SHORT CIRCUIT STUDIES

Size: px
Start display at page:

Download "SHORT CIRCUIT STUDIES"

Transcription

1 4 SHORT CIRCUIT STUDIES 4.1 INTRODUCTION In a power system short circuits occur once in a while due to lightning, flash over due to polluted insulation, falling of tree branches on the overhead system, animal intrusion and erroneous operations. When the fault current magnitudes are significant, it can cause damage to equipment and explosion if the fault is not cleared for prolonged time. Also, electrical fires and shock hazards to people are possible in a faulted power system. Therefore, it is important to design the power system such that the fault is isolated quickly to minimize the equipment damage and improve personnel safety. Short circuit studies are performed to determine the magnitude of the current flowing throughout the power system at various time intervals after a fault. The magnitude of the current through the power system after a fault varies with time until it reaches a steady state condition. During the fault, the power system is called on to detect, interrupt and isolate these faults, The duty impressed on the equipment is dependent on the magnitude of the current, which is a function of the time of fault initiation. Such calculations are performed for various types of fault such as three-phase, single line to ground fault, double line to ground fault and at different location of the system. The calculated short circuit results are used to select fuses, circuit breakers and protective relays. The symmetrical component model is used in the analysis of the unsymmetrical faults with mutual coupling.

2 The power system components such as utility sources, generators, motors, transformers and cables are represented by impedance value. The short circuit study is performed by representing the electric network in a matrix form. The program places a fault at a required location and performs the short circuit calculations. The short circuit study results are performed according to the applicable industry standards. 4.2 SOURCES OF SHORT CIRCUIT CURRENTS The short circuit current contributions are from the utility sources, generators, synchronous condensers and induction motors. Typical current waveforms during a short circuit are shown in Figure 4.1 for various types of contributing sources. Utility sources - A utility represents the large interconnection of generators, transmission lines and load circuits. The transmission lines, distribution lines and transformers introduce impedance between the generator source and the fault point during a short circuit. Therefore, the source voltage remains unaffected during fault conditions. Generator sources - An in-plant generator contributes to a short circuit and the current decreases exponentially. The generator is driven by a prime mover and an exciter supplies the field; the steady state current will persist unless the circuit is open by a circuit breaker. The generator fault current is determined by three reactance values during various time frames: Xd" - Direct axis sub-transient reactance, during the first cycle Xd' - Direct axis transient reactance, during 1 to 2 seconds Xd - Direct axis reactance, during steady state The total short circuit current (It) of a generator consists of an ac component (lac) and a dc component (Idc). These components are given by equations 4.1 through 4.3. The ac component of the generator fault current is: Iac = X d X d e Td" + xd X d (4.1) The dc component of the generator currents is: r( 1 1 JL Idc = (V2) e'td (4.2)

3 The total generator fault current (It) is: c + Idc (4.3) The reactance values are expressed in per unit in the above equations and the calculated currents will be in per unit. An example is presented at the end of this Chapter to show the generator short circuit currents. Synchronous motor and synchronous condenser - The synchronous machines supply fault current like a synchronous generator. The fault current decays rapidly since the inertia of the motor and load acts as the prime mover with the field excitation maintained. The fault current diminishes as the motor/condenser slows down and the motor excitation decays. Induction motor load - The fault current contribution from an induction motor is due to the generator action produced by the load after the fault. The field flux of the induction motor is produced due to the stator voltage and hence the current contribution decays very rapidly upon fault clearing as the terminal voltage is removed. Total fault current as a function of time - When a short circuit occurs in a system, the circuit impedance decreases appreciably. Therefore, the circuit current increases significantly as shown in Figure 4.2. During an asymmetrical fault, the total current can be treated as the sum of a dc current and a symmetrical ac component. The direct component eventually decays to zero as the stored energy in the system is expended in the form of I R loss. The direct current decay is inversely proportional to the X/R ratio of the system between the source and the fault. Therefore, it is important to analyze the short circuit current during the first cycle, the next several cycles and in the steady state.

4 UTILITY CONTRIBUTION GENERATOR CONTRIBUTION SYNCHRONOUS MOTOR CONTRIBUTION INDUCTION MOTOR CONTRIBUTION TOTAL SHORT-CIRCUIT CURRENT WAVEFORM Figure 4.1 Decaying Short Circuit Current Waveforms

5 TOTAL DC SHORT-CIRCUIT COMPONENT a CURRENT 4.3 SYSTEM IMPEDANCE DATA Figure 4.2 Total Fault Current Waveform Each component in an electrical system is represented by a suitable impedance value. Then the impedance values are converted to a common base. The system impedance data related issues are presented below. Source data - The utility source is represented by a per unit impedance which is equivalent to the maximum short circuit MVA level available from the utility at the point of common coupling. The minimum source impedance is used in the short circuit current calculations for relay settings. The source impedance data is usually provided by the system/utility. Example The three-phase and one line to ground fault short circuit duties of a 230 kv, 3-phase power system is 671 MVA and 738 MVA respectively. Find the symmetrical component impedance values on a 100 MVA base. Solution - Use an X/R ratio of 20. _~ kv MVA,3ph 671 = 78.8 Ohm X (base) on 100 MVA base = (230 x 230)/ Ohm

6 X, on 100 MVA base = Ohm/529 Ohm P.U. Ri on 100 MVA base = P.U./20 = P.U. X = - =57.5 Ohm 0 MVA, slg MVA,3ph X 0 on 100 MVA base = 57.5 Ohm/529 Ohm = P.U. Ro on 1 00 MVA base = P.U./ P.U. Transmission lines - The transmission lines are represented by positive and zero sequence impedance values. The approach to calculate the transmission line constants and typical values are presented in Chapter 2. In transmission lines it is assumed that the positive and negative sequence impedance values are equal. Cable data - The cable impedance values are presented by the positive and zero sequence impedance values. The calculation procedures are discussed in Chapter 2. Transformer impedance - The transformer impedance values are given in percentage on the self-cooled transformer kva rating and are converted to per unit on the study base. Typical impedance data of two winding transformers up to 2.4 kv are presented in Table 4.1. Table 4.1 Typical Transformer Impedance up to 2.4 kv 3-Phase kva X/R Ratio % Impedance Range The impedance values for the transformers above 2.4 kv are listed in Table 4.2.

