1 DATA ACQUISITION UNIT DATA ACQUISITION UNIT SUB UNIT <<Contents>> <<Index>> General Specifications Data Acquisition Unit DA100 Main unit stand-alone type (style number:s10) expandable type (style number:s10) Sub units DS400/DS600 (style number:s10) Refer to the following cautionary notes before you configure your system. DARWIN is a system comprising a number of dataacquisition equipment components. In the course of system growth, new models, software, various input/output s and optional features are added to the family to enhance the systems expandability and flexibility.you can check the versions of your equipment and software by referring to the style number:sn* shown on the nameplate of the main unit. When configuring a system, you must confirm that the style number of each component unit and software meets the following requirements: * release number in the case of software:rn (1) The style number of each input/output must be the same as or lower than that of the main unit or sub-unit to which the is connected. The following product was discontinued as of March, Discontinued products: DA100-2 Data Acquisition Unit (Expandable Model) stand-alone type (2) The release number of a dedicated software package must be the same as or higher than the style number of the main unit or sub-unit where the package is installed and where it performs control. Any equipment/software not meeting these requirements is incompatible with your system configuration. For information on how to upgrade to compatible equipment/software, consult our sales personnel. expandable type Model Features Increasing number of input channels, changing kinds of inputs Kinds of inputs Input and output s that can be connected to the main unit Connection of sub units, and remote measurement distance Input and output s that can be connected to the sub units Max scanning speed DA100 Data acquisition unit DA100 stand-alone type DA100 expandable type Integrated type capable of measuring data from up to 40 Can be expanded up to 300 channels. channels. You can perform multi-channel measurement with the Can be carried about easily and is suitable for small scale minimum of wiring by connecting sub units to the main data logging. unit with dedicated cable. The number of channels can be increased from 10 to 40 The number of channels can be increased from 10 to 300 channels in a steps, and also the kinds of inputs channels in a steps, and also the kinds of inputs can be changed. can be changed. Universal, DC V/TC/DI, ma, power monitor, strain, Pulse, DI Universal, DC V/TC/DI, ma, power monitor, strain, Pulse, DI Input s, communication, DI/DO, (Input s are connected to the sub units.) alarm output s, retransmission s Communications, DI/DO, alarm output s Not applicable Up to 6 units, 500 m max (Full extension) Not applicable All channels/0.5 sec Input s, DI/DO, alarm output, retransmission s All channels/0.5 sec Copyright November 1995 (YK) 13th Edition: Aug (KP)

2 DATA ACQUISITION UNIT DATA ACQUISITION UNIT SUB UNIT <<Contents>> <<Index>> Outline of the stand-alone type The DA100 data acquisition unit (stand-alone type) measures input signals from between 10 and 40 channels, and transfers the measured data in realtime to a personal computer. This highly portable unit is also suitable for on-site data logging. DA100 stand-alone type main unit + PC Main features (1) Compact: Occupies only 1/5 of the space of Yokogawa s remote scanner for the DA2500E. (2) High speed: Can measure data from 40 channels in 0.5 second maximum. (3) A wide range of inputs: Universal (DC voltage, thermocouple, RTD, contact), DC voltage/ thermocouple/contact dedicated inputs, ma, power monitor, strain, pulse, DI input. Outline of functions (1) Setting and control of connected input/output s (2) The measured results obtained using input s can be transferred to a personal computer via a GP-IB, RS-232-C, RS-422- A/RS-485, Ethernet communications interface. Outline of expandable type The main unit of the DA100 data acquisition unit (expandable type) can be connected to DS400 (4-slot type) or DS600 (6-slot type) sub units containing various input s, in order to configure a system that can acquire data from a maximum of 300 channels. The measured data is transferred in realtime to a personal computer. DA100 expandable type main unit + sub unit + PC Main features (1) Compact: Occupies only 1/5 of the volume of other Yokogawa units. (Comparison between a system consisting of the DA100 main unit + one sub unit and a system consisting of one DA2500E + one remote scanner) (2) High speed: Can measure data from 300 channels at 0.5-second intervals maximum. (3) A wide range of inputs: Universal (DC voltage, thermocouple, RTD, contact), DC voltage/ thermocouple/contact dedicated inputs, ma, power monitor, strain, pulse, DI input. (4) Remote measurement: The sub unit is designed to be connected to the main unit with dedicated cable, enabling it to be located up to 500 m away from the main unit. Outline of functions (1) Setting and control of input/output s on the sub units connected with dedicated cable (Setting is done using the connected personal computer and the setting software provided.) (2) Control of alarm output s, DI/DO s, communication interface s connected to the DA100 main unit. (3) Acquisition by the DA100 main unit of the measured results from the input s, via the sub units. (4) Transfer of the measured results acquired by the DA100 main unit to a personal computer, via a GP-IB, RS-232-C, or RS-422-A/RS- 485, and Ethernet communication interfaces. Outline of sub units The DS400/DS600 sub unit functions as an interface between the expandable version of the DA100 data acquisition and the various input/ output s to which it is connected. A maximum of four input and output s of various kinds (4 slots) can be connected to the DS400, and a maximum of six input and output s (6 slots) can be connected to the DS600. A maximum of six sub units can be connected to one main unit. Both DS400 and DS600 sub units can be connected to the same main unit. The main unit can be connected to the sub units, or the sub units to each other, with dedicated cable, enabling them to be separated by up to 500 m. The sub units have excellent environmental toughness and can be installed very easily, enabling them to be installed over a wide area without environmental restrictions. Outline of functions (1) Setting and control of the connected input/output s (by means of commands from the DA100 main unit.) (2) Measured values output to the DA100 main unit. 2

