RS 6/C/ Published January RATING STANDARD for the CERTIFICATION of LIQUID CHILLING PACKAGES

Size: px
Start display at page:

Download "RS 6/C/ Published January RATING STANDARD for the CERTIFICATION of LIQUID CHILLING PACKAGES"

Transcription

1 RATING STANDARD for the CERTIFICATION of LIQUID CHILLING PACKAGES

2 Supersedes RS/6C/ (Dec 2014) Editing (date): Arnaud LACOURT 26 March 2015 Checking (date): Jean FOURCROY 6 December 2015 Approval (date): Compliance Committee for LCP-HP 7 October 2015 Approval (date): CPPC 15 January 2016 Comes into effect from: 29 January 2016 Modifications as against last version: Nb Modifications Section Page 1 Updating of pressure drop definition III Modification of Eurovent Energy classes according CM ed.11 III Running test at TOL is removed IV Clarification of LRcontmin definition IV Standard Rating Conditions are updated according OM (New names of applications, and Low and Medium Temperature Process Chillers V Part Loads for SEER and Comfort chillers V Part Loads for SEPR and High Temperature Process chillers V Part Loads for SEPR and Medium Temperature Process chillers V Part Loads for SEPR and Low Temperature Process chillers V Modification of published data VI Updating of tolerances for Seasonal tests in Heating VII 18 This document is strictly reserved for use in the Certification Programmes of Eurovent Certita Certification. Reproduction or translation of any part of the document is forbidden without written permission from of Eurovent Certita Certification. Published by Eurovent Certita Certification S.A.S rue de la Victoire, Paris, France Tel: a.lacourt@eurovent-certification.com Published Janaury 2016 Page 2 of 24

3 TABLE OF CONTENTS I. PURPOSE 4 II. SCOPE 4 III. DEFINITIONS 4 III.1 General definitions... 4 III.2 Part Load, Load Rate, Cycling Coefficient, EER at part load condition and ESEER... 5 III.3 Energy Classification... 6 IV. TESTING REQUIREMENTS 7 IV.1 Cooling and heating capacity... 7 IV.2 Power consumption during off mode, thermostat off mode, standby mode and crankcase heater mode IV.3 Sound Power Level... 7 IV.4 Part Load Testing of Air Conditioning Chillers... 8 IV.5 LRcontmin and Ccp LRcontmin... 8 IV.6 Testing in Participant s Laboratory... 9 a. Introduction... 9 b. Basic outline of the procedure... 9 c. Detailed procedure... 9 V. RATING REQUIREMENTS 11 V.1 General requirements V.2 Treatment of frosting of heat exchangers V.3 Checking of refrigerant a. Composition of refrigerant b. Refrigerant charge V.4 Capacity Tests V.5 Part Load Rating Conditions for ESEER (cooling mode of air conditioning chillers) V.6 Part Load Rating Conditions for SEER (cooling mode for comfort chillers) V.7 Part Load Rating Conditions for SEPR (cooling mode high temperature process chillers) V.8 Part Load Rating Conditions for SEPR (cooling mode medium temperature process chillers) V.9 Part Load Rating Conditions for SEPR (cooling mode low temperature process chillers) 17 VI. CERTIFIED PERFORMANCES 17 VII. TOLERANCES 18 APPENDIX A. EXAMPLE OF ESEER CALCULATIONS 20 APPENDIX B. ESEER DECLARATION GUIDELINES 21 B.I. Certified characteristics B.II. Part load declaration Page 3 of 24

4 I. PURPOSE The purpose of this Rating Standard is to establish definitions and specifications for the operation of the certification programme for Liquid Chilling Packages and Hydronic Heat Pumps. II. SCOPE The scope of the programme is defined in the relevant Operational Manual OM-3. This standard describes the rating standards for cooling-only and reversible Liquid Chilling Packages or Heat-Pumps. Rating standards for heating-only Heat Pumps are given in RS 6/C/003A. III. DEFINITIONS III.1 General definitions Eurovent Certita Certification Certified Published Ratings: A statement of the assigned values of those performance characteristics (full in cooling and heating mode and part load in cooling mode) under stated rating conditions, by which a unit may be chosen to fit its application. These values apply to all units of nominal size and type produced by the same Participant. The term "published rating" includes those shown on the unit, published in specifications, advertising computer selection programmes and other literature controlled by the Company. If the Participant publishes non-certified ratings they shall be clearly indicated. Standard Ratings: A statement of performance characteristics based on tests performed at standard rating conditions as specified in this Rating Standard. Application Ratings: A statement of performance characteristics based on other than standard test conditions. Basic Model Groups (BMG): The basic models shall be defined by units which are essentially the same in terms of thermal performance and function and application. The same or comparable in terms of basic components, specifically fans, coils, compressors and motors. Single-phase and three-phase versions of one model belong to the same BMG. Liquid Chilling Package: A factory assembled unit of the self-contained type designed to cool liquid using a compressor, an evaporator and an integral condenser and appropriate controls. Hydronic Heat Pump: A factory assembled unit of the self-contained type designed to heat liquid using a compressor, an evaporator and an integral condenser and appropriate controls. Liquid Pressure Drop on Indoor side: Liquid internal pressure difference between outlet and inlet of unit on Indoor side (kpa). Liquid Pressure Drop on Outdoor side: Liquid internal pressure difference between outlet and inlet of unit on Outdoor side (kpa). Page 4 of 24

