ATV780C35Y V Bussmann 170M8547 (3 pcs) ATV780C45Y V Bussmann 170M8547 (3 pcs) ATV780C50Y V Bussmann 170M5813 (6 pcs) ATV780C56Y V Bussmann 170M5813 (6 pcs) ATV780C63Y V Bussmann 170M5813 (6 pcs) ATV780C71Y V Bussmann 170M5813 (6 pcs) Table 11. Fuse recommendations 8.3 Installing EMC grounding The output cables to the motor must be 360 o EMC earthed. The EMC grounding clamps can, for instance, be installed on the mounting plate in front of the AC choke as shown in the figure below. The EMC grounding clamps must be suited to the output cable diameter to give a 360 o contact with the cables. Refer to the User's Manual for output cable diameters. EMC grounding PE rail Cable fixing clamps Figure 13. Installing EMC grounding 7

18 18 PREPARING FOR EXTERNAL POWER CONNECTIONS 8.4 Understanding the power unit topology Figure 14 shows the principles for mains and motor connections of ATV780C20 to ATV780C71. ATV78C50 has double input devices and requires an even number of supply cables but an uneven number of motor cables can be used. ATV780C56 to ATV780C71 consist of two power modules and require an even number of supply and motor cables. See Figure 14 and Table 12. M M M Note! Min cable length 5m ATV780C20Y to ATV780C45Y Single input Single output ATV780C50Y Double input* Single output ATV780C56Y to ATV780C71Y Double input Double output Figure 14. Topology of mechanical sizes FR10 FR Connecting input and output power Mains and motor cables The mains cables are connected to terminals L1, L2 and L3 and the motor cables to terminals marked with U, V and W, see Figure 8. In ATV780C50Y to ATV780C71Y an even number of input cables is required. In converters consisting of double power modules (FR12) an even number of input cables and an even number of motor cables is needed. WARNING In types with double inputs (ATV780C50Y to ATV780C71Y) or outputs (ATV780C56Y to ATV780C71Y) is it very important that the same cable dimensions, type and routing is used for all cables. In case the cabling between the converter modules is not symmetrical, unequal load inside converter might reduce loadability or even damage the converter. WARNING In units with double motor outputs the motor cables must not be connected together in the converter end. Always connect the parallel motor cables together in the motor end only. The minimum motor cable length is 5m. The output cables to the motor must be 360 o EMC earthed. The EMC grounding clamps can, for instance, be installed on the mounting plate in front of the AC choke as shown in the figure below. The EMC grounding clamps must be suited to the output cable diameter to give a 360 o contact with the cables. 7

19 PREPARING FOR EXTERNAL POWER CONNECTIONS 19 As a rule of thumb, cables and the fuses can be dimensioned according to the frequency converter nominal OUTPUT current which you can find on the rating plate. Dimensioning according to the output current is recommended because the frequency converter input current never significantly exceeds the output current. Table 12 shows the minimum dimensions of Cu- and Al-cables and the recommended ar fuse sizes. If the motor temperature protection of the drive (see the Programming Manual, on the CD) is used as an overload protection, the cable should be chosen accordingly. If three or more cables are used in parallel (per block) in bigger units each cable requires a separate overload protection. Frame FR10 FR11 FR12 Type ATV780C20Y ATV780C25Y ATV780C31Y ATV780C35Y ATV780C45Y ATV780C50Y ATV780C56Y ATV780C63Y I L [A] Bussmann fuse type Fuse I n [A] M5813 (3 pcs) M5813 (3 pcs) M5813 (3 pcs) M8547 (3 pcs) M8547 (3 pcs) M5813 (6 pcs) M5813 (6 pcs) M5813 (6 pcs) 700 ATV780C71Y M5813 (6 pcs) 700 Table 12. Cable recommendations Mains and motor cable 1) [mm 2 ] Cu: 1*(3*185+95) Al: 2*(3*120Al+41 Cu) Cu: 1*(3* ) Al: 2*(3*150Al+41Cu) Cu: 2*(3*120+70) Al: 2*(3*185Al+57Cu) Cu: 2*(3*150+70) Al: 2*(3*240Al+72Cu) Cu: 2*(3*185+95) Al: 2*(3*300Al+88 Cu) Cu: 2*(3* ) Al: 4*(3*120Al+41Cu) Cu: 4*(3*95+50) Al: 4*(3*150Al+41Cu) Cu: 4*(3*120+70) Al: 4*(3*150Al+41Cu) Cu: 4*(3*150+70) Al: 4*(3*185Al+57Cu) No of supply cables Even/Odd Even/Odd Even/Odd Even/Odd Even/Odd Even Even Even Even No of motor cables Even/Odd Even/Odd Even/Odd Even/Odd Even/Odd Even/Odd Even Even Even 7

