Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

Size: px
Start display at page:

Download "Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035"

Transcription

1 Instruction Bulletin February 999 Middletown, OH, USA DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 605

2 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Contents February 999 CONTENTS DSII AND DSLII LOW VOLTAGE POWER CIRCUIT BREAKERS Ordering instructions POLE UNITS Type DS-206, DSL-206, DSII-08, DSLII Type DS-206E, DS-206H, DS-206S, DS-46, DSL-46, DS-46H, DS-46S, DS-420, DSII-508, DSII-608, DSII-56, DSII-66, DSII-620, DSLII Type DS-62 and DSII Type DS-840 and DSII ARC CHUTES BARRIERS MAIN DISCONNECT CONTACT ASSEMBLY MECHANISM MECHANISM AND RELATED PARTS CONTROL COMPONENTS AUTOMATIC TRIPPING STSTEMS Current Sensors CURRENT LIMITING BREAKERS ACCESSORIES AND OTHER PARTS SWITCHGEAR CELL PROVISIONS AND UPGRADES RECOMMENDED SPARE PARTS FOR STOCK i

3 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts General Information DSII AND DSLII LOW VOLTAGE POWER CIRCUIT BREAKERS DIGITRIP Trip Unit Outside Wiring Guide Shutter Drawout Unit Position Indicator Padlock Plate Trip Plate Escutcheon Plate Nameplate Emergency Charging Handle Open-Close Indicator Close Bar Spring Charge indicator Front Cover : DSII-08 Breaker Front View Automatic Trip Relay (ATR) (optional) DIGITRIP Trip Unit Rating Plug Auxiliary Switch Wire Guide PT Module (80D Only) Auxiliary Switch (optional) Auxiliary Current Sensors Emergency Charging Handle Shunt Trip (optional) Direct Trip Actuator Levering Mechanism Assembly Overcurrent Trip Switch (optional) Spring Charge Motor (Power Operated Circuit Breakers Only) Opening Spring 2: DS-46 Breaker with Front Cover Removed

4 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Ordering Instructions February 999 Arc Chutes Secondary Disconnect Contact Mounting Frame Secondary Disconnect Contact Cover Moving Secondary Disconnect Contacts Auxiliary Switch (optional) Levering Arm Device Main Disconnect Contacts Roller (4 per circuit breaker) Sensors : DS-46 Breaker Side View without Barriers ORDERING INSTRUCTIONS. Check the nameplate to identify the type of breaker you have. 2. Identify the part(s) from the photos shown.. Determine the style number for the required parts. 4. Specify the quantity required. 5. Contact your local Square D Distributor to place your order. 2

5 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Pole Units POLE UNITS Type DS-206, DSL-206, DSII-08, DSLII : DS-206 and DSII-08 Pole Unit Assembly (Front View) 6: DS-206 and DSII-08 Lower Stud Assembly : DS-206 and DSII-08 Pole Unit Assembly (Rear View) 7: DS-206 and DSII-08 Upper Stud Assembly Description Required Per Breaker DS-206 and DSII-08 Style DSL-206 and DSLII-08 Style Three Pole Unit Assembly 4, 5 40D52G05 40D52G07 A three pole unit assembly includes: Molded Base Lower Stud Assembly 6 59C652G0 59C652G0 Upper Stud Assembly 7 59C65G0 59C65G0 Only available in a three pole unit assembly.

6 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Pole Units February 999 Type DS-206E, DS-206H, DS-206S, DS-46, DSL-46, DS-46H, DS-46S, DS-420, DSII-508, DSII-608, DSII-56, DSII-66, DSII-620, DSLII : DS-46 Pole Unit Assembly (Front View) 0: DS-46 Lower Stud Assembly : DS-46 Pole Unit Assembly (Rear View) : DS-46 Upper Stud Assembly Description No. No. Req d Per Breaker DS-206H, DS-206S DS-46, DSII-508 DSII-56 Style DSL-46 DSLII-56 Style DS-206E, DS-46H DS-46S, DS-420 DSII-608, DSII66 DSII-620 Style Single Pole Unit Assembly 8, 9 5D064G0 5D065G0 5D065G02 A single pole unit includes: Molded Base ➁ ➁ ➁ Lower Stud Assembly 0 26D298G06 9D6G04 9D6G05 Upper Stud Assembly 59C750G02 9D65G0 9D65G02 ➁ Only available in a single pole unit assembly. This is a direct replacement pole unit. It is different in appearance than the original. 4

7 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Pole Units Type DS-62 and DSII : DS-62 and DSII-62 Pole Unit Assembly (Front View) 4: DS-62 and DSII-62 Lower Stud Assembly : DS-62 and DSII-62 Pole Unit Assembly (Rear View) 5: DS-62 and DSII-62 Upper Stud Assembly Description Required Per Breaker DS-62, DSII-62 Style Single Pole Unit Assembly 2, 567F962G0 A single pole unit assembly includes: Molded Base Lower Stud Assembly 4 40D09G05 Upper Stud Assembly 5 26D299G02 Only available in a single pole unit assembly. 5

8 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Pole Units February 999 Type DS-840 and DSII : DS-840 and DSII-840 Pole Unit Assembly (Front View) 8: DS-840 and DSII-840 Lower Stud Assembly : DS-840 and DSII-840 Pole Unit Assembly (Rear View) 9: DS-840 and DSII-840 Upper Stud Assembly Description Required Per Breaker DS-840, DSII-840 Style Single Pole Unit Assembly 6, 7 567F99G0 A single pole unit assembly includes: Molded Base Lower Stud Assembly 8 40D778G0 Upper Stud Assembly 9 40D779G0 Only available in a single pole unit assembly. 6

9 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Arc Chutes ARC CHUTES Arc Chutes : DS-840 without Barriers : 2: : 24: Breaker Type Required Per Breaker Arc Chute Kit (Includes ) Style DS-206, DSL-206, DSII-08, DSLII-08 2 A568G0 DS-206E, DS-206H, DS-206S, DS-46, DS-46H, DS-46S, DSL-46, DS-420, DSII-508, DSII-608, DSII-56, DSII-66, DSII-620, DSLII A568G02 DS-62, DSII-62 2 A568G0 DS-840, DSII A568G04 7

