Section Fiber Optic Cable and Equipment
|
|
- Benedict Leonard Allison
- 7 years ago
- Views:
Transcription
1 Section Fiber Optic Cable and Equipment 1 GENERAL The work specified in this Section consists of the design, furnishing, and installing of a fiber optic cable system in accordance with this specification. The work shall include a Fiber Optic (FO) Cable path from West Comm. node to the Comm. nodes at: Civic, Arsenal, 49 th St, and Phil CSH at Phil-Amtrak interlocking along the Regional Rail Elwyn Line and Philadelphia Airport. All communications work shall be in conducted accordance with the requirements of this Section, as well as those requirements as described within these construction specifications. A. The Contractor shall provide a Fiber Optic Cable System (FOCS), including cable, cable attachments, cable supports, cable termination equipment, cable splice equipment, cable system installation, cable testing, and all associated materials and services. The FOCS points of access shall be: 1. West Communications Shelter (West); located in the 30th Street yard (existing). 2. Walnut RIH shelter (Walnut); located south of Walnut Street (existing). 3. CSH Cab Signal House (CSH); located 100 ft north of the Walnut RIH (proposed). 4. University City Communications Shelter (Univ. City); located at University City Station (existing). 5. Civic CIL Shelter (Civic); located 1,500 ft south of Univ. City (proposed). 6. Arsenal RIH Shelter (Arsenal); located 3,200 ft south of Univ. City (existing). 7. Arsenal CIL shelter (Arsenal CIL); located 100 ft south of Arsenal radio interface housing (RIH) (proposed) th Street Communications shelter (49th St); Located at 49th St Station (existing). 9. Phil CSH shelter (Phil-Amt interlocking) located 3300 ft south of Elwin/ Airport turnout in Arsenal interlocking (proposed). See Appendix for Cable Block Diagram for specific routing details (Sheet 1). B. The FO Cable shall be: 1. All Dielectric Self-Supporting (ADSS), Single Mode (SM), Double Jacketed, Water blocking layer, Low Smoke Zero Halogen (LSZH), loose tube Strand, NFPA-130, Gel-Filled buffer tube for Transit tunnel use Strand, 250 ft Span with NESC Heavy Load, Gel-Filled Buffer tube for aerial use Strand, 250 ft Span with NESC Heavy Load, Gel-Filled Buffer tube, for aerial use strand, 250 ft Span with NESC Heavy Load, Gel-Filled Buffer tube, for aerial use. Page 1 of 8 November 2015
2 C. There shall be 50 ft of cable stored in a Contractor provided slack enclosure for each cable entering and leaving a communications node. D. In the communications node, the cable shall be spliced in an accessible wall mount splice enclosure with sufficient capacity to allow for all pass through and pigtail splices. The splice enclosure shall have front doors, be supplied with cable entry plates which allow various entry options including standard cable entry, routing and guide plates along with clips. E. Factory terminated single mode ST UPC pigtails, shall be installed in the fiber optic termination housing and routed into the wall mount fiber optic splice housing where they shall be fusion spliced as directed by SEPTA Project Manager. All splices shall be fusion; mechanical splices will not be accepted. F. All fiber optic cables, pigtails, splice enclosures, termination enclosure shall be identified with permanent and legible tags. The Contractor shall measure the station distances to determine the FO cable length. 2 SUBMITTALS A. Testing/ Quality Verification: The Contractor shall provide all product data evidence of testing/ quality verification, listing, and labeling either by printed mark on the data or by a separate listing card. B. Product Data and Catalog Cuts: The Contractor shall submit product data for all products provided. Indicate clearly the usage of each product. C. Installer Qualifications: Prior to installation, the Contractor shall submit data of installer's experience and qualifications for performing fiber work. D. Test Plan: The Contractor shall provide a complete and detailed test plan for the fiber cabling system including a complete list of test equipment, calibration certification dates, optical fiber components, cable routing plan and attachments and accessories. Include procedures for certification, validation, and testing. This test plan shall be submitted to the SEPTA Project Manager for approval. The Contractor shall not perform the site testing prior to receipt of formal approval. E. The Contractor shall submit Operation and Maintenance (O & M) Manuals which shall include detailed parts lists, lists of recommended spare parts, circuit diagrams, maintenance procedures, and operating instructions. F. Test Reports: The Contractor shall furnish factory reel tests of all optical fiber cables. Page 2 of 8 November 2015