20 20 Control of main air flow 9. CONTROL OF MAIN AIR FLOW CAUTION! It is of utmost importance for the operation and lifetime of the frequency converter that the enclosure is well ventilated to keep the temperature below the maximum operating temperature. Repeated overheating will shorten the lifetime of the converter. 9.1 Arranging ventilation of the enclosure The enclosure door must be provided with air gaps for air intake. To achieve sufficient cooling inside the cabinet, the dimensions for the total area of free openings for incoming air given in Table 9 must be followed. For instance, there could be two screened gaps as presented in Figure 0 (Manufacturer s recommendation). This layout ensures a sufficient air flow to the module fans as well as cooling of the additional components. 2 Air outlet gaps must be situated on top of the cabinet. The minimum effective air outlet area per converter frame is given in Table 9.The cooling arrangements inside the cabinet must be such that they prevent hot output air from mixing with the incoming fresh air (see page 21 below). The ventilation gaps must fulfil the requirements set by the selected IP class. The examples in this manual apply to protection class IP21. During operation, air is sucked in and circulated by a fan blower at the bottom of the power unit. If the power unit is placed in the upper part of the cabinet, the fan blower will be in the mid of the cabinet, at the height of the upper ventilation grid. 1 FR10 FR11 FR12 1 2x13 dm 2 2x20 dm 2 2x26 dm dm 2 11 dm 2 14 dm 2 Table 13. Ventilation requirements Figure 15 Ventilation arrangements on the cabinet 7

21 Control of main air flow Steering the internal air flow Cooling air must be sucked in through the ventilation gaps on the door and blown out at the top of the enclosure. To steer the hot air from the power unit to the outlet at the top of the enclosure and prevent it from circulating back to the fan blower, use either of the following arrangements: A. Install a closed air duct from the power unit to the outlet on top of the enclosure (A in the figure below). B. Install shields in the gaps between the power unit and the cabinet walls (B in the figure below). Place the shields above the air outlet gaps at the sides of the module. In ATV780C56Y to ATV780C71Y, close the opposing gaps in the upper part of the cabinets with a sheet metal plate to ensure proper cooling. A Air duct B Sheet metal Shields Touch protection cover Choke upper support Mesh type touch protection Figure 17. Arrangements for steering hot air to the outlet at the top of the cabinet 7

22 22 Control of main air flow NOTE! NOTE! To allow free air circulation, the touch cover at the bottom of the cabinet must be of type meshed sheet metal screen. For the same reason, the busbar touch protection cover and the choke upper support must be equipped with holes. See Figure 17. If a flat roof is used, mount a V-shaped air guide on the underside of the roof to direct the air flow horizontally. See Figure 18. Figure 18. Roof structure seen from the side 9.3 Heat dissipation The efficiency of the frequency converter is a function of switching frequency, operating frequency and load (see User s manual). Based on this information, heat dissipation can be calculated at a certain operating point. For most cases the following general formula based on frequency converter load can be used to estimate the heat dissipation of the power module: P [ kw ] Pmot [ kw ]* loss = The following table shows the heat dissipation from the AC choke. Choke Heat dissipation CHK W CHK W CHK W Table Heat dissipation from the AC choke 9.4 Temperatures measured during test run The following table shows the temperatures measured during a test run of a 520A/400V unit with nominal The test unit was installed in a Rittal TS8 enclosure following the guidelines described in this manual. Measurement Temperature [ C] Note Ambient air 30 Outside enclosure Fan intake air 36 Module input terminal 59 L2-phase Output terminal 65 V-phase AC choke 92 L2 winding surface Table Temperatures measured during an accepted test run 7

