ULTREX. PVC/Nylon and XLPE Insulated Tray Cables
|
|
- Sophia Clark
- 7 years ago
- Views:
Transcription
1 ULTREX PVC/Nylon and XLPE Insulated Tray Cables
2 ULTREX Tray Cables UL Type TC, 600 Volt Power and Control Cables Introduction ULTREX PVC/Nylon Insulated, PVC Jacketed Applications and Description AWG Unshielded AWG Shielded AWG Unshielded AWG Shielded AWG Unshielded AWG Shielded AWG Unshielded AWG Shielded AWG Unshielded AWG Shielded Conductors with Ground Conductors with Ground Dupont Construction Dupont Composite Construction Dow Composite Construction Composite Cables ULTREX XL - XLTC XLP Insulated, PVC Jacketed Applications and Description AWG Unshielded AWG Unshielded AWG Unshielded Conductors with Ground Conductors with Ground Conductor or Phase Identification Notices
3 Introduction Nexans brings energy to life through an extensive range of cables and cabling solutions that deliver impeccable performance for our customers worldwide. With more than a century of experience in cable manufacturing, you can rely on the quality of Nexans products. Our teams are committed to a partnership approach that supports customers in four main business areas: Power transmission and distribution (Submarine and Land), Energy resources (Oil & Gas, Mining and Renewables), Transportation (Road, Rail, Air, Sea) and Building (Commercial, Residential, Industrial and Data Centers). Nexans strategy is founded on continuous innovation in products, solutions and services, employee development, customer training and the introduction of safe, low-environmental-impact industrial processes. In 2013, Nexans became the first cable manufacturer to create a Foundation to introduce sustained initiatives for access to energy for disadvantaged communities worldwide. This catalog has been prepared for the convenience of those using electrical conductors in industrial applications. The information included in the many tabulations will be of particular value to the architect, engineer, electrician, and layperson alike. For your convenience, we have referenced applicable Articles and Tables from the NEC. All the cables in this catalog are LEAD FREE. This indicates that the Nexans cable components have less than 300 ppm of lead, which is well below the 1000 ppm level indicated in RoHS (restriction of hazardous substances) regulations and below the level requiring labeling by California Proposition #65. 2
4 ULTREX PVC/Nylon Type TC or TC-ER 600 Volt Power and Control Cable Temperature rating of 90 C dry / wet rated Applications Nexans 600 V ULTREX Tray Cables are listed as type TC or TC-ER under UL 1277 Electrical Power and Control Cables. These cables may be installed in wet or dry locations; in cable trays, raceways and open air; and are suitable for exposure to weather, direct burial and for Class I, Div. 2 (also Zone 2) and Class II, Div. 2 hazardous locations per NEC. Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Construction Conductor: bare, annealed copper conforming to ASTM B3 and Class B stranded in accordance to ASTM B8, from 18 AWG to 500 kcmil. Compressed copper for 14 AWG through 500 kcmil. Insulation: flame-retardant PVC/Nylon type THHN/THWN-2 per UL 83 for sizes 14 AWG to 500 kcmil and type TFN per UL 66 for 18 AWG and 16 AWG. Assembly : Non-shielded: cables with 3 or more conductors are cabled in concentric layers with interstices filled with suitable fillers, as required. Two-conductor cables are supplied in a flat/parallel configuration. Ground wires are sized as required by UL 1277 (refer to the applicable product tables for the standard sizes provided). Sizes 14 AWG to 6 AWG have an insulated green ground wire. Sizes 4 AWG and larger have a bare ground wire. Where necessary, a binder tape of synthetic material assembles the core in a tight circular configuration. Shielded: cabled in concentric layers with interstices filled with suitable fillers as required. A helically wrapped aluminum tape, with synthetic backing, gives 100% shielding. A tinned copper drain wire is placed in contact with the aluminum side of the tape, to lower the resistance and to assist in the termination of the shield. Jacket: UL listed sunlight and moisture resistant, black, flame retardant polyvinyl chloride (PVC) material meeting the requirements of. A Nylon ripcord is included for ease of jacket removal. Jacket surface is printed with required UL / NEC code information and sequential footage markings. Sample Print Legend: NEXANS-C ULTREX- 600V TC-ER 3/C-12AWG THHN/THWN-2 SUN RES DIR BUR (UL) ROHS MFG DATE Conductor Identification (See page 26 of this catalog) 18 AWG to 10 AWG: Color coded per Method #1-E2 per ICEA S AWG to 500 kcmil: black with number coding per Method 4 of ICEA S Composite Power: Black with number coding per Method 4 of ICEA S Control: Color coded per Method #1-E2 per ICEA S Specifications Meets : Power and Control Tray Cables with Optional Fiber Members. Meets UL 83: Thermoplastic-Insulated Wires and Cables for 14 AWG and larger. Meets UL 66: Fixture Wire for 18 AWG and 16 AWG. Meets ICEA S , NEMA Publication No. WC-70: Non-Shielded Power Cables rated 2000 volts or Less for the Distribution of Electrical Energy. Dupont constructions meet Dupont Engineering Specification SE33.4B: 600-Volt Multiconductor Type TC Cable; THWN- THHN or TFN Insulated and with Vinyl Jacket Product Features UL approved cables Type TC or TC-ER, 600 V. UL approved insulated conductors. Cables pass UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr. Cables are UL listed to IEEE 1202 and FT4 70,000 BTU/hr flame test. For use in power, lighting, control and signal circuits. Can be used within industrial establishments where serviced by qualified personnel and not subject to physical damage. Can operate at continuous temperatures of 90 C dry and wet. Cold bend of 25 C per. Can be used In Class I Division 2 and Class II Division 2 Hazardous Locations and Intrinsically Safe applications as permitted by NEC Articles 392, 501, 502, 503, and 505.* As indicated in : The overall jackets of these cables are a gas/vapor tight continuous sheath as discussed in NEC Article (D) & (E).