1 Xantrex GT30 Grid-Tied Photovoltaic Inverter Installation, Operation and Maintenance Manual

2

3 Xantrex GT30 Grid-Tied Photovoltaic Inverter Installation, Operation and Maintenance Manual

4 About Schneider Electric As a global specialist in energy management with operations in more than 100 countries, Schneider Electric offers integrated solutions across multiple market segments, including leadership positions in energy and infrastructure, industrial processes, building automation, and data centres/networks, as well as a broad presence in residential applications. Focused on making energy safe, reliable, and efficient, the company's 120,000 employees achieved sales of more than 17.3 billion euros in 2007, through an active commitment to help individuals and organizations Make the most of their energy. Trademarks Schneider Electric, the Schneider Electric logo, and Xantrex are trademarks or registered trademarks of the Schneider Electric group of companies. Other trademarks, registered trademarks, and product names are the property of their respective owners and are used herein for identification purposes only. Notice of Copyright Copyright 2009, 2010 Xantrex Technology Inc. All rights reserved. No part of this document may be reproduced in any form or disclosed to third parties without the express written consent of: Xantrex Technology Inc. 161-G South Vasco Road Livermore, California USA Xantrex Technology Inc. reserves the right to revise this document and to periodically make changes to the content hereof without obligation or organization of such revisions or changes unless required to do so by prior arrangement. Exclusion for Documentation UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. ( XANTREX ) (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; (B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK; AND (C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT Date and Revision March 2010 Revision B Part Number Contact Information Telephone: Fax: re.techsupport@schneider-electric.com Web: ii

5 About This Manual Purpose Audience Organization The purpose of this Installation, Operation and Maintenance Manual is to provide explanations and procedures for installing, commissioning, operating, troubleshooting and maintaining the Xantrex GT30 Grid-Tied Photovoltaic Inverter. Chapter 1 and Chapter 2 are intended for anyone who needs to operate the Xantrex GT30 Grid-Tied Photovoltaic Inverter. Operators must be familiar with all the safety regulations pertaining to operating high-voltage equipment as dictated by local code. Operators must also have a complete understanding of this equipment s features and functions. Do not to use this product unless it has been installed by qualified personnel in accordance with the instructions in Chapter 3, Installation. Chapter 3, Chapter 4, Chapter 5, Chapter 6 and Chapter 7 are intended for qualified personnel who need to install the Xantrex GT30 Grid-Tied Photovoltaic Inverter. Only qualified personnel should perform the transportation, installation, commissioning and maintenance of the Xantrex GT30. Qualified personnel have training, knowledge, and experience in: installing electrical equipment and PV power systems (up to 1000 V), applying all applicable installation codes, analyzing and reducing the hazards involved in performing electrical work, and, selecting and using Personal Protective Equipment (PPE). This Manual is organized into seven chapters and three appendices. Chapter 1, Introduction contains information about the features and functions of the Xantrex GT30 Grid-Tied Photovoltaic Inverter. Chapter 2, Operation contains information on the basic operation of the Xantrex GT30 Grid-Tied Photovoltaic Inverter. Chapter 3, Installation provides information and procedures for installing the Xantrex GT30 Grid-Tied Photovoltaic Inverter. Chapter 4, Commissioning contains information on safely commissioning the Xantrex GT30 Grid-Tied Photovoltaic Inverter iii

6 About This Manual Conventions Used Chapter 5, Remote Programming and Advanced Settings contains information for using remote control features and adjusting customizable settings for optimization. Chapter 6, Troubleshooting contains information and procedures for troubleshooting the Xantrex GT30 Grid-Tied Photovoltaic Inverter. It provides descriptions of common situations and errors that may occur and provides possible solutions for resolving fault conditions. It also provides instructions for clearing faults manually, if required. Chapter 7, Preventative Maintenance contains information and procedures for performing preventative maintenance on the Xantrex GT30 Grid-Tied Photovoltaic Inverter. Appendix A provides the environmental and electrical specifications for the Xantrex GT30 Grid-Tied Photovoltaic Inverter. Appendix B contains the Commissioning Test Record for the Xantrex GT30 Grid- Tied Photovoltaic Inverter. Appendix C contains the Commissioning Test Record for the GT30 Grid-Tied Photovoltaic Inverter. The following conventions are used in this guide. WARNING Warnings identify conditions or practices that could result in personal injury or loss of life CAUTION Cautions identify conditions or practices that could result in damage to the unit or other equipment. Important: These notes describe things which are important for you to know, but are not as serious as a caution or warning. iv

7 About This Manual Abbreviations and Acronyms ANSI CSA GUI IEEE IGBT NEC NFPA PV PV GFP STC UL American National Standards Institute Canadian Standards Association Graphical User Interface Institute of Electrical and Electronics Engineers Insulated Gate Bipolar Transistor (US) National Electric Code National Fire Protection Association Photovoltaic PV Ground Fault Protection STC - Standard Test Conditions - solar panel specifications are based on standard conditions such as irradiance of 1000W/m 2 Underwriters Laboratory Definitions PV Monopole PV Subarray In this manual, PV monopole refers to a single photovoltaic source connected to the PV1 terminals or the PV2 terminals. Two equal PV monopoles of opposite polarity, with respect to earth ground, must be used to configure the bipolar array required to operate the Xantrex GT30. In this manual, the term PV subarray is interchangeable with the term PV monopole. Related Information You can find more information about Xantrex Technology Inc. as well as its products and services at v

8 vi

9 IMPORTANT SAFETY INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS - DO NOT DISCARD This manual contains important safety instructions for the Xantrex GT30 Grid- Tied Photovoltaic Inverter that must be followed during installation and maintenance procedures. WARNING: Limitations on Use The Xantrex GT30 Grid-Tied Photovoltaic Inverter is not intended for use in connection with life support systems or other medical equipment or devices. WARNING: Shock Hazard Before operating or performing maintenance on the Xantrex GT30, read all instructions, safety information, and all other appropriate sections of this manual. Failure to adhere to these warnings could result in severe shock or possible death. Exercise extreme caution at all times to prevent accidents. WARNING: Shock Hazard The Xantrex GT30 inverter enclosure contains exposed hazardous voltage conductors. The inverter enclosure covers should remain in place and secured by all provided screws, except during maintenance or testing. These instructions are for use by qualified personnel who meet all local and governmental code requirements for licensing and training for the installation of Electrical Power Systems with AC and DC voltage to 1000 volts. To reduce the risk of electric shock, do not perform any installation or servicing unless you are qualified to do so. Do not open the enclosure if extreme moisture is present (rain or heavy dew). Follow the Lockout and Tag/Isolation Procedure on page x. WARNING: Shock Hazard from Multiple Locations In order to remove all sources of voltage from the Xantrex GT30, all sources of incoming power must be de-energized. To fully remove AC power, you must open the main utility circuit breaker. Only opening the Xantrex GT30's AC disconnect switch (breaker) leaves live parts at the inverter's AC output terminals energized. To completely de-energize the two PV input circuits, you must open all field PV disconnect switches or remove all PV string fuses in all field PV combiner boxes. Only opening the Xantrex GT30's PV disconnect switch leaves live parts at the inverter's PV input terminals energized. Review the system configuration to determine all of the possible sources of energy. In addition, allow five minutes for the internal DC bus capacitors to discharge after removing power before removing the covers. Follow the Lockout and Tag/Isolation Procedure on page x vii

10 Safety WARNING: Shock Hazard If there is a PV array ground fault in the field, as indicated by the Xantrex GT30 display panel, normally grounded parts and conductors of the inverter, arrays, and other PV equipment may be ungrounded and energized at hazardous voltage, even when the integral and field PV disconnects are opened and PV string fuses removed. WARNING: Crush Hazard The Xantrex GT30 weighs enough to cause injury if it is dropped or falls onto a part of the body. Exercise caution and correct procedures when lifting, moving, or mounting the inverter. The inverter must be secured in place in accordance with these instructions. WARNING: Burn Hazard The Xantrex GT30 contains internal components that become hot during normal operation. Be extremely careful not to touch any internal components during maintenance or testing if the unit is still at operating temperature. Risks CAUTION: Risk of Overheating The Xantrex GT30 incorporates an air intake and two exhaust air areas, which must remain unobstructed during use. Failure to follow clearance requirements around the unit can result in the inverter overheating, leading to reduced output or to shutdown. CAUTION: Risk of Damage Due to Static Discharge Sensitive electronics inside the Xantrex GT30 can be destroyed if touched by an electrostatically charged person or object. Follow proper electrostatic discharge (ESD) protection procedures when working on the inverter. General Safety Precautions 1. Obey all worker safety codes and regulations. Never work alone when installing this equipment. A team of two is required until the equipment is properly closed and secured. 2. When installing the Xantrex GT30 use only components recommended or sold by Xantrex. Doing otherwise may result in a risk of fire, electric shock, injury to persons, and will void the warranty. viii

11 Safety 3. Do not attempt to install the Xantrex GT30 if it has been dropped, or received more than cosmetic damage during transport or shipping. If the Xantrex GT30 is damaged, or suspected to be damaged, see Warranty and Return Information. 4. Before installing and using the Xantrex GT30 Inverter, read all instructions and cautionary markings on the unit and all appropriate sections of this manual. Be sure to read all instructions and cautionary markings for any equipment used as part of the installation of this unit. 5. To avoid a risk of fire and electric shock, ensure that existing wiring is in good condition and that wire is not undersized. Do not operate the Xantrex GT30 with damaged or substandard wiring. 6. Do not disassemble the Xantrex GT30. It contains no user-serviceable parts. See Warranty for instructions on obtaining service. Attempting to service the Xantrex GT30 yourself will void your warranty and may result in a risk of electrical shock or fire. 7. Use insulated tools to reduce the chance of short-circuits when installing or working with the inverter or a PV array. Thoroughly inspect the equipment prior to energizing. Verify that no tools or equipment have inadvertently been left behind. 8. Several diagrams contained within this manual are basic in nature and are included only to depict different installation options. All details may not be shown, and as such, local electrical codes must still be referenced. 9. The Xantrex GT30 unit is designed and certified for full power operation at ambient temperatures up to 50 C. Operation above 50 C is outside the rated operating range, and may result in reduced output or shutdown. Safety Equipment Authorized service personnel must be equipped with standard safety equipment including the following: Safety glasses Steel-toed safety boots Safety hard hats Padlocks and tags Appropriate meter to verify that the circuits are de-energized (1000 Vac and Vdc rated, minimum) Check local safety regulations for other requirements ix

12 Safety Lockout and Tag/Isolation Procedure Safety requirements mandate that this equipment not be serviced while energized. Power sources for the Xantrex GT30 must be locked-out and tagged prior to servicing. A padlock and tag should be installed on each energy source prior to servicing. WARNING: Shock Hazard Review the system schematic for the installation to verify that all available energy sources are de-energized. DC bus voltage may also be present. Be sure to wait the full five minutes to allow the capacitors to discharge completely The Xantrex GT30 can be energized from both the AC source and the DC source. To ensure that the inverter is de-energized prior to servicing, lockout and tag the Xantrex GT30 using the following procedure. 1. Turn the Xantrex GT30 AC disconnect to the OFF position. This stops the inverter from exporting power to the AC utility grid. 2. Turn the Xantrex GT30 PV disconnect switch to the OFF position. See Figure 1-1 on page 1 4 for the location of the PV disconnect switch. 3. Open, lockout, and tag the AC power at the utility circuit breaker. 4. Open, lockout and tag all PV field disconnect switches. If PV field disconnect switches are not used, pull all PV string fuses in all PV string combiner enclosures, lock and tag all PV combiner enclosures. 5. Using a voltmeter that has been verified to be functioning properly by testing it on a known source, verify all power to the inverter is de-energized. Check the following locations: AC Utility Terminals: [L1, L2, L3, N] See Figure 3-6 on page 3 13 for the location of these terminals. PV Terminals: [PV1+, PV1, PV2+, PV2 ] See Figure 3-6 on page 3 13 for the location of these terminals. 6. If there is a voltage to ground/chassis on terminal PV1- or PV2+, sub-array PV1 or PV2 respectively have a fault to ground. The ground fault must be repaired before the Xantrex GT30 is safe for servicing. x