23 10. APPENDICES 10.1 Dimensional drawings, Power modules Figure 19. Power module dimensions, ATV780C20Y to ATV780C31Y

24 24 APPENDICES 709 Without terminal cover: DC- DC+ R- 1L11L21L32L12L2 2L With integrated control unit Figure 20. Power module dimensions, ATV780C35Y to ATV780C50Y ATV780C56 to ATV780C71 (frame FR12) is built of two FR10 modules. 7

25 APPENDICES Dimensional drawings, AC chokes CHK Figure 21. Dimensions of AC choke CHK 520 CHK Figure 22. Dimensions of AC choke CHK 400 7

26 26 APPENDICES CHK min. 19mm Figure 23. Dimensions of AC choke CHK 261 7

27 APPENDICES Optic fibre cables, signal lists and connections In frame ATV780C56Y to ATV780C71Y, which consist of two power modules, you will have to connect the fibre cables from the star coupler board to the other power module. See chapter 3.2. Connect the cables according to the figures below ATV780C56Y to ATV780C71Y Star coupler board on control unit Terminals on ASIC board of power module 1 H8 Trip signal from power module 1 H7 VaconBus data from ASIC 1 to control board H6 VaconBus data from control board to ASIC 1 H5 ADC synchronization, power module 1 H4 Phase W control, power module 1 H3 Phase V control, power module 1 H2 Phase U control, power module 1 H1 Gate control enable, power module 1 H18 Trip signal from power module 2 H17 VaconBus data from ASIC 2 to control board H16 VaconBus data from control board to ASIC 2 H15 ADC synchronization, power module 2 H14 Phase W control, power module 2 H13 Phase V control, power module 2 H12 Phase U control, power module 2 H11 Gate control enable, power module 2 H23 H22 H21 Feedback phase W Feedback phase V Feedback phase U H8 H7 H6 H5 H4 H3 H2 H1 H18 H17 H16 H15 H14 H13 H12 H11 H23 U V W T H1 H2 H3 H4 H5 H6 H7 H1 H2 H3 H4 H5 H6 H7 H8 H1 Gate control enable H2 Phase U control H3 Phase V control H4 Phase W control H5 ADC synchronization H6 VaconBus data from control board to ASIC H7 VaconBus data from ASIC to control board U Feedback phase U V Feedback phase V W Feedback phase W T Trip signal Terminals on ASIC board of power module 2 H1 Gate control enable H2 Phase U control H3 Phase V control H4 Phase W control H5 ADC synchronization H6 VaconBus data from control board to ASIC H7 VaconBus data from ASIC to control board T Trip signal H22 H21 Figure 24. Internal fibre cable connections, ATV780C56Y to ATV780C71Y 7

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Low Voltage Switchboards The Best Technical Solution for Your Ship

Low Voltage Switchboards The Best Technical Solution for Your Ship The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Pre-installation Manual. CONCEPT Processor 305 DW / 405 DW / 505 DW 505 DW XP

Pre-installation Manual. CONCEPT Processor 305 DW / 405 DW / 505 DW 505 DW XP Pre-installation Manual CONCEPT Processor 305 DW / 405 DW / 505 DW 505 DW XP Pre-installation Manual CONCEPT Processor 305 DW / 405 DW / 505 DW / 505 DW XP T11336 Edition AA, April 2013 This book has

