EnergyPro Building Energy Analysis. Hotel Building

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "EnergyPro Building Energy Analysis. Hotel Building"

Transcription

1 EnergyPro Building Energy Analysis Hotel Building

2 EnergyPro Building Energy Analysis for a hotel building Project Scope The purpose of the EnergyPro model was to evaluate the energy usage of a building installed with a VRFZ solution compared to that of a packaged terminal heat pump (PTHP) system, a water-source heat pump (WSHP) system, and a hot-water/chilled-water four-pipe fan coil system. The selected systems were then compared with the solutions across the country:, GA,, FL,, MA, New York City, NY,, IL,, TX, Los Angeles, CA, and, WA. The goal of the energy model was to understand how HVAC systems compared with standard HVAC systems in various climate zones. Building Description The simulated building chosen was a 100,000 square foot, four-story, rectangularshaped hotel. The hotel modeled was a 4 story select service type containing 123 guestrooms, entrance lobby, meeting rooms, exercise area, and back of house services. The main section of the building runs east and west with two wings on the north end; there is a great deal of exterior exposure on all sides. The building was modeled in each of the cities listed in the previous paragraph. Building specifications such as floor plans, R-Values, U-Values, etc., followed what was typical for construction values in each of the areas specified. The building was modeled in EnergyPro, and four simulations were created: a heatrecovery system, a packaged terminal heat pump system, a boiler and chiller serving four-pipe fan coil units, and a water-source heat pump system. The non-hvac energy usage such as lighting, plug loads, etc., were the same in all models (see the Engineering Assumptions Table for specifics). All utility rates used in the savings analysis were obtained from The rates are provided in the Utility Rate Summary Table. Mitsubishi Electric Design Description For the simulated hotel, a single ducted unit was used in each guest room. For larger zones in the simulated hotel s first floor such as the lobby and meeting rooms, a combination of ducted units and ceiling cassettes were used. Ten R2-Series heat recovery outdoor units served the building, with two outdoor units serving each of the three guest room floors. The outside air load was applied directly to each of the indoor units at the zone level. PTHP Design Description The hotel was modeled with a PTHP system with auxiliary electric heat in each room. The PTHP s were modeled with an EER (Energy Efficiency Ratio) of 10.7 and an HSPF (Heat Seasonal Performance Factor) of 7.5. The common areas were conditioned using PTHP s sized and spaced throughout the zones as needed to maintain room temperature. The outside air was conditioned by the PTHPs. Water-source Heat Pump (WSHP) Design Description To provide conditioning to the simulated hotel, water-source heat pumps with a 15.4 EER and a 4.7 COP (Coefficient of Performance) were modeled. The water-source heat pumps were served by a two-speed cooling tower and a pump to circulate the water. A supplemental condensing boiler was attached to the condenser water loop to provide heat when the cooling tower could not maintain the water-loop temperature. The outside air was conditioned by the water-source heat pumps. A single heat pump was provided to serve each of the guest rooms. The common areas were conditioned using WSHP s sized and spaced throughout the zones as needed to maintain room temperature. Four-pipe Design Description To provide conditioning to the simulated hotel, a chiller and boiler serving four-pipe fan coil units were modeled. A water-cooled chiller with an efficiency of 0.72 kw/ton was used. The chiller was served by a two-speed cooling tower, and each was served by a set of pumps to circulate condenser water and chilled water. A condensing boiler with an efficiency of 91.5% provided hot water to the fan coil units. The outside air was conditioned by the fan coil units. A single fan coil unit was provided to serve each of the guest rooms. The common areas were conditioned using fan coil units sized and spaced throughout the zones as needed to maintain room temperature.

3 Total Energy Cost Savings vs. PTHP vs. WSHP vs. Four-pipe Location 0% 3.5% 7% 10.5% 14% 17.5% 21% 24.5% 28% 31.5% 35% 38.5% Total Energy Cost Savings (%) (Reference Table 3 for more details) LEED NC 2.2 and VRFZ Systems are helpful in obtaining points for LEED (Leadership in Energy and Environmental Design) Energy and Atmosphere credit 1. The U.S. Green Building Council (USGBC) developed the LEED Green Building Rating System as a voluntary, consensus-based national standard for developing high-performance, sustainable buildings. Building energy savings can be demonstrated by performing a building energy model using the EnergyPro software available from EnergySoft, LLC. and comparing the building design with a baseline building as defined by ASHRAE std EnergyPro is approved by the USGBC for EAc1 calculations. As shown below, the percentage of total energy savings relates directly to LEED credits. LEED Points based on Total Energy Savings (EA Credit 1) New Buildings Existing Building Renovations Points 10.5% 3.5% 1 14% 7% % 10.5% 3 21% 14% % 17.5% 5 28% 21% % 24.5% 7 35% 28% % 31.5% 9 42% 35% 10 The graphs on the following page show the percentage savings of VRFZ over the ASHRAE std baseline which is the PTHP system as well as other system types. Quality and reliability are significantly more important to hotel design professionals than other mechanical product-related factors. High importance is also placed on ease of use in hotel rooms by guests, operating efficiency and operating sound levels. - according to a recent study conducted by Clear Seas Research.

4 The most common challenges in providing a comfortable hotel environment include cost, sound control and humidity. The most frequent complaint regarding comfort focuses on the temperature being too hot or too cold. - according to a recent study conducted by Clear Seas Research. $200,000 Total Energy Cost Comparison for and Packaged Terminal Heat Pump $175,000 Total Energy Cost ($) $150,000 $125,000 $100,000 PTHP $75,000 $50,000 $25,000 $0 Location 32% 13% 40% 36% 38% 22% 20% 37% as compared to PTHP A PTHP system is the baseline defined by ASHRAE std for this building size and type. Energy usage was calculated for the buildings using both systems. On average, the system saw a total energy cost savings of 30% when compared with the PTHP systems, and a 41% average savings when comparing HVAC energy cost. The savings varied greatly based upon the modeled location and the applied local utility rates. Based on the average energy cost savings from the models, future projects would meet the LEED EA credit 1 prerequisite and qualify for six LEED points. Specific results for each area have been detailed in the Energy Usage Summary (Tables 3, 4).

5 Total Energy Cost ($) $200,000 $175,000 $150,000 $125,000 $100,000 $75,000 $50,000 $25,000 $0 Location Total Cost Comparison for and Water Source Heat Pump 21% 22% 11% 15% 8% 20% 28% 14% WSHP as compared to WSHP WSHP systems have recently become a popular choice for hotels needing to replace outdated HVAC systems. Energy usage was calculated for the buildings using both systems. The total energy cost savings realized with the system was 17% on average compared to a WSHP system. When comparing the energy cost used by the HVAC systems alone, was 25% less on average. The energy use is detailed in the Energy Usage Summary (Tables 3, 4). Total Energy Cost ($) $200,000 $175,000 $150,000 $125,000 $100,000 $75,000 $50,000 $25,000 $0 Location Total Energy Cost Comparison for and Four-pipe 25% 22% 18% 16% 17% 20% 25% 22% Four-pipe as compared to Four-pipe A four-pipe fan coil unit system is a standard HVAC package used in many building types. Energy usage was calculated for the buildings using both systems. On average, the total energy cost savings realized with the system was 21% when compared to a four-pipe fan coil unit system and a 30% average savings when comparing HVAC energy cost. Savings were fairly constant across all locations. Savings for each location are detailed in the Energy Usage Summary (Tables 3, 4).

6 Engineering Assumptions Weather Profile based on locations shown in the ASHRAE Design Temperature table. Item Design Assumption Building Area As defined by the provided plans Glass selection Double Thermal Break Clear U-Value: SHGC: Walls Construction: Wood frame Insulation: R-19 Total Assembly U-Value: Roof Construction: R-19 Roof over Metal Deck Insulation: R-19 Total Assembly U-Value: Reflectivity: 0.7 Energy savings is the most important cost-related factor for the hotel community when it comes to a comfortable internal environment, followed by prod- uct life and maintenance costs. - according to a recent study by Clear Seas Research. VRFZ system PTHP HVAC system Water Source Heat Pump HVAC system 4-Pipe Fan Coil Unit HVAC system A R2-Series heat recovery system with ducted and wall-mounted units. Packaged Terminal Heat Pump (PTHP) with auxiliary electric strip heat EER, 7.5 HSPF Water source heat pumps served by a 2-speed cooling tower and a 91.5 % efficient supplemental boiler, The heat pumps have an efficiency of 15.4 EER and a COP of 4.7. All pumps were sized per ASHRAE recommendations. Fan Coil Units served by a 91.5% efficient boiler, a water cooled screw chiller with an efficiency of 0.72kw/ton and a 2-speed cooling tower. All pumps were sized per ASHRAE recommendations. Miscellaneous Loads Hotel: 1.5 Watts/ft 2 Schedules Utility Rates Standard ASHRAE 90.1 Profile and Operation Schedules See Utility Rate Summary Table Table 1. Utility Rate Summary Electric ($/KWH) Gas ($/Therm) Table 2. ASHRAE Design Temperature Summer DB 0.40% Summer MWB 0.40% Winter DB 99.6%

7 Table 3. Total Energy Usage Summary Total KWH 620, , , , , , , ,896 Total Therm Total MMBTU 2,117 2,584 2,137 2,119 2,335 2,263 1,827 1,874 Total Cost $69,254 $88,852 $110,761 $122,578 $74,800 $92,362 $80,163 $42,539 Total KWH 913, ,571 1,039, ,563 1,099, , , ,813 PTHP Total Therm Total MMBTU 3,118 2,959 3,548 3,294 3,755 2,907 2,279 2,984 Total Cost $101,994 $101,735 $183,909 $190,501 $120,302 $118,697 $49,974 $67,720 Total KWH 783, , , , , , , ,797 WSHP Total Therm , Total MMBTU 2,692 3,329 2,458 2,524 2,607 2,849 2,532 2,179 Total Cost $87,760 $114,450 $124,375 $143,369 $81,002 $115,910 $111,094 $49,239 Total KWH 726, , , , , , , ,528 Four-pipe MMBTU Savings Cost Savings Total Therm 8, ,453 14,243 17,546 5,773 1,230 14,174 Total MMBTU 3,328 3,334 3,831 3,624 3,949 3,272 2,543 3,130 Total Cost $92,627 $114,627 $134,398 $145,702 $89,806 $116,134 $107,590 $54,587 CM vs. PTHP 32% 13% 40% 36% 38% 22% 20% 37% CM vs. WSHP 21% 22% 13% 16% 10% 21% 28% 14% CM vs. Four-pipe 36% 22% 44% 42% 41% 31% 28% 40% CM vs. PTHP 32% 13% 40% 36% 38% 22% 20% 37% CM vs. WSHP 21% 22% 11% 15% 8% 20% 28% 14% CM vs. Four-pipe 25% 22% 18% 16% 17% 20% 25% 22% Table 4. HVAC Only Energy Usage Summary Total KWH 375, , , , , , , ,146 Total Therm Total MMBTU 1,282 1,749 1,301 1,284 1,499 1, ,039 Total Cost $41,916 $60,119 $67,441 $74,240 $48,025 $58,244 $43,500 $23,571 Total KWH 668, , , , , , , ,063 PTHP Total Therm Total MMBTU 2,282 2,123 2,712 2,458 2,919 2,072 1,443 2,148 Total Cost $74,656 $73,002 $140,588 $142,163 $93,527 $84,579 $63,311 $48,752 Total KWH 538, , , , , , , ,047 WSHP Total Therm , Total MMBTU 1,857 2,493 1,623 1,689 1,772 2,013 1,697 1,343 Total Cost $60,422 $85,716 $81,055 $95,031 $54,227 $81,793 $74,436 $30,271 Total KWH 481, , , , , , , ,778 Four-pipe MMBTU Savings Cost Savings Total Therm 8, ,453 14,243 17,546 5,773 1,230 14,174 Total MMBTU 2,493 2,498 2,995 2,788 3,113 2,436 1,708 2,295 Total Cost $65,289 $85,534 $91,078 $97,364 $63,031 $82,016 $70,927 $35,619 CM vs. PTHP 44% 18% 52% 48% 49% 31% 31% 52% CM vs. WSHP 31% 30% 20% 24% 15% 29% 42% 23% CM vs. Four-pipe 49% 30% 57% 54% 52% 41% 42% 55% CM vs. PTHP 44% 18% 52% 48% 49% 31% 31% 52% CM vs. WSHP 31% 30% 17% 22% 11% 29% 42% 22% CM vs. Four-pipe 36% 30% 26% 24% 24% 29% 39% 34% * is abbreviated as CM in the above tables.

8 Advantages of over Comparable Systems The EnergyPro model demonstrated that systems offer reduced energy costs because of part-load efficiency and the ability to simultaneously cool and heat. R2-Series heat recovery systems can simultaneously cool and heat different zones, which allows energy to be recovered from one zone and used in another, resulting in a huge increase in efficiency and energy savings over all of the compared systems. There are some major areas in which the system offers an advantage over other systems: 1. Initial Cost: systems consist of an outdoor unit, an indoor unit in each zone, a BC controller (R2-Series only), refrigerant piping, and a very simple controls system. A four-pipe fan coil unit system includes a boiler, chiller, fan coil units, pumps, hot water piping, chilled water piping, a controls system, etc. A water-source heat pump system includes a cooling tower, supplemental boiler, condenser water piping, condenser water pumps, heat pumps, a controls system, etc. The reduced equipment required and ease of installation makes the a superior first cost solution. 2. Comfort: One of the biggest advantages that CITY MULTI VRFZ solutions have over other systems is the increased comfort level for the occupants. VRFZ technology allows indoor units to operate at the precise level necessary to maintain room temperature which, when combined with the powerful controls system, allows the occupants to experience consistent comfort throughout the day. 3. Quiet Operation: indoor and outdoor units operate at low sound levels; for example, a 20-ton outdoor unit operating at high speed has a sound level of 63 db(a). Some indoor models have an operating sound level in the low 20 db(a)s range, depending on fan speed and duct design. For contrast, the sound level for normal conversation is approximately 60 db(a). 4. Installation Space: systems do not require a mechanical room. Outdoor units can be installed outside either on grade or the roof and piped directly to indoor units, eliminating the need for pumps. Depending on the type of indoor unit, they can be installed in plenum spaces, on walls, or in the ceiling. Refrigerant piping is routed to the BC controller, also located in the plenum space, and then to the outdoor unit. 5. Installation Time: Because there are fewer components in a system, the time it takes for installation is much shorter than for other systems. An indoor unit can be mounted and piped from the BC controller in hours. 6. Flexibility: The zoning capabilities of systems allow for one indoor unit to be taken offline without affecting other indoor units. An outdoor unit can also be shut down and affect only a few zones. However with other systems if an air-handling unit should fail, or a component of the central mechanical system should fail (chiller, cooling tower or pumps) a large portion, if not all, building conditioning would be lost. 7. Versatility: systems offer a choice of inside air handlers: ducted, wall-mounted, ceiling-mounted, and floor-mounted. Many other systems only offer limited indoor unit selections. 8. Efficiency: R2-Series systems have the ability to recover energy when simultaneously cooling and heating, thereby reducing energy and increasing operating efficiency. Variable refrigerant flow zoning technology also allows to automatically adjust to changing loads in each zone, maintaining the required temperature levels and operating at a lower cost. 9. Maintenance: systems require significantly less maintenance; typically only requiring filter changes. systems have a life expectancy of 15 to 20 years. Water-source heat pump systems require regular maintenance to maintain the compressor and keep the system functioning properly. Form No. EPBROHTLBLD-7-09 V2 For more information visit Please recycle. Mitsubishi Electric Advanced Products Division 3400 Lawrenceville Suwanee Road Suwanee, GA Phone: Fax: Mitsubishi Electric & Electronics USA, Inc. is a registered trademark of Mitsubishi Electric. The three-diamond logo is a registered logo of Mitsubishi Electric Corporation.

EnergyPro Building Energy Analysis. Assisted Living Building

EnergyPro Building Energy Analysis. Assisted Living Building EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the

More information

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System)

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System) Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V Water II Heat VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BL-001-US 011M05 Executive Summary Contents

More information

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V III Heat Recovery VRF System)

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V III Heat Recovery VRF System) Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V III Heat Recovery VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BK-011-US 011L18 Executive Summary

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can

More information

The ABC s of VRF: A Green HVAC Technology An Ideal Green School Solution. Presented by: Fujitsu General America, Inc.

The ABC s of VRF: A Green HVAC Technology An Ideal Green School Solution. Presented by: Fujitsu General America, Inc. The ABC s of VRF: A Green HVAC Technology An Ideal Green School Solution Presented by: Fujitsu General America, Inc. What to look for in a Green HVAC solution? What if your HVAC system could provide Individual

More information

Heating & Cooling Efficiency

Heating & Cooling Efficiency Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.

More information

Introduction To VRF: System Overview, Applications, & Savings Opportunities

Introduction To VRF: System Overview, Applications, & Savings Opportunities Introduction To VRF: System Overview, Applications, & Savings Opportunities System Overview What is VRF? Zoning System Two-Pipe / Three Pipe System Packaged DDC Control Operates as a Heat Pump Simultaneous

More information

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs

More information

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient

More information

Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code

Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code Julia Gauthier, LEED AP BD+C Jeanne Huntsman, AIA, LEED Green Associate The Weidt Group Raising the Bar Special statements

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Air-Conditioning Buying Guide

Air-Conditioning Buying Guide Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence

More information

VRF Zoning: An Ideal HVAC Solution for Multifamily Applications

VRF Zoning: An Ideal HVAC Solution for Multifamily Applications VRF Zoning: An Ideal HVAC Solution for Multifamily Applications White Paper June 2014 1 Variable Refrigerant Flow (VRF) zoning systems are the fastest growing segment of the U.S. HVAC market. This paper

More information

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing

More information

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building. MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating

More information

TRACE 700 Building Energy Modeling Guide for LG Multi V

TRACE 700 Building Energy Modeling Guide for LG Multi V TRACE 700 Building Energy Modeling Guide for LG Multi V 2012 LG Electronics USA Inc. LG - Internal Use Only VRF-ES-EL-001-US 012H21 This Guide 1 Table of Contents This Guide...2 1. Disclaimer... 2 Import

More information

BPC Green Builders. Green building for new and existing homes. Health Comfort Energy

BPC Green Builders. Green building for new and existing homes. Health Comfort Energy BPC Green Builders Green building for new and existing homes Health Comfort Energy Mechanical Systems Installed HVAC Systems Primary energy source large, roof mounted, solar thermal array (AET flat plate)

More information

Heat Pump Applications

Heat Pump Applications Heat Pump Applications For Rebel Commercial Rooftop Systems Rebel Advantages Rebel Is Much Better Than Competitive Heat Pumps Optional variable volume cooling Excellent energy savings Why install a unit

More information

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable

More information

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is

More information

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li * Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting

More information

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747 POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609

More information

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling HOT & COLD Basic Thermodynamics and Large Building Heating and Cooling What is Thermodynamics? It s the study of energy conversion using heat and other forms of energy based on temperature, volume, and

More information

HEATING, VENTILATION & AIR CONDITIONING

HEATING, VENTILATION & AIR CONDITIONING HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating

More information

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment

More information

Energy Savings in High-Rise Buildings Using High-Reflective Coatings

Energy Savings in High-Rise Buildings Using High-Reflective Coatings Energy Savings in High-Rise Buildings Using High-Reflective Coatings Executive Summary: Nevertheless, the simulation analyses showed that when designing a building for low energy consumption, even in cold

More information

Mechanical Systems Proposal revised

Mechanical Systems Proposal revised Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option

More information

Mechanical Insulation. Hospitals and Schools

Mechanical Insulation. Hospitals and Schools Study on Mechanical Insulation in Hospitals and Schools March 1, 2011 Study Mechanical Insulation in Hospitals and Schools G. Christopher P. Crall, P.E. Ronald L. King Executive Summary Mechanical insulation

More information

Ductless Heat Pumps. Gary Nordeen January 2009. www.nwbuildings.org/dhp.aspx info@nwbuildings.org

Ductless Heat Pumps. Gary Nordeen January 2009. www.nwbuildings.org/dhp.aspx info@nwbuildings.org Ductless Heat Pumps Gary Nordeen January 2009 www.nwbuildings.org/dhp.aspx info@nwbuildings.org Outline Heat Pump Basics Ductless Heat Pumps Efficiency Advantages Commercial installations Planning (applications,

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump

Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump s.doty 10-2014 White Paper #30 Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump System Switches Fuels Automatically for Economy. What is an Air-Source Heat Pump? A heat pump is a modified air conditioning

More information

Whole House Dehumidification for Occupant Comfort and Energy Savings

Whole House Dehumidification for Occupant Comfort and Energy Savings Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J. Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation

More information

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs

More information

Energy Efficiency: Integrated Design and HVAC Systems HEALTHCARE - TOP 5 GREEN BUILDING STRATEGIES

Energy Efficiency: Integrated Design and HVAC Systems HEALTHCARE - TOP 5 GREEN BUILDING STRATEGIES EPA Publication 909-F-07-001 What? Energy use in healthcare facilities is higher than nearly all other building types. With rising energy costs and climate change concerns energy efficiency is financially

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

3/29/2012 INTRODUCTION HVAC BASICS

3/29/2012 INTRODUCTION HVAC BASICS INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Variable Refrigerant Flow Systems

Variable Refrigerant Flow Systems The following article was published in ASHRAE Journal, April 2007. Copyright 2007 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Section 2: Estimating Energy Savings and Incentives

Section 2: Estimating Energy Savings and Incentives Section 2: Estimating Energy Savings and Incentives 2.1 Estimating Energy Savings and Incentives... 2 2.2 Customized Measures - Estimation Software... 2 2.2.1 AC&R I - High Efficiency Chiller... 3 2.2.2

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Selecting a Home Cooling System

Selecting a Home Cooling System Selecting a Home Cooling System January 2000 Introduction Selection of a cooling system for a new or existing home requires an understanding of how various systems operate, their initial cost, and their

More information

Sustainable Strategies for Rehabilitation Projects: 9th Street Office Building Adaptive Reuse Case Study

Sustainable Strategies for Rehabilitation Projects: 9th Street Office Building Adaptive Reuse Case Study Sustainable Strategies for Rehabilitation Projects: 9th Street Office Building Adaptive Reuse Case Study Robert C. Burns, AIA, LEED AP Principal Director of Historic Architecture 804. 648. 5040, ext. 1107

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

Life s Good! What is LG?

Life s Good! What is LG? PRODUCT CATALOG Life s Good! From installation to maintenance and repair, LG runs more than 60 global air conditioning academies, each provides training for air conditioning professionals. What is LG?

More information

Ground-Source Variable Refrigerant Flow Heat Pumps:

Ground-Source Variable Refrigerant Flow Heat Pumps: Energy Efficiency Factsheet: Ground-Source Variable Refrigerant Flow Heat Pumps Page 1 Ground-Source Variable Refrigerant Flow Heat Pumps: A Solution for Affordable Housing, Assisted Living, Hotels and

More information

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

2006 Delta T Corporation dba Big Ass Fan Company

2006 Delta T Corporation dba Big Ass Fan Company Saving Energy Savings with HVLS Fans Josh Eddy LEED-AP National Sales Manager Big Ass Fans Outline Who is Big Ass Fans HVLS fan types How HVLS fans save energy HVLS fan applications How utilities are helping

More information

LG Air Conditioning Solutions COMFORT MADE EASY. COMFORT MADE BEAUTIFUL.