13 Safety Regulatory/Standards Compliance The Xantrex GT30 Grid-Tied Photovoltaic Inverter is CSA certified to appropriate US and Canadian standards. See page A 3 in Appendix A, Regulatory Specifications for more detailed information. The Xantrex GT30 Grid-Tied Photovoltaic Inverter is intended to be used for commercial and industrial applications. Do NOT use this unit for applications for which it is not listed (i.e., residential, land vehicles or marine craft). It may not comply with the safety code requirements or could possibly present other operational or safety hazards. FCC Statement The Xantrex GT30 Grid-Tied Photovoltaic Inverter has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment under FCC rules. Industry Canada Compliance Statement This Class A digital apparatus meets the requirements of the Canadian Interference-Causing Equipment Regulations. Intended Use The Xantrex GT30 may only be used in connection with PV modules. It is not suitable for use with batteries or any other applications xi

14 Safety xii

15 Contents IMPORTANT SAFETY INSTRUCTIONS vii 1 Introduction Description of the GT Advanced Design Features Physical Characteristics Operator Interface Controls AC Disconnect and PV Disconnect Switches Remote ON/OFF Switch Operation Features Fixed Unity Power Factor Operation Peak Power Tracking Utility Voltage/Frequency Fault Automatic Reset Inverter Functions Power Quality Standby Mode Remote Access and Firmware Download Fault Notification Fault Conditions Safety and Protection Features Anti-Islanding Protection PV Ground Fault Protection IGBT Device Protection Under and Over Voltage and Frequency Detection Phase Rotation Detection Additional Protection Communication Features and Methods LCD System Status and Fault Reporting Optional Equipment Communication Modems xiii

16 Contents 2 Operation Description of System Operation Overview Operating States Initializing Sleep Wake-up Power Tracking Sleep Test System Fault Shutdown State De-Energize Procedure (Shutdown Mode) Energize Procedure (Startup) Installation Overview of GT30 Installation PV Planning Environmental Requirements Grounding Requirements System Neutral Requirements Pre-Installation Knockout Preparation Tools Required Mounting Wiring Compartment Wiring Requirements AC Interface DC Interface Communications Interface Commissioning Commissioning Procedure Starting the Commissioning Test Serial Number Inspect and Verify Field Wiring AC Wiring DC Wiring Verify Voltages AC Voltages DC Voltages Startup Completed Commissioning xiv

17 5 Remote Programming and Advanced Settings Contents Computer Communications with the GT Customizable Parameters Data Logging Accumulated Energy Accumulated Energy Sold Since Commissioning Time and Date Data Recording Fault History LCD Display Text Troubleshooting Faults and Fault Codes General Troubleshooting Clearing Faults Manually Fault Code Descriptions Preventative Maintenance Maintenance Safety Periodic Maintenance Monthly Maintenance Six-Month Maintenance A B Specifications System Specifications A 2 Environmental Specifications A 2 Electrical Specifications A 3 Regulatory Specifications A 3 Over Voltage, Under Voltage and Frequency Ranges A 4 Dimensions A 5 Commissioning Test Record Commissioning Test Record B 3 Warranty and Return Information WA xv

18 xvi

19 Figures Figure 1-1 GT30 Operator Interface Components Figure 1-2 LCD Display Location Figure 2-1 State Transition Diagram Figure 3-1 GT30 Inverter Dimensions Figure 3-2 GT30 Mounting Bracket Dimensions Figure 3-3 GT30 Conduit Knockout Locations Figure 3-4 Mounting the GT30 on a Wall or Vertical Surface Figure 3-5 Removing the Front Panel on the GT Figure 3-6 GT30 Wiring Compartment Figure 3-7 GT30 AC Connection using External Step-up Transformer Figure 3-8 GT30 Field Wiring Diagram Figure 7-1 Location of Screened Vents for Cleaning Figure 7-2 GT30 Wiring Compartment Figure A-1 GT30 Dimensions A xvii

20 xviii

21 Tables Table 2-1 Operating States Table 3-1 PV Array Sizing Criteria for the GT Table 3-2 AC Conductor Size and Torque Requirements Table 3-3 DC Conductor Size and Torque Requirements Table 5-1 Customizable Parameters Table 5-2 Advanced Customizable Parameters Table 5-3 Data Logging Parameters Table 6-1 Fault Codes Table A-1 Environmental Specifications A 2 Table A-2 Electrical Specifications A 3 Table A-3 Regulatory Specifications A 3 Table A-4 Over/Under Voltage and Over/Under Frequency Ranges A 4 Table A-5 Accuracy/Tolerances for Adjustable Voltage & Temperature Settings A i

22 ii

23 1 Introduction Chapter 1, Introduction contains information about the features and functions of the Xantrex GT30 Grid-Tied Photovoltaic Inverter.

24 Introduction Description of the Xantrex GT30 Advanced Design Features Transformerless Operation The Xantrex GT30 Grid-Tied Photovoltaic Inverter (Xantrex GT30) is a transformerless, system-integrated, 3-phase utility interactive power converter for photovoltaic applications. The Xantrex GT30 is housed in a corrosion resistant aluminum enclosure for outdoor deployment. Multiple Xantrex GT30 units may be directly paralleled in higher power installations. The Xantrex GT30 does not require an internal or external isolation transformer and connects directly to a 120/208Vac utility service. The associated cost, weight and losses of an isolation transformer are eliminated. High Efficiency The Xantrex GT30 has a CEC conversion efficiency rating of 96%. Low Standby Power The Xantrex GT30 has a standby power less than 20 watts. Imbalanced Array Operation Wide PV Power Tracking Range Expandable Variable Speed Cooling Fan HALT Tested The Xantrex GT30 uses a proprietary control method that allows the inverter to continue operating in a reduced capacity with grossly imbalanced bipolar PV arrays. The MPPT figure of merit for any PV inverter is the ratio of maximum open circuit voltage to minimum PV power tracking voltage. The Xantrex GT30 ratio is 2.3:1 most other PV inverters have a ratio of less than 2:1. The Xantrex GT30 supports multiple-inverter systems for large-scale photovoltaic power plants. The Xantrex GT30 is convection cooled using a high reliability DC brushless fan with a variable speed control to minimize the number of fan rotations over the life of the inverter. The Xantrex GT30 has undergone Highly Accelerated Life Testing as part of the design process, to increase reliability. Approvals The Xantrex GT30 approvals include UL1741 Rev 2005 and IEEE Auto Phase The Xantrex GT30 automatically synchronizes to any AC utility phase rotation. Rotation Detection

25 Physical Characteristics Operator Interface Controls Physical Characteristics The Xantrex GT30 is assembled in a single NEMA-3R, corrosion resistant, powder coated, aluminum enclosure that includes two access panels, the upper one for all the power electronics and the lower one for field wiring and communications access. Operator interface controls are located on the front face of the inverter enclosure. These controls include a 4-line LCD display, an AC disconnect switch handle, and an PV disconnect switch handle

26 Introduction LCD Display PV Disconnect AC Disconnect ON ON PV Disconnect Switch OFF OFF AC Disconnect Switch Figure 1-1 Xantrex GT30 Operator Interface Components

27 Operator Interface Controls AC Disconnect and PV Disconnect Switches When operating, the Xantrex GT30 can be switched off by rotating either the AC or PV disconnect switch 90 degrees counter clockwise (CCW) to the off position. Opening the AC or PV disconnect switches (placing the disconnect switch in the OFF position) initiates an orderly shutdown of the Xantrex GT30 and power production will cease. Special circuitry allows the PV disconnect to be used in conjunction with internal DC load-break contactors and DC-to-AC converter controls to perform a DC load-break function. WARNING: Shock Hazard With the AC and PV disconnect switches in the OFF positions, it is NOT SAFE to remove either front access panel. Hazardous voltages remain present on the field wiring terminals of the disconnects unless the PV and AC circuits have been externally disconnected. Before removing either front access panel, refer to the Lockout and Tag/Isolation Procedure on page x. Remote ON/OFF Switch Terminals are provided for an external ON/OFF switch if remote ON/OFF control is required or if the PV system specification requires an emergency stop switch

28 Introduction Operation Features The Xantrex GT30 has the following operation features. Fixed Unity Power Factor Operation Peak Power Tracking The Xantrex GT30 maintains power factor close to unity (0.99 at full load) during operation. The control software constantly senses utility voltage, and constructs the output current waveform to match the utility voltage. The Xantrex GT30 is not capable of operation without the presence of normal utility voltage, nor is it capable of varying the output power factor from unity. An advanced, field-proven, Maximum Peak Power Tracker (MPPT) algorithm integrated within the Xantrex GT30 control software ensures the optimum power throughput for harvesting energy from the photovoltaic array. The peak power voltage point of a PV array can vary, primarily depending upon solar irradiance and surface temperature of the PV panels. This peak power voltage point is somewhat volatile, and can easily move along the I-V curve of the PV array every few seconds. The MPPT algorithm allows the Xantrex GT30 to constantly seek the optimum voltage and current operating points of the PV array, and maintain the maximum peak PV output power. Accessible using the serial ports (see Chapter 5), there are five user-settable parameters that control the behavior of the maximum peak power tracker within the Xantrex GT30. User settable parameters include: PPT V Ref, I PPT Max, PPT Enable, PPT Rate, and PPT V Step

29 Inverter Functions Utility Voltage/Frequency Fault Automatic Reset In the event of a utility voltage or frequency excursion outside of preset (adjustable) limits, the Xantrex GT30 will stop operation and display a fault at the operator interface. Once the utility voltage has stabilized within acceptable limits for a period of at least 5 minutes (adjustable), the Xantrex GT30 will automatically clear the fault and resume normal operation. Inverter Functions Power Quality Standby Mode The use of IGBT devices allows for high switching frequencies. The combination of the high switching frequencies and AC line filter produces high fidelity waveforms which are below the limits recommended in IEEE 1547 for total harmonic current distortion as well as the limits for individual harmonics. The inverter allows the power factor to be regulated precisely at unity, eliminating the need for external reactive power compensation. The inverter has the ability to go into a standby mode if the photovoltaic cells are not producing adequate energy for the inverter to generate a minimum level of power. During standby mode the inverter will disconnect from the utility AC line and from the PV source array, and draw a maximum of 20 watts. Standby mode will occur during the night and when cloud cover reduces available photovoltaic cell energy. Remote Access and Firmware Download Fault Notification Remote access is available through multiple communication options. The ability to control and monitor the status of the inverter (including fault and data logging) is available using remote access, see Chapter 5, Remote Programming and Advanced Settings. The firmware for the main inverter microprocessor can be upgraded using a download from local laptop or remote computer through the remote access port. Important: Remote downloading should only be done by Xantrex field service, and not the customer. The inverter will provide notification to the Operator that a fault has occurred on the inverter. Fault notification may occur through the LCD or by remote access using the PV View Graphic User Interface (GUI) software

30 Introduction Fault Conditions The following conditions will create a fault condition and will cause the unit to shutdown or refuse to start, and to report a fault code. AC Frequency High or Low AC Voltage High or Low AC Over-Current Fault Power Supply Fault DC Bus Over-Voltage PV Ground Fault Power Matrix Over- or Under-Temp. Disconnect Switch Open Safety and Protection Features Anti-Islanding Protection The inverter has many built-in safety and protection features to prevent or limit damage to the photovoltaic system, the inverter, and the utility distribution system in the event of a component or system-level failure. These features provide for orderly system shut-down with a minimum number of external protective devices. A condition referred to as "Islanding" occurs when a distributed generation source (such as the Xantrex GT30 Grid-tied Photovoltaic inverter) continues to energize a portion of the utility grid after the utility experiences an interruption in service. This type of condition may compromise personnel safety, restoration of service, and equipment reliability. The Xantrex GT30 employs a method for detecting the islanding condition using a Phase-Shift-Loop (PSL). This method is implemented in the Xantrex GT30 Controller to prevent islanding of the Xantrex GT30. The Xantrex GT30 Controller continuously makes minor adjustments to the power factor phase angle above and below unity. In the event of a utility interruption or outage, these adjustments destabilize the feedback between the inverter and the remaining load, resulting in an over/under frequency or voltage condition. Upon detection of such a condition, the Xantrex GT30 then performs an immediate orderly shutdown and opens both the main AC and DC contactors. The fault condition will remain latched until the utility voltage and frequency have returned to normal for at least 5 minutes. This method has been extensively tested and proven to exceed the requirements of IEEE-1547 (Standard for Interconnecting Distributed Resources with Electric Power Systems) and UL 1741 (Controllers and Interconnection System Equipment for Use With Distributed Energy Resources)

31 Safety and Protection Features PV Ground Fault Protection The Xantrex GT30 will automatically detect and interrupt fault currents from the PV array to earth ground. In normal operation, PV1- and PV2+ terminals are electrically connected to the N (neutral) terminal within the Xantrex GT30. The N terminal is connected to the electrical utility point of service load center and bonded therein to the system earth ground. If either subarray experiences a ground fault, the Xantrex GT30 automatically breaks all current carrying PV connections, and leaves both subarrays, PV1 and PV2, ungrounded and floating. The ground fault will be annunciated on the GT30 front panel display. To restart the Xantrex GT30 after a ground fault has been repaired, replace all open PV GFP fuses (Type KLKD1 only) and reset the Xantrex GT30. See Figure 3-6 on page 3 13 for location of PV GFP fuses. See page 6 3 for Xantrex GT30 reset procedure. WARNING: Fire hazard Replace these fuses only with fuses rated for 600VDC, 1A type KLKD 1 or equivalent. IGBT Device Protection IGBTs are protected against DC over-voltage and AC over-current, and DC desaturation conditions by control hardware and firmware within the inverter. The temperature of the primary heatsink for the IGBT devices is monitored. In the event an over-temperature condition, the power tracker is adjusted to reduce the dissipation in the inverter in an attempt to continue delivering power to the utility. If the over-temperature conditions persists, the inverter will go into overtemperature fault shutdown response and will re-start when the heatsink returns to an acceptable temperature. Under and Over Voltage and Frequency Detection Phase Rotation Detection The inverter constantly monitors the grid voltage and frequency. During conditions where the utility voltage or frequency are outside acceptable adjustable limits, the inverter automatically ceases to export power until the grid recovers. These setpoints are field adjustable, subject to acceptance of the new setpoints by the utility or authority having jurisdiction. This is in compliance with UL 1741 Rev 2005 and IEEE The inverter automatically detects the phase rotation of the 3-phase input upon power-up, and sets the AC output reference accordingly

32 Introduction Additional Protection AC circuit breaker at the AC input line to protect from utility short circuit contribution AC voltage imbalance detection to prevent operation with a blown fuse (single-phasing) AC Current Imbalance PV over-voltage and over-current protection Utility DC injection Over-temperature protection for the inverter bridge to protect against IGBT damage by reducing output or shutting down the inverter to limit temperatures

33 ON OFF ON OFF Communication Features and Methods Communication Features and Methods The Xantrex GT30 provides system status, fault information and historical performance data information to the user. System status and fault information can be accessed using the front panel LCD, using an RS232 connection to a PC or using an RS485/Modbus connection to a remote monitoring system. Data logging is available using the RS232 or the RS485/Modbus connection, see Chapter 5. LCD System Status and Fault Reporting Basic system status and all fault conditions rising from within the Xantrex GT30 are available to the user. The 4-line LCD will display a brief text description of the fault. See Chapter 5, Remote Programming and Advanced Settings for information on the text that will display during different situations. LCD Display PV Disconnect AC Disconnect Optional Equipment Communication Modems Figure 1-2 LCD Display Location The following options are available for purchase for use with the Xantrex GT30 to enhance its capability. Contact a Xantrex distributor for further information on installation options. Xantrex offers modems that can be connected to the RS232 serial port for remote monitoring of the inverter. Please check with Xantrex on available modem types. The remote user has the ability to control and monitor the status of the inverter through this connection

34 Introduction

35 2 Operation Chapter 2, Operation contains information on the basic operation of the Xantrex GT30 Grid-Tied Photovoltaic Inverter.

36 Operation Description of System Operation Overview The Xantrex GT30 is a fully automated grid-interactive photovoltaic power inverter. System startup, system shutdown, PV power tracking, and fault detection scenarios are all governed and monitored by the Xantrex GT30 controller. Manual interaction or control of the inverter is necessary only in the event of a system fault that cannot be automatically cleared. Additionally, the following conditions govern operation of the Xantrex GT30. Stable utility AC voltage and frequency as specified in Table A-2 must be present for all states of operation. PV voltage as specified in Table A-2 must be present. Both the AC and PV disconnect switches must be in the ON or closed position. Fault conditions must not be present. Remote shutdown terminals RSD+ and RSD must be shorted together by switch closure or wire jumper. Operating States A state machine implemented within the Xantrex GT30 control software governs the operation of the Xantrex GT30 with clearly defined transitions between its operating states. There are five steady-state operating states and numerous intermediate transition states. Table 2-1 Operating States State Initializing Sleep Wake-up Power Tracking Sleep Test Fault Shutdown Process Initializing Insufficient PV Voltage Sufficient PV Voltage Testing Inverter is Running Inverter is Running and Power is low. Inverter Disconnected due to a Fault PV disconnect is open, remote shutdown command is asserted from the user interface, or remote shutdown terminal current loop is opened The user should be aware of the following conditions governing state transitions: Qualified utility voltage must be present for all states of operation

37 Operating States Fault states are automatic from any state of operation. A fault will cause the Xantrex GT30 to immediately stop processing all power. The fault condition will be reported on the front panel LCD. Most Xantrex GT30 faults are auto-clearing and must be cleared (either by waiting for the auto-clear to resolve or by manually clearing it) before transitioning to another operating state. APPLY POWER INITIALIZING OPEN SWITCH OR REMOTE SHUTDOWN SLEEP CONTACTORS OPEN CLOSE SWITCH OR REMOTE ENABLE SHUTDOWN CONTACTORS OPEN V < PV V START V > PV V START WAKE-UP TEST 5 MINUTES SYSTEM FAULT CONTACTORS OPEN AUTO-CLEAR DELAY 5 MINUTES ONLINE CONTACTORS CLOSE P > P_MIN P < P_MIN SLEEP TEST 5 MINUTES Figure 2-1 State Transition Diagram These operating states are commanded by the state machine according to the conditions applied to the inverter, compared to the parameters set at the factory and by the user

38 Operation Initializing When powered up, the Xantrex GT30 will invoke the INITIALIZATION state. Upon completion of initialization, the Xantrex GT30 will transition to the SLEEP State. The Xantrex GT30 will perform a fuse test during initialization, if the PV voltage is sufficient. When the PV voltage is low, the fuse test will continue until the voltage rises. Once the fuse test passes, the DC Ground contactors (KCOM+ and KCOM-) are closed and remain closed at all times, unless a ground fault is detected. Sleep While in the SLEEP state, the Xantrex GT30 will monitor the PV input voltage to determine if it is time to start. The inverter monitors the status of the PV array and utility grid, waiting in standby until the PV array is available to produce power to the grid. Wake-up When the PV voltage is greater than the user settable minimum start voltage, and no fault conditions exist, the state changes to WAKEUP. Adhering to a UL 1741 rev 2005 and IEEE 1547 stipulation, this state is maintained for five minutes (default). After remaining in WAKEUP state exclusively for five minutes, the state will transition to POWER TRACKING. Power Tracking In this state the inverter is energized. Maximum Power Point Tracker (MPPT) mode is the default mode in this state. MPPT may be turned off from the user interface, in which case the inverter operating voltage stays at a settable voltage value. Sleep Test While POWER TRACKING, if power drops below 300W (default) the state changes to SLEEP TEST. If power rises back above the set point for minimum power during SLEEP TEST state, then the state returns to POWER TRACKING. If the power remains below the user settable minimum power or if the PV voltage drops below the Minimum Operating Voltage for a user settable amount of time, the state will transition back to SLEEP. System Fault With the exception of the Stop State, regardless of which state the machine is in, it will transition to the FAULT state if any fault is detected in the inverter. Transitions to the fault state follows the same sequence as transitions to the SLEEP state. In this state the inverter is disconnected from the AC line. If the fault requires manual reset, the inverter will exit the fault state only when the cause of

Xantrex GT500 480, Xantrex GT500 480 PG, Xantrex GT500 600 & Xantrex GT500 600 PG 500 kw Grid-Tied Photovoltaic Inverters

Xantrex GT500 480, Xantrex GT500 480 PG, Xantrex GT500 600 & Xantrex GT500 600 PG 500 kw Grid-Tied Photovoltaic Inverters Xantrex GT500 480, Xantrex GT500 480 PG, Xantrex GT500 600 & Xantrex GT500 600 PG 500 kw Grid-Tied Photovoltaic Inverters Planning and Installation Manual www.schneider-electric.com Xantrex GT500 480,

More information

AC Coupling of Inverters for Grid Tied PV Systems

AC Coupling of Inverters for Grid Tied PV Systems AC Coupling of Inverters for Grid Tied PV Systems AC Coupling with Conext s, Xantrex GT Inverters, and Conext TX Inverters Application Note 976-0240-01-01 Rev B DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION,

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

Xantrex GT500 MVX & Xantrex GT500 MVX PG 500 kw Grid-Tied Photovoltaic Inverters

Xantrex GT500 MVX & Xantrex GT500 MVX PG 500 kw Grid-Tied Photovoltaic Inverters Xantrex GT500 MVX & Xantrex GT500 MVX PG 500 kw Grid-Tied Photovoltaic Inverters Planning and Installation Manual www.schneider-electric.com Xantrex GT500 MVX & Xantrex GT500 MVX PG 500 kw Grid-Tied Photovoltaic

More information

Conext Grid Tie Solar Inverter Conext TX 2800 NA Conext TX 3300 NA Conext TX 3800 NA Conext TX 5000 NA

Conext Grid Tie Solar Inverter Conext TX 2800 NA Conext TX 3300 NA Conext TX 3800 NA Conext TX 5000 NA Conext Grid Tie Solar Inverter Conext TX 2800 NA Conext TX 3300 NA Conext TX 3800 NA Conext TX 5000 NA Owner s Manual www.schneider-electric.com Conext Grid Tie Solar Inverter Owner s Manual www.schneider-electric.com

More information

Xantrex GT630 E GI 1K. Grid-Tied Photovoltaic Inverters

Xantrex GT630 E GI 1K. Grid-Tied Photovoltaic Inverters Xantrex GT500 E 500 kw and Xantrex GT630 E 630 kw Grid-Tied Photovoltaic Inverters Xantrex GT500 E Xantrex GT500 E GI Xantrex GT630 E Xantrex GT630 E GI Xantrex GT630 E GI 1K Planning, Installation, Troubleshooting

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

Cooling Fan Replacement September 2008 975-0455-01-01 Rev A1 Page 1 of 6

Cooling Fan Replacement September 2008 975-0455-01-01 Rev A1 Page 1 of 6 975-0455-01-01 Rev A1 Page 1 of 6 0 I WARNING RI SK OF ELE CTRI CA L S HOCK DO NO T REM OVE COVER, NO USER SERVICEABLE PARTS INSIDE. STORED ENERG Y IN CAPACITOR. ALLOW AT LEAST 5 MINUTES AFTER DISCONNECTI

More information

YSmart Technology Co.,Ltd

YSmart Technology Co.,Ltd YSmart Technology Co.,Ltd GWV Series Grid Tie Microinverter User Manual The copyright of this user manual belong to YSmart TechnologyCompany Limited. Without the written permission of the copyright holder,

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers Technical Note Freedom/Fleet Power 512-0084-01-01 Rev 1 Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers Overview This document is a guide for troubleshooting inverters, battery chargers,

More information

VLT Series 300 Watt True Sine Wave Inverter

VLT Series 300 Watt True Sine Wave Inverter VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS

More information

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide circuit. Reverse connection will damage the module and may result in fire. CAUTIONS Solar electric modules produce DC electricity

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

RIGOL. Quick Guide. DS1000CA Series Oscilloscope. Aug. 2011. RIGOL Technologies, Inc.

RIGOL. Quick Guide. DS1000CA Series Oscilloscope. Aug. 2011. RIGOL Technologies, Inc. Quick Guide DS1000CA Series Oscilloscope Aug. 2011 Technologies, Inc. Guaranty and Declaration Copyright 2011 Technologies, Inc. All Rights Reserved. Trademark Information is a registered trademark of

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification

Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification Assembly 025A0215 600A0942 Rev. A May 14, 2012 025A0215 Brushless DC Motor Controller Page 1 Revision History ECN # Date Rev Description

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

2.06. Version. Kinglong New Energy Technology Co.Ltd. Sunteams 1500 Sunteams 3000. Sunteams 4000 Sunteams 5000

2.06. Version. Kinglong New Energy Technology Co.Ltd. Sunteams 1500 Sunteams 3000. Sunteams 4000 Sunteams 5000 Photovoltaic Inverter Specification Version 2.06 1500 2000 3000 4000 5000 Kinglong New Energy Technology Co.Ltd. Kinglong New Energy Technology Co.Ltd. specification 1.1. Introduction... 3 1.1.1. Environment...

