SURGICAL SUITE TEMPERATURE AND HUMIDITY: PROVIDING WHAT SURGEONS WANT VERSUS THE LIMITATION OF YOUR EQUIPMENT

Size: px
Start display at page:

Download "SURGICAL SUITE TEMPERATURE AND HUMIDITY: PROVIDING WHAT SURGEONS WANT VERSUS THE LIMITATION OF YOUR EQUIPMENT"

Transcription

1 PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT Ronnie Moffitt PE, EM Principal Applications Engineer Trane Lexington, KY Paper Presented July 21, 2008 at the American Society for ealthcare Engineering 45 th Annual onference

2 Getting the Dew Point Temperature Required Do your surgeons want the operating room temperature and humidity controlled to a point that can not be achieved with your current system or infrastructure? There are multiple reasons why the current air handling system can not deliver the air required to meet the needs of the surgeons. The primary reason is the supply air dew point temperature that can be delivered by the air handling system. The difficulty of achieving the required dew point temperature is not regional. The extra cooling capacity required by most systems is minimal. There are multiple ways to solve the problem. Since there is more than one way to solve the problem, the question then becomes what is the infrastructure impact of each option? If it physically can be achieved, then what is the potential energy impact?

3 Past Designs Many past surgical room were designed around the AIA guideline. It recommends the operating room air temperature be 68-75F with a 30-60% relative humidity. To get this condition the air flow is dictated by a recommendation of 15 total air changes per hour, A, with 3 air changes per hour with respect to outside air. Out of this recommendation the typical room was designed for 15A with 20% outside air and design target conditions for the room of 68F 50%R. This temperature and relative humidity equates to a design room dew point temperature of 48.7F. With so many air changes per hour the supply air dew point temperature required was only slightly lower, 48F. This supply air dew point temperature could easily be achieved with a conventional water coil being supply with 42-44F chilled water from the hospital chiller plant. ooling air down the air to 48F leaving the coil would achieve the 48F dew point required to meet the humidity requirement. With the large amount of supply air (15 A), to maintain 68F temperature in the space, the supply air must be reheated to 56-59F at design conditions to prevent overcooling of the space.. Figure 1 Psychrometric Plot of Room and AU Supply onditions An operating room designed to the AIA guideline will require an approximate 48F leaving air temperature off the cooling coil.

4 urrent Designs Today there are often longer procedures, more gowning to wear, more people and equipment in proximity of the surgeon. For surgeon comfort, cooler temperatures are desired. There may also be procedures being performed that benefit from a lower room temperature; one for example is the use of cements or adhesives that are aided by cooler temperatures. ommon temperatures requested for the operating room by the surgeons have been lowered to 60-64F or even lower. The requirement is still in place to keep the room at a target of 50% R to reduce the risk of nosocomial infections. To keep the room at 50% relative humidity with the air temperature at 60-64F will require the air to be at a dew point temperature of 40- when delivered to the room. With the typical hospital having chilled water at 42-44F, this new requirement is impossible to achieve with what equipment is in place. A change in the VA system used needs to occur to make this desired target. Figure 2 Psychrometric Plot of Room and AU Supply onditions An operating room designed to the common desired conditions will require an approximate leaving air temperature off the cooling coil.