LG Air Conditioning Solutions COMFORT MADE EASY. COMFORT MADE BEAUTIFUL. Residential Brochure LG Air Conditioning Solutions COMFORT MADE EASY. COMFORT MADE BEAUTIFUL. LG DUCT-FREE Split SYSTEMS BRING COMFORTING INNOVATION LG Duct-Free Split systems allow you to cool or heat

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

HYDRONIC RADIANT CEILINGS and CHILLED BEAMS. Low Mass Heating and Cooling

HYDRONIC RADIANT CEILINGS and CHILLED BEAMS. Low Mass Heating and Cooling HYDRONIC RADIANT CEILINGS and CHILLED BEAMS Low Mass Heating and Cooling Learning Objectives How does radiant heating and cooling work how does low mass differ from high? What are hydronic radiant panels?

More information

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency Randy Mead, C.E.M, CMVP Introduction Chilled water plant efficiency refers to the total electrical energy it

More information

VRF Zoning: A Flexible, Energy-Efficient HVAC System for Schools and Universities

VRF Zoning: A Flexible, Energy-Efficient HVAC System for Schools and Universities VRF Zoning: A Flexible, Energy-Efficient HVAC System for Schools and Universities White Paper September 2012 1 A proven HVAC technology worldwide, Variable Refrigerant Flow (VRF) zoning systems are poised

More information

Variable Refrigerant Flow Systems vs. Geothermal Water Source Heat Pump Systems

Variable Refrigerant Flow Systems vs. Geothermal Water Source Heat Pump Systems Variable Refrigerant Flow Systems vs. Geothermal Water Source Heat Pump Systems Presented by: Matt Green Agenda Section I: Case Study Northern Illinois Food Bank NIFB challenge/goal System choices considered

More information

Daikin VRV, controls, and lighting retrofit gives St. Louis area high school new life

Daikin VRV, controls, and lighting retrofit gives St. Louis area high school new life Daikin VRV, controls, and lighting retrofit gives St. Louis area high school new life The Challenges The original 1957 wing had no existing cooling system and structural limitations that left precious

More information

Chapter 4.9: HVAC System

Chapter 4.9: HVAC System Chapter 4.9: HVAC System Short type questions 1. Define tons of refrigeration?. One ton of refrigeration is the amount of cooling obtained by one ton of ice melting in one day. It is equivalent to kcal/h,

More information

Below are detailed instructions for using the EMS load calculator.

Below are detailed instructions for using the EMS load calculator. Introduction The EMS load calculator is designed to make load calculating as painless as possible. For sizing the equipment, only the first three tabs (Steps 1, 2 & 3) need to be completed. This process

More information

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers HEAT RECOVERY FROM CHILLED WATER SYSTEMS Applications for Heat Reclaim Chillers April 2008 TABLE OF CONTENTS INTRODUCTION... 3 WASTE HEAT SOURCES... 3,4 Capturing Sufficient Heat for Useful Purposes...

More information

Building Controls Training Courses from the BCIA

Building Controls Training Courses from the BCIA Building Controls Training Courses from the BCIA BCO Introduction to building controls and HVAC This introductory course is designed for those who either do not require the full technical detail of the

More information

Wet Bulb Temperature and Its Impact on Building Performance

Wet Bulb Temperature and Its Impact on Building Performance Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,

More information

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact

More information

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:

More information

SECTION 140.4 PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS

SECTION 140.4 PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS 2013 Building Energy Efficiency Standards Page 162 SECTION 140.4 PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS A building complies with this section by being designed with and having constructed

More information

EarthCents (DSM) Program Summary

EarthCents (DSM) Program Summary EarthCents (DSM) Program Summary Renewable Energy EarthCents Programs Solar Water Heating This program is available to residential customers for the installation of a qualifying solar thermal water heater.