3 3 QUALITY ASSURANCE A. The Contractor shall provide products that are listed and labeled by Underwriters Laboratory (UL), approved by Factory Mutual, or certified as meeting the standards of UL by the Electrical Testing Laboratory unless products meeting the requirements of these testing laboratories are not readily available or unless standards do not exist for the products. Provide products that are listed and labeled or approved as stated above for the location installed in, and listed and labeled or approved as indicated and specified for the applications the items are intended for. B. Manufacturer Qualifications: The Contractor shall provide data attesting to manufacturers experience with manufacturing all products indicated. C. The Contractor shall conform all work to NFPA 70, National Electrical Code. D. Contactor Qualifications: The Contractor shall provide description on the Contractor s previous experience in completing similar fiber optic work Install work under supervision of skilled licensed electricians. 4 REFERENCES A. American National Standards Institute (ANSI)/Telecommunications Industry Association (TIA)/Electronics Industry Alliance (EIA): 1. EIA A FOTP-21 Mating Durability of Fiber Optic Interconnecting Devices. 2. ANSI/TIA/EIA OFSTP-7 Measurement of Optical Power Loss of Installed Single-Mode Fiber Cable Plant. 3. ANSI/TIA/EIA A OFSTP-14A Optical Power Loss Measurement of Installed Multimode Fiber Cable Plant. 4. ANSI/TIA/EIA-568-C.3 Optical Fiber Cabling Components Standard. 5. ANSI/TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings. B. Insulated Cable Engineers Association (ICEA): 1. ANSI/ICEA S Communication Wire and Cable for Wiring of Premises. 2. ANSI/ICEA S Fiber Optic Premises Distribution Cable. 3. ANSI/ICEA S Optical Fiber Indoor/Outdoor Cable. C. National Electrical Manufacturers Association (NEMA): 1. NEMA WC 63.1 Telecommunications Cables Page 3 of 8 November 2015
4 D. Underwriters Laboratories (UL): 1. UL 467 Grounding and Bonding Equipment. 2. UL 1863 UL Standard for Safety for Communications-Circuit Accessories. E. National Fire Protection Association (NFPA): 1. NFPA 70 National Electrical Code (NEC). 2. NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems. 3. NFPA 502 Standard for Road Tunnels, Bridges, and Limited Access Highways. FIBER OPTIC CABLE SYSTEM PRODUCTS A. All fiber optic system products to be provided under this Contract: 1. Shall be new 2. Are subject to SEPTA Project Manager s review and approval 3. Shall be furnished and installed with all specified and additional components necessary under this Contract to constitute a functional and complete FOCS system 4. Shall be size termination panels to accommodate fiber terminations as per SEPTA Project Manager s direction with a minimum of 6 spare terminations and or up to 10% spare capacity 5. Acceptable manufactures are: a. AFL b. Corning Systems 6. Equipment Racks shall be: a. Standard 19 (480 mm) equipment rack, b. floor mounted modular type, c. 16 gauge steel construction treated to resist corrosion, consisting of (2) vertical uprights, (2) floor angles, (2) top angles, and assembly hardware. 7. Equipped with vertical and horizontal cable management channels, top and bottom cable troughs and full-height copper bus bar. 5 FIBER OPTIC PRODUCT SPECIFICATIONS A. Fiber Optic Cable Specifications 1. The Fiber Optic Cable shall be, Arctic Low temperature, Gel-Fill, Double jacket, 144 fiber, SM, (OD in) ADSS Loose Tube Cable, complaint to IEEE The cable shall have a dual layer jacketing system, consisting of outer FR-LSZH chemicalresistant jacket, buffer tube, inner FR-LSZH jacket, water blocking layer and anti-buckling element, optical fibers, rip cord and cut-resistant matrix. 3. All of the FO cables shall meet all of the following Cable Specifications: a. OFNG-LS Listed, CSA-FT4, IEEE1202 and UL 1685 Page 4 of 8 November 2015
5 b. ICEA S , CSA 22.2 No. 230 and 232 c. Fluid immersion testing per ASTM D412 d. Sunlight Resistant Jacket e. Oil Res II compliant Jacketing System f. Zero Halogen Per MIL PRF g. Temperature Range- Operating:-55ºC to +70ºC,Storage: -60ºC to +70ºC h. Installation: -30ºC to +50ºC. 4. The FO cable for use in the Transit Tunnel shall meet all of the above and be LSZH and meet the requirements of NFPA 130 and NFPA 502 for use in Fixed-Guideway Transit Systems and Road Tunnels. 5. The Transit Tunnel Fiber Optic Cable shall be AFL LA Series, Part number LA1449CC111N1, Arctic low temperature. No approved equal is permitted. 6. The Aerial Fiber Optic Cable shall be AFL Mini-Span 693 EA Series, Part number AE1449CC20EA0, AE0489CC20EA0, AE0249CC20EA0 or approved equal. B. Fiber Optic Splice Enclosure 1. Enclosures to be used inside the shelters shall be wall mounted with hinged and gasketed door, NEMA 3, aluminum or steel construction, electrostatically applied, powder coat, lockable and modular. 