G M TREBLE LTD. Operating & Maintenance Instructions For Single Pump Sealed System Pressurisation Unit & Expansion Vessel.

Size: px
Start display at page:

Download "G M TREBLE LTD. Operating & Maintenance Instructions For Single Pump Sealed System Pressurisation Unit & Expansion Vessel."

Transcription

1 G M TREBLE LTD Operating & Maintenance Instructions For Single Pump Sealed System Pressurisation Unit & Expansion Vessel Model: Serial No: PH-1L

2 INSTALLATION Fixing & Piping: The Ph-1L unit and the system expansion vessel should be bolted down side by side, if possible on to a firm level base. The heating/cooling system should be connected primarily to the expansion vessel using a minimum 1 /28mm diameter expansion pipe, for LPHW heating systems the pipe should incorporate an anti-gravity loop where possible 2 metres high, with an air vent at its highest point, then connected into the system return on the suction side of any recirculating pumps, should they be fitted on the system return. This expansion pipe should be fitted with a lockable or otherwise tamperproof isolation valve, with a drain cock fitted on the expansion side of the isolation valve, to facilitate setting up and future servicing of the equipment. A minimum ¾ /22mm diameter delivery pipe from the PH-1L unit, fitted with a further lockshield isolation valve, should be run to tee into the 1 expansion pipe on the expansion tank side of the system isolation valve. A 15mm diameter cold water supply pipe should be connected to the ½ ball float valve on the PH-1L unit feed water tank. Take care to ensure that all pipework is adequately supported to prevent any undue strain on the connection and prevent the ball float valve from bouncing. The system high and low pressure fault switches should be mounted together and their ¼ BSPM connections piped into a further 2tee in the system expansion pipe. Electrical Connections A single phase electrical supply and earth should be connected to the switch/fuse on the PH-1L unit, preferably fed from the contactor starter having a motor overload set at approximately (2.8amps). when no starter is incorporated on the PH-1L, the power supply should not be interrupted by any time clock which may be used to control the boiler or chiller. In addition, wiring connections should be made from the boiler/chiller control circuit to separate TBV high and low pressure fault switches to interrupt boiler/chiller operation in the event of a pressure fault. PRE-START CHECKS Note: If a G.M Treble commissioning engineer is used to put this equipment into operation then the following paragraphs need not be followed, skip to Normal Operation. Expansion Vessel Preferably before the system is filled with water but in any case with the system expansion pipe isolation valve closed, fit a hose pipe to the expansion pipe drain cock to discharge to the nearest drain, open the drain cock and allow any water to escape. Check the air cushion pressure on the expansion valve by using a standard tyre pressure gauge on the Schrader valve normally located beneath a black plastic cap on the top of the vessel and if necessary adjust it to match the desired cold fill pressure. Most expansion vessels are shipped with a higher air cushion pressure than the average system will require, some air will therefore usually need to be released, however if a higher than usual pressure is needed then an oil-free air or nitrogen source will be necessary. 2

3 PH-1L Unit Unless otherwise requested, all PH-1L units are preset on test in our factory for a nominal cold fill pressure of 1.0 bar. Open the ¼ Easyprime valve on the top of the pump body, before turning on the cold water supply to the feed tank, allowing the tank to fill, check that the ball float valve has closed and stopped running before closing the Easyprime valve, the pump should have now been primed. Check the air cushion pressure on the accumulator vessel at the top of the unit in the same manner as the expansion vessel, this should be set at 0.8 bar. With the PH-1L discharge valve open, the drain hose in place and with the expansion tank drain cock open, switch on the pump at the switch/fuse, the pressure should begin to rise on the pressure gauge and the water should run from the drain hose. Depending on the resistance through the drain hose, the pump may build up sufficient pressure to switch itself off briefly before restarting again, but in any event allow it to run for a minute or so to clear away any remaining air. Finally check the pump switching pressures. With the discharge valve slightly open the pump will start at approximately 0.9 bar, run for a few seconds and will stop at approximately 1.1 bar. With the discharge valve completely closed should the pump fail to build up pressure and stop, switch it off and re-vent it by opening the Easyvent valve for a few seconds, close the valve again then retry. If the cold fill pressure does not correspond with your requirements, refer to Adjusting Cold Fill Pressure below. When satisfied with the pressure setting the expansion tank drain cock can be closed and the PH-1L discharge isolating valve opened, the pump will the probably start and run for somewhat longer than previously, before building up pressure and stopping. Adjusting Cold Fill Pressure Should it be necessary to make any adjustment to the standard cold fill pressure setting of 1.0 bar, proceed as follows: Switch off the PH-1L pump at the switch/fuse, with the expansion pipe isolated from the heating/cooling system open the drain cock to allow any water stored in the expansion tank and the PH-1L accumulator to empty until the pressure gauge reads zero. Check the accumulator air cushion pressure by using a standard tyre pressure gauge on the Schrader valve located beneath the black plastic cap on the end of the accumulator and if necessary adjust it using oil free compressed air or nitrogen until it is 0.2 bar below the desired cold pressure. Roughly set the pump control pressure switch Range (RH) scale to the desired cold fill pressure, then with the drain cock still open and the PH-1L discharge isolating valve slightly open switch on the switch/fuse and observe the pressures at which the pump starts and stops, until a setting 0.1 bar either side of the required cold fill pressure is reached. High & Low Pressure Fault Switches Once the correct cold fill pressure has been established in the expansion pipe the pressure fault switches may be set; with the power supply to the switches isolated the top covers of both switches can be removed after loosening their retaining screws, allowing the main covers to be pulled off. The Differential (LH) scale adjustment should be first be set to minimum on both switches, then the high pressure switch Range (RH) scale adjusted to a setting of 0.5 bar above the calculated final working pressure or 0.3 bar below the safety valve lifting pressure, whichever is the lower. After rechecking that the correct cold fill pressure is still being maintained, check if the low pressure switch has operated by confirming that the end of the operating lever on the bottom left of the switch is in the high position, if it is not wind the Range (RH) scale adjustment anti-clockwise it clicks up. Then wind the adjusting screw clockwise until the switch operates again, finally turn the screw a further ½ turn to achieve the correct setting. 3

4 The covers and lids may then be refitted and the power supply restored to check that the boiler/chiller is able to operate and any fault/normal lamps operate correctly. INITIAL START-UP System Filling: The system boiler/chiller and pipework must be completely filled with water before running the recirculation pumps, normally this can be done by back filling using a hose connection with an approved double check valve, though the pressurisation unit pump is continuously rated and may be used to assist with this process if desired, though it may prove to be slower. If a hose is used the system should be filled until a pressure of approximately 0.2 bar below the desired cold fill pressure has been reached, when the expansion pipe system isolation valve to the pressurisation equipment can be opened to allow the PH-1L unit to top the system up. All pipework high points should be vented to remove as much as possible. The PH-1L unit will ensure that the system is kept topped up. Starting Up: Once the foregoing procedures have been carried out it is permissible to start the heating/cooling system circulating pump, since it is almost certain that some air will still be present in the pipework this can be released from system high points either manually or by automatic air vents if fitted, by occasionally stopping the circulating pump. The pressurisation equipment is now functional. OPERATION Normal Running: The PH-1L should always be left powered up and supplied with water, it will then be able to operate at any time to ensure the system pressure never drops below the minimum cold fill setting. Expansion and contraction of the water with heating/cooling is accommodated by the expansion vessel, as the system water temperature rises it is displaces into the expansion tank, resulting in a general system pressure rise. The extent of this rise will vary with expansion vessel size and operating temperature but working pressures between 1½ and up to twice the cold fill pressure can be considered quite normal. The expanded pressure can be seen on the pressure gauge of the PH-1L unit, but it should be noted that the pressure indicated on the system circulating pump delivery gauge will be somewhat higher than this. During normal heating/cooling system operation pressurisation pump activity should be minimal, unless there is any significant water leakage, the PH-1L pump will seldom be seen running, and then only briefly when the system is cooling down. MAINTENANCE Maintenance is confined to checks made on the air cushion pressures of the PH-1L accumulator and the heating/cooling system expansion tank, both tasks should normally be carried out annually. The pump requires no lubrication but a visual check should be made for any signs of leakage or any unusual sounds when running. To check the accumulator and expansion tank air cushion pressures, shut down the heating system, turn off the PH-1L at the switch/fuse, close the heating system expansion pipe isolating valve, fit a hose on the drain cock and empty the contents of the of the expansion tank to drain until the PH-1L pressure gauge falls to zero and the flow stops. 4

5 Remove the air valve cap on the end of the accumulator and the cap on top of the expansion tank, and using a standard tyre pressure gauge check the air cushion pressure and check with the figures indicated on our commissioning report (if commissioned by G M Treble) or the figures below if the set-up is as our standard factory set-up: Accumulator air cushion pressure - Expansion tank air cushion pressure bar 1.0 bar If either pressure is found to have fallen below their respective figure, reflate to the correct level using a suitable oil free or nitrogen supply. When the air pressure have been restored, close the drain cock, remove the hose, replace the air valve covers and reopen the system expansion pipe isolating valve before switching the switch/fuse back on. Depending on the circuit pressure a PH-1L pump may run to restore the correct minimum operating pressure. IF THE AIR CUSHION PRESSURE IS VERY LOW OR ABSENT Normally after draining the expansion tank and accumulator their air cushion pressures will only be a little below the correct level, unless this check has been neglected for some time. If the air cushion pressure is found to be very low a further check should be made on all vessel connections, covers and around the Schrader valve fitting for possible leaks, this is best carried out with soap/water solution or leak detector after reflation, any revealed leaks then being rectified. It the air cushion pressure is totally absent, and particularly if the air discharges from the drain valve when reflation is attempted or water discharges from the Schrader valve, then diaphragm failure is possible. A new diaphragm may need to be fitted. 5

6 FAULT TRACING MAKE-UP PUMP CYCLES ON/OFF RAPIDLY MAKE-UP PUMP WILL NOT RUN MAKE-UP PUMP WILL NOT START HIGH PRESSURE FAULT LOW PRESSURE FAULT Drain the accumulator and expansion tank and check that the air cushion pressures are set to the recommended level, any substantial under (or over) pressure will affect the frequency of pump operation. Check for debris or damage to non-return valve fitted to the PH-1L discharge connection. Check the power supply to the switch/fuse and that the correct 5 Amp fuse is fitted and not blown. Check the system is not already up to pressure. Check that the feed tank level is adequate. Check that the pump is free to turn by removing the cooling fan cowl & turning the fan by hand. Check that the pressure switch is functioning by operating it manually. Check that the switch off pressure indicated on the foregoing page is being reached on the pressure gauge. Check that the pressure switch is functioning by operating it manually. Check that the pump has not lost its prime, re=prime if necessary. Expansion tank air cushion pressure too low or too high. Drain the expansion tank and check that its air cushion pressure is set to the recommended level. Heating/cooling system temperature is too high. System has been manually filled to an excessively high pressure. PH-1L pump is not switched on. Switch fuse has blown. Pump has lost its prime. GM TREBLE LTD New Street Parkfields Wolverhampton West Midlands WV4 6AN Tel: Fax:

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS 1 WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS Please read and follow all these instructions carefully before proceeding with the installation,

More information

Maxi Pressurisation Units (Maxi, Maxi Plus & HP)

Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Installation and Maintenance Instructions Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Factory owners must ensure the boiler is:

Factory owners must ensure the boiler is: Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised

More information

FILLING AND PURGING THE SYSTEM

FILLING AND PURGING THE SYSTEM FILLING INSTRUCTIONS FOR WATER HEATER OR CONDENSING BOILER (City Water) Safety tip: Before beginning, turn off power to boiler and circulator. FILLING AND PURGING Step 1: Close Return Manifold Isolation

More information

Operation & Maintenance Manual

Operation & Maintenance Manual Operation & Maintenance Manual Flexfiller Digital Pressurisation Equipment Flexfiller Models (125D, 225D, 150D, 250D, 280D) Midi Models (125D, 225D, 150D, 250D) Mini Models (130D, 230D) Contents About

More information

SHHH AIR COMPRESSOR Model Nos. SHHH2 - SHHH2/9 - SHHH3/9 - SHH3/24

SHHH AIR COMPRESSOR Model Nos. SHHH2 - SHHH2/9 - SHHH3/9 - SHH3/24 SHHH AIR COMPRESSOR Model Nos. SHHH2 - SHHH2/9 - SHHH3/9 - SHH3/24 OPERATING & MAINTENANCE INSTRUCTIONS 1205 PARTS & SERVICE For Spare Parts and Service,please contact your nearest dealer, or CLARKE International,

More information

PC1131 Electric Air Compressor

PC1131 Electric Air Compressor Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in

More information

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. MULTIPOINT Please read and understand these instructions before starting work. Please leave this leaflet

More information

Operators manual Basic water heater

Operators manual Basic water heater Operators manual Basic water heater Isotemp Basic water heater has been designed and produced to ensure that your water heater will give long and trouble free operation for many years. It is important,

More information

Elson Coral E. Open Vented Thermal Store providing mains pressure hot water heated by electricity. Installation, Servicing and User's Instructions

Elson Coral E. Open Vented Thermal Store providing mains pressure hot water heated by electricity. Installation, Servicing and User's Instructions Part No. 130009 Iss. 12 August 2004 Elson www.elsonhotwater.co.uk Open Vented Thermal Store providing mains pressure hot water heated by electricity Installation, Servicing and User's Instructions Read

More information

PC1130 Electric Air Compressor

PC1130 Electric Air Compressor Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1130 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in

More information

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................

More information

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS 1. Define an accumulator and explain its function A hydraulic accumulator is a device that stores the potential energy of an incompressible fluid

More information

OPERATING & MAINTENANCE AIR COMPRESSOR RANGER 35 INSTRUCTIONS. Part No: 2331000

OPERATING & MAINTENANCE AIR COMPRESSOR RANGER 35 INSTRUCTIONS. Part No: 2331000 RANGER 35 AIR COMPRESSOR Part No: 2331000 OPERATING & MAINTENANCE INSTRUCTIONS 1102 Clarke International. All rights reserved. Dec. 1998 2 SPECIFICATIONS Rotational Speed... 2850 rpm Max. Pressure... 8

More information

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 A refrigerant retrofit project, involving the conversion of a large Data Room cooling system from R22 to R422D (DuPont

More information

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 gpm@gpmhydraulic.com www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS

More information

Draining and filling cooling system

Draining and filling cooling system Page 1 of 9 Draining and filling cooling system Special tools and workshop equipment required Adapter -V.A.G 1274/8- Pipe -V.A.G 1274/10- Drip tray -V.A.G 1306- or drip tray for workshop hoist -VAS 6208-

More information

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions

More information

Operating instructions

Operating instructions 6300 9681 02/2006 GB For the user Operating instructions Logano GE315 Boiler for oil-/gas-fired pressure jet burners Please read thoroughly before use. Operating instructions Logano GE315 Dear Customer,

More information

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive

More information

TOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?

TOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump? KNOWLEDGE: K1.01 [3.3/3.5] