SURGICAL SUITE TEMPERATURE AND HUMIDITY: PROVIDING WHAT SURGEONS WANT VERSUS THE LIMITATION OF YOUR EQUIPMENT
|
|
- Marcus Hensley
- 7 years ago
- Views:
Transcription
1 PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT Ronnie Moffitt PE, EM Principal Applications Engineer Trane Lexington, KY Paper Presented July 21, 2008 at the American Society for ealthcare Engineering 45 th Annual onference
2 Getting the Dew Point Temperature Required Do your surgeons want the operating room temperature and humidity controlled to a point that can not be achieved with your current system or infrastructure? There are multiple reasons why the current air handling system can not deliver the air required to meet the needs of the surgeons. The primary reason is the supply air dew point temperature that can be delivered by the air handling system. The difficulty of achieving the required dew point temperature is not regional. The extra cooling capacity required by most systems is minimal. There are multiple ways to solve the problem. Since there is more than one way to solve the problem, the question then becomes what is the infrastructure impact of each option? If it physically can be achieved, then what is the potential energy impact?
3 Past Designs Many past surgical room were designed around the AIA guideline. It recommends the operating room air temperature be 68-75F with a 30-60% relative humidity. To get this condition the air flow is dictated by a recommendation of 15 total air changes per hour, A, with 3 air changes per hour with respect to outside air. Out of this recommendation the typical room was designed for 15A with 20% outside air and design target conditions for the room of 68F 50%R. This temperature and relative humidity equates to a design room dew point temperature of 48.7F. With so many air changes per hour the supply air dew point temperature required was only slightly lower, 48F. This supply air dew point temperature could easily be achieved with a conventional water coil being supply with 42-44F chilled water from the hospital chiller plant. ooling air down the air to 48F leaving the coil would achieve the 48F dew point required to meet the humidity requirement. With the large amount of supply air (15 A), to maintain 68F temperature in the space, the supply air must be reheated to 56-59F at design conditions to prevent overcooling of the space.. Figure 1 Psychrometric Plot of Room and AU Supply onditions An operating room designed to the AIA guideline will require an approximate 48F leaving air temperature off the cooling coil.
4 urrent Designs Today there are often longer procedures, more gowning to wear, more people and equipment in proximity of the surgeon. For surgeon comfort, cooler temperatures are desired. There may also be procedures being performed that benefit from a lower room temperature; one for example is the use of cements or adhesives that are aided by cooler temperatures. ommon temperatures requested for the operating room by the surgeons have been lowered to 60-64F or even lower. The requirement is still in place to keep the room at a target of 50% R to reduce the risk of nosocomial infections. To keep the room at 50% relative humidity with the air temperature at 60-64F will require the air to be at a dew point temperature of 40- when delivered to the room. With the typical hospital having chilled water at 42-44F, this new requirement is impossible to achieve with what equipment is in place. A change in the VA system used needs to occur to make this desired target. Figure 2 Psychrometric Plot of Room and AU Supply onditions An operating room designed to the common desired conditions will require an approximate leaving air temperature off the cooling coil.
5 hange in VA Design The set point in the operating room is going dictate how dry and cold the air needs to be at the main air handler and cause changes required for the system. The air handling equipment will most likely be serving multiple procedural rooms, scrub rooms and other zones that support the surgical rooms. The example will focus on a single OR room to help the reader see what may be required to retrofit from a previous design around the AIA guideline, design A, versus going with typical new design conditions, design B. Example: Operating Room: 575ft^2 x 10ft high 14,400btu/hr Internal Sensible Load 1,600 btu/hr Internal Latent Load 135gr/lbm onditioning of Delivered: Supply Volume, Vsa = 15 A 5750 ft3 / 60 = 1,438 cfm Outside Volume, Voa = 0.20 x 1,44= 288 cfm Return Volume, Vra = Vsa Vra =1,150 cfm Supply ΔT = 14400/ (1.085*1438) = Δ9.2F Supply ΔW = 1,600/ (0.68 x 1438) = Δ1.6gr/lbm Design A Room onditions = 68F 50%R, 50.9gr/lbm Supply Temperature = 58.8F Supply umidity = 49.3gr/lbm Supply Dewpoint Temperature = 47.8F Design B Room onditions = 62F 50%R, 41.2 gr/lb Supply Temperature = 52.8F Supply umidity = 39.6gr/lbm Supply Dewpoint Temperature = 42.1F
6 ool Reheat System The starting point for Design A is a cool reheat system, the air at the central air handler is cooled to 48F to dehumidify than reheated to 58.8F. Redesigning the system to Design B and setting the room to 62F, will require the air handler to cool the air down to 40F and reheat it to 53F. This requires a 4% increase in cooling capacity and a 4% reduction in heating energy for each operating room. Though 4% more chilled water may be hard to obtain in many cases, this looks like a minor impact on the infrastructure. owever the dew point is below what is achievable with 42-44F chilled water from the chiller plant. This system will require an additional source of chilled water. The infrastructure changes include: adding a glycol chiller, a new AU with a second cooling coil and piping to a second cooling coil. The glycol chiller does not have to be sized for the entire design load. As much cooling as possible would still be accomplished by the central plant chilled water, with a new second coil fed by 36F chilled glycol to help achieve the leaving air conditions required. Though there is only a small increase in the cooling capacity required by the surgical suite. The energy use will be greater as now 35% or higher of the cooling is now accomplished by an air cooled glycol chiller versus the central plant chiller. Flow Process Diagram ool-reheat Return 1150cfm Outside 135 gr/lbm 68F 50%R 51 gr/lbm WS ooling oil Design A 48F 98%R 49 gr/lbm eating oil 56F 73%R 49 gr/lbm 180F WS Supply 1438cfm Supply Fan 58.8F 67%R 49 gr/lbm 48F DPT Figure 3 ool and Reheat Process for treating air for operating room for Design A onditions. What s Needed hilled water <180F ot Water ow Much per OR 55,700 btuh ooling 12,800 btuh eating Return 1150cfm Outside 135 gr/lbm Flow Process Diagram ool-reheat 62F 50%R 41 gr/lbm WS ooling oil Design B 50F 98%R 49 gr/lbm 36F WS ooling oil 42.5F 98%R 39 gr/lbm eating oil 50F 74%R 39 gr/lbm 180F WS Supply 1438cfm Supply Fan 52.8F 67%R 39 gr/lbm DPT Figure4 ool and Reheat Process for treating air for operating room for Design B onditions. What s Needed hilled Water 36F hilled Glycol <180F ot Water ow Much per OR 57,800 btuh ooling 37,000btuh coil1 20,800btuh coil2 12,000 btuh eating
7 Active Desiccant System Instead of using a glycol chiller to drop the dew point temperature past the chilled water temperature, this could be done by using an active desiccant dehumidifier. The most common system used for this application dehumidifies the outside air. The outside air is first pre-cooled by a new chilled water coil then dehumidified further by a heat activated desiccant. The heat activated desiccant rotor is typically regenerated by a direct fired gas heater or high pressure steam that heats a second path of outside air flow. The regeneration air is heated above 180F. This heated air heats the desiccant which changes the isotherm, and reduces the ability of the desiccant to adsorb water vapor. This heat regenerates the desiccant to enable it to adsorb more vapor as it rotates around to the cooled outside air. Versus the past design A this will require about 4% more heating energy and reduce the cooling needed by 5%. The heat required will now require an infrastructure change as natural gas piping and service is needed. Also piping for additional cooling coil, a secondary outside air intake and an additional