3 NO C b -/B -/A NO C b -/B -/A SUB UNIT <<Contents>> <<Index>> Configuration Component units b -/B -/A b -/B -/A DA100 main unit stand-alone type ALM1 ALM2 ALM3 ALM4 ALM5 ALM6 ALM7 ALM8 ALM9 ALM10 ALM1 ALM2 ALM3 ALM4 ALM5 ALM6 ALM7 ALM8 ALM9 ALM10 b -/B -/A DATA ACQUISITION UNIT POWER VAC 50/60Hz 70VA MAX DATA ACQUISITION UNIT POWER VAC 50/60Hz 70VA MAX DA100 expandable type: Expandable type main unit + sub units (DS400 or DS600) + various input/output s + communication interface + data acquisition software Available groups The DA100 data acquisition unit can be freely configured for different functions by selecting s from the following groups and connecting them to the main or sub units. Input s: Universal (DC voltage, thermocouple, RTD, contact), DC voltage/ thermocouple/contact dedicated input s, ma, power monitor, strain, pulse, DI input. Alarm s: 4 point out put (transfer contact) or 10 point out put (make contact) (The number of alarm channels can be increased in units.) Communications s: Select one type from GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet. DI/DO s: Alarm 2-point output (transfer contact), fail output, command DO, remote control signal input. Retransmission s: Re-output of measured values and computed results. NOTE Refer to Standard connection s in GS 04M01E01-11E, or GS 04M01E01-50E for detailed specifications of the above s. DA100 main unit expandable type b -/B -/A b -/B -/A b -/B -/A b -/B -/A DS400 sub unit SUB UNIT POWER VAC 50/60Hz 70VA MAX Package software DARWIN DAQ 32 (Standard Package) DARWIN DAQ 32 Plus (Optional Package) General DAQ 32 and DAQ 32 Plus are software packages developed by YOKOGAWA specially for the DARWIN series. These packages run on a personal computer, achieving highly dependable data acquisition using DARWIN series units (DA100, DC100, DR130, DR230, and DR240) and superb operability. The main differences between the two packages are in the monitoring functions. The DAQ 32 only offers two display formats - waveform trend and digital; has 2 groups of 10 channels/ window; and does not support alarm display. If simultaneous multi point monitoring or more flexible display forms of data such as level meter, analog meter, and thermometer faceplates, and alarm indications are required, use the optional DAQ 32 Plus. b -/B -/A b -/B -/A b -/B -/A POWER VAC 50/60Hz 70VA MAX DS600 sub unit Unit configuration The DA100 comes in the following two types, each of which is intended to be set and controlled by a personal computer via a general purpose communications interface. DA100 stand-alone type: Stand-alone type main unit + various input/output s + communication interface s + data acquisiton software 3

4 <<Contents>> <<Index>> Ethernet STRAIN Communication interface RS-232-C RS-422-A/485 PULSE Personal computer DA100 main unit ma(current) GP-IB A current Communication interface cable DATA ACQUISITION UNIT POWER VAC 50/60Hz 70VA MAX Strain ~ AC b -/B -/A b -/B -/A b -/B -/A Input No alarm or DI/DO can beconnected to theright side of this input. Power Contact Status Install Pulse DAQLOGGER DI RTD package software DARWIN DAQ 32 Plus Universal DC V/TC/DI TC DA100 stand-alone type system configuration Set-up and control software DARWIN DAQ 32 Module I/O Retransmission Alarm output DI/DO 1-5 V 4-20 ma Input DC V 4

5 ALM1 ALM2 NO C ALM3 ALM4 ALM5 ALM6 ALM7 ALM8 ALM9 ALM10 ALM1 ALM2 NO C ALM3 ALM4 ALM5 ALM6 ALM7 ALM8 ALM9 ALM10 <<Contents>> <<Index>> Ethernet Sub unit Communication interface RS-232-C RS-422-A/485 STRAIN GP-IB PULSE Personal computer Communication interface cable DA100 main unit DATA ACQUISITION UNIT POWER VAC 50/60Hz 70VA MAX Dedicated cable (up to 500 m) Input No alarm or DI/DO can beconnected to theright side of this input. Power ma(current) Pulse input Strain ~ A Contact Status AC current DI Install DAQLOGGER Universal DC V/TC/DI RTD DA100 expandable type system configuration Set-up and control software package software DARWIN DAQ 32 DARWIN DAQ 32 Plus Sub unit Module I/O Retransmission Remote measurement Alarm output DI/DO 1-5 V 4-20 ma Extension Input DCV TC 5

6 Connecting s Connecting s to the stand-alone type Modules that can be connected Input s: Universal (DC voltage, thermocouple, RTD, contact), DC voltage/ thermocouple/contact dedicated, ma, power monitor, strain, pluse, DI input s Alarm s: 4 channels (transfer contact) or 10 channels (make contact) (The number of alarm channels can be increased in units.) Communications s: Select one type from GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet DI/DO s: Alarm 2-point output (transfer contact), fail output, command DO, remote control signal input Retransmission s: Re-output of measured values and computed results Extension : For remote measurment Definition of number of connections A maximum of six s can be connected to the main unit. One of these must always be a communications. The number of DI/DO s must be no greater than one. The alarm output, DI/DO, and retrandmission must be connected on the left side of the input s. Number of input s 4 Number of input s + number of alarm s + DI/DO + communications 6 One extension can be connect to the main unit Number of retransmission s 4 The standard operating temperature and humidity are different for each type. Therefore,always make sure to verify this when connecting the. Connecting s to the expandable type Modules that can be connected Main unit Alarm s: 4-point output (transfer contact) or 10-point output (make contact) (The number of alarm channels can be increased in units.) Communications s: Select one type from GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet DI/DO s: Alarm 2-point output (transfer contact), fail output, command DO, remote control signal input. Sub unit DS400/DS600 Input s: Universal (DC voltage, thermocouple, RTD, contact), DC voltage, thermocouple, contact dedicated input s, pulse Alarm s: 4-point output (transfer contact) or 10-point output (make contact) (The number of alarm channels can be increased in units.) DI/DO s: Alarm 2-point output (transfer contact), fail output, command DO s and remote control signal input Extension : For remote measurment Retransmission s: Re-output of measured values and computed results Definition of number of connections for the expandable type DA100 main unit: The number of input s and retransmission s is 0. Also, 1 communications must always be connected. Number of alarm s + DI/DO 3 Sub unit DS400: The maximum number of s per slot that can be connected is 4. Number of input s + DI/DO + alarm s + retransmission s 4 Sub unit DS600: The maximum number of s per slot that can be connected is 6. Number of input s + DI/DO + alarm s + retransmission s 6 Common to all: One DI/DO can be connected to one expandable type system The alarm output and DI/DO must be connected on the left side of the input s. One extension can be connected to one sub unit. The retransmission can be connected to the sub unit only. Up to 30 s. The standard operating temperature and humidity are different for each type. Therefore, always make sure to verify this when connecting the. Method of connecting s The standared operating temperature and humidity are different for each type. Therefore, always make sure to verify these when connecting the. Stand-alone type: Connect directly to the main unit. The alarm output modlues and DI/DO must be connected on the left side of the input s. Expandable type: Connect the input s, retransmission s, or extension directly to the sub unit. (You cannot connect these s directly to the main unit.) Connect the alarm s, communications and DI/DO directly to the main unit. The alarm output modlues and DI/DO must be connected on the left side of the input s. Connecting sub units Kinds of sub units (type name): DS400 sub unit: For 4 slots DS600 sub unit: For 6 slots Number of sub units to be connected: Stand-alone type:cannot be connected. Expandable type:a maximum of six sub units can be connected. (This also applies when 4-slot sub units and 6-slot sub units are connected to the same main unit.) Method of connecting sub units: A sub unit can be connected to either the main unit or another sub unit with dedicated cable. Maximum total extension length is 500 m. 6

7 Standard specifications General specifications Construction Installation method: Floor mounting: Use the stand at the bottom of each unit. Direct panel mounting: the unit directly to the panel at the specified points. Rack mounting: Use the dedicated mounting brackets. (Regardless of which mounting method you use, be sure to install the units in an upright position.) Materials: Steel plate, aluminum castings, plastic moldings Paint color: Base unit: Modules: Lamp black (equivalent to Munsell 0.8Y2.5/0.4) Slate gray light (equivalent to Munsell 0.1PB4.6/ 0.2) Slate gray light (equivalent to Munsell 0.1PB4.6/ 0.2) External dimensions: Stand-alone type main unit: Approx. 422 (W) 176 (H) 100 (D) mm Expandable type main unit: Approx. 336 (W) 165 (H) 100 (D) mm DS400 sub unit: Approx. 336 (W) 165 (H) 100 (D) mm DS600 sub unit: Approx. 422 (W) 176 (H) 100 (D) mm Weight: Stand-alone type main unit: Approx. 3.5 kg (with 4 input s + 1 alarm output + 1 communications installed) Approx. 1.1 kg* Expandable type main unit: Approx. 2.5 kg (with 4 input/output s installed) Approx. 0.9 kg* DS400 sub unit: Approx. 2.5 kg (with 4 input/output s installed) Approx. 0.9 kg* DS600 sub unit: Approx. 3.5 kg (with 6 input/output s installed) Approx. 1.1 kg* *: is the weight of each unit without s installed. Input Measurement range: NOTE Refer to Standard connection s in GS 04M01E01-11E for detailed specifications of the measurement range. Measurement interval: Selectable from 0.5, 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60 sec depending on the minimum measurement interval (when s with different minimum intervals are installed together, the measurement interval is determined by whichever has the maximum interval). Stand-alone type: Max 40 channels/500 ms (when the software provided is used) Expandable type: Max 300 channels/500 ms (when the software provided is used) A/D integration period (dependent on the ): Selectable from 20 ms (50 Hz), 16.7 ms (60 Hz), 100 ms (10 Hz), and auto switching (unavailable for a DC power supply model). Alarm Number of settings: Up to four settings can be made for each channel. Kinds of alarms: Selection from higher limit, lower limit, difference higher limit, difference lower limit, higher limit of rate of change, lower limit of rate of change. Rate of change alarm time interval: Can be set to measurement interval 1 to 15 (common to both rising and falling limits) Output mode: Excitation/non-excitation selection, AND/OR mode selection, and output hold/non-hold specification can be made. (common to all channels) Six reflash alarm output contacts can be specified. Number of alarm output points: Stand-alone type: 2 points (DI/DO ) to 40 points max Expandable type: Up to 30 points can be connected to the DA100 main unit (the number of alarm points can be increased in units) By connecting sub units, (the number of alarm points can be increased in units). Number of alarm output s that can be connected: Stand-alone type: The number of alarm points can be increased in units. Expandable type: Up to 3 s can be connected to the DA100 main unit, up to 6 s can be connected to one sub unit, and up to 4 s can be connected to one subunit. Standard computation functions Computation functions: Difference between arbitrary channels, linear scaling, moving average Scaling: Ranges for which scaling can be done: DC voltage, thermocouple, RTD, contact, strain, ma, Scaling range: to Decimal point: Can be set freely. Measurement accuracy for scaling: Measurement accuracy for scaling (digits) = Measurement accuracy (digits) Scaling span (digits)/measurement span (digits) + 2 digits (Numbers below the decimal point are rounded up.) Moving average: The moving average results for between 2 to 64 scans are computed. Communications functions Communication s: GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet communications interface s 7

8 Output functions DI/DO : Internal alarm output 2 points, fail output function, command Do. Retransmission s: Re-output of measured values and computed results. 10 voltage and 2 current channels. AC power supply section Rated supply voltage: 100 to 240 VAC (free supply voltage selection) Usable supply voltage range: 90 to 250 VAC Rated supply frequency: 50/60 Hz Power consumption: Stand-alone type main unit (when 6 connectable s are installed) max approx. 55 VA (when 100 VAC is input) max approx. 70 VA (when 240 VAC is input) Expandable type main unit (when 4 connectable s are installed) max approx. 45 VA (when 100 VAC is input) max approx. 55 VA (when 240 VAC is input) DS400 sub unit (when 4 connectable input/output s are installed) max approx. 45VA (when 100 VAC is input) max approx. 55 VA (when 240 VAC is input) DS600 sub unit (When 6 connectable input/output s are installed) max approx. 55 VA (when 100 VAC is input) max approx. 70 VA (when 240 VAC is input) DC power Supply section (DC power supply only, Specify when ordering) Rated supply voltage: 12 to 28 VDC Usable supply voltage range: 10 to 32 VDC Power consumption: Approx. 25 VA max. Terminal: Dedicated connector Other: Automatic selection of A/D integral period does not function. AC Adapter (for DC power supply model only, optional accessary) Rated supply voltage: 100 to 240 VAC Usable supply voltage range: 90 to 250 VAC Rated supply frequency: 50/60 Hz Power consumption: max. 90 VA Others Clock: With calendar function (Western calendar). Clock accuracy: ±100 ppm System alarm: Contact output (when DI/DO is connected) Set value backup: Lithium battery backup (approx. 10 years), excluding clock function Insulation resistance: At least 20 MΩ between each terminal and ground (measured with 500 VDC) 8 Withstand voltage: Between AC power supply terminal and case of DA100 main unit:1500 VAC (50/60 Hz) for one minute Between DC power supply terminal and case of DA100 main unit:1000 VAC (50/60 Hz) for one minute Between input terminal and case of DA100 main unit:1500 VAC (50/60 Hz) for one minute Between output terminal and case of DA100 main unit:2300 VAC (50/60 Hz) for one minute Normal operation conditions Supply voltage: 90 to 250 VAC, 10 to 32 VDC Supply frequency:50 Hz ± 2%, 60 Hz ± 2% Ambient temperature: Stand-alone type main unit Expandable type main unit When floor-mounted and Desk top : 0 to 50 C When panel-mounted : 0 to 50 C When Rack-mounted : 0 to 50 C DS400/DS600 sub unit When floor-mounted and Desk top : -10 to 50 C When panel-mounted : -10 to 60 C When Rack-mounted : -10 to 50 C When DC power operation : 0 to 50 C Ambient humidity: Temperature 10 to 40 C 40 to 50 C 50 to 60 C * no ice formation Humidity 20 to 80% RH 10 to 50% RH 5 to 30% RH Vibration: 10 to 60 Hz 0.2 m/s 2 Shock: Not allowed Magnetic field: 400 A/m max (50/60 Hz) Position: Mount the unit left-right horizontally or vertically, as a general rule. Installation location: Room Installation height: Altitude up to 2,000 m Installation category: II (according to CSA22.2 No ) Measurement category: II (according to IEC ) Degree of pollution: 2 Warm-up time: At least 30 minutes after power switch-on Standard performance Measurement accuracy: Reference operation state: 23 ± 2 C, 55 ± 10% RH, supply voltage: 90 to 250 VAC, supply frequency: 50/60 Hz ± 1%, Warmup: At least 30 minutes; When operating, the system must not adversely affect the operation of other measuring instruments by generating vibration, for example. enerating vibration, for example. NOTE Refer to Standard connection s in GS 04M01E01-11E for detailed specifications of the measurement accuracy.