5 hange in VA Design The set point in the operating room is going dictate how dry and cold the air needs to be at the main air handler and cause changes required for the system. The air handling equipment will most likely be serving multiple procedural rooms, scrub rooms and other zones that support the surgical rooms. The example will focus on a single OR room to help the reader see what may be required to retrofit from a previous design around the AIA guideline, design A, versus going with typical new design conditions, design B. Example: Operating Room: 575ft^2 x 10ft high 14,400btu/hr Internal Sensible Load 1,600 btu/hr Internal Latent Load 135gr/lbm onditioning of Delivered: Supply Volume, Vsa = 15 A 5750 ft3 / 60 = 1,438 cfm Outside Volume, Voa = 0.20 x 1,44= 288 cfm Return Volume, Vra = Vsa Vra =1,150 cfm Supply ΔT = 14400/ (1.085*1438) = Δ9.2F Supply ΔW = 1,600/ (0.68 x 1438) = Δ1.6gr/lbm Design A Room onditions = 68F 50%R, 50.9gr/lbm Supply Temperature = 58.8F Supply umidity = 49.3gr/lbm Supply Dewpoint Temperature = 47.8F Design B Room onditions = 62F 50%R, 41.2 gr/lb Supply Temperature = 52.8F Supply umidity = 39.6gr/lbm Supply Dewpoint Temperature = 42.1F

6 ool Reheat System The starting point for Design A is a cool reheat system, the air at the central air handler is cooled to 48F to dehumidify than reheated to 58.8F. Redesigning the system to Design B and setting the room to 62F, will require the air handler to cool the air down to 40F and reheat it to 53F. This requires a 4% increase in cooling capacity and a 4% reduction in heating energy for each operating room. Though 4% more chilled water may be hard to obtain in many cases, this looks like a minor impact on the infrastructure. owever the dew point is below what is achievable with 42-44F chilled water from the chiller plant. This system will require an additional source of chilled water. The infrastructure changes include: adding a glycol chiller, a new AU with a second cooling coil and piping to a second cooling coil. The glycol chiller does not have to be sized for the entire design load. As much cooling as possible would still be accomplished by the central plant chilled water, with a new second coil fed by 36F chilled glycol to help achieve the leaving air conditions required. Though there is only a small increase in the cooling capacity required by the surgical suite. The energy use will be greater as now 35% or higher of the cooling is now accomplished by an air cooled glycol chiller versus the central plant chiller. Flow Process Diagram ool-reheat Return 1150cfm Outside 135 gr/lbm 68F 50%R 51 gr/lbm WS ooling oil Design A 48F 98%R 49 gr/lbm eating oil 56F 73%R 49 gr/lbm 180F WS Supply 1438cfm Supply Fan 58.8F 67%R 49 gr/lbm 48F DPT Figure 3 ool and Reheat Process for treating air for operating room for Design A onditions. What s Needed hilled water <180F ot Water ow Much per OR 55,700 btuh ooling 12,800 btuh eating Return 1150cfm Outside 135 gr/lbm Flow Process Diagram ool-reheat 62F 50%R 41 gr/lbm WS ooling oil Design B 50F 98%R 49 gr/lbm 36F WS ooling oil 42.5F 98%R 39 gr/lbm eating oil 50F 74%R 39 gr/lbm 180F WS Supply 1438cfm Supply Fan 52.8F 67%R 39 gr/lbm DPT Figure4 ool and Reheat Process for treating air for operating room for Design B onditions. What s Needed hilled Water 36F hilled Glycol <180F ot Water ow Much per OR 57,800 btuh ooling 37,000btuh coil1 20,800btuh coil2 12,000 btuh eating

7 Active Desiccant System Instead of using a glycol chiller to drop the dew point temperature past the chilled water temperature, this could be done by using an active desiccant dehumidifier. The most common system used for this application dehumidifies the outside air. The outside air is first pre-cooled by a new chilled water coil then dehumidified further by a heat activated desiccant. The heat activated desiccant rotor is typically regenerated by a direct fired gas heater or high pressure steam that heats a second path of outside air flow. The regeneration air is heated above 180F. This heated air heats the desiccant which changes the isotherm, and reduces the ability of the desiccant to adsorb water vapor. This heat regenerates the desiccant to enable it to adsorb more vapor as it rotates around to the cooled outside air. Versus the past design A this will require about 4% more heating energy and reduce the cooling needed by 5%. The heat required will now require an infrastructure change as natural gas piping and service is needed. Also piping for additional cooling coil, a secondary outside air intake and an additional exhaust air outlet, an an additional unit or adding a larger custom air handler which will have at least two fans. By separating the air streams the cooling accomplished by the chiller is slightly reduced. owever, some of the dehumidification work is moved to the desiccant dehumidifier which has a OP<1.0 vs a OP>3.0 for the chiller. The added heat energy will require more energy usage by the OR than the initial design A. Figure5 Preool Active Desiccant Process for treating air for operating room for Design B onditions. What s Needed hilled Water Natural Gas Service Exhaust Outlet Secondary Outdoor Inlet ow Much per OR 52,700 btuh ooling 23,500btuh coil1 29,200btuh coil2 13,200 btuh eating