More information

SERVER ROOM CABINET INSTALLATION CONCEPTS

SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS ZPAS 169 EXAMPLES OF SERVER ROOMS PROJECTS WITH ZPAS CABINETS Data Box in the

More information

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The

More information

vacon 100 vacon 100 flow vacon 100 hvac ac drives installation manual wall-mounted drives

vacon 100 vacon 100 flow vacon 100 hvac ac drives installation manual wall-mounted drives vacon 100 vacon 100 flow vacon 100 hvac ac drives installation manual wall-mounted drives PREFACE VACON 3 PREFACE Document ID: DPD01711F Date: 8.7.2015 ABOUT THIS MANUAL This manual is copyright of Vacon

More information

Technical data UNIBLOCK UBSF 180 625

Technical data UNIBLOCK UBSF 180 625 Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power

More information

1. How to Read these Operating Instructions 3. 2. Safety Instructions and General Warning 7

1. How to Read these Operating Instructions 3. 2. Safety Instructions and General Warning 7 VLT Automation Drive FC 300 Contents Contents 1. How to Read these Operating Instructions 3 How to Read these Operating Instructions 3 Approvals 4 Symbols 4 Abbreviations 5 2. Safety Instructions and General

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

DIGITUS Network & Server Cabinets. UNIQUE Series

DIGITUS Network & Server Cabinets. UNIQUE Series DIGITUS Network & Server Cabinets UNIQUE Series Benefits - Server Rack 4-Point locking system front door 3-point locking system rear door Swing handle lock with profile zylinder in front and rear door

More information

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit Installation Instructions This document provides instructions for the installation of a DC bus connector kit for PowerFlex 700S and 700H frame 12 drives

More information

ST Series POWER SUPPLIES USER INSTRUCTIONS

ST Series POWER SUPPLIES USER INSTRUCTIONS Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional

More information

AC-DC Converter Application Guidelines

AC-DC Converter Application Guidelines AC-DC Converter Application Guidelines 1. Foreword The following guidelines should be carefully read prior to converter use. Improper use may result in the risk of electric shock, damaging the converter,

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................

More information

USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920

USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920 USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920 [This page intentionally left blank] Warning for Your Protection 1. Read these instructions. 2. Keep these

More information

Incubator with mechanical convection

Incubator with mechanical convection BF series 400 Incubators and cooling incubators Incubator with mechanical convection The BINDER incubator of the BF series with mechanical convection is suitable for all gentle incubation applications,

More information

Power Supplies 3. SDN-P DIN Rail Series

Power Supplies 3. SDN-P DIN Rail Series SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

Cooktop Low-Profile Ventilation Hoods

Cooktop Low-Profile Ventilation Hoods INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............

More information

EFC 3600. Frequency converters

EFC 3600. Frequency converters 2 Bosch Rexroth AG Electric Drives and Controls Documentation Compact and complete: space saving side-by-side assembly, plug-in I/O terminals, with brake chopper and mains filter for ultra-simple installation

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module! Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8

More information

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power: PHOTOVOLTAIC (PV) solar panels Electricity - CE & ISO 9000 certified Photovoltaic solar panels convert sunlight into useful electricity. ZEDfabric supplies high quality mono-crystalline silicon cell PV

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

Frequency Converter Fv

Frequency Converter Fv 2 Bosch Rexroth AG Electric Drives and Controls Documentation Brake chopper with up to 30 kw continuous braking power Easy to operate and service (detachable fan, LCD operating panel with copy function)

More information

I/A Series HARDWARE Product Specifications. G50 Server Enclosure PSS 21H-2X50 B4 FEATURES

I/A Series HARDWARE Product Specifications. G50 Server Enclosure PSS 21H-2X50 B4 FEATURES I/A Series HARDWARE Product Specifications G50 Server Enclosure PSS 21H-2X50 B4 Note: Shown without Cable Base (Included) The I/A Series G50 Server Enclosure with front and rear access provides environmental

More information

Access Server Rack Cabinet Compatibility Guide

Access Server Rack Cabinet Compatibility Guide Access Server Rack Cabinet Compatibility Guide A Guide to the Selection and Evaluation of Access Server Rack Cabinets for Compatibility and Use with Third Party Server Chassis Kalkenstraat 91-93 B-8800

More information

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table

More information

SINAMICS G130. Braking Module / braking resistor. Operating Instructions 05/2010 SINAMICS

SINAMICS G130. Braking Module / braking resistor. Operating Instructions 05/2010 SINAMICS SINAMICS G130 Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Connection 4 Maintenance and servicing 5

More information

-Liquid-cooled frequency converter switchgear

-Liquid-cooled frequency converter switchgear -Liquid-cooled frequency converter switchgear VEO knows your needs We deliver automation and electrification solutions for energy production, distribution and consumption in close collaboration with our

More information

IT infrastructure Efficiency-boosting solutions. nextlevel. for data centre

IT infrastructure Efficiency-boosting solutions. nextlevel. for data centre IT infrastructure Efficiency-boosting solutions nextlevel for data centre 2 Rittal IT infrastructure The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind,

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

M7250P. PoE Powered. Gigabit Ethernet Media Converter 1000BASE-TX TO 1000BASE-SX/LX. Installation Guide

M7250P. PoE Powered. Gigabit Ethernet Media Converter 1000BASE-TX TO 1000BASE-SX/LX. Installation Guide M7250P PoE Powered Gigabit Ethernet Media Converter 1000BASE-TX TO 1000BASE-SX/LX Installation Guide September 2009 VERSITRON, Inc. 83 Albe Drive - Suite C Newark, DE 19702 www.versitron.com www.versitron.com

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

39HQ Airovision Air Handling Units

39HQ Airovision Air Handling Units 39HQ Airovision Air Handling Units Mounting instructions CONTENTS 1 - TRANSPORT AND LIFTING INSTRUCTIONS... 3 1.1 - General... 3 1.2 - Transport and storage... 3 1.3 - Roof edge protection during transport

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

42U/45U 28" Wide Rack Installation & Service Guide

42U/45U 28 Wide Rack Installation & Service Guide 42U/45U 28" Wide Rack Installation & Service Guide 96-00171-005 Rev B Important Information Information in this document is subject to change without notice and does not represent a commitment on the part

More information

Technical Description. Transistor D.C. Chopper Controller Type GS 24 S

Technical Description. Transistor D.C. Chopper Controller Type GS 24 S Technical Description Transistor D.C. Chopper Controller Type GS 24 S Table of contents 1. Getting started guide 2. General information 2.1. Characteristics 2.2. Accessories 3. Information about the Machine

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole) Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

Rack installation instructions

Rack installation instructions Rack installation instructions Review the documentation that comes with the rack cabinet for safety and cabling information. Before you install the server in a rack cabinet, review the following guidelines:

More information

16/32 Channel 1U Rack Mount CCTV Power Supply

16/32 Channel 1U Rack Mount CCTV Power Supply 16/32 Channel 1U Rack Mount CCTV Power Supply Manual PH-A3224-GUQ Shown 16-Channel 32-Channel PTC PH-A1612-PUQ PH-A3224-PUQ Glass Fuse PH-A1612-GUQ PH-A3224-GUQ Industrial design 12 Amp 3 Amps per channel

More information

Material test chamber with mechanical convection

Material test chamber with mechanical convection FP series 400 Material test chambers Material test chamber with mechanical convection A BINDER material test chamber with mechanical convection of the FP series provides reliably short drying times and

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

INFRARED QUARTZ WALL HEATER

INFRARED QUARTZ WALL HEATER INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this

More information

RAY-MAX Integrated Solar Power Strip

RAY-MAX Integrated Solar Power Strip RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...