10 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Barriers February 999 BARRIERS Barriers : DS-840 with Barriers : 28: : 29: Breaker Type Required Per Breaker Barrier Kit (Includes 4) Style DS-206, DSL-206, DSII-08, DSLII A569G0 DS-206E, DS-206H, DS-206S DS-46, DS-46H, DS-46S, DSL-46, DS-420, 27 4 A569G02 DSII-508, DSII-56, DSII-608, DSII-66, DSII-620, DSLII-56 DS-62, DSII A569G04 DS-840, DSII A569G05 8

11 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Main Disconnect Contact Assembly MAIN DISCONNECT CONTACT ASSEMBLY : : : 4: : Breaker Type Maximum Amp. Rating Required Per Breaker Main Disconnect Contact Assembly Kit DS-206, DSL-206, DSII-08, DSLII A570G0 DS-206H, DS-206S, DS-46, DSL-46, DSII-508, DSII-56, DSLII-56 6 A570G02 DS-206E, DS-46H, DS-46S, DS-420, DSII-608, DSII-66, DSII A570G0 DS-62, DSII A570G04 DS-840, DSII A570G05 A kit includes the total number of main disconnect contact assemblies required for one breaker. 9

12 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Mechanism February 999 MECHANISM Description Required Per Breaker All Types DS/ DSL DSII/DSLII except DS-62, DSII-62, DS-840, DSII-840 Style DS-62, DSII-62 Style DS-840, DSII-840 Style 5: Levering Mechanism Assembly Levering Mechanism Assembly 5 449D224G04 449D224G04 449D224G05 Crank Kit includes: Crank Arm with Roller, Special Bolt and Elastic Stop Nut A95G0 88A95G02 88A95G : Crank Kit MECHANISM AND RELATED PARTS : Electrically Operated with Closing Spring 40: Emergency Charge Handle Kit 4: Opening Spring : Manual Charge Handle Kit with Charging Cams 44: Trip Shaft Kit 8: Manual Mechanism with Closing Spring : Closing Spring Assembly 42: Oscillator Assembly Kit 45: Hold Pawl and Ratchet Kit 0

13 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Mechanism and Related Parts Description Mechanism Assembly without Closing Spring Includes: Main Drive Link Assembly (with roller) Oscillator Assembly Oscillator Reset Spring Emergency Charge Device Trip Latch, Trip Lever (for Motor Cutoff Switch) Trip Latch Reset Spring Mechanism Assembly without Closing Spring Includes: Main Drive Link Assembly (with roller) Trip Latch, Trip Lever (for Motor Cutoff Switch) Trip Latch Reset Spring Closing Spring Assembly Includes: Closing Spring and Spring Ends DS-206, DS-206S, DSL-206, DSII-08,DSLII-08 DS-206H, DS-46, DS-46S DSL-46, DSII-508, DSII-56, DSLII-56 DS-206E, DS-46H, DS-420, DSII-608, DSII-66, DSII-620 Emergency Charge Handle Kit Includes: Emergency Charge Device and Emergency Charge Handle Manual Charge Handle Kit Includes: Manual Charge Assembly and Manual Charge Handle and Charging Cams Oscillator Assembly Kit Includes: Oscillator Assembly, and Oscillator Reset Spring Required Per Breaker ALL DS/DSL, DSII/DSLII except DS-62, DS-840, DSII-62, DSII-840 Electrically Operated Style Manually Operated Style DS-62, DS-840,DSII-62, DSII-840 Electrically Operated Style Manually Operated Style 7 567F759G02 N/A 567F759G04 N/A 8 N/A 567F759G0 N/A 567F759G A67G0 79A67G A52G0 49A52G A67G02 79A67G A67G0 79A67G A96G02 N/A 88A96G02 N/A 4 N/A 88A96G0 N/A 88A96G0 42 A566G0 N/A A5566G0 N/A Opening Spring B907H0 698B907H0 698B907H0 698B907H0 Trip Shaft Kit Includes: Trip Shaft Lever, Trip Shaft, and Trip Shaft Return Spring 44 A567G0 A567G0 A567G0 A567G0 Hold Pawl and Ratchet Wheel Kit 45 A579G0 N/A A579G0 N/A Two Opening springs are required for DS-62, DS-840, DSII-62, DSII-840

14 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Control Components February 999 CONTROL COMPONENTS 46: 47: 48: Spring Charging Motor Kit Anti-Pump Relay Undervoltage Trip Assembly Description Spring Charging Motor Kit Includes: Motor Crank, Roller, Connectors, Mtg. Bracket and Hardware Anti-Pump Relay UNDERVOLTAGE TRIP ASSEMBLY WITH WIRES (INSTANTANEOUS) UNDERVOLTAGE TRIP ASSEMBLY WITH WIRES (TIME DELAY) Voltage 48 DC 25 DC 250 DC 20 60HZ HZ 48DC 25DC 250DC 20 60HZ HZ 20 60HZ HZ HZ HZ 48 DC 25 DC 250 DC 24 DC 5 50HZ HZ 20 50HZ HZ 45 50HZ HZ 20 60HZ HZ HZ HZ 48 DC 25 DC 250 DC 24 DC 5 50HZ HZ 20 50HZ HZ 45 50HZ HZ DS/DSL DSII/DSLII except DS-840 DSII-840 Style 449D4G0 449D4G0 449D4G02 449D4G0 449D4G02 829A05G0 829A05G04 829A05G05 829A05G0 829A05G02 752A05G0 752A05G02 752A05G0 752A05G04 752A05G05 752A05G06 752A05G07 752A45G0 752A45G02 752A45G0 752A45G04 752A45G05 752A45G05 752A45G06 752A06G0 752A06G02 752A06G0 752A06G04 752A06G05 752A06G06 752A06G07 752A46G0 752A46G02 752A46G0 752A46G04 752A46G05 752A46G05 752A46G06 DS-840 DSII-840 Style 449D4G0 449D4G0 449D4G02 449D4G0 449D4G02 829A05G0 829A05G04 829A05G05 829A05G0 829A05G02 752A25G0 752A25G02 752A25G0 752A25G04 752A25G05 752A25G06 752A25G07 752A45G0 752A45G02 752A45G0 752A45G04 752A45G05 752A45G05 752A45G06 752A26G0 752A26G02 752A26G0 752A26G04 752A26G05 752A26G06 752A26G07 752A46G0 752A46G02 752A46G0 752A46G04 752A46G05 752A46G05 752A46G06 LATCH CHECK SWITCH 49 ALL 40D6G0 40D6G0 Replacement shunt trip, spring release and undervoltage trip are complete assemblies and include mounting hardware and wire leads (not shown). If adding shunt trip, spring release or undervoltage trip to manual breakers; an auxiliary switch (page 4), and wiring guide kit (page 9) are required. Confirm that secondary contacts exist in the rear of the breaker. All changes or additions on the breaker should be wired per the standard drawing and indicate the change on the breaker nameplate : Latch Check Switch 2

15 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Control Components Description Voltage DS/DSL DSII/DSLII except DS-840 DSII-840 Style DS-840 DSII-840 Style Shunt trip Assembly with wires DC 2 DC 48 DC 25 DC 250 DC 20 60HZ HZ 752A02G0 752A02G02 752A02G0 752A02G04 752A02G05 752A02G06 752A02G07 752A22G0 752A22G02 752A22G0 752A22G04 752A22G05 752A22G06 752A22G07 50: Shunt Trip Assembly For use with Capacitor Trip (25VDC) 752A02G08 752A22G08 Overcurrent Trip Switch Manual Reset (2 Cont. with wires) 5 ALL 752A04G0 752A24G0 Overcurrent Trip Switch Manual Reset ( Cont. with wires) 5 ALL 752A04G02 752A24G02 5: Overcurrent Trip Switch Manual Reset Overcurrent Trip Switch Manual Reset (4 Cont. with wires) Overcurrent Trip Switch Electrical Reset Includes: coil (2 Cont. with wires) 5 ALL 752A04G0 752A24G DC 5 AC 25 DC 20 AC 250 DC 752A04G04 752A04G05 752A04G06 752A04G07 752A04G08 752A24G04 752A24G05 752A24G06 752A24G07 752A24G08 Overcurrent Trip Switch Electrical Reset includes coil ( Cont. with wires) 5 48 DC 5 AC 25 DC 20 AC 250 DC 752A04G09 752A04G0 752A04G 752A04G2 752A04G 752A24G09 752A24G0 752A24G 752A24G2 752A24G 52: Spring Release Assembly Spring Release Assembly with wires Motor Cut-off Switch Includes: Mounting Bracket and Insulation DC 25 DC 250 DC 20 60HZ HZ 752A0G0 752A0G02 752A0G0 752A0G04 752A0G05 752A2G0 752A2G02 752A2G0 752A2G04 752A2G05 5 ALL 567F40G06 567F40G06 Replacement shunt trip, spring release and undervoltage trip are complete assemblies and include mounting hardware and wire leads (not shown). If adding shunt trip, spring release or undervoltage trip to manual breakers; an auxiliary switch (page 4), and wiring guide kit (page 9) are required. Confirm that secondary contacts exist in the rear of the breaker. All changes or additions on the breaker should be wired per the standard drawing and indicate the change on the breaker nameplate : Motor Cut-Off Switch

16 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Automatic Tripping Systems February : New Auxiliary Switch Assembly Kit (round) - one high New Auxiliary Switch Assembly Kit (round) (Includes mounting bracket, switch, covers, and screw) High Assembly Kit 2 High Assembly Kit Additional Auxiliary Switch Assembly with cover (rectangular) ➁ 2nd Auxiliary Switch rd Auxiliary Switch Replacement Auxiliary Switches Assembly (rectangular) ➂ (Includes: switch, drive link and hardware) st Auxiliary Switch (ABAB only) 2nd Auxiliary Switch rd Auxiliary Switch Replacement Auxiliary Switch Only (rectangular) ABAB Auxiliary Switch AAAA Auxiliary Switch BBBB Auxiliary Switch AAAB Auxiliary Switch ABBB Auxiliary Switch A = N.O. B= N.C. Style A57G0 A57G02 697B56G08 697B56G09 697B56G04 697B56G05 697B56G06 449D622G 449D622G4 449D622G5 449D622G6 449D622G7 ➁ ➂ When adding an auxiliary switch, be sure that the wiring guides are installed. There are three wiring guides and they are located as follows: one inside and one outside on the left side of the breaker, and one between the right side of the trip unit and the auxiliary switch. Refer to on page and 2 on page for location and to page 9 for style numbers. Additional secondary contacts and covers may be required. Refer to on page 2 and page 9 for the style number. For adding to breakers with existing rectangular auxiliary switches. Used for replacement only of existing rectangular auxiliary switches. AUTOMATIC TRIPPING STSTEMS Digitrip Mounting Type of Trip Unit 50 with Gnd 50 without Gnd 60 with Gnd 60 without Gnd 80D with Gnd, ATR, and PT module 80D without Gnd and with ATR and PT module Style 694C75G0 694C75G02 694C75G0 694C75G C75G C75G : Direct Trip Actuator (DTA) Direct Trip Actuator (DTA) Style For use with Digitrip box 6482C55G28 For use with Digitrip Mounting 6482C55G Auxiliary CT Mounting Type with Gnd without Gnd Style 694C740G0 694C740G02 Digitrip ( 58) Trip Unit Trip Functions Style LI LSI LS LIG LSG LSIG 7829C05G0 7829C05G C05G0 7829C05G C05G C05G06 4

17 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Automatic Tripping Systems Digitrip ( 58) LI LSI LS LIG LSG LSIG 7829C0G0 7829C0G C0G0 7829C0G C0G C0G D 80D 80D 80D 80D 80D LI LSI LS LIG LSG LSIG 7829C54G0 7829C54G C54G0 7829C54G C54G C54G06 56: Digitrip Mounting with ATR and PT Module Digitrip Rating Plugs Digitrip Rating Plugs for 50, 60, 80D Rated Current l n Current Sensor Rating Hertz Style D8674G0 D8674G02 57: Auxiliary CT Mounting (for use with Digitrip Mounting) D8674G0 D8674G04 D8674G05 D8674G06 D8674G07 D8674G08 D8674G D8674G0 D8674G D8674G D8674G D8674G4 D8674G D8674G6 D8674G7 D8674G8 D8674G D8674G20 D8674G2 D8674G22 D8674G2 58: Digitrip with Rating Plug D8674G24 D8674G25 D8674G26 D8674G27 D8674G28 D8674G29 D8674G D8674G D8674G2 D8674G D8674G42 D8674G D8674G5 D8674G6 D8674G7 D8674G D8674G9 D8674G40 D8674G4 For use with forced air cooled DS-840 only. 5