8 ool-reheat System with Desiccant Wheel in Series The next system uses a desiccant wheel in series to lower the dew point temperature. owever, it does not require high heat or a separate regeneration air stream. It utilizes the recirculated air from the operating rooms to regenerate the wheel. This is possible because a different type of desiccant is utilized. Using recirculated air also removes the introduction of an additional air stream. The type III isotherm wheel has the ability to adsorb water vapor at high relative humidity conditions. This affinity for water vapor quickly drops off at a lower relative humidity. This allows for water vapor to be transferred with out adding regeneration heat. This system will allow for an AU with the same chilled water as in design A with still one coil, one fan and one air path achieve the conditions for Design B. The air is dehumidified and cooled by the cooling coil as in a cool reheat system. The air actually leaves the cooling coil at a temperature actually higher than design A. After the cooling coil additional water vapor is removed by the wheel and some heat is added from the adsorption process. The water vapor that is removed by the wheel is added to the mixed air flow on the other side of the wheel. This occurs because it is at a lower relative humidity. The water vapor transferred then takes a second pass at the cooling coil and is removed. The end result is a 19% reduction in cooling capacity required and an 86% reduction in heat required at new design condition versus the original design A. The infrastructure changes are limited to a new AU with a wheel. The operating rooms are taken from past 68F 50%R to the improved 62F 50%R, at the same time the heat and cooling required is reduced without changing the hospital infrastructure. Outside 135 gr/lbm Return 1150cfm Flow Process Diagram Series Desiccant Wheel 62F 50%R 41 gr/lbm 66F 63%R 60 gr/lbm Desiccant Wheel 62F 74%R 69 gr/lbm Figure6 ool and Reheat w/ Series Desiccant Wheel for treating air for operating room for Design B onditions. What s Needed hilled Water <180F ot Water Supply 1438cfm 52F 68%R 39 gr/lbm 48F 97%R 48 gr/lbm 65F 69 gr/lbm Supply Fan ow Much per OR 48,000 btuh ooling 1,500 btuh eating %R 39 gr/lbm DPT 180F WS eating oil WS ooling oil

9 Summary The more stringent conditions being expected by surgeons for operating rooms often drives the infrastructure requirements and increases the energy usage for the hospital. There are different ways to minimize the impact of these vital spaces. With new technologies, there are methods that improve dehumidification capability. It may be possible to increase the dehumidification performance of the system to meet new requirements without increasing the heating and cooling required from the facility. This might be to the extent that the cooling and heating needed can be reduced while at the same time improving the conditions in the surgical suite. References Greim,., D. Garrison, and R. Marchessault. A Precision Operation. Engineered Systems 23(7). July pp Moffitt, R. Taking the eat Out of Desiccants. PA 79(3). March pp Murphy, J. Temperature and umidity ontrol in Surgery Rooms. ASE Journal 48(6). June pp Murphy, J. and B. Bradley, Advances in Desiccant-Based Dehumidification, ADM- APN016-EN, Trane Engineers Newsletter.

10 PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT Ronnie Moffitt, PE EM Principal Applications Engineer, Trane 45 th Annual onference & Technical Exhibition PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT Session Outline: System Design Past Typical Operating Room Design urrent Typical Operating Room Design ool-reheat andling System Impact of hanging To urrent Room Design ool-reheat System Active Desiccant System ool-reheat Series Desiccant PAST OPETING ROOM DESIGN OR Room Design 68F 50% 90% 80% 70% Altitude 0ft 60% 50% 40% 30% 20% 10% umidity Ratio Grains/lbm Dry Bulb Temperature (F)

11 URRENT OPETING ROOM DESIGN OR Room Design 62F 50% 90% 80% 70% Altitude 0ft 60% 50% 40% 30% 20% 10% umidity Ratio Grains/lbm Dry Bulb Temperature (F) OOL REEAT DEUMIDIFIATION AND TEMPERING T space R EA T space R entral andling Unit hilled Water 42-44F Example: Design A 68F 50% Single Operating Room entral andling Unit T operating room R EA T space R hilled Water

12 Example: Design A 68F 50% Single Operating Room 1,150cfm entral andling Unit hilled Water T operating room R EA 5750ft 3 15A Total 3A Total Example: Design A 68F 50% Single Operating Room 1,150cfm entral andling Unit 58.8F hilled Water 49 gr/lbm 47.8F Dew Point T 68F R 50% 51 51gr/lbm EA Sensible Load 14,400btu/hr Latent Load 1,600btu/hr URRENT OPETING ROOM DESIGN 90% 80% 70% Altitude 0ft 60% 50% % LVG ool oil Lvg Reheat Supply Mixed Return Outside Dew Point Design Day 30% 20% 10% umidity Ratio Grains/lbm Dry Bulb Temperature (F)

13 Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 68F 51gr/lbm 48F 56F 98% 49gr/lbm 47.5F DPT WS entral andling Unit 180F WS 58.8F 67% 49gr/lbm 47.5F DPT Required for Operating Room ooling Plant 55,700btu/hr eating Plant 12,800btu/hr Example: Design B 62F 50% Single Operating Room 1,150cfm entral andling Unit 52.8F hilled Water 39 gr/lbm 42.0F Dew Point T 62F R 50% 41 41gr/lbm EA Sensible Load 14,400btu/hr Latent Load 1,600btu/hr Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 62F 41gr/lbm 42.5F 98% DPT WS entral andling Unit Required for Operating Room ooling Plant 57,800btu/hr eating Plant 12,000btu/hr 50F 180F WS 52.8F 67% DPT Infrastructure hanges Glycol hiller 2 nd ooling oil

14 Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 62F 41gr/lbm 50F 98% 52gr/lbm 42.5F 98% DPT WS 36F WS Required for Operating Room ooling Plant 37,000btu/hr New hiller 20,800btu/hr eating Plant 12,000btu/hr entral andling Unit 50F 180F WS 52.8F 67% DPT Infrastructure hanges Glycol hiller 2 nd ooling oil Active Desiccant Wheel eat-activated Desiccant Wheel EA RG 8-24 rph Process eat used to dehumidify 2,250 to 3,000 Btu/lbm water removed Active Desiccant Isotherms %Weight Water Type I Isotherms F 70F 90F 110F 130F Desiccant % 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% %R Regeneration 150F 170F 190F 210F Regeneration primary a function of temperature, hange in isotherm

15 Example: Design B 62F 50% Single Operating Room Pretreat Active Desiccant EA 55F 64gr/lbm 135gr/lbm WS 100cfm 205F 94F 34gr/lbm Natural Gas 1,150cfm 62F 41gr/lbm 50F 73% DPT WS 52.8F 67% DPT URRENT OPETING ROOM DESIGN 90% 80% 70% Altitude 0ft 60% 50% % LVG ool oil Outside Dew Point Design Day 30% 20% umidity Ratio Grains/lbm Return 10% Lvg ool oil 2 Supply Mixed Lvg Desiccant Wheel Dry Bulb Temperature (F) Example: Design B 62F 50% Single Operating Room Pretreat Active Desiccant EA 135gr/lbm WS 100cfm 205F 94F 34gr/lbm Natural Gas 1,150cfm 62F 41gr/lbm Required for Operating Room ooling Plant 52,700btu/hr eating Plant 13,200btu/hr 50F 73% DPT WS 52.8F 67% DPT Infrastructure hanges Natural Gas 2 nd ooling oil 2 nd Outside Inlet 2 nd Exhaust outlet 2 nd Unit or Tall AU

16 ool-reheat with Series Desiccant Wheel Type III Desiccant Wheel 50% R ΔW = +10 to 25gr 8-24 rph ΔW = -10 to 25gr 98% R ooling oil used for dehumidification Wheel enhances latent work done by coil Final Supply Dew Point Temperature << oil LVG Temp Type III Desiccant Isotherms Type III Series Desiccant Wheel 50% R ΔW = +10 to 25gr A T A T 8-24 rph ΔW = -10 to 25gr 98% R A Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 62F 41gr/lbm 66F 63% 60gr/lbm entral andling Unit 62F 74% 69gr/lbm 52.8F 67% 42.0F DPT 180F WS 52F 68% Required for Operating Room ooling Plant 48,000btu/hr eating Plant 1,500btu/hr 48F 97% 48gr/lbm WS

17 URRENT OPETING ROOM DESIGN 90% 80% 70% Altitude 0ft 60% 50% % LVG Regen Outside Dew Point Design Day 30% 20% umidity Ratio Grains/lbm LVG ool oil Supply Mixed Return 10% Dry Bulb Temperature (F) Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 62F 41gr/lbm 66F 63% 60gr/lbm entral andling Unit 62F 74% 69gr/lbm 52.8F 67% 42.0F DPT 52F 68% Required for Operating Room ooling Plant 48,000btu/hr eating Plant 1,500btu/hr 48F 97% 48gr/lbm WS Infrastructure hanges Taller AU ase Study Data: Extending Achievable Dew Point St. Vincent s ospital, Data was logged by University of entral Florida in collaboration with the Oak Ridge National Laboratory/ Department of Energy (Office of Distributed energy, within the Office of Energy Efficiency and Renewable Energy) for more information go to

18 ase Study Data: Extending Achievable Dew Point 5F or lower dew point temperatures with same chilled water Typical Mixed onditions for Surgical Suites Operating Room Example Going From Design A To B Going from 68F 50% to 62F 50% Potential Building System Impact Estimated hange in Required apacity Infrastructure AU Design ooling eating Equipment AU Piping ot entral entral New ooling hilled Water or Natural Total Plant Total Plant /eating Plants New AU Water Steam Gas New AU Ducting Inlet or Outlets No hange 1oil ooling with Reheat 4% -33% -4% -4% Glycol hiller Longer 2 oils No hange No hange Active Desiccant Taller New, New EA with ooling -5% -5% 4% -100% Gas Burner /Longer 2 oils None Burner ooling with Series No hange 1oil Desiccant -19% -19% -89% -89% No hange Taller None No hange No hange Operating Room Example Going From Design A To B Going from 68F 50% to 62F 50% Potential Energy Impact Estimated hange in Required apacity AU Design ooling Total Infrastructure eating Equipment entral entral New ooling Plant Plant /eating Plants Total Energy Impact ooling with Reheat 4% -33% -4% -4% Glycol hiller igher combined KW/TON Active Desiccant with ooling -5% -5% 4% -100% Gas Burner Desiccant Dehumidification vs Vapor ompression ooling with Series Desiccant -19% -19% -89% -89% No hange Less eat Energy, Less ooling Energy at same KW/Ton

19 Operating Room Example Going From Design A To B PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT onclusions: Impact of hanging To older Operating Room More infrastructure impact vs cooling capacity Lower dew point temperature can make the cooling required less efficient Series desiccant wheel can help achieve dew point temperatures required with out hurting cooling efficiency and lowering the capacity required PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT Thank - You?? Questions?? Additional References: Greim,., D. Garrison, and R. Marchessault. A Precision Operation. Engineered Systems 23(7). July pp Moffitt, R. Taking the eat Out of Desiccants. PA 79(3). March pp Murphy, J. Temperature and umidity ontrol in Surgery Rooms. ASE Journal 48(6). June pp Murphy, J. and B. Bradley, Advances in Desiccant-Based Dehumidification, ADM-APN016- EN, Trane Engineers Newsletter.