More information

2013 Wireless Video Intercom INSTALLATION GUIDE

2013 Wireless Video Intercom INSTALLATION GUIDE 2013 Wireless Video Intercom INSTALLATION GUIDE INDEX System configuration and wiring VL-SWD501 System Component.. 4 VL-SWD501EX wiring schematic diagram VL-SWD501EX wiring type and length... 5.... 6 Door

More information

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels

More information

Installation Instructions For Slider Casement Air Conditioners

Installation Instructions For Slider Casement Air Conditioners Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT

More information

Contractors Guide Central Inverter System Installation

Contractors Guide Central Inverter System Installation Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

How To Build A Low Voltage Capacitor Lvcp

How To Build A Low Voltage Capacitor Lvcp Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched

More information

Installation Instructions

Installation Instructions READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

Bubble King. User Manual

Bubble King. User Manual Bubble King User Manual TABLE OF CONTENTS 1. Before You Begin... 3 What Is Included... 3 Unpacking Instructions... 3 Claims... 3 Text Conventions... 3 Icons... 3 Document Information... 3 Product at a

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

KNX L. Brightness Sensor. Technical specifications and installation instructions Item number 70119

KNX L. Brightness Sensor. Technical specifications and installation instructions Item number 70119 EN KNX L Brightness Sensor Technical specifications and installation instructions Item number 70119 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49 (0) 70

More information

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01 ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions

More information

Dimensions (HxDxW) Total Cabinet Area 89.96x 39.69 x 24 in/ 2,285 x 1,008.17 x 612.77 mm 95.47x 48 x 32 in/ 2,425 x 1,219.2 x 812.

Dimensions (HxDxW) Total Cabinet Area 89.96x 39.69 x 24 in/ 2,285 x 1,008.17 x 612.77 mm 95.47x 48 x 32 in/ 2,425 x 1,219.2 x 812. 1 Compaq 10000 Series Racks The 10000 series racks are a family of 1000mm deep racks which are available in 22U, 36U, 42U and 47U 600mm widths. Compaq 10000 Series Racks provides a common, integrated platform

More information

vacon nxs/p user manual wall-mounted drives standalone drives ac drives

vacon nxs/p user manual wall-mounted drives standalone drives ac drives vacon nxs/p ac drives user manual wall-mounted drives standalone drives PREFACE VACON 3 PREFACE Document ID: DPD00910D Date: 20.2.2015 ABOUT THIS MANUAL This manual is copyright of Vacon Plc. All Rights

More information

VLT Series 3500 Adjustable Frequency Drive Instruction Manual

VLT Series 3500 Adjustable Frequency Drive Instruction Manual Adjustable Frequency Drive Instruction Manual VLT Series 3500 Instruction Manual 175R5237 - Document Version 5.00 This manual applies to all VLT Series 3502-3800 Adjustable Frequency Drives with software

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

KNX R. Rain Sensor. Installation and Adjustment

KNX R. Rain Sensor. Installation and Adjustment EN KNX R Rain Sensor Installation and Adjustment 1 Content 1. Description... 3 1.1. Technical specifications... 3 2. Installation and commissioning... 4 2.1. Installation notes... 4 2.2. Location... 4

More information

=============================== WARNING

=============================== WARNING =============================== WARNING EXPLANATION OF GRAPHICAL SYMBOLS This symbol is intended to alert the user to the presence of unprotected dangerous voltage" within the product's enclosure that

More information

3 IN 1 BATHROOM HEATER

3 IN 1 BATHROOM HEATER 3 IN 1 BATHROOM HEATER MODEL NO.: A515 - SH MINI FUNCTION: HEATER, EXHAUST FAN AND LIGHT Dear customers, Thank you for selecting the AUPU 3 in 1 Bathroom Heater. Please read all instructions before commencing

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Installation instructions of the MIDI-Heki roof light with operating bar, with crank or electrical version

Installation instructions of the MIDI-Heki roof light with operating bar, with crank or electrical version Installation instructions of the MIDI-Heki roof light with operating bar, with crank or electrical version with operating bar with crank electrical version 1. Prerequisite for a correct installation of

More information

Terminal Boxes Series 8146

Terminal Boxes Series 8146 Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm

More information

GRID TIE INVERTER MANUAL GRID TIE INVERTER SWEA EUROPE FRIENDLY CARE FOR YOUR EXPENSES AND OUR ENVIRONMENT! WWW.SWEA.

