1 Data Bulletin 0760DB0204R9/07 12/2007 Cedar Rapids, IA, USA Replaces 0760DB0204 Dated 04/2001 Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760 Precautions DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH This document is written for qualified electricians. Other than connecting and disconnecting receptacle loads, the work described here should be done only by trained professionals. Failure to follow these instructions will result in death or serious injury. Introduction Types of AFCIs When an AFCI trips, the cause of the trip must be determined before placing the circuit back into service. This data bulletin outlines several of the most common causes of AFCI tripping however it does not cover all possible causes that can occur. Arc Fault Circuit Interrupters (AFCIs) are required for installation in residences under the 2002 National Electrical Code (NEC ). The 2005 NEC requires AFCIs to transition from the present (branch/feeder) AFCIs to combination AFCIs. The QO and Homeline Combination Arc-fault Circuit Interrupters, also referred to as CAFCIs, were developed to meet the NEC 2005 requirements effective January 1, Arc Fault Circuit Interrupters (AFCIs) are devices intended to mitigate the effects of arcing faults by functioning to de-energize the circuit when an arcfault is detected. It is important to understand which device you have before attempting to determine the cause of AFCI tripping. Branch/Feeder AFCI: An arc fault circuit interrupter intended to provide protection for branch circuit wiring against unwanted effects of arcing. Square D branch/feeder AFCIs have either blue or green test buttons. Combination AFCI: An arc fault circuit interrupter provides the same protection as the branch/feeder AFCI with the additional protection for branch circuit extension wiring (including power cords, extension cords, etc.). Square D combination AFCIs have white test buttons. Figure 1: Types of AFCIs (Example Labels) Branch/Feeder AFCI (Blue or Green Test Button) Combination AFCI (White Test Button) 1

2 Determining the Cause of AFCI Tripping 0760DB0204R9/07 Data Bulletin 12/2007 Causes of AFCI Tripping A standard QO or Homeline circuit breaker will trip to protect a circuit from overloads or short circuits. In addition to standard circuit breaker protection, AFCIs mitigate against the effects of arc faults. If an AFCI trips soon after it has been installed, the cause of the tripping may be different than if the AFCI has been in service for some time. The cause of tripping for newly installed AFCIs is much more likely to be incorrect installation, and much less likely to be an appliance problem. An AFCI can trip by one of the following causes: Overloads (Page 2) faults (Page 5) Short circuits (Page 2) Damaged AFCI (Page 5) Improper AFCI Installation (Page 3) Arc faults (Page 6) Some specific examples of several of these causes are described on pages 8 and 9. AFCI Trip due to Overload NOTE: When calculating loads, always include everything on the circuit. Keep in mind that the circuit may serve loads outside the affected room. AFCI Trip due to Short Circuit An overload trip is caused by a circuit carrying more current than the handle rating of the circuit breaker allows. For example, a 20 A circuit breaker can carry a load totaling 2,400 watts (at 120 V), but should not be loaded with more than 80% or 16 A (1,920 watts) continuous, per the NEC. The overload feature of most circuit breakers (including AFCIs) works via a bi-metal component of the circuit breaker heating and bending to cause the circuit breaker to open. Its operation is a function of the time and current. Tripping occurs after a delay; the greater the overload, the faster the circuit breaker will trip. First check to see if there are high current loads overloading the circuit. Be sure to check all receptacles on the circuit, not only the receptacles in the affected room. Calculate the loads to ensure they don t exceed the circuit breaker s carrying capacity. An example of an overload trip is described on page 8 A short circuit allows a very high amount of current to flow through the circuit. A short can be between either line to the neutral or line to ground. As with most circuit breakers, an AFCI has an electromagnetic function that opens almost instantaneously when it detects a short circuit, typically in less than one-tenth of a second. It is important that the circuit breaker operates quickly to avoid damage to the conductors between the load center and the short circuit. Short Circuits If a circuit breaker trips instantaneously when an appliance is plugged in or turned on, remove the appliance from the circuit and turn the circuit breaker on. If the circuit breaker does not trip, there is possibly a short circuit in the appliance or its electrical cord. If there does not appear to be a short circuit in one of the plugged-in devices, including the electrical cords, then there may be a short circuit in the permanent wiring. Before checking the circuit, remove all power from the circuit by moving the AFCI handle to the OFF position. Next, unplug all the devices from all receptacles on the circuit and turn off all lights or other loads. Finally, using an ohmmeter at the load center, check the resistance between line and neutral and line and ground. If either measurement shows low resistance (less than one kilohm), there is a short circuit between those conductors (or there are still connected loads). High resistance indicates the likely absence of a short circuit. For additional information, refer to Types of Faults Leading to AFCI Tripping on page Schneider Electric All Rights Reserved