2. Splices shall be fusion type. 3. Splice trays shall handle up to 576 single fusions per enclosure. 4. The wall mounted splice housing shall be AFL Light Link Optical Entrance, Model OEE- 288/576 or OEE 720/1440 or approved equal. 5. Enclosures shall provide storage and protection of fiber splices in individually accessible trays. a. Splice housing shall be equipped with cable strain-relief hardware, routing guides, record label on inside of front door, multiple grommet cable entry ports, work shelf, sealing and retention hardware as required. b. Each splice housing shall be equipped with the quantity of splice trays required to splice the quantity of fibers. C. Fiber Optic Patch Panels 1. Fiber Optic Patch Panel ST UPC Termination panel shall be constructed of 0.09 inch (2.2 mm) minimum aluminum and shall be compatible with an EIA 19 inches (480 mm) equipment rack. 2. Each panel shall be equipped fully loaded ultra-polished ST style single-mode adapters with a pre-installed connectorized pigtail of sufficient length to be fusion spliced in a wall mounted splice enclosure as directed by SEPTA Project Manager. The adapters shall be constructed with a zirconia ceramic alignment insert and a metal housing. The adapters shall provide a maximum attenuation of nm with less than a 0.2 db change after 500 mating cycles. Adapters shall comply with EIA A. Provide dust cover for all unused adapters. Panels shall have each adapter factory numbered and be equipped with laminated plastic nameplates Page 5 of 8 November 2015
6 above each adapter. 3. The rear of each panel shall have a cable management tray a minimum of 8 inches (203 mm) deep with removable cover, incoming cable strain-relief and routing guides and shall accommodate top, bottom or side cable entry. Patch panels shall be AFL Light Link LAN System series high density. 4. The Patch Panels shall be mounted in a standard 19 rack as directed by SEPTA Project Manager. If no suitable rack exists at the time of construction, the Contractor shall provide and install the rack. Racks shall be fastened to the shelter floor in a manner directed by SEPTA Project Manager. D. Trunnion and Dead-end Mounts 1. To complete the bracket number the Contractor shall determine the specific size of the H beam and it s orientation to the cable/ tracks. 2. When only one FO cable is required to be mounted, the Contractor shall use the double mount to provide for future expansion. 3. Trunnion mounts shall be specific to the cable size being used. 4. The dead end mount shall be specific to the cable size being used. EXECUTION A. Installation 1. The Contractor shall be responsible for providing the final design of the fiber optic cable system routing through the tunnels and to all other locations as specified within the Contract Documents. 2. Upon commencing the project, the Contractor shall thoroughly inspect the site and record exact distances for each cable segment. 3. The Contractor shall prepare a Shop Drawing showing the actual locations of all relevant structures; the actual distances between shelters; the actual cable distances; the details of mounting the cables in the tunnel; the details of areal installation; and the details of installing the patch and splice panels. 4. The Contractor shall submit the Shop Drawings to SEPTA for review. 5. No materials purchasing or installation work shall be initiated prior to receiving SEPTA Project Manager s approval of the Shop Drawings. The Shop Drawings shall reflect actual distances. 6. The Contractor shall not allow installation or mounting hardware to interfere, obstruct or cause damage to any of SEPTA s trains or vehicles. All installation hardware and cables shall confine to the distance from the tunnel wall as approved by the SEPTA Project Manager. In the aeriel application the cables shall be installed on the side of the H posts away from the tracks. 7. The Contractor shall be responsible to submit to the SEPTA Project Manager for approval the final fiber optic cable routing and installation design showing terminations locations, equipment installation locations, hanger methods and all other work to be installed under this project. Page 6 of 8 November 2015