9 Effect of Operation Conditions Ambient temperature: Variation for a temperature change of 10 C within ±(0.1% of rdg + 1 digit) ±(0.2% of span + 1 digit) for Cu 10 Ω Voltage variation: Within ±1 digit over the range of 90 to 132, or 180 to 250 VAC (frequency 50/60 Hz) External magnetic field: Variation with respect to AC (50/60 Hz) and DC magnetic fields of 400 A/m... Within ±(0.1% of rdg + 10 digits) Radio wave: Within ±(1% of span) at 1 m from 150 MHz or 460 MHz field Signal source resistance: Variation with respect to signal source resistance + 1 kω change (1) Voltage 2 V range or below... Within ±10 µv 6 V range or above... Within ±0.1% of rdg (2) Thermocouple Within ±10 µv; However, it must be within ±100 µ when burnout is specified. (3) RTD Variation with respect to change of 10 Ω per wire (when all three wires are the same resistance value) Indication... Within ±(0.1% of rdg + 1 digit) Variation in indication with respect to a difference of 40 mω in the resistance between conductors (max difference between 3 wires)... Approx. 0.1 C Mounting position: Variation when the unit is mounted horizontally on a panel... Within ±(0.1% of rdg + 1 digit) excluding RJC error Vibration: Variation when sinusoidal vibration of acceleration 0.2 m/s 2 is applied for 2 hours in each of the 3 axial directions over a frequency range of 10 to 60 Hz... Within ±(0.1% of rdg + 1 digit) Transportation and storage conditions These refer to the environmental conditions existing during transportation and storage from the time of shipment from the factory until commencement of use, and also during transportation and storage in the case of a temporary period of non-use. If the environmental conditions are maintained within the specified range, the unit will not incur permanent damage, and can be returned to a normal working condition (re-adjustment may be required in some cases). Ambient temperature: 25 to 60 C Humidity: 5 to 95% RH Vibration: 10 to 60 Hz 4.9 m/s 2 max Shock: 392 m/s 2 max (in packed condition) Supported standards CSA UL CE C-Tick KC marking Obtained CSA22.2 No Installation category (Overvoltage category): II, Degree of pollution: 2 Obtained UL No (CSA NRTL/C) CE marking was removed under the publication of the 3rd edition of IEC Standard. EN Class A, Group 1 Electromagnetic wave interference prevention standard, electromagnetic wave protection standard compliance /M1: MATH Function Computation types Types: Four arithmetical operations, SQR (square root), ABS (absolute value), LOG (common logarithm), LN (natural logarithm), EXP (exponent), statistical computation*, logical computation (AND, OR, NOT, and XOR), relational computation, exponentiation, previously-measured value reference, hold**, reset, clear, and remote RJC. * Statistical computation CLOG: Computation process of simultaneously measured values within a group (total, maximum, minimum, average, and maximum - minimum) TLOG: Computation process of a specific channel over time axis (total, maximum, minimum, average, and maximum - minimum) Statistical computation interval: Set by the event/action function (effective when /M1 option is selected) **Temporary hold of the computed result Can be controlled by event/action function (such as remote control signal, time specified, and alarm status). (effective when /M1 option is selected) Number of channels for computing (Number of channels that can be allocated for computational purposes.): Stand-alone type: 30ch maximum Expandable type: 60ch maximum Computation interval: Every measurement interval (except when the computation becomes too difficult to be processed every measured interval, in which case an alarm is generated) Significant digits during computation: ±10 38 Significant digits of the computed result: to (Decimal point can be set to have 1 to 4 digits on the right of the decimal point) Input from communication interface: Digital value (ASCII numerical array) input from the communication interface Computation start/stop: Can be controlled by communication commands and event/action function (such as remote control signal, time specified, and alarm status) Other functions included in the math function: Remote RJC Input type: Thermocouple (TC) Accuracy: (Twice the measurement accuracy of the standard thermocouple input) + (temperature difference between the terminal of the remote terminal section and thermocouple section for measuring the remote terminal temperature) Thermocouple burnout: not selectable /M3: Report Function Refer to the GS 04M01B01-31E 9

10 Type name and specification code Data Acquisition Unit DA100 Model DA100 Type Software Power Supply Power Inlet & Power Cable Optional Features -1-2 Suffix Code D F H R S W Y Optional Code /M1 /M3 /FC Description Data acquisition unit Stand-alone type Expandable type DARWIN DAQ 32 for IBM PC-AT 100 VAC to 240 VAC 12 VDC to 28 VDC (DC power supply only) (always specify Y for the power cable) 3-pin power inlet w/ul, CSA cable 3-pin power inlet w/vde cable 3-pin power inlet w/ccc cable 3-pin power inlet w/saa cable 3-pin power inlet w/bs cable 3-pin power inlet w/screw terminal Dedicated connector for DC power supply w/o power cable Math function (including RRJC) Report function DARWIN DAQ 32 is supplied with floppy disks Subunit DS400/DS600 Model Suffix Code DS400 DS600 Type -00 Power Supply -1-2 Power Inlet & Power Cable D F H R S W Y Optional Code Description 4 slots subunit for inputs and alarm output 6 slots subunit for inputs and alarm output Always VAC to 240 VAC 12 VDC to 28 VDC (DC power supply only) (always specify Y for the power cable) 3-pin power inlet w/ul, CSA cable 3-pin power inlet w/vde cable 3-pin power inlet w/ccc cable 3-pin power inlet w/saa cable 3-pin power inlet w/bs cable 3-pin power inlet w/screw terminal Dedicated connector for DC power supply w/o power cable 10