GRID TIE INVERTER MANUAL GRID TIE INVERTER SWEA EUROPE FRIENDLY CARE FOR YOUR EXPENSES AND OUR ENVIRONMENT! WWW.SWEA. GRID TIE INVERTER MANUAL GRID TIE INVERTER STARTER-KIT FOR SMALL urban WindturbineS UP TO MAX 1000 Watt TYPE: UWT-I-250 ST-KIT SWEA EUROPE FRIENDLY CARE FOR YOUR EXPENSES AND OUR ENVIRONMENT! WWW.SWEA.NL

More information

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: info@switchgearcompany.eu

More information

ATS Overhead Table Shelf System INSTRUCTION MANUAL

ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship

More information

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for. The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved

More information

19" Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted.

19 Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted. 19" Data Racks Attractive design and high quality are characteristic. Basic framework is welded from multiple bent metal plate, which assures great rigidity suitable for heavier equipment. All profile

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Operating Manual UWAPS-TINY Series

Operating Manual UWAPS-TINY Series Operating Manual UWAPS-TINY Series Powecon Oy WWW.POWECON.FI 1/9 Table of content 1 Warranty...3 2 Safety information...3 3 Abbreviations and terminology...3 4 List of appendices...4 5 Introduction...4

More information

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual 5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...

More information

Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W)

Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Table of Contents Introduction.. Power Over Ethernet (PoE) & Features.... Unpacking and

More information

Installation, operation and maintenance manual TX 35A

Installation, operation and maintenance manual TX 35A Installation, operation and maintenance manual TX 35A Rev.10 may 2012 Page 1 of 18 1.0.0 Table of contents INSTALLATION, OPERATION AND MAINTENANCE MANUAL...1 1.0.0 TABLE OF CONTENTS...2 2.0.0 ILLUSTRATIONS...2

More information

SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction

SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to

More information

4KVA/5KVA Parallel Installation Guide

4KVA/5KVA Parallel Installation Guide 4KVA/5KVA Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to 4 units. The supported maximum

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

Heating oven with mechanical convection

Heating oven with mechanical convection FD series 53 Drying ovens / Heating ovens Heating oven with mechanical convection A BINDER FD series heating oven is always used when fast drying and sterilization is required. Thanks to its fully homogeneous

More information

SNQ-60x0-320 Series Data Center Switch. Quick Installation Guide

SNQ-60x0-320 Series Data Center Switch. Quick Installation Guide Introduction This guide is to assist the reader with the most basic form of installation and connection to switches in this series. As there is more than one switch in this series, the diagrams might slightly

More information

Elegant ECM. ELEGANT ECM air conditioners allow. The range is made up of 12 models: Ceiling Air Conditioner

Elegant ECM. ELEGANT ECM air conditioners allow. The range is made up of 12 models: Ceiling Air Conditioner Elegant ECM Ceiling Air Conditioner ELEGANT ECM air conditioners allow to heat and cool very economically small and medium areas, like shops, show rooms, workshops, supermarkets. The range is made up of

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

LOW-VOLTAGE CURRENT TRANSFORMERS

LOW-VOLTAGE CURRENT TRANSFORMERS LOWVOLTAGE CURRENT TRANSFORMERS 5 A Power network meters ND0 and ND type. N4Z and N5Z Tel: (+48 68) 45 75 39; 45 75 305; 45 75 3; 45 75 368; email: export@lumel.com.pl ul. Słubicka 657 Zielona Góra CONTENTS

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information