exhaust air outlet, an an additional unit or adding a larger custom air handler which will have at least two fans. By separating the air streams the cooling accomplished by the chiller is slightly reduced. owever, some of the dehumidification work is moved to the desiccant dehumidifier which has a OP<1.0 vs a OP>3.0 for the chiller. The added heat energy will require more energy usage by the OR than the initial design A. Figure5 Preool Active Desiccant Process for treating air for operating room for Design B onditions. What s Needed hilled Water Natural Gas Service Exhaust Outlet Secondary Outdoor Inlet ow Much per OR 52,700 btuh ooling 23,500btuh coil1 29,200btuh coil2 13,200 btuh eating
8 ool-reheat System with Desiccant Wheel in Series The next system uses a desiccant wheel in series to lower the dew point temperature. owever, it does not require high heat or a separate regeneration air stream. It utilizes the recirculated air from the operating rooms to regenerate the wheel. This is possible because a different type of desiccant is utilized. Using recirculated air also removes the introduction of an additional air stream. The type III isotherm wheel has the ability to adsorb water vapor at high relative humidity conditions. This affinity for water vapor quickly drops off at a lower relative humidity. This allows for water vapor to be transferred with out adding regeneration heat. This system will allow for an AU with the same chilled water as in design A with still one coil, one fan and one air path achieve the conditions for Design B. The air is dehumidified and cooled by the cooling coil as in a cool reheat system. The air actually leaves the cooling coil at a temperature actually higher than design A. After the cooling coil additional water vapor is removed by the wheel and some heat is added from the adsorption process. The water vapor that is removed by the wheel is added to the mixed air flow on the other side of the wheel. This occurs because it is at a lower relative humidity. The water vapor transferred then takes a second pass at the cooling coil and is removed. The end result is a 19% reduction in cooling capacity required and an 86% reduction in heat required at new design condition versus the original design A. The infrastructure changes are limited to a new AU with a wheel. The operating rooms are taken from past 68F 50%R to the improved 62F 50%R, at the same time the heat and cooling required is reduced without changing the hospital infrastructure. Outside 135 gr/lbm Return 1150cfm Flow Process Diagram Series Desiccant Wheel 62F 50%R 41 gr/lbm 66F 63%R 60 gr/lbm Desiccant Wheel 62F 74%R 69 gr/lbm Figure6 ool and Reheat w/ Series Desiccant Wheel for treating air for operating room for Design B onditions. What s Needed hilled Water <180F ot Water Supply 1438cfm 52F 68%R 39 gr/lbm 48F 97%R 48 gr/lbm 65F 69 gr/lbm Supply Fan ow Much per OR 48,000 btuh ooling 1,500 btuh eating %R 39 gr/lbm DPT 180F WS eating oil WS ooling oil
9 Summary The more stringent conditions being expected by surgeons for operating rooms often drives the infrastructure requirements and increases the energy usage for the hospital. There are different ways to minimize the impact of these vital spaces. With new technologies, there are methods that improve dehumidification capability. It may be possible to increase the dehumidification performance of the system to meet new requirements without increasing the heating and cooling required from the facility. This might be to the extent that the cooling and heating needed can be reduced while at the same time improving the conditions in the surgical suite. References Greim,., D. Garrison, and R. Marchessault. A Precision Operation. Engineered Systems 23(7). July pp Moffitt, R. Taking the eat Out of Desiccants. PA 79(3). March pp Murphy, J. Temperature and umidity ontrol in Surgery Rooms. ASE Journal 48(6). June pp Murphy, J. and B. Bradley, Advances in Desiccant-Based Dehumidification, ADM- APN016-EN, Trane Engineers Newsletter.
10 PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT Ronnie Moffitt, PE EM Principal Applications Engineer, Trane 45 th Annual onference & Technical Exhibition PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT Session Outline: System Design Past Typical Operating Room Design urrent Typical Operating Room Design ool-reheat andling System Impact of hanging To urrent Room Design ool-reheat System Active Desiccant System ool-reheat Series Desiccant PAST OPETING ROOM DESIGN OR Room Design 68F 50% 90% 80% 70% Altitude 0ft 60% 50% 40% 30% 20% 10% umidity Ratio Grains/lbm Dry Bulb Temperature (F)
11 URRENT OPETING ROOM DESIGN OR Room Design 62F 50% 90% 80% 70% Altitude 0ft 60% 50% 40% 30% 20% 10% umidity Ratio Grains/lbm Dry Bulb Temperature (F) OOL REEAT DEUMIDIFIATION AND TEMPERING T space R EA T space R entral andling Unit hilled Water 42-44F Example: Design A 68F 50% Single Operating Room entral andling Unit T operating room R EA T space R hilled Water
12 Example: Design A 68F 50% Single Operating Room 1,150cfm entral andling Unit hilled Water T operating room R EA 5750ft 3 15A Total 3A Total Example: Design A 68F 50% Single Operating Room 1,150cfm entral andling Unit 58.8F hilled Water 49 gr/lbm 47.8F Dew Point T 68F R 50% 51 51gr/lbm EA Sensible Load 14,400btu/hr Latent Load 1,600btu/hr URRENT OPETING ROOM DESIGN 90% 80% 70% Altitude 0ft 60% 50% % LVG ool oil Lvg Reheat Supply Mixed Return Outside Dew Point Design Day 30% 20% 10% umidity Ratio Grains/lbm Dry Bulb Temperature (F)
13 Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 68F 51gr/lbm 48F 56F 98% 49gr/lbm 47.5F DPT WS entral andling Unit 180F WS 58.8F 67% 49gr/lbm 47.5F DPT Required for Operating Room ooling Plant 55,700btu/hr eating Plant 12,800btu/hr Example: Design B 62F 50% Single Operating Room 1,150cfm entral andling Unit 52.8F hilled Water 39 gr/lbm 42.0F Dew Point T 62F R 50% 41 41gr/lbm EA Sensible Load 14,400btu/hr Latent Load 1,600btu/hr Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 62F 41gr/lbm 42.5F 98% DPT WS entral andling Unit Required for Operating Room ooling Plant 57,800btu/hr eating Plant 12,000btu/hr 50F 180F WS 52.8F 67% DPT Infrastructure hanges Glycol hiller 2 nd ooling oil
14 Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 62F 41gr/lbm 50F 98% 52gr/lbm 42.5F 98% DPT WS 36F WS Required for Operating Room ooling Plant 37,000btu/hr New hiller 20,800btu/hr eating Plant 12,000btu/hr entral andling Unit 50F 180F WS 52.8F 67% DPT Infrastructure hanges Glycol hiller 2 nd ooling oil Active Desiccant Wheel eat-activated Desiccant Wheel EA RG 8-24 rph Process eat used to dehumidify 2,250 to 3,000 Btu/lbm water removed Active Desiccant Isotherms %Weight Water Type I Isotherms F 70F 90F 110F 130F Desiccant % 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% %R Regeneration 150F 170F 190F 210F Regeneration primary a function of temperature, hange in isotherm
15 Example: Design B 62F 50% Single Operating Room Pretreat Active Desiccant EA 55F 64gr/lbm 135gr/lbm WS 100cfm 205F 94F 34gr/lbm Natural Gas 1,150cfm 62F 41gr/lbm 50F 73% DPT WS 52.8F 67% DPT URRENT OPETING ROOM DESIGN 90% 80% 70% Altitude 0ft 60% 50% % LVG ool oil Outside Dew Point Design Day 30% 20% umidity Ratio Grains/lbm Return 10% Lvg ool oil 2 Supply Mixed Lvg Desiccant Wheel Dry Bulb Temperature (F) Example: Design B 62F 50% Single Operating Room Pretreat Active Desiccant EA 135gr/lbm WS 100cfm 205F 94F 34gr/lbm Natural Gas 1,150cfm 62F 41gr/lbm Required for Operating Room ooling Plant 52,700btu/hr eating Plant 13,200btu/hr 50F 73% DPT WS 52.8F 67% DPT Infrastructure hanges Natural Gas 2 nd ooling oil 2 nd Outside Inlet 2 nd Exhaust outlet 2 nd Unit or Tall AU
16 ool-reheat with Series Desiccant Wheel Type III Desiccant Wheel 50% R ΔW = +10 to 25gr 8-24 rph ΔW = -10 to 25gr 98% R ooling oil used for dehumidification Wheel enhances latent work done by coil Final Supply Dew Point Temperature << oil LVG Temp Type III Desiccant Isotherms Type III Series Desiccant Wheel 50% R ΔW = +10 to 25gr A T A T 8-24 rph ΔW = -10 to 25gr 98% R A Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 62F 41gr/lbm 66F 63% 60gr/lbm entral andling Unit 62F 74% 69gr/lbm 52.8F 67% 42.0F DPT 180F WS 52F 68% Required for Operating Room ooling Plant 48,000btu/hr eating Plant 1,500btu/hr 48F 97% 48gr/lbm WS
17 URRENT OPETING ROOM DESIGN 90% 80% 70% Altitude 0ft 60% 50% % LVG Regen Outside Dew Point Design Day 30% 20% umidity Ratio Grains/lbm LVG ool oil Supply Mixed Return 10% Dry Bulb Temperature (F) Example: Design B 62F 50% Single Operating Room ool Reheat AU 135gr/lbm 1,150cfm 62F 41gr/lbm 66F 63% 60gr/lbm entral andling Unit 62F 74% 69gr/lbm 52.8F 67% 42.0F DPT 52F 68% Required for Operating Room ooling Plant 48,000btu/hr eating Plant 1,500btu/hr 48F 97% 48gr/lbm WS Infrastructure hanges Taller AU ase Study Data: Extending Achievable Dew Point St. Vincent s ospital, Data was logged by University of entral Florida in collaboration with the Oak Ridge National Laboratory/ Department of Energy (Office of Distributed energy, within the Office of Energy Efficiency and Renewable Energy) for more information go to