11 Input Model Code DU DU DU DU DU DU DU DU DU DU DU DU DU DU DU DU DU DU DU DU DU Description 10ch universal input (DCV/TC/DI & RTD) 20ch universal input (DCV/TC/DI & RTD) 30ch universal input (DCV/TC/DI & RTD) 10ch universal input (DCV/TC/DI & RTD) 20ch universal input (DCV/TC/DI & RTD) 30ch universal input (DCV/TC/DI & RTD) 10ch DCV/TC/DI input 20ch DCV/TC/DI input 30ch DCV/TC/DI input 10ch DCV/TC/DI input 20ch DCV/TC/DI input 30ch DCV/TC/DI input 10ch ma input 10ch ma input Power monitor for single phase Power monitor for 3 phase 10ch strain input (120 Ω) 10ch strain input (350 Ω) 10ch strain input (External bridge box) 10ch pulse input 10ch DI input Terminal NDIS Other Model Code DT DT DT DT DT DT DT DT DT Description 2 alarm, 12 remote, fail/chart end terminal 4 alarm relay output (transfer contacts) terminal 10 alarm relay output (make contacts) terminal GP-IB interface RS-232-C interface RS-422-A/RS-485 interface Ethernet interface 10 channels, 1-5 V output retransmission 2 channels, 4-20 ma output retransmission 11

12 Accessories Model Code DV DV DV DV DV DC DV DV DV DV DV DV DV DV DV DV DV DV DV DV DV DV DV DV DV DV DV DV DV Description Extension Extension base unit Extension cable (0.5 m) Extension cable (1 m) Extension cable (2 m) Extension cable (5 m) Extension cable (10 m) Extension cable (20 m) Extension cable (50 m) Extension cable (100 m) Extension cable (200 m) Extension cable (300 m) Extension cable (400 m) Extension cable (500 m) Cable adapter Shunt resistor 10 Ω for screw input terminal Shunt resistor 10 Ω for clamped input terminal Shunt resistor 100 Ω for screw input terminal Shunt resistor 100 Ω for clamped input terminal Shunt resistor 250 Ω for screw input terminal Shunt resistor 250 Ω for clamped input terminal Rack mount kit (DA100 exp./ds400) for ANSI Rack mount kit (DA100 stand./ds600) for ANSI Strain conversion cable AC adapter W/UL, CSA cable AC adapter W/VDE cable AC adapter W/SAA cable AC adapter W/BS cable AC adapter W/CCC cable Package software Model Code DP WX102/CD1 WX101/CD1 Description DARWIN DAQ 32 software (Windows XP/Vista/7) (comes standard) DARWIN DAQ 32 Plus software (Windows 2000/XP/Vista/7) (optional) DAQLOGGER for multi-channel data logging software (Windows 2000/XP/Vista/7) (optional) 12

13 Wiring Input Signal Lines (to Universal and DCV/TC/DI input s) Terminals type terminal b - B + A DC voltage TC contact RTD* type terminal A B b + - *There are no RTD input terminals on the DCV/TC/DI input. Wiring Diagram DC voltage input/di input (contact) - + DC input DC voltage input - + DC current input - TC input - + RTD input b B Shunt resistor Note:For 4 to 20 ma input, shunt resistance value should be 250 Ω ± 0.1% A Compensation lead 10 Ω* max./leadwire Three wire resistances should be approx. equal. *10 Ω max. for Pt 100 Ω and Pt 50 Ω, 1 Ω max. for Cu 10 Ω. b A B Wiring Alarm Output SIgnal Lines (to DI/DO and Alarm output s) Terminals NO C NC DT NO C NC Contact capacity: 250 VDC/0.1 A (with a resistor load) 250 VAC/2 A (with a resistor load) 30 VDC/2 A (with a resistor load) Fail output: becomes de-activated when an error is detected in the system. 1 2 Fail output (transfer contact) Remote control input Can be used for event/action function only when the /M1 option of DA100 is specified. Alarm output (transfer contact) DT NO C Alarm output (transfer contact) Alarm output (transfer contact) DT Alarm output (make contact) 13

14 Location and Location Number (Channel Number, Alarm Output Number, DI/DO Number) The location numbers correspond to channel numbers for locations where the input is connected, to alarm output numbers for locations where the alarm output is connected, and to DI/DO numbers for locations where the DI/DO is connected. In case of the DA100 Stand-alone type The location numbers correspond to the location of each as shown in the figure below. Module 5 (Location numbers:051 to 060) Module 4 (Location numbers:041 to 050) Module 3 (Location numbers:031 to 040) Module 2 (Location numbers:021 to 030) Module 1 (Location numbers:011 to 020) Module 0 (Location numbers:001 to 010) In case of the DA100 Expandable type The unit number (the number of the main unit is fixed at I ) and location numbers correspond to the location of each as shown in the figure below. Module 3 (Location numbers:131 to 140) Module 2 (Location numbers:121 to 130) Module 1 (Location numbers:111 to 120) Module 0 (Location numbers:101 to 110) Main unit Input s cannot be connected. Unit No.:I Module 5 (Location numbers:051 to 060) Module 4 (Location numbers:041 to 050) Module 3 (Location numbers:031 to 040) Module 2 (Location numbers:021 to 030) Module 1 (Location numbers:011 to 020) Module 0 (Location numbers:001 to 010) Subunit DS600 Unit No.:0 Module 3 (Location numbers:131 to 140) Module 2 (Location numbers:121 to 130) Module 1 (Location numbers:111 to 120) Module 0 (Location numbers:101 to 110) Subunit DS400 Unit No.:1 14

15 Name and Function of Each Part DA100 Stand-alone type (DA100-1) Installation holes Module connector DA100 Expandable type (DA100-2) holes for installation Power switch Function grounding terminal (below power switch) Feet Status indicator Power connector (when specifying W, changed to screw terminal) (when specifying Y, changed to dedicated connector) Holes for fastening the feet Module connector Lid covering the extension cable connector Subunit DS400 holes for installation Power switch Function grounding terminal (below power switch) Feet Status indicator Installation holes Power connector (when specifying W, changed to screw terminal) (when specifying Y, changed to dedicated connector) Holes for fastening the feet Module connector Switch to set the unit number holes for installation Power switch Function grounding terminal (below power switch) Feet Lid covering the extension cable connector Status indicator Installation holes Power connector (when specifying W, changed to screw terminal) (when specifying Y, changed to dedicated connector) Holes for fastening the feet 15

16 Subunit DS600 Installation holes Module connector Lid covering the extension cable connector holes for installation Switch to set the unit number Power switch Function grounding terminal (below power switch) Feet Status indicator Power connector (when specifying W, changed to screw terminal) (when specifying Y, changed to dedicated connector) Holes for fastening the feet Rack Mount Fitting (ANSI/EIA) DA100 expandable type/ds400 subunit DA100 stand-alone type/ds600 subunit