18 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Automatic Tripping Systems February 999 Current Sensors 59: DS-206, DSII-08 Sensor with Spacer Sensor Ampere Rating Breaker Types ALL DS-206, DS-46, DS- 420 ALL DSII-08,DSII-508, DSII-608, DSII-56, DSII-66, DSII-620 All DS-46, DS-420 All DSII-56, DSII-66, DSII-620 Breaker Frame Rating Style 5D995G0 5D995G5 5D995G02 5D995G0 5D995G04 5D995G06 5D995G08 5D995G2 5D995G DS-420, DSII D995G DS-62, DSII DS-840, DSII D995G2 ➁ 5D995G24 ➂ 5D995G ➁ 5D995G2 ➂ 588C74G02 ➃ 588C74G DS-850, DSII C74G0 ➄ DS-206, DSII-08 Spacer Kit (For DS-206 & DSII-08 only. 794A965G0 ➅ Not required for DS-206E, DS-206H, DS-206S, DSII-508, or DSII-608) ➁ ➂ ➃ ➄ ➅ These are replacements for sensors style 794A70G series, and are for phase or neutral use, except as noted. For neutral use only. For phase use only. For DS-840 and DSII-840 only. For use with forced air cooled. Kit includes 2 spacers : DS-62, DSII-62 Sensor : DS-840, DSII-840 Sensor 6

19 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Current Limiting Breakers CURRENT LIMITING BREAKERS Description Required Per Breaker Style Blown Limiter Indicator Assembly 40D777G0 Blown Limiter indicator Assembly (For fuse Truck) 40D777G0 Isolating Transformer Assembly 59C755G0 Isolating Transformer Only 795A82H0 Includes transformers. Current Limiters 62: DSLII-56 (Front View) Breaker Type DSL-206, DSLII-08 DSL-206, DSLII-08 DSL-206, DSLII-08 Required Per Breaker Amp Rating Style 40D6G0 40D6G02 40D6G0 DSL-206, DSLII-08 DSL-206, DSLII-08 DSL-206, DSLII D6G04 40D6G05 40D6G06 DSL-206, DSLII-08 DSL-206, DSLII-08 DSL-206, DSLII D6G07 40D6G0 40D6G DSL-206, DSLII-08 DSL-46, DSLII-56 DSL-46, DSLII D6G2 5D92G0 5D92G02 DSL-46, DSLII-56 DSL-46, DSLII-56 DSL-46, DSLII D92G0 5D92G04 5D92G DSL-46, DSLII-56 DSL-46, DSLII D92G09 5D92G0 6: DSLII-56 without Barriers (Rear View) Drawout Fuse Truck Type Current Limiters Truck Type DSL-200 DSLII-200 DSL-4000 DSLII-4000 Required Per Breaker Amp Rating Style 5980C0G0 ➁ 5980C0G02 ➁ 5980C0G0 ➁ 5980C0G0 ➁ 5980C0G02 ➁ 5980C0G0 ➁ 5980C0G04 ➁ ➁ Limiters are mounted on a separate fuse truck. 7

20 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Accessories and Other Parts February 999 ACCESSORIES AND OTHER PARTS : Replacement Nameplate (DSL Shown) 67: Portable Lifter (Style RC000) : DS and DSII Breaker Label Kit (Style 887A84G0) 68: Lifting Yoke (Spreader Bar) (Style , ) : DSL and DSLII Breaker Label Kit (Style 8A07G0) 69: Levering-In Tool (Style ) 8

21 Bulletin No February 999 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Accessories and Other Parts 70: Fastener Kit (Style 586A86G0 ) Each kit includes 84 fasteners in various sizes and quantities of the types shown in 70 Description Replacement Nameplate Secondary Disconnect Contact Secondary Disconnect Contact Cover Secondary Disconnect Mounting Frame with 8 point contact block Drawout Breaker Front Covers for Digitrip Box No. Use Application Style 64 Used to replace the nameplates on the front of the breaker For Disconnecting secondary control Covers top of secondary contacts For replacing secondary disconnect mounting frame, or for adding to breaker originally supplied without secondary contacts DS Dummy DS Drawout DSL Fuse Truck DS Fixed DS/DSL DS/DSL DS/DSL Covers Front of Breaker All DS (except DS-62 /DSII-62 DS-840/DSII-840) 994D95H6 994D95H6 994D95H64 994D95H65 994D95H67 59C498G06 50B569H0 59C498G07 567F498H0 7: Finger Cluster Removal Tool (Style 59C90G0) Escutcheon Plate DS-62, DSII-62 DS-840, DSII-840 DSL-206 DSL-46 DSLII-08 DSLII-56 Mounts on front cover All DS/DSII Breakers All DSL /DSLII Breakers 567F499H0 567F50H02 567F498H0 567F498H0 567F498H0 567F498H0 695C02H0 695C0H0 Breaker Roller Kit (double edge type) and Retaining Rings To roll the breaker in and out of the housing (Set of four) All Breakers A578G0 Wiring Guide Kit Guides for wiring All DS (except DS-840) A588G0 72: 7: Breaker Test Kit and Adapter (Style 8779C02G02) Test Kit Adapter (Style 8779C02G0) DS-840 All DSL Breaker 5D48G0 A589G0 Wire Channels Guides for wiring DSII/DSLII 5D48G02 Wire Support Spacer Secondary Contact Block Assembly Right Hand Side Support Secondary Contact Frame Wire Support Bracket Communications Receptacle Assembly Right Hand Wire Retainer Right Hand Wire Retainer Right Hand Wire Through Spacer for wire channels Disconnecting secondary control For mounting secondary contact blocks For mounting secondary contact blocks DSII/DSLII DSII/DSLII DSII/DSLII DSII/DSLII 88A97H0 69C68G0 695C8H02 695C49G0 Support wire channels DSII/DSLII 795C072H02 N/A Disconnecting communications DSII/DSLII 806A80G0 Guides for wiring DSII 47B242H04 Guides for wiring DSLII 47B242H05 Guides for wiring DSLII-08,DSLII- 46, DSLII C989H04 Customer is to provide the following original information: GO, P.O., Item, FN and Option s. 9

