DC Ammeter Shunts. General Information. Leads. Installation. Characteristics of Manganin Shunt Cold Formed Stress Relieved

Size: px
Start display at page:

Download "DC Ammeter Shunts. General Information. Leads. Installation. Characteristics of Manganin Shunt Cold Formed Stress Relieved"

Transcription

1 General Information CSI shunts are designed for use with 50 or 100 millivolt measuring instruments, calibrated in terms of the ampere ratings of the shunt. The accuracy of our shunts is better than ±1/4% of the rated value and the temperature coefficient is ± It is important that the resistance be constant under different temperature conditions. It is usually assumed that the maximum temperature will be about 80 C and the usual range is C. For continuous operation, it is recommended that shunts are not run at more than two-thirds (2/3) the rated current under normal conditions of use as per IEEE standards. If the shunt is used in an AC or pulse current environment make sure that the highest pulse current does not exceed the recommended two-thirds, the rated current for continuous operation. In this case the average millivolt reading using a rms meter will be proportional with the duty cycle of the AC current. Installation By definition, a shunt is a resistor, and will generate heat with passage of current. Because of this, the resistance blades of the shunt should be mounted in a vertical position to promote free convectional flow of air. Where this mounting position is impractical and in installations where the shunt is in a confined location forced air cooling should be provided. Under no condition should the manganin shunt strip be allowed to surpass 145 C, as this will cause a permanent change in resistance. Shunts should be installed to protect them from damage by thermal expansion forces in the connecting bus bars or by short circuit forces. It should be recognized that shunts are inherently weaker than their current connections and that special flexibility may be needed at times. Where possible all shunts should be connected in the grounded side of the line. Portable type shunts, with an insulating base, when used on circuits above 750 volts should be mounted in the grounded side of the circuit. Where more than one bus bar is to be connected to each end of a single terminal shunt, these bars should be distributed as equally as possible on each side of the shunt terminals. Leads In some applications it is not feasible to mount the shunt close enough to the instrument to permit the use of the standard lead lengths. If longer lead lengths are necessary, the additional drop in the leads must be taken into consideration when ordering analog instruments. Characteristics of Manganin Shunt Cold Formed Stress Relieved % CHANGE OF RESISTANCE TEMP. C Temperature coefficient of resistance: ± 15ppm/ C. 18

2 Shunt Selection Guide Definition: Instrument Shunt is a particular type of resistor designed to be connected in parallel with the measuring device to extend the current range beyond some particular value for which the instrument is already complete. Any shunt by definition is a resistor and will generate heat with the passage of current. Shunt ratings are established by finding the power required to achieve a specified manganin temperature rise in free air at certain predetermined conditions. When operating conditions are significantly different from the rating conditions, the shunt should be de-rated or up-rated accordingly to keep the manganin temperature within reasonable limits in order to prevent premature failure, reduced reliability, reduced rated accuracy or causing permanent change in resistance. CSI s standard shunts are rated to meet IEEE Standard Requirements for Direct Current Instrument Shunt. IEEE 6.2 Current Ratings: Selection of ratings should be based on operation at a normal current of 2/3 the rated value. Ratings are based on mountings in accordance with Reference Test Conditions: Reference Temperature: 25 C (±2 C) Position: Current terminals and resistance blades, vertical, allowing free air circulation Connections: Tightly bolted to current bus using all terminal slots and specified depth of blade insertion or tightly bolted to lugs with cables or proper cross-section Since a shunt is essentially part of a bus-bar assembly, it depends on the structure to conduct away a major portion of the heat generated within the shunt and then to radiate this heat. It is important, therefore, that these connecting buses be of ample size and properly attached to the shunt. Design Considerations When trying to find the correct shunt rating to specify for a given application, there are four things to take into account: A) Duty continuous, intermittent or surge B) Ambient elevated temperature or high altitudes C) Temperature rise normal or limited D) Environment grouped, enclosed, forced air E) Combinations of A through D Although each of these conditions will be considered separately, any combination of them may exist in a specific case. When this happens it will be necessary to use more than one of the following sections to arrive at the correct rating. 19