17 Dimensional Drawings DA100 Stand-alone type/subunit DS600 Unit: mm DA100 Expandable type/subunit DS If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the tolerance is ±0.3 mm. Subject to change withut notice. 17

Panel Meters and Controllers Modular Panel Meter Type EDM 35

Panel Meters and Controllers Modular Panel Meter Type EDM 35 Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800 Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

J TB/TW Temperature limiter, temperature monitor

J TB/TW Temperature limiter, temperature monitor JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net

More information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus

More information

How to Use the PHF Digital Memory System

How to Use the PHF Digital Memory System Type: PHF Long Term Record Data Saving 4years in Compact Flash (In case of using 512MB Compact Flash) Saved Data playback Saved data in Memory card can be easily called out and played back on display (1Base-T)

More information

Series Six Plus Programmable Controller

Series Six Plus Programmable Controller Series Six Plus Programmable Controller Gl?K-0147B June 1989 Central Processor Unit 8-Slot Rack 1l-Slot Rack General Description The Central Processor Unit (CPU) for the Series Six Plus Programmable Logic

More information

Programmable Terminal. NPSeries. Easy Setup with the Low-cost, Compact NP Series

Programmable Terminal. NPSeries. Easy Setup with the Low-cost, Compact NP Series Programmable Terminal NPSeries Easy Setup with the Low-cost, Compact NP Series Simpler and More Versatile.OMRON s Compact NP Series Connect! Easier connection to OMRON PLCs and Temperature Controllers,

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Ordering Information. Cylindrical Proximity Sensor E2E/E2E2

Ordering Information. Cylindrical Proximity Sensor E2E/E2E2 Cylindrical Sensor E2E/E2E2 A New Series of Easy-to-use and Tough E2E/E2E2 Models Long-size E2E2 Sensor Conforms to CENELEC Ideal for a variety of applications. With a metal connector that can be tightened

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

General Specifications

General Specifications General Specifications GS 33K50E20-50E Models AFV40S, AFV40D Field Control Unit Duplexed Field Control Unit (for Vnet/IP and FIO, with Cabinet) GENERAL This GS covers the hardware specifications of the

More information

6ES7313-5BF03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A

6ES7313-5BF03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A 6ES7313-5BF03-0AB0 Page 1 Product data sheet 6ES7313-5BF03-0AB0 SIMATIC S7-300, CPU 313C, COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO 1 PT100, 3 FAST COUNTERS (30 KHZ), INTEGRATED 24V DC POWER SUPPLY,

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

RY2 miniature industrial relays

RY2 miniature industrial relays 6 RY2 Relays of general application For plug-in sockets, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting Flat insert connectors - faston x 0,5 mm Recognitions, certifications, directives: RoHS,

More information

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current. Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.

More information

Shunt lock function 3066

Shunt lock function 3066 Version: January 2004 Contents Alarm System Activation unit Deactivation unit Digital locking cylinder or Smart Relay 1.0 Method of Operation 4 1.1 General 4 1.2 Turning the Alarm System On 4 1.3 Turning

More information

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate 1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration

More information

40.3. Control Relays and Timers

40.3. Control Relays and Timers .3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories

More information

DCS Input/Output Relay Card Series

DCS Input/Output Relay Card Series Input/Output Relay Card Series I/O RELAY CARD (with loopback test function) 8N The 8N series I/O Relay Cards easily and quickly standardize and facilitate installation of the relay board. Loopback test

More information

Long sensing range. Most suitable for conveyor lines and parking lot applications. 10 m 32.808 ft (Red LED)

Long sensing range. Most suitable for conveyor lines and parking lot applications. 10 m 32.808 ft (Red LED) NX SERIES Compact Multi-voltage Photoelectric Power Supply Built-in Multi-voltage photoelectric sensor usable worldwide Conforming to ow Voltage and EMC Directive Multi-voltage The NX series can operate

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

Tilt switches N3 / N4... MEMS technology, one or two axis. Use. Options. + long lifetime and highly reliability due to mechanism-free MEMS technology

Tilt switches N3 / N4... MEMS technology, one or two axis. Use. Options. + long lifetime and highly reliability due to mechanism-free MEMS technology Tilt switches MEMS technology, one or two axis N3 / N4... + long lifetime and highly reliability due to mechanism-free MEMS technology + combinable output signals + one or two axis measurement + tilt range

More information

EQUIPMENT SPECIFICATIONS

EQUIPMENT SPECIFICATIONS EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access

More information

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in 891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000 Electrical Specification for: CPCI-3U-AC-300W-R Rugged 300W AC Input 3U CompactPCI Power Supply Telkoor Part Number: 900-4602-0000 GENERAL SCALE RELEASE DATE 12/9/06 SHEET 1 OF 6 REVISION HISTORY Rev Level

More information

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES Auto-tune PID Temperature Controller FEATURES Easy-to-use Fuzzy modified PID heat & cool control Fast A-D sampling rate (5 times/s) Universal input (PT100, thermocouple) with high accuracy 18-bit A-D Analog

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5 Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis

More information

General Specifications

General Specifications General Specifications List of RoHS (2011/65/EU) Directive Compliant Products GS 04A01A01-00EN Overview This is a list of recorder and controller products that support the RoHS (2011/65/EU) directive.

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

IPThermo206G. Offline/online data collector, SMS alarm sender, watchdog terminal for IPThermo Pro network

IPThermo206G. Offline/online data collector, SMS alarm sender, watchdog terminal for IPThermo Pro network IPThermo206G Offline/online data collector, SMS alarm sender, watchdog terminal for IPThermo Pro network IPThermo 206G is the central data handling terminal of the IPThermo Pro measurement network. This

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

Appearance Type Setting distance Sensing area Model Remarks Camera with lighting. 34mm to 49mm 5mm x 4.9mm to 9mm x 8.