More information

Department of Mechanical and Materials Engineering Florida International University, Miami, FL. EML 4905 Senior Design Project

Department of Mechanical and Materials Engineering Florida International University, Miami, FL. EML 4905 Senior Design Project Department of Mechanical and Materials Engineering Florida International University, Miami, FL EML 4905 Senior Design Project HVAC Design for Green Building Miami Green Final Report Submitted By: James

More information

MEETING AGENDA. Project Administrator:

MEETING AGENDA. Project Administrator: MEETING AGENDA Project Administrator: To: Ann Green M. Baker, SLCS C. Bullinger, SLCS R. Clark, SLCS Board C. Cox, SLCS S. Dotinga, Granger J. Graham, SLCS J. Gusick, SLCS, Board C. Hanshaw, SLCS Board

More information

Selection Tips For Air-Conditioning Cooling Systems

Selection Tips For Air-Conditioning Cooling Systems PDHonline Course M117 (2 PDH) Selection Tips For -Conditioning Cooling Systems Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation

More information

Ductless Heat Pumps for Passive Houses

Ductless Heat Pumps for Passive Houses 7 th th Annual North American Passive House Conference September 27-30, 2012 Denver CO Ductless Heat Pumps for Passive Houses Mark T. Kuntz, PE, LEED-AP Mitsubishi Heating and Cooling mkuntz@hvac.mea.com

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

POWER USAGE EFFECTIVENESS. Developing Best Practices Manual for Indian Data Centers. Presentation by HVAC Core Group

POWER USAGE EFFECTIVENESS. Developing Best Practices Manual for Indian Data Centers. Presentation by HVAC Core Group POWER USAGE EFFECTIVENESS Developing Best Practices Manual for Indian Data Centers PUE - Power usage effectiveness is Total incoming power( IT equipment + electrical And mechanical support system ) / Presentation

More information

Daikin VRV, controls, and lighting retrofit gives St. Louis area high school new life

Daikin VRV, controls, and lighting retrofit gives St. Louis area high school new life Daikin VRV, controls, and lighting retrofit gives St. Louis area high school new life The Challenges The original 957 wing had no existing cooling system and structural limitations that left precious little

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems 1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system

More information

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems

More information

FLORIDA SOLAR ENERGY CENTER

FLORIDA SOLAR ENERGY CENTER FLORIDA SOLAR ENERGY CENTER Creating Energy Independence Since 1975 Impact of Energy-Efficiency Parameters on Home Humidity Rob Vieira Florida Solar Energy Center A Research Institute of the University

More information

COMMERCIAL HVAC AIR-HANDLING EQUIPMENT. Central Station Air Handlers

COMMERCIAL HVAC AIR-HANDLING EQUIPMENT. Central Station Air Handlers COMMERCIAL HVAC AIR-HANDLING EQUIPMENT Central Station Air Handlers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application

More information

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation

More information

BUILDING PERFORMANCE METRICS

BUILDING PERFORMANCE METRICS BUILDING PERFORMANCE METRICS Hugh Crowther P. Eng. Executive Vice President, Product Management and Technology There is a steady and determined march towards designing better and better performing buildings.

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

HVAC SYSTEMS ACOUSTICAL, COST & ENERGY STUDY

HVAC SYSTEMS ACOUSTICAL, COST & ENERGY STUDY HVAC SYSTEMS ACOUSTICAL, COST & ENERGY STUDY Prepared for the Los Angeles Unified School District Facilities Services Division June 6, 2005 By Maroko & Shwe, Inc., Professional Engineers With Schaffer

More information

AMERICA S #1 SELLING BRAND OF DUCTLESS

AMERICA S #1 SELLING BRAND OF DUCTLESS Now You Can MAKE COMFORT PERSONAL AMERICA S #1 SELLING BRAND OF DUCTLESS mitsubishicomfort.com CONBRO 02.2016 REVISED 2016 MITSUBISHI ELECTRIC US, INC. THE FUTURE OF HOME COMFORT Mitsubishi Electric offers

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

The Only GUY To Call. Why are my utility bills so high? What can I do to lower my energy expenses?

The Only GUY To Call. Why are my utility bills so high? What can I do to lower my energy expenses? The Only GUY To Call May 2014 412.885.2356 Why are my utility bills so high? What can I do to lower my energy expenses? Did you know... that between 2007 and 2012, the average U.S. household spent more

More information