22 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Bulletin No Switchgear Cell Provisions and Upgrades February 999 SWITCHGEAR CELL PROVISIONS AND UPGRADES If the original switchgear has blank compartments or if an existing breaker needs to be upgraded, cell parts can be ordered. They typically include some or all of the following parts: Mounting pan, extension rails, and push-to-trip mechanism Interference brackets Polyester backplate (CT mounting plate) Line and load stabs Load bus runbacks, extensions, supports, and lug adapters Door with handle, hinge and trip button Gas and arc shields Seismic positioner Contact your local Square D sales representative with the following information: Factory Order number Date of manufacture RECOMMENDED SPARE PARTS FOR STOCK The quantities listed are recommended for 5 breakers of the same rating. Items 8-0 are only required for electrically operated breakers. The reference page number contains the complete styles of the required parts. Where needed, fill in or complete the style numbers for your application and forward to your local Square D sales representative. Item Quantity Description Pole Unit Assembly Main Disconnect Contact Assembly Kit Trip Shaft Kit Direct Trip Actuator (DTA) Opening Spring Fastener Kit Secondary Disconnect Contact Shunt Trip Assembly Spring Release Assembly Anti-Pump Relay Spring Charging Motor Kit Reference Page Style A570G A576G0 6482C55G 698B907H0 586A86G0 59C498G06 752A G0_ 752A G0_ 829A05G 449D4G0_ 20

23

24 Trademark Acknowledgements DIGITRIP is a registered trademark of Cutler-Hammer. Square D Company 500 S. University Blvd. Middletown, OH, USA (5) Square D, POWERLOGIC, SY/LINK, SY/MAX, SY/NET and are registered trademarks of Square D Company. System Manager is a trademark of Square D Company. All other trademarks are the intellectual property of their respective companies. Electrical equipment should be serviced only by qualified electrical maintenance personnel. No responsibility is assumed by Square D for any consequences arising out of the use of this material. Bulletin No February 999. Replaces 605- dated 0/92.

LVA Take Offs in Bid Manager

LVA Take Offs in Bid Manager Electrical Sales and Distributor Training Low Voltage Assemblies (LVA) LVA Take Offs in Bid Manager This job aid helps to define some of the common selection questions that are encountered when configuring

More information

PowlVac Type PVDST Replacement Vacuum Circuit Breaker Replacement for Federal Pacific Type DST Air-Magnetic Circuit Breakers

PowlVac Type PVDST Replacement Vacuum Circuit Breaker Replacement for Federal Pacific Type DST Air-Magnetic Circuit Breakers Instructions IB-50031 PowlVac Type PVDST Replacement Vacuum Circuit Breaker Replacement for Federal Pacific Type DST Air-Magnetic Circuit Breakers Installation Maintenance Renewal Parts POWELL ELECTRICAL

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

Instructions for Installation, Operation and Maintenance of 24kV Type W-VAC Vacuum Circuit Breaker

Instructions for Installation, Operation and Maintenance of 24kV Type W-VAC Vacuum Circuit Breaker Instructions for Installation, Operation and Maintenance of 24kV Type W-VAC Vacuum Circuit Breaker Effective 2/98 ! WARNING! WARNING IMPROPERLY INSTALLING OR MAINTAINING THESE PRODUCTS CAN RESULT IN DEATH,

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

IB-77130 PowlVac-ND ITE-HK 5kV Replacement Vacuum Circuit Breaker. Replacement for ABB Type ITE-HK Air Circuit Breaker.

IB-77130 PowlVac-ND ITE-HK 5kV Replacement Vacuum Circuit Breaker. Replacement for ABB Type ITE-HK Air Circuit Breaker. IB-77130 PowlVac-ND ITE-HK 5kV Replacement Vacuum Circuit Breaker Replacement for ABB Type ITE-HK Air Circuit Breaker IB-77130 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140) 9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

Vacuum Circuit Breaker Type VAD-3

Vacuum Circuit Breaker Type VAD-3 Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A Low voltage electrical distribution Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A User manual 09/2009 User manual for circuit breakers and switch-disconnectors Masterpact

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

IZM ACB/Circuit-breakers. Robust safety. Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors

IZM ACB/Circuit-breakers. Robust safety. Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors IZM ACB/Circuit-breakers Robust safety Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors t [s] 0.1 0.05 0.04 0.03 0.02 0.01 20 1230DIA-125 (70C1043) 30 40 50 60 80 100

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

SECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE

SECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated on the drawings, a deadfront type, arc resistant

More information

Medium voltage VCP-W MR2 (integral racking)

Medium voltage VCP-W MR2 (integral racking) Supersedes March 2013 Contents Description Page Notices and warnings...................... 2 Introduction.............................. 3 Breaker pan configurations.................. 3 Inspection/maintenance.....................

More information

GEK-90214B. GE Lift Truck. User s Guide 144D2933G1 144D2912G1 144D2911G5

GEK-90214B. GE Lift Truck. User s Guide 144D2933G1 144D2912G1 144D2911G5 g GEK-90214B GE Lift Truck User s Guide 144D2933G1 144D2912G1 144D2911G5 GE LIFT TRUCK EACH USER HAS THE RESPONSIBILITY TO INSTRUCT ALL PERSONNEL ASSOCIATED WITH THIS EQUIPMENT ON ALL SAFETY PRECAUTIONS

More information

Section M POWER LIFTS

Section M POWER LIFTS Section M POWER LIFTS December 2009 1M Index 1. 53-520244-000 Poly V Idler Assembly 2. 53-520205-000 N.A. Mounting Bracket 3. 53-520212-000 Cable Assembly 4. 53-600149-000 Wire Harness Assembly 5. 53-860322-010

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

Sample - No Commercial Use

Sample - No Commercial Use COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

Schneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing

Schneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing Scopes of Work for Electrical Acceptance Testing Schneider Electric Services: life-cycle solutions for electrical distribution equipment Make the most of your energy SM Scopes of Work for Electrical Acceptance

More information

Bolted contact switches. Pringle switches

Bolted contact switches. Pringle switches Bolted contact switches Pringle switches Eaton s Pringle bolted contact switches History Eaton s PringleT switches have helped pioneer the development of high-quality electrical products for commercial

More information

11-600036D PRO MAC 60 07/72 to 12/76 IPL 89321 Page 1 of 19 Accessories

11-600036D PRO MAC 60 07/72 to 12/76 IPL 89321 Page 1 of 19 Accessories 11-600036D PRO MAC 60 07/72 to 12/76 IPL 89321 Page 1 of 19 Accessories 11-600036D PRO MAC 60 07/72 to 12/76 IPL 89321 Page 2 of 19 Accessories 84453 Kit - Piston tool 69191 Kit - Pressure test adaptor

More information

POWER LOCK KIT GENERAL INSTALLATION -J04427 REV. 2007-12-04. Kit Number. Models. Additional Parts Required. Kit Contents

POWER LOCK KIT GENERAL INSTALLATION -J04427 REV. 2007-12-04. Kit Number. Models. Additional Parts Required. Kit Contents -J0 REV. 00--0 POWER LOCK KIT GENERAL Kit Number -0, 0-0 Models For model fitment information, please see the P&A Retail Catalog or the Parts and Accessories section of www.harleydavidson.com (English

More information

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for. The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved

More information

OVEN PARTS For Models:GSC308PJB05, GSC308PJQ05, GSC308PJT05, GSC308PJS05 (Black) (White) (Biscuit) (Black Stainless)

OVEN PARTS For Models:GSC308PJB05, GSC308PJQ05, GSC308PJT05, GSC308PJS05 (Black) (White) (Biscuit) (Black Stainless) OVEN PARTS 30" BUILT IN ELECTRIC COMBO SENSOR/SC (GOLD LINE) 3 05 Litho In U.S.A. (cre) 1 Part No. Rev.A OVEN PARTS 1 Literature Parts 4455994 Installation Instructions Use & Care Guide 8300346 Microwave

More information

DOOR PARTS SECTION D-1

DOOR PARTS SECTION D-1 DOOR PARTS SECTION D-1 1 11 10 11 9 8 1 1 7 6 10 5 4 D- DOOR ASSEMBLY ITEM NO DESCRIPTION QTY. PART NO 1 SERVICE DOOR ASSEMBLY ~ * CONTROL PANEL 1 * DOOR GUARD 1 * 4 DOOR ROLLER ASSEMBLY 1 1148-7 5 T-HANDLE

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

OVEN PARTS For Models:GMC305PDB07, GMC305PDQ07, GMC305PDT07, GMC305PDS07 (Black) (White) (Biscuit) (S.Steel)

OVEN PARTS For Models:GMC305PDB07, GMC305PDQ07, GMC305PDT07, GMC305PDS07 (Black) (White) (Biscuit) (S.Steel) OVEN PARTS 30" BUILT IN ELECTRIC COMBO SENSOR/SC (GOLD LINE) 7 03 Litho In U.S.A. (cre) 1 Part No. OVEN PARTS NOTE: The screws and nuts required to attach a part are listed immediately following that part.

More information

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED

More information

COMMERCIAL GAS DRYER

COMMERCIAL GAS DRYER COMMERCIAL GAS DRYER MODELS CGM2941TQ0 CGM2941TQ1 07 08 Litho in U.S.A. (LT)(mek) c 2008 WHIRLPOOL CORPORATION Part No. Rev. B BULKHEAD PARTS (White) (White) 2 BULKHEAD PARTS 1 Literature Parts 8563800

More information

Spare parts Catalogue

Spare parts Catalogue Technical catalogue Spare parts Catalogue Low voltage circuit-breakers Product support ABB SACE SDC0000D00 Not every original spare parts are really original spare parts. Availability of spare parts for

More information

SENTRON Switching and Protection Devices Air Circuit Breakers

SENTRON Switching and Protection Devices Air Circuit Breakers Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

01.4IB.66000B Power/Vac Vacuum Circuit Breaker. Equipped with ML-17 or ML-17H Mechanism. Powered by Safety

01.4IB.66000B Power/Vac Vacuum Circuit Breaker. Equipped with ML-17 or ML-17H Mechanism. Powered by Safety 0.4IB.66000B Power/Vac Vacuum Circuit Breaker Equipped with ML-7 or ML-7H Mechanism Power/Vac is a registered trademark of Powell Industries, Inc. Powered by Safety Power/Vac Vacuum Circuit Breakers Equipped

More information

Edge 28B. Simple. Clean. PARTS LIST KENT model: 908 4703 010 146 3087 000(1)2007-01

Edge 28B. Simple. Clean. PARTS LIST KENT model: 908 4703 010 146 3087 000(1)2007-01 PARTS LIST KENT model: 908 4703 010 Simple. Clean. 2007-01 2 2007-01 TABLE OF CONTENTS 1 DESCRIPTION PLAN GENERAL VIEW 2-3 CHASSIS SYSTEM 4-5 SIDE BROOM ASSEMBLY 6-7 HOPPER SYSTEM 8-9 TRANSMISSION SYSTEM

More information

Number Wheeler P/N Description Set Rex P/N Notes 1 603500 Base 1 J001 2 603501 Support, Right 1 J002 3 603502 Support, Left 1 J003 4 600328 Nut (M8)

Number Wheeler P/N Description Set Rex P/N Notes 1 603500 Base 1 J001 2 603501 Support, Right 1 J002 3 603502 Support, Left 1 J003 4 600328 Nut (M8) 1 603500 Base 1 J001 2 603501 Support, Right 1 J002 3 603502 Support, Left 1 J003 4 600328 Nut (M8) 4 5 600130 Spring Washer (8mm) 4 6 600344 Roll Pin (M6x30) 4 7 600129 Socket Hd Cap Screw (M8x25) 4 8

More information

Circuit Breakers. Next Generation of Protection Capabilities

Circuit Breakers. Next Generation of Protection Capabilities Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many

