1 Global Short-Circuit Current Ratings Global Products, Global Solutions Jeff Battani Business Development Manager Industrial Components Business Rev 5058-CO900B

2 DISCLAIMER This document is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this document is not intended to constitute application, design, software or other professional engineering advice or services. Before making any decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor. ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS DOCUMENT AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES. ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON- INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you. Excerpts from UL Standard for Safety for Industrial Control Panels, UL508A are copyright Underwriter s Laboratories Inc. Excerpts from the 2011 National Electrical Code are copyright National Fire Protection Association 2

3 Presentation Agenda SCCR Background NEC, UL 508A SB vs. IEC MCS Motor Starter Circuits SMC Soft-Starter Circuits PowerFlex Drive Circuits rockwellautomation.com Web Tool Global SCCR Summary 3

4 Global Short-Circuit Current Ratings Global Products, Global Solutions! Customer Solutions Competitiveness Common Design Coordinated Protection Complete Solutions 4

5 Importance of Short-Circuit Current Ratings Short-Circuit: An over-current fault the exceeds normal full load currents... 10x, 100x, 1,000x of FLC Catastrophic results if SC Faults are not cleared properly SC Faults are critical to: Worker Safety Customer Applications (Critical Care, Continuous Process) Circuit Components, Assemblies & System Installations Productivity & Downtime ($100k s per hour) We forget how much power we are really discussing: 400V 480V 690V Current (A) Available Short Circuit Current (I pa) Non-Current Limiting Peak Let-Thru (I pl) Let-Thru (I 2 t) Time Clearing Time (t c) Normal Load Current Short Circuit Current 5

6 What is a Short-Circuit Current Rating? Short-Circuit Interrupting Rating (Breaking Capacity): The maximum short circuit current at rated voltage that a over-current protective device can safely interrupt and clear (Fuses & Circuit Breakers) Short-Circuit Current Rating SCCR: The maximum available short-circuit current an electrical component can sustain without the occurrence of excessive damage when protected with an over-current protective device Motor Protection Circuit Breaker Protective Device Icu/Ics = 400V Combination Motor Controllers Icu/Ics = 400V IEC Type 2 Coordination

7 Building a Short-Circuit Current Rating Protection Levels: Component Combinations Branch Circuit Panel Assembly Motor Protection Circuit Breaker Icu/Ics = 400V Combination Motor Controllers Icu/Ics = 400V IEC Type 2 Coordination Panel SCCR 400V Branch Circuit SCCR 400V 7

8 Common Global SCCR Requirements Utility V MCB1 480V, 60Hz Determine System Voltage & Frequency Determine Available Fault Currents (AFC) Ensure Control Panel SCCR covers the AFC Mark the Panels Accordingly Main Switchgear SCCR Evaluation Process varies greatly F1 X 22kA AFC X 48kA AFC X 14kA AFC X 35kA AFC 8

9 Presentation Agenda SCCR Background NEC, UL 508A SB vs. IEC MCS Motor Starter Circuits SMC Soft-Starter Circuits PowerFlex Drive Circuits rockwellautomation.com Web Tool Global SCCR Summary 9

10 NEC, UL 508A SB vs. IEC Category Products Panels & Machinery North American Markets UL 508 Part I All Equipment UL 508, 489, 1077 Circuit Breakers UL 98 Disconnect Switches UL 508 Part II Mag Motor Controllers UL 508 Part III Man Motor Controllers UL 508 Part IV Comb Motor Controllers UL 508 Part V Reduced Voltage Starters UL 508 Part IV Solid-State AC Motor Control UL 508 Part X Auxiliary Devices UL 1059 Power & Terminal Blocks UL 508C Power Conversion Equipment NFPA 79 Electrical Standard for Industrial Machinery UL 508A (SB) Industrial Control Panels UL 845 Motor Control Centers UL 1558 LV Switchgear International Markets IEC General IEC Circuit Breakers IEC Disconnect Switches IEC Contactors & Starters IEC Soft-Starters IEC Control Circuit Devices IEC Terminal Blocks IEC Variable Freq Drives IEC Electrical Equipment of Industrial Machines IEC LV Control-gear & Switchgear Assemblies IEC Application of SCCR (TR) Electrical Installations NEC (NFPA 70) National Electrical Code CEC Canadian Electrical Code IEC Low-Voltage Electrical Installations for Buildings 10