7 Table 4.2 Typical Transformer Impedance Above 2.4 kv Ratings Primary kv Primary kvbil % Impedance Range For the calculation of the line to ground fault short circuit currents, the zero sequence connection diagram for certain transformers are required. Synchronous machines - A synchronous machine is represented by the subtransient direct axis reactance. Typical reactance values for various synchronous machines are presented in Table 4.3. Table 4.3 Typical Reactance of Synchronous Machines in Percentage Type of Generator Turbo generator, 2 -pole Turbo generator, 4-pole Waterwheel generator, no damper Waterwheel generator, with damper Synchronous condenser Salient pole motor, high speed Salient pole motor, low speed Xd Xq Xd' Xd" X xo Note: Use average value as typical data and on machine MVA base. Induction motors - The kva rating of induction motors is approximately equal to the hp rating. The sub-transient reactance is given by the locked rotor reactance. Typical locked rotor reactance values of various induction motors are given by: Over 600 V = 0.17 P.U. on machine kva base 600 V and less = 0.25 P.U. on machine kva base The motor resistance can be calculated using the X/R ratio curve given in ANSI Standard 242. Sometimes, the motors in each substation are lumped by type and size and a single per unit impedance is determined based on the lumped kva.

8 4.4 SHORT CIRCUIT CALCULATIONS The following short circuit calculations are generally performed. Three-phase fault - The three-phase conductors are shorted together. The magnitude of the fault current is given by: If = (4.4) L \ Where E is the phase voltage and Zl is the positive sequence impedance. Phase to ground fault - Where one phase conductor is shorted to ground. The fault current magnitude is given by: If = (Z + z E +z ) (L \ +L 2 0 } (4 ' 5) Where Zi, Zi and Zo are the positive, negative and zero sequence impedances respectively. Double line to ground fault - Where two phase conductors are shorted to ground. The positive sequence current magnitude is given by: z /rz +z Z 0 ( 2 (4 ' 6) The three-phase fault currents are the highest and least for phase to ground fault. However, the phase to ground fault current can be the highest under certain circumstances such as: Near solidly grounded synchronous machines. Near the solidly connected wye of a delta/wye transformer of the three phase core/three leg design. A grounded wye/delta tertiary auto-transformer. A grounded wye grounded wye/delta, three winding transformer. Therefore, in systems with the above type of connections, it is necessary to conduct a phase to ground fault calculation. For resistance grounded systems, the phase to ground fault currents will be limited. The following assumptions are made in the short circuit calculations:

9 An unloaded power system is considered. The impedance at the fault location is assumed to be zero. Load characteristics are ignored. Motors are assumed to run at rated speed with rated terminal voltage. Nominal transformer taps will be considered. A symmetrical three-phase power system is considered. The momentary or first cycle, the interrupting and the symmetrical short circuit currents are calculated to meet the circuit breaker selection and relay applications. Momentary or first cycle short circuit current calculations - The momentary or first cycle current is used to evaluate the closing or latching of the medium or high voltage circuit breaker. The circuit impedance of the utility sources, generators, transmission lines and transformers are used for the momentary current calculations. The sub-transient reactance of utility source and the generator are used. The reactance of the synchronous motors and induction motors are modified according to Table 4.4 from IEEE Standard 141. Table 4.4 Multipliers for Short Circuit Current Calculations Type of Rotating Machine LV Studies First Cycle Interrupting Generator, hydro generators with amortisseur windings & condensers Synchronous motors Induction motors Above 1000 hp at 1800 rpm or less Above 250 hp at 3600 rpm All others, 50 hp and above Less than 50 hp 1.0 Xd" 1.0 Xd" 1.0 Xd" 1.0 Xd" 1.0 Xd" Neglect 1.0 Xd" 1.0 Xd" 1.0 Xd" 1.0 Xd" 1.2Xd" Neglect 1.0 Xd" l.sxd" 1.5Xd" l.sxd" 3.0Xd" Neglect The impedance of the equivalent network is established and is converted into per unit at each fault point. The first cycle fault current is calculated using the pre fault voltage and the impedance at the faulted node. The approximate calculated first cycle fault current for comparison with the circuit breaker capability is obtained by using a 1.6 multiplier specified in ANSI C The total three phase symmetrical fault current (Isc tot) is: Isc tot Epu L6 Ibase (4.7) Xpu This current magnitude is compared with the latching current rating of a circuit breaker and the instantaneous rating of the relay settings.

10 Interrupting current calculations - The interrupting fault currents are calculated in accordance with ANSI C for symmetrical current rated circuit breaker applications. The reactance of the rotating machines is chosen and applied as per the multiplying factors listed in Table 4.4. For the calculation of the interrupting currents, both the resistance and reactance of the equivalent circuit is needed. Therefore, the equivalent R and X are calculated at the fault point and the X/R ratio is determined. The interrupting current is calculated using the E/Z method. A multiplying factor is calculated using the X/R ratio and the contact parting time of the circuit breaker. The minimum contact parting times are presented in Table 4.5 obtained from ANSI C Table 4.5 Contact Parting Time for Circuit Breakers Rated Interrupting Time Cycles at 60 Hz Minimum Contact Parting Time, Cycles at 60 Hz The multiplying factors are plotted in ANSI C for two specific conditions. Fault fed predominantly from generators for three-phase faults (8, 5, 3 and 2 cycles). Fault fed predominantly from networks with two or more transformations for three phase and line to ground faults (8, 5, 3 and 2 cycles). The calculated interrupting fault current (lin) is given by: Epu lin = (Multiplying Factor) ibase (4.10) Xpu This interrupting current is to be compared with circuit breaker interrupting capability. It can be seen that the short circuit calculation procedures for the momentary duty and the interrupting duty are different. Short circuit calculations for low voltage circuit breaker applications - The impedance diagram for evaluating the short circuit current at the faulted point developed. The rotating machine impedance values used without multiplying factors are shown in Table 4.4. The resistance values are also calculated using the