18 ase Study Data: Extending Achievable Dew Point 5F or lower dew point temperatures with same chilled water Typical Mixed onditions for Surgical Suites Operating Room Example Going From Design A To B Going from 68F 50% to 62F 50% Potential Building System Impact Estimated hange in Required apacity Infrastructure AU Design ooling eating Equipment AU Piping ot entral entral New ooling hilled Water or Natural Total Plant Total Plant /eating Plants New AU Water Steam Gas New AU Ducting Inlet or Outlets No hange 1oil ooling with Reheat 4% -33% -4% -4% Glycol hiller Longer 2 oils No hange No hange Active Desiccant Taller New, New EA with ooling -5% -5% 4% -100% Gas Burner /Longer 2 oils None Burner ooling with Series No hange 1oil Desiccant -19% -19% -89% -89% No hange Taller None No hange No hange Operating Room Example Going From Design A To B Going from 68F 50% to 62F 50% Potential Energy Impact Estimated hange in Required apacity AU Design ooling Total Infrastructure eating Equipment entral entral New ooling Plant Plant /eating Plants Total Energy Impact ooling with Reheat 4% -33% -4% -4% Glycol hiller igher combined KW/TON Active Desiccant with ooling -5% -5% 4% -100% Gas Burner Desiccant Dehumidification vs Vapor ompression ooling with Series Desiccant -19% -19% -89% -89% No hange Less eat Energy, Less ooling Energy at same KW/Ton
19 Operating Room Example Going From Design A To B PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT onclusions: Impact of hanging To older Operating Room More infrastructure impact vs cooling capacity Lower dew point temperature can make the cooling required less efficient Series desiccant wheel can help achieve dew point temperatures required with out hurting cooling efficiency and lowering the capacity required PROVIDING WAT SURGEONS WANT VERSUS TE LIMITATION OF YOUR EQUIPMENT Thank - You?? Questions?? Additional References: Greim,., D. Garrison, and R. Marchessault. A Precision Operation. Engineered Systems 23(7). July pp Moffitt, R. Taking the eat Out of Desiccants. PA 79(3). March pp Murphy, J. Temperature and umidity ontrol in Surgery Rooms. ASE Journal 48(6). June pp Murphy, J. and B. Bradley, Advances in Desiccant-Based Dehumidification, ADM-APN016- EN, Trane Engineers Newsletter.
Hospital Application Guide. Cost-effective climate control for hospitals
Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing
More informationInnovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
More informationBy Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
More informationPreliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
More informationAkton Psychrometric Chart Tutorial and Examples
Akton Psychrometric Chart Tutorial and Examples December 1999 Akton Associates Inc. 3600 Clayton Road, Suite D Concord, California 94521 (925) 688-0333 http://www.aktonassoc.com Copyright 1999 Akton Associates
More informationDr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
More informationComparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
More information85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
More informationSelecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment
AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.
More informationAPPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
More informationDedicated Outdoor Air Systems (D.O.A.S.)
Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationTheoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning
More informationTaking the Heat out of
Taking the Heat out of Desiccants Enhancing the dehumidification capability of traditional vapor-compression equipment widely used in commercial applications The rising cost of natural gas, combined with
More informationControlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015
Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed
More informationHVAC and REFRIGERATION
This is a preview. Some pages have been omitted. PE principles and practice prracticce of engineering mechanical: HVAC and REFRIGERATION sample questions + solutions Copyright 2011 by NCEES. All rights
More informationPresentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
More informationnewsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?
engineers volume 35 2 newsletter providing insights for today s hvac system designer keeping cool with outdoor air Airside Economizers from the editor For the denizens of commercial buildings, comfort
More informationMoisture Control. It s The Dew Point. Stupid! Its not the humidity.
Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR
More informationBecause here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the
Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture
More informationHEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS
HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS William K. Scullion, Application Engineering Leader, MEGTEC Systems, De Pere, WI Introduction Competitive pressures continuously motivate us to examine our
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationTHE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University
THE PSYCHROMETRIC CHART: Theory and Application Perry Peralta NC State University PSYCHROMETRIC CHART Identify parts of the chart Determine moist air properties Use chart to analyze processes involving
More informationAdvanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
More informationAnalysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
More informationAPPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
More informationMeasuring The Right Thing For Humidity Control It s the Dew Point Stupid!
Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air
More informationHeat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools
Heat Recovery Dehumidification (HRD) system Designed for municipal swimming pools A dehumidification and ventilation system with dynamic heat pump heat recovery to swimming pool water and air ENVIRONMENTAL
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
More informationSPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
More informationRating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory
More informationWet Bulb Temperature and Its Impact on Building Performance
Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?
More informationFAN COIL UNIT SOFTWARE User Manual
User Manual Thanks for using Tiba fan coil units' selection software. To start the selection process to software selection there are some steps we need to follow: Front page: 1. Only selection 2. Performance
More informationInternational Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
More informationPool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
More informationImproving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
More informationBuilding Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
More informationGuidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
More informationAIR SYSTEMS ENERGY SERIES Energy Recovery Wheels
AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels APPLICATION GUIDE Supercedes: Nothing Form 102.20-AG6 (305) INTRODUCTION As fossil fuel reserves are depleted, the cost of energy continues to rise. According
More informationLIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start
More informationRittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationDedicated Outdoor Air-Dual Wheel System Control Requirements
4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance
More informationRole of Economizers in Dedicated Outdoor Air Systems
Introduction: Role of Economizers in Dedicated Outdoor Air Systems A question that frequently arises when a dedicated outdoor air system (DOAS) (Mumma, 2001) is discussed, particularly when the parallel
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationOptimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
More informationHVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
More informationTotal Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
More informationWhole House Dehumidification for Occupant Comfort and Energy Savings
Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009
More informationVenice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
More informationWhy Do I Need Precision Air Conditioning?
Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationHow and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for
More informationEnergy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.
Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024
More informationEngineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2
providing insights for today s hvac system designer Engineers Newsletter volume 42 2 Understanding Single-Zone VAV Systems Single-zone variable-air-volume (VAV) is not a new concept, but due to new energy
More informationTHE U.S. ENVIRONMENTAL PROTECTION AGENCY S NATIONAL VEHICLE AND FUEL EMISSIONS LABORATORY, ANN ARBOR, MICHIGAN
L ABORATORIES FOR THE 21ST C ENTURY: C ASE S TUDIES Case Study Index Laboratory Type Wet lab Dry lab Clean room Construction Type New Retrofit Type of Operation Research/development Manufacturing Teaching
More informationHumid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2
Humid Air Water vapor in air Oxygen 21% Trace Glasses 1% Argon (A) Water vapor (H 2 O) Carbon dioxide (CO 2 ) Neon (Ne) Helium (He) Krypton (Kr) Hydrogen (H) Ozone (O 3 ) Nitrogen 78% Humid Air Water vapor
More informationThe Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
More informationMaximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
More informationLesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
More informationApplication Potential of Solar-assisted Desiccant Cooling System in Sub-tropical Hong Kong
Application Potential of Solar-assisted esiccant Cooling System in Sub-tropical ong Kong Kwong Fai Fong and Tin Tai Chow Building Energy and Environmental Technology esearch Unit, ivision of Building Science
More informationIncreasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas
Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Mark Schiffhauer, ATSI Engineering Services Cameron Veitch, Combustion and Energy Systems Scott Larsen, New York State Energy
More information9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in
More informationfor Plans Examiners and Building Inspectors
Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared
More informationEvaporative Cooling. Terminology. Date: February 28, 2012. Concepts
Evaporative Cooling Date: February 28, 2012 P R E S E N T E D B Y R O B E R T P A D G E T E 3 M S E N G I N E E R E D M E C H A N I C A L S Y S T E M S Concepts 1. Evaporation is a cooling process. Using
More informationTHE PSYCHROMETRIC CHART AND ITS USE
Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader
More informationAir Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010
Air Water Vapor Mixtures: Psychrometrics Leon R. Glicksman c 1996, 2010 Introduction To establish proper comfort conditions within a building space, the designer must consider the air temperature and the
More informationThermochemical Storage for Air-Conditioning using Open Cycle Liquid Desiccant Technology
Thermochemical Storage for Air-Conditioning using Open Cycle Liquid Desiccant Technology E. Laevemann, M. Peltzer, A. Hublitz, A. Kroenauer, U. Raab, A. Hauer Bavarian Center for Applied Energy Research
More informationPrinting and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
More informationActive Chilled Beam System Design & Layout
Active Chilled Beam System Design & Layout Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle nsearle@dadanco.com Contents Active Chilled Beam Basics Design Considerations Air System Design &
More informationDesiccant Enhanced Evaporative Air-Conditioning (DEVap): Evaluation of a New Concept in Ultra Efficient Air Conditioning
Desiccant Enhanced Evaporative Air-Conditioning (DEVap): Evaluation of a New Concept in Ultra Efficient Air Conditioning Eric Kozubal, Jason Woods, Jay Burch, Aaron Boranian, and Tim Merrigan NREL is a
More informationNetwork Based Control of Fluid Distribution Systems
Network Based ontrol of Fluid Distribution Systems by homas Hartman, P.E. he Hartman ompany www.hartmanco.com ext of the presentation made to the International onference RENEWABLE AND ADVANED ENERGY SYSEMS
More informationBest Practices in HVAC Design/Retrofit
Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 jlewis@ucdavis.edu 1 What s the problem here?
More informationPrinciples of Rice Drying How does rice dry?
Principles of Rice Drying James F. Thompson June 30, 1998 How does rice dry? Rice gains or loses moisture based on its moisture and the humidity of the air around it. If the humidity is low, high moisture
More informationLIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air 0 Optimal Air Quality: Critical to Hotels Provides comfortable environment for guests no overcooling Protects building, carpets
More informationCauses of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
More informationGLOBACON 05 HVAC Systems for Cogen
GLOBACON 05 HVAC Systems for Cogen Track 2, Session 2B Advanced HVAC and Building Systems Date: March 24th, 2005 Gearoid Foley President Integrated CHP Systems Corp. Integrated CHP Systems Corp. Electricity
More informationDehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
More informationMechanical Systems Proposal revised
Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option
More informationData Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
More informationHow To Control Humidity With A Humidifier
Control of ventilation and air conditioning plants Building Technologies s Contents.Temperature control in air treatment systems 2. Humidity controls 3. Recirculated air mixing. Internal heat sources 6.2
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationTo provide good indoor air quality
Conditioning Ventilation Air for Improved Performance and Air Quality The practice of using a mixing chamber for mixing outdoor and return in a single system should be replaced by a technique with two
More informationDesign Options for HVAC Distribution Systems
Design Options for HVAC Distribution Systems Course No: M06-017 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)
More informationPerformance Test of Solar Assisted Solid Desiccant Dryer
Performance Test of Solar Assisted Solid Desiccant Dryer S. MISHA 1,2,*, S. MAT 1, M. H. RUSLAN 1, K. SOPIAN 1, E. SALLEH 1, M. A. M. ROSLI 1 1 Solar Energy Research Institute, Universiti Kebangsaan Malaysia,
More informationRittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy
Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and
More informationChilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
More informationPrincipals of Condensing Boiler System Design
Principals of Condensing Boiler System Design Dennis Jones, P.E. Member ASHRAE ABSTRACT Condensing boilers can provide significant energy savings due to operating efficiencies as high as 98% as compared
More informationBuilding Performance With District Cooling
Reprinting this proof for distribution or posting on web sites is not permitted. Authors may request permission to reprint or post on their web site once the fi nal version has been published. A reprint
More informationHEATING AND COOLING GENERATION AND DISTRIBUTION SYSTEMS
HEATING AND COOLING GENERATION AND DISTRIBUTION SYSTEMS Central Vs Decentralized Systems Stephan Richter, Ph.D GEF Inginieur, Germany Scot Duncan Retrofit Originality Incorporated, USA Heating and cooling
More informationCharacteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
More informationEconomizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
More informationAIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
More informationnewsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer
engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems
More informationHumidification Strategies for Data Centers and Network Rooms
Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving
More informationHVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
More informationSTULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
More information