7 8. In addition, the Contractor shall provide for the SEPTA Project Manager all construction installation details for approval prior to commencing with the work 9. The Contractor shall install all fiber optic cabling and equipment in accordance with the manufacturers written instructions. B. Test Procedures 1. The Contractor shall perform a comprehensive series of continuity and optical loss tests for each fiber and segment to ensure conformance with Contract and manufacturer s specifications as well as the operational requirements. 2. Contractor shall test all strands with fiber optic light meters recording all fiber loss measurements. Contractor shall provide Optical Time Domain (OTDR) trace measurements of each fiber strand between termination points. 3. All testing shall be recorded and turned over to SEPTA Project Manager for review and approval. Test results shall provide in both a software file and 8.5 x11 printed paper copy. The Contractor shall provide all required software need to view and manipulate the trace files and test results. 4. Acceptance Testing for Optical Fiber Cabling: a. The Contractor shall perform tests in accordance with ANSI/TIA/EIA for single mode optical fiber. b. The tests shall be scheduled as indicated in the following table: Test Wave Length Equipment Needed End-to-end attenuation, both directions 1310 and 1550 nm Power meter, light source Connector loss 1310 or 1550 nm OTDR Splice loss 1310 or 1550 nm OTDR and fusion splicer reading OTDR Trace 1310 or 1550 nm OTDR Table 1: FO Cable Test Requirements C. Documentation 1. Testing shall be performed to verify compliance with the requirements of this Section and shall be performed in accordance with the approved testing plan. Correct any malfunctions as they occur, said malfunctions shall include, but not be limited to, equipment failure or failure of the fiber optic system to comply with the requirements of this Section. After corrections have been made, the test shall restart and shall continue until the results are satisfactory to the SEPTA Project Manager. Page 7 of 8 November 2015
8 2. Prior to cable installation, an acceptance test must be performed on all cable reels and all fibers using an OTDR to verify fiber integrity and quality. a. In the event the reel acceptance tests are not acceptable it is the Contractors responsibility to contact the cable manufacturer for a suitable resolution. b. All proposed resolutions shall be approved by SEPTA Project Manager. 3. All fibers shall be tested for insertion loss, end-to-end at 1310nm and 1550nm and the results recorded electronically. 4. Tests shall be conducted in both directions; fiber length, signature of test technician, and test date shall be recorded. The Contractor shall provide any required viewer software with the test readings. 5. The Contractor shall conduct the final inspection after the SEPTA Project Manager approves the the Contractor s proposal describing the test procedures, test result forms, and timetable for component testing. 6. Test Criteria. Total measured signal loss by field measurement shall not exceed the Max. Link Attenuation as described below. 7. Max. Link Attenuation shall be as calculated below: a. Link Attenuation = Cable Attn + Connector Attn + Splice Attn. b. Cable Attn (db) = Attenuation coefficient (db/km) x Length (Km) c. Attenuation Coefficient i nm for loose tube single-mode outside plant cable ii nm for loose tube single-mode outside plant cable iii nm for tight buffered single-mode inside plant cable iv nm for tight buffered single-mode inside plant cable(e.g db/km x 10km = 3.5dB) d. Connector Attn (db) = number of connector pairs times maximum connector loss in db (e.g. 2 connector pairs x 0.20 db = 0.4 db loss) e. Splice Attn (db) = number of splices times maximum splice loss in (db) (e.g. 4 splices x 0.1 db = 0.4 db loss) f. A max. Link Attenuation calculation shall be prepared for each unique FO path as described in the Contract Documents. 8. The measured Link Attenuation shall not exceed the calculate Max. Link Attenuation. a. If any link is found to equal to or greater than the Max. Link Attenuation, the Contractor shall, at no additional cost, make any needed corrections. b. These needed corrections may include replacement of any non-conforming cables. 9. Single-mode backbone links shall be tested at 1310 nm and 1550 nm in accordance with ANSI/TIA/EIA-526-7, Method A.1, and One Reference Jumper method. END SECTION Page 8 of 8 November 2015
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
More informationSTATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007
804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice
More informationSECTION 16121 FIBER OPTIC CABLE AND ACCESSORIES
SECTION 16121 FIBER OPTIC CABLE AND ACCESSORIES PART 1 GENERAL 1.1 Summary A. This section includes the components and fiber optic cable necessary to provide a network Connection as indicated. The components
More informationNORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
More informationhome site map help ECMS Project: 70197 Standard / Federal Oversight Advertised
Page 1 of 6 S PECIAL PROVISION home site map help ECMS BP ADMIN Project: 70197 Standard / Federal Oversight Advertised Short Description: US 422 Schuylkill River Bridge - D/B: Retaining Wall; ITS Devices;
More informationSECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
More informationCORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.
CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS September 2006 Revision 7 Corning Cable Systems reserves the right to update
More informationPresenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
More informationSECTION 27 08 23 TESTING OF FIBER OPTIC CABLES
SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,
More informationSECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING
SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
More informationFiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable
Fiber Optic Cable Assemblies Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable 1 Cable assemblies used in patch panels (Fiber Distribution Units) are an essential interface
More informationPatch Cords for Data Center Applications
Applications General use of patch cords includes the interconnection of the optical fiber cable plant with opto-electronic equipment, and/or the cross-connection between cable plant segments. Pigtails
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationReliable, Consistent, Quality
Reliable, Consistent, Quality 1-877-320-3143 www.fibertronics.com Reliable, Consistent, Quality Welcome To Fibertronics Inc. Reliability, consistency, and quality is what we put behind every Fiber optic
More informationSECTION 680 FIBER OPTIC CABLE DESCRIPTION
680 SECTION 680 FIBER OPTIC CABLE DESCRIPTION 680.01.01 GENERAL A. The work under this section shall consist of furnishing, installing, and testing all underground and outdoor fiber optic cables. B. All
More informationSpecial Specification 6033 Computerized Transportation Management System
6033 Special Specification 6033 Computerized Transportation Management System 1. DESCRIPTION Relocate computerized transportation management system (CTMS) equipment as shown on the plans and as described
More informationFiber-to-the-Home/FTTH
Hands-On Design, Installation, Maintenance & Troubleshooting Active and Passive Optical Networks Course Description This Hands-On 2-day course is designed to provide technicians with Hands-On practical
More informationPretium Connector Housings
Pretium Connector Housings A LANscape Pretium Solutions Product Applications Main cross connect, intermediate cross connects and telecommunications rooms Rack or equipment cabinet installations Data center
More informationATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6
050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY
More information270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
More informationTechnical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations
The Fiber Optic Association, Inc. 1119 S. Mission Road #355, Fallbrook, CA 92028 1-760-451-3655 Fax 1-781-207-2421 Email: info@thefoa.org http://www.thefoa.org Technical Bulletin Guidelines For Testing
More informationSTATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE AND COMPONENTS. January 15, 2016
804.01 Description 804.02 General 804.03 Materials 804.04 Warranties 804.05 Fiber Optic Cable 804.06 Fan-Out Kit 804.07 Drop Cable 804.08 Fiber Optic Patch Cord 804.09 Fiber Termination Panel 804.10 Fusion
More informationPretium EDGE HD Solutions
Pretium EDGE HD Solutions for Enterprise Data Centers and Storage Area Networks Corning Cable Systems Pretium EDGE HD Solutions create a fiber optic tip-to-tip solution for Data Centers and Storage Area
More informationSECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
More information1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
More informationUT Southwestern Medical Center Information Resources Cable Installation Standard
UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system
More informationSECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
More informationSECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
More informationThe following terms are defined within the context of the fiber optic industry
The following terms are defined within the context of the fiber optic industry Adapter A mechanical media termination device designed to align and join fiber optic connectors. Often referred to as coupling,
More informationHOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
More informationCHARTER TOWNSHIP OF SHELBY REQUEST FOR PROPOSAL. Fiber Optic and Data Cabling Project Shelby Township Police Building
CHARTER TOWNSHIP OF SHELBY REQUEST FOR PROPOSAL The Charter Township of Shelby is soliciting proposals to install fiber optic and data cabling to serve a new Police Building that is under construction
More informationADC-APC Integrated Cisco Data Center Solutions
Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the
More informationMETER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
More informationSECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
More informationRittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow
More informationSection 27 05 26 Grounding and Bonding for Communications
Part 1 General 1.1 General 1.1.1 Summary A. This section governs the products and execution requirements relating to furnishing and installing grounding and bonding for the communication systems. B. Description
More informationCalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
More informationReduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U
Reduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U Applications The High Density Cabinets are suitable for Central Offices and can be used as fiber nodes and termination points
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationSPECIFICATION STANDARD OPTICAL FIBER BACKBONE CABLING 27 13 23
PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and
More informationThe Contractor shall furnish and install all shielded power cable suitable for use on this project.
Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS
More informationDiscontinued. Volition. Fiber Optic Cable. 3Innovation
Volition Fiber Optic Cable Tough enough to take it. Easy to handle. The Volition Network Solution from 3M includes horizontal and backbone cable with 62.5/125 µm and 50/125 µm multimode fiber, and 9/125
More informationPolymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
More informationFIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
More informationFiber Optic Specifications
Fiber Optic Specifications All Fiber Optic shall be Corning Altos Single Mode OS1 Outdoor Loose Tube Gel Free Cable Corning Fiber Products only will be accepted and no substitutions or alternates will
More informationBIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors
C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution
More informationOptical Fiber Data Center Field Testing. ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices
Optical Fiber Data Center Field Testing ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices Abstract Data Centers are a growing segment of the enterprise market. Regardless of whether
More information1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
More informationStructured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based
More informationFIBER OPTIC APPLICATION IN A PROFIBUS NETWORK
FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK Field busses are industrial control systems using Programmable Logic lers (PLC) to control and manage field devices found in industrial environments. The communication
More informationFiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications
Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications Topics! Understanding Fiber Types! Powering your Remotes via Composite Fiber! Fiber Design
More informationSECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532.
SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE A. Interior Raceways, Fittings, and Accessories: Section 260532. B. Wiring, General - 600 Volts
More informationManaging High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
More informationfiberopt Whirlwind Fiber Optic Solutions product guide 1-800- 733-9473 99 Ling Rd. Rochester, NY 14612 whirlwindusa. com
fiberopt Whirlwind Fiber Optic Solutions product guide 1-800- 733-9473 99 Ling Rd. Rochester, NY 14612 whirlwindusa. com OpticalCON DUO, QUAD and ADAPTER CABLES 1 2 OC-4-OQ-OQ-0-050 OC-2-M50-OD-SC-0-005
More informationMini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications
Product Description Product Description The Mini Power-Zone Unit Substation from Schneider Electric is a miniaturized version of our Power-Zone Unit Substation. Included are: Circuit Breaker Sealed Step-Down
More informationSUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
More information2301.1 Scope: Communications and Electronic Systems addressed in this section include:
Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and
More informationNUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationSECTION 18370 SIGNAL WIRE AND CABLE
SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory
More informationWall Mounted Products
Metallic Indoor PK Termination Boxes Prysmian Part Numbers: see below Metallic PK Termination Boxes are designed for the termination, branching and distribution of fibre optic cables in telecommunication,
More informationAccelerating Light. Copper Cabling Solutions. Category 6A
Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity
More informationDEPARTMENTAL REGULATION
U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies
More informationSpecifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
More informationTrueAlarm Fire Alarm Systems
TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es
More informationSECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)
SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply
More informationSECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES
SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES 611-1 Description. This Section sets forth Contract acceptance procedures for installations of traffic control signals and devices
More informationSECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING
PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation
More informationCable Installation Project
Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280
More informationCabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
BryComm, LLC -SDD-1901 Cabling Services (per pull) - Labor Only STANDARD TIME The price per cable pull represents all labor to include fishing walls, running cable through modular furniture, terminating,
More informationMultiple Solutions for Connecting Multiple Dwelling Units (MDUs) WHITE PAPER
Multiple Solutions for Connecting Multiple Dwelling Units (MDUs) WHITE PAPER Multiple Solutions for Connecting Multiple Dwelling Units (MDUs) Abstract Fiber-to-the-Premises (FTTP) networks increasingly
More informationData Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
More informationDIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
More informationStructured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
More information4RU High Density Shelf Installation Instructions
4RU High Density Shelf Installation Instructions Table of Contents General Product Information... 1.0 Safety Precautions... 2.0 Tools Required... 3.0 Package Contents... 4.0 Installing the Product Unpacking...
More informationFiber Optic Cable. www.ptsupply.com marketing@ptsupply.com 800-238-7514
Fiber Optic Cable Optical fibers from a choice of major cable manufacturers are available in several grades to manage the bandwidth requirements of today's voice, data and video networks. Single Mode Enhanced
More informationPURE : REliable planning of data center cabling
PURE : REliable planning of data center cabling THE PURE EFFEct: TWICE AS MANY CONNEctionS AND 15 METERS MORE CHannEL LEngtH * PreCONNECT PURE is a milestone in the development of high-end IT cabling for
More informationANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
More informationFiber Optic Cordage. Interconnect A Furukawa Company. Product Description. Why OFS Interconnect Cordage?
Fiber Optic Cordage Interconnect A Furukawa Company Durable, Flexible Cordage Surpasses Industry Strength Standards for Interconnect Cables Product Description OFS Fiber Optic Interconnect Cordage offers
More informationAerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW
Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: sales@supremeco.com Website:
More informationGeneric Category 5e Cabling Specification
Telecommunications Cabling System Technical Specification Category 5e Tyco Electronics Corporation provides this information as a courtesy to its customers and potential customers. Customer should review
More informationAERIAL FIBER OPTIC CABLE PLACEMENT
Installation Practice IP003 Aerial Fiber Optic Cable Placement Rev.-June 2000 Page 1 of 6 AERIAL FIBER OPTIC CABLE PLACEMENT CONTENTS PARAGRAPH SCOPE...1 GENERAL PRECAUTIONS...2 GENERAL DESCRIPTION OF
More informationCOMMUNICATIONS 270000-1
SECTION 270000 COMMUNICATIONS PART 1 - GENERAL 1.1 INTRODUCTION/ RELATED DOCUMENTS A. These specifications establish technical and operation requirements for various technologies planned for the CityWalk
More informationHIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)
Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission
More informationGenerator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
More informationSection 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1
Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader
More informationTelecommunications Systems Narrative Page 1 The Engineering Enterprise
I. TELECOMMUNICATIONS GENERAL REQUIREMENTS A. The project consists of a renovation to the historic Clinical Sciences building, originally built in 1933. The existing building has a total area of 105,000
More informationCabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council
Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Date: 6/19/2013 Version: 1.0 Prepared by: Gregory Cotten Department of General Services District
More informationPHOENIX OPTIX WIRING AND INTERCONNECT SOLUTIONS
PHOENIX OPTIX WIRING AND INTERCONNECT SOLUTIONS Copper or Fiber...Data & Power Solutions Optimized for Low Loss Performance in Commercial and Military Environments PHOENIX OPTIX Wiring Solutions that Meet
More informationADC Structured Cabling Solutions
ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution
More informationPlug & Play Universal Systems
Plug & Play Universal Systems A LANscape Pretium Plug & Play Universal Systems for Data Centers and Storage Area Networks (SANs) Corning Plug & Play universal systems create a fiber optic tip-to-tip solution
More informationCabling & Test Considerations for 10 Gigabit Ethernet LAN
Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit
More informationAPPLICATIONS ROV & AUV SEISMIC PRODUCTION SYSTEMS DOWNHOLE JUMPER & CABLE SYSTEMS DRILLING CONTROL
APPLICATIONS ROV & AUV SEISMIC PRODUCTION SYSTEMS DOWNHOLE JUMPER & CABLE SYSTEMS DRILLING CONTROL ROV & AUV PRODUCTS GRE (Glass Reinforced Epoxy) CS-MS 55 & 66 SERIES MINI-CON HUMMER GLOBE-CON ALL-WET
More informationNORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS
SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications
More informationINTELLIGENT INFRASTRUCTURE MANAGEMENT
F/ System F/ Assemblies, 9.0 W W W. S I E M O N. C O M SECTION CONTENTS System...............................9. IM Software........................... 9. Analyzers..............................9. System
More informationFiber Optics in Harsh Environment Applications
Fiber Optics in Harsh Environment Applications Table of Contents Industrial Testing Comparisons 2 Fiber Optics in Harsh Environment Applications 3 Oil & Gas Products 4 Mining Products 6 Manufacturing 8
More informationGuidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...
LANscape Solutions Recommended Fiber Optic Test Guidelines Table of Contents 1. Introduction...1 2. Why Test?...1 3. Tier 1 and Tier 2 Testing...2 4. Encircled Flux...3 5. Link-Loss Budgets...4 6. Proper
More informationSOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels
More informationNetworks. The two main network types are: Peer networks
Networks Networking is all about sharing information and resources. Computers connected to a network can avail of many facilities not available to standalone computers: Share a printer or a plotter among
More information