3 0760DB0204R9/07 Determining the Cause of AFCI Tripping 12/2007 Data Bulletin High Inrush Currents Improper AFCI Installation Inadvertent ed One phenomenon that appears as a short circuit to a circuit breaker (including AFCIs) is high inrush current. Consider receptacles with one-half switched by a light switch. High inrush current can occur when several loads (or one large load) are connected to the switched half of the receptacles. If all of the individual loads (plugged into the switched half of the receptacle) are in the ON position, and then the light switch that controls these receptacles is then switched ON, a momentary high inrush current that far exceeds the normal operating current of these loads may occur. This will appear as a short circuit to a circuit breaker and cause it to trip. The solution to this situation is to simply plug most of the loads into the non-switched half of the receptacles. This will avoid turning on several of the loads simultaneously. NOTE: The AFCI includes a test button on the front. Its purpose is to verify that the AFCI is functioning properly. This test button only functions if the AFCI is installed correctly. A special type of ground fault (but a frequent one) is an inadvertent grounded neutral. This occurs when the neutral conductor contacts a grounded conductor (ground wire, grounded outlet box, etc.). This can happen in a receptacle box, switch box, or a fixture. When this condition occurs, the balance between the line and neutral currents no longer exists and the AFCI trips. Figure 2: Detection of ed detection by AFCI Load ed neutral A grounded neutral appears as a ground fault (not necessarily an arcing fault) Improper AFCI Connections The next thing to check is the installation of the AFCI in the load center. Were the connections to the AFCI made properly? It is mandatory that these three connections are correct: Load power wire (black) Load neutral wire (white) Panel neutral wire (coiled, white pigtail) Make sure the load power and load neutral wires are not intermixed between two or more branch circuits. If they are, the AFCI will immediately trip when any load is applied. If you see a red wire connected to the load power terminal of the AFCI, see AFCI Tripping on Circuits with Shared s on page 4. NOTE: Usually, the color-coded wires make it easy to confirm that they were installed in the load center correctly. Refer to the installation instructions that came with the AFCI: Branch/feeder AFCIs (blue or green test button): (bulletin no xx or xx). Combination AFCIs (white test button): (bulletin no xx or xx). Figure 3: Example of Proper AFCI Wiring 120/240 Vac Source N L1 L2 Load Power 120 Hot Load Duplex Receptacle Schneider Electric All Rights Reserved 3

4 Determining the Cause of AFCI Tripping 0760DB0204R9/07 Data Bulletin 12/2007 AFCI Tripping on Circuits with Shared s A single-pole AFCI will not operate properly on shared neutral wiring. This may not become apparent until a load is applied to at least one of the circuits. Figure 4: Example of Shared NL1L2 Circuit 2 Red Red Black Shared Circuit 1 Black Load Center Junction Box Some localities allow the use of a shared neutral when running a home run cable to two adjacent bedrooms at the far end of a house. Other situations where shared neutrals may be found include: separate circuits for lighting and receptacle outlets kitchen circuits where under-cabinet outlets are separate from abovecounter receptacles The most obvious clue that there is shared neutral wiring is the presence of a black, a red, and a white wire (in the load center) from one cable going to two single-pole AFCIs (See Figure 4). The best solution to this is to avoid the use of shared neutrals and their inherent problems. Serious Disadvantages to Sharing s The practice of shared neutrals may seem attractive due to possible savings associated with the reduction of a neutral conductor. However, there are serious disadvantages to sharing neutrals: Figure 5: System with Shared System with Lost Shared Damaging Voltage Rise Due to Loss of Shared 1 Shared V 120 V 120 V XV 240 XV Load 1 Load 2 Load 1 Load 2 If the shared neutral is lost, the connected loads are subject to voltages varying from 0 to 240 V (line-to-line). This is especially true if one load has much larger impedance than the other. The likely result from this is severe damage to some connected devices due to extreme under- and over-voltage conditions. See Figure 5. On two-pole common-trip circuit breakers, both circuits are interrupted during any type of fault. If a shared neutral circuit feeds two rooms, then both rooms lose power if a fault occurs in either. If a shared neutral circuit feeds receptacles and lights, both will lose power with a fault on either one. On two-pole independent-trip circuit breakers, one may find hot wires in a junction box that was presumed dead. One cannot overemphasize how dangerous this would be. If one of the shared neutral circuits were to trip due to a short-circuit or overload, the other circuit would remain hot. Anyone servicing any device in that junction box may be exposed to live conductors Schneider Electric All Rights Reserved