11 SCCR on UL Industrial Control Panels NEC & UL 508A NEC Articles: 409 Industrial Control Panels General use, 600V or less 440 Air Conditioning & Refrigeration 610 Cranes & Hoists 670 Industrial Machinery Marking: (3) Short-circuit current rating of the industrial control panel based on one of the following: a. Short-circuit current rating of a listed and labeled assembly b. Short-circuit current rating established utilizing an approved method FPN: UL 508A-2001, Supplement SB, is an example of an approved method General Use Industrial Control Panels: Construction Panels Power Circuits Control Circuits Ratings Markings Specific Use IC Panels Supplement SB: SCCR for IC Panels 11 11

12 UL 508A Supplement SB UL 508A Industrial Control Panels Panel Builders Standard Standardized process to determining SCCR for panels Limited traditional analysis methods Evaluates Voltage Ratings (Y/D Systems) Default to minimum assigned ratings Forces all power components to have high fault SCCR ratings Umbrella Testing UL Witnessed all High Fault Tests! 12

13 UL 508A SB Determining SCCR s - 3 Basic Steps UL 508A Supplement SB Short-Circuit Current Ratings for Industrial Control Panels Shall be determined by the following evaluation procedure: SB4.1: Short-Circuit Current Rating (SCCR) a) First, establish the short circuit current ratings of individual power circuit components as specified in SB4.2 b) Second, modify (limit) the available short-circuit current within a portion of a circuit in the panel due to the presence of current limiting components as specified in SB4.3 c) Third, determine the overall panel short-circuit current rating as specified in SB4.4 13

14 UL 508A SB4.2 Individual Power Circuit Components SB4.2.1 All power circuit components, including disconnect switches, branch circuit protective devices, branch circuit fuse holders, load controllers, motor overload relays, terminal blocks, and bus bars, shall have a short-circuit current rating expressed in amperes or kilo-amperes and voltage. Exception No. 1: Power transformers, reactors, current transformers, dry-type capacitors, resistors, varistors, and voltmeters are not required to have a short circuit current rating. Exception No. 2: The S contactor of a wye-delta motor controller is not required to have a shortcircuit current rating. 14

15 UL 508A SB4.3 Feeder Devices that Limit SC Current SB4.3 Feeder components that limit the short-circuit current available: SB4.3.1 For branch circuits supplied by a power transformer with an isolated secondary winding, a power transformer with an isolated secondary SB4.3.2 For branch circuits supplied by a Listed circuit breaker marked current limiting in the feeder circuit, the short circuit current rating SB4.3.3 For branch circuits supplied by a Class CC, G, J, L, RK1, RK5, or T fuse in the feeder circuit, the short-circuit current rating 15

16 UL 508A SB4.3 Current-Limiting Components SB4.3.2 For branch circuits supplied by a Listed circuit breaker marked current-limiting in the feeder circuit, the short-circuit current rating on the line side of the circuit breaker shall be one of the following: a) The short-circuit current rating of the feeder circuit breaker when all of the components in the branch circuit have a shortcircuit current rating not less than the published peak letthrough current of the circuit breaker, see Figure SB4.1, and the short-circuit current rating of all branch circuit protective devices on the load side are not less than the short-circuit current rating of the feeder circuit breaker; Feeder CB Current Limiting 65kA SCCR 65kA SCC Available 17kA Ip Let-through b) The smallest short-circuit current rating of any branch circuit protective device on the load side of the feeder circuit breaker, when the conditions of SB4.3.2(a) exist except the short-circuit current rating of the branch circuit protective devices on the load side are less than the short-circuit current rating of the feeder circuit breaker. c Branch Circuit PD 65kA SCCR Motor Controller 18kA SCCR a) 65kA Panel SCCR 16

17 UL 508A SB4.4 Overall SCCR of the Panel 10kA 100kA SB4.4.1 For each branch circuit provided with branch circuit protection within the industrial control panel, the smallest short-circuit current rating of all power circuit components on the load side of a branch circuit protective device and the control circuit over-current protection in SB3.2.1 shall be determined and compared with the short-circuit current rating of the branch circuit protective device. The smaller of the two ratings shall be assigned to the line side of the branch circuit protective device. 65kA 70kA 65kA In other words, use the lowest rating of a component or branch protective device to determine branch rating. 10kA Panel Rating 17

18 UL 508A SB4.4 Panel SCCR Validate Results 1. Panel SCCR will be determined by the smallest SCCR of any feeder or branch over-current protective device or component Available Fault Current: 480V 2. Branch Circuit Protection Devices, BCPDs must cover panel available fault level 3. All components and controllers with SCCR s based on high-fault ratings must be used with the specified branch circuit protective device 4. And finally, the panel SCCR must cover the available fault current supplying the panel! 18

19 UL 508A SB Components Requiring High Fault SCCR High Fault Ratings with Circuit Breakers & Fuses Circuit Breaker & Fuse Solutions! Motor Controllers: Motor Starters Soft-starters Drives Servo Controllers Wiring & Connection Systems: Busbar Mounting Systems Adapter Modules Commoning Links & Feeder Blocks Power Distribution Blocks Terminal Blocks Fuse Holders Feeder Devices: Disconnect Switches Circuit Breakers 19 19

20 140U-D Branch Circuit Protection Device 140U-D MCCB UL 489 Molded Case Circuit Breaker Current Limiting Thermal/Magnetic Protection 2 & 3 Pole A Ir Range 480V, kA Interrupting Ratings 45mm wide Full Line Accessories: Aux, Shunt, Under-voltage Commoning Links & Feeder Block Operating Handles Connection Modules 20

21 MCC & IC Panel Applications 140U-D Vertical Bus 480V) Fuseless & Mission Critical Circuits ACB Main Incomer Motor Branch Circuit Breaker 140U-H..L MCCB (Iq = 480V) Horizontal Bus 480V) Feeder Breaker 140U-H..L MCCB (Iq = 480V) Non Motor Loads Lighting Heaters Metering Transformers Power Supplies Control Circuits PLC Control (Iq = 480V) Branch 140U-D MCCB (Iq = 480V) Eliminates requirement for Series or Cascading Ratings 21

22 IEC Switchgear & Control-gear Application of SCCR per IEC IEC Part 1 - General Rules Covers all Switchgear & Control-gear variants in Series No longer includes TTA or PTTA designations, now satisfied thru verification rules General requirements: Panel must have a SCCR rating that covers the available fault current Same requirement as NEC & UL Panel SCCR is determined by equipment manufacturer per Same requirement as NEC & UL Different process to determine ratings 22

23 IEC Verification of Performance under Short-circuit Conditions Verification by the application of Design Rules, Calculation or Test. Verification based on the Reference Design Original Manufacturer Design Must be Tested Verification not required for the following; Short-circuit Prospective Fault (Icp) or Withstand (Icw) is <10kA Conditional Short-circuit Current where the Ipk is <17kA Auxiliary Circuits are connected to transformers < 10kA All other circuits must be verified 23

24 IEC Reference Design Reference Design based on: Original Manufacturer assembly Focus on the bus structure & connection systems Verification by test for SC Current Withstand! Types of Ratings: Short-time Current Withstand Icw = Rated ka for 1..3 sec. I 2 t & Ipk (Thermal/Dynamic Stress) Conditional Short-circuit Current Reference Design Ue = 415V Icw = 50kA, 1 sec Ipk = 105kA Icc = Rated ka at rated voltage with specified SCPD (CB or Fuses) Ratings can be used for verification by calculation: Acceptability of assembly for installation Evaluation of circuits within the assembly Coordination of SCPD selection System V = 400V f = 50Hz Icp = 25kA Internal Circuits Feeders & BCPD = CB Icu/Ics = 50kA V = 415V Branch Components Icc= 50kA V = 415V 24

25 IEC SC Verification Design Checklist Verification by Design Compares original Reference Design to new variant assembly Design Checklist reviews: Icw, conductor cross-section, spacings, materials, enclosure size & compartment design If all questions answered yes, additional verification not required Additional evaluations: Series or Cascading Ratings Circuit Impedances, Cable Lengths Let-thru Characteristics (I 2 t & Ipk) Withstand Characteristics (ka & tsec) Devices evaluated (power blocks?) 25

26 Presentation Agenda SCCR Background NEC, UL 508A SB and IEC MCS Motor Starter Circuits SMC Soft-Starter Circuits PowerFlex Drive Circuits rockwellautomation.com Web Tool Executive Summary 26

27 Branch Circuit Solutions Branch circuit solutions can be complex: Component selection can be difficult to determine coordinated High Fault SCCR RA Branch Circuit Solutions: Tested at RA Accredited High Current Test Facilities Test Programs approved & witnessed by UL Third Party Certification Ratings included in UL File Reports Ratings are typically attained with standard component sizing, limited oversizing required Provide web tool for customer ease of selection Select product solution Select application parameters Output: SCCR Selection Table and One Line BOM 27

28 Global SCCR Applications 25kA, 690V 50kA, 575V 30kA, 575V 65kA, 460V 65kA, V 65kA, 400V 50kA, V 80kA, 690V 50kA, 380V 65kA, V 50kA, 380V 50kA, 415V 50kA, 400V 50kA, 440V 65kA, 400V 50kA, 525V 65kA, 400V 50kA, 690V 28

29 Presentation Agenda SCCR Background NEC, UL 508A SB vs. IEC MCS Motor Starter Circuits SMC Soft-Starter Circuits PowerFlex Drive Circuits rockwellautomation.com Web Tool Global SCCR Summary 29

30 SCCR for Motor Starter Combinations Global Voltages: V, 415V, 440V, 525V, 690V 50Hz 460/480, 575/600V 60Hz Short Circuit Performance: 50, 65 & 100kA Type 1, Type 2 Branch Protection Devices: Fuses, MCP, MCCB, MPCB Motor Starters: ( A) 2C Starters (MPCB + Contactor) 3C Starters (MCP + Contactor + OLR) 3C Starters (Fuses + Contactor + OLR) 2C Load Feeder (MCCB + Contactor) Motor Overload Protection: Electronic Bimetal

31 Selection Tables & Test Summary Letters 3 Component Starters (MCP + Contactor + OLR) - SCCR: 460V - 3C Starters w/ UL MCP - Type 2 Coordination 31

32 Selection Tables & Test Summary Letters 2 Component Starters (MPCB + Contactor) - SCCR: 400V - 2C Starters w/ MPCB - Type 2 Coordination 32

33 Presentation Agenda SCCR Background NEC, UL 508A SB vs. IEC MCS Motor Starter Circuits SMC Soft-Starter Circuits PowerFlex Drive Circuits rockwellautomation.com Web Tool Global SCCR Summary 33

34 SCCR Branch Circuit Solutions SMC Soft-Starters Global Voltages: 220V, V, 415V, 440V, 525V, 690V 50Hz V, 230V, 460V, 575V 60Hz Short Circuit Performance: Standard Fault, 65 & 100kA Type 1, Type 2 Coordination Branch Protection Devices: Fuses & Circuit Breakers Soft-Starters: (1..800A) SMC-3 SMC-50 SMC Flex Starting Modes: Line & Delta Connected Motors Standard & Heavy Duty 34

35 Soft-Starter Circuit Solutions Line & Delta Connected SMC-3 SMC-50 Line Connected Delta Connected Line Connected Delta Connected Fuse SCPD BCPD Fused Disconnect BCPD Fused Disconnect BCPD Fused Disconnect K1M Input K1M Input K1M Input K1M Input Terminal Block SCR Fuse SCR Fuse SCR Fuse SCR Fuse SMC 3 SMC 3 R By pass Starter R By pass Starter SMC 50 SMC 50 K2M Output K2M Output K2M Output K2M Output M 3~ M 3~ M 3~ M 3~ 35

36 SCCR Selection Table SMC-3 w/ Fuses Short-circuit Coordination Starter Type: S.C. Protective Device: Soft-starter - Line Connected Motors Normal Duty Rating - AC53b Fuses + Line Contactors + SMC-3 UL/CSA Class J & L Fuses, Current Limiting Line Contactor: 100-C, 100-D (100S-C, 100S-D) Soft-starter: SMC-3 Smart Motor Controller Rated Operational Voltage: 460V 60Hz (480V Line) Test Voltage: 600V 60Hz Rated Conditional S.C. Current (Iq): 70kA (rms sym.) Level of S.C. Coordination: Type "1" or "2" per IEC UL 508 High Fault SCCR M 3~ Fuse SCPD K1M Input SCR Fuse SMC 3 K2M Output - SCCR: 460V - UL Fuse Protection - Normal Duty Starting - Type 2 Coordination Motor SMC-3 Branch Circuit Protection Device - Fuse Line Contactor SCR Fuse (Optional) IEC Coordination 3 ph 1500 rpm Thermal Utilization Max. Current Disconnect Switch Input/Output Max Current Coordination Cat. No. Setting Category Class Rating Cat. No. Cat. No. Class Rating Type [HP] [A] 1) 2) [A] IEC ) [A] Class J & L Fuses 4) 5) [A] 6) Remark 1/ C3NB AC53b: : 3585 J R-J C09 HSJ / C3NB AC53b: : 3585 J R-J C09 HSJ C3NB AC53b: : 3585 J 3 194R-J C09 HSJ / C3NB AC53b: : 3585 J R-J C09 HSJ C9NB AC53b: : 3585 J 6 194R-J C09 HSJ C9NB AC53b: : 3585 J 8 194R-J C09 HSJ C9NB AC53b: : 3585 J R-J C09 HSJ / C16NB AC53b: : 3585 J R-J C12 HSJ C16NB AC53b: : 3585 J R-J C16 HSJ 25 Type C25NB AC53b: : 3585 J R-J C23 HSJ C30NB AC53b: : 3585 J R-J C30 A70P C37NB AC53b: : 3585 J R-J C37 A70P C43NB AC53b: : 1770 J R-J C43 A70P C60NB AC53b: : 1770 J R-J C60 A70P C85NB AC53b: : 3570 J R-J C72 A70P C85NB AC53b: : 3570 J R-J C85 A70P C135NB AC53b: : 1770 J R-J C97 A70P C135NB AC53b: : 1770 J R-J D140 A70P C201NB AC53b: : 1770 J R-J D180 A70P C201NB AC53b: : 1770 J R-J D180 A70P C251NB AC53b: : 1770 J R-J D250 A70P 630 Type C317NB AC53b: : 1770 J R-J D300 A70P C361NB AC53b: : 1770 J R-J D420 A70P C480NB AC53b: : 1770 L R-L D630 A70P kA C480NB AC53b: : 1770 L R-L D630 A70P kA 36

37 Presentation Agenda SCCR Background NEC, UL 508A SB vs. IEC MCS Motor Starter Circuits SMC Soft-Starter Circuits PowerFlex Drive Circuits rockwellautomation.com Web Tool Executive Summary 37

38 SCCR Branch Circuit Solutions PowerFlex Component Drives Global Voltages: 220V, V, 415V, 440V, 525V, 690V 50Hz 230/240V, 460/480, 575/600V 60Hz Short Circuit Performance: 65 & 100kA IEC Type 1 & 2 Coordination Branch Protection Devices: Fuses & Circuit Breakers (MCCB, MPCB) Motor Starters: (1..800A) PowerFlex 525 PowerFlex 4/4M PowerFlex 750 Series Circuit Variables: Circuit Protection Components Power/Line Conditioning Components Control Components 38

39 Drive Circuit Solutions Core Drive Components: Branch Circuit Protection Drive EMC Filter Isolation Transformers Line Reactors (Input/Output) Terminators Reflective Wave Devices Bypass Starter Line Branch circuit Protection Device Fuses or Circuit Breakers Isolation Contactor Line Reactor Control Components: Branch Circuit Protection Isolation Contactors (Input /Output) Bypass Starters SCR Fuse Output Contactor Multi-Motor Controllers (Output) Note: Components require SCCR s per UL 508A SB RWTM Single Motor Multi-motor 39

40 SCCR Selection Table PowerFlex 525 w/ Fuses - SCCR: 460V - UL Fuse Protection - Standard Fuse Sizing (Max) - Normal & Heavy Duty Starting - Type 2 Coordination 40

41 SCCR Selection Table PowerFlex 525 w/ Fuses - SCCR: 460V - UL Fuse Protection - Optimized Fuse Sizing - Normal & Heavy Duty Starting - Type 2 Coordination 41

42 SCCR Selection Table PowerFlex 525 w/ Circuit Breakers - SCCR: 460V - MCCB Circuit Breaker Protection - Normal & Heavy Duty Starting - Type 2 Coordination 42

43 SCCR Selection Table PowerFlex 525 w/ Circuit Breakers - SCCR: 400V - Circuit Breaker Protection - Normal & Heavy Duty Starting - Type 2 Coordination 43

44 Disconnecting Means Branch Circuits Control Connection Systems Branch Circuits Power 44

45 Presentation Agenda SCCR Background NEC, UL 508A SB vs. IEC MCS Motor Starter Circuits SMC Soft-Starter Circuits PowerFlex Drive Circuits rockwellautomation.com Web Tool Global SCCR Summary 45

46 Web Selection Tool Focus on Branch Circuit Solutions: Electromechanical Starters Soft-Starters Component Drives Selection based on: Common Voltage & Frequency Common SCCR Common Level of Coordination Data subject to change: New component introductions Optimized combination ratings Always Use Current Posted Documentation 46

47 Product Category IEC Motor Control 47

48 General Starter Data - Starter Type 2 Component Starters (MPCB + Contactor) 48

49 System Voltage Data Motor Voltage 460V, 60Hz 49

50 Performance Specification 140M C (Type E) 50

51 Available Documents SCCR Selection Table & Test Summary Letter 51

52 Selection Table & Test Summary Letter View, Print or Download 460V, 65kA HP SCCR Selection Table 460V, 65kA HP Test Summary Letter 52

53 productcertifications/ul508a 53

54 Global SCCR Summary High Fault SCCR requirements increasing globally UL 508A SB procedure can be applied to global applications RA customers require solutions for global voltages & faults levels Utilize Complete Branch Circuit Solutions: MCS Starter Circuits SMC Soft-starter Circuits PowerFlex Drive Circuits UL Witnessed & Listed Ratings SCCR Selection Tables One Line BOM Improving Customer Solutions! 54

55 Global Short-Circuit Current Ratings Global Products, Global Solutions Thank you for your time!! Follow ROKAutomation on Facebook & Twitter. Connect with us on LinkedIn. Rev 5058-CO900B

56 Presentation Agenda SCCR Background NEC, UL 508A SB vs. IEC MCS Motor Starter Circuits SMC Soft-Starter Circuits PowerFlex Drive Circuits rockwellautomation.com Web Tool Global SCCR Summary 57

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Guidelines on the Short Circuit Current Rating for Industrial Control Panels usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A

More information

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved.

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved. UL 508A Industrial Control Panels Power Distribution and Control Lunch & Learn Training 2002 Eaton Corporation. All rights reserved. Agenda Who is UL and what role do they play? What is the UL 508A Standard?

More information

UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL

UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL Definition of Terms / Explanations Overview of Basic Devices Construction Types acc. to UL 508 Self-Protected Combination Motor Controller

More information

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A Short-circuit current rating (SCCR) of industrial control panels NEC Article 409 and UL 508A Short-circuit current rating (SCCR) of industrial control panels 1 Introduction 2 Overview of NEC Article 409

More information

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Are You Ready For The New SCCR Marking Requirements? What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components

More information

Circuit Breakers. Next Generation of Protection Capabilities

Circuit Breakers. Next Generation of Protection Capabilities Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many

More information

Circuit Breakers Supplementary Protectors Manual Motor Controllers

Circuit Breakers Supplementary Protectors Manual Motor Controllers WHITE PAPER Circuit Breakers Supplementary Protectors Manual Motor Controllers Circuit Protection Methods Differentiating between Supplementary Protection, Branch Circuit Protection, and Self-Protected

More information

Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors. Technical Data

Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors. Technical Data Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors Technical Data Table of Contents Introduction... 4 Definitions... 5 Product Range... 8 Product Line Overview...11

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

Low Voltage Fuses For Motor Protection

Low Voltage Fuses For Motor Protection Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors.

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

Sentron Series Circuit Breakers

Sentron Series Circuit Breakers Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of

More information

Modan 3000 ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER. Systems Products and Services. Motor Control Centers Modan 3000

Modan 3000 ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER. Systems Products and Services. Motor Control Centers Modan 3000 Systems Products Motor Control Centers Modan 3 Modan 3 UL / CSA ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER MODAN 3 Motor Control Centers Offer: Over 1 years of Motor Control experience

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203 03/2013 Retain for future use. Introduction Short-circuit current s (SCCRs) for variable frequency drives (VFDs) is

More information

CONDUCTOR SHORT-CIRCUIT PROTECTION

CONDUCTOR SHORT-CIRCUIT PROTECTION CONDUCTOR SHORT-CIRCUIT PROTECTION Introduction: This paper analyzes the protection of wire from fault currents. It gives the specifier the necessary information regarding the short-circuit current rating

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Mission Critical Data Center Systems

Mission Critical Data Center Systems Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Safety By Design. Strategies for Electrical Contractors

Safety By Design. Strategies for Electrical Contractors Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure

More information

The easy way to build switchgear and controlgear assemblies in compliance with the regulations

The easy way to build switchgear and controlgear assemblies in compliance with the regulations The easy way to build switchgear and controlgear assemblies in compliance with the regulations A guide for partially type-tested switchgear and controlgear assemblies in compliance with EN 60 439 What

More information

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents

More information

Engineering Series Ratings: Is It Practical?