11 procedure used in the interrupting current calculations. The fault current is given by E/Z. The low voltage short circuit values are used for the selection of the circuit breakers including the molded case types. Short circuit current calculation for relay applications - For the instantaneous relay setting, the fault current magnitude from the momentary duty is used. For other applications with a time delay, the steady state symmetrical fault currents are calculated and used. The impedance for the transformer, overhead line and the cables are obtained for the steady state conditions. The motor contributions are neglected. For synchronous machines the steady state reactance can be used. In this case it can be seen that the dc component has almost decayed to zero and it is not considered. The required symmetrical fault current is obtained by using the E/Z method. In many power system and industrial set ups, the source impedance is different for peak and off-peak conditions. Therefore, the maximum and minimum fault currents are to be calculated and the relay settings should be verified for both conditions. Impedance diagram - The impedance diagram is derived from the one line diagram by modeling the circuit elements by the respective impedance. The impedance magnitude used for the fault calculation depends on many factors which are discussed in the circuit breaker current rating calculations. This is important for the reactance of the rotating machines (see Table 4.4). Once the fault location and type of short circuit is identified, then the corresponding impedance diagram is developed. This concept is demonstrated with the help of an example. Per unit quantities - For a balanced three-phase system, the relation of three-phase kva, line to line voltage, base current and base impedance are defined as: Base kva Base current = T= (411) V3(BasekV) (BasekVA) 2 Base impedance = (4 12) BaseMVA For changing the P.U. impedance from the given base kv to new base kv: Xnew (Xgiven) 'kv. given ~kv new (4.13) When both the kva and kv are new, then the new P.U. impedance can be calculated using the following equation:

12 Xnew f.,,. kva new (Xgiven) kva ^ given \f-kv. given (4.14) kv new Example The nameplate specifications of a two winding transformer are 40 MVA, 69 kv/13.8 kv, delta/wye-grounded, 7% impedance. This transformer is to be connected in a 13.2 kv distribution system. The system studies are performed on a 100 MVA base. Calculate the transformer impedance on 13.2 kv and 100 MVA base. Solution - The new P.U. impedance can be calculated as: f r\r\\ f i o \^ Xnew = (7.0% J[ J =2.7324% 4.5 COMPUTER-AIDED ANALYSIS There are several programs available to perform the short circuit studies. These programs can be used to perform the following data-related operations. Convert the raw system data to a common base. Prepare one-line diagrams. Determine system impedance for the calculation of momentary, interrupting, symmetrical and relay short circuit currents. The input data to these programs can be entered interactively or presented in ASCII data files or through graphic interface. The output of the short circuit study includes the following. Short circuit input data used in the network analysis. Calculations of three-phase, single line to ground fault, line to line and double line to ground fault currents. For the three-phase, 4 wire system with a neutral conductor, the short circuit currents are required for the line to neutral short circuit. Calculation of appropriate circuit breaker current ratings based on ANSI or IEC standards. Some programs present the short circuit outputs in a one line diagram with the calculated values. Summary of currents at all the buses. The user selects the necessary short circuit results at appropriate buses and

13 compares the results with the circuit breaker ratings. Also, the short circuit currents are compared with the equipment short circuit ratings to ensure safe performance. Example An industrial power plant is shown in Figure 4.3. The 230 kv source has a three-phase circuit current rating of 28,000 A. The step down transformer (Tl) is 100 MVA, 230/24 kv, 0.10 P.U. reactance, delta/wyegrounded with an X/R ratio of 20. There is a 500 MVA standby generator connected to the 24 kv bus. The reactance of the generator is 0.2 P.U with X/R ratio of 20. Transformer T2 is 75 MVA, 24/4.16 kv, delta/wye, 0.11 P.U. reactance with X/R ratio of 30. There are two 2,000 hp, 0.9 power factor, Xd" = 0.2 P.U, Xd 1 = 0.26 P.U. with X/R ratio of 20. The low voltage system contains a transformer T3, 4.16 kv/600 V, 0.08 P.U reactance and X/R There is a low voltage motor at the 600 V bus with a rating of 400 hp, Xd" = 0.3 and X/R = 30. Perform a short circuit study using computer-aided software and determine the short circuit currents at Fl and F2. Also, show the step-by-step calculations. Compare the results. Solution - The reactance of all the passive elements are listed below. A 100 MVA base is used in the calculations. Transformer, Tl, X = (0.10)( 100/100) Transformer, T2, X = (0.11)( 100/75) Transformer, T3, X = (0.08)(100/0.75) = 0.1 P.U. =0.15 P.U. = P.U. Sub-transient reactance of rotating machines 230 kv system short circuit MVA = (>/3 ) (230 kv) (28 ka) = kv source impedance, X = 1.0 (100/11154) = P.U. Generator Gl, X = (0.25) (100/500) = 0.05 P.U. Induction motor Ml, X = (0.20) (100/2) = 10 P.U. Induction motor M2, X = (0.20) (100/2) = 10 P.U. Induction motor M3, X = (0.30) (100/0.4) = 75 P.U. Momentary fault current calculations - For the momentary or first cycle short circuit calculation, induction motors less than 50 hp are omitted. For the 400 hp motor, X = 1.2 Xd" = (1.2) (75 P.U.) = 90 P.U. The reactance of the source, generator and the induction motors are identified in the impedance diagram for the first cycle or momentary short circuit calculations, in Figure 4.4.