5 0760DB0204R9/07 Determining the Cause of AFCI Tripping 12/2007 Data Bulletin AFCI Trip due to Fault faults are sometimes called residual-current faults or earthleakage faults. They are due to unwanted paths from line to ground or neutral to ground. Unlike a short circuit, ground faults are typically much lower current. Most frequently, ground faults are caused by gradual deterioration of the wiring insulation or by moisture in the circuit. Figure 6: Diagram of a Fault A ground-fault trip may be due to a very small amount of current leaking to ground. Leakage to ground Fault Interrupters (GFIs) Locating a Fault Damaged AFCI Fault Interrupters (GFIs) can be found in a kitchen, bathroom, utility room, or outdoors. GFIs have the sensitivity (4 6 ma) needed to provide protection for people who might contact the circuit in some way. Square D AFCIs do not provide people protection, but do detect residual current levels starting at approximately 50 ma. In simple terms, both GFIs and AFCIs detect residual current by comparing the current flowing out on a line with current returning via the neutral. If these currents are not equal, then it is likely that there is an alternate return path, and thus a ground fault. A ground fault can be in either the permanent wiring, in an appliance, or in the appliance cord. If, after all appliances are removed from the circuit, the AFCI continues to trip, there may be a ground fault in the permanent wiring. A test to check for a ground fault is to temporarily substitute a GFI circuit breaker for the AFCI. The GFI will trip at 4 6 ma which is a lower level than the AFCI. If a ground fault is diagnosed, the faulty circuit (or the appliance) must be replaced or repaired. NOTE: Some electrical equipment such as motors, power converters, etc. may give the appearance of a ground fault, due to normal, non-linear behavior. But usually this leakage is much less than the 50 ma level, especially for devices found in a bedroom. Also refer to Inadvertent ed on page 3 for additional information. Disconnect the load power and the load neutral wires from the AFCI. If it continues to trip, the AFCI may be damaged and should be replaced. If it is not obvious whether the problem is in the AFCI or the circuit, replace the AFCI with a new one. If the new AFCI does not trip, it is likely that the old one was damaged Schneider Electric All Rights Reserved 5

6 Determining the Cause of AFCI Tripping 0760DB0204R9/07 Data Bulletin 12/2007 Arc Fault Trip CAUTION HAZARD OF INJURY OR EQUIPMENT DAMAGE Do not continue to use any suspect loads until they are inspected and serviced. Replace them if necessary. Failure to follow this instruction can result in injury or equipment damage. Tripping due to an arc fault appears to be instantaneous as do those from a short circuit trip and a ground-fault trip (typically in less than one second). The only type of tripping that responds relatively slowly is tripping due to overloads (seconds or tens of seconds). If an arc-fault is suspected, the first diagnostic step should be to determine if the arc fault is in the appliance, its power cord, or if it is in the permanent wiring. Figure 7: Damaged Electrical Cord Old, damaged electrical cords are a common place for short circuits. Checking Appliances Checking Permanent Wiring To narrow the problem down to the appliance or its power cord, first, isolate all appliances by unplugging them. If the AFCI does NOT trip when it is reclosed, then the problem is likely an arc fault in either the appliance or its power cord. A series arc fault will not be detected until a load is connected and energized. The faulty appliance can be identified by connecting one load at a time until the AFCI trips again. Check the last load connected for arcing, insulation problems, shorted or pinched wires, etc. For additional information refer to Types of Faults on page 7. Also see Example 4 Arc Fault Trip on page 9. If the AFCI continues to trip after all of the appliances are unplugged, then a problem in the permanent circuit or a problem with the AFCI can be considered. First, check for arcing, insulation problems, and shorted or pinched wires at outlets, switches, and junction boxes. For additional information refer to Types of Faults on page Schneider Electric All Rights Reserved

7 0760DB0204R9/07 Determining the Cause of AFCI Tripping 12/2007 Data Bulletin Types of Faults The following table can be used to determine the type of fault that may cause an AFCI to trip. CAUTION HAZARD OF INJURY OR EQUIPMENT DAMAGE It is important to recognize that the AFCI has provided an indication of a condition that could be a fire hazard. Do not continue to use a circuit in this condition without correction. Failure to follow this instruction can result in injury or equipment damage. Table 1: Types of Faults Leading to AFCI Tripping Type of Fault Current Available at the Fault 1 Detected by: (AFCI Type) Description Branch/Feeder AFCI 50 ma Combination AFCI 75 A Branch/Feeder AFCI 5 A Combination AFCI The AFCI trips with or without a load connected to a receptacle. 5 A Combination AFCI 50 ma Branch/Feeder AFCI Combination AFCI The AFCI trips only with a load connected to a receptacle. 5 A Combination AFCI 1 Values are approximate Schneider Electric All Rights Reserved 7