Engineering Series Ratings: Is It Practical? Engineering Series Ratings: Is It Practical? By the National Electrical Manufacturers Association The 2005 National Electrical Code (NEC) introduces a change regarding series ratings for circuit breakers

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Bulletin 1489-A Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable

More information

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole) Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic

More information

SMC -3 Specifications

SMC -3 Specifications Technical Data SMC -3 Specifications Bulletin Number 150 Topic Page Product Overview 2 Standards Compliance and Certifications 2 Features 3 Catalog Number Explanation 4 Wiring Diagrams 6 General Specifications

More information

Softstarters Type PSR

Softstarters Type PSR Catalog Softstarters Softstarters ABB Softstarters General To the left: A combination with PSR and a manual Motor Starter MS116 Above: PSR16, PSR30 and PSR 45 1 ABB Automation Products serve customers

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

PSR The compact range Description

PSR The compact range Description Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides

More information

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE WHITE PAPER WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE EXPLANATION AND ASSISTANCE FOR APPLYING SOLID STATE SOFT STARTERS IN TRADITIONAL REDUCED VOLTAGE APPLICATIONS Introduction..............................................................2

More information

History and Overview. Manual Motor Protectors & Combination Motor Controllers

History and Overview. Manual Motor Protectors & Combination Motor Controllers Manual Motor Protectors & Application te May 2005 Supersedes, April 2004 Applications: Manual Motor Starter Manual Motor Disconnect IEC Circuit Breaker (European Market) NEC Group Installation Motor Starter

More information

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents

More information

Applications. Remote Display Mounting Kits

Applications. Remote Display Mounting Kits June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge

More information

Vilter motor starter solutions The NEW industry standard in motor starter packages

Vilter motor starter solutions The NEW industry standard in motor starter packages Vilter motor starter solutions The NEW industry standard in motor starter packages Electrical safety by design Built to Underwriters Laboratory (UL) 508A UL Standard for Safety for Industrial Control Panels.

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Securing your electrical installations Prisma,

Securing your electrical installations Prisma, Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards

More information

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY PowerGate - Cost effective solutions for F 1 Horsepower Rating 001 1-40 HP (208V) 075 1-75 HP (480V) Input Voltage 2V 208-240V 4V 380-480V Disconnect

More information

Fusible Disconnect Switch

Fusible Disconnect Switch Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit

More information

3K Load-Break Switches The Program for Safety and Performance. sentric

3K Load-Break Switches The Program for Safety and Performance. sentric 3K Load-Break Switches The Program for Safety and Performance sentric Whether for reliable switching and isolation under load, or for protection against overload or short-circuits our 3K range of load-break

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

Corner-Grounded Delta (Grounded B Phase) Systems

Corner-Grounded Delta (Grounded B Phase) Systems Data Bulletin 2700DB0202R03/12 09/2012 Replaces 2700DB0202R2/09 dated 02/2009 Corner-Grounded Delta (Grounded B Phase) Systems Class 2700 Retain for future use. Introduction Corner-grounded delta systems

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers

Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Catalog 2004 Class 601 CONTENTS Description..............................................Page INTRODUCTION.............................................

More information

White paper. ABB solutions for switching and protection of low speed wind turbines

White paper. ABB solutions for switching and protection of low speed wind turbines White paper ABB solutions for switching and protection of low speed wind turbines ABB solutions for switching and protection of low speed wind turbines Index 1 Introduction...2 2 Full converter configuration...4

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,

More information

Overcurrent Protection

Overcurrent Protection Overcurrent Protection Data Bulletin 0600DB0301 R03/12, 03/2012 0600DB0301 R03/12, 03/2012 Overcurrent Protection Table of Contents Table of Contents Section 1: Overcurrent Protection Fundamentals and

More information

MOTOR PROTECTION AGAINST SINGLE-PHASING

MOTOR PROTECTION AGAINST SINGLE-PHASING THE SINGLE-PHASE DILEMMA: FACT OR FICTION PROTECTION AGAINST SINGLE-PHASING Bulletin PSP The Single-Phasing Issue: Fact or Fiction Overview Before discussing SINGLE-PHASING, let s take a look at some of

More information

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

National Craft Assessment and Certification Program S P E C I F I C A T I O N S National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

Using Murrelektronik MICO Modules to Create Low Voltage Limited Energy Circuits in Industrial Control Panels according to UL508A.

Using Murrelektronik MICO Modules to Create Low Voltage Limited Energy Circuits in Industrial Control Panels according to UL508A. WHITEPAPER Using Murrelektronik MICO Modules to Create Low Voltage Limited Energy Circuits in Industrial Control Panels according to UL508A. January 1 st, 2014 Sources: UL508A: UL Standard for Safety for

More information

PowerFlex 700 and 700H Packaged Drives. Technical Data

PowerFlex 700 and 700H Packaged Drives. Technical Data PowerFlex 700 and 700H Packaged Drives Technical Data Overview The heart of every PowerFlex 700/700H packaged drive package is a PowerFlex Adjustable Frequency Drive. The packaged drives program provides

