1 TIPS OF THE TRADE There s money to be saved. C opperclad ground rods cost too much. Changing to galvanized steel can take up to 58 percent out of ground rod cost. Based on 1995 average prices, a 5 / 8 -inch 8- foot-long copperclad ground rod cost $6.25. Galvanized cost for the same size was $3.94 for a savings of $2.31 per rod. Calculate the savings over a utility s annual ground rod usage and the savings are substantial. There is little difference in electrical resistance between galvanized and copperclad rods; and, in any event, the resistance of the ground rod is negligible when compared to the resistance of the earth itself. Also, use of copperclad rods requires special care to prevent galvanic action and rapid corrosion of anchor rods, anchors, piles, and associated hardware. These are the major conclusions which may be drawn from a recent comparison study of galvanized-steel ground rods and copperclad-steel ground rods. Resistance Study Observation of a ground rod system shows that its resistance to the earth may be considered to have three components. 1. The resistance of the ground rod itself Ground rods are adequate in cross-section so their resistance is a negligible part of the total resistance of the ground rod system. The resistance of a 5 / 8 -inch mild-steel ground rod 8-foot-long is ohms, as calculated from the resistivity of mild steel. 1 1
2 2. The interface resistance between ground rod and earth Study by the National Bureau of Standards has shown that for a ground rod free of grease or paint, the contact resistance between the ground rod and earth is negligible Resistance of earth around ground rod The resistance of the earth around a single ground rod is commonly calculated from the following equation developed by H. B. Dwight. 3 ρ R = 2 π L [ ln ( 4 L a ) -1 ] Where ρ = Average soil resistivity - (ohms-cm) L = Ground Rod Length - (cm) a = Ground Rod Radius - (cm) R = Resistance of Ground Rod to Earth - (ohms) Figure 1 shows the earth resistance for a 5 / 8 - inch-diameter ground rod (8-foot and 16-foot lengths) in soils of various resistivities as calculated by the earth resistance formula. Note that the resistances are high as compared to the resistance of the ground rod itself. In fact, the earth resistance is 600 to more than 10,000 times the resistance of the ground rod itself. Corrosion of Ground Rods The earth s resistance is by far the major component of resistance in a grounding system. So, from an electrical standpoint, galvanized and copperclad rods are nearly identical. However, an installed ground rod should resist corrosion well enough to provide a sufficient metallic cross section throughout its anticipated life. The National Association of Corrosion Engineers conducted a seven-year study of grounding materials at 20 test sites across the nation. (4) The ground rods were examined at 1, 3, and 7 year intervals. The study was conducted both on individual ground rods and on various materials coupled to each other. The data on single copperclad rods, single galvanized rods, single CONTINUED, NEXT PAGE 2
3 bare-steel rods, and galvanized rods bonded to copperclad rods are shown in Figure 2, which compares ground rod weight loss per year for the various materials. Figure 2 shows, as expected, that the copperclad ground rod (A) has better corrosion resistance than the galvanized (B) or bare-steel ground rods (C). The graph also shows that when a galvanized rod is coupled to a copperclad rod (D), as would be the case with a copperclad ground rod and a galvanized anchor rod in a bonded system, a galvanized rod (D) corrodes at a rate of 10 times faster than would be the case if a galvanized ground rod (B) were used. This is one reason Rural Utility Services (RUS formerly REA) suggests the use of galvanized steel for grounding. To quote RUS: A B C D Corrosion Weight Loss (Grams Per Year) Copperclad Ground Rod Galvanized Steel Ground Rod Bare Steel Ground Rod Galvanized Ground Rod Coupled to Copperclad Ground Rod Average corrosion weight loss for 7-year period at 20 sites across the nation. Data from N.A.C.E. driven ground rod year test program Figure 2 Galvanized steel materials are suggested for grounding of all distribution lines, above ground and underground. This is a continuation of practices that have been recommended by RUS since the early 1960s for pole lines and, more recently, for underground construction. (5) The average corrosion rate of 5.6 grams per year of the galvanized ground rod shown in Figure 2 can be shown to represent approximately 15 years of service before the galvanizing is gone. This assumes average coating of 2.26 oz/ft 2 of galvanizing. Chance production SPC records on 5 / 8 - inch ground rods show an average coating of 2.26 oz/ft 2. When the galvanizing is gone, a bare steel rod corrodes at an average rate of 15 grams per year as shown in Figure 2. Assuming this rate for the balance of nominal 30-year service life, or 15 years (30-15=15), the diameter of the ground rod will be reduced by approximately inch. CONTINUED, NEXT PAGE 3