8 Determining the Cause of AFCI Tripping 0760DB0204R9/07 Data Bulletin 12/2007 Examples Example 1 AFCI Trip Due to Overload NOTE: When calculating loads, always include everything on the circuit. Keep in mind that the circuit may serve loads outside the affected room. The bedroom AFCI trips about 30 seconds after a blow-dryer is turned on. The following devices shut off at the same time. Electric space heater Dresser lights Floor lamp Television Coffee maker Hair dryer Total 1,300 watts 150 watts 150 watts 200 watts 600 watts 1,200 watts 3,600 watts In example one, the trip was not instantaneous. This indicates an overload trip. Calculating the total load of the circuit results in a total of 3,600 watts, far exceeding the 2,400 watts that a 20 A AFCI can serve without tripping. In fact, checking the trip curve for the AFCI shows that tripping should occur in 30 seconds when subjected to an overload of 1.5 times the rating (in this case, 3,600 watts). One of the more obvious fixes for this example would be to leave the space heater off while using the hair dryer. Reset the AFCI and turn on each device except the space heater. Example 2 Short Circuit in the Device The bedroom AFCI trips immediately whenever the electric space heater is turned on, causing everything in the room to turn off. Unlike the previous scenario, the hair dryer is not in use and there is no 30-second delay. In example two, the trip was instantaneous. This indicates some kind of short circuit, or possibly a ground fault or arc fault. First, determine what load may have been added to the circuit when the circuit breaker tripped. In this case, it was the electric heater, so it should be unplugged and checked for shorts if the circuit breaker can be reset when the electric heater is disconnected, this would indicate a possible short in the heater or its electrical cord, but may also indicate a ground fault or arc fault. Example 3 Fault Trip Neither an overload nor a short circuit are found to be the cause of the bedroom AFCI tripping. Does this mean the trip was caused by an arc fault? Not necessarily. An AFCI can also be tripped by the presence of a ground fault. In example three, disconnect all appliances from the circuit. Substitute a GFI circuit breaker for the AFCI. If the GFI trips, then there is probably a ground fault in the circuit. If the GFI does not trip, add the appliances to the circuit. If the GFI trips when one of the appliances is added, that appliance must be replaced or repaired. If the GFI does not trip when all of the appliances are added, there is probably not a ground fault Schneider Electric All Rights Reserved

9 0760DB0204R9/07 Determining the Cause of AFCI Tripping 12/2007 Data Bulletin Example 4 Arc Fault Trip The AFCI trips only when someone is sitting in a rocker in the corner. The old lamp cord passing under the rocker has been there long enough so that the insulation on both conductors has been damaged, causing a parallel arc fault (line to neutral). The cord should be replaced. In example four, disconnect all appliances from the circuit. The AFCI does not trip when reclosed, so the problem would appear to be one of the appliances. A series arc fault will not be detected until a load is connected and energized. See further discussion below. Connecting them one load at a time shows that the AFCI trips when the lamp in the corner is plugged in. An inspection of the lamp shows that the lamp cord, which is old and worn, has damage to the insulation on both conductors, causing a parallel arc fault (line to neutral). Example 5 Inadvertent ed The wiring in a new split-level is complete and the electric utility has hooked up the meter. Inspection shows that all the circuits are fine except for one bedroom AFCI. It trips whenever a ceiling light is turned on. To determine if the problem in example five is a grounded neutral, visually inspect the wiring at the ceiling light fixture. Discovery of the bare ground wire touching the neutral wiring connector of the lamp shows an inadvertent grounded neutral. The symptom the AFCI tripping immediately when the lamp is turned on is explained by the ground wire touching the neutral Schneider Electric All Rights Reserved 9

10 Determining the Cause of AFCI Tripping 0760DB0204R9/07 Data Bulletin 12/2007 Conclusion Just as in existing installations, parallel arc faults in new installations are generally an infrequent cause of an AFCI tripping. However, if other causes of tripping have been ruled out, look at two potential arc fault causes: Series arcing: A series arc is caused by a break in a conductor, and low current flow created by the high-resistance break attempts to cross the break and thus arcs. Loose connections can also be the cause of a series arc. Branch/feeder circuit breakers typically do not detect and clear the lower-energy, series arcs, unless the condition involves a fault to ground. However, the AFCI circuit breaker will detect and clear this type of fault. The sensing circuitry in the AFCI circuit breaker will sense either a parallel or series arc fault as low as 5 amperes and residual current levels starting at approximately 50 ma Parallel arcing: A parallel arc is caused by an arcing fault between the line conductor and either neutral or ground. While these may be easy to detect in appliances and their electric cords, they can be difficult to locate in the permanent wiring. The most common cause of arcing in permanent circuits is a nail or screw driven through the wall into the conductor, damaging the insulation, and creating a low impedance path for the arc. Understanding the different trip functions of an AFCI can help to determine why it has tripped. The preceding examples are not comprehensive but they should serve as a beginning guide to help you determine what has happened to cause a trip and what the proper correction should be. Schneider Electric USA 3700 Sixth St SW Cedar Rapids, IA, USA SquareD ( ) Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material Schneider Electric All Rights Reserved

Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760

Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760 Data Bulletin Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760 Retain for future use. 0760DB0204 Replaces 0760DB0204 R09/07 Precautions DANGER

More information

GE Industrial Solutions. Residential Electronic Circuit Interrupters

GE Industrial Solutions. Residential Electronic Circuit Interrupters GE Industrial Solutions Residential Electronic Circuit Interrupters Dual Function Circuit Interrupter (DFCI) Provides ground fault and arc fault circuit protection in one unit The 2014 National Electric

More information

2 electrical. electrical. 2010 PulteGroup, Inc. All Rights Reserved.

2 electrical. electrical. 2010 PulteGroup, Inc. All Rights Reserved. 2 12 2010 PulteGroup, Inc. All Rights Reserved. circuit breakers Circuit breakers protect your home s system from power failure. The wiring in your home is protected by circuit breakers. Circuit breakers,

More information

Arc Fault Circuit Interrupters Frequently Asked Questions

Arc Fault Circuit Interrupters Frequently Asked Questions Contents My AFCI is tripping! What do I do? What is the difference between branch feeder and combination type Arc Fault Circuit Interrupters? What is new with the 2008 NEC versus the 2005 NEC with respect

More information

in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put it into perspective: Electrocutions can be Prevented

in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put it into perspective: Electrocutions can be Prevented Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, injure 1,400 people, and account

More information

in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put Into Perspective Electrocutions Can Be Prevented

in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put Into Perspective Electrocutions Can Be Prevented Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, 1,400 injuries, and $1.4 billion

More information

Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?

Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords? Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are

More information

Help protect your home, possessions and family.

Help protect your home, possessions and family. Help protect your home, possessions and family. A guide to your Square D electrical distribution system SM Make the most of your energy Understanding your home s electrical distribution system As one of

More information

HOUSING QUALITY STANDARDS (HQS)

HOUSING QUALITY STANDARDS (HQS) HOUSING QUALITY STANDARDS (HQS) Series 5 Electrical Safety And INSPECTIONS 5.01 ELS Revised 8-17-06 Electricity is Dangerous All electrical repairs should be made by licensed professionals. Touching any

More information

OSHA Region 1 Cooperative and State Programs Electrical Training/Inspection Roll Up

OSHA Region 1 Cooperative and State Programs Electrical Training/Inspection Roll Up OSHA Region 1 Cooperative and State Programs Electrical Training/Inspection Roll Up Extension Cords GFCIs Power tools Electrical Training/Inspection Electrical equipment, cords and power tools are used

More information

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY RV Products Division SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY Airxcel, Inc. RV Products Division P.O. Box 4020 Wichita, KS 67204 1976A376 (1-11) TABLE OF CONTENTS

More information

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if

More information

Electrical Resistance Resistance (R)

Electrical Resistance Resistance (R) Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed

More information

Protect your home and family with Advanced Technology from Cutler-Hammer

Protect your home and family with Advanced Technology from Cutler-Hammer Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths

More information

Electrical Safety - Construction. OSHA Office of Training & Education 1

Electrical Safety - Construction. OSHA Office of Training & Education 1 Electrical Safety - Construction OSHA Office of Training & Education 1 Electricity - The Dangers About 5 workers are electrocuted every week Causes 12% of young worker workplace deaths Takes very little

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

Home Electrical Safety Challenge

Home Electrical Safety Challenge Home Electrical Safety Challenge Home Electrical Safety Challenge Why is there a different kind of outlet in my bathroom? What does that TEST button do? Why does the circuit breaker trip every time my

More information

Section B: Electricity

Section B: Electricity Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn

More information

Parallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected

Parallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected This sample chapter is for review purposes only. Copyright The Goodheart-Willcox Co., Inc. All rights reserved. Electricity Objectives After studying this chapter, you will be able to answer these questions:.

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

CONSIDERATIONS FOR INSTALLATION OF SMOKE ALARMS ON RESIDENTIAL BRANCH CIRCUITS

CONSIDERATIONS FOR INSTALLATION OF SMOKE ALARMS ON RESIDENTIAL BRANCH CIRCUITS CONSIDERATIONS FOR INSTALLATION OF SMOKE ALARMS ON RESIDENTIAL BRANCH CIRCUITS October 2005 CPSC-ES-0504 The views expressed in this report are those of the CPSC staff and have not been reviewed or approved

More information

Go Power! Manual GP TS-30. Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: Fax:

Go Power! Manual GP TS-30. Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: Fax: Go Power! Manual GP TS-30 Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: 866-247-6527 Fax: 866-607-6527 Email: info@gpelectric.com Table of Contents 1. INTRODUCTION... 3 2. INSTALLATION...

More information

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.) Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Transfer Switch GPTS 30. Owner s Manual

Transfer Switch GPTS 30. Owner s Manual Transfer Switch GPTS 30 Owner s Manual Table of Contents Introduction 2 Installation 3 Operational Testing 7 Troubleshooting 8 Hi-Pot Testing 9 Generator Note 10 Medical Appliances 10 Caution 10 Warranty

More information

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

ELECTRICAL SAFETY. The standard unit for measuring electrical current. ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety

More information

Ducoterra Radiant Heating Panel Installation Manual

Ducoterra Radiant Heating Panel Installation Manual Ducoterra Radiant Heating Panel Installation Manual 1. Introduction Your new radiant heating panels are designed to heat living and working spaces rapidly and efficiently by radiant heating. Like the sun,

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

Progressive Industries, Inc. EMS Electrical Management System

Progressive Industries, Inc. EMS Electrical Management System Progressive Industries, Inc. EMS Electrical Management System Complete Installation Guide and Operating Instructions for: Model EMS-HW50C Rated at 240V/50A Manufactured by: Progressive Industries, Inc.

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Electrical Safety Tips. Help us keep you safe

Electrical Safety Tips. Help us keep you safe Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural

More information

Reverse-feed applications for circuit breakers

Reverse-feed applications for circuit breakers Technical Publication PU01200001E Contents Description Page Intoduction.......................................................................... 2 breaker classifications..........................................................

More information

A guide to understanding and maintaining your home s electrical system. A publication presented by the Electrical Safety Foundation International

A guide to understanding and maintaining your home s electrical system. A publication presented by the Electrical Safety Foundation International A guide to understanding and maintaining your home s electrical system A publication presented by the Electrical Safety Foundation International What s Inside? Everything you need to know Should You Do-It-Yourself?

More information

Electrical Hazards. Power Tools. Extension Cords

Electrical Hazards. Power Tools. Extension Cords Electrical Hazards Electrical hazards can be found in nearly every roofing work site. Whether the hazard is posed by worn or damaged power tools or cords, improperly grounded tools or equipment, or the

More information

October Safety Subject

October Safety Subject October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that

More information

Understanding GFCIs Developed by the NEMA 5PP Personnel Protection Technical Committee

Understanding GFCIs Developed by the NEMA 5PP Personnel Protection Technical Committee Understanding GFCIs Developed by the NEMA 5PP Personnel Protection Technical Committee The Association of Electrical and What Is to Be Covered? Electrical Shock - Why Have GFCIs? How GFCI s Operate Proper

More information

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management

More information

The Association of Electrical and Medical Imaging Equipment Manufacturers Arc Fault Circuit Interrupter

The Association of Electrical and Medical Imaging Equipment Manufacturers Arc Fault Circuit Interrupter Arc Fault Circuit Interrupter SUCCESS STORIES AFCIs avert potential disaster in South Carolina I would like to take the time and thank you for the Arc Fault breaker, your product saved our lives and our

More information

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section

More information

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by

More information

3053 Electrical Safety Training Program Course Outline

3053 Electrical Safety Training Program Course Outline 3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting

More information

Designing Hipot Test Stations an overview

Designing Hipot Test Stations an overview Designing Hipot Test Stations an overview Dielectric Withstand (Hipot) testing is the most accepted method of ensuring that primary wiring and components are isolated from the safety ground. When combined

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity

More information

Title: Grounding and Bonding Rev-01

Title: Grounding and Bonding Rev-01 Procedure No.: BMEHS-002-012 Page: 1 of 12 Preparer: Owner: Approver: EHS Team Member S/H Manager Site Manager Signed Copy on File Signed Copy on File Signed Copy on File Document Revision Change Table

More information

Construction Electrical Terminology. Electricians

Construction Electrical Terminology. Electricians Construction Electrical Terminology Electricians Acknowledgments Winnipeg Technical College and the Department of Labour and Immigration of Manitoba wish to express sincere appreciation to all contributors.

More information

Introducing Electricity and Electrical Safety

Introducing Electricity and Electrical Safety Introducing Electricity and Electrical Safety Unit: Mechanical Systems and Technology Problem Area: Electrical Systems Student Learning Objectives. Instruction in this lesson should result in students

More information

ELECTRICAL SAFETY RISK ASSESSMENT

ELECTRICAL SAFETY RISK ASSESSMENT ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures

More information

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to

More information

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide *619751* P/N 619751 - Rev C IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS

More information

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents

More information

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS

More information

2015 AFCI code compliant safety. Understanding the CE Code. requirements for AFCI protection

2015 AFCI code compliant safety. Understanding the CE Code. requirements for AFCI protection 2015 AFCI code compliant safety Understanding the 2015 CE Code requirements for AFCI protection Understanding the code for code compliant safety An arc fault is an unintended arc created by current flowing

More information

technology using advanced to reduce electrical fires arc fault circuit interrupters

technology using advanced to reduce electrical fires arc fault circuit interrupters arc fault circuit interrupters using advanced technology to reduce electrical fires NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION Low Voltage Distribution Equipment Section I NTRO D U CTI O N Arc Fault

More information

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical

More information

Generator Transfer Switch Model # HTS15-AUTO

Generator Transfer Switch Model # HTS15-AUTO Generator Transfer Switch Model # HTS15-AUTO Congratulations on your purchase of our Single Circuit Generator Transfer Switch, We hope this meets and exceeds your expectations. If at anytime you have any

More information

Electrocution Hazards

Electrocution Hazards Electrocution Hazards 1 Electricity Accidents People who work directly or indirectly with electricity can be the victims of serious electrocution injury or death on construction sites. These accidents

More information

PORTABLE SCR REGULATED BATTERY CHARGER TECHNICIAN SERVICE GUIDE

PORTABLE SCR REGULATED BATTERY CHARGER TECHNICIAN SERVICE GUIDE *33367* PORTABLE SCR REGULATED BATTERY CHARGER TECHNICIAN SERVICE GUIDE PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS To be able to troubleshoot safely and effectively, it is important