14 SOURCE, 23O kv Gl 24 kv 4.16 kv M2 Ml M3 Figure 4.3 One-Line Diagram for Example P.U Figure 4.4 Impedance Diagram for the Momentary Duty Calculation The symmetrical first cycle or momentary short circuit current at the faulted point Fl is calculated as: Ibase at the 4.16 kv bus = 100 MVA/( >/3 )(4.16 kv) ka 1 Isym = (13.879kA) =78.3 ka The peak value of the momentary short circuit current is (1.6 x 78.3 ka) ka.

15 Calculation of the interrupting short circuit current - The impedance diagram is shown in Figure 4.5. The reactance, X/R ratios and the resistances for the circuit breaker interrupting current calculations are listed below. Transformer Tl, X/R = 30, R = (0.10/30) Transformer T2, X/R = 30, R = (0.15/30) Transformer T3, X/R = 30, R = (10.67/30) 230 kv system, X/R = 20, R - ( /20) Generator Gl, X/R = 20, R = (0.05/20) Motor Ml, X = (1.5 Xd") = (1.5 x 10) Motor Ml, X/R = 20, R = (15/20) Motor M2, X/R = 20, R = (15/20) Motor M3, X = (3 Xd") = 3 x 75 Motor M3, X/R = 30, R = (225/30) E/X = (13.879kA) = 77.32kA J = P.U. = P.U P.U. = P.U. = P.U. = 15 P.U. = 0.75 P.U. = 0.75 P.U. = 225 P.U. = 7.5 P.U P.U 1795 P.U Figure 4.5 Impedance Diagram for the Interrupting Duty Calculation

16 P.U Figure 4.6 Resistance Diagram for the Interrupting Duty Calculation The resistance circuit for the interrupting duty calculation is presented in Figure 4.6. Using the reduced R, the X/R ratio is calculated at the faulted point Fl. The X/R ratio at the faulted point Fl = / = The corresponding NCAD ratio is determined from C The NCAD ratio for X/R ratio of is The interrupting current = (77.32 ka) (0.96) = 74.2 ka Short circuit calculation for low voltage circuit breaker applications - The impedance diagram for evaluating the short circuit current at the faulted point F2 is shown in Figure 4.7. The impedance at F2 = ( j ) P.U. = P.U. The base current at 600 V is ka. The short circuit current at F2is ka P.IM P.U P.U P.U 3.56 P.U 2.5 P.U Figure 4.7 Impedance Diagram for the Low Voltage Short Circuit Current Study

17 Computer-aided analysis - The data is entered interactively to the program and the input data listings and the output summary are presented below. The software used in the calculations was the AFAULT program from the SKM System Analysis. The present version of the program is called Power tools for Windows with the particular option [9]. The program performs the calculations by placing various faults at each node for different fault duties. The equipment voltage rating, reactance and the reactance to the 100 MVA base are displayed. The input data is classified into various sections as discussed below. Source data as per List From Bus, to Bus, Voltage, Base MVA, Xd", X/R, X on 100 MVA Base. List 4.1 Source Data From Bus To Bus kv Base MVA Xd" P.U X/R Zon 100 MVA Base P.U Source Generator 1 Motor M 1 Motor M2 Motor M3 Bus 1 Bus 5 Bus 9 Bus 10 Bus ( J ) ( j 0.05) (0.5 +j 10) (0.5 +j 10) (2.5+J75) Feeder data as per List 4.2. The assumed impedance values are low and are not used in the step-by-step calculations. From Bus, to Bus, Voltage, Length in Feet, Zl or Z2 in P.U, ZO in P.U. List 4.2 Feeder Data From Bus Bus 1 Bus 3 Bus 4 Bus 4 Bus? Bus 8 Bus 9 To Bus Bus 2 Bus 4 Bus 5 Bus 6 Bus 8 Bus 9 Bus 10 Line Length kv Feet ZlorZ2, P.U. ZO, P.U (0.0 +j 0.01) (0.0 +j 0.03) (0.0 +j 0.01) (0.0 +j 0.03) (0.0 + j ) (0.0 + j ) (0.0 +j ) (0.0 + j ) (0.0 +j ) (0.0 + j ) (0.0 + j ) (0.0 +j ) (0.0 +j ) (0.0 +j 0.026) Transformer data as per List Primary Bus, Connection, Voltage, Secondary Bus, Connection, Voltage, MVA Base, Z1/Z2 on 100 MVA Base, ZO on 100 MVA Base.

18 List 4.3 Transformer Data From Bus To Bus Primary Conn Primary Sec kv Conn Sec kv Zl orz2, P.U. ZO, P.U. Bus 2 Bus 6 Bus 8 Bus 3 Bus? Bus 11 Del Del Del Wye Wye Wye (0.03 +j 0.10) ( j ) (0.36 +j ) ( j 0.10) ( JO. 1467) (0.36 +j ) The program calculates the short circuit components at each bus location for the various fault duties along with the summary for each type of calculations. The summary of the typical output listing is presented below. Fault current for the low voltage circuit breaker applications as per List 4.4. The list includes the Bus Number, Bus Name, Voltage, Fault Current for Three- Phase, X/R Ratio, Fault Current for SLG, X/R Ratio. List 4.4 Fault Current for the Low Voltage Circuit Breaker Applications Bus# Bus Name Voltage Volts 3 Phase Fit, ka 3 Phase X/R SLG ka SLG X/R BUS 1 BUS 2 BUS 3 BUS 4 BUSS BUS 6 BUS 7 BUSS BUS 9 BUS 10 BUS Fault current for momentary or first cycle as per List 4.5. The list includes the Bus Number, Bus Name, Voltage, Fault Current for 3-Phase, X/R Ratio, Fault Current for SLG, X/R Ratio. The fault current magnitude is 1.6 times the short circuit at the fault location. Fault current for interrupting as per List 4.6. The output contains the Bus Number, Bus Name, Voltage, decrement ratio, Fault Current for three-phase, X/R Ratio, Fault Current for SLG, X/R Ratio.

