CORROSION OF BOILER TUBES SOME CASE STUDIES 1

Size: px
Start display at page:

Download "CORROSION OF BOILER TUBES SOME CASE STUDIES 1"

Transcription

1 ABSTRACT CORROSION OF BOILER TUBES SOME CASE STUDIES 1 Anees U. Malik, Ismail Andijani, Mohammad Mobin, Fahd Al-Muaili and Mohammad Al-Hajri Saline Water Desalination Research Institute Saline Water Conversion Corporation (SWCC) P O Box 8328, Al-Jubail Kingdom of Saudi Arabia rdc@swcc.gov.sa Failure of boiler tubes by corrosion attack has been a familiar phenomenon in power plants resulting in unscheduled plant shut down, in consequence, there are heavy losses in industrial production and disruptions to civil amenities. The failure of boiler tubes appears in the form of bending, bulging, cracking, wearing or rupture, causing leakage of the tubes. The failure can be caused by one or more modes such as overheating, stress corrosion cracking (SCC), hydrogen embrittlement, creep, flame impingement, sulfide attack, weld attack, dew point corrosion, etc. In this presentation, information related to boiler tube failures are given in the form of some case studies. The case studies are comprised of failures occurred due to SCC, overheating, flame impingement and creep. The description of the failure, possible causes and mechanism(s) will be presented followed by conclusions and recommendations. INTRODUCTION The failure of industrial boiler has been a prominent feature in fossil fuel power plants. The contribution of one or several factors appears to be responsible for failures, culminating in the partial or complete shut down of the plant resulting in heavy losses in industrial production and disruption to civil amenities. The use of inferior tube materials, use of high sulfur or/and vanadium containing fuels, exceeding the design limit of temperature and pressure during operation, poor maintenance and aging are some of the factors which have a detrimental effect on the performance of materials of construction. The failure of boiler tubes appeared in the form of bending, bulging, 1 Published in the Proceeding of 4 th SWCC Acquired Experience Symposium held at Jeddah in 2005, pp

2 wearing or rupture, decarburization, carburization causing leakage of the tubes. The failure can be caused by one or more modes such as overheating, SCC, hydrogen embrittlement, creep, flame impingement, sulfide attack, weld attack, dew point attack, hot corrosion, etc. In the present paper, information related to boiler tube failures are given in the form of five cases studies. CASE - I : Flame Impingement of Water Wall Tubes - Shoaiba Phase- II During unit reliability operation by Shoaiba plant engineers, flame impingement test was conducted on water wall tubes for a few hours and it was found that flame touched the rear wall of the furnace. It was decided by the Plant management to send some tubes to R&D Center for investigating the effect of flame impingement on water wall tubes. Physical Inspection Out of the 6 tubes provided for analysis, 3 tubes (# 1 to 3) were from flame impingement area, 2 tubes (#4 and 5) from non-flame impingement area and one tube (#6) was unused tube for comparison purposes (Fig. 1). The tubes were in services since August 2000 at variable boiler load conditions. All the tubes were electrical resistance welded seam (ERWS), however, the location of the seam was not visible by naked eye. The position of the seam in the tube was located by grinding, polishing and deep etching of the tube. The original thickness of the tube was 6.2 mm and the material composition corresponded to SA 178C. Steam side (internal surface) of the tubes (#1 to 5) contains very thin adherent dark grey colored scales. The results of analysis steam side scales indicate high concentrations of Cu (19-28%) and Ni (6 to 11%) along with Zn, P, Ca and Al in significant concentrations (Table 1).

3 There is much higher concentration of Cu and Ni in steam side scales in tubes from flame impingement zone. All these compounds are contaminated with magnetite scales. The analysis of fire side (external) scales shows the presence of S and V. The source appears to be fuel (Table 1, Fig.2). Microstructural Studies The microstructures of the cross-sections of unused, non-flame impingement zone and flame impingement zone tubes were studied. The microstructures of the cross-sections of all the tubes were observed at the seam area. In general, the microstructures of the seam areas show contour shaped structures in which contours in opposite directions can be seen along a vertical axis. Some typical microstructures are discussed below: (i) Unused Tube (#6): Contour type with well defined central line structure is pearlitic-ferritic type with no decarburization layer (Fig. 3). (ii) Non-Flame Impingement Zone Tube (#4 and 5) : Diffused line along the opposite contours with no decarburization (Fig. 4). (iii) Flame Impingement Zone Tubes (# 1 to 3): There are following cases: (a) When the seam is not facing flame directly, there is a contour structure but no evidence of decarburization (Fig. 5). (b) When the seam is directly facing the flame (#1), refinement of the grains along the vertical axis can be seen with a well-defined decarburized layer (Fig. 6). This tube appears to be most affected by flame impingement. In all the tubes, there is reduction in wall thickness (5 to 8%) after operation. Conclusions 1. No decarburization was found in the unused tube and non-impingement zone tubes. However, in flame impingement zone tubes, a well-defined decarburized layer is present in area between the opposite contours. 2. A clear decarburization layer is probably only when the seam of the boiler tube is directly facing the flames.

4 CASE - II : Creep Failure of Boiler Reheater Tubes in a Power Plant R&D Center received 2 reheater boiler tubes (#3 and 4) for analysis. The boilers were commissioned about 24 years ago and had been in operation for more than 150,000 hrs. Following were the salient features of the boiler tubes: Tube material : Medium carbon steel SA 192 Nature of the tube : Seamless Outer diameter : mm Nominal thickness : 3.4 mm Working pressure : 345 psig Metallography Photograph of the reheater tubes # 3 and 4 is shown in as received condition (Fig. 7). External surface appeared reddish brown. Steam Side Scales The steam side scales contain dark grey magnetite. The inner surface is covered with small and big pits with hematite stringers (Figs. 8 and 9). Tubes are shown after cleaning (Fig. 10). Microstructural Studies The microstructures of the boiler tubes (#3 and 4) were studied by observing the structures of cross-sections through a photometallurgical microscope. The main observations were as follows: (i) Cross-section of boiler unit # 3, steam side: Ferritic-pearlitic structure, there is dispersion of carbides and accumulation at grain boundaries (Fig. 11). (ii) Cross-section of boiler unit #3, fire side: Carbides are dispersed in ferrite matrix and precipitated at the grain boundaries (Fig. 12). (iii) Cross-section of boiler unit # 4, steam side: Pearlitic structure. Dispersion of carbides in the matrix, precipitation of carbide at the grain boundaries and spheroidization of carbides. Presence of voids is also indicated.

5 (iv) Cross-section of boiler unit # 4, fire side: Pearlitic structure. Huge dispersion of carbides, spheroidization and accumulation of carbide at the grain boundaries (Fig. 13). Discussion Microstructural studies reveal the following features: (i) Structure is ferritic-pearlitic (ii) Dispersion of carbides in the ferritic matrix (iii) Accumulation of carbides at the grain boundaries (iv) Spheropidization of carbides (v) Presence of voids in some cases The afore-mentioned observations provide strong evidence for a creep induced failure of type II which appeared to be dominant during current operation of the boiler. No cracking or leakage was found in the tube which indicates that stage III creep has not yet reached, so tubes can be used for some more time. Scale density and scale thickness values of the boiler tubes are high but still they can be operated without cleaning. Conclusion The results of metallographic studies point out the involvement of creep type II behavior in reheater tubes from boiler unit # 3 and 4. Recommendation As the reheater tubes from boiler unit # 3and 4 appear to be under deterioration due to the influence of creep type II behavior. Therefore, the replacement of the tubes shall be required in near future. A better tube material like a low alloy steel shall be a better choice at the operating boiler temperature above 500 o C.

6 CASE - III : Failure of High Temperature Superheater Tube of Boiler # 63, Al-Jubail Plant The boiler # 63 had been in operation for more than 15 years. It was found that superheater tube # 67 had failed at 2 locations. The failed portions were from the same pendant. The first portion of the failure was found at the bottom of the first loop near the upstream side of the first bend (Fig. 14). This portion was sent to ANSALDO for investigation. The second portion of the failure was found at the bottom portion of the third loop upstream of the weld point (Fig. 15). This portion of the tube consisting of outlet and inlet tubes were sent to R&D Center for investigation. The pipe sheared at the bottom portion. From the photograph, it is observed that the failure of the tube occurred by rupture at the bottom portion of the third loop upstream side of the weld joint (Fig. 16). Specifications of the unit # 63 boiler are given in Table 2. SEM Studies The inner section of the ruptured tube outlet and inlet are marked 1 to 5 indicating different locations. (Fig. 17). The fractography of the tube sample at locations 1 and 3 was carried out by SEM. Whilst at location 1 (expanded portion) there are clear indications of intergranular cracking originated from the outside surface (Fig. 18), the cracks at location 3 (protruded portion) are intergranular as well as transgranular (Fig. 19). The cracks at location 5 (inlet of tube) are transgranular (Fig. 20). All cracks showed multiple direction of propagation which are typically arising out of stresses in the scales and the metal at high temperature. Quantification of the Scales The quantification of scale densities carried out near fracture surface of the tubes, as determined by acid dissolution technique was found to be 483 and 219 mg/cm 2 for

7 superheater inlet and outlet tubes (both third loop), respectively. The scale densities seem to exceed the limits set by Otker Jonas for chemical cleaning of the boiler tubes. Discussion The presence of thick scale deposition in the fractured boiler tubes would result in overheating leading to fracture under operating pressure-temperature conditions. The presence of trans and intergranular fracture in SEM further proves the consequences of thick scale deposition over steam side. Conclusions (i) Optical and SEM studies and quantification of the scale densities indicate the cause of superheater tube is overheating. (ii) Overheating of the tube at the bottom of 3 rd loop near the upstream side is due to heavy scale deposition. Recommendations (i) In view of abnormal deposition of scales at various locations of superheater tubes, chemical cleaning of all high temperature superheater tubes be carried out to avoid failure in future. (ii) Periodic evaluation of superheater tubes for its scale density and tube life should be planned in every maintenance schedule in consultation with R&D Center. CASE - IV : Failure Analysis of Failed Generation Bank Tube in Boiler # 4, Madina-Yanbu Plant Medina-Yanbu plant has 5 identical boilers and the manufacturer is MHI. Boiler No. 4 has failure at the generation bank tube zone. The boiler had been in service for approx 23 years. T&I report indicated rupture of the tube # 9 and leakage in the tube # 2 (at 6 O clock position). Figure 21shows drawing of the boiler front indicating the location of generation bank tubes.

8 Physical Examination Figure 22 shows ruptured generation bank tube in as received condition. Figure 23 shows inside water drum at the end of ruptured generation bank tube and Figure 24 shows broken away refractory laying between bank tubes and rear wall tubes. Pits and tube thinning were noticed near the ruptured side indicating localized corrosion and metal loss (Fig. 25). The pits are indicative of corrosion and thinning indicates partial dissolution of metal due to corrosion near the rupture. After removal of internal and external scales, the photograph of internal surface shows presence of small pits (Fig. 26). The corrosion inside the tube could be the result of dissolved oxygen in water which was further confirmed by heavy corrosion inside the water drum (Fig. 23). Microstructural Studies Cross-sections of the ruptured tube samples were selected for microstructural studies. Sample at the end of rupture shows transgranular crack propagation (Figs.27 and 28). Presence of S, V, Ca and K in the fire side scales (EDX analysis) indicates that fuel oil containing these impurities (Fig. 29). Due to rupture, there is contamination of S and V in the scales from the outside combustion gases ( Fig. 30). Discussion Hydrojetting is carried out during shut down by using alkali (10% NaOH) to remove heavy external deposits on the tube. The S-containing deposits are acidic in nature forming aqueous solution of acid (mainly H 2 SO 4 ) and salts by reacting with alkali. During hydrojetting of the boiler tubes, low ph liquid (ph~2) is formed as affluent where most of the liquid is drained off, some liquid remained adsorbed on the refractories. The acidic liquid adsorbed by the refractories attacked the adjacent metallic tubing. With time this gradually thinned down the metal and ultimately due to high pressure (70 mm Hg) inside the tube, rupture of the tube occurred. During the start of shut down period, the combustion gas contaminated with S also condensed as H 2 SO 4 at the dew point temperature and initiated dew point corrosion. V compounds present in the combustion gases react with scale/corrosion products in

9 presence of oxygen forming low melting vanadates which undergo flushing reaction resulting in accelerated or hot corrosion of metal. The thinning of the wall tube by residual adsorbed acid along with combination of dew point and hot corrosion resulted in rupture of the tube. Conclusion The rupture of the boiler tube occurred as a result of combination of 3 processes namely, (i) thinning of wall tube by residual adsorbed acid attack (ii) dew point corrosion and (iii) hot corrosion. Recommendations (i) Inspection of rest of the generation bank tubes, which are vulnerable to attack by acid adsorbed at the refractories should be checked for corrosion. (ii) During hydrojetting, ph of the washing affluent of the boiler tubes at different locations should be monitored and should not be below 7.5. (iii) It is advised to keep the S and V contamination level in the fuel oil to minimum by using appropriate additive. CASE - V : Failure Investigations of Boiler Tubes, Al-Khafji Plant Two pieces of wall tubes of rolled area of water drum from boiler # 200 were received for investigation by the R&D Center. The specifications of the boiler tube and operation parameters were as follows: Nature of the failure : Cracks on wall tubes just above expanded and flared Area at water drum Boiler No. : # 200 Years in service : About 13 years Drum pressure : 20 bars Tube orientation : Vertical Wall tube material : ASTM 178A Tube dimension : 60.8 mm x 3.2 mm No. of failed tubes : 8, 2 received for investigation

10 Physical Inspection Figures 31 shows photograph of the wall tubes in as received condition. In the thick walled fracture, the cracks appeared to be originating from outside. Microstructural Studies The cross-sections of the samples reveal branching associated with the cracks. The cracks are continuous, intergranular, transgranular or mixed type, running through the wall tubes (Fig. 32 and 33). EDAX Studies EDAX of the cracked area revealed presence of elements like S, V, Cl, Fe, Ni, Mo and Cu (Fig. 34). Discussion Presence of intergranular and transgranular multi-branch cracks and occurrence of thick walled fracture indicate failure caused by stress corrosion cracking (SCC). There are two principal causes that govern SCC in the boiler environment. First, the metal in the affected region must be stressed to a sufficiently higher level. Second, concentration of a specific corrodent at the stressed metal site must occur. Both the above mentioned factors are observed to play a role ion SCC of the tube. Just above the failure site a hole was detected in the super heater inlet header tube. In order to take out the tubes from the drum, huge amount of green fluid was found while removing the refractory insulation. It is quite possible that steam leaked from the superheater and might have condensed at the bottom of the furnace. The condensate dissolved the soot containing sulfur and vanadium and through the ceramic, led it seeped down to the outer surface of the drum. Due to dissolution of S and V from soot and SO 3 gas from the combustion gases, condensate must be very corrosive. Boiler wall tubes are joined to the water drum by expanding and flaring the tubes in the drum plate hole. It seems during fabrication the tube ends were not stress relieved and when these tubes with enough residual stresses came into contact with corrosive

11 condensate, a synergic interaction of tensile stress and a corrodent occurred and resulted into SCC. Conclusions Corrosive condensate formed by the condensation of leaked out steam from superheater tubes, initiated SCC of wall tubes fixed in the water drum. Recommendations (1) The boiler components should be stress free this can be done by altering operational parameters or redesigning the affected components. (2) Residual stresses can be relieved by proper annealing. (3) Presence of corrodent in boiler tube auxiliaries which is responsible for SCC, can be avoided by keeping internal surfaces sufficiently free of deposits, preventing in-leakage of condensers, heat exchangers and process steam. Table 1. Chemical Composition of External and Internal Deposits S. No. Deposits Description of Tube Parameters (weight %) Sample V Si Cr Fe Mn Cu Ni Zn Al Ca 1 External Flame Impingement Zone (fire side) 2 External Flame Impingement Zone (wall side) 3 External Non Flame Impingement Zone (fire side) 4 External Non Flame Impingement Zone (wall side) 5 Internal Flame Impingement Zone 6 Internal Non Flame Impingement Zone 0.5 < 0.1 < < 0.1 < < < 0.1 < < <

12 Table 2. Operational and Design Parameters of Boiler Unit # 63 Maximum continuous evaporation, kg/hr Maximum design pressure, Bar ga. Pressure at super heater outlet, Bar ga. Super heater steam temperature o C Feed water temp. at economizer inlet o C Air Temperature: Air heater inlet o C Air heater outlet o C Flue Gas Temperature: Furnace exist temperature o C Primary superheater inlet temperature o C Air heater inlet temperature Air heater outlet temperature o C Feed Water: Feed water inlet temperature o C Feed water pressure after regulator Bar ga Feed water temperature entering boiler drum o C Steam: Steam drum pressure Bar ga. Secondary superheater outlet pressure bar ga. Secondary superheater outlet temperature o C Design 730, o C 235 o C 72 o C 315 o C 750 o C 820 o C 360 o C 146 o C 235 o C 1 o C 312 o C o C Operation o C o C Figure 1. Photograph of fire side water wall tubes in as received conditions

13 cps 50 Fe O 10 Fe V Fe 0 Si S Cr Mn Energy (kev) Figure 2. EDX profile of external deposits (fire side) collected from the boiler tubes from non flame impingement zone Figure 3. Microstructure at the center of the weld seam in the unused tube x 100

14 Figure 4. Microstructure at the center of the weld seam in the tube # 4 from non flame impingement zone X 100 Figure 5. Microstructure at the center of the weld seam in the tube # 3 from flame impingement zone X 100 Figure 6a. Photomicrograph of boiler tube (#1) showing refined grains with evidence of decarburization (fire side) X 100

15 Figure 6b. Photomicrograph of boiler tube (#1) showing refined grains with evidence of decarburization (steam side) X100 Figure 7. Photograph of the reheater tubes, Ghazlan Unit # 3 and #4- as in received condition Figure 8. Photograph of the splitted reheater tube Unit # 3 showing steam side magnified view

16 Figure 9. Photograph of the splitted reheater tube Unit # 4 showing steam side magnified view (a) (b) Figure 10. Photograph showing (a) reheater tube Unit # 3 (steam side) after cleaning (b) reheater tube Unit # 4 (steam side) after cleaning

17 Figure 11. Photograph of a cross-section of reheater tube Unit # 3 showing steam side scales X 200 Figure 12. Photomicrograph of a cross-section of reheater tube Unit # 3 showing fire side scales X 200

18 Figure 13. Photomicrograph of a cross-section of reheater tube Unit # 4 showing central portion X200 Figure 14. Photograph showing longitudinal open crack at the bottom of I loop upstream side of the I bend of Boiler # 3

19 Figure 15. Photograph showing ruptured and sheared tube at the bottom of the 3 rd loop upstream side of boiler # 63 Figure 16. Inlet and outlet portions of the ruptured tube at the bottom of the 3 rd loop upstream of boiler # 63, HTSH Pendent 67 As received condition

20 Figure 17. Inner section of ruptured superheater tube # 63 (Outlet) 3 rd loop (HTSH Pendent # 67) Figure 18. SEM fractograph of the tube (sample location # 1) (I.G.C.)

21 Figure 19. SEM fractograph of the tube (sample location # 3) (T.G.C.) Figure 20. SEM fractograph of the tube (sample location # 5) (T.G.C.) Figure 21. Schematic drawing of the boiler front indicating the location of generation bank tubes

22 Figure 22 Ruptured generation bank tube # 9 in as received condition showing front view. Figure 23. Pictures of ruptured generation bank tube # 9 (end shown inside water drum)

23 Figure 24. Pictures of broken away refractory installed on the area between generation bank tubes and rear well tubes Figure 25. Picture of the portion of ruptured generation tube showing localized attack and metal loss Figure 26. Photograph of the ruptured tube after removal of the scales (external side) showing pitting and thinning of the tube

24 Figure 27. Photomicrograph of a cross-section of boiler tube # 9 at a location where the rupture zone ends Figure 28. SEM photograph of sample #2 showing a deep transgranular crack cps 20 Fe V O Al 5 S Cu Si Ca K V Mn Fe Ni Cu Cu Energy (kev) Figure 29. EDX profile of the outside scale deposits formed on bank generation tube # 9

25 cps 60 Fe O 10 0 Fe Al Mg Si S K K V Mn Fe Energy (kev) Figure 30. EDX profile of the scales formed at the steam side (inner) of generation bank tube # 9 Figure 31. As received cracked samples of boiler wall tube taken out from the water drum

26 Figure 32. Micrograph of the cross-section of the stress corrosion cracks in the boiler tubes shown in Fig. 41. X 200 Figure 33. Micrograph showing intergranular mode of SCC X400

27 Figure 34. Energy dispersive X-ray analysis (EDAX) of the cross-section of the cracks showing presence of S, V and Cl at the crack

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain

More information

WJM Technologies excellence in material joining

WJM Technologies excellence in material joining Girish P. Kelkar, Ph.D. (562) 743-7576 girish@welding-consultant.com www.welding-consultant.com Weld Cracks An Engineer s Worst Nightmare There are a variety of physical defects such as undercut, insufficient

More information

AUSTENITIC STAINLESS DAMASCENE STEEL

AUSTENITIC STAINLESS DAMASCENE STEEL AUSTENITIC STAINLESS DAMASCENE STEEL Damasteel s austenitic stainless Damascene Steel is a mix between types 304L and 316L stainless steels which are variations of the 18 percent chromium 8 percent nickel

More information

CURRENT EXPERIENCE IN TYPICAL PROBLEMS AND FAILURES WITH BOILER PIPING COMPONENTS AND SUPPORTS

CURRENT EXPERIENCE IN TYPICAL PROBLEMS AND FAILURES WITH BOILER PIPING COMPONENTS AND SUPPORTS A DB RILEY TECHNICAL PUBLICATION CURRENT EXPERIENCE IN TYPICAL PROBLEMS AND FAILURES WITH BOILER PIPING COMPONENTS AND SUPPORTS by James P. King, Design Manager DB Riley, Inc. Presented at the 1998 ASME

More information

North American Stainless

North American Stainless North American Stainless Long Products Stainless Steel Grade Sheet 2205 UNS S2205 EN 1.4462 2304 UNS S2304 EN 1.4362 INTRODUCTION Types 2205 and 2304 are duplex stainless steel grades with a microstructure,

More information

ATI 2205 ATI 2205. Technical Data Sheet. Duplex Stainless Steel GENERAL PROPERTIES. (UNS S31803 and S32205)

ATI 2205 ATI 2205. Technical Data Sheet. Duplex Stainless Steel GENERAL PROPERTIES. (UNS S31803 and S32205) ATI 2205 Duplex Stainless Steel (UNS S31803 and S32205) GENERAL PROPERTIES ATI 2205 alloy (UNS S31803 and/or S32205) is a nitrogen-enhanced duplex stainless steel alloy. The nitrogen serves to significantly

More information

Tube Damage Mechanism and Analysis in Feed Water Heaters

Tube Damage Mechanism and Analysis in Feed Water Heaters Tube Damage Mechanism and Analysis in Feed Water Heaters Asst. prof. Dr. Rafaa Abbas Al-Baldawi College of Engineering Al-Mustansirya University rafa_a70@yahoo.com Dr. Mohammed Najm Abdullah College of

More information

North American Stainless

North American Stainless North American Stainless Flat Products Stainless Steel Grade Sheet 310S (S31008)/ EN 1.4845 Introduction: SS310 is a highly alloyed austenitic stainless steel designed for elevated-temperature service.

More information

GENERAL PROPERTIES //////////////////////////////////////////////////////

GENERAL PROPERTIES ////////////////////////////////////////////////////// ALLOY 625 DATA SHEET //// Alloy 625 (UNS designation N06625) is a nickel-chromium-molybdenum alloy possessing excellent resistance to oxidation and corrosion over a broad range of corrosive conditions,

More information

X15TN TM. A high hardness, corrosion and fatigue resistance martensitic grade CONTINUOUS INNOVATION RESEARCH SERVICE.

X15TN TM. A high hardness, corrosion and fatigue resistance martensitic grade CONTINUOUS INNOVATION RESEARCH SERVICE. TM A high hardness, corrosion and fatigue resistance martensitic grade CONTINUOUS METALLURGICAL SPECIAL STEELS INNOVATION RESEARCH SERVICE DEVELOPMENT Enhancing your performance THE INDUSTRIAL ENVIRONMENT

More information

Evaluation of the Susceptibility of Simulated Welds In HSLA-100 and HY-100 Steels to Hydrogen Induced Cracking

Evaluation of the Susceptibility of Simulated Welds In HSLA-100 and HY-100 Steels to Hydrogen Induced Cracking Evaluation of the Susceptibility of Simulated Welds In HSLA-100 and HY-100 Steels to Hydrogen Induced Cracking R. E. Ricker, M. R. Stoudt, and D. J. Pitchure Materials Performance Group Metallurgy Division

More information

North American Stainless

North American Stainless North American Stainless Long Products Stainless Steel Grade Sheet AISI 316 UNS S31600 EN 1.4401 AISI 316L UNS S31630 EN 1.4404 INTRODUCTION NAS provides 316 and 316L SS, which are molybdenum-bearing austenitic

More information

Problems in Welding of High Strength Aluminium Alloys

Problems in Welding of High Strength Aluminium Alloys Singapore Welding Society Newsletter, September 1999 Problems in Welding of High Strength Aluminium Alloys Wei Zhou Nanyang Technological University, Singapore E-mail: WZhou@Cantab.Net Pure aluminium has

More information

ALLOY 2205 DATA SHEET

ALLOY 2205 DATA SHEET ALLOY 2205 DATA SHEET UNS S32205, EN 1.4462 / UNS S31803 GENERAL PROPERTIES ////////////////////////////////////////////////////// //// 2205 (UNS designations S32205 / S31803) is a 22 % chromium, 3 % molybdenum,

More information

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2 WASTE HEAT BOILERS CONTENTS 1 INTRODUCTION... 3 2 CONCEPTION OF WASTE HEAT BOILERS... 4 2.1 Complex Solution...4 2.2 Kind of Heat Exchange...5 2.3 Heat Recovery Units and Their Usage...5 2.4 Materials

More information

The soot and scale problems

The soot and scale problems Dr. Albrecht Kaupp Page 1 The soot and scale problems Issue Soot and scale do not only increase energy consumption but are as well a major cause of tube failure. Learning Objectives Understanding the implications

More information

North American Stainless

North American Stainless North American Stainless Flat Product Stainless Steel Grade Sheet 316 (S31600)/EN 1.4401 316L (S31603)/ EN 1.4404 INTRODUCTION NAS provides 316 and 316L SS, which are molybdenum-bearing austenitic stainless

More information

Stainless steel grade chart

Stainless steel grade chart Stainless steel grade chart ATLAS STEELS METAL DISTRIBUTION Chemical analysis (%) specified C Si Mn P S Cr Mo Ni Other Austenitic stainless steels 253MA S30815 0.05 1.1-2.0 0.8 0.040 0.030 20.0-22.0 10.0-12.0

More information

North American Stainless

North American Stainless Introduction: North American Stainless Flat Products Stainless Steel Grade Sheet 309S (S30908)/ EN1.4833 SS309 is a highly alloyed austenitic stainless steel used for its excellent oxidation resistance,

More information

ODS Alloys in Coal-Fired Heat Exchangers Prototypes and Testing

ODS Alloys in Coal-Fired Heat Exchangers Prototypes and Testing ODS Alloys in Coal-Fired Heat Exchangers Prototypes and Testing 2010 ODS Alloy Workshop San Diego, California November 17 18, 2010 John P. Hurley Senior Research Advisor Energy & Environmental Research

More information

ASTM A860/A860M-09 Standard Specification for Wrought High Strength. Ferritic Steel Butt Welding Fittings. 1. Scope :- 2. Reference Documents :-

ASTM A860/A860M-09 Standard Specification for Wrought High Strength. Ferritic Steel Butt Welding Fittings. 1. Scope :- 2. Reference Documents :- Standard Specification for Wrought High Strength Ferritic Steel Butt Welding Fittings 1. Scope :- 1.1 This specification covers wrought high strength ferritic steel butt-welding fitting of seamless and

More information

NAWTEC16-1916. Proceedings of NAWTEC16 16th Annual North American Waste-to-Energy Conference May 19-21, 2008, Philadelphia, Pennsylvania, USA

NAWTEC16-1916. Proceedings of NAWTEC16 16th Annual North American Waste-to-Energy Conference May 19-21, 2008, Philadelphia, Pennsylvania, USA Proceedings of NAWTEC16 16th Annual North American Waste-to-Energy Conference May 19-21, 8, Philadelphia, Pennsylvania, USA NAWTEC16-1916 The effects of varied hydrogen chloride gas concentrations on corrosion

More information

Urea and Nitric Acid Plants: Improvement of Shut-Down, Revamping, Debottlenecking and Refurbishment

Urea and Nitric Acid Plants: Improvement of Shut-Down, Revamping, Debottlenecking and Refurbishment pp Urea and Nitric Acid Plants: Improvement of Shut-Down, Revamping, Debottlenecking and Refurbishment J. M. SLUYTERS GEMACO SA Herstal, Belgium A presentation on special corrosion-resistant steels for

More information

TABLE OF CONTENTS 2 Heavy-Wall Seamless & Welded Carbon Steel Pipe. 4 Alloy Pipe & Tube. 6 Chrome-Moly Pipe. 7 Low-Temp Pipe

TABLE OF CONTENTS 2 Heavy-Wall Seamless & Welded Carbon Steel Pipe. 4 Alloy Pipe & Tube. 6 Chrome-Moly Pipe. 7 Low-Temp Pipe PRODUCT CATALOG TABLE OF CONTENTS 2 Heavy-Wall Seamless & Welded Carbon Steel Pipe 4 Alloy Pipe & Tube 6 Chrome-Moly Pipe 7 Low-Temp Pipe 9 Services amerpipe.com 1.800.316.5737 sales@amerpipe.com 18333

More information

The National Board of Boiler and Pressure Vessel Inspectors 1055 Crupper Avenue Columbus, Ohio 43229 614.888.8320

The National Board of Boiler and Pressure Vessel Inspectors 1055 Crupper Avenue Columbus, Ohio 43229 614.888.8320 TheNationalBoardofBoilerandPressureVesselInspectors 1055CrupperAvenue Columbus,Ohio43229 614.888.8320 NB-410, Revision 3 Sept, 2015 1 1.0 GENERAL The purpose of this document is to provide basic guidelines

More information

DX2202 Duplex stainless steel

DX2202 Duplex stainless steel Stainless Europe Grade DX22 Duplex stainless steel Chemical Composition Elements C Mn Cr Ni Mo N %.25.3 23. 2.5

More information

INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9

INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9 TABLE OF CONTENTS Description Page Number SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9 Indeck Keystone Energy, LLC. 5451 Merwin Lane, Suite 100 Erie,

More information

Paper to be published in 2004

Paper to be published in 2004 Paper to be published in 2004 RECENT ACTIVITIES ON HIGH TEMPERARTURE HYDROGEN ATTACK Koji Kawano, PhD. Senior Engineering Coordinator Idemitsu Engineering Company, Ltd. Chiba, Japan ABSTRACT Existing C-0.5Mo

More information

Material Failures in Fire Protection Systems

Material Failures in Fire Protection Systems Material Failures in Fire Protection Systems March 4, 2014 University of Central Florida (UCF), Orlando, FL Jeff Pfaendtner Materials/Metallurgical Engineer Crane Engineering Inc., Plymouth, MN Crane Engineering

More information

TRIAL CHEMICAL CLEANING OF FOULED APH BASKETS

TRIAL CHEMICAL CLEANING OF FOULED APH BASKETS TRIAL CHEMICAL CLEANING OF FOULED APH BASKETS Dr. Abhay Kumar Sahay, AGM(CC OS) Bijay Manjul, AGM( Operation) Kahalgaon Boiler has three inputs Steam generator 1. WATER 2. COAL 3. AIR Burner Air preheater

More information

Best Practice in Boiler Water Treatment

Best Practice in Boiler Water Treatment Best Practice in Boiler Water Treatment Boiler Water Treatment Part 2 Internal Treatment Objectives of Internal Water Treatment 1 To control the level of total dissolved solids (TDS) within the boiler

More information

North American Stainless

North American Stainless North American Stainless Long Products Stainless Steel Grade Sheet AISI 304 UNS S30400 EN 1.4301 AISI 304L UNS S30430 EN 1.4307 INTRODUCTION: Types 304 and 304L are the most versatile and widely used of

More information

VeMet, Utrecht, NL «Solution in Wear Protection» 26.10.2011 Dipl.-Ing. Wolfgang Leichnitz. Quit

VeMet, Utrecht, NL «Solution in Wear Protection» 26.10.2011 Dipl.-Ing. Wolfgang Leichnitz. Quit VeMet, Utrecht, NL «Solution in Wear Protection» 26.10.2011 Dipl.-Ing. Wolfgang Leichnitz Quit Theory and Practice of Wear Definition In materials science, wear is the erosion of material from a solid

More information

Lecture 35: Atmosphere in Furnaces

Lecture 35: Atmosphere in Furnaces Lecture 35: Atmosphere in Furnaces Contents: Selection of atmosphere: Gases and their behavior: Prepared atmospheres Protective atmospheres applications Atmosphere volume requirements Atmosphere sensors

More information

ALLOY C276 DATA SHEET

ALLOY C276 DATA SHEET ALLOY C276 DATA SHEET //// Alloy C276 (UNS designation N10276) is a nickel-molybdenum-chromium-iron-tungsten alloy known for its corrosion resistance in a wide range of aggressive media. It is one of the

More information

Section 4: NiResist Iron

Section 4: NiResist Iron Section 4: NiResist Iron Section 4 Ni-Resist Description of Grades...4-2 201 (Type 1) Ni-Resist...4-3 202 (Type 2) Ni-Resist...4-6 Stock Listings...4-8 4-1 Ni-Resist Description of Grades Ni-Resist Dura-Bar

More information

Brush Plating of Nickel-Tungsten Alloy for Engineering Application

Brush Plating of Nickel-Tungsten Alloy for Engineering Application Brush Plating of Nickel-Tungsten Alloy for Engineering Application Zhimin Zhong & Sid Clouser ASETS Defense 12 1 Engineering (functional) applications Hardness, wear resistance, & corrosion protection

More information

Copper and Copper Alloy Tube, Pipe and Fittings

Copper and Copper Alloy Tube, Pipe and Fittings Copper and Copper Alloy Tube, Pipe and Fittings COPPER and COPPER ALLOY TUBE and PIPE Seamless Copper Pipe: Copper pipe is almost pure copper manufactured to the requirements of ASTM B 42 - Standard Specification

More information

Martin RICHEZ. Franck ZANONCELLI

Martin RICHEZ. Franck ZANONCELLI DILLINGER PRESSURE VESSEL COLLOQUIUM Dillingen 16/17 th september 2009 TOTAL Requirements for equipment in severe wet H2S service. Examples of equipment made from Dillinger steel plates Martin RICHEZ Franck

More information

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound. Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of

More information

North American Stainless

North American Stainless North American Stainless Flat Products Stainless Steel Grade Sheet 304 (S30400)/ EN 1.4301 304L (S30403) / EN 1.4307 304H (S30409) Introduction: Types 304, 304L and 304H are the most versatile and widely

More information

Condition Assessment Services. Put our team of specialists to work for you

Condition Assessment Services. Put our team of specialists to work for you Condition Assessment Services Put our team of specialists to work for you HEADERS Don t let a steam leak be your first sign of header problems High Temperature Headers High temperature superheater and

More information

I. STEAM GENERATION, BOILER TYPES

I. STEAM GENERATION, BOILER TYPES I. STEAM GENERATION, BOILER TYPES and BOILER PLANT SYSTEMS 1 Steam Generation Water s Unique Properties: High Thermal Capacity (Specific Heat) High Critical Temperature Ideal Medium for Heat Delivery High

More information

Overview of Stress Corrosion Cracking in Stainless Steel: Electronic Enclosures in Extreme Environmental Conditions

Overview of Stress Corrosion Cracking in Stainless Steel: Electronic Enclosures in Extreme Environmental Conditions Overview of Stress Corrosion Cracking in Stainless Steel: Electronic Enclosures in Extreme Environmental Conditions Stephani Gulbrandsen Introduction: Electronic Enclosures 316L stainless steel is found

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Anode Rods, Cathodic Protection and the Porcelain (glass) Lining

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Anode Rods, Cathodic Protection and the Porcelain (glass) Lining Corrosion can be defined as the destructive attack of a metal by an electrochemical reaction with its environment. Steel exposed to moisture and oxygen will rust and corrode. Corrosion is defined as the

More information

NAWTEC18-3541 CONCEPTS AND EXPERIENCES FOR HIGHER PLANT EFFICIENCY WITH MODERN ADVANCED BOILER AND INCINERATION TECHNOLOGY

NAWTEC18-3541 CONCEPTS AND EXPERIENCES FOR HIGHER PLANT EFFICIENCY WITH MODERN ADVANCED BOILER AND INCINERATION TECHNOLOGY Proceedings of the 18th Annual North American Waste-to-Energy Conference NAWTEC18 May 11-13, 2010, Orlando, Florida, USA NAWTEC18-3541 CONCEPTS AND EXPERIENCES FOR HIGHER PLANT EFFICIENCY WITH MODERN ADVANCED

More information

Performance of the Boiler and To Improving the Boiler Efficiency Using Cfd Modeling

Performance of the Boiler and To Improving the Boiler Efficiency Using Cfd Modeling IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 8, Issue 6 (Sep. - Oct. 2013), PP 25-29 Performance of the Boiler and To Improving the Boiler Efficiency

More information

RISK BASED INSPECTION (RBI)

RISK BASED INSPECTION (RBI) 1 RISK BASED INSPECTION (RBI) Roy Johnsen Professor, Institutt for produktutvikling og materialer (IPM), NTNU Roy.johnsen@ntnu.no Tlf: +47 93245101 2 CONTENT Introduction - Corrosion Management What is

More information

CHALLENGES IN A DILUTION STEAM GENERATOR SYSTEM

CHALLENGES IN A DILUTION STEAM GENERATOR SYSTEM CHALLENGES IN A DILUTION STEAM GENERATOR SYSTEM Lee Siang Hua Titan Petrochemicals (M) Sdn Bhd Cheah Phaik Sim Titan Petrochemicals (M) sdn Bhd piximmink@yahhoo.com Karl Kolmetz Westlake Group, Lake Charles,

More information

1. A belt pulley is 3 ft. in diameter and rotates at 250 rpm. The belt which is 5 ins. wide makes an angle of contact of 190 over the pulley.

1. A belt pulley is 3 ft. in diameter and rotates at 250 rpm. The belt which is 5 ins. wide makes an angle of contact of 190 over the pulley. Sample Questions REVISED FIRST CLASS PARTS A1, A2, AND A3 (NOTE: these questions are intended as representations of the style of questions that may appear on examinations. They are not intended as study

More information

WATER WALL BOILER FOR AIR AND OXYGEN FIRED CLAUS SULPHUR RECOVERY UNITS

WATER WALL BOILER FOR AIR AND OXYGEN FIRED CLAUS SULPHUR RECOVERY UNITS WATER WALL BOILER FOR AIR AND OXYGEN FIRED CLAUS SULPHUR RECOVERY UNITS Abstract Mahin RAMESHNI, P.E. Technical Director, Sulphur Technology Mahin.Rameshni@worleyparsons.com WorleyParsons 125 West Huntington

More information

Avoiding Burning Through: Control the Inside Surface Temperature, Not the Pressure

Avoiding Burning Through: Control the Inside Surface Temperature, Not the Pressure Originally published in the Canadian Welding Association Journal, Spring 2013, pp 30 39 Welding on In service Pipelines: Dispelling Popular Myths and Misconceptions Bill Amend Sr. Principal Engineer, Welding

More information

Welding and Corrosion Performance of INCO-WELD 686CPT Filler Metal In Waste-To-Energy Power Plants

Welding and Corrosion Performance of INCO-WELD 686CPT Filler Metal In Waste-To-Energy Power Plants Welding and Corrosion Performance of INCO-WELD 686CPT Filler Metal In Waste-To-Energy Power Plants Christopher E Thornton * 1, Craig Cooper 2 1. Special Metals Welding Products Company, Canada House, Waterloo

More information

Duplex Stainless Steel Fabrication. Gary M. Carinci TMR Stainless Consultant for International Molybdenum Association

Duplex Stainless Steel Fabrication. Gary M. Carinci TMR Stainless Consultant for International Molybdenum Association Duplex Stainless Steel Fabrication Gary M. Carinci TMR Stainless Consultant for International Molybdenum Association 1 Promoting molybdenum - as a material with superior properties and performance in a

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification Number: 3503-11.2.610 Rev. 2 Rubber Lined Steel Pipe and Fittings Mechanically Coupled Plain End Type System Issued Revised Approved

More information

Tubing Data. Contents. Tubing Selection. Tubing Handling. Tubing Material. Tubing Outside Diameter Hardness. Tubing Wall Thickness

Tubing Data. Contents. Tubing Selection. Tubing Handling. Tubing Material. Tubing Outside Diameter Hardness. Tubing Wall Thickness www.swagelok.com Tubing Data Contents Tubing Selection... 1 Tubing Handling.... 1 Gas Service... 2 Tubing Installation.... 2 Suggested Allowable Working Pressure Tables Carbon Steel Tubing... 3 Stainless

More information

SPECIFICATIONS FOR STEEL PIPE

SPECIFICATIONS FOR STEEL PIPE SPECIFICATIONS FOR STEEL PIPE Published pipe standards serve three functions. 1. They dictate manufacturing and testing requirements and prescribed methods of measuring the required mechanical and physical

More information

Investigating the Impact of Boiler Aging In Replacement Decisions

Investigating the Impact of Boiler Aging In Replacement Decisions Investigating the Impact of Boiler Aging In Replacement Decisions Siddika Pasi and Michael R. Muller, Rutgers University - Center for Advanced Energy Systems ABSTRACT Traditionally boilers were believed

More information

North American Stainless

North American Stainless North American Stainless Flat Products Stainless Steel Sheet T409 INTRODUCTION NAS 409 is an 11% chromium, stabilized ferritic stainless steel. It is not as resistant to corrosion or high-temperature oxidation

More information

ROLLED STAINLESS STEEL PLATES, SECTIONS AND BARS

ROLLED STAINLESS STEEL PLATES, SECTIONS AND BARS STANDARD FOR CERTIFICATION No. 2.9 ROLLED STAINLESS STEEL PLATES, SECTIONS AND BARS OCTOBER 2008 Veritasveien 1, NO-1322 Høvik, Norway Tel.: +47 67 57 99 00 Fax: +47 67 57 99 11 FOREWORD (DNV) is an autonomous

More information

Chapter 8 - Chemical Equations and Reactions

Chapter 8 - Chemical Equations and Reactions Chapter 8 - Chemical Equations and Reactions 8-1 Describing Chemical Reactions I. Introduction A. Reactants 1. Original substances entering into a chemical rxn B. Products 1. The resulting substances from

More information

SULFUR RECOVERY UNIT. Thermal Oxidizer

SULFUR RECOVERY UNIT. Thermal Oxidizer SULFUR RECOVERY UNIT Thermal Oxidizer BURNERS FLARES INCINERATORS PARTS & SERVICE SULFUR RECOVERY UNIT Thermal Oxidizer Tail Gas Thermal Oxidizer designed and built to GOST-R requirements. Zeeco can meet

More information

Quartz Glass. Tubes and Rods

Quartz Glass. Tubes and Rods Quartz Glass Tubes and Rods PH 300, GE 214, QI PN GVB Solutions in Glass Schlackstrasse 3 52080 Aachen Germany +49-241/9108588 +49-241/9108589 E- info@g-v-b.de www.g-v-b.de Table of contents General Information

More information

ALLOY 6022 SHEET. Higher Strength with Improved Formability SUPPLYING THE WORLD S BEST

ALLOY 6022 SHEET. Higher Strength with Improved Formability SUPPLYING THE WORLD S BEST SUPPLYING THE WORLD S BEST DESCRIPTION 6022 is a heat treatable low copper, Al-Si-Mg sheet alloy developed by Alcoa to satisfy the needs of automotive manufacturers for closure panels, such as a hood,

More information

Wear-resistant steels. Technical terms of delivery for heavy plates. voestalpine Grobblech GmbH www.voestalpine.com/grobblech

Wear-resistant steels. Technical terms of delivery for heavy plates. voestalpine Grobblech GmbH www.voestalpine.com/grobblech Wear-resistant steels Technical terms of delivery for heavy plates voestalpine Grobblech GmbH www.voestalpine.com/grobblech Wear-resistant steels durostat durostat 400 durostat 450 durostat 500 durostat

More information

CENTRIFUGAL CASTING. Email: amitjoshi@iitb.ac.in amitjoshi1000@yahoo.ca

CENTRIFUGAL CASTING. Email: amitjoshi@iitb.ac.in amitjoshi1000@yahoo.ca CENTRIFUGAL CASTING Amit M Joshi (B.Engg. Mechanical, A.M.I.Prod.E, A.I.E) Dept. of Metallurgical Engg. & Material Science, Indian Institute of Technology Bombay, India. Email: amitjoshi@iitb.ac.in amitjoshi1000@yahoo.ca

More information

HEAT TREATMENT OF STEEL

HEAT TREATMENT OF STEEL HEAT TREATMENT OF STEEL Heat Treatment of Steel Most heat treating operations begin with heating the alloy into the austenitic phase field to dissolve the carbide in the iron. Steel heat treating practice

More information

SALT SPRAY AND IMMERSION CORROSION TESTING OF PM STAINLESS STEEL MATERIALS. W. Brian James Hoeganaes Corporation. Cinnaminson, NJ 08077

SALT SPRAY AND IMMERSION CORROSION TESTING OF PM STAINLESS STEEL MATERIALS. W. Brian James Hoeganaes Corporation. Cinnaminson, NJ 08077 SALT SPRAY AND IMMERSION CORROSION TESTING OF PM STAINLESS STEEL MATERIALS W. Brian James Hoeganaes Corporation Cinnaminson, NJ 08077 Leander F. Pease III Powder-Tech Associates Inc. Andover, MA 01845

More information

DIN 17172-78 STEEL PIPES FOR PIPE LINES FOR THE TRANSPORT OF COMBUSTIBLE FLUIDS AND GASES

DIN 17172-78 STEEL PIPES FOR PIPE LINES FOR THE TRANSPORT OF COMBUSTIBLE FLUIDS AND GASES DIN 17172-78 STEEL PIPES FOR PIPE LINES FOR THE TRANSPORT OF COMBUSTIBLE FLUIDS AND GASES For connection with the International Draft Standards 3183 and 3845 published by the International Organization

More information

Hydrogen Induced Cracking of Low Strength Steels in Geothermal Fluids

Hydrogen Induced Cracking of Low Strength Steels in Geothermal Fluids Proceedings World Geothermal Congress 2005 Antalya, Turkey, 24-29 April 2005 Hydrogen Induced Cracking of Low Strength Steels in Geothermal Fluids Keith A. Lichti, David M Firth and Annette D Karstensen

More information

JIS G3472 Electric Resistance Welded Carbon Steel Tubes for Automobile Structural Purposes

JIS G3472 Electric Resistance Welded Carbon Steel Tubes for Automobile Structural Purposes JIS G3472 Electric Resistance Welded Carbon Steel Tubes for Automobile Structural Purposes 1. Scope This Japanese Industrial Standard specifies the electric resistance welded carbon steel tubes, hereinafter

More information

A REVIEW OF THE COMMON CAUSES OF BOILER FAILURE IN THE SUGAR INDUSTRY

A REVIEW OF THE COMMON CAUSES OF BOILER FAILURE IN THE SUGAR INDUSTRY A REVIEW OF THE COMMON CAUSES OF BOILER FAILURE IN THE SUGAR INDUSTRY K B MCINTYRE Alstom Power - John Thompson Boiler Division, Cape Town, South Africa E-mail: keithmac@johnthompsonafrica.co.za Abstract

More information

Improved Broaching Steel Technology

Improved Broaching Steel Technology Improved Broaching Steel Technology Michael E. Burnett TimkenSteel Corporation 1835 Dueber Ave. SW, Canton Ohio 44706 Phone: (330) 471-3273 Email: michael.burnett@timkensteel.com Key Words: Alloy Steel,

More information

DIN 2403 Identification of pipelines according to the fluid conveyed. Marking of pipes according to fluid transported

DIN 2403 Identification of pipelines according to the fluid conveyed. Marking of pipes according to fluid transported DIN 2403 Identification of pipelines according to the fluid conveyed. Marking of pipes according to fluid transported 1 Field of application This standard specifies the colours for the identification of

More information

SELECTIVE DISSOLUTION AND CORROSION FATIGUE BEHAVIORS OF 2205 DUPLEX STAINLESS STEEL

SELECTIVE DISSOLUTION AND CORROSION FATIGUE BEHAVIORS OF 2205 DUPLEX STAINLESS STEEL W.-T. Tsai, I.-H. Lo Department of Materials Science and Engineering National Cheng Kung University Tainan, Taiwan SELECTIVE DISSOLUTION AND CORROSION FATIGUE BEHAVIORS OF 2205 DUPLEX STAINLESS STEEL ABSTRACT

More information

Steam System Best Practices Condensate System Piping

Steam System Best Practices Condensate System Piping Steam System Best Practices Condensate System Piping Summary The best method for improving steam system energy efficiency, reducing chemical costs, and reducing make-up water costs is to return the maximum

More information

Drill Pipe Hard-facing

Drill Pipe Hard-facing Drill Pipe Hard-facing GLOBAL PROTECTION AGAINST WEAR AND TEAR Oxyacetylene Rods Flux- and Metal Cored Wires Electrodes PTA - Welding Oxyacetylene Welding and Spray Powders Flame Spraying FLSP Arc Spraying

More information

Technical Data BLUE SHEET. Martensitic. stainless steels. Types 410, 420, 425 Mod, and 440A GENERAL PROPERTIES APPLICATIONS PRODUCT FORM

Technical Data BLUE SHEET. Martensitic. stainless steels. Types 410, 420, 425 Mod, and 440A GENERAL PROPERTIES APPLICATIONS PRODUCT FORM Technical Data BLUE SHEET Allegheny Ludlum Corporation Pittsburgh, PA Martensitic Stainless Steels Types 410, 420, 425 Mod, and 440A GENERAL PROPERTIES Allegheny Ludlum Types 410, 420, 425 Modified, and

More information

Austin Peay State University Department of Chemistry CHEM 1111. Empirical Formula of a Compound

Austin Peay State University Department of Chemistry CHEM 1111. Empirical Formula of a Compound Cautions Magnesium ribbon is flammable. Nitric acid (HNO 3 ) is toxic, corrosive and contact with eyes or skin may cause severe burns. Ammonia gas (NH 3 ) is toxic and harmful. Hot ceramic crucibles and

More information

Start the Design Study!