Appearance Type Setting distance Sensing area Model Remarks Camera with lighting. 34mm to 49mm 5mm x 4.9mm to 9mm x 8. ZFX-C/25-CD Easy Vision Touch, Connect & Go Easy vision intuitive teach & go user interfaces Live built-in LCD touch monitors for setup and iediate feedback Counication centralized setup & inspection via

More information

How To Use A Ds340 (Dsp)

How To Use A Ds340 (Dsp) Ideal for monitoring dust levels in the exhaust gas of industrial combustion or air filtration processes. Innovative Dynamic Detection Principle (DDP) measurement technique Immune to gradual reductions

More information

NX safety stand-alone

NX safety stand-alone NX-S@ NX safety stand-alone stand-alone into machine automation Expandable safety system up to 32 safety connections or 63 standard connections controller flexible system lets your freely mix safety I/O

More information

Adjustment functions for both span and shift have been incorporated

Adjustment functions for both span and shift have been incorporated SENSORS FOR SERIES LED Type Wafer Alignment Sensor FX-0-F FT-F9 FD-F7 EX-F70/F60 M SH-7 FD-L4 M-DW The use of a safe LED light beam now allows for high precision detection with a resolution of 0!m (.8

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

Digital input modules

Digital input modules 8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

Computer Controlled Generating Stations Control and Regulation Simulator, with SCADA SCE

Computer Controlled Generating Stations Control and Regulation Simulator, with SCADA SCE Technical Teaching Equipment Computer Controlled Generating Stations Control and Regulation Simulator, with SCADA SCE EDIBON SCADA System Teaching Technique used 4 5 2 Data Acquisition Board Cables and

More information

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component. Overview Switch and button modules The dimensions of the switch and button modules are adapted to the electronic components in the integral housing. The modules are equipped with the universal clip-on

More information

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES AC averaging technique used to rectify, amplify, and filter 50 Hz to 400 Hz sine-wave signals. Accepts inputs of between 20 mv to 550 V rms to give

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

Long Distance Industrial Wireless Transmitters and Receivers

Long Distance Industrial Wireless Transmitters and Receivers Long Distance Industrial Wireless s and Receivers Up to 450 m (1500') Line of Sight Range UWXL Series U Thermocouple, RTD, Temperature, RH, ph, Process Voltage/ Current and Input Models U J, K, T, E, R,

More information

CQM1-SF200/CS1W-SF200

CQM1-SF200/CS1W-SF200 Safety Relay Unit ( I/O Unit Type) CQM1-SF200/CS1W-SF200 CSM_CQM1-SF200_CS1W-SF200_DS_E_2_1 A Safety Relay Unit That Functions as a I/O Unit. Less Installation Space and Wiring Required. Safety Relay Unit

More information

The DL-1000/2000 series offers further breakthroughs in data acquisition and processing.

The DL-1000/2000 series offers further breakthroughs in data acquisition and processing. Series The hardware components can be freely combined to support the different types of sensors, allowing you to build a compact test system that can best meet your measurement needs, especially for actual

More information

g9sp Programmable Safety controllers compact Stand-Alone Programmable controller NEW! example of System configuration G9SP

g9sp Programmable Safety controllers compact Stand-Alone Programmable controller NEW! example of System configuration G9SP Programmable Safety controllers g9sp G9SP compact Stand-Alone Programmable controller Stand-alone safety controller for small and mid-sized machinery Easy programming for complex safety control Three types

More information

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES TSI and TSI logo are registered trademarks of TSI Incorporated. SmartTune is a trademark of TSI Incorporated. THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES IFA 300 Constant Temperature Anemometry

More information

Color Mark Sensor with Red or Green LED E3S-VS

Color Mark Sensor with Red or Green LED E3S-VS Color Mark Sensor with Red or Green LED Rugged IP67 Color Mark Sensor 1 ms response time Detects a wide variety of color marks PNP or NPN output ls Light-on/ Dark-on operation, wire selectable Vertical

More information

Multi-Range Programmable DC Power Supplies 9115 Series

Multi-Range Programmable DC Power Supplies 9115 Series Data Sheet 1200 W Multi-Range DC Power Supplies Features & Benefits Any 9115 series model can replace several supplies on your bench or in your rack. Unlike conventional supplies with fixed output ratings,

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

General Specification

General Specification General YS1310 Indicator with GS 01B08D01-01E G GENERAL The YS1310 Indicator with s is an input indicator that has alarms with two inputs Two loops can be displayed simultaneously A high limit alarm, low

More information

zseries 18-Slot Chassis 18-Slot 3U PXI Express Chassis with AC Up to 8 GB/s

zseries 18-Slot Chassis 18-Slot 3U PXI Express Chassis with AC Up to 8 GB/s TECHNICAL SPECIFICATIONS zseries 18-Slot Chassis 18-Slot 3U PXI Express Chassis with AC Up to 8 GB/s 2015 LitePoint, A Teradyne Company. All rights reserved. The LitePoint zseries 18-slot chassis is an

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

High Power Programmable DC Power Supplies PVS Series

High Power Programmable DC Power Supplies PVS Series Data Sheet High Power Programmable DC Power Supplies The PVS10005, PVS60085, and PVS60085MR programmable DC power supplies offer clean output power up to 5.1 kw, excellent regulation, and fast transient

More information

4-Channel Thermometer / Datalogger

4-Channel Thermometer / Datalogger USER GUIDE 4-Channel Thermometer / Datalogger RTD and Thermocouple Inputs Model SDL200 Introduction Congratulations on your purchase of the Extech SDL200 Thermometer, an SD Logger Series meter. This meter

More information

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no. 6814053.

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no. 6814053. PROFINET slave Integrated Ethernet switch 100 Mbps supported 2 x M12, 4-pin, D-coded, Ethernet fieldbus connection Glass-fiber reinforced housing Shock and vibration tested Potted module electronics Protection

More information

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850

More information

VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS

VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS CEMB SPA Via Risorgimento, 9 Mandello del Lario (Lc), Italy stm@cemb.com www.cemb.com INSTRUMENT FOR MONITORING VIBRATIONS OF FANS INSTALLED IN ROAD

More information

Automatic Transfer Switch-Controller ATS-C by Eaton. Automatic Transfer Switch- Controller ATS-C 96 and C 144

Automatic Transfer Switch-Controller ATS-C by Eaton. Automatic Transfer Switch- Controller ATS-C 96 and C 144 Automatic Transfer Switch-Controller ATS-C by Eaton Automatic Transfer Switch- Controller ATS-C 96 and C 144 Supply safety for low voltage energy distribution. Automatic Transfer Switch-Controller ATS-C

More information

Brushless DC Motors Intro duction BLF BLU BLH Installation. Brushless DC Motors. DC Input. AC Input DC Input. BLH Series. Page. BLH Series B-52 B-51

Brushless DC Motors Intro duction BLF BLU BLH Installation. Brushless DC Motors. DC Input. AC Input DC Input. BLH Series. Page. BLH Series B-52 B-51 DC Input BLH Series Brushless DC Motors Intro duction BLF BLU BLH Installation C Input DC Input Page BLH Series B-52 B-51 RoHS-Compliant Brushless DC Motor and Package BLH Series The BLH Series combines

More information

PC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS

PC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS PC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS FRANCE Head office USA 4 Rue du Bois Chêne le loup Parc d Activité de Brabois 54 500 VANDOEUVRE LES NANCY (33) 0383442413, Fax (33) 0383443797

More information

I STAR COMPUTER CO., LTD

I STAR COMPUTER CO., LTD I STAR COMPUTER CO., LTD Mini Redundant Power Supply 300W+300W for IPC-Computer Model No. TC-300R8 Table of content 1. Introduction...1 2. Specification 2.1 Input Voltage...1 2.2 DC Output...1 2.3 PS-ON

More information

Physical Specifications (Custom design available.)

Physical Specifications (Custom design available.) Helmholtz Coils A useful laboratory technique for getting a fairly uniform magnetic field, is to use a pair of circular coils on a common axis with equal currents flowing in the same sense. For a given

More information

Tubular Analog model resolution: 0,5 mm (SLOW mode), 1 mm (FAST mode) Right angle Repeatibility: 0,7 mm Vdc

Tubular Analog model resolution: 0,5 mm (SLOW mode), 1 mm (FAST mode) Right angle Repeatibility: 0,7 mm Vdc Ultrasonic sensors for high precision detection of clear and transparent objects Clear object detection, inspection on transparent or highly reflective film and liquid level measurement Standard M18 tubular

More information

How To Power A Schen

How To Power A Schen Automation / Mini Type SCH32F Hollow Shaft Encoder - Ø 32 mm Hollow Bore: Ø 6 mm to Ø 3/8 inch Resolution up to 5000 ppr IP 65 (IP 50 for IDC connector option) Electrical Specifications Code: Resolution:

More information

3500/22M Transient Data Interface

3500/22M Transient Data Interface 3500/22M Transient Data Interface Bently Nevada* Asset Condition Monitoring Description The 3500 Transient Data Interface (TDI) is the interface between the 3500 monitoring system and GE s System 1* machinery

More information

Standard Cables (Without electromagnetic brake, with electromagnetic brake) CC010ES-2. 1 m CC020ES-2. 2 m CC030ES-2. 3 m CC050ES-2.

Standard Cables (Without electromagnetic brake, with electromagnetic brake) CC010ES-2. 1 m CC020ES-2. 2 m CC030ES-2. 3 m CC050ES-2. Motorized Actuators Motor Cables EZS /EZS for Clean Room Use This cable is a dedicated cable for connecting the linear slide of the EZS Series and EZS Series for Clean Room Use with the controller. Use

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Material: Weight: Bearing Life: Shaft Speed: Starting Torque: Mass Moment of Inertia: Shaft Loads:

Material: Weight: Bearing Life: Shaft Speed: Starting Torque: Mass Moment of Inertia: Shaft Loads: Automation / Mini Type SCH32F Hollow Shaft Encoder - Ø 32 mm Hollow Bore: Ø 6 mm to Ø 3/8 inch Resolution up to 5000 ppr IP 65 (IP 50 for IDC connector option) Electrical Specifications Code: Resolution:

More information

SENSORS. Fiber Optic Sensors - S70. Advanced fiber optic amplifiers for high speed and low contrast applications

SENSORS. Fiber Optic Sensors - S70. Advanced fiber optic amplifiers for high speed and low contrast applications Fiber Optic Sensors - S7 Advanced fiber optic amplifiers for high speed and low contrast applications DIN rail mountable models with dual digital displays speed models: 2 μs...5 ms Super high speed models:

More information

ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL

ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL INTRODUCTION... 2.. TECHNICAL DATA... 3 ACCESSORIES... 5. INSTALLATION... 7 OPERATION... 12. TECHNICAL INFORMATION... 13 MAINTENANCE... 14. CONFIGURATIONS...

More information

SINEAX U553 Transducer for AC Voltage

SINEAX U553 Transducer for AC Voltage With power supply RMS value measurement Carrying rail housing P/0 Application he transducer SINEAX U55 (Fig. ) converts a sinusoidal or a distorted AC voltage into a load independent DC current or a load

More information

Frequency selective monitoring and logging of environmental electromagnetic fields

Frequency selective monitoring and logging of environmental electromagnetic fields FREQUENCY SELECTIVE EMF AREA MONITOR AMS-8060 Frequency selective monitoring and logging of environmental electromagnetic fields Up to 20 fully programmable frequency bands Real built-in spectrum analyser

More information

Table of Contents. TransformerIQ FAQs 1

Table of Contents. TransformerIQ FAQs 1 [12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is

More information

Radiant Temperature Sensor TY7321

Radiant Temperature Sensor TY7321 AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional

More information

Multifunction devices

Multifunction devices devices devices devices, electronic Type Page LED multifunction displays pulse, frequency, time (DC) Codix 524 240 pulse, frequency, time (AC+DC) Codix 544 243 LCD multifunction preset counters 1 or 2

More information

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

How To Read A Pipe From A Sensor

How To Read A Pipe From A Sensor Liquid Level Sensor Installation on pipes. Sensing by means electrostatic capacity and is not influenced by the color of the pipe or liquid. Available in 8 to mm dia. and to mm dia. models to enable sensing

More information

SENSORS. Miniature Sensors - S3Z. Advanced line of miniature Asian style of photoelectric sensors. 40-300 mm background suppression

SENSORS. Miniature Sensors - S3Z. Advanced line of miniature Asian style of photoelectric sensors. 40-300 mm background suppression Advanced line of miniature Asian style of photoelectric sensors 4-3 background suppression.7 m proximity, 15 with narrow beam 4 m polarized retroreflective 3 m LASER through beam Standard 3-wire output

More information

Uninterruptible Power Supply

Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features

More information

Agilent 4338B Milliohm Meter

Agilent 4338B Milliohm Meter Agilent 4338B Milliohm Meter 10 µω to 100 kω Technical Overview Introduction Ideal for precise measurements of extremely low resistances using an ac test signal, the Agilent Technologies 4338B suits bench-top

More information

MOUNTING AND OPERATING INSTRUCTIONS

MOUNTING AND OPERATING INSTRUCTIONS MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall

More information

Appearance Type Setting distance Sensing area Model Remarks Camera with lighting. 34mm to 49mm 5mm x 4.9mm to 9mm x 8.

Appearance Type Setting distance Sensing area Model Remarks Camera with lighting. 34mm to 49mm 5mm x 4.9mm to 9mm x 8. ZFX-C10/15-CD Easy Vision Touch, Connect & Go Easy vision intuitive teach & go user interfaces Live built-in LCD touch monitors for setup and iediate feedback Counication centralized setup & inspection

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual 5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

How To Use A Flowmeter

How To Use A Flowmeter INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information