* For use in cable trays, raceways, conduits, or for aerial applications where installed with a messenger. For Direct Burial applications. Cables of 2 or more conductors (plus a ground conductor) are UL listed for Exposed Run (ER) per NEC Article (7): 1) Cables sized from 18 AWG to 6 AWG have an insulated ground conductor. 2) Cables sized 4 AWG and larger have a bare ground conductor. As permitted in NEC Article 725 for Class 1 circuits. As permitted for non-power-limited alarm circuits as defined in NEC Article 760. Lead free and RoHS compliant Sunlight and moisture resistant Options The following constructions can be provided on special orders: Cables sized 4 AWG and larger with an insulated ground conductor Dow Construction DuPont Construction Composite Cable Construction Insulated or bare ground wires Different conductor methods * Use in hazardous locations: Please note that no investigation of these cables has been performed regarding the transmission of gases or vapors through the core. When these cables are used in hazardous locations they should be sealed properly as required by the NEC. 3
5 Unshielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 66 Multiconductor 18 AWG Type TFN Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps Flat x Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation pull-in. Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Article , and Table Allowable for Fixture Wires at an ambient temperature of 30 C (with no load diversity). for cables having more than three conductors have been derated as stated in NEC Article (A), using the derating factors of NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC Refer to NEC Article 240.4(D) for overcurrent protection requirements. 4
6 Shielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 66 Multiconductor 18 AWG Type TFN Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering Drain Wire: 20 AWG (7w) Tinned Copper Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during. installation pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Article , and Table Allowable for Fixture Wires at an ambient temperature of 30 C (with no load diversity). for cables having more than three conductors have been derated as stated in NEC Article (A), using the derating factors of NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC Refer to NEC Article 240.4(D) for overcurrent protection requirements. 5
7 Unshielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 66 Multiconductor 16 AWG Type TFN Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps Flat x Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Article , and Table Allowable for Fixture Wires at an ambient temperature of 30 C (with no load diversity). for cables having more than three conductors have been derated as stated in NEC Article (A), using the derating factors of NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC Refer to NEC Article 240.4(D) for overcurrent protection requirements. 6
8 Shielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 66 Multiconductor 16 AWG Type TFN Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering Drain Wire: 18 AWG (7w) Tinned Copper Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Article , and Table Allowable for Fixture Wires at an ambient temperature of 30 C (with no load diversity). for cables having more than three conductors have been derated as stated in NEC Article (A), using the derating factors of NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC Refer to NEC Article 240.4(D) for overcurrent protection requirements. 7
9 Unshielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 83 Multiconductor 14 AWG Type THHN/THWN-2 Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering Jacket Diameter over Approximate Net # of Thickness Jacket Cable Weight Number Conductors mils inches lb/kft amps Flat x /25.0 (1) Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG copper conducts after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). (1) Where the 4th conductor is the neutral of a balanced 3 phase system. 8
10 Shielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 83 Multiconductor 14 AWG Type THHN/THWN-2 Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering Drain Wire: 16 AWG (7w) Tinned Copper Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps /25.0 (1) Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). (1) Where the 4th conductor is the neutral of a balanced 3 phase system. 9
11 Unshielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 83 Multiconductor 12 AWG Type THHN/THWN-2 Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering Number Jacket Diameter over Approximate Net # of Thickness Jacket Cable Weight Conductors mils inches lb/kft amps Flat x /30.0 (1) Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). (1) Where the 4th conductor is the neutral of a balanced 3 phase system. 10
12 Shielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 83 Multiconductor 12 AWG Type THHN/THWN-2 Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering Drain Wire: 16 AWG (7w) Tinned Copper Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps /30.0 (1) Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). (1) Where the 4th conductor is the neutral of a balanced 3 phase system. 11
13 Unshielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 83 Multiconductor 10 AWG Type THHN/THWN-2 Insulation Thickness: 20 mils / 0.51 mm PVC, 4 mils / 0.10 mm Nylon Covering Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conduct ors mils inches lb/kft amps Flat x /40 (1) Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). (1) Where the 4th conductor is the neutral of a balanced 3 phase system. 12
14 Shielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 83 Multiconductor 10 AWG Type THHN/THWN-2 Insulation Thickness: 20 mils / 0.51 mm PVC, 4 mils / 0.10 mm Nylon Covering Drain Wire: 16 AWG (7w) Tinned Copper Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps /40 (1) Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). (1) Where the 4th conductor is the neutral of a balanced 3 phase system. 13