Start the Design Study! A Design Study in Centrifugal Steel Castings Hydraulic Accumulator Cylinder for Navy Submarines Design Study Outline Introduction Design for Performance Duplex Steel Approach Alloy Selection Design for

More information

The mechanical properties of metal affected by heat treatment are:

The mechanical properties of metal affected by heat treatment are: Training Objective After watching this video and reviewing the printed material, the student/trainee will learn the basic concepts of the heat treating processes as they pertain to carbon and alloy steels.

More information

JIS G3461 Carbon Steel Tubes for Boiler and Heat Exchanger

JIS G3461 Carbon Steel Tubes for Boiler and Heat Exchanger JIS G3461 Carbon Steel Tubes for Boiler and Heat Exchanger 1. Scope This Japanese Industrial Standard specifies the carbon steel tubes, hereinafter referred to as the "tubes", used for exchanging heat

More information

Boiler Preparation, Start-Up and Shutdown

Boiler Preparation, Start-Up and Shutdown Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.

More information

Weld Cracking. An Excerpt from The Fabricators' and Erectors' Guide to Welded Steel Construction. The James F. Lincoln Arc Welding Foundation

Weld Cracking. An Excerpt from The Fabricators' and Erectors' Guide to Welded Steel Construction. The James F. Lincoln Arc Welding Foundation Weld Cracking An Excerpt from The Fabricators' and Erectors' Guide to Welded Steel Construction The James F. Lincoln Arc Welding Foundation Weld Cracking Several types of discontinuities may occur in welds

More information

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)

More information

CHAPTER 3: MATTER. Active Learning Questions: 1-6, 9, 13-14; End-of-Chapter Questions: 1-18, 20, 24-32, 38-42, 44, 49-52, 55-56, 61-64

CHAPTER 3: MATTER. Active Learning Questions: 1-6, 9, 13-14; End-of-Chapter Questions: 1-18, 20, 24-32, 38-42, 44, 49-52, 55-56, 61-64 CHAPTER 3: MATTER Active Learning Questions: 1-6, 9, 13-14; End-of-Chapter Questions: 1-18, 20, 24-32, 38-42, 44, 49-52, 55-56, 61-64 3.1 MATTER Matter: Anything that has mass and occupies volume We study

More information

Oil and Gas Pipeline Design, Maintenance and Repair

Oil and Gas Pipeline Design, Maintenance and Repair Oil and Gas Pipeline Design, Maintenance and Repair Dr. Abdel-Alim Hashem Professor of Petroleum Engineering Mining, Petroleum & Metallurgical Eng. Dept. Faculty of Engineering Cairo University aelsayed@mail.eng.cu.edu.eg

More information

Objectives/Introduction Extraction of zinc Physical properties of zinc Zinc casting alloys Wrought zinc alloys Engineering design with zinc alloys

Objectives/Introduction Extraction of zinc Physical properties of zinc Zinc casting alloys Wrought zinc alloys Engineering design with zinc alloys Lecture 7 Zinc and its alloys Subjects of interest Objectives/Introduction Extraction of zinc Physical properties of zinc Zinc casting alloys Wrought zinc alloys Engineering design with zinc alloys Objectives

More information

Full Density Properties of Low Alloy Steels

Full Density Properties of Low Alloy Steels Full Density Properties of Low Alloy Steels Michael L. Marucci & Arthur J. Rawlings Hoeganaes Corporation, Cinnaminson, NJ Presented at PM 2 TEC2005 International Conference on Powder Metallurgy and Particulate

More information

FORENSIC ENGINEERING ANALYSIS OF A COMBUSTION TURBINE COMPRESSOR BLADE FAILURE

FORENSIC ENGINEERING ANALYSIS OF A COMBUSTION TURBINE COMPRESSOR BLADE FAILURE FORENSIC ENGINEERING ANALYSIS OF A COMBUSTION TURBINE COMPRESSOR BLADE FAILURE Teodoro Leon-Salamanca, Ph.D. Reinhart & Associates, Inc. Austin, TX CT Compressor Blade Failure 36th Turbomachinery Symposium

More information

How To Write A Recipe Card

How To Write A Recipe Card Forging stock standards guideline Issue n 10 FORGING STOCK 30 Microstructure 34 Grain size Air melted (except if δ ferrite or problem 1 per batch) 50 Cleanness/ Inclusion See EN 2157-2. 51 Macrostructure

More information

A Primer on Protecting Idle Boilers By Howard Benisvy, Member ASHRAE

A Primer on Protecting Idle Boilers By Howard Benisvy, Member ASHRAE The following article was published in ASHRAE Journal, December 2002. Copyright 2002 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

TARIFF CODE and updates standard

TARIFF CODE and updates standard TARIFF CODE and updates standard No HS CODE AHTN CODE PRODUCT DESCRIPTION PRODUCT TYPE STANDARDS IDENTIFIED 7207 Semi finished products of iron or non alloy steel Containing by weight less than 0.25% of

More information

BODY OF KNOWLEDGE API-570 AUTHORIZED PIPING INSPECTOR CERTIFICATION EXAMINATION

BODY OF KNOWLEDGE API-570 AUTHORIZED PIPING INSPECTOR CERTIFICATION EXAMINATION BODY OF KNOWLEDGE API-570 AUTHORIZED PIPING INSPECTOR CERTIFICATION EXAMINATION 2015 (Replaces July 2013) API Authorized Piping Inspectors must have a broad knowledge base relating to maintenance, inspection,

More information

TEMA DESIGNATIONS OF HEAT EXCHANGERS REMOVABLE BUNDLE EXCHANGERS NON REMOVABLE BUNDLE EXCHANGERS SOURCE: WWW.WERMAC.ORG/

TEMA DESIGNATIONS OF HEAT EXCHANGERS REMOVABLE BUNDLE EXCHANGERS NON REMOVABLE BUNDLE EXCHANGERS SOURCE: WWW.WERMAC.ORG/ TEMA DESIGNATIONS OF HEAT EXCHANGERS Because of the number of variations in mechanical designs for front and rear heads and shells, and for commercial reasons, TEMA has designated a system of notations

More information

Boiler & Pressure Vessel Inspection discrepancies and failures

Boiler & Pressure Vessel Inspection discrepancies and failures Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:

More information