19 Bus# List 4.5 Fault Current for the Momentary Duty Bus Name BUS1 BUS 2 BUS 3 BUS 4 BUSS BUS 6 BUS 7 BUSS BUS 9 BUS 10 Voltage Volts Phase E/Z* Phase X/R SLG E/Z* SLG X/R List 4.6 Fault Current for the Interrupting Duty Bus# Bus Name Voltage Volts Ratio 3 Phase E/ZKA 3 Phase X/R SLG E/ZKA SLG X/R BUS 1 BUS 2 BUSS BUS 4 BUSS BUS 6 BUS 7 BUS 8 BUS 9 BUS The results from the step-by-step calculations and the computer-aided analysis are compared at the faulted points Fl (node 8) and F2 (node 11). Description Calculated Computer-Aided Momentary at Fl (node 8) ka ka Interrupting at F1 (node 8) 74.2 ka ka Low voltage short circuit at F2 (node 11) ka ka In the step-by-step calculations, the cable lengths are ignored. Therefore, the calculated short circuit currents are higher than the values from the computer-aided analysis.

20 4.6 LIMITING THE SHORT CIRCUIT CURRENTS Using series reactors, high impedance transformers and high resistance grounding can control the short circuit current in the power system. The series reactor can be used in the generator circuits, bus bars, feeders and in the shunt capacitance circuits. There are advantages and limitations to these approaches. With the application of shunt capacitor banks for power factor correction, there is always the inrush current issue during energization. Also, the outrush current from the capacitor banks is a concern when a line circuit breaker closes in to a nearby fault. In order to limit both the inrush and outrush currents series reactors are used. Three schemes of series reactors for shunt capacitor application are discussed. Scheme 1: Series reactor with each capacitor bank - Such a scheme is shown in Figure 4.8. In order to satisfy the criteria (Iph. f) to less than 2.0E+7, there will be two reactors with two capacitor banks. Scheme 2: Series capacitors for inrush and outrush requirements - The required scheme is shown in Figure 4.8. The reactor size for each capacitor bank will be small to limit the inrush current. A third reactor will be used to limit the outrush current. Scheme 3: Reactor to limit outrush current and breaker to limit the inrush current - The inrush current can be controlled by using circuit breaker with controlled switching or by using closing resistor/inductor. The outrush current can be controlled by using a series reactor. Such a scheme is shown in Figure 4.8. Example In order to demonstrate the circuit breaker selection and the application of series reactor for the current limiting a shunt capacitor bank, a case is presented. The circuit breaker is chosen to meet this application and the short circuit current magnitudes are calculated if the required current specifications are met. Then a reactor is chosen in series with the circuit breaker and the procedure is repeated. The system is a 230 kv, 60 Hz, three-phase with a short circuit rating of 40 ka. The circuit breaker has to be selected for capacitor switching application. The capacitor is available in two banks each of which is 60 MVAR.

21 Scheme 1 L1, L2 - Series Reactors C1, C2 - Capacitance L3 L1 -C1 L2 Scheme 2 L1, L2, L3- Series Reactors C1, C2 - Capacitance L3 L2 Scheme 3 L2, L3 - Series Reactors C1, C2 - Capacitance C2 Figure 4.8 Series Reactor Schemes for Current Limiting Solution - The circuit breaker is intended to switch 120 MVAR shunt capacitor banks and should meet the performance criteria described in ANSI C37.06 [7]. The desired performance specifications of the circuit breaker to meet the capacitor switching application (definite purpose) of the 230 kv systems are: Nominal voltage rating Maximum voltage rating Rated current Three-phase short circuit rating = 230 kv = 242 kv = 2000 A = 40kA

22 Rated capacitive current (breaking duty) TRY 188 kv peak - peak voltage base Inrush current Transient frequency = 400 A = 443 kv (2.4 PU) = 20 ka peak = 4,250 Hz Without current limiting reactor - When a system fault occurs near the capacitor bank location, the electrical energy stored in the capacitor bank discharges through the low fault impedance with considerable magnitude and at high frequency. Such a system is shown in Figure 4.9. The size of the 230 kv capacitor bank is 60 MVAR, three-phase. System Fault 'pk Capacitor Bank Figure 4.9 Fault Outside the Circuit Breaker Without Series Reactor The expected outrush current magnitude and frequency, for a single 60 MVAR, 230 kv capacitor bank is given by: /-< _ MVAR 60 2 >r(60) xkv 2 2 ;r(60) x = 3 MFD V 230 kvx / r Pk TI _ V/V3, A pk --_--^= kA.T _ 2 ^L f xc 2 >/36.1//Hx3//F = 15.3kHz An inductance of 10^ H for the bank and JU H/ft with a 100 feet cable length is used (IEEE C ).

23 The calculated outrush current magnitude of 54.1 ka is much higher than the allowable IEEE Standard C37.06 (Table 3A) value of 20 ka. Also, the frequency of the outrush current is higher than the allowed value of 4,250 Hz. The outrush current from the capacitor bank needs to be controlled using current limiting series reactors. The minimum series reactor needed to limit the (I p k x f) product to less than 2.0 x 10 is given by: V pk 'min 7 2n x2 xlo With current limiting reactor - The equivalent circuit with a series reactor in the shunt capacitor circuit is shown in Figure For the proposed 230 kv, 60 MVAR bank the minimum reactor needed is: T _ min ~ 230 kvx 2 ;r(2x!0 7 ) = 1.5 mh For the high outrush current to occur, a breaker must close into a fault very close to the 230 kv substation. A series inductor of 3 mh is selected for the 230 kv circuit and the corresponding Ipk and the frequency of oscillation are given by: = 6kA f = 2 A f xc 2 ^3000 yuhx3 = 1.68 khz This peak current and the frequency of oscillation are below the ANSI C37.06 values. Therefore, the circuit breaker is acceptable for the energization of the 230 kv, 60 MVAR shunt capacitor bank.