More information

WHITE PAPER: HOME REMODELING & AFCI PROTECTION

WHITE PAPER: HOME REMODELING & AFCI PROTECTION WHITE PAPER: HOME REMODELING & AFCI PROTECTION Remodeling with AFCIs/Page 2 Introduction Americans spent more than $235 billion on home remodeling in 2007 1, fueled in part by do-ityourself home centers,

More information

Unit 4: Electricity (Part 2)

Unit 4: Electricity (Part 2) Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State

More information

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018 USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and

More information

For Models #6-5001, #6-7501, #10-7501 & #10-12K1

For Models #6-5001, #6-7501, #10-7501 & #10-12K1 EmerGen Switch Manual Transfer Switch Manufactured by CONNECTICUT ELECTRIC SWITCH MFG. CO. 1-800-730-2557 OWNER S MANUAL & INSTALLATION INSTRUCTIONS For Models #6-5001, #6-7501, #10-7501 & #10-12K1 PLEASE

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850 Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:

More information

Your Guide to. Electrical Safety

Your Guide to. Electrical Safety Your Guide to Electrical Safety AN INTRODUCTION Electricity is an important part of our daily lives. It's everywhere. It lights our homes, cooks our food, powers our tools, and runs our televisions, radios

More information

Underwater Pool and Spa White LED Light

Underwater Pool and Spa White LED Light Underwater Pool and Spa White LED Light Installation and User s Guide IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Technical Support Phone: (800) 831-7133 - Fax:

More information

Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series

Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series Operating Instructions WARNING CONCERNING THE REMOVAL OF COVER: CAUTION: TO PREVENT THE RISK OF ELECTRIC

More information

Utility Distribution Systems

Utility Distribution Systems Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date

More information

Transfer Switch 30 Amps STS-30. Manual. Please read this manual before operating your transfer switch

Transfer Switch 30 Amps STS-30. Manual. Please read this manual before operating your transfer switch Transfer Switch 30 Amps STS-30 Owner's Manual Please read this manual before operating your transfer switch Section 1 Introduction Function of a Transfer Switch In case of failure of the main AC power

More information

Square D Clipsal C-Bus Network Analyzer

Square D Clipsal C-Bus Network Analyzer Square D Clipsal C-Bus Network Analyzer for Use with C-Bus Wired Networks Instruction Bulletin Retain for future use. Square D Clipsal C-Bus Network Analyzer 63249-420-234A1 Instruction Bulletin 12/2006

More information

Type STAR Radiant Heater For Fixed Overhead Installations

Type STAR Radiant Heater For Fixed Overhead Installations (Supersedes PG434-4) PG434-5 JULY, 2012 Type STAR Radiant Heater For Fixed Overhead Installations 2.0 kw 4.5 kw B 11-9/16" 11-9/16" 15-1/2" 15-1/2" 55-3/4" 33-1/4" Figure 1 6.0 kw 13.5 kw 11-1/2" 11-1/2"

More information

Electrical safety and you

Electrical safety and you Electrical safety and you A brief guide Introduction Electricity can kill or severely injure people and cause damage to property. Every year many accidents at work involving electric shock or burns are

More information

Fire Protection Notice No. 9 ELECTRICAL SAFETY

Fire Protection Notice No. 9 ELECTRICAL SAFETY Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily

More information

Extension Cord Safety Policy

Extension Cord Safety Policy NATIONAL HIGH MAGNETIC FIELD LABORATORY Operated by Florida State University, University of Florida, Los Alamos National Laboratory Florida State University, 1800 East Paul Dirac Drive, Tallahassee, Florida

More information

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers 9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product

More information

TROUBLESHOOTING. for the 5 BUTTON COMFORT CONTROL CENTER SYSTEM AIR CONDITIONER BULLETIN A29/2A JANUARY 2002

TROUBLESHOOTING. for the 5 BUTTON COMFORT CONTROL CENTER SYSTEM AIR CONDITIONER BULLETIN A29/2A JANUARY 2002 INTRODUCTION The Comfort Control Center control system can be used to operate the following Duo-Therm Units: Roof Top Air Conditioners Roof Top Heat Pumps Basement Air Conditioners Basement Heat Pumps

More information

Electrical Safety In and Around the Home

Electrical Safety In and Around the Home In and Around the Home Electrical Safety In and Around the Home Developed by: American Burn Association Burn Prevention Committee Funded by: United States Fire Administration/ Federal Emergency Management

More information

TROUBLESHOOTING GUIDE

TROUBLESHOOTING GUIDE TROUBLESHOOTING GUIDE LESTRONIC II BATTERY CHARGER FOR MOTIVE POWER BATTERIES PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment, it is important to read

More information

Household electrical & gas Safety tips...