15 Unshielded Tray Cable UL Type TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 83 ICEA S Conductors Type THHN/THWN-2 with Ground Conductor Ground Insulation Thickness Jacket Diameter Approximate Net Size Size PVC/Nylon Thickness over Jacket Cable Weight Number AWG or kcmil AWG mils mils inches lb/kft amps / (1) / (1) / (1) / / * / * / / * 1/0 6 50/ /0 6 50/ /0 4 50/ /0 4 50/ / / / * DOW construction cables. Mininum Bending Radius: 5 x overall diameter installed Bend Radius : 7.5 x overall diameter during installation. pull-in Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC (1) NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). * DOW construction means: Control conductors are color coded E2 (See chart page 26) Power conductors are black with numbers M4 (See chart page 26) fillers where applicable 14
16 Unshielded Tray Cable UL Type TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 83 ICEA S Conductors Type THHN/THWN-2 with Ground Conductor Ground Insulation Thickness Jacket Diameter Approximate Net Size Size PVC/Nylon Thickness over Jacket Cable Weight Number AWG or kcmil AWG mils mils inches lb/kft amps amps (1) / / / / / /0 6 50/ * 2/0 6 50/ /0 4 50/ /0 4 50/ / * / * / * DOW construction cables Mininum Bending Radius : 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Notes: Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC (1) Where the 4th conductor is the neutral of a balanced 3 phase system. * DOW construction means: Control conductors are color coded E2 (See chart page 26) Power conductors are black with numbers M4 (See chart page 26) where applicable 15
17 Unshielded Tray Cable - DuPont Construction* UL Type TC or TC-ER, 600 V, 90 C dry / wet rated 16 ULTREX UL 83 ICEA S Dupont SE33.4B Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps (2) Multiconductor 14 AWG Type THHN/THWN-2 Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils /0.10 mm Nylon Covering x /25 (1) Multiconductor 12 AWG Type THHN/THWN-2 Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils /0.10 mm Nylon Covering x /30 (1) Multiconductor 10 AWG Type THHN/THWN-2 Insulation Thickness: 20 mils / 0.51 mm PVC, 4 mils / 0.10 mm Nylon Covering x /40 (1) Multiconductor 8 AWG Type THHN/THWN-2 Insulation Thickness: 30 mils /0.76 mm PVC, 5 mils /0.13 mm Nylon Covering (1) Multiconductor 6 AWG Type THHN/THWN-2 Insulation Thickness: 30 mils /0.76 mm PVC, 5 mils /0.13 mm Nylon Covering (1) Multiconductor 4 AWG Type THHN/THWN-2 Insulation Thickness: 40 mils / 1.02 mm PVC, 6 mils / 0.15 mm Nylon Covering (1) Multiconductor 2 AWG Type THHN/THWN-2 Insulation Thickness: 40 mils / 1.02 mm PVC, 6 mils /0.15 mm Nylon Covering (1)
18 Unshielded Tray Cable - DuPont Construction* - (continued) UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX UL 83 ICEA S Dupont SE33.4B Composite Conductors Type THHN/THWN-2 with Insulated Ground Composite - 4 Control Conductors with 3 Power Conductors and 1 Insulated Ground Insulation Insulation Diameter Approximate Control Power Ground Jacket Control Power Thickness Thickness Over Net Cable Size Size Size Thickness Number PVC/Nylon PVC/Nylon Jacket Weight AWG mils AWG mils AWG mils inches lb/kft amps amps Mininum Bending Radius : 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Notes for DuPont Constructions: Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). (1) Where the 4th conductor is the neutral of a balanced 3 phase system. (2) Conductor ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more. than three conductors have been derated per NEC Table (B)(3)(a). For correction factors for different ambient temperatures and ampacitities at different conductor temperature ratings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). *Dupont construction means: Conductor black insulation with white print numbered conductors (Method 4). See chart on page 26. Nylon where applicable Mylar tape around core 17
19 Unshielded Tray Cable - Dow Construction* UL Type TC -ER, 600 V, 90 C dry / wet rated ULTREX UL 83 ICEA S Composite Conductors Type THHN/THWN-2 with Ground Composite - 4 Control Conductors with 3 Power Conductors and 1 Ground Number Control Size Insulation Thickness PVC/Nylon Power Size Insulation Thickness PVC/Nylon Ground Size Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC For correction factors for different ambient temperatures and ampacitities at different conductor temperature ratings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). Jacket Thickness Diameter Over Jacket Approximate Net Cable Weight Control Power AWG mils AWG mils AWG mils inches lb/kft amps amps / / / / /4 8 30/ /4 6 30/ /4 4 40/ /4 2 40/ *DOW construction means: Control conductors are color coded E2 (See chart page 26) Power conductors are black with numbers M4 (See chart page 26) Fillers where applicable 18
20 Unshielded Tray Cable UL Type TC -ER, 600 V, 90 C dry / wet rated ULTREX UL 83 ICEA S Composite Conductors Type THHN/THWN-2 with Ground Composite - 4 Control Conductors with 3 Power Conductors and 1 Ground Insulation Insulation Diameter Approximate Control Power Ground Jacket Control Power Thickness Thickness Over Net Cable Size Size Size Thickness Number PVC/Nylon PVC/Nylon Jacket Weight AWG mils AWG mils AWG mils inches lb/kft amps amps / / /4 8 30/ /4 6 30/ /4 4 40/ /4 2 40/ Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation pull-in Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). Color codes: Power and Control conductors are black with number coding per Method 4 of ICEA S
21 ULTREX XL XLPE/PVC Type TC or TC-ER 600 Volt Power and Control Cable Temperature rating of 90 C dry / wet rated Applications Nexans 600 V ULTREX XL Tray Cables are listed as type TC or TC-ER under UL 1277 Electrical Power and Control Cables. These cables may be installed in wet or dry locations; in cable trays, raceways and open air; and are suitable for exposure to weather, direct burial and for Class I, Div. 2 (also Zone 2) and Class II, Div. 2 hazardous locations per NEC. Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Construction Conductor: bare, annealed copper conforming to ASTM B3 and Class B stranded in accordance with ASTM B8, from 14 AWG to 500 kcmil. Insulation: flame-retardant cross-linked polyethylene meeting the requirements for XHHW-2 per UL 44 and the requirements of ICEA S for XLPE insulation as standard. Sizes 14 AWG to 8 AWG are VW-1, and sizes 6 AWG and larger are not VW-1. Assembly: conductors are cabled in concentric layers with interstices filled with suitable fillers, as required. Ground wires are sized as required by (refer to the applicable product tables for the standard sizes provided). Sizes 14 AWG to 6 AWG have an insulated green ground wire. Sizes 4 AWG and larger have a bare ground wire. A binder tape of synthetic material assembles the core in a tight circular configuration. Jacket: UL listed sunlight and moisture resistant, sequentially length marked, black, flame retardant polyvinyl chloride (PVC) material meeting the requirements of UL Sample Print Legend: (mon/year) NEXANS ULTREX-XL 3/C 250 kcmil - 4 AWG GRD CU TYPE TC-ER XHHW-2 (UL) E64956 F SUN RES DIR BUR 600V Conductor Identification (See page 26 of this catalog) 14 AWG to 10 AWG: 2 37 conductors: Color coded per Method #1-E2 per ICEA S and More Conductors: Black with number coding per Method 4 of ICEA S AWG to 500 kcmil: black with number coding per Method 4 of ICEA S Specifications Meets : Power and Control Tray Cables with Optional Fiber Members. Meets UL 44: Thermoset-Insulated Wires and Cables. Meets ICEA S , NEMA Publication No. WC-70: Nonshielded Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy. Product features UL approved cables Type TC or TC-ER, 600 V. UL approved insulated conductors. Cables pass UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr. All cables pass IEEE 1202 and FT4 70,000 BTU/hr flame test. All cables pass ICEA T ,000 BTU/hr flame test. For use in power, lighting, control and signal circuits. Can be used within industrial establishments where serviced by qualified personnel and not subject to physical damage. Continuous operation temperatures of 90 C dry and wet. Cold bend of 25 C per Can be used In Class I Division 2 and Class II Division 2 Hazardous Locations and Intrinsically Safe applications as permitted by NEC Articles 392, 501, 502, 503, and 505.* 20 As indicated in : The overall jackets of these cables are a gas/vapor tight continuous sheath as discussed in NEC Article (D) & (E).* For use in cable trays, raceways, conduits, or for aerial applications where installed with a messenger. For Direct Burial applications. Cables of 2 or more conductors (plus a ground conductor) are UL listed for Exposed Run (ER) per NEC Article (7): 1) Cables sized from 14 AWG to 6 AWG have an insulated ground conductor. 2) Cables sized 4 AWG and larger have a bare ground conductor. As permitted in NEC Articles and 725 for Class 1 circuits. As permitted for non-power-limited alarm circuits as defined in NEC Articles and Lead free and RoHS compliant Sunlight and moisture resistant Options The following constructions can be provided on special orders: Cables sized 4 AWG and larger with an insulated ground conductor Aluminum alloy conductors in sizes 12 AWG to 1000 kcmil Insulated or bare ground wires Different conductor methods Shields of aluminum/mylar tape (with or without a tinned copper drain wire) Composite constructions of different sized conductors volt rated cables with RHH/RHW-2 insulated conductors. * Use in hazardous locations: Please note that no investigation of these cables has been performed regarding the transmission of gases or vapors through the core. When these cables are used in hazardous locations they should be sealed properly as required by the NEC.
22 Unshielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX XL UL 44 Multiconductor 14 AWG Type XHHW-2 Insulation Thickness: 30 mils / 0.76 mm Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conduct ors mils inches lb/kft amps /25.0 (1) Mininum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation pull-in Notes: Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature raitings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 Article 240.4(E) through (G). (1) Where the 4th conductor is the neutral of a balanced 3 phase system. 21
23 Unshielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated Multiconductor 12 AWG Type XHHW-2 Insulation Thickness: 30 mils / 0.76 mm ULTREX XL UL 44 Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps /30.0 (1) Minimum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature raitings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). 1) Where the 4th conductor is the neutral of a balanced 3 phase system. 22
24 Unshielded Tray Cable UL Type TC or TC-ER, 600 V, 90 C dry / wet rated ULTREX XL UL 44 Multiconductor 10 AWG Type XHHW-2 Insulation Thickness: 30 mils / 0.76 mm Jacket Diameter Approximate Net # of Thickness over Jacket Cable Weight Number Conductors mils inches lb/kft amps /40 (1) Minimum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. Ampacities for cables having more than three conductors have been derated per NEC Table (B)(3)(a). For load diversity of 50%, refer to NEC Table B (B)(2)(11). For correction factors for different ambient temperatures and ampacities at different conductor temperature raitings see NEC NEC Article 240.4(D) requires that overcurrent protection not exceed 30 amperes for 10 AWG copper after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). (1) Where the 4th conductor is the neutral of a balanced 3 phase system. 23
25 Unshielded Tray Cable UL Type TC-ER, 600 V, 90 C dry / wet rated ULTREX XL UL 44 ICEA S Conductors Type XHHW-2 with Ground Conductor Ground Insulation Thickness Jacket Diameter Approximate Net Size Size PVC/Nylon Thickness over Jacket Cable Weight Number AWG or kcmil AWG mils mils inches lb/kft amps (1) (1) / / / / Minimum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation pull-in Dimensions and weights shown are nominal values. They are subject to standard manufacturing tolerances. Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in a raceway or direct buried at 30 C ambient temperature and 90 C rated conductors. For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC (1) NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article (E) through (G). 24
26 Unshielded Tray Cable UL Type TC-ER, 600 V, 90 C dry / wet rated ULTREX XL UL 44 ICEA S Conductors Type XHHW-2 with Ground Number Conductor Ground Insulation Thickness Jacket Diameter Approximate Net Size Size PVC/Nylon Thickness over Jacket Cable Weight AWG or kcmil AWG mils mils inches lb/kft amps (1) / / / / Minimum Bending Radius: 5 x overall diameter installed 7.5 x overall diameter during installation. pull-in Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article (7). Ampacities are in accordance with NEC Table (B)(16) for conductors in raceway or direct buried at 30 C ambient temperature and 90 C rated conductors, where the fourth conductor is the neutral of a balanced 3 phase, 4 wire system. For correction factors for different ambient temperature ratings and ampacities at different conductor temperatures see NEC (1) NEC Article 240.4(D) requires that overcurrent protection not exceed 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G). 25
LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m
FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2
More informationIndustrial Cable Solutions for Variable Frequency Drives
Industrial Cable Solutions for Variable Frequency Drives Tough challenges call for innovative solutions, and General Cable is your worldwide source for new products and a wide range of industry-leading
More informationThe National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
More informationType XHHW-2 or RHH/RHW-2/USE-2 GenFree II LSZH XLPO Single Conductor
TABLE OF CONTENTS SECTION I. SUBJECT SCOPE 2 II. APPLICABLE DOCUMENTS 2 III. CONDUCTOR 3 IV. SEPARATOR 3 V. INSULATION 3 A. 3-4 B. Electrical Properties 4 C. Flame Resistance 5 D. Smoke and Halogen Testing
More information100% EMI Emission Containment
100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive
More informationMANUFACTURER S CERTIFICATE OF COMPLIANCE
s Type AC (Armored Clad) aluminum and steel interlocked metal clad 600-volt cable is produced 100% in the United States of America using accepted practices and quality assurance procedures to comply with
More informationEast Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE
SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,
More informationCCW Continuously Corrugated Welded Cable A RMORED CAB LE FO R HAZAR D O U S LOCATI O N S
CCW Continuously Corrugated Welded Cable A RMORED CAB LE FO R HAZAR D O U S LOCATI O N S OCTOBER 2014 CCW Servicing Industrial and Specialty Applications This catalog contains in-depth information on the
More informationIEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED
More informationCIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*
Gexol CIR Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL n Available in Standard and Arctic Grade Jackets n Highly
More informationKNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
More informationKNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
More informationBuilding Cables and Wires
Building Cables and Wires 4 Introduction alfanar is equipped with state-of-the-art manufacturing facilities such as latest machineries, instrumentation, quality control and testing laboratory, etc., for
More informationInstrumentation Cable...14-17. Power Cable...2-11. Assembly Solutions...32
Severe Cold Durability Exceeds CSA Cold Bend / Cold Impact (-0 C/-35 C) Drilling Mud Resistant Flame Retardant Certified to IEC 9-3 (33-3A) and IEEE 580 Oil Resistant Assemblies...3-33 Ester Based Mud
More informationSection 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
More informationOutside Telephone Cable
Outside Telephone Cable Filled Core. Moisture Barrier. Description Soft copper wires insulated with high density polyethylene, foam skin or solid. Filled core, conformed by groups of pairs or by unit of
More informationGexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments
Gexol Gexol World Class World Class Designed for safe, reliable performance in the harshest oil and gas operating environments Power Control Instrument VFD The Global Cable Solutions Company Gexol World
More informationDIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
More informationExane 125 Drilling Rig and Commercial Marine Cable
Exane 125 Drilling Rig and Commercial Marine Cable Over 20 Years of Superior Perfomance On Oil Rigs Around The World Engineered Wire & Cable for Demanding Applications Certified as Type P per IEEE-45 STD
More informationSTABILOY BRAND FeeDeR SOLuTIONS
STABILOY BRAND Feeder Solutions DATA CENTER Introduction General Cable understands that data centers depend heavily on a steady, reliable and scalable source of power. That is why our STABILOY Brand aluminum
More informationSTABILOY BRAND FeeDeR SOLuTIONS
STABILOY BRAND Feeder Solutions DATA CENTER Introduction General Cable understands that data centers depend heavily on a steady, reliable and scalable source of power. That is why our STABILOY Brand aluminum
More informationRoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables
RoHS DATA, COAXIAL AND ELECTRONIC D A TA, C O A X I A L, A N D EL E CTRON I C Cables Index SOLID MULTI-CONDUCTOR CABLES STRANDED MULTI-CONDUCTOR CABLES SPEAKER/ZIP WIRE THERMOSTAT CABLE FIRE ALARM CABLE
More informationTHE STABILOY BRAND ADVANTAGE UNLOCKING THE SECRETS OF ALUMINUM A LOOK AT THE ADVANTAGES OF ALUMINUM ALLOY OVER COPPER
THE STABILOY BRAND ADVANTAGE UNLOCKING THE SECRETS OF ALUMINUM A LOOK AT THE ADVANTAGES OF ALUMINUM ALLOY OVER COPPER Ever Wonder Why There s No Copper in the Air? Since the early 1900s, aluminum and aluminum
More information2012 CATALOG AEROSPACE VVIRE & CABLE INC. aerospacewire.com
* 2012 CATALOG AEROSPACE VVIRE & CABLE INC. A VV aerospacewire.com W e p r o u d l y m a n u f a c t u r e h i - t e m p w i r e & c a b l e. PLENUM CABLE. INDUSTRIAL CABLE. TRAY CABLE. MILITARY WIRE.
More informationUNDERSTANDING. C&M Corporation 51 South Walnut Street, Wauregan, CT 06387 Phone: 860.774.4812 Fax: 860.774.7330 www.cmcorporation.
UNDERSTANDING UNDERSTANDING NFPA 79 By Ned Lloyd and Mike Levesque NFPA-79 is the electrical standard that has been developed by the National Fire Protection Association (NFPA) and is intended to minimize
More information2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G
Seattle Cit y Light 1 of 4 2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G 1. Scope This standard covers the detailed requirements
More informationSTABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES
STABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES Introduction General Cable understands that assisted living facilities require complex building designs that must address a wide range of systems
More informationYour Only Solution for All Variable Frequency Drive Applications
ASD/VFD Cable System ASDBrochure.indd 1 Your Only Solution for All Variable Frequency Drive Applications 11/2/12 9:23 AM Inadequacies in Standard VFD Cables: EMC-Electro Magnetic Compatibility Electromagnetic
More informationCable Products HONEYWELL SECURITY & CUSTOM ELECTRONICS. Honeywell's Genesis Series provides a full range
HONEYWELL SECURITY & CUSTOM ELECTRONICS Cable Products Honeywell's Genesis Series provides a full range of low voltage cables for security, fire, sound, voice and data, video, structured cabling and other
More informationCable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks
Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Introduction This document presents the fundamental aspects of cable and conductor selection for connecting pad mounted shunt
More informationPROFIBUS cable. PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications
Data Sheet 10/63-6.47-EN Rev. D PROFIBUS cable PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications PROFIBUS PA cables Non-Ex (Hazardous) applications Ex (Hazardous) applications
More informationThe Contractor shall furnish and install all shielded power cable suitable for use on this project.
Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS
More informationSECTION 18370 SIGNAL WIRE AND CABLE
SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory
More informationW-2. Stranding Comparison
Wire Knowledge W-1 W-2 Stranding Comparison Conductor Coatings/Coverings PURPOSE To facilitate stripping of components applied over the conductor To prevent compound fall-in Improve solderability Prevent
More informationTable of Contents. Table of Contents
Table of Contents Bare Copper Solid ed Single Conductors XHHW-2 SIS USE-2/RHH/RHW-2 Jacketed Singles Photovoltaic Wire THW and THW-2 Weatherproof Line Wire Cathodic Protection Transformer Riser Wire Twisted
More informationInstallation and Application Guide. for 600V Conductors
for 600V Conductors for 600V Conductors Foreward This guide discusses recommended or best practices for installing 600 volt conductors in conduit. The purpose of the guide is to identify those critical
More informationCONFLEX ELECTRIC CABLE
CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard
More information450-750 VOLTS - Copper conductor PVC insulated SSA 1320, IEC 60227 & BS 6004 HO 7V - U With Solid Conductor - TYPE 60227 IEC 01. Insulation Thickness
450 50 VOLTS Copper conductor PVC insulated SSA 320, IEC 6022 & BS 6004 HO V U With Solid TYPE 6022 IEC 0 For internal wiring equipment rated voltage up to 000 V AC and up to 50 V to earth. Catalogue Number
More informationCable Tray Selection-
Cable Selection- For allowable cable types see the Appendix page A-9. The following guidelines are based on the 2002 National Electrical Code, Article 392. I) Number of Multiconductor Cables rated 2000
More informationUnarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
More informationCommunication, Signal & Data Cables
Communication, Signal & Data Cables Used for indoor installation and interconnection of transmission, telephone, telegraph and electronic equipment as well as media equipments www.alfanar.com Communication
More informationA quick product finder for commercial applications JUDD WIRE INC. A member of the Sumitomo Electric Industries group of companies
A quick product finder for commercial applications JUDD WIRE INC. A member of the Sumitomo Electric Industries group of companies Select, Customize, Order & Receive Products with Ease This catalog contains
More informationServo Motor & Drive Cables
Servo Motor & Drive Cables Servo-Motor & Drive Cable Contents Servo-SM (Servo-Motor & Feedback Cables to Siemens Specifications) 970 SERVO-SM5-6FX5008-1BD.. UL/CSA/CE SHLD PVC Feedback Cable- Green 971
More informationBasic Cable Assemblies DELIVERING QUALITY SINCE 1952.
Basic Cable Assemblies DELIVERING QUALITY SINCE 1952. Cable Types Cable Types Hook-up & Lead Wire Most Basic 2 Cable Types Cable Types Twisted Pair Cable A type of cable that consists of two independently
More informationElectrical Design Training Class Ampacity WSDOT Winter 2008 BZA
Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA presented by: Keith Calais 1 What is it? Ampacity is the current, in Amperes, that a conductor can carry continuously under the conditions
More informationL O W - S M O K E, Z E R O - H A L O G E N C A B L E S :
L O W - S M O K E, Z E R O - H A L O G E N C A B L E S : B R I D G I N G T H E P E R F O R M A N C E G A P Next Generation Low-Smoke, Zero-Halogen (LSZH) Thermoset Insulation A Look at General Cable s
More informationContact Hueson Corporation for additional information or details. http://www.huesonwire.com 38 Sutton Street Northbridge, MA 01534 508-234-6372
Hueson Corporation of Northbridge MA, a specialty wire and cable manufacturer has recently introduced a solution to a long term industry challenge in the Trailer Cable Industry. Their solution involves
More informationCHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
More informationUptown Campus, Primary Electric Master Plan - Program Study State University of New York At Albany, SUCF Project No. 01832 V.
V. DESIGN STANDARDS i. Medium Voltage Cables ii. iii. iv. Separable Connectors Splices & Fault Indicators Manholes & Ductbanks Primary Switches & Medium Voltage Transformers v. Metering, Monitoring, &
More informationDIRECTCONNECT SERVICE
DIRECTCONNECT SERVICE PRE-ASSEMBLED: LEADS, GROUNDS AND STINGERS/WHIPS Save Time, Labor and Money Lead Stinger/Whip Stock Colors (Blue, Green, Red, Yellow) available Stocked genuine Lenco and Tweco Connectors
More informationRecommended Practices for Designing and Installing Copper Building Wire Systems
Recommended Practices for Designing and Installing Copper Building Wire Systems CDA - CWIS Committee December 3, 2013 Developed by the Copper Development Association Inc. www.copper.org Foreword This document
More informationGenerator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
More informationFIRE RESISTANT CABLE CONSTRUCTION OF CABLES
FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the
More informationThe Instrumentation Cable Experts
1 The Instrumentation Cable Experts Facilities Head office & factory 1300 Industrial Boulevard Mt Pleasant, Texas 75455, USA www.dekoroncable.com Stocking Centres USA Mt Pleasant and Houston Singapore
More informationCorporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS
Corporate Profile MODERN ROYAL ELECTRIC Ideal Power Solution ROYAL MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS MAJOR STOCKIST >>> CATHODIC PROTECTION CABLES >>> LOW VOLTAGE CABLES >>> MEDIUM
More informationLUTZE Flexible Cable and Wire Management for Industrial Automation
USA Cable Solutions LUTZE Flexible Cable and Wire Management for Industrial Automation Control Cable Electronic Cable Actuator Sensor Cable BUS and Network Cable Motor Supply, VFD, Servo and Feedback Cable
More informationTri-Rated Flexible PVC Equipment Wire
Application: High temperature, flame retardant wire designed for use in the switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier
More informationWire types and sizes
Wire types and sizes This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
More informationHIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)
Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission
More informationTechnical Information Handbook
Technical Information Handbook Wire and Cable Products. Technology. Services. Delivered Globally. We are a leading global supplier of communications and security products, electrical and electronic wire
More informationSound, Alarm & Security Cable 7
Electronics Sound, Alarm & Security Cable 7 Index Page The sound and security industry in the United States has grown from a simple and unsophisticated business, begun some 45 years ago, to one which has
More informationAutomotive Wire and Cable Products
Automotive Wire and Cable Products Primary Wires: ISO: Classes B - H JASO: AEX, AESSX, AVX, AVSSX : TXL, GXL, STX Engine Harness Wire: AutoRad Transmission Wire: Silicon & Non-Silicon Blocked Sensor Cables:
More informationOFFICE OF CIVIL ENGINEERING UNITED STATES COAST GUARD WASHINGTON, D.C. APRIL 1996 MARINE CABLE, POWER AND CONTROL SPECIFICATION NO.
OFFICE OF CIVIL ENGINEERING UNITED STATES COAST GUARD WASHINGTON, D.C. APRIL 1996 MARINE CABLE, POWER AND CONTROL SPECIFICATION NO. G-SEC-390E 1. SCOPE 1.1 Purpose. This specification establishes the basic
More informationAll Wires and Cables Are Not Created Equal
All Wires and Cables Are Not Created Equal When comparing life cycle costs for wires and cables in wind systems, consider the specific applications, cost per failure and dielectric losses to determine
More informationAN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY. (The following code explanations are to be used with a copy of the 2011 NEC.
AN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY (The following code explanations are to be used with a copy of the 2011 NEC.) To obtain a copy of the NEC contact: National Fire Protection Association
More information600V Power Cable 600V SOOW SOW
600V Power Cable Type SOOW UL/CSA 90 C 600V Part AWG No of Insulation Jacket Nominal Wieght/Mft Number Stranding conductors Thickness Thickness O.D. Nom. 18 2 SOOW 18 AWG 2.30 71 18 3 SOOW 16/.010 3.030
More informationHIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec
More informationELECTRICAL: WIRE, CABLE, AND TERMINATIONS
ELECTRICAL: WIRE, CABLE, AND TERMINATIONS BASIS OF DESIGN This section applies to the design and installation of wire and cable systems and terminations. Design Criteria Medium Voltage Review and modify
More informationCORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.
CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS September 2006 Revision 7 Corning Cable Systems reserves the right to update
More informationAPPLICATION ORIENTED DESIGN OF CABLES
APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. rohinib@ducab.com Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. Nawaf@ducab.com
More informationETHERLINE Ethernet Cable, Connectors & Tools
Ethernet Cable, ors & Tools 2 Pair 242 4 Pair 249 Industrial Ethernet ors & Tools 256 Ethernet Cable, ors & Tools ETHERNET CABLE, CONNECTORS & TOOLS Quick Select Chart 240 2 Pair 2 Pair: CAT.5/5e; Stationary
More informationFrom a single wire harness to an entire Electrical Distribution System (EDS), PKC delivers power where and when you need it.
CATALOG INDEX Introduction 2 Overview 3 PVC-Automotive 5 PVC-UL and CSA 6 XLPE-Automotive 9 XLPE-UL and CSA 10 Metric Wire 11 Automotive Battery Cable 12 Boat Cable 12 Introduction PKC Group PKC Group
More informationPROFIBUS cable. for PROFIBUS-PA and -DP 10/63-6.46 EN
for PROFIBUS-PA and -DP 10/63-6.46 EN CPN 080/CPE 080-Ex PROFIBUS-PA basis cable AWG 18, 0.88 mm 2 Use For fixed installation indoor and outdoor, on racks and in conduits. Application Fieldbus cable for
More informationEcoFlex Cable. Smaller. Lighter. Tougher. 100% Recyclable.
EcoFlex Cable Smaller. Lighter. Tougher. 100% Recyclable. Total Performance, Completely Recyclable EcoFlex cable is Alpha Wire s newest innovation in control cabling. A true engineering breakthrough, EcoFlex
More informationMESSENGERS FOR AERIAL CABLE
MESSENGERS FOR AERIAL CABLE COPPERWELD - EHS, 30% CONDUCTIVITY MES(size)CUWELD Size O.D. Stranding Breaking Strength Wgt./Mft. MES1/4CUWELD 1/4".242 7 #12 5,783 lbs. 128 MES5/16CUWELD 5/16".306 7 # 10
More informationStandard Buccaneer - Ethernet
IP6 rated compliant PUR jacket on cable Shielded system shielded coupler Shroud on RJ45 Screw coupling Rewireable flex connector PCB mounted panel connector IDC termination panel connector Earth lead version
More informationStandards Affecting a Premise T-1 Installation
Standards Affecting a Premise T-1 Installation The T-carrier system originated many years ago as a technology developed by AT&T. The intended use of the scheme was to increase the voice channel capacity
More informationBRÖCKSKES D-VIERSEN PV1-F 4,0 mm BRÖCKSKES D-VIERSEN PV1-F 4,0 mm d d 2 2 C VDE-REG.-Nr. 8292 10/2009
d BRÖCKSKES BRÖCKSKES D-VIERSEN D-VIERSEN PV1-F PV1-F 4,0 mm 4,0 2 mm VDE-REG.-Nr. 2 C 8292 10/2009 s - THE COMPANY DIN EN ISO 9001 More than 60 years of experience in temperature measurement and control
More informationCABLE SPECIFICATION CAN CAB RJ45-SUBD9
CABLE SPECIFICATION All technical information contained in this document is the exclusive property of STI and may neither be used nor disclosed without its prior written consent. AAV 33801 1/8 Connector
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
More informationThe Quality Connection. BETAflam Fire Resistant Safety Cables
The Quality Connection BETAflam Fire Resistant Safety Cables 2 Contact Consulting and sales Switzerland Phone +41 (0)62 288 82 82 Fax +41 (0)62 288 83 83 sales@leoni-studer.ch www.leoni-infrastructure-datacom.com
More information2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
More informationFirst Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897
OCA #230100 First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897 AN ORDINANCE AMENDING SECTIONS 4.A.080, 4.1.020, 4.1.110, 4.2.010, 4.2.070, 4.2.125, 4.2.170, 4.2.175 AND 4.2.220;
More informationHow To Use A Grounded Neutral System
Installation Instructions Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives Important User Information Read this document and the documents listed in the additional resources section
More information1394 locking cables. Your locking cables for AVT IEEE 1394 cameras
Your locking cables for AVT IEEE 1394 cameras AVT locking cables are ideal for connection of IEEE 1394 cameras in any industrial application. The high quality cables guarantee low damping and best signal
More informationInstallation Instructions. Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives
Installation Instructions Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives Important User Information Solid-state equipment has operational characteristics differing from those
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationSecurity & Control Cables
Security & Control Cables Our multi-conductor cables are manufactured in a wide variety of gage sizes, shielding configurations and jacketing materials including plenum, riser and general purpose. Applications
More informationComplete Firestop Systems Guide
Complete Firestop Systems Guide Passive Fire Protection products are tested to various test requirements, please check with your local building code for the requirements within your municipality. Firestop
More information< SD 200 C TP Continuously flexible TPE/PUR paired data cable with coloured cores and overall copper screen... 10
CONTENT General < The Company..................................................................................... 3 Customized cables for different applications < Data / POF Cables POF-LWL and hybrid
More informationWest Penn Wire. Access Control Systems and Cables WEST PENN WIRE CABLE WITH CONFIDENCE
West Penn Wire Access Control Systems and Cables Access Control Cables AWG Size CARD READER CABLES # of Cond. CMR Shielded CMP Shielded CMR Unshielded CMP Unshielded 22 4 3241 253241B 241 25241B 22 6 3270
More informationwith coloured cores and overall copper screen UL/CSA... 17
CONTENT Cable Track Cables y SD 200 extremely flexible TPE/PUR data cable with coloured cores for continuous movement..... 6 y S 200 extremely flexible TPE/PUR control cable with numbered cores for continuous
More informationAWG: Cat5e: Cat6: Cat6A:
Some of the terms used in the cable business can be vexing to even the most seasoned folks in the industry. If any of this terminology has ever made you scratch your head, you are certainly not alone.
More informationwww.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
More informationConductor Sizing and the National Electrical Code
Conductor Sizing and the National Electrical Code The National Electrical Code requirements for conductor sizing and overcurrent protection have always been confusing and complex. Factors that must be
More informationShort Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More informationMEDIUM VOLTAGE POWER CABLES
MEDIUM VOLTAGE POWER CABLES CONTENTS 1 GENERAL INTRODUCTION 4 TECHNICAL INFORMATION 15 25 35 45 Single Core XLPE Insulated PVC Sheathed Cables UNARMOURED CABLES COPPER UNARMOURED CABLES ALUMINUM ALUMINUM
More informationAC 800M EtherNet/IP DeviceNet Installation
AC 800M EtherNet/IP DeviceNet Installation System Version 6.0 Power and productivity for a better world TM AC 800M EtherNet/IP DeviceNet Installation System Version 6.0 NOTICE This document contains information
More informationGeneral Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE
Excerpt from PRYMIAN WIRE AND CABLE ENGINEERING GUIDE Page 1 of 0 Voltage Rating The selection of the cable insulation level to be used in a particular installation shall be made on the basis of the applicable
More informationSECTION 260513 MEDIUM VOLTAGE CABLE
SECTION 260513 MEDIUM VOLTAGE CABLE PART 1 - GENERAL 1.1 SUMMARY A. Related Documents: 1. Drawings and general provisions of the Subcontract apply to this Section. 2. Review these documents for coordination
More information