More information

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

Rotary Disconnect Switch Specifications

Rotary Disconnect Switch Specifications Technical Data Rotary Disconnect Switch Specifications Bulletin Number 194R Topic Page Product Line Overview 2 General Specifications Fuse Description 12 Approximate Dimensions 14 Additional Resources

More information

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

SENTRON Switching and Protection Devices Air Circuit Breakers

SENTRON Switching and Protection Devices Air Circuit Breakers Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General

More information

Guide to the China Compulsory Certification System December 2009 OMRON Corporation Industrial Automation Company

Guide to the China Compulsory Certification System December 2009 OMRON Corporation Industrial Automation Company Guide to the China Compulsory Certification System December 2009 OMRON Corporation Industrial Automation Company -1- Contents Page 1. What Is CCC? 3 2. Procedure for Judging If a Product Is Subject to

More information

Medium Voltage Motor Control Assemblies

Medium Voltage Motor Control Assemblies Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................

More information

Low Voltage Switchboards The Best Technical Solution for Your Ship

Low Voltage Switchboards The Best Technical Solution for Your Ship The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

General information Circuit breakers for power distribution T1 T3

General information Circuit breakers for power distribution T1 T3 Circuit breakers for power distribution T1 T3 T1 T2 T3 T1 1P T1 T2 T3 UL 489 CSA C22.2 Frame size A 100 100 100 225 Number of poles Nr 1 3, 4 3, 4 3, 4 Rated voltage AC (50-60 Hz) V 277 600Y / 347V 480

More information

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) Fig1. CPTR SMART CONTROL PRECISION CUSTOMIZED MANUAL OR AUTO SCR OR DIODE DRY TYPE SWITCH MODE DRY TYPE SCR OR DIODE OIL TYPE 1 INDEX PAGE 1. Cover 2. Index

More information

Number 1 in efficiency

Number 1 in efficiency PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter Why

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

Changing industry standards: friend or foe?

Changing industry standards: friend or foe? Changing industry standards: friend or foe? In 1998, Google was founded, the first Apple imac was introduced and the legendary Windows 98 was released by Microsoft. In a less glamorous but equally important

More information

Application Technique. Safety Function: Magnetic Door Switch Monitoring

Application Technique. Safety Function: Magnetic Door Switch Monitoring Application Technique Safety Function: Magnetic Door Switch Monitoring Products: MC1 Magnetically-coded Door Switch, Guardmaster Dual-input Safety Relay Safety Rating: CAT. 3, PLd to EN ISO 13849-1: 2008

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

CPS 100 480Y S K CPS 100 480Y S C

CPS 100 480Y S K CPS 100 480Y S C Ref. No. 1299 Visor Series Ordering Guidelines Table.1-4. Retrofit Surge Protection Products TVSS General Description Clipper Power System Visor Series CPS 100 480Y S K.1-9 Surge Ratings 100 = /phase 120

More information

PREFACE. The products covered by this Guide are:

PREFACE. The products covered by this Guide are: PREFACE UL has developed the Molded-Case Circuit Breaker (MCCB) Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in

More information

IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

High Speed Fuses. High Speed Fuses

High Speed Fuses. High Speed Fuses Section Contents Page General Applications........................ 9-95 North American fuses & accessories............9-113 DFJ - High speed Class J fuse...................97 Square Body fuses & accessories............

More information

Motor Control Solutions for the North American Market

Motor Control Solutions for the North American Market Motor Control Solutions for the North American Market Data Bulletin 8536DB0901 Rev. 11/11, 1/2013 Retain for future use. Motor Control Solutions 8536DB0901 Table of Contents Rev. 11/11, 1/2013 Table of

More information

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module

More information

Electrical Shore Connections / Cold Ironing

Electrical Shore Connections / Cold Ironing STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

Comparative study for cables and busbars

Comparative study for cables and busbars Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary

More information

Data Bulletin. Choosing a Trip Unit for PowerPact H-, J-, and L-Frame Circuit Breakers. Introduction. Thermal-Magnetic or Electronic Trip Unit?

Data Bulletin. Choosing a Trip Unit for PowerPact H-, J-, and L-Frame Circuit Breakers. Introduction. Thermal-Magnetic or Electronic Trip Unit? Data Bulletin 011DB110 07/01 Choosing a Trip Unit for PowerPact H-, J-, and L-Frame Circuit Breakers ENGLISH Inoduction Thermal-Magnetic or Eleconic Trip Unit? Thermal-Magnetic Trip Units 01171 t 0119

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information