3 Duty For duty which is less than continuous, a shunt need not be rated as high as a straight calculation based on resistance and voltage or current would indicate. If, for instance the shunt is repeatedly energized for a short period (not to exceed 5 minutes) a conservative rating may be obtained as follows: K1 = D P puls = P max / K1 P max = P rated x 0.66 P max = maximum continuous power P rated = catalog rated power P puls = maximum pulsating power where D is the ratio of ON time to the total period. For surge and pulse service a different approach must be used. In these cases it is necessary to provide enough thermal mass to absorb the energy to be dissipated and be sure that the construction of the shunt is adequate to accommodate the peak power. Therefore, it is recommended that a complete description of the pulse/surge wave shape or circuit constants and operating conditions be submitted to the CSI Engineering Department for the selection of a suitable shunt. Example: A 800 Amp 500mV shunt is energized for 15 seconds of each minute. D = 15 / 60 = 0.25 and K1 = 0.25 = 0.5 thus, P rated = 800 x 0.05 = 40 watts P max = P rated x 0.66 = 40 x 0.66 = 26.4 watts P puls = P max / K1 = / 0.5 = 52.8 watts therefore this shunt can be loaded up to 910 Amps. Ambient If the ambient temperature of the area in which the shunt is to operate exceeds the ambient Reference Test Conditions, a de-rating factor must be applied to prevent the manganin temperature from going above the safe limit of 125 C. The following formula may be used to find the de-rating power. P out = P max x (1-T/A) P max = P rated x 0.66 where T is the difference between the rated and operating ambient temperatures, A is the rise allowed above the rated ambient and Pmax is the Pout at 25 C. Example: If a 150 Amp 50 mv shunt is to operate in a 100 C ambient, what is the maximum load? 100 C is 75 degrees above the ambient, so T = 75 C, and the rated rise A is 100 C. Therefore: P out = P max x (1-75 / 100) = P max x 0.25 P max = 0.66 x P rated = 0.66 x (150 x 0.05) = 4.95 watts P out for an ambient of 100 C is P out = 4.95 x 0.25 = 1.23 watts, 60 Amps will be the maximum load. 20

4 Temperature Rise In many cases it is desirable to limit the temperature rise of a shunt for increased accuracy and stability or to protect other equipment near it. A satisfactory de-rating factor K2 may be obtained from: K2 = 1 - t / 125 where t is the difference between the rated and the newly imposed rise limit. Example: Suppose it is necessary to limit the temperature rise of a shunt type LC800 Amp 50 mv to 75 C. What is the maximum safe load? t=125-75=50 K2=1-50 / 125=0.6 P rated x 0.66 = 26.4 watts = P max at 25 C K2 x P max = 26.6 x 0.6 = watts; therefore 510 Amps represents the maximum safe load. Environment 1. Space requirement Any shunt by definition is a resistor and hence will generate heat with passage of current. Shunts should be mounted in a location where there is free circulation of air to carry away the heat generated. Shunt blades should be mounted in a vertical position to promote free airflow. If there is not enough natural convection, forced air cooling should be applied. 2. Enclosures Shunts are frequently mounted in enclosures for protection from the surroundings or to safeguard operators and personnel. If the unvented enclosure is large in proportion to the amount of energy to be dissipated, there is no need for concern. If the power density is greater than 1/4 watt per square inch of enclosure surface, provision must be made for cooling air using vents or fans. Note: Call CSI Engineering Department for mathematical formulas and examples regarding Venting, Force air cooling, Grouping, Altitude and Combinations. Conclusion The foregoing discussions are intended as a guide to the design engineer in the selection of the correct shunt for application and should be adequate under normal circumstances. Since it is often difficult to determine what the shunt will actually see in service, it is wise to use a conservative approach in all cases. If unusual conditions exist or if the engineer is unsure of the application, CSI Engineering Department is always ready to help in the selection of shunt for the case at hand. 21