Household electrical & gas Safety tips... Household electrical & gas Safety tips... Household Electrical Safety Tips Electrical There are about 12,500 electrical fires in homes across the UK each year. Although many incidents are caused by faulty

More information

Beware; the Multiwire Branch Circuit

Beware; the Multiwire Branch Circuit eware; the Multiwire ranch ircuit The electrical industry has a formal ode, and it has unwritten rules-of-thumb, just as any other discipline involving construction. The ode changes every three years,

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

TECHNICAL & PROPERTY SERVICES HEALTH & SAFETY GUIDANCE NOTE: HSGN 1. PAT Testing

TECHNICAL & PROPERTY SERVICES HEALTH & SAFETY GUIDANCE NOTE: HSGN 1. PAT Testing TECHNICAL & PROPERTY SERVICES HEALTH & SAFETY GUIDANCE NOTE: HSGN 1 PAT Testing Index 1. Objective 2. Background 3. Definitions 4. Roles and Responsibilities 5. Portable Electrical Equipment Safety Information

More information

Remote Control Cut Off Switch NEFA20 Plus F1

Remote Control Cut Off Switch NEFA20 Plus F1 Remote Control Cut Off Switch NEFA20 Plus F1 Installation Guide Please read this entire guide before beginning the installation! Supplied Parts Antenna NEFA20 F1 Plus Cutoff Switch Protective Covers DIN

More information

Model 1756 Test Lead Kit

Model 1756 Test Lead Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you

More information

Odyssey of the Mind Technology Fair. Simple Electronics

Odyssey of the Mind Technology Fair. Simple Electronics Simple Electronics 1. Terms volts, amps, ohms, watts, positive, negative, AC, DC 2. Matching voltages a. Series vs. parallel 3. Battery capacity 4. Simple electronic circuit light bulb 5. Chose the right

More information

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module

More information

Boating and Marina Safety: Avoid Electric Shock Drowning

Boating and Marina Safety: Avoid Electric Shock Drowning Boating and Marina Safety: Avoid Electric Shock Drowning Unknowingly, many swimmers and boat and marina operators place themselves in the face of danger by swimming near electric-powered boats and docks.

More information

Progressive Industries, Inc. Electrical Management System

Progressive Industries, Inc. Electrical Management System Progressive Industries, Inc. Electrical Management System Operating Instructions for: Model EMS-PT30C Rated at 120V/30A Manufactured by: Progressive Industries, Inc. 414B Airport Boulevard Morrisville,

More information

ALUMINUM ELECTRICAL WIRING

ALUMINUM ELECTRICAL WIRING ALUMINUM ELECTRICAL WIRING prepared by Fire Prevention and Investigation Division Denver Fire Department Department of Safety and Electrical Inspections Section Denver Building Inspection Division Community

More information

6.0 Electrical Installations

6.0 Electrical Installations 6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is

More information

Essential Electrical Concepts

Essential Electrical Concepts Essential Electrical Concepts Introduction Modern vehicles incorporate many electrical and electronic components and systems: Audio Lights Navigation Engine control Transmission control Braking and traction

More information

BATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716

BATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716 BATHROOM HEATER User's Manual Page 2...A515 Page 9...A716 BATHROOM HEATER User's Manual A515 SAVE THESE INSTRUCTIONS AND READ ALL INSTRUCTIONS BEFORE USING THE HEATER. Dear customers, Thank you for selecting

More information

AFCIs Come of Age. by Douglas Hansen

AFCIs Come of Age. by Douglas Hansen AFCIs Come of Age by Douglas Hansen Arc Fault Circuit Interrupters were the new kid on the block when they first appeared in the 1999 National Electrical Code (NEC). Since then we have seen the technology

More information

Single Phase Soft Starter

Single Phase Soft Starter Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................

More information

HOME ELECTRICAL Safety Checklist

HOME ELECTRICAL Safety Checklist Keeping You and Your Family Safe, Room-by-Room U.S. Consumer Product Commission 4330 East West Highway Bethesda, MD 20814 Pub 513 July 2008 This document was prepared by CPSC staff, has not been reviewed

More information

FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7

FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7 FAQs Conserve package Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7 FAQs Gateway Can I have someone install my system for me? If you are concerned

More information

Table of Contents. Keep an Eye on Electric Safety. Safety in an Emergency. Important Phone Numbers. Downed Power Lines

Table of Contents. Keep an Eye on Electric Safety. Safety in an Emergency. Important Phone Numbers. Downed Power Lines Table of Contents Keep an Eye on Electric Safety................ 1 Safety in an Emergency...................... 1 Downed Power Lines...................... 1 Keep an Eye on Electric Safety Electricity is

More information

Instructions & Safety Information Models A220-20D and A220-20L Version 2

Instructions & Safety Information Models A220-20D and A220-20L Version 2 Quick 220 Voltage Converting Power Supply Instructions & Safety Information Models A220-20D and A220-20L Version 2 Quick 220 Systems LLC PO Box 47489 Phoenix, Arizona 85068-7489 800-347-0394 602-938-6057

More information

EE 417 Notes Fall

EE 417 Notes Fall EE 417 Notes Fall 2010 1 Audio Electrical Wiring Basic branch circuits in homes and businesses (U.S.) Service Panel Circuit Breaker Black Wire ("hot") (from power company and power meter) White Wire (neutral)

More information