5 A-weighed Sound Power Level: Sound power level radiated by the air cooled chiller (Lw(A)) expressed in db(a) The following definitions are in accordance with EN :2013. Total Cooling Capacity: Heat given off from the heat transfer medium to the unit per unit time (kw). Effective Power Input: Average electrical power input of the unit within the defined interval of time (kw) obtained from: the power input for operation of the compressor(s) and any power input for defrosting the power input of all control and safety devices of the unit proportional power input of the conveying devices (e.g. fans, pumps) for ensuring the transport of the heat transfer media inside the unit Heating Capacity: Heat given off by the unit to the heat transfer medium per unit of time (kw). Energy Efficiency Ratio (EER): Ratio of the total cooling capacity to the effective power input of the unit (-). Coefficient of Performance (COP): Ratio of the heating capacity to the effective power input of the unit (-). Power input in stand-by mode Psb: as defined in EN 14825:2013. LRcontmin: Load rate under which a unit with a variable speed compressor behaves as an ON/OFF unit. For staged capacity units it is the load rate of the smallest capacity step in full mode. For ON/OFF units LRcontmin equals 1. CcpLRcontmin: Ratio of the COP (or EER) at LRcontmin and the COP (or EER) at full load. III.2 Part Load, Load Rate, Cycling Coefficient, EER at part load condition and ESEER Part Load: Operation at partial capacity. Load Rate: Ratio of the cooling capacity at partial capacity and reduced condenser inlet water or air temperature to the cooling capacity at the part-load rating conditions (part-load rating conditions as defined in Table 6): %Part Load* Pc FullLoad LR (eq. 1) Pc%Part LoadConditions Cycling coefficient: The cycling coefficient is defined by: Cc MSP 1 Pe(c) (eq. 2) Where: MSP is Measured Sleep Power, Pe(c) is effective power input of the cycling stage for given source temperatures. A default value of 0.9 will be used for the cycling coefficient for all chillers. Page 5 of 24

6 EER at part load condition: When to reach a certain part load capacity (25%, 50% or 75%), cycling is Pc %Part LoadConditions necessary on the last stage, meaning that LR<1 or > Pc FullLoad % Part Load, then EER at part load condition is defined by: Pc LR EER %Part Load x (eq. 3) Pe(c) Cc x LR 1 Cc % Part Load Conditions It is automatically calculated by the Technical Datasheet. When to reach a certain part load capacity (25%, 50% or 75%) the unit has to cycle between two stages, i.e. Pc Stagen-1 Pc Stagen % Part Load, EER at part load condition is a Pc FullLoad Pc FullLoad Pc % Stagen-1 Pc Stagen combination between and automatically calculated by the Pc FullLoad Pc FullLoad Technical Datasheet. ESEER (only for the cooling mode of air conditioning chillers): The European Seasonal Energy Efficiency Ratio is a weighted formula enabling to take into account the variation of EER with the load rate and the variation of air or water inlet condenser temperature. ESEER = A.EER100% + B.EER75% + C.EER50% + D.EER25% (eq. 4) Table 1: Weighting coefficients A to D for calculation of ESEER Load Rate (%) Weighting coefficients A = 0.03 B = 0.33 C = 0.41 D = 0.23 It is automatically calculated by the Technical Datasheet. III.3 Energy Classification Classification concerns EER and COP at full load operation as defined in section III.1. The energy efficiency of chillers is designated by Eurovent Certita Certification Class in catalogues and in the present ECP Website of Certified products. The following limits between classes have been defined (see Table 2).Table 2: Eurovent Certita Certification energy classification for chillers Cooling Mode Air-cooled Air-cooled, Air-cooled Water-cooled Water-cooled EER ducted Floor Class LCP/A/../../N/... LCP/A/../../D/ LCP/A/../../N/.. LCP/W/../../N/.. LCP/W/../../N/.. AC AC CHF AC CHF A 2.9 EER< EER< EER< EER< EER<5.1 B 2.7 EER< EER< EER< EER< EER<4.9 C 2.5 EER< EER< EER< EER< EER<4.7 D EER<2.5 EER<2.1 EER<3.35 EER<3.85 EER<4.5 E Page 6 of 24

7 Heating Mode Air-cooled Air-cooled, Air-cooled Water-cooled Water-cooled COP ducted Floor Class LCP/A/R/../N/.. LCP/A/R/../D/ LCP/A/R/../N/.. LCP/A/R/../N/.. LCP/A/R/../N/.. AC AC CHF AC CHF A 3.0 COP< COP< COP< COP< COP<4.5 B 2.8 COP< COP< COP< COP< COP<4.25 C 2.6 COP< COP< COP< COP< COP<4 D COP<2.6 COP<2.4 COP<3.6 COP<3.55 COP<3.75 E Note: For air source units, COP classes are defined for COP at +7 C and not +2 C. IV. TESTING REQUIREMENTS All standard ratings shall be verified by tests conducted by an approved independent laboratory in accordance with the following standards, and shall be established at the Standard Rating Conditions specified in Section V. IV.1 Cooling and heating capacity Test method: EN :2013 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling- Part 3: Test methods. Test conditions: EN 14825:2013 Air conditioners, liquid chilling packages and heat pumps, with electrically driven compressors, for space heating and cooling. Testing and rating at part load conditions and calculation of seasonal performance. IV.2 Power consumption during off mode, thermostat off mode, standby mode and crankcase heater mode. EN 14825:2013 "Air conditioners, liquid chilling packages and heat pumps, with electrically driven compressors, for space heating and cooling. Testing and rating at part-load conditions and calculation of seasonal performance. IV.3 Sound Power Level Standard EN 12102:2013 shall be used in conjunction with: ISO 9614:2009 by sound intensity method (Part 1: Measurement by discrete points) ISO 3744:2012 (if ISO 9614 is no applicable) by free field method or: ISO 3741:2012, Precision methods for reverberation test rooms For sound testing the following conditions shall be used: Test at full load in cooling mode for the AC application With the pump running All fans running at nominal speed Page 7 of 24

8 For ducted air cooled units the same airflow and ESP shall be kept as in cooling mode Inlet air temperature at the condenser between 30 C and 35 C for units with cooling capacity below 100 kw 1 Inlet air temperature at the condenser between 20 C and 35 C for units with cooling capacity above 100 kw For non-ducted air-cooled units, the sound power to be tested is the sound power radiated outdoor side For ducted air-cooled chillers the sound power to be tested is the discharge sound power level Case of reversible chillers: For air-cooled units with Pdesignh below 70 kw, the sound testing can be carried out also always Standard conditions (EN 14511) but in heating mode (Air Temperature = +7 C) with a water temperature in accordance with Regulations: +35 C or +55 C For water-cooled units, the sound testing can be carried out, as an option, at Standard conditions (EN 14511) in heating mode with a water temperature in accordance with Regulations: +35 C or +55 C IV.4 Part Load Testing of Air Conditioning Chillers For air conditioning chillers, part load testing is done as indicated by the Participant to Eurovent Certita Certification in the Technical Datasheet. The testing methodology provided by the Participant by filling the Technical Datasheet shall ensure the stable operation of the compression circuit (frequency for inverter driven compressors, slide valve position for slide valve screw chillers, and sequence of activated compressors for capacity staged chillers). For air cooled chillers, the condenser fan(s) should be operated by the control of the chiller. Whenever cycling of the condenser fan(s) occurs, the test should be done as follows: An acquisition time period of 1 hour is required. Tolerance on leaving water temperature can exceed the maximum permissible deviation. If cycles exceed 1 minute, an entire number of periods shall be acquired. IV.5 LRcontmin and CcpLRcontmin A test shall be performed at LRcontmin under standard condition 7/12 in cooling mode (AC application) or 30/35 in heating mode (CHF application). If the miniumum water flow rate of the unit doesn t allow to reach the required ΔT (7/12 C), the test has to be done, exemple for the cooling mode, at 7 C as leaving water temperature and the minimum flow is declared by the manufacturer. 1 See minutes of meeting held on 15/01/2008. Page 8 of 24

9 IV.6 Testing in Participant s Laboratory a. Introduction All units with cooling capacity at Eurovent Certita Certification Standard Rating Conditions below the limits defined in the relevant Operational Manual shall be tested in an independent laboratory approved and under contract with Eurovent Certita Certification. The choice of the independent laboratory is made by Eurovent Certita Certification. Units with higher capacity shall be tested either in an independent laboratory or in a Participant laboratory (approved by Eurovent Certita Certification) by an independent agency (selected by Eurovent Certita Certification) following the procedures specified in the Rating Standard. The test agency is requested to install its own instruments and to carry out complete test under its own responsibility. The Participant s personnel are requested to help during the preparation and to operate the test installation during the measurement. The Participant may perform its own measurement in parallel, but only results obtained by the independent test agency are considered by Eurovent Certita Certification. b. Basic outline of the procedure The following procedure shall be applied: Approval of independent test agencies by Eurovent Certita Certification (based on technical capabilities and cost) Approval of Participant s laboratory by the independent agency selected by Eurovent Certita Certification (based on characteristics of test installation) Selection of unit to be tested by Eurovent Certita Certification Selection of test agency by Eurovent Certita Certification (based on availability, cost or other considerations) The Participant provides the selected test agency with all the required information concerning test installation The test agency notifies the Participant of its requirements to prepare adjustments for installation of measuring probes and instruments On the agreed date of test, the test agency installs its own instruments and performs the test; the Participant s personnel assures the correct operation of the installation Test report prepared by the test agency is sent to Eurovent Certita Certification c. Detailed procedure 1. Approval of Independent Test Agencies The Independent Test Agency shall have qualified personnel and adequate instruments in order to meet the requirements concerning maximum acceptable uncertainty of measurement as specified in EN 14511:2013. The cooling and heating capacity at full load shall be determined within a maximum tolerance of 5% independent of the individual uncertainties of measurement, including the uncertainties on the properties of fluids. Page 9 of 24

10 Concerning the acquisition time period for the output measurement, it is necessary to record all the meaningful data continuously; in the case of recording instruments which operate on a cyclic basis, the sequence shall be adjusted such that a complete recording is effected at least once every 10 s. The test agency shall have at least the following equipment: Water flow rate (uncertainty + 1%): Electromagnetic flow meter class 0.3 or Ultrasonic flow meter (only intrusion) Temperatures (uncertainty: Liquid K, Air K): 12 PT 100 probes with display giving 0.01 C resolution Pressure drop (uncertainty + 5%): 2 differential transducers up to 1 bar with display (class 0.5) Electrical measurements (uncertainty + 1%): Wattmeter (class 0.5) or Network analyser Refrigerant pressure (uncertainty + 1%): Manometer (class 0.5) or Pressure transducers with display (class 0.5) Data acquisition system 2. Approval of Participant Laboratory The Participant shall send an application form to Eurovent Certita Certification. Essential characteristics of test installation shall be indicated. The test installation shall be able to satisfy the requirement of the EN 14511:2013 Standard concerning the maximum permissible deviations of measured values from set values. The test installation shall be designed in such a way that requirement from test agencies concerning installation of measuring probes and instruments be satisfied. That concerns in particular the installation of a water flow meter for which the diameter and length of the connecting pipe are specified. In order to obtain a homogeneous water temperature, a mixing device shall be used on the leaving water. In case the test agency determines that the Participant laboratory does not fulfil the required specifications, the test shall not be carried out. The Participant shall then send his unit to the Independent Laboratory for testing. 3. Organisation of test When the unit to be tested and the test agency have been selected by Eurovent Certita Certification, the direct contact between test agency and Participant shall be established. The test agency shall provide detailed request for preparation to be executed by Participants: Connection of water flow meter Adaptor for temperature probes Adaptor for pressure transducer This preparation shall be carried out before the day of the test. The test agency and Participant shall agree on the date of test. The test agency personnel shall inspect the test installation and connect measuring devices. The test is then performed under full responsibility of the test agency. Eurovent Certita Certification shall receive the test report prepared by the test agency. Page 10 of 24

11 V. RATING REQUIREMENTS V.1 General requirements Tests with brine shall be carried out with the brine composition as specified in the table below. Table 3: Brine composition Medium Brine Low Brine Applications concerned MB, AC-MB, CHF-MB, LB HT-MB, VHT-MB Brine type Ethylene Glycol Brine composition 30% (weight) 50% (weight) All tests shall be carried out with clean heat exchangers and that shall be specified in catalogues with published ratings. For ducted air-cooled chillers tests for capacity shall be carried out at the air flow rate specified as nominal in the published ratings. A unit is considered as ducted if the measured ESP at the declared nominal airflow is higher than 30 Pa. V.2 Treatment of frosting of heat exchangers The treatment of frosting shall be done according to EN 14511:2013. V.3 Checking of refrigerant a. Composition of refrigerant For 10% of the total number of tests in a test campaign, randomly chosen by Eurovent Certita Certification, a sample of refrigerant is taken just after the end of the test for composition checking. 2 b. Refrigerant charge The lack of refrigerant is the main reason for failure on cooling capacity. A Participant can choose to send units already equipped with Pressure / Temperature gauges (one for suction, one for liquid, one for discharge). In that case, checking the values by simple reading is part of the unit installation instructions. 3 As an option, a Participant can request that the laboratory provide information on suction and discharge pressures and sub-cooling and superheating temperatures. That may help Participants to explain the failure. If the laboratory detects a leak of refrigerant, the test shall be stopped and the leak repaired. If the Participant requests to check the refrigerant charge before the test, it can be done and the extra cost will be invoiced accordingly. In this case, the laboratory cannot be held responsible in case of failure due to lack of refrigerant. 2 See minutes of meeting held on 25/04/ See minutes of meeting held on 10/03/2008 Page 11 of 24

12 V.4 Capacity Tests For capacity tests the following Standard Rating Conditions Table 4 and Table 5 shall be used: Table 4: Standard rating conditions for capacity tests in cooling mode Cooling Floor Air Conditioning Medium Brine Low Brine Code Evap Cond LCP/A.. /CHF 23 / a LCP/W.. /CHF Water/Water LCP/W.. /CHF-MB Water/Water 23 / / 35 LCP/A.. /AC 12 / LCP/W.. /AC Water/Water LCP/W.. /AC-MB Water/Water 12 / 7 30 / 35 LCP/A.. /MB -2 / a LCP/W.. /MB Brine/Water -2 / / 35 LCP/A.. /LB -19 / a LCP/W.. /LB Brine/Water -19 / / 35 Table 5: Standard rating conditions for capacity tests in heating mode Low Temperature (previously Heating Floor) Intermediate Temperature (previously Air Conditioning) Medium Temperature (previously High Temperature) High Temperature (previously Very High Temperature) Code Evap Cond LCP/A.. /CHF 7 (6) 30 / 35 LCP/W.. /CHF Water/Water LCP/W.. /CHF-MB Brine/Water 10 / 7 30 / 35 0 / / 35 LCP/A.. /AC 7 (6) 40 / 45 LCP/W.. /AC Water/Water LCP/W.. /AC-MB Brine/Water 10 / 7 40 / 45 0 / / 45 LCP/A.. /HT 7 (6) 47 / 55 LCP/W.. /HT Water/Water LCP/W.. /HT-MB Brine/Water 10 / 7 47 / 55 0 / / 55 LCP/A.. /VHT 7 (6) 55 / 65 LCP/W.. /VHT Water/Water LCP/W.. /VHT-MB Brine/Water 10 / 7 55 / 65 0 / / 65 4 Dry bulb Page 12 of 24

13 V.5 Part Load Rating Conditions for ESEER (cooling mode of air conditioning chillers) For Part load tests the following Standard Rating Conditions (Table 6) shall be used: Table 6: Part load rating conditions % Part Load 100 % 75 % 50 % 25 % Air-cooled chillers Water-cooled chillers Air temperature at condenser inlet ( C) Water temperature at condenser inlet ( C) The following rating conditions are required: For air-cooled chillers The leaving water temperature is set at 7 C (Air conditioning application) The evaporator water-flow rate is equal to the standard rating water-flow rate The air-flow rate is controlled by the chiller For water-cooled chillers The leaving water temperature is set at 7 C (Air conditioning application) The evaporator water-flow rates are equal to the standard rating water-flow rates The condenser water flow rate is controlled by the chiller. If the chiller doesn t control it, the condenser water flow rate will be equal to the standard rating water flow rate Page 13 of 24

14 V.6 Part Load Rating Conditions for SEER (cooling mode for comfort chillers) For each application, units either allowing or not allowing a variation of the outlet water temperature with the outdoor temperature are considered. The part load conditions for determining the declared capacity and the declared energy efficiency ratio are given in the following table. The variable outlet temperature (Toutlet_average) shall only be applied when the control provides an outdoor air temperature dependant modification of the outlet temperature. Table 7: Part load rating conditions for Air-cooled units Part Load ratio Outdoor heat exchanger Indoor heat exchanger Conditions Inlet/outler water Air dry bulb temperature temperature % Variable C Fixed outlet outlet A / 7 12 / 7 B a / 7 a / 8,5 C a / 7 a / 10 D a / 7 a / 11,5 a With the water flow rate as determined during A test for units with a fixed water flow rate or with a fixed delta T of 5 K for units with a variable water flow rate. If the resulting flow rate is below the minimum flow rate then this minimum flow rate is used with the outlet temperature. Table 8: Part load rating conditions for Water-cooled units Part Load ratio Outdoor heat exchanger Indoor heat exchanger Inlet/outler water Conditions Inlet/outlet temperature water Variable % temperatures Fixed outlet outlet A / / 7 12 / 7 B / a a / 7 a / 8,5 C / a a / 7 a / 10 D / a a / 7 a / 11,5 a With the water flow rate as determined during A test for units with a fixed water flow rate or with a fixed delta T of 5 K for units with a variable water flow rate. If the resulting flow rate is below the minimum flow rate then this minimum flow rate is used with the outlet temperature. Page 14 of 24

15 V.7 Part Load Rating Conditions for SEPR (cooling mode high temperature process chillers) The part load conditions for determining the declared capacity and the declared energy efficiency ratio are given in the following table. Table 9: Part load rating conditions for Air-cooled units Part Load ratio Outdoor heat exchanger Indoor heat exchanger Conditions Inlet/outler water Air dry bulb temperature temperature % Variable C Fixed outlet outlet A / 7 12 / 7 B a / 7 a / 8,5 C a / 7 a / 10 D 80 5 a / 7 a / 11,5 a With the water flow rate as determined during A test for units with a fixed water flow rate or with a fixed delta T of 5 K for units with a variable water. If the resulting flow rate is below the minimum flow rate then this minimum flow rate is used with the outlet temperature. Table 10: Part load rating conditions for Water-cooled units Part Load ratio Outdoor heat exchanger Indoor heat exchanger Inlet/outler water Conditions Inlet/outlet temperature water Variable % temperatures Fixed outlet outlet A / / 7 12 / 7 B / a a / 7 a / 8,5 C / a a / 7 a / 10 D 80 9 / a a / 7 a / 11,5 a With the water flow rate as determined during A test for units with a fixed water flow rate or with a fixed delta T of 5 K for units with a variable water. If the resulting flow rate is below the minimum flow rate then this minimum flow rate is used with the outlet temperature. Page 15 of 24

16 V.8 Part Load Rating Conditions for SEPR (cooling mode medium temperature process chillers) The part load conditions for determining the declared capacity and the declared energy efficiency ratio are given in the following table. Table 11: Part load rating conditions for Air-cooled units Conditions Part Load ratio % Outdoor heat exchanger Air dry bulb temperature C Indoor heat exchanger Inlet/outler water temperature Fixed outlet A / -8 B a / -8 C a / -8 D 80 5 a / -8 a With the water flow rate as determined during A test for units with a fixed water flow rate or with a fixed delta T of 6 K for units with a variable water. If the resulting flow rate is below the minimum flow rate then this minimum flow rate is used with the outlet temperature. Table 12: Part load rating conditions for Water-cooled units Part Outdoor heat Load exchanger Indoor heat exchanger Conditions ratio % Inlet/outlet water temperatures Inlet/outler water temperature Fixed outlet A / 35-2 / -8 B / a a / -8 C / a a / -8 D 80 9 / a a / -8 a With the water flow rate as determined during A test for units with a fixed water flow rate or with a fixed delta T of 6 K for units with a variable water. If the resulting flow rate is below the minimum flow rate then this minimum flow rate is used with the outlet temperature. Page 16 of 24

17 V.9 Part Load Rating Conditions for SEPR (cooling mode low temperature process chillers) The part load conditions for determining the declared capacity and the declared energy efficiency ratio are given in the following table. Table 13: Part load rating conditions for Air-cooled units Conditions Part Load ratio % Outdoor heat exchanger Air dry bulb temperature C Indoor heat exchanger Inlet/outler water temperature Fixed outlet A / -25 B a / -25 C a / -25 D 80 5 a / -25 a With the water flow rate as determined during A test for units with a fixed water flow rate or with a fixed delta T of 6 K for units with a variable water. If the resulting flow rate is below the minimum flow rate then this minimum flow rate is used with the outlet temperature. Table 14: Part load rating conditions for Water-cooled units Part Outdoor heat Load exchanger Indoor heat exchanger Conditions ratio % Inlet/outlet water temperatures Inlet/outler water temperature Fixed outlet A / / -25 B / a a / -25 C / a a / -25 D 80 9 / a a / -25 a With the water flow rate as determined during A test for units with a fixed water flow rate or with a fixed delta T of 6 K for units with a variable water. If the resulting flow rate is below the minimum flow rate then this minimum flow rate is used with the outlet temperature. VI. CERTIFIED PERFORMANCES The following performances at standard conditions shall be certified: Cooling capacity [kw] Energy efficiency Ratio (EER) [-] European Seasonal Energy Efficiency Ratio (ESEER) for air-conditioning application [-] until 31/12/2017 Water pressure drop at Indoor side [kpa] Water pressure drop at at Outdoor side for water-to-water units [kpa] Heating capacity for reverse cycle units [kw] Page 17 of 24

18 Coefficient of Performance (COP) for reverse cycle units [-] A-weighted sound power level for Air Cooled Units in cooling mode [db(a)] All ratings refer to a fouling factor equal to zero. Psb, LRcontmin and CcpLRcontmin in cooling and heating For relevant units (see OM II.4.b) Capacity at Pdesignh [kw] Seasonal Efficiency in heating (SCOP & ηs) [-] A-weighted sound power level for Air Cooled Units in heating mode [db(a)] A-weighted sound power level for Water Cooled Units in heating mode [db(a)] (Option) From 1 st July 2016 for Low Temperature and Medium Temperature Process Chillers: Cooling Capacity [kw] Seasonal Efficiency SEPR [-] From 1 st January 2018: Capacity at Pdesignc [kw] Seasonal Efficiency in cooling (SEER and/or SEPR) [-] Primary Seasonal Efficiency in cooling (ηs,c) [-] The published literature or computer programme for all the products shall include all the certified performances. VII. TOLERANCES When tested by the laboratory selected by Eurovent Certita Certification, the performances obtained shall not differ from the claimed values by more than the tolerance (see Table 7). High deviation lead to penalty tests (see IV.4 Failure treatment in the relevant Operational Manual). Page 18 of 24

19 Table 7: Table of tolerances, intermediate and high deviations Tolerance Intermediate High deviation Standard Point (EN 14511) Cooling or heating capacity, EER or COP, < -5% < -8% < -10% EER on part load point if only one or two points are tested (%) < -(2+3/%Part Load) ESEER < -(3+4.5/%Part Load) < -(4+6/%Part Load) Part Load 75% <-6% <-9% <-12% Part Load 50% <-8% <-12% <-16% Part Load 25% <-14% <-21% <-28% ESEER if all points have been tested <-9% <-13% <-17% Sound A-weighted sound power level rounded to the closest integer value (*) in heating mode for units 70 kw. > +3 db(a) > + 2 db(a)* > +5 db(a) > +7 db(a) Other Water pressure drop LRcontmin CcpLRcontmin > + 15% +/- 5% (point) < - 5% (point) Auxiliaries P off > +10% P sb > +10% Pto > +10% P ck > +10% SCOP COP on part load < -(3+4.5/%Part < -(4+6/%Part < -(2+3/%Part Load) point Load) Load) Part Load A / Tbiv <-5.4% <-8% <-11% Part Load B <-7.6% <-11% <-15% Part Load C <-10.6% <-16% <-21% Part Load D <-22% <-33% <-44% Page 19 of 24

20 APPENDIX A. EXAMPLE OF ESEER CALCULATIONS Figure 1: ESEER calculations, example of Load Rate and EER at part load condition Capacity stage number: 3 Temperatures [ C] FULL LOAD Stage 2 Stage 3 Cycling coefficient Pc 100 Pe(c) 50 Weighting coefficients 26 Pc % - 50 % - 75 % % Pe(c) Pc Pe(c) Pc 33 ESEER: 1.87 Pe(c) 22 Compute ESEER Part load 100% 75% 50% 25% EER PartLoad %Part Load* Pc FullLoad LR (eq. 1) Pc%Part LoadConditions In this example, according to eq. 1, LR (25%) = 0.25 x 100 / 33, LR (50%) = 0.5 x 100 / 100 and LR (75%) = 0.75 x 100 / 100. When cycling is necessary, EER %Part Load Pc LR x (eq. 3) Pe(c) Cc x LR 1 Cc In this example, since 33/100>0.25, %Part LoadConditions 0.25x EER 33 25% x x ESEER = A.EER100% + B.EER75% + C.EER50% + D.EER25% (eq. 4) In this example, ESEER = 0.03 x 100 / x x x 1.45 Page 20 of 24

21 APPENDIX B. ESEER DECLARATION GUIDELINES B.I. Certified characteristics Only the European Seasonal Energy Efficiency Ratio (ESEER) will be published on the of Eurovent Certified Performance website. The declaration of part load data is mandatory for the selected units for test. If the Participant is unable to declare part load, Eurovent Certita Certification will ask the laboratory to test the unit for each load rate. B.II. Part load declaration For the unit selected for testing, Participants have to fill in the declaration form sent by Eurovent Certita Certification as follows: Participants have to give the number of stages. According to the number of stages of the selected chiller, the table corresponding to the number of stages is built automatically in the Excel sheet. Participants have to declare the cooling capacity (Pc) and the power input (Pe(c)) for the points necessary to calculate the ESEER. The proposed format and absolute cell position of the table have to be strictly respected. Participants have to press the button Compute ESEER, the macro associated to ESEER calculation will run as follows: Calculate and display ESEER Show the intermediary points that have been calculated at 25, 50 and 75% load in order to use the weighting coefficients derived for ESEER. ************** Figure 2: Example of a Scroll chiller, 1 compressor, part load control: ON/OFF Capacity stage number: 1 Temperatures [ C] FULL LOAD Cycling coefficient Pc 10 Pe(c) 2.5 Weighting coefficients 26 Pc % - 50 % - 75 % % Pe(c) Pc 10.8 Pe(c) 2 18 Pc 11.2 ESEER: 4.61 Pe(c) 1.9 Compute ESEER Part load 100% 75% 50% 25% EER PartLoad Load Rate EER Full Load In Figure 2: a) Load Rate is calculated for each temperature using Load Rate definition (eq. 1, given in gray). EERFull Load is calculated for each Temperature as the ratio between Pc and Pe(c). b) EERPart Load is calculated for each Temperature directly using the cycling formula (eq. 3) c) ESEER is calculated using the ESEER definition (eq. 4). ************** Page 21 of 24

22 Figure 3: Example of a Scroll chiller, 1 circuit, 2 compressors of the same size Capacity stage number: 2 Temperatures [ C] FULL LOAD Stage 2 Cycling coefficient Pc 50 Pe(c) 12.5 Weighting coefficients 26 Pc % - 50 % - 75 % % Pe(c) Pc 28.1 Pe(c) Pc 29.1 ESEER: 5.49 Pe(c) 4.4 Compute ESEER Part load 100% 75% 50% 25% EER PartLoad In Figure 3: a. The full load cooling capacity is 50 kw. b. The capacity at 75% is 0.75x50=37.5 kw. To obtain this capacity at 26 C, the chiller has to cycle on stage 1 and stage 2. c. The capacity at 50% is 0.5x50=25 kw. To obtain this capacity at 22 C the chiller has to cycle on stage 2. d. The capacity at 25% is 12.5 kw. To obtain this capacity at 18 C the chiller has to cycle on stage 2. ************** Figure 4: Example of a Scroll chiller, 1 circuit, 2 compressors of different sizes (33 % / 66 %) Capacity stage number: 3 Temperatures [ C] FULL LOAD Stage 2 Stage 3 Cycling coefficient Pc 100 Pe(c) 25 Weighting coefficients 26 Pc % - 50 % - 75 % % Pe(c) Pc Pe(c) Pc 39.2 ESEER: 5.96 Pe(c) 5.3 Compute ESEER Part load 100% 75% 50% 25% EER PartLoad In Figure 4: a. The full load cooling capacity is 100 kw b. The capacity at 75% is 0.75x100=75 kw. To obtain this capacity at 26 C, the chiller has to cycle on stage 1, the full load stage, and stage 2. c. The capacity at 50% is 0.50x100=50 kw. To obtain this capacity at 22 C, the chiller has to cycle on stage 2 and stage 3. d. The capacity at 25% is 0.25x100=25 kw. To obtain this capacity at 18 C, the chiller has to cycle on stage 3 to obtain 25% capacity. ************** Page 22 of 24

23 Figure 5: Example of a Screw chiller, 2 circuits, 1 compressor by circuit with 50% unloading step for each compressor Capacity stage number: 4 Temperatures [ C] FULL LOAD Stage 2 Stage 3 Stage 4 Cycling coefficient Pc 200 Pe(c) 50 Weighting coefficients 26 Pc % - 50 % - 75 % % Pe(c) Pc Pe(c) Pc 55.4 ESEER: 4.87 Pe(c) 10.9 Compute ESEER Part load 100% 75% 50% 25% EER PartLoad In Figure 5: a. The full load cooling capacity is 200 kw b. The capacity at 75% is 0.75x200=150 kw. To obtain this capacity at 26 C, the chiller has to cycle on stage 2 and stage 3. c. The capacity at 50% is 0.50x200=100 kw. To obtain this capacity at 22 C the chiller has to cycle on stage 3 and stage 4. d. The capacity at 25% is 0.25x200=50 kw. To obtain this capacity at 18 C the chiller has to cycle on stage 4. ************** Screw chiller, 1 circuit, continuous control with slide valve, unloading from 100% to 15% capacity The Participant has 2 options: supply only four points (Figure 6) or consider the unit as a ten steps chiller (Figure 7). Figure 6: Example of a declaration of the chiller as a 4 steps chiller Capacity stage number: 4 Temperatures [ C] FULL LOAD Stage 2 Stage 3 Stage 4 Cycling coefficient Pc 200 Pe(c) 50 Weighting coefficients 26 Pc % - 50 % - 75 % % Pe(c) Pc 100 Pe(c) Pc 50 ESEER: 4.26 Pe(c) 15 Compute ESEER Part load 100% 75% 50% 25% EER PartLoad In Figure 6: The Participant is able to supply four exact matching points at 25, 50, 75 and 100% for the condensing temperature indicated, 30, 26, 22 & 18 C for water cooled units and 35, 30, 25 & 20 C for air cooled units. In this case, the number of stages is 4. If the Participant doesn t complete the table with the exact value for each load (25, 50 & 75%) to run the macro, the ESEER can t be calculated. For example if the full load capacity is 200 kw, at 25%, the cooling capacity has to be 50 kw. Page 23 of 24

24 Figure 7: Example of a declaration of the chiller as a 10 steps chiller Capacity stage number: 10 Temperatures [ C] FULL Stage LOAD 2 Cycling coefficient Pc Pe(c) Weighting coefficients 26 Pc % - 50 % - 75 % % Pe(c) Pc Pe(c) Pc ESEER: 4.24 Pe(c) Part load 100% 75% 50% 25% Compute ESEER EER PartLoad In Figure 7: In this case, the Participant will calculate part load data every 10% load of the chiller. In this example: a. The full load cooling capacity is 200 kw b. The capacity at 75% is 0.75x200=150 kw. To obtain this capacity at 26 C, the chiller has to cycle between 80% and 70% load. c. The capacity at 50% is 0.50x200=100 kw. To obtain this capacity at 22 C the chiller has to cycle on 50% and 40% load. d. The capacity at 25% is 0.25x200=50 kw. To obtain this capacity at 18 C the chiller has to cycle on 30% and 20% load. Stage 3 Stage 4 Stage 5 Stage 6 Stage 7 Stage 8 Stage 9 Stage 10 Page 24 of 24

OM-1-2015 Published December 2014. OPERATIONAL MANUAL for the CERTIFICATION of AIR CONDITIONERS

OM-1-2015 Published December 2014. OPERATIONAL MANUAL for the CERTIFICATION of AIR CONDITIONERS OM-1-2015 OPERATIONAL MANUAL for the CERTIFICATION of AIR CONDITIONERS OM-1-2015 To supersede OM-1-2014 (Dec. 2013) Editing (date): Arnaud LACOURT 23 July 2014 Checking (date): Jean FOURCROY 13 November

More information

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER

More information

New energy evaluating methodology of Air conditioner and Heat pump

New energy evaluating methodology of Air conditioner and Heat pump New energy evaluating methodology of Air conditioner and Heat pump The 3 rd Conference Research and Development of Heat Pump and Thermal Storage Technologies in Industrial and Residential Sectors 8 October

More information

WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS

WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT ON Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT in the framework of the implementation of

More information

HVAC Efficiency Definitions

HVAC Efficiency Definitions HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

Test Report issued under the responsibility of:

Test Report issued under the responsibility of: Test Report issued under the responsibility of: TEST REPORT EHPA-DACH Testing Regulation Supplemental requirements for granting the international quality label for heat pumps Testing of Air/Water Heat

More information

Development and testing of a multi-type air conditioner without using AC inverters

Development and testing of a multi-type air conditioner without using AC inverters Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department

More information

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment

More information

AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps

AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

Research on the Air Conditioning Water Heater System

Research on the Air Conditioning Water Heater System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Appendix C. Minimum Equipment Efficiency Standards

Appendix C. Minimum Equipment Efficiency Standards Appendix C Minimum Equipment Efficiency Standards Appendix C: Minimum Equipment Efficiency Standards This Appendix is an overview of building and equipment standards in the State of California that have

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

Technical data. Danfoss DHP-A

Technical data. Danfoss DHP-A Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs

More information

Testing methods applicable to refrigeration components and systems

Testing methods applicable to refrigeration components and systems Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University

More information

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units 2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not

More information

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

More information

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient

More information

Condensing unit type EPSILON-ECHOS LE Technical information manual

Condensing unit type EPSILON-ECHOS LE Technical information manual Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS SASO XXXX:2016 (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS PERFORMANCE REQUIREMENTS AND METHODS OF TESTING 1 LARGE CAPACITY AIR CONDITIONERS

More information

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July 2008. Prepared by

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July 2008. Prepared by Regency TAFE, SA An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump July 2008 Prepared by Andrew Pang Andrew Pang & Associates Pty Ltd Phone: 0438 188 180 Facsimile: 9331 0898

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Cool Design for Homes and Offices

Cool Design for Homes and Offices AIR BLUE AIR BLUE air conditioning Homes Easy to install and use, quiet, attractive, and designed to fit any space: there are Cool Design for Homes and Offices a lot of reasons why Air Blue air conditioners

More information

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005 KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed

More information

your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction

your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction What is DNSS EcoSave? The Daikin Network Service System (DNSS EcoSave) is a Daikin developed internet based remote

More information

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW - AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

Schedule 3(A) Room Air Conditioners

Schedule 3(A) Room Air Conditioners Schedule 3(A) Room Air Conditioners Revision : 1 Date : 21/08/15 1. Scope 1.1 This Standard specifies the energy labeling requirements for single-phase split air conditioners of the vapour compression

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

3/29/2012 INTRODUCTION HVAC BASICS

3/29/2012 INTRODUCTION HVAC BASICS INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)

More information

1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/

1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ 1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ ISO 9001 ISO 14001 Certified number : 01 100 89394 Certified number : 01 104 9245101 Fujitsu General (Thailand) Co.,

More information

SMM. Installation Operation Maintenance

SMM. Installation Operation Maintenance SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation Foreword These installation,

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in

More information

Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc

Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled

More information

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.

More information

User manual. 086U6297 Rev. 9 EN

User manual. 086U6297 Rev. 9 EN User manual Atria Atria Duo Atria Duo Optimum Atria Optimum Comfort Diplomat Diplomat Duo Diplomat Duo Optimum Diplomat Duo Optimum G2 Diplomat Optimum Diplomat Optimum G2 086U6297 Rev. 9 EN Thermia Värme

More information

SASO 2663 :2014 ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE REQUIREMENTS FOR AIR-CONDITIONERS

SASO 2663 :2014 ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE REQUIREMENTS FOR AIR-CONDITIONERS SASO 2663 :2014 (SASO 2663/2012 including the modifications approved in Saudi Council Board No../2014) ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE REQUIREMENTS FOR AIR-CONDITIONERS ENERGY LABELLING

More information

Eurovent Certification

Eurovent Certification Eurovent Certification Performance Testing and Certification Dedicated Outdoor Air Systems AHU s & Cooling Towers REHVA Seminar ACREX 7 th March 2013 Ian Butler ECC Audit Manager & Key Speaker 2/30 First

More information

Air conditioning systems Final report of Task 6

Air conditioning systems Final report of Task 6 Center of Energy and Processes Van Holsteijn and Kemna Building Research Establishment Service Contract to DG Enterprise Sustainable Industrial Policy Building on the Ecodesign Directive Energy-Using Product

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None

1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None 1-Way Chilled Water Cassettes KCO 60, 90 & 120 Technical Brochure TM KCO-W.1GB Date : November 2005 Supersedes : None General Features Control valve (optional) Air vent In-tube electric heating elements

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

ZUBA-CENTRALTM. Heating & Cooling. Evolved. HEATING AND AIR CONDITIONING FOR WHOLE-HOME, YEAR-ROUND COMFORT

ZUBA-CENTRALTM. Heating & Cooling. Evolved. HEATING AND AIR CONDITIONING FOR WHOLE-HOME, YEAR-ROUND COMFORT ZUBA-CENTRALTM Heating & Cooling. Evolved. HEATING AND AIR CONDITIONING FOR WHOLE-HOME, YEAR-ROUND COMFORT Energy-efficient. Easy to install. Extremely quiet. Zuba-Central is simply the new and better

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

DIABLO VALLEY COLLEGE CATALOG 2015-2016

DIABLO VALLEY COLLEGE CATALOG 2015-2016 HEATING, VENTILATION, AIR CONDITIONING, REFRIGERATION - HVACR Tish Young, Dean Physical Sciences and Engineering Division Physical Sciences Building, Room 263 Possible career opportunities Upon successful

More information

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment

More information

Residential Air Conditioning. Program Standards

Residential Air Conditioning. Program Standards Residential Air Conditioning Program Standards Effective: January 1, 2015 Florida Power & Light Company Residential Air Conditioning Program Standards Table of Contents Program Objective... 1 Customer

More information

REFRIGERATION & AIR CONDITIONING SYSTEM

REFRIGERATION & AIR CONDITIONING SYSTEM REFRIGERATION & AIR CONDITIONING SYSTEM 1. INTRODUCTION...1 2. TYPES OF REFRIGERATION AND AIR CONDITIONING...3 3. ASSESSMENT OF REFRIGERATION AND AIR CONDITIONING...9 4. ENERGY EFFICIENCY OPPORTUNITIES...12

More information

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

Air-Conditioning Buying Guide

Air-Conditioning Buying Guide Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory

More information

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories

More information

How To Save Energy With High Pressure Control

How To Save Energy With High Pressure Control Energy savings in commercial refrigeration equipment : High Pressure Control July 2011/White paper by Christophe Borlein AFF and IIF-IIR member Make the most of your energy Summary Executive summary I

More information

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

Midea Commercial Air Conditioner Malfunction Handbook

Midea Commercial Air Conditioner Malfunction Handbook Midea Commercial Air Conditioner Malfunction Handbook May 1, 2008 Customer Service Philosophy of Midea Air Conditioner Service Target: 100% Customer Satisfaction Service Standard: 100% Earnestness Service

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged

More information

FULL DC INVERTER SYSTEMS

FULL DC INVERTER SYSTEMS FULL DC INVERTER SYSTEMS INDIDUAL AND MODULAR DESIGN & FLEXIBLE COMBINATION commercial air conditioners SDV4 2011/2012 AIR CONDITIONING 1 WELCOME TO THE WORLD of SINCLAIR AIR CONDITIONERS Company operation

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D) Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment. Partner Commitments.

ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment. Partner Commitments. ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment Partner Commitments Commitment The following are the terms of the ENERGY STAR Partnership

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

Appendix - Controllers 179

Appendix - Controllers 179 Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2

More information

Performance Rating of Room Fan- Coils

Performance Rating of Room Fan- Coils ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS

More information

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under

More information

Increasing the evaporation temperature with the help of an internal heat exchanger

Increasing the evaporation temperature with the help of an internal heat exchanger Increasing the evaporation temperature with the help of an internal heat exchanger A. TAMBOVTSEV (a), H. QUACK (b) (a,b) Technische Universität Dresden, D-01062, Dresden, Germany (a) Fax: (+49351) 463-37247,

More information

MAROON 2. 6 78 kw. General information. Unique selling points

MAROON 2. 6 78 kw. General information. Unique selling points 6 78 kw General information Dedicated heat pumps new series with Scroll compressors, with and without vapor injection. /HT version in 15 sizes Cooling capacity (35;W7): 6 73 KW Heating capacity (7;W45):

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,

More information

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets 2 Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets - Extending Use of New Heat Pump System in Cold Regions

More information

Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement

Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement 7 Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement Steve Doty, PE, CEM sdoty@csu.org ABSTRACT A value of 1-1.5% power reduction per degree Fahrenheit (F) has been used successfully

More information

AIR SOURCE CHILLERS FOR OUTDOOR INSTALLATION

AIR SOURCE CHILLERS FOR OUTDOOR INSTALLATION AIR SOURCE CHILLERS FOR OUTDOOR INSTALLATION HIGH EFFICIENCY LATEST CONTROL SYSTEM LEED RELEVANT PRODUCT EXTREMELY SILENT OPERATIONS Features High efficiency chiller, air source for outdoor installation

More information

TRAINING, EXAMINATION AND CERTIFICATION

TRAINING, EXAMINATION AND CERTIFICATION TECHNICAL STANDARDS & SAFETY AUTHORITY TRAINING, EXAMINATION AND CERTIFICATION REFRIGERATION OPERATOR CLASS B CERTIFICATION & EXAMINATION GUIDE REVISED EDITION 2 CERTIFICATIONS PERSUANT TO THE OPERATING

More information

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Low GWP Replacements for R404A in Commercial Refrigeration Applications Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, Samuel.YanaMotta@honeywell.com Abstract

More information

Ventilation for buildings Energy performance of buildings Guidelines for inspection of air-conditioning systems

Ventilation for buildings Energy performance of buildings Guidelines for inspection of air-conditioning systems CEN/TC 156 Date: 2006-05 pren 15240 CEN/TC 156 Secretariat: BSI Ventilation for buildings Energy performance of buildings Guidelines for inspection of air-conditioning systems ICS: Descriptors: Document

More information

SECTION 15950 - TESTING, ADJUSTING, AND BALANCING

SECTION 15950 - TESTING, ADJUSTING, AND BALANCING SECTION 15950 - TESTING, ADJUSTING, AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

How Ground/Water Source Heat Pumps Work

How Ground/Water Source Heat Pumps Work How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy

More information

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard

More information

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange ING. TOMMASO FERRARESE Thermodynamics Laboratory Engineer

More information