More information

7.1. Part Lists. Hardware Insertion Machine. Instructions. Instructions

7.1. Part Lists. Hardware Insertion Machine. Instructions. Instructions Instructions Instructions The Parts in this section of the manual are listed by Item Number, Part Number, Description and Quantity. The Item Numbers are in a circle with an arrow pointing to the specific

More information

MDT5N25 & MTD5N40 SERVICE PARTS

MDT5N25 & MTD5N40 SERVICE PARTS MDTN & MTDN0 SERVICE PARTS This parts list contains the service parts and wiring diagrams for this model. Check the model number of the machine requiring the parts to be sure that this is the correct parts

More information

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Instructions CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Catalog Number 2100-SD1 Description The Bulletin 2100 smoke detector unit is a 0.5 space factor unit for use in Bulletin

More information

Motor Control V12-T13-2 V12-T13-72 V12-T13-76 V12-T13-87

Motor Control V12-T13-2 V12-T13-72 V12-T13-76 V12-T13-87 Motor Control Motor Control............................. Adjustable Frequency AC Drives............................. Synchronous............................................ Starters (Medium Voltage)..................................

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

POWER WAVE 455M/STT & (CE)

POWER WAVE 455M/STT & (CE) Illustration of Sub Assemblies Illustration of Sub Assemblies Illustration of Sub Assemblies Illustration of Sub Assemblies P-450 P-450 PARTS LIST FOR POWER WAVE 455M/STT & (CE) P-450-A P-450-A ILLUSTRATION

More information

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to

More information

INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04 I.L. 32-693 A INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04 DANGER DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTE- NANCE ON EQUIPMENT

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

15VHK-VR Model 20 Replacement Circuit Breaker

15VHK-VR Model 20 Replacement Circuit Breaker Instruction Book IB182053EN Supercedes March 2016 Effective June 2016 15VHK-VR Model 20 15VHK-VR Model20 1200A Shown DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations,

More information

Model 2300DR Installation Guide

Model 2300DR Installation Guide Model 2300DR Installation Guide POWER ACCESS CORPORATION P.O. BOX 1050 170 MAIN STREET NEW HARTFORD, CT 06057 800-344-0088 WEBSITE: www.power-access.com EMAIL: salesinfo@power-access.com 1 STANDARD PARTS

More information

Contractors Guide Central Inverter System Installation

Contractors Guide Central Inverter System Installation Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator

JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator The Janus Pantheon mini operator does not typically require the provision of any additional site requirements other than

More information

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear. OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in

More information

TERMINATION EQUIPMENT INSTRUCTION MANUAL TELE-PIERCE P/N 356-246

TERMINATION EQUIPMENT INSTRUCTION MANUAL TELE-PIERCE P/N 356-246 TERMINATION EQUIPMENT INSTRUCTION MANUAL TELE-PIERCE P/N 356-246 OPERATION AND SERVICE INSTRUCTIONS AMPHENOL 157 SERIES TELE-PIERCE MULTI-WIRE TERMINATION TOOL 356-246 AMPHENOL TERMINATION SYSTEMS 1830

More information

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents

More information

S&C Type FVR Vacuum Substation Circuit Breaker

S&C Type FVR Vacuum Substation Circuit Breaker S&C Type FVR Vacuum Substation Circuit Breaker 15 kv to 38 kv, 110 kv BIL to 150 kv BIL, 1200 A to 4000 A, Class 6065 Instructions for Installation 6065-3001 S&C ELECTRIC COMPANY Specialists in Electric

More information

Solid State Timers Type F

Solid State Timers Type F Solid State Timers Type F Class 9050 CATALOG CONTENTS Description.....................................................Page Product Descriptions............................................. 3 Application

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

Models: WA182, WA242. Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List... 4. Control Panel.

Models: WA182, WA242. Contents. Cabinet Components. Functional Components  Exploded View... 3  Usage List... 4. Control Panel. REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE AIR CONDITIONER Models: WA182, WA242 General Notes! Revised and/or additional pages may be issued from time to time.! A complete and current manual consists

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Number Wheeler P/N Description Set Rex P/N Notes

Number Wheeler P/N Description Set Rex P/N Notes 1 607051 Base 1 A050 2 607052 Motor Cover 1 A052 3 600778 Socket Hd Cap Screw (M8x60) 2 4 607053 Scrap Receiver 1 A053 5 607054 Tank Upper Cover 1 A054 6 607055 Oil Pot 1 A055 7 607056 Strainer 1 A056

More information

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C 41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers

More information

K&T Saw Shop 606-678-9623 or 606-561-4983. 12-400165 MC 91C 11/74 to 04/76 IPL 84456 Page 1 of 11 Accessories

K&T Saw Shop 606-678-9623 or 606-561-4983. 12-400165 MC 91C 11/74 to 04/76 IPL 84456 Page 1 of 11 Accessories 12-400165 MC 91C 11/74 to 04/76 IPL 84456 Page 1 of 11 Accessories 12-400165 MC 91C 11/74 to 04/76 IPL 84456 Page 2 of 11 Accessories 68899 Piston Assy - 0.005 in. oversize 66790 Ring Set - Piston 0.005

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Model 10A Electric Switch Lock

Model 10A Electric Switch Lock Model 10A Electric Switch Lock Installation Operation Maintenance June 2003 Manual 8542 TABLE OF CONTENTS SECTION 1 INTRODUCTION SCOPE OF MANUAL... 1-1 OPERATION NORMAL RELEASE... 1-1 Preliminary Unlock

More information

Flextec 450 PARTS LIST FOR RETURN TO MAIN INDEX

Flextec 450 PARTS LIST FOR RETURN TO MAIN INDEX Illustration of Sub Assemblies Illustration of Sub Assemblies Illustration of Sub Assemblies Illustration of Sub Assemblies P-652 RETURN TO MAIN INDEX PARTS LIST FOR Flextec 450 P-652 P-652-A P-652-A ILLUSTRATION

More information

Lexmark 4037-05E Laser Printer

Lexmark 4037-05E Laser Printer Lexmark 4037-05E Laser Printer asm_1 Covers asm_2 Left Side Frame asm_3 Frame and Redrive [1 of 2] asm_3a Frame and Redrive [2 of 2] asm_4 Top Cover asm_5 Standard Paper Tray asm_6 Fuser asm_7 Electronics