Hospital Application Guide. Cost-effective climate control for hospitals

Hospital Application Guide. Cost-effective climate control for hospitals Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

Akton Psychrometric Chart Tutorial and Examples

Akton Psychrometric Chart Tutorial and Examples Akton Psychrometric Chart Tutorial and Examples December 1999 Akton Associates Inc. 3600 Clayton Road, Suite D Concord, California 94521 (925) 688-0333 http://www.aktonassoc.com Copyright 1999 Akton Associates

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)

More information

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1 Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio

More information

Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment

Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

Dedicated Outdoor Air Systems (D.O.A.S.)

Dedicated Outdoor Air Systems (D.O.A.S.) Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning

More information

Taking the Heat out of

Taking the Heat out of Taking the Heat out of Desiccants Enhancing the dehumidification capability of traditional vapor-compression equipment widely used in commercial applications The rising cost of natural gas, combined with

More information

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015 Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed

More information

HVAC and REFRIGERATION

HVAC and REFRIGERATION This is a preview. Some pages have been omitted. PE principles and practice prracticce of engineering mechanical: HVAC and REFRIGERATION sample questions + solutions Copyright 2011 by NCEES. All rights

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work? engineers volume 35 2 newsletter providing insights for today s hvac system designer keeping cool with outdoor air Airside Economizers from the editor For the denizens of commercial buildings, comfort

More information

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Moisture Control. It s The Dew Point. Stupid! Its not the humidity. Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR

More information

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture

More information

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS William K. Scullion, Application Engineering Leader, MEGTEC Systems, De Pere, WI Introduction Competitive pressures continuously motivate us to examine our

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University THE PSYCHROMETRIC CHART: Theory and Application Perry Peralta NC State University PSYCHROMETRIC CHART Identify parts of the chart Determine moist air properties Use chart to analyze processes involving

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air

More information

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools Heat Recovery Dehumidification (HRD) system Designed for municipal swimming pools A dehumidification and ventilation system with dynamic heat pump heat recovery to swimming pool water and air ENVIRONMENTAL

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory

More information

Wet Bulb Temperature and Its Impact on Building Performance

Wet Bulb Temperature and Its Impact on Building Performance Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?

More information

FAN COIL UNIT SOFTWARE User Manual

FAN COIL UNIT SOFTWARE User Manual User Manual Thanks for using Tiba fan coil units' selection software. To start the selection process to software selection there are some steps we need to follow: Front page: 1. Only selection 2. Performance

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels APPLICATION GUIDE Supercedes: Nothing Form 102.20-AG6 (305) INTRODUCTION As fossil fuel reserves are depleted, the cost of energy continues to rise. According

More information

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc. LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start

More information

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Dedicated Outdoor Air-Dual Wheel System Control Requirements

Dedicated Outdoor Air-Dual Wheel System Control Requirements 4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance

More information

Role of Economizers in Dedicated Outdoor Air Systems

Role of Economizers in Dedicated Outdoor Air Systems Introduction: Role of Economizers in Dedicated Outdoor Air Systems A question that frequently arises when a dedicated outdoor air system (DOAS) (Mumma, 2001) is discussed, particularly when the parallel

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Optimization of Water - Cooled Chiller Cooling Tower Combinations Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

Whole House Dehumidification for Occupant Comfort and Energy Savings

Whole House Dehumidification for Occupant Comfort and Energy Savings Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

Why Do I Need Precision Air Conditioning?