5 Custom Applications Give us your specs and we ll give you a solution for your application. We invite your inquiry for special shunts. See Questionnaire on our Products & Services page. Other Fine Products Knife Switches Heavy Duty Knife Switches 100% Electrolytic Copper Ratings up to 20,000 amperes and 600 volts DC/AC Construction styles: Front or Back connected Fusible or non-fusible. Complete Engineering Services for special designs Telecom Fused Disconnects Fused Disconnects Type TPL : Ratings up to 600A and 145Vdc will hold fuse types: Bussmann TPL or Littelfuse L17T Type DF : Ratings up to 600A and 60Vdc will hold fuse types: Bussmann TPL or Littelfuse L17T Switch Fused Disconnects Type TPL : Two TPL mounted on a common base with a switch mechanism. Ratings up to 600A and 145Vdc Type TR : Two DF mounted on a common base with a switch mechanism. Ratings up to 600A and 60Vdc 22

AC-DC Converter Application Guidelines

AC-DC Converter Application Guidelines AC-DC Converter Application Guidelines 1. Foreword The following guidelines should be carefully read prior to converter use. Improper use may result in the risk of electric shock, damaging the converter,

More information

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT? Data Bulletin April 2001 Raleigh, NC, USA Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW Variable frequency drives are available from manufacturers as enclosed engineered

More information

POWER AND VOLTAGE RATING

POWER AND VOLTAGE RATING POWER AND VOLTAGE RATING SCOPE: The purpose of this document is to take the confusion out of power and voltage ratings in specifications and in product information publications. This will be accomplished

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Calibrating DC Shunts: Techniques and Uncertainties

Calibrating DC Shunts: Techniques and Uncertainties Calibrating DC Shunts: Techniques and Uncertainties Jay Klevens Ohm-Labs, Inc. 611 E. Carson St., Pittsburgh, PA 15203 (412) 431-0640 jklevens@ohm-labs.com Abstract Accurate electrical current measurement

More information

Shrinking a power supply and the challenge to maintain high reliability.

Shrinking a power supply and the challenge to maintain high reliability. Application Note - AN1201 Shrinking a power supply and the challenge to maintain high reliability. Shane Callanan, Director of Applications Engineering, Excelsys Technologies considers the challenges associated

More information

ST Series POWER SUPPLIES USER INSTRUCTIONS

ST Series POWER SUPPLIES USER INSTRUCTIONS Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional

More information

The Effect of Forced Air Cooling on Heat Sink Thermal Ratings

The Effect of Forced Air Cooling on Heat Sink Thermal Ratings zpero 1 The Effect of Forced Air Cooling on Heat Sink Thermal Ratings By Paul Bachman, Fellow Engineer & Ronnie Haiduk, Applications Engineer, Crydom, Inc. ABSTRACT A heat sink s ability to dissipate thermal

More information

BB-18 Black Body High Vacuum System Technical Description

BB-18 Black Body High Vacuum System Technical Description BB-18 Black Body High Vacuum System Technical Description The BB-18 Black Body is versatile and is programmed for use as a fixed cold target at 80 K or variable target, at 80 K- 350 K no extra cost. The

More information

THERMAL DESIGN AND TEST REQUIREMENTS FOR OUTSIDE PLANT CABLE TELECOMMUNICATIONS EQUIPMENT Al Marshall, P.E. Philips Broadband Networks

THERMAL DESIGN AND TEST REQUIREMENTS FOR OUTSIDE PLANT CABLE TELECOMMUNICATIONS EQUIPMENT Al Marshall, P.E. Philips Broadband Networks THERMAL DESIGN AND TEST REQUIREMENTS FOR OUTSIDE PLANT CABLE TELECOMMUNICATIONS EQUIPMENT Al Marshall, P.E. Philips Broadband Networks Abstract Shrinking thermal margins, driven by sophisticated but thermally

More information

CHAPTER 6 THERMAL DESIGN CONSIDERATIONS. page. Introduction 6-2. Thermal resistance 6-2. Junction temperature 6-2. Factors affecting R th(j-a) 6-2

CHAPTER 6 THERMAL DESIGN CONSIDERATIONS. page. Introduction 6-2. Thermal resistance 6-2. Junction temperature 6-2. Factors affecting R th(j-a) 6-2 CHAPTER 6 THERMAL DESIGN CONSIDERATIONS page Introduction 6-2 Thermal resistance 6-2 Junction temperature 6-2 Factors affecting 6-2 Thermal resistance test methods 6-3 Test procedure 6-3 Forced air factors