4 Of course, this diameter decrease will cause the ground rod resistance to increase; but as seen below, the increase is negligible. Resistance of 5 / 8 -inch ground rod reduced.019" in dia. = ohms. Original resistance 5 / 8 " ground rod = ohms. Resistance increase = ohms. This corresponds to a resistance increase of 6.4 percent. The resistance increase is obviously quite small when compared to the resistance of the earth as shown in Figure 1 (previous page) (0.01 percent to percent of the resistance of the earth). How to Install Ground Rods Ground rods should be installed near the ground wire and the base of the pole. The rod must be driven to its full length into the ground and, after driven in place must have a resistance less than 25 ohms (National Electric Safety Code Rule 96.8). If the resistance is greater than 25 ohms, an additional ground rod must be used in parallel. The ground wire must be wrapped around the mounting hardware bolt and the mounting hardware tightened firmly to assure a continuing bond. By using Chance galvanized ground rods, you can save money at no sacrifice of performance. Chance has a complete family of rods and the necessary clamps. Talk to your representative and cut your costs. References: (1) Resistivity of mild steel from page 15-6 of Marks Handbook 8th Edition. (2) Grounding Connections for Electrical Systems, O.S. Peters, U.S. Dept. of Commerce, National Bureau of Standards, Technological Paper 108, June (3) Calculation of Resistance to Ground, H.B. Dwight, Electrical Engineering, Vol. 55, December (4) Driven Ground Rod Year Test Program, Final Report, Draft No. 2 September 1971, National Association of Corrosion Engineers. (5) Manual on Underground Corrosion Control in Rural Electric Systems, REA Bulletin , October 1977, Part IV, page 18. 4
5 UNITED STATES HUBBELL POWER SYSTEMS, INC. 210 N. Allen Centralia, Mo Phone: Fax: CANADA HUBBELL CANADA, INC. 870 Brock Road South Pickering, Ontario L1W 1Z8 Phone: Fax: MEXICO HUBBELL DE MEXICO, S.A. DE. CV Av. Coyoacan No Col. Del Valle Mexico, D.F. Phone: Fax: ASIA HUBBELL S.E. ASIA PTE. LTD. 159 Sin Ming Road #05-08 Amtech Building Singapore Phone: Fax: EUROPE HUBBELL POWER SYSTEMS Ronald Close Woburn Road Industrial Estate Kempston, Bedford MK42 7SH, England Phone: Fax: TAIWAN HUBBELL TAIAN CO., LTD. 12th Floor 66 Sec. 2 Chien Kwo North Road Taipei, Taiwan Phone Fax: Fax: skao@hubbell-taian.com.tw Hubbell Power Systems, Inc. ANDERSON POWER SYSTEMS, INC Fax NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. Copyright 2000 Hubbell 210 North Allen Street Centralia, MO & TiPS NEWS View from Vol 3 No 2 April WB 5
CATHODIC PROTECTION SYSTEM DESIGN
CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of
More informationEZ-48-3AB-125-35 Weather Station Mounting Tripod and Mast
EZ-48-3AB-125-35 Weather Station Mounting Tripod and Mast EZ-125-35M 35 Mast Extension (Optional) EZ-125-SK Stake Kit (Optional) EZ-46-3 Tar Pad Kit (Optional) EZ-GWA Guy Wire Kit (Optional) Ambient Weather
More informationA Solid Foundation Solution for Homeowners. from. Our products are made with 90% Recycled Material Down. Right. Solid. GREEN.
A Solid Foundation Solution for Homeowners from Our products are made with 90% Recycled Material Down. Right. Solid. GREEN. Stop the damaging effects of foundation settling... Sinking foundations, cracked
More informationSpecifications for Lightning Protection. ASAE Engineering Practice
Chapter 8: Lightning Specifications for Lightning Protection ASAE safety standards are not laws. They are recommended voluntary standards used by designers, engineers, manufacturers and users of the equipment,
More informationLEGACY REPORT ER-5110. www.icc-es.org. ICC Evaluation Service, Inc. Reissued November 1, 2003. Legacy report on the 1997 Uniform Building Code
LEGACY REPORT Reissued November 1, 2003 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900
More informationTransmission Foundations Case History : Helical piles Hydro One Networks Inc.
Transmission Foundations Case History : Helical piles Hydro One Networks Inc. www.hubbellpowersystems.com Late in 2008, an aerial patrol discovered three 500kV towers with partially-collapsed foundations
More informationNEGRP TEST SUMMARY. Joseph A. Lanzoni, November 2005
NEGRP TEST SUMMARY Joseph A. Lanzoni, November 2005 The National Electrical Grounding Research Project (NEGRP) was a project managed and sponsored by the National Fire Protection Association (NFPA) Research
More informationChapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
More informationUnderstanding Soil Resistivity Testing
Technical Hotline: (00) -9 Technical Hotline: (00) -9 www.aemc.com www.aemc.com Understanding Testing Effects of on Ground Electrode Resistance Factors Affecting APPLICATION NOTES JULY rev.0 Understanding
More informationSTREETLIGHT SYSTEM GROUNDING AND BONDING
Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial
More informationPOLE MOUNT SYSTEM-3 INSTALLATION
1 May 2014 POLE MOUNT SYSTEM-3 INSTALLATION The Pole Mount System-3 is an easy to install and flexible system designed to allow ONE SYSTEMS loudspeaker products to be mounted to pole structures. The only
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationLightning Protection Introduction
Lightning Protection Introduction Structural lightning protection design considerations BS 6651 (Protection of structures against lightning) clearly advises strict adherence to the provision of a conventional
More information12 Appendix 12 Earth Electrodes And Earth Electrode
12 Appendix 12 Earth Electrodes And Earth Electrode Testing 12.1 Introduction This appendix provides guidance and background information an earth electrode testing and some limited information on earth
More informationINSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS
INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS GENERAL DESCRIPTION:
More informationATLAS RESISTANCE Pier Foundation Systems
ATLAS RESISTANCE Pier Foundation Systems Foundation Repair Systems for Civil Construction Applications: Residential, Commercial, Industrial Atlas Resistance Piers have been used to restore and/or stabilize
More informationNew construction Repairing failed or old foundations Retrofit foundations Permanent battered piers Machinery/equipment foundations
from New construction foundations don t have to be a headache. The CHANCE Helical Pier Foundation System gives you the performance of concrete without the drawbacks and liabilities of driven piles and
More informationTS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
More informationNew and Improved Protective Grounding-Set Tester
Instructions for the preparation and use of New and Improved Protective Grounding-Set Tester Catalog No. C403-3220 U.S. Patent 5,811,979! WARNING Select actual work-site values for system-fault current,
More informationGUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
More informationCONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION
Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED
More informationInstallation Instructions Hustler 6-BTV Trap Vertical
Installation Instructions Hustler 6-BTV Trap Vertical ASSEMBLY 1. Check the package contents against the parts list on page 2. 2. WARNING. Installation of this product near power lines is dangerous. For
More informationNewson Gale. Is it ever Safe to use Plastic Drums and Containers in Hazardous areas? White Paper. Author Details:
White Paper Is it ever Safe to use Plastic Drums Author Details: Mike O Brien, Head of Product Marketing for If you have any questions relating to the topics discussed in this article, you can contact
More informationAssessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria
Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria Abstract Gabriel A. Adegboyega and Kehinde O. Odeyemi Department of Electrical and Electronic
More informationEstimating AC Mitigation Requirements for Pipelines Installed in High Voltage AC Corridors: Fault Conditions
Estimating AC Mitigation Requirements for Pipelines Installed in High Voltage AC Corridors: Fault Conditions R. D. Southey, Eng. W. Ruan, Ph.D. F. P. Dawalibi, Eng., Ph.D. S. Fortin, Ph.D. Safe Engineering
More informationCable Trays Technical Instructions & Specifications
Cable Trays Technical Instructions & Specifications Products Catalogue Objective and Structure The company s main objective is the supply of quality products, with respect to: practical design increased
More informationCombined Close Interval Potential Surveys and Direct Current Voltage Surveys for Increased Pipeline Integrity
Combined Close Interval Potential Surveys and Direct Current Voltage Surveys for Increased Pipeline Integrity John Peter Nicholson NACE Accredited Senior Corrosion Technologist Managing Director Cathodic
More informationStrength and Durability for Life CORROSION CONTROL. The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines
Strength and Durability for Life CORROSION CONTROL The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines Last Revised: May 2016 Sharing of rights-of-way by AC power lines and buried
More informationThis mount uses concrete parking bumpers and a Davis tripod to create a mounting solution for nonpenetrable
NON-PENETRATING FLAT ROOF MOUNT Application Note 18 For Any Davis Weather Station Installed on a Mounting Tripod Introduction This application note describes various mounting solutions for non-penetrable
More informationDock Hardware & Accessory Products Catalog
Dock Hardware & Accessory Products Catalog Product Page # Product Page # Angle Brackets/Clips 8 Back Up Plate 5 Backing Plate/Hurricane Stop 10 Carriage Bolt Sets 4 Chain Retainer 10 Connector Pin Set
More information7.4A/7.4B STUDENT ACTIVITY #1
7.4A/7.4B STUDENT ACTIVITY #1 Write a formula that could be used to find the radius of a circle, r, given the circumference of the circle, C. The formula in the Grade 7 Mathematics Chart that relates the
More informationHilti, Inc. 5400 South 122 nd East Avenue Tulsa, OK 74146. 1-800-879-8000 www.hilti.com
Attached are page(s) from the 2014 Hilti North American Product Tech Guide. For complete details on this product, including data development, product specifications, general suitability, installation,
More informationThe Stabilizer TM. Benefits. www.griptite.com. Supplemental support system for sagging beams and floor joists within a crawl space
The Stabilizer TM Supplemental support system for sagging beams and floor joists within a crawl space Pre-drilled holes in steel plate allow for connection to beam or floor joists. Benefits Levels and
More informationEARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
More informationCABLE TRENCH INSTALLATION GUIDE
1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL INFORMATION 4.0 PLANNING INFORMATION 5.0 CREW INFORMATION 6.0 CONTRACTOR INFORMATION 7.0 PRECASTED/ POURED-IN-PLACE TRENCH DRAWINGS 2.0 PURPOSE This standard
More informationPaper Reference. Edexcel GCSE Mathematics (Linear) 1380 Paper 3 (Non-Calculator) Monday 6 June 2011 Afternoon Time: 1 hour 45 minutes
Centre No. Candidate No. Paper Reference 1 3 8 0 3 H Paper Reference(s) 1380/3H Edexcel GCSE Mathematics (Linear) 1380 Paper 3 (Non-Calculator) Higher Tier Monday 6 June 2011 Afternoon Time: 1 hour 45
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More informationEARTHING SYSTEM CALCULATION
BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references
More informationTypical values for a Kapton Polyimide tape wrapped sample, according to NEMA Specifications
DACRON DACRON GLASS FIBER COVERED MAGNET WIRE CLASS 200 INSULATION DACRON Glass Fiber-covered Magnet Wire is manufactured by serving a combination of glass and Dacron fibers over a bare or film-coated
More informationNEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps
NEW SERVICE INSTALLATION STEPS Here is the step-by-step process required to fulfill your service installation request. Please take a few minutes to review the steps, become familiar with key milestones
More informationSECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
More informationI = V/r P = VI. I = P/V = 100 W / 6 V = 16.66 amps. What would happen if you use a 12-volt battery and a 12-volt light bulb to get 100 watts of power?
Volts, Amps and Ohms Measuring Electricity The three most basic units in electricity are voltage (V), current (I) and resistance (r). Voltage is measured in volts, current is measured in amps and resistance
More informationWisconsin Building Products Evaluation
Safety & Buildings Division 201 West Washington Avenue P.O. Box 2658 Madison, WI 53701-2658 Evaluation # 200813-O Wisconsin Building Products Evaluation Material Best Management Standards for Foundation
More informationSOIL RESISTIVITY MEASUREMENTS
SOIL RESISTIVITY MEASUREMENTS APPENDIX B B Soil resistivity directly affects the design of a grounding (earthing) electrode system and is the prime factor that determines the resistance to earth of a grounding
More informationSeries 90 Portable Capstan Hoist. Owners Manual ! CAUTION
Series 90 Portable Capstan Hoist Owners Manual! CAUTION The equipment covered in this document should be installed, used, and serviced only by competent personnel familiar with and following good work
More informationTECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR
TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before
More informationTransmission Foundations. helical piles and guy anchors for transmission structures. www.hubbellpowersystems.com
Transmission Foundations helical piles and guy anchors for transmission structures www.hubbellpowersystems.com Grid locked on your transmission job? Instant Foundation helical piles go places concrete
More informationSystem. Stability. Security. Integrity. 150 Helical Anchor
Model 150 HELICAL ANCHOR System PN #MBHAT Stability. Security. Integrity. 150 Helical Anchor System About Foundation Supportworks is a network of the most experienced and knowledgeable foundation repair
More informationStrengthening of Large Storage Tank Foundation Walls in an Aggressive Environment by External Post-tensioning. May 7th 2013: Dominique Deschamps
Strengthening of Large Storage Tank Foundation Walls in an Aggressive Environment by External Post-tensioning May 7th 2013: Dominique Deschamps Scope of the paper Presentation of the project Cause of cracks
More informationSteel Pole & Tower Assessment & Remediation Turnkey Solutions for Aging Steel Infrastructure
Steel Pole & Tower Assessment & Remediation Turnkey Solutions for Aging Steel Infrastructure Understanding and Addressing the Risks of Aging Steel T&D Assets Once thought to be permanent structures free
More informationEmbedded Parts Introduction - Anchors
In the plant construction or process plants such as chemical, petrochemical, gas or power plants various disciplines are brought into contact and built on each other. Civil, mechanical, electro technical
More informationOVERALL CONVEYOR WIDTH STEEL ALUMINUM MODEL # PER FT. 10 FT. 5 FT. PER FT. 10 FT. 5 FT. PER FT. 10 FT. 5 FT. PER FT. 10 FT. 5 FT.
Pick Smarter. Pick Better. Pick UNEX. Skatewheel (SW) Skatewheel Gravity Conveyor is ideally suited to convey lightweight packages and where operations require portable or temporary conveyor lines such
More informationActivity 2.3b Engineering Problem Solving Answer Key
Activity.3b Engineering roblem Solving Answer Key 1. A force of 00 lbs pushes against a rectangular plate that is 1 ft. by ft. Determine the lb lb pressure in and that the plate exerts on the ground due
More informationMETHOD STATEMENT HIGH STRIAN DYNAMIC TESTING OF PILE. Prepared by
METHOD STATEMENT HIGH STRIAN DYNAMIC TESTING OF PILE Prepared by Infratech ASTM CO., LTD. Contents Chapter Description Page Contents...... 1 List of Appendix. 1 1. Introduction.. 2 2. Test Method..2 3.
More informationFigure A-1. Figure A-2. continued on next page... HPM-1. Grout Reservoir. Neat Cement Grout (Very Flowable) Extension Displacement Plate
Addendum HELICAL PULLDOWN Micropile (HPM) Introduction The HPM is a system for constructing a grout column around the shaft of a standard Helical Screw Foundation (see Figure A1). To begin the process,
More informationDuPont Freon REFRIGERANTS
DuPont Freon REFRIGERANTS Technical Information T-12 SI Thermodynamic Properties of DuPont Freon 12 (R-12) Refrigerant Thermodynamic Properties of DuPont Freon 12 (R12) SI Units Tables of the thermodynamic
More informationFlamco Stainless steel mountings
S TA I N L E S S S T E E L M O U N T I N G S 9 Flamco Stainless steel mountings BRS-A BSF - SS RAIL R - SS GP - SS Edition 2007 / UK Stainless steel mountings Flamco offers the best attachment options
More informationMany Styles and Custom Options
Many Styles and Custom Options Livestock Equipment Available Nationally! www.aopv.com Feeds Supplies Business: (937) 964-7133 Mobile: (937) 631-3649 FAX: (937) 964-7134 St. Paris, Ohio Fair or Show Pens,
More informationGENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
More informationPOLE MOUNT SYSTEM EX-3 INSTALLATION
May 2014 POLE MOUNT SYSTEM EX-3 INSTALLATION The Pole Mount System EX-3 is an easy to install and flexible system designed to allow ONE SYSTEMS loudspeaker systems to be mounted to pole structures. The
More informationSession 14 Cable Support Systems
Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load
More informationNorth American Stainless Long Products
North American Stainless Long Products 1 North American Stainless North American Stainless is part of the most competitive stainless steel manufacturing group in the world, Acerinox, S.A. The development
More informationA99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
More informationCable Installation Accessories. Cable Hoisting and Attachment. Snap-In Hangers. SnapStak Hangers
SnapStak Hangers New design increases stack height SnapStak hangers have become the industry standard for maximizing space utilization on crowded towers and now that utility is further expanded with the
More informationWire rope slings, the hazards surrounding
Recommended loads for wire rope slings Wire rope slings, the hazards surrounding their use, and safety measures or alternatives to avoid injury will be covered in this data sheet. 2. Wire rope made from
More informationScepter PVC Molded Junction Boxes
Scepter PVC Molded Junction Boxes ELECTRICAL SYSTEMS PVC MOLDED JUNCTION BOXES 4" to 12" We build tough products for tough environments Standing Still is Not an Option. We re proud to introduce the NEW
More informationInstallation Guide. WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers. February, 2011
WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers Installation Guide February, 2011 Pace Scientific Inc www.pace-sci.com Tel: 704-799-0688 sales@pace-sci.com 1 Disclaimer The following warranty
More informationCLICKBOND FASTENER OVERVIEW:
Infastech Pty Ltd A.B.N. 98 000 482 986 A.C.N. 000 482 986 891 Wellington Road, Rowville, Victoria, 3178 Telephone: (03) 9765 6400 Fax (03) 9765 6444 CLICKBOND FASTENER OVERVIEW: The CLICKBOND fastening
More informationTYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE
TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE A. GENERAL NOTES: Service entrance line and load conductors, conduit straps, weatherhead, lock nuts, bushings, connectors, and
More informationDesigning For A Low Resistance Earth Interface (Grounding) Roy B. Carpenter, Jr. Joseph A. Lanzoni
Designing For A Low Resistance Earth Interface (Grounding) Roy B. Carpenter, Jr. Joseph A. Lanzoni An LEC Publication Revised 2007 TM DESIGNING FOR A LOW RESISTANCE EARTH INTERFACE (GROUNDING) Roy B. Carpenter,
More informationAcceleration due to Gravity
Acceleration due to Gravity 1 Object To determine the acceleration due to gravity by different methods. 2 Apparatus Balance, ball bearing, clamps, electric timers, meter stick, paper strips, precision
More informationSECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationPTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE
FORM A PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE The following suggested specifications are written as a guide to assist the specifier in writing his own specifications. Specific circumstances
More informationReport on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars
Report on Wind Resistance of Signs supported by Glass Fiber Reinforced Concrete (GFRC) Pillars Prepared for US Sign and Fabrication Corporation January, 2006 SUMMARY This study found the attachment of
More informationHOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
More informationOpen Channel Diffusers
Open Channel Diffusers Application Information: Open channel diffusers are used to increase mixing and absorbance efficiency of a chemical solution into the process water. Specifically designed penetrations
More informationNORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS
SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications
More informationSECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
More informationwww.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
More informationM2 Antenna Systems, Inc. Model No: KT34M2
M2 Antenna Systems, Inc. Model No: KT34M2 10m f, MHz G, dbi F/B, db 28.0 7.3 18 28.2 7.3 23 28.4 7.4 25 28.6 7.5 24 29.2 7.6 20 15m f, MHz G, dbi F/B, db 21.0 6.9 19 21.1 6.9 22 21.2 7.0 24 21.3 7.0 24
More informationWelding Reel ERA 4000 Service Manual
AERO-MOTIVE COMPANY A Woodhead Industries, Inc. Subsidiary Welding Reel ERA 4000 Service Manual IMPORTANT SAFETY INSTRUCTIONS Please read this manual carefully and follow its instructions. Improper use
More informationMS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water
MS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water 105 Decker Court, Suite 825, Irving, TX 75062 P: 469-499-1044 F: 469-499-1063 www.plasticpipe.org HDPE
More informationMETHOD OF STATEMENT FOR STATIC LOADING TEST
Compression Test, METHOD OF STATEMENT FOR STATIC LOADING TEST Tension Test and Lateral Test According to the American Standards ASTM D1143 07, ASTM D3689 07, ASTM D3966 07 and Euro Codes EC7 Table of Contents
More informationSteel Grounding Design Guide and Application Notes
Steel Grounding Design Guide and Application Notes P.K. Sen, Ph.D., P.E. Colorado School of Mines Golden, Colorado 80401 psen@mines.edu Keith Malmedal, P.E. NEI Electric Power Eng., Inc. Arvada, Colorado
More informationInternational Greenhouse Company
Greenhouse Foundation Design As with any building, a good solid foundation is crucial for the long term durability and functionality of your greenhouse. A weak foundation will cause your greenhouse to
More informationSolahart BLACK CHROME XII SOLAR WATER HEATER OWNER S MANUAL SUPPLEMENT. and WARRANTY INFORMATION MODELS 151, 181, 182, 221, 222, 302, 303, 443.
Solahart BLACK CHROME XII SOLAR WATER HEATER OWNER S MANUAL SUPPLEMENT and WARRANTY INFORMATION MODELS 151, 181, 182, 221, 222, 302, 303, 443. FOR SERVICE PLEASE CALL (08) 93514600 Solahart Industries
More informationEvaluation Report CCMC 13102-R Pieux Vissés Vistech / Postech Screw Piles
Evaluation Report CCMC 13102-R Pieux Vissés Vistech / Postech Screw Piles 1. Opinion 1of 6 MASTERFORMAT: 31 62 16.01 Evaluation issued: 2003-02-13 Re-evaluated: 2015-03-13 Re-evaluation due: 2018-02-13
More informationElectrical Service Guidelines
Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4
More informationWind Direction Smart Sensor (S-WDA-M003)
(S-WDA-M003) The Wind Direction smart sensor is designed to work with HOBO Stations. The smart sensor has a plug-in modular connector that allows it to be added easily to a HOBO Station. All sensor parameters
More informationLiftAlloy Chain Slings
CHAIN SLING BASICS Slings Lift-All chain slings meet or exceed all OSHA, ASME B30.9 and NACM standards and regulations. chain slings, available in 80 for 7/32" and 7/8"- /4" and 00 for 9/32"-3/4", are
More informationGuidelines for Earthquake Bracing Residential Water Heaters
Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the
More informationCALIBRATION OF A THERMISTOR THERMOMETER (version = fall 2001)
CALIBRATION OF A THERMISTOR THERMOMETER (version = fall 2001) I. Introduction Calibration experiments or procedures are fairly common in laboratory work which involves any type of instrumentation. Calibration
More informationLes Produits MURPHCO Ltée
DESCRIPTION The Murphco support clamp is an assembly made entirely of stainless steel and conceived for all sleeved roof drains. The Murphco Support Clamp is compatible with all types of Murphco* copper
More informationGrounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
More informationPole Guying More Complicated Than Meets the Eye. NRECA TechAdvantage 2014 Presented by Jason Settle, P.E. jason.settle@gdsassociates.
Pole Guying More Complicated Than Meets the Eye NRECA TechAdvantage 2014 Presented by Jason Settle, P.E. jason.settle@gdsassociates.com Pole Guying Strength of components NESC vs. RUS Guy Factor Grounding
More informationTransmission Silicone Insulators Line Post 69 kv to 161 kv
K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 161 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines
More informationJune 2007 CHAPTER 7 - CULVERTS 7.0 CHAPTER 7 - CULVERTS 7.1 GENERAL
7.0 7.1 GENERAL For the purpose of this manual, culverts are defined as structures that are completely surrounded by soil and located below the surface of the roadway parallel to the general direction
More informationModeling of Transmission Lines
Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward
More informationPuddle Flange. FRANK Puddle Flange
Puddle Flange FRANK Puddle Flange The problem Problems keep on occurring when connecting pipes during construction work. Pipes laid in the ground must be introduced into concrete walls or shafts. In many
More informationOhm's Law and Circuits
2. Conductance, Insulators and Resistance A. A conductor in electricity is a material that allows electrons to flow through it easily. Metals, in general, are good conductors. Why? The property of conductance
More information