24 Reactor Circuit Breaker C1 = 60 MVAR Figure Capacitor Circuit with Series Reactor From this example, it is clear that series reactors can be useful in shunt capacitor circuits to limit the fault current magnitudes and in the protection of circuit breakers. Example Consider a 800 MVA, 13.8 kv generator with the following parameters: Xd" Xd? Xd = P.U P.U. =1.820 P.U. TdO" = TdO 1 = TdO =0.330 Calculate the total fault currents at 1.5 cycles. Solution - (IT) Xd" = (0.210)1 -^- = P.U. v j X'd = (0.330) = P.U. 800 f 100^1 Xd =(1.820) = P.U. \800j The ac components of the generator short circuit currents are: Id" = v^ xday = P.U.

25 Id' - = P.U. Id = V y = P.U. The time constants of the ac currents are given by: " ^ (TdO") = s = cycles T'd = Xd. X, (TdO') = s = cycles The ac component of the generator fault current is: t t Iac = (Id"-Id')e"Td" +(I'd-Id) e ~Td' +W At 1.5 cycles, the ac current components are: lac Ibase lac = ( x ) + ( x 0.982) = on 100 MVA base 100MVA = 4.18kA V3(13.8kV) = ( P.U.) (4.18 ka) = ka The dc component of the generator currents is: Idc = (A/2) (38.10) e ~Td Where Td in cycles is (0.33 x 60) 19.8 cycles. Idc at a time oft =1.5 cycles is: Idc = P.U. on a 100 MVA base = ( P.U. x 4.18 ka) = ka

26 The total generator fault current (It) is: It = Vlac 2 + Idc 2 = V = ka Therefore, in the generator circuit there are both ac and dc current components present as shown. PROBLEMS 1. The three-phase short circuit rating of a 230 kv, 60 Hz system is 670 MVA. The single line to ground fault rating is 600 MVA. Calculate the source impedance values on a 100 MVA base. State the assumptions made, if any. 2. The three phase short circuit rating of a 345 kv source is 20,000 MVA and the single line to ground short circuit MVA is 15,200 MVA. Calculate the sequence impedance of the source in P.U. on a 100 MAV base. 3. A 75 kva, 14 kv/4.16 kv, delta/wye-grounded, 6% impedance transformer is to be used in a 13.8 kv distribution system. The system studies are performed on a 100 MVA base. Calculate the transformer impedance for the new bases. 4. Calculate the total fault currents due to a 3-phase fault at the open terminals of a generator at 1.6 cycles. The name plate specifications of the generator are 500 MVA, 13.8 kv with the following parameters: Xd" =0.200 P.U. TdO" =0.030 Xd' =0.350 P.U. TdO' =8.000 Xd =1.800 P.U. TdO = What are the different types of faults in a power system? What is the role of a neutral conductor in the power system? 6. Why is it necessary to select a circuit breaker based on the short circuit current ratings? 7. Consider an industrial power system with a 115 kv source from a substation (Bus 1) to the next substation (Bus 2) connected through an overhead line. Bus 2 is connected to Bus 3 through an underground cable of 2,000 feet length. A step down transformer at Bus 3 supplies an electrical motor at 13.8 kv. The necessary system data are as follow:

27 Source impedance on 100 MVA base is: Z, =Z 2 = ( j ) P.U. Zo = ( j ) P.U. Overhead line impedance between Bus 1 and Bus 2 on 100 MVA base: Z = ( j ) P.U. Cable impedance between Bus 2 and Bus 3: Zi = ( j ) Ohm/1000 feet ZO = ( j ) Ohm/1000 feet Transformer impedance at Bus 3: MVA = 120 Voltage ratio =115 kv/4.16 kv Connection = Wye/Delta Reactance = 12% Induction motor drive: Rating =100MW Voltage = 13.8kV Power factor =0.8 Draw the one-line diagram of the system and state the assumptions. Calculate the short circuit currents at each node and select the circuit breaker ratings at appropriate locations. Also calculate the voltage drop at various locations. If the voltage profile is not acceptable, suggest suitable remedial actions. Compare the calculated results with a computer program output. 8. Refer to Example 4 regarding the energization of a 60 MVAR capacitor bank. Using the same circuit breaker, an additional 60 MVAR shunt capacitor bank is to be connected for power factor correction purposes. This capacitor bank is to be energized through a circuit switcher as shown in Figure The value of the series reactor is 20 mh. Calculate the Ipk and frequency of oscillation without series reactor and with series reactor. Discuss the circuit breaker suitability for the given application.

28 Circuit Switcher with Series Reactor Reactor Circuit Breaker C1 = 60 MVAR C2 = 60 MVAR Figure 4.11 Back-to-Back Capacitor Switching with a Circuit Switcher REFERENCES 1. ANSI/IEEE Standard: 141, IEEE Recommended Practice for Electrical Distribution for Industrial Plants, 1996 (Red Book). 2. ANSI/IEEE Standard: 399, IEEE Recommended Practice for Power System Analysis, 1990 (Brown Book). 3. ANSI Standard: C37.10, American National Standard Requirements for Transformers 230,000 Volts and Below. 4. ANSI Standard 242, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems, ANSI/IEEE Standard C37.010, IEEE Application Guide for AC High Voltage Circuit Breakers Based on a Symmetrical Current Basis, ANSI/IEEE Standard C37.13, IEEE Standard for Low Voltage AC Power Circuit Breakers Used in Enclosures, ANSI Standard C37.06, AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis, ANSI Standard C37.012, Application Guide for Capacitance Current Switching for AC High Voltage Circuit Breaker Rated on a Symmetrical Current Basis, Power Tools for Windows, SKM System Analysis, Inc., Manhattan Beach, California.

Physical Address: City: State: Zip Code:

Physical Address: City: State: Zip Code: Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (For Small Generator Facilities with Electric Nameplate Capacities of 10 MW and less) Applicant Contact

More information

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection

Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (See ARSD chapter 20:10:36 for the requirements for a Tier 2, Tier 3, or Tier 4 Interconnection.) Applicant/Interconnection

More information

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6 Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

PI734D - Technical Data Sheet

PI734D - Technical Data Sheet PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

PI734B - Technical Data Sheet

PI734B - Technical Data Sheet PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

PM734F - Technical Data Sheet Winding 28

PM734F - Technical Data Sheet Winding 28 - Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including

More information

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS PI144K - Winding 311 Technical Data Sheet PI144K SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section

More information

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet PI044E - Winding 311 Technical Data Sheet PI044E SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

UCI274C - Technical Data Sheet

UCI274C - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

UCI274H - Technical Data Sheet

UCI274H - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

Chapter 9 Balanced Faults

Chapter 9 Balanced Faults Chapter 9 alanced Faults 9.1 Introduction The most common types of fault are (in order) single-line-to-ground fault, line-to-line fault, and double-line-to-ground fault. All of these are unbalanced faults.

More information

FIT TIER 2 Application

FIT TIER 2 Application FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of

More information

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012 INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably

More information

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr. Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley

More information

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant

More information

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the

More information

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR 1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.

More information

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System

More information

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 106 Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos Grande-Moran, Ph.D. Principal

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

Unit 33 Three-Phase Motors

Unit 33 Three-Phase Motors Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

TABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4

TABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4 Page: 1 of 14 KEY BULLETIN POINTS: THIS GUIDE OUTLINES MINIMUM REQUIREMENTS FOR CONNECTION OF CUSTOMER-OWNED EMERGENCY AND STANDBY (ESG) TO THE GEORGIA POWER COMPANY (GPC) DISTRIBUTION SYSTEM. THESE ARE

More information

6. Synchronous machine dynamics

6. Synchronous machine dynamics 1 6. Synchronous machine dynamics In the middle of eighties, the present Type 59 synchronous machine model program was implemented and put into practical use in EMTP. In the first half of nineties, also

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan claudio.mardegan@engepower.com www.engepower.com Phone: 55 3579-8777

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.

More information

Joslyn Clark Controls, Inc.

Joslyn Clark Controls, Inc. Joslyn Clark Controls, Inc. CAPACITOR SWITCHING VACUUM CONTACTORS vs. AIR BREAK CONTACTORS APPLICATION PRECAUTIONS & CALCULATIONS TO LIMIT HIGH FREQUENCY & HIGH CURRENT 2 QUESTION: WHY IS A VACUUM CONTACTOR

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SUPPLY TO A THREE-PHASE AC FOR CONTROLLING THE SPEED OF A THREE-PHASE INDUCTION MOTOR BY USING A THREE-PHASE TO THREE-PHASE CYCLOCONVERTER

USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SUPPLY TO A THREE-PHASE AC FOR CONTROLLING THE SPEED OF A THREE-PHASE INDUCTION MOTOR BY USING A THREE-PHASE TO THREE-PHASE CYCLOCONVERTER International Journal of Electrical Engineering & Technology (IJEET) Volume 7, Issue 2, March-April, 2016, pp.19-28, Article ID: IJEET_07_02_003 Available online at http:// http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=7&itype=2

More information

Basics of Electricity

Basics of Electricity Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components

More information

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for

More information

Loading Considerations When Paralleling Transformers

Loading Considerations When Paralleling Transformers Application Guide 7400DB0701 02/2007 Nashville, TN, USA Loading Considerations When Paralleling Transformers Class 7400 Retain for future use. Introduction Principles of Paralleling This application guide

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

Introduction. Harmonics and IEEE 519 Page 1 of 19

Introduction. Harmonics and IEEE 519 Page 1 of 19 Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms

More information

AC-Synchronous Generator

AC-Synchronous Generator Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Power Quality Paper #3

Power Quality Paper #3 The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

BCI184E - Technical Data Sheet

BCI184E - Technical Data Sheet BCI184E - Technical Data Sheet BCI184E SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

Three phase circuits

Three phase circuits Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors

More information

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt. Lab 9: Synchronous motor. Objective: to examine the design of a 3-phase synchronous motor; to learn how to connect it; to obtain its starting characteristic; to determine the full-load characteristic of

More information

Chapter 12: Three Phase Circuits

Chapter 12: Three Phase Circuits Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in

More information

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS Bachelor's Thesis Electrical Engineering June 2014 SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS MD FARUQUL ALAM SALMAN SAIF HAMID ALI School of Engineering Blekinge Tekniska

More information

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters

More information

Simulation of Ungrounded Shipboard Power Systems in PSpice

Simulation of Ungrounded Shipboard Power Systems in PSpice Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University

More information

ACCURACY OF POTENTIALTRANSFORMERS

ACCURACY OF POTENTIALTRANSFORMERS 8 VOLTAGE TRANSFORMERS Two types of voltage transformer are used for protective-relaying purposes, as follows: (1) the "instrument potential transformer," hereafter to be called simply "potential transformer,"

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink Transient analysis of integrated solar/diesel hybrid power system using ATLAB Simulink Takyin Taky Chan School of Electrical Engineering Victoria University PO Box 14428 C, elbourne 81, Australia. Taky.Chan@vu.edu.au

More information

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc. Short-circuit, Protective Device Coordination & Arc Flash Analysis By Albert Marroquin Operation Technology, Inc. Agenda Short-circuit Calculations for Arc Flash Analysis Protection and Coordination Principles

More information

Interconnection of Generators to EDI s Distribution System

Interconnection of Generators to EDI s Distribution System Interconnection of Generators to EDI s Distribution System May 22, 2002 This document sets forth the guidelines for connecting a power producing facility to the Alberta Interconnected Electric System through

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

EARTHING SYSTEM CALCULATION

EARTHING SYSTEM CALCULATION BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references

More information

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC

More information

Appendix N: GENERATOR DATA SHEET FOR SYNCHRONOUS GENERATORS CONNECTED TO PG&E ELECTRIC SYSTEM

Appendix N: GENERATOR DATA SHEET FOR SYNCHRONOUS GENERATORS CONNECTED TO PG&E ELECTRIC SYSTEM Appendix N: GENERATOR DATA SHEET FOR SYNCHRONOUS GENERATORS CONNECTED TO PG&E ELECTRIC SYSTEM TECHNICAL DATA SHEET FOR SYNCHRONOUS MACHINES IN THE PG&E SYSTEM FOR POWER FLOW, TRANSIENT STABILITY, AND FAULT

More information

High Efficiency Motor Protection. Industry White Paper

High Efficiency Motor Protection. Industry White Paper High Efficiency Motor Protection Industry White Paper 2 High Efficiency Motor Protection High Efficiency Motor Protection - An Overview Electric motor protection depends on the accurate selection of overloads,

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

Voltage regulation in distribution systems - Tap changer and Wind Power

Voltage regulation in distribution systems - Tap changer and Wind Power CODEN:LUTEDX/(TEIE-5270)/1-59/(2010) Industrial Electrical Engineering and Automation Voltage regulation in distribution systems - Tap changer and Wind Power David Sáez Romero D of Industrial Electrical

More information

SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER SIZING GUIDELINES

SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER SIZING GUIDELINES Issued 06-01-07 DESIGN Section DVD00 INFORMATION SECTION Page 1 of 1 INDEX SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER INTRODUCTION... Page 2 LOAD ESTIMATING AND TRANSFORMER SIZING GUIDELINES...Page

More information

3790 en - 06.2007 / d. Alternators LSA 46.2-4 Pole. Electrical and mechanical data

3790 en - 06.2007 / d. Alternators LSA 46.2-4 Pole. Electrical and mechanical data 379 en - 6.7 / d Alternators LSA 46.2-4 Pole Electrical and mechanical data SPECIALLY ADAPTED FOR APPLICATIONS The LSA 46.2 alternator is designed to be suitable for typical generator applications, such

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Fault Analysis I13-1. 2008 PowerWorld Corporation

Fault Analysis I13-1. 2008 PowerWorld Corporation Fault Analysis Analysis of power system parameters resulting from a ground or line to line fault somewhere in the system Simulator contains a tool for analyzing faults in an automatic fashion Can perform

More information

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables

More information

Low Voltage Transformer Through-Fault Protection: A System Approach

Low Voltage Transformer Through-Fault Protection: A System Approach Data Bulletin 7400DB1001 Nashville, TN USA Low Voltage Transformer Through-Fault Protection: A System Approach Introduction Low Voltage Transformer Protection Criteria NEC Article 450 Transformers and

More information

Paralleling Power Sources Which Share a Common Neutral

Paralleling Power Sources Which Share a Common Neutral Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share

More information

Power System Analysis

Power System Analysis PDHonline Course E194 (15 PDH) Power System Analysis Instructor: Timothy L. O'Hearn, PE 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University PURPOSE: The purpose of this lab is to introduce PSS/E. This lab will introduce the following aspects of PSS/E: Introduction to

More information

Verification of Short Circuit Test Results of Salient Poles Synchronous Generator

Verification of Short Circuit Test Results of Salient Poles Synchronous Generator Verification of Short Circuit Test Results of Salient Poles Synchronous Generator Abdul Jabbar Khan 1, Amjadullah Khattak 2 1 PG Student, University of Engineering and Technology, Peshawar, Department

More information

Section 10. Application Manual for NEMA Motors. Special Applications

Section 10. Application Manual for NEMA Motors. Special Applications Special Applications 1 Power Factor Correction 1 Methods of Starting 3AC Induction Motors 5 3 Duty Cycles and Inertia 3 4 Horsepower Determination 30 5 Formulas and General Data 34 Power Factor Correction

More information

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203 03/2013 Retain for future use. Introduction Short-circuit current s (SCCRs) for variable frequency drives (VFDs) is

More information

Science and Reactor Fundamentals Electrical CNSC Technical Training Group. Table of Contents

Science and Reactor Fundamentals Electrical CNSC Technical Training Group. Table of Contents Electrical Science and Reactor Fundamentals Electrical i Table of Contents 1 Objectives... 1 1.1 BASIC ELECTRICAL THEORY... 1 1.2 TRANSFORMERS... 1 1.3 GENERATORS... 2 1.4 PROTECTION... 3 2 BASIC ELECTRICAL

More information

AC Generators. Basic Generator

AC Generators. Basic Generator AC Generators Basic Generator A basic generator consists of a magnetic field, an armature, slip rings, brushes and a resistive load. The magnetic field is usually an electromagnet. An armature is any number

More information

7. Reactive energy compensation

7. Reactive energy compensation 593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical

More information

Three-phase AC circuits

Three-phase AC circuits Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

SPECIFICATION COG-2007

SPECIFICATION COG-2007 Cleco Power LLC SPECIFICATION COG-2007 FOR PARALLEL OPPERATION OF CUSTOMER-OWNED GENERATION ON CLECO S ELECTRICAL SYSTEM Revised: March 7, 2014 CONTENTS ITEM NO. TITLE PAGE NO. 1.0 Scope 3 2.0 Policy On

More information

PowerFlex Dynamic Braking Resistor Calculator

PowerFlex Dynamic Braking Resistor Calculator Application Technique PowerFlex Dynamic Braking Resistor Calculator Catalog Numbers 20A, 20B, 20F, 20G, 22A, 22B Important User Information Solid-state equipment has operational characteristics differing

More information

Introduction to Short Circuit Analysis

Introduction to Short Circuit Analysis www.pdhcenter.com PDH Course E04 www.pdhonline.org Introduction to Short Circuit Analysis Course Content A short circuit is a low-resistance connection established by accident or intention between two

More information