More information

Application Note: String sizing Conext CL Series

Application Note: String sizing Conext CL Series : String sizing Conext CL Series 965-0066-01-01 Rev A DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH This Application Note is in addition to, and incorporates by reference, the installation

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Solar Inverter Sunny Boy 5000US, 6000US, 7000US

Solar Inverter Sunny Boy 5000US, 6000US, 7000US Solar Inverter Sunny Boy 5000US, 6000US, 7000US Installation Guide SB50US-70US-IUS090523 TBUS-SB50_60_70US Version 2.3 US Copyright 2008 SMA America, Inc. All rights reserved. No part of this document

More information

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface

More information

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems This Agreement is made and entered into this day of, 20, ( Effective Date ) by and between the Orlando Utilities Commission

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

Fronius IG Plus. The next generation grid-connected PV inverter

Fronius IG Plus. The next generation grid-connected PV inverter Fronius IG Plus The next generation grid-connected PV inverter Maximum energy harvest cloudy or clear The first complete inverter solution. Reliable. Proven. Smart. An outstanding addition to the family:

More information

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

More information

User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1

User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1 User Manual Hybrid 1KW-5KW INVERTER / CHARGER Version: 1.1 Table of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Product Overview... 3 INSTALLATION...

More information

PV System Disconnect PV System Discon-

PV System Disconnect PV System Discon- PV System Disconnect PV System Discon- INSTALLATION & OPERATION MANUAL 97-600100-06-A02 Preface PV Powered PV Powered designs, manufactures, and markets the solar power industry s most reliable photovoltaic

More information

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

Mobile Data Power Model: MDP-25

Mobile Data Power Model: MDP-25 Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss

More information

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the

More information

About the HotWire 7900 10-Slot Standalone Shelf

About the HotWire 7900 10-Slot Standalone Shelf TM HotWire Model 7900 10-Slot Standalone Shelf Installation Instructions Document Number 7900-A2-GN10-10 About the HotWire 7900 10-Slot Standalone Shelf The HotWire 7900 10-Slot Standalone Shelf is designed

More information

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported PCIe Cards 1.2 PACKAGE

More information

Brushless DC Motor Controller Product Specification Assembly 025F0129

Brushless DC Motor Controller Product Specification Assembly 025F0129 Brushless DC Motor Controller Product Specification Assembly 025F0129 September 16, 2009 025F0129 ST B Brushless DC Motor Controller Data Sheet Page 1 Revision History ECN # Date Rev Description By 07058

More information

How To Install A Sunny Boy

How To Install A Sunny Boy PV Inverter SUNNY BOY 3000-US / 3800-US / 4000-US Installation Guide SB30-40US-IUS103030 TBUS-SB30_40US Version 3.0 EN SMA America, LLC Legal Restrictions Copyright 2010 SMA America, LLC. All rights reserved.

More information

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS + Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,

More information

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers 9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product

More information

User Manual DONGGUAN SHENGYANG INDUSTRIAL CO., LTD. SY WMVC Smart Grid Tie Microinverter. Dongguan Shengyang Industrial Co., Ltd.

User Manual DONGGUAN SHENGYANG INDUSTRIAL CO., LTD. SY WMVC Smart Grid Tie Microinverter. Dongguan Shengyang Industrial Co., Ltd. DONGGUAN SHENGYANG INDUSTRIAL CO., LTD SY WMVC Smart Grid Tie Microinverter User Manual Dongguan Shengyang Industrial Co., Ltd. ADD: No. 1 Shangxin Road, New Village, Xin An Community, Chang An Town, Dongguan

More information

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire) FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

Owner s Guide SunPower SPRx Solar Monitor Manual Type

Owner s Guide SunPower SPRx Solar Monitor Manual Type SunPower-Wired-Remote.book Page i Friday, July 7, 2006 5:09 PM Owner s Guide SunPower SPRx Solar Monitor Manual Type SunPower-Wired-Remote.book Page ii Friday, July 7, 2006 5:09 PM SunPower-Wired-Remote.book

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

StorTrends 3400 Hardware Guide for Onsite Support

StorTrends 3400 Hardware Guide for Onsite Support StorTrends 3400 Hardware Guide for Onsite Support MAN-3400-SS 11/21/2012 Copyright 1985-2012 American Megatrends, Inc. All rights reserved. American Megatrends, Inc. 5555 Oakbrook Parkway, Building 200

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

3000W Power Inverter

3000W Power Inverter 3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE

More information

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your

More information

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

Installation and Operation Back-UPS 1250, 1300, 1500

Installation and Operation Back-UPS 1250, 1300, 1500 Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with

More information

Solar Electric Power System Owner s Manual

Solar Electric Power System Owner s Manual GE Energy Solar Electric Power System Owner s Manual v4.2nmtr Safety...3 Documents...4 Congratulations...5 Principles of Operation...5 Measuring Your Power and Energy...7 Table of Contents Estimating Your

More information

EGCP-3 LS 8406-113 Revision L. Explanation of Software Changes Made for the EGCP-3 LS Control. Application Note 51294

EGCP-3 LS 8406-113 Revision L. Explanation of Software Changes Made for the EGCP-3 LS Control. Application Note 51294 EGCP-3 LS 8406-113 Revision L Explanation of Software Changes Made for the EGCP-3 LS Control Application Note 51294 WARNING DANGER OF DEATH OR PERSONAL INJURY WARNING FOLLOW INSTRUCTIONS Read this entire

More information

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed

More information

ST Series POWER SUPPLIES USER INSTRUCTIONS

ST Series POWER SUPPLIES USER INSTRUCTIONS Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional

More information

OWNER S MANUAL 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada

OWNER S MANUAL 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) OWNER S MANUAL 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada Tel: (604) 420-1585 Fax: (604) 420-1591 http:// www. statpower.com PROsine 2.5/3.0 ACS Panel

More information

Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P

Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P Distributed in the U.S.A. and Canada by CHENG USA, INC. Sales (574) 294-8997 Warranty Service (877) 294-8997

More information

12 Volt 30 Amp Digital Solar Charge Controller

12 Volt 30 Amp Digital Solar Charge Controller 12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

SOLAR POWER CONDITIONER Service Manual

SOLAR POWER CONDITIONER Service Manual SOLAR POWER CONDITIONER Service Manual JH-1600E Released in May 2009 Version: V00 TABLE OF CONTS Important Service Safety Precautions 2 Warning.. 3 General Information.. 5 1 System Overview... 5 2 Overview

More information

AGS. Owner's Manual. Xantrex Automatic Generator Start Control System

AGS. Owner's Manual. Xantrex Automatic Generator Start Control System AGS Owner's Manual Xantrex Automatic Generator Start Control System TABLE OF CONTENTS INTRODUCTION...3 Main Features...3 Safety Summary...3 THINGS YOU SHOULD KNOW...4 THEORY OF OPERATION...5 System...5

More information

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters AP-XC-025 Revision B DANGER RISK OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in addition to, and

More information

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Arc Flash Avoidance and its Application to Overhead Traveling Cranes Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS

GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS TR TSY 000757 GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS 1. Introduction.... 1.1 Purpose and Scope 1.2 Organization.. 1.3 Reason for Reissue From Technical Advisory

More information

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance WHITE PAPER Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance Overview Enphase has developed a new microinverter family that includes the M250 and new

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

ELECTRICAL SAFETY. The standard unit for measuring electrical current. ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety

More information

Re-defining the utility-scale inverter

Re-defining the utility-scale inverter Re-defining the utility-scale inverter We believe in green energy in the ability to meet and contribute to growing power demands while supporting a smart grid that serves a smart society. Solution at a

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

NASS Solar DC Pool Pumps

NASS Solar DC Pool Pumps Technical Data Manual For NASS Models: NASS 500 NASS 900 NASS 1200 NASS 2200 X NASS 2200 JP15-14/600 JP31-19/1000 JP35-22/2000 JP60-13/2200 NASS Solar DC Pool Pumps NASS JP Type DC Pool Pumps For pumping,

More information

Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger

Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger Digital echo-charge Owner s Manual Xantrex Digital echo-charge Battery Charger Thank you for purchasing a Xantrex Digital echo-charge. Xantrex Technology Inc. takes pride in manufacturing quality products

More information

Manual. Solar Fountain Mobile Phone Charger

Manual. Solar Fountain Mobile Phone Charger EN Manual Solar Fountain Mobile Phone Charger Copyrights 2008 Victron Energy B.V. All Rights Reserved This publication or parts thereof may not be reproduced in any form, by any method, for any purpose.

More information

Transfer Equipment Controls

Transfer Equipment Controls Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment

More information

Digi-Motor Installation Guide

Digi-Motor Installation Guide Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support

More information

PV-Inverter SunPower SPR-5000m / SPR-6000m / SPR-7000m / SPR-8000m

PV-Inverter SunPower SPR-5000m / SPR-6000m / SPR-7000m / SPR-8000m PV-Inverter SunPower SPR-5000m / SPR-6000m / SPR-7000m / SPR-8000m Installation Guide SPR50-80m-IUS102630 TB-SPR50_60_70M DMS#. 001-16803 Rev *E US Copyright 2010 SunPower, Corp. All rights reserved.

More information

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01 ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions

More information

ADDENDUM #1(BID PACKAGE # 3)

ADDENDUM #1(BID PACKAGE # 3) H2Engineering, Inc. 114 East Fifth Avenue Tallahassee, FL 32303 Phone 850.224.7922 Fax 850.224.5876 ADDENDUM #1(BID PACKAGE # 3) To: Jeff Williams From: Peter Lindstrom Co: Leon County Date: October 04,

More information

PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V

PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V PHOTOVOLTAIC SYSTEM CONTROLLERS OPERATOR S MANUAL SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V 6A / 12V 10A / 12V 10A / 24V 20A / 12V 20A

More information

SPR-2800x SPR-3300x SPR-4000x SPR-5000x. Owner s Manual. SunPower Solar Inverter

SPR-2800x SPR-3300x SPR-4000x SPR-5000x. Owner s Manual. SunPower Solar Inverter SPR-2800x SPR-3300x SPR-4000x SPR-5000x Owner s Manual SunPower Solar Inverter SunPower Solar Inverter Owner s Manual Trademarks SunPower Solar Inverter is a trademark of SunPower Corporation. Other trademarks,

More information

Business Audio System: Music & Messaging MP3 Player. by Grace Digital Audio. User Guide. Model No. GDI-USBM10

Business Audio System: Music & Messaging MP3 Player. by Grace Digital Audio. User Guide. Model No. GDI-USBM10 Business Audio System: Music & Messaging MP3 Player by Grace Digital Audio User Guide Model No. GDI-USBM10 User Guide Contents Introduction 2 Safety & General Use Information 2 Features 3 Set Up & Operation

More information

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a

More information

USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE. AeroVironment EV Solutions

USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE. AeroVironment EV Solutions USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE AeroVironment EV Solutions 2013 AeroVironment, Inc. All rights reserved. AeroVironment, EV Solutions, and the AeroVironment logo are trademarks

More information

Back-UPS Pro 1300/1500 Installation and Operation

Back-UPS Pro 1300/1500 Installation and Operation Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a

More information

Paralleling Switchgear

Paralleling Switchgear Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more

More information

70-Series CAN Power Management System

70-Series CAN Power Management System Owner s Manual VANNBus 70Series Power Management System With CAN Capable Smart Monitor TM Table of Contents Introduction. 3 Specifications.. 4 Theory of Operation... 5 Typical Applications...... 8 Installation

More information

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

Analog Servo Drive 25A8

Analog Servo Drive 25A8 Description Power Range NOTE: This product has been replaced by the AxCent family of servo drives. Please visit our website at www.a-m-c.com or contact us for replacement model information and retrofit

More information

MODEL 2202IQ (1991-MSRP $549.00)

MODEL 2202IQ (1991-MSRP $549.00) F O R T H E L O V E O F M U S I C F O R T H E L O V E O F M U S I C MODEL 2202IQ (1991-MSRP $549.00) OWNER'S MANUAL AND INSTALLATION GUIDE INTRODUCTION Congratulations on your decision to purchase a LINEAR

More information

ADEMCO 4500 Thermostat

ADEMCO 4500 Thermostat ADEMCO 4500 Thermostat User Guide N7972V1 5/05 Rev. A TABLE OF CONTENTS About the 4500 Thermostat...1 Saving Money on Energy Bills...1 The 4500 Thermostat Provides Comfort and Convenience...1 How the 4500

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only

More information