More information

Power Dissipation Considerations in High Precision Vishay Sfernice Thin Film Chips Resistors and Arrays (P, PRA etc.) (High Temperature Applications)

Power Dissipation Considerations in High Precision Vishay Sfernice Thin Film Chips Resistors and Arrays (P, PRA etc.) (High Temperature Applications) VISHAY SFERNICE Resistive Products Application Note ABSTRACT On our thin film chips resistors and arrays the main path for the heat, more than 90 %, is conduction through the body of the component, the

More information

Calculating Heat Loss by Mark Crombie, Chromalox

Calculating Heat Loss by Mark Crombie, Chromalox Calculating Heat Loss by Mark Crombie, Chromalox Posted: January 30, 2006 This article deals with the basic principles of heat transfer and the calculations used for pipes and vessels. By understanding

More information

RMS Power. The Meaning of Average

RMS Power. The Meaning of Average RMS Power Discussion in the rec.radio.amateur.homebrew newsgroup showed a widespread misunderstanding of the meaning and importance of RMS and average values of voltage, current, and power. So I ve put

More information

OPERATING YOUR JEN-KEN GLASS KILN

OPERATING YOUR JEN-KEN GLASS KILN OPERATING YOUR JEN-KEN GLASS KILN SETTING UP THE KILN: G, GS AND GS-E GLASS KILLN SERIES Place your kiln in an open area away from all flammable surfaces, including walls and floors. If your floor is not

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

Current and Temperature Ratings

Current and Temperature Ratings Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and

More information

Carbon Cable. Sergio Rubio Carles Paul Albert Monte

Carbon Cable. Sergio Rubio Carles Paul Albert Monte Carbon Cable Sergio Rubio Carles Paul Albert Monte Carbon, Copper and Manganine PhYsical PropERTieS CARBON PROPERTIES Carbon physical Properties Temperature Coefficient α -0,0005 ºC-1 Density D 2260 kg/m3

More information

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations 12S, 14S, 15S Series Time Delay Relays and Sequencers Time Delay Relays and Sequencers The Therm-O-Disc type 12S, 14S and 15S series time delay relays and sequencers are field-proven devices for controlling

More information

Temperature Rise Calculation Software Tutorial. In Accordance with the Calculation Method to IEC 60890

Temperature Rise Calculation Software Tutorial. In Accordance with the Calculation Method to IEC 60890 Temperature Rise Calculation Software Tutorial In Accordance with the Calculation Method to IEC 60890 Temperature Rise Calculation Software (TRCS) Rockwell Automation All rights reserved. No parts of this

More information

Bussmann series Third rail fuse links application guide. Leadership in fusible circuit protection solutions

Bussmann series Third rail fuse links application guide. Leadership in fusible circuit protection solutions Bussmann series Third rail fuse links application guide Leadership in fusible circuit protection solutions Eaton s Bussmann business has over 100 years of experience in the design and manufacture of fuse

More information

Specifying a Variable Frequency Drive s

Specifying a Variable Frequency Drive s Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com Product description Wide rated operational voltage 208 600 V AC Wide rated control supply voltage 100 250 V, 50/60 Hz Rated operational current 18 to 370 A Wide ambient temperature range, -25 to +60 ºC

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

DC/DC power modules basics

DC/DC power modules basics DC/DC power modules basics Design Note 024 Ericsson Power Modules General Abstract This design note covers basic considerations for the use of on-board switch mode DC/DC power modules, also commonly known

More information

PSR The compact range Description

PSR The compact range Description Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides

More information

Comparative study for cables and busbars

Comparative study for cables and busbars Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary

More information

Current transformers (CT) & Shunts

Current transformers (CT) & Shunts Current transformers (CT) & Shunts Genreal overview LV CURRENT TRANSFORMERS Product selection guide Standard industrial transformers?????? TCR - TCRO range NEW 9 9 9 Current summation JVM 0 9 TCR usbar

More information

Bourns Resistive Products

Bourns Resistive Products Bourns Resistive Products Diverse Requirements Drive Innovations to Pulse Resistors Introduction Countless circuits depend on the protection provided by one of the most fundamental types of passive components:

More information

Pulse Withstanding Thick Film Chip Resistor-SMDP Series. official distributor of

Pulse Withstanding Thick Film Chip Resistor-SMDP Series. official distributor of Product: Pulse Withstanding Thick Film Chip Resistor-SMDP Series Size: /// official distributor of Pulse Withstanding Thick Film Chip Resistor-SMDP Series 1. Scope -This specification applies to ~ sizes

More information

STRATO LED Drivers 70W, Single output

STRATO LED Drivers 70W, Single output Features STRATO switch mode driver technology is designed to generate one constant current output from a wide range AC input. The size and performance of these products make them the ideal choice for LED

More information

WINDING RESISTANCE TESTING

WINDING RESISTANCE TESTING WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991

More information

We will discuss common industrial applications with guides for the proper use of electric motors on these.

We will discuss common industrial applications with guides for the proper use of electric motors on these. INTRODUCTION: Baldor Electric Company has prepared this Specifiers Guide to help you cover all the bases when you are specifying electric motors. It will cover in a generic way most of the subjects which

More information

Kit 106. 50 Watt Audio Amplifier

Kit 106. 50 Watt Audio Amplifier Kit 106 50 Watt Audio Amplifier T his kit is based on an amazing IC amplifier module from ST Electronics, the TDA7294 It is intended for use as a high quality audio class AB amplifier in hi-fi applications

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:

More information

THE KW107 SUPERMATCH ATU manual, courtesy of Barry G0DWZ

THE KW107 SUPERMATCH ATU manual, courtesy of Barry G0DWZ THE KW107 SUPERMATCH ATU manual, courtesy of Barry G0DWZ I ve copied the following directly from the KW107 manual without alteration. To clear up one or two ambiguous points, I have added my own comments

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

High Speed Fuses. High Speed Fuses

High Speed Fuses. High Speed Fuses Section Contents Page General Applications........................ 9-95 North American fuses & accessories............9-113 DFJ - High speed Class J fuse...................97 Square Body fuses & accessories............

More information

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20 USE OF ELECTRICAL TEST EQUIPMENT Test equipment is necessary for determining proper set-up, adjustment, operation, and maintenance of electrical systems and control panels. The following is a general procedure

More information

In today s world of wireless communications

In today s world of wireless communications TUTORIAL RF CERAMIC CHIP CAPACITORS IN HIGH RF POWER APPLICATIONS Reprinted with permission of MICROWAVE JOURNAL from the April 2000 issue. 2000 Horizon House Publications, Inc. In today s world of wireless

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C 41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers

More information

Application Note TMA Series

Application Note TMA Series 1W, SIP, Single & Dual Output DC/DC Converters Features SIP Package with Industry Standard Pinout Package Dimension: 19.5 x 10.2 x 6.1 mm (0.77 x 0.4 x 0.24 ) 5V&12V Models 19.5 x 10.2 x 7.1 mm (0.77 x

More information

Insulation Resistance Testing of Low Voltage Cables in the Field

Insulation Resistance Testing of Low Voltage Cables in the Field Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS by John Houdek, President, Allied Industrial Marketing, Inc., and Cesar Chavez, Engineering Manager, ARTECHE / Inelap Abstract: The addition of power factor improvement capacitors to individual motors

More information

PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V

PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V PHOTOVOLTAIC SYSTEM CONTROLLERS OPERATOR S MANUAL SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V 6A / 12V 10A / 12V 10A / 24V 20A / 12V 20A

More information

Manual Ranging MultiMeter

Manual Ranging MultiMeter Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

Everline Module Application Note: Round LED Module Thermal Management

Everline Module Application Note: Round LED Module Thermal Management Everline Module Application Note: Round LED Module Thermal Management PURPOSE: Use of proper thermal management is a critical element of Light Emitting Diode (LED) system design. The LED temperature directly

More information

Fan Basics and Selection Criteria (How to Use)

Fan Basics and Selection Criteria (How to Use) Feature: Understanding SANYO DENKI Products from Scratch Fan Basics and Selection Criteria (How to Use) Honami Osawa 1. Introduction In recent years, the importance of cooling technology has become even

More information

GS Semiconductor Fuselinks. GE Power Controls. GS Semiconductor fuselinks

GS Semiconductor Fuselinks. GE Power Controls. GS Semiconductor fuselinks GE Power Controls GS Semiconductor fuselinks TYPE GS Semiconductor Fuselinks Technical information Full GS range of fuselinks are designed to the requirements of IEC269 -IV (1986) Precise Pre-determined

More information

Charge Regulator SCR 12 Marine

Charge Regulator SCR 12 Marine Charge Regulator SCR 12 Marine Manual Many thanks for purchasing a superwind product. The SCR 12 Marine is a charge regulator of highest quality and will perfectly and reliably charge your batteries for

More information

Bolted contact switches. Pringle switches

Bolted contact switches. Pringle switches Bolted contact switches Pringle switches Eaton s Pringle bolted contact switches History Eaton s PringleT switches have helped pioneer the development of high-quality electrical products for commercial

More information

Low and High Voltage Power Supplies

Low and High Voltage Power Supplies Low and High Voltage Power Supplies We work according to ISO 9001: 2008 Since 1994 Fug works according to the quality assurance system ISO 9001. All shipped units are checked and documented in our testing

More information

UMEC International Corporation

UMEC International Corporation UP1301A SERIES 130 Watt Open Frame Switchers Small Size 3*5*1.2(inches) Universal Input to 264 VAC Low Power Consumption Overvoltage Protection Continuous Short Circuit Protection Over Temperature Protection

More information

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions: The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery

More information

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) Fig1. CPTR SMART CONTROL PRECISION CUSTOMIZED MANUAL OR AUTO SCR OR DIODE DRY TYPE SWITCH MODE DRY TYPE SCR OR DIODE OIL TYPE 1 INDEX PAGE 1. Cover 2. Index

More information

Features. Applications

Features. Applications LM555 Timer General Description The LM555 is a highly stable device for generating accurate time delays or oscillation. Additional terminals are provided for triggering or resetting if desired. In the

More information

AutoRanging Digital MultiMeter

AutoRanging Digital MultiMeter Owner's Manual AutoRanging Digital MultiMeter Model No. 82139 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance

More information

Current Limiting Power Resistors for High-Power LED Module Lighting Applications

Current Limiting Power Resistors for High-Power LED Module Lighting Applications Current Limiting Power Resistors for High-Power LED Module Lighting Applications PWR263 An ongoing trend toward miniaturization of virtually all electronics is accompanied by the demand for a reduction

More information

INTEGRATED CIRCUITS DATA SHEET. TDA7000 FM radio circuit. Product specification File under Integrated Circuits, IC01

INTEGRATED CIRCUITS DATA SHEET. TDA7000 FM radio circuit. Product specification File under Integrated Circuits, IC01 INTEGRATED CIRCUITS DATA SHEET File under Integrated Circuits, IC01 May 1992 GENERAL DESCRIPTION The is a monolithic integrated circuit for mono FM portable radios, where a minimum on peripheral components

More information

P O W E R C A P A C I T O R A S S E M B L I E S

P O W E R C A P A C I T O R A S S E M B L I E S AMERICAN TECHNICAL CERAMICS P O W E R C A P A C I T O R A S S E M B L I E S ISO 9001 REGISTERED COMPANY Overview About ATC Power Assemblies ATC standard & custom Power Assemblies are fabricated from PARALLEL

More information

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power Features: Universal AC input / Full range Programmable output Voltage (0% ~ 05%) Programmable output Current (% ~ 05%) + / 0.5A auxiliary output Forced current sharing at parallel operation Power OK signal

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox HOME APPLICATION NOTES Iron Powder Cores for Switchmode Power Supply Inductors by: Jim Cox Purpose: The purpose of this application note is to cover the properties of iron powder as a magnetic core material

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

Copper and Aluminum busbars

Copper and Aluminum busbars Copper and Aluminum busbars Two metals are currently used as conductors in electric panel boards: copper and aluminum In particular, when in need to define a power distribution inside an electric panel

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

Experiment #4, Ohmic Heat

Experiment #4, Ohmic Heat Experiment #4, Ohmic Heat 1 Purpose Physics 18 - Fall 013 - Experiment #4 1 1. To demonstrate the conversion of the electric energy into heat.. To demonstrate that the rate of heat generation in an electrical

More information

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit) 000W Single Output Power Supply AK-000 series Features: Universal AC input / Full range Programmable output Voltage (0% ~ 05%) Programmable output Current (% ~ 05%) + / 0.5A auxiliary output U profile,

More information

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

APPLICATION NOTES. Bimetal Disc Thermostat. Operating Principle

APPLICATION NOTES. Bimetal Disc Thermostat. Operating Principle Bimetal Disc Thermostat APPLICATION NOTES Operating Principle Bimetal disc thermostats are thermally actuated switches. When the bimetal disc is exposed to its predetermined calibration temperature, it

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

RADIANT PLASMA 4700 Plasma Spark Generator

RADIANT PLASMA 4700 Plasma Spark Generator RADIANT PLASMA 4700 Plasma Spark Generator Installation Guide / User Manual A S P A R K O F F R E S H A I R Aquapulser.com Contents 1 Introduction 2 1.1 About the Product....................................

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Variable Frequency Drives - a Comparison of VSI versus LCI Systems Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been

More information

VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS

VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS CEMB SPA Via Risorgimento, 9 Mandello del Lario (Lc), Italy stm@cemb.com www.cemb.com INSTRUMENT FOR MONITORING VIBRATIONS OF FANS INSTALLED IN ROAD

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity

Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity Effects of AC Ripple Current on VRLA Battery Life A Technical Note from the Experts in Business-Critical Continuity Introduction Given the importance of battery life to UPS system users and the fact that

More information

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases

More information

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 NUCLEAR MAGNETIC RESONANCE

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 NUCLEAR MAGNETIC RESONANCE E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 NUCLEAR MAGNETIC RESONANCE References for Nuclear Magnetic Resonance 1. Slichter, Principles of Magnetic Resonance, Harper and Row, 1963. chapter

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.

More information

Objectives 200 CHAPTER 4 RESISTANCE

Objectives 200 CHAPTER 4 RESISTANCE Objectives Explain the differences among conductors, insulators, and semiconductors. Define electrical resistance. Solve problems using resistance, voltage, and current. Describe a material that obeys

More information

CS4525 Power Calculator

CS4525 Power Calculator 1. OVERVIEW CS4525 Power Calculator The CS4525 Power Calculator provides many important application-specific performance numbers for the CS4525 based on user-supplied design parameters. The Power Calculator

More information

Power Supply Cables and Connectors

Power Supply Cables and Connectors Power Supply Cables and Connectors Often during the excitement of designing a challenging new system, some of the more mundane engineering aspects get overlooked. This is especially true of connections

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Battery Power Inverters

Battery Power Inverters Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.1 Important Safety Instructions Please save these instructions.

More information

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter FEATURES: Click on Series name for product info on aimtec.com Models Single output Model Max Output Power (W) 1 AC-DC Constant Current or Constant Over temperature protection Voltage LED Driver Over current

More information

MP-4000 Alarm List (Software version 2.4.3 or later)

MP-4000 Alarm List (Software version 2.4.3 or later) Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.

More information

Varactor Diodes. Introduction. Key Electrical Parameters. Reverse Breakdown Voltage and Reverse Leakage Current APPLICATION NOTE

Varactor Diodes. Introduction. Key Electrical Parameters. Reverse Breakdown Voltage and Reverse Leakage Current APPLICATION NOTE APPLICATION NOTE Varactor Diodes Introduction A varactor diode is a P-N junction diode that changes its capacitance and the series resistance as the bias applied to the diode is varied. The property of

More information

Buck - Boost Transformers

Buck - Boost Transformers Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single

More information

Forms of Energy. Freshman Seminar

Forms of Energy. Freshman Seminar Forms of Energy Freshman Seminar Energy Energy The ability & capacity to do work Energy can take many different forms Energy can be quantified Law of Conservation of energy In any change from one form

More information

Low Voltage Disconnect Switches. NFPA79 and UL508A Industrial Machinery Operating Handle Requirements White Paper

Low Voltage Disconnect Switches. NFPA79 and UL508A Industrial Machinery Operating Handle Requirements White Paper Low Voltage Disconnect Switches NFPA79 and UL508A Industrial Machinery Operating Handle Requirements White Paper Scope This document is intended to discuss the functional requirements for the disconnecting

More information