Why Do I Need Precision Air Conditioning? Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for

More information

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0. Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024

More information

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2 providing insights for today s hvac system designer Engineers Newsletter volume 42 2 Understanding Single-Zone VAV Systems Single-zone variable-air-volume (VAV) is not a new concept, but due to new energy

More information

THE U.S. ENVIRONMENTAL PROTECTION AGENCY S NATIONAL VEHICLE AND FUEL EMISSIONS LABORATORY, ANN ARBOR, MICHIGAN

THE U.S. ENVIRONMENTAL PROTECTION AGENCY S NATIONAL VEHICLE AND FUEL EMISSIONS LABORATORY, ANN ARBOR, MICHIGAN L ABORATORIES FOR THE 21ST C ENTURY: C ASE S TUDIES Case Study Index Laboratory Type Wet lab Dry lab Clean room Construction Type New Retrofit Type of Operation Research/development Manufacturing Teaching

More information

Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2

Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2 Humid Air Water vapor in air Oxygen 21% Trace Glasses 1% Argon (A) Water vapor (H 2 O) Carbon dioxide (CO 2 ) Neon (Ne) Helium (He) Krypton (Kr) Hydrogen (H) Ozone (O 3 ) Nitrogen 78% Humid Air Water vapor

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Application Potential of Solar-assisted Desiccant Cooling System in Sub-tropical Hong Kong

Application Potential of Solar-assisted Desiccant Cooling System in Sub-tropical Hong Kong Application Potential of Solar-assisted esiccant Cooling System in Sub-tropical ong Kong Kwong Fai Fong and Tin Tai Chow Building Energy and Environmental Technology esearch Unit, ivision of Building Science

More information

Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas

Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Mark Schiffhauer, ATSI Engineering Services Cameron Veitch, Combustion and Energy Systems Scott Larsen, New York State Energy

More information

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in

More information

for Plans Examiners and Building Inspectors

for Plans Examiners and Building Inspectors Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared

More information

Evaporative Cooling. Terminology. Date: February 28, 2012. Concepts

Evaporative Cooling. Terminology. Date: February 28, 2012. Concepts Evaporative Cooling Date: February 28, 2012 P R E S E N T E D B Y R O B E R T P A D G E T E 3 M S E N G I N E E R E D M E C H A N I C A L S Y S T E M S Concepts 1. Evaporation is a cooling process. Using

More information

THE PSYCHROMETRIC CHART AND ITS USE

THE PSYCHROMETRIC CHART AND ITS USE Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader

More information

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010 Air Water Vapor Mixtures: Psychrometrics Leon R. Glicksman c 1996, 2010 Introduction To establish proper comfort conditions within a building space, the designer must consider the air temperature and the

More information

Thermochemical Storage for Air-Conditioning using Open Cycle Liquid Desiccant Technology

Thermochemical Storage for Air-Conditioning using Open Cycle Liquid Desiccant Technology Thermochemical Storage for Air-Conditioning using Open Cycle Liquid Desiccant Technology E. Laevemann, M. Peltzer, A. Hublitz, A. Kroenauer, U. Raab, A. Hauer Bavarian Center for Applied Energy Research

More information

Printing and Publishing Energy Savings Guide

Printing and Publishing Energy Savings Guide Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand

More information

Active Chilled Beam System Design & Layout

Active Chilled Beam System Design & Layout Active Chilled Beam System Design & Layout Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle nsearle@dadanco.com Contents Active Chilled Beam Basics Design Considerations Air System Design &

More information

Desiccant Enhanced Evaporative Air-Conditioning (DEVap): Evaluation of a New Concept in Ultra Efficient Air Conditioning

Desiccant Enhanced Evaporative Air-Conditioning (DEVap): Evaluation of a New Concept in Ultra Efficient Air Conditioning Desiccant Enhanced Evaporative Air-Conditioning (DEVap): Evaluation of a New Concept in Ultra Efficient Air Conditioning Eric Kozubal, Jason Woods, Jay Burch, Aaron Boranian, and Tim Merrigan NREL is a

More information

Network Based Control of Fluid Distribution Systems

Network Based Control of Fluid Distribution Systems Network Based ontrol of Fluid Distribution Systems by homas Hartman, P.E. he Hartman ompany www.hartmanco.com ext of the presentation made to the International onference RENEWABLE AND ADVANED ENERGY SYSEMS

More information

Best Practices in HVAC Design/Retrofit

Best Practices in HVAC Design/Retrofit Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 jlewis@ucdavis.edu 1 What s the problem here?

More information

Principles of Rice Drying How does rice dry?

Principles of Rice Drying How does rice dry? Principles of Rice Drying James F. Thompson June 30, 1998 How does rice dry? Rice gains or loses moisture based on its moisture and the humidity of the air around it. If the humidity is low, high moisture

More information

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air 0 Optimal Air Quality: Critical to Hotels Provides comfortable environment for guests no overcooling Protects building, carpets

More information

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb

More information

GLOBACON 05 HVAC Systems for Cogen

GLOBACON 05 HVAC Systems for Cogen GLOBACON 05 HVAC Systems for Cogen Track 2, Session 2B Advanced HVAC and Building Systems Date: March 24th, 2005 Gearoid Foley President Integrated CHP Systems Corp. Integrated CHP Systems Corp. Electricity

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

Mechanical Systems Proposal revised

Mechanical Systems Proposal revised Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option

More information

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however

More information

How To Control Humidity With A Humidifier

How To Control Humidity With A Humidifier Control of ventilation and air conditioning plants Building Technologies s Contents.Temperature control in air treatment systems 2. Humidity controls 3. Recirculated air mixing. Internal heat sources 6.2

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is

More information

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010 White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence

More information

To provide good indoor air quality

To provide good indoor air quality Conditioning Ventilation Air for Improved Performance and Air Quality The practice of using a mixing chamber for mixing outdoor and return in a single system should be replaced by a technique with two

More information

Design Options for HVAC Distribution Systems

Design Options for HVAC Distribution Systems Design Options for HVAC Distribution Systems Course No: M06-017 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)

More information

Performance Test of Solar Assisted Solid Desiccant Dryer

Performance Test of Solar Assisted Solid Desiccant Dryer Performance Test of Solar Assisted Solid Desiccant Dryer S. MISHA 1,2,*, S. MAT 1, M. H. RUSLAN 1, K. SOPIAN 1, E. SALLEH 1, M. A. M. ROSLI 1 1 Solar Energy Research Institute, Universiti Kebangsaan Malaysia,

More information

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and

More information

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is

More information

Principals of Condensing Boiler System Design

Principals of Condensing Boiler System Design Principals of Condensing Boiler System Design Dennis Jones, P.E. Member ASHRAE ABSTRACT Condensing boilers can provide significant energy savings due to operating efficiencies as high as 98% as compared

More information

Building Performance With District Cooling

Building Performance With District Cooling Reprinting this proof for distribution or posting on web sites is not permitted. Authors may request permission to reprint or post on their web site once the fi nal version has been published. A reprint

More information

HEATING AND COOLING GENERATION AND DISTRIBUTION SYSTEMS

HEATING AND COOLING GENERATION AND DISTRIBUTION SYSTEMS HEATING AND COOLING GENERATION AND DISTRIBUTION SYSTEMS Central Vs Decentralized Systems Stephan Richter, Ph.D GEF Inginieur, Germany Scot Duncan Retrofit Originality Incorporated, USA Heating and cooling

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems

More information

Humidification Strategies for Data Centers and Network Rooms

Humidification Strategies for Data Centers and Network Rooms Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving

More information

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming

More information

STULZ Water-Side Economizer Solutions

STULZ Water-Side Economizer Solutions STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014

More information