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 techsupport@securitron.com in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install

HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install Carrier-Grade Instructions HP Part Number: AM275-9001A Published: July 2012 Edition: 3 Copyright 2009, 2012 Hewlett-Packard Development Company,

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

Installation instructions for Series NRX INCOM communications adapter module

Installation instructions for Series NRX INCOM communications adapter module 4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply

More information

SBM Control & Transfer Switch Rotary switches for circuit breaker control, motor control or instrument transfer. Features and Benefits Applications

SBM Control & Transfer Switch Rotary switches for circuit breaker control, motor control or instrument transfer. Features and Benefits Applications SBM Control & Transfer Switch Rotary switches for circuit breaker control, motor control or instrument transfer. Features and Benefits Compact design Up to 10 stages (20 contacts) Double surface cams (one

More information

COMMERCIAL GAS DRYER

COMMERCIAL GAS DRYER COMMERCIAL GAS DRYER MODELS CGM2751TQ0 (WHITE) CGM2751TQ1 (WHITE) 5 12 Litho in U.S.A. (CMS) (psw) c 2012 WHIRLPOOL CORPORATION Part No. W10119631 Rev. C TOP AND CONSOLE PARTS W10119631 2 TOP AND CONSOLE

More information

46431x92A Garden Tractor (1998) Page 1 of 16 Body Chassis

46431x92A Garden Tractor (1998) Page 1 of 16 Body Chassis 46431x92A Garden Tractor (1998) Page 1 of 16 Body Chassis 46431x92A Garden Tractor (1998) Page 2 of 16 Body Chassis 1 092546E701 Bracket, Seat 2 091963 Z Plate Assembly, Switch 3 164X26 Spring, Compression

More information

EATON I.L. 29C615E. 4.3 Short Delay/lnstantaneous Trip... 7 4.4 Ground Fault Protection... 7 5.0 Protection Settings... 7

EATON I.L. 29C615E. 4.3 Short Delay/lnstantaneous Trip... 7 4.4 Ground Fault Protection... 7 5.0 Protection Settings... 7 IL 29C615E Instructions for the Digitrip RMS 310 3-Pole and 4-Pole Trip Unit Installation and Operation with L-Frame and MDL-Frame Series C Circuit Breakers Table of Contents Description Page 1 O General

More information

Part Name/Description Part Number Quantity. Power Cable 4000950-5 1

Part Name/Description Part Number Quantity. Power Cable 4000950-5 1 Note: Indented items indicate parts included in an assembly listed above Part Name/Description Part Number Quantity Power Cable 4000950-5 1 Raven Harness Adapter Kit 4100525 1 Installation Instructions

More information

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen

More information

Molded case circuit breakers

Molded case circuit breakers Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product technology. Never before has the industry seen such high

More information

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Class 6065 Instruction Bulletin 6065-13 11/2011 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully and look

More information

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com

More information

Installation. Smart-UPS VT and MGE Galaxy 3500. Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V

Installation. Smart-UPS VT and MGE Galaxy 3500. Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V Installation Smart-UPS VT and MGE Galaxy 3500 Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V Contents Safety... 1 SAVE THESE INSTRUCTIONS...............................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

AP/UP, AP/MIL Series. Magnetic Circuit Protectors

AP/UP, AP/MIL Series. Magnetic Circuit Protectors AP/UP, AP/MIL Series Magnetic Circuit Protectors Introduction Poles Configurations Operating Characteristics Delay Curves Specifications Decision Tables 71 72 75 76 77 78 79 AP/UP, AP/MIL Series Hydraulic

More information

Emax UL Listed ABB SACE. Installation, service and maintenance instructions for low voltage air power circuit breakers

Emax UL Listed ABB SACE. Installation, service and maintenance instructions for low voltage air power circuit breakers Installation and service instructions Installation, service and maintenance instructions for low voltage air power circuit breakers Listed ABB SACE Dis. App. Uff. Resp. Uff. Utilizz. Title Installation,

More information

Sentron Series Circuit Breakers

Sentron Series Circuit Breakers Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of

More information

DEH 40368 Instructions. PowerVac Vacuum Circuit Breaker with ML-20 Mechanism

DEH 40368 Instructions. PowerVac Vacuum Circuit Breaker with ML-20 Mechanism g DEH 40368 Instructions PowerVac Vacuum Circuit Breaker with ML-20 Mechanism PowerVac Vacuum Circuit Breaker with ML-20 Mechanism Table of Contents Description Page Description Page SECTION 1 Introduction...

More information

Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear

Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear Class 6055 Instruction Bulletin 6055-62 06/2012 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully

More information

GROENEVELD AUTOMATIC GREASING SYSTEMS

GROENEVELD AUTOMATIC GREASING SYSTEMS GROENEVELD AUTOMATIC GREASING SYSTEMS TWIN Parts & Accessories Book Pumps, Fittings, Injectors, Lining, etc. www.groeneveld-group.com 1 TWIN ELECTRICAL Item Part # Description 1 F113966 Switch 24V 2 F122991

More information

3AH5 Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG 11.05 2010

3AH5 Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG 11.05 2010 Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.05 2010 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.05 2010 Contents Contents Page 3AH5 Vacuum Circuit-Breakers Medium-Voltage

More information

TS93 EMR T/PT/TDE. Surface applied door closer

TS93 EMR T/PT/TDE. Surface applied door closer TS EMR T/PT/TDE Surface applied door closer Installation instructions: Pull side track mount door closer with smoke detector (EMR T) Push side track mount door closer with smoke detector (EMR PT) Double

More information

Installation Guide for the TJ LCG PRO Suspension System (Low Center of Gravity) Available 4 or 5

Installation Guide for the TJ LCG PRO Suspension System (Low Center of Gravity) Available 4 or 5 INSTALLATION GUIDE Installation Guide for the TJ LCG PRO Suspension System (Low Center of Gravity) Available 4 or 5 Take every precaution to make this installation a safe procedure. Make safety the number

More information

Electro-Pneumatic Bus Door Control Mechanism

Electro-Pneumatic Bus Door Control Mechanism Electro-Pneumatic Bus Door Control Mechanism Application and Feature 1. Pneumatic Door Mechanism actuates the open/close movements of bus door through two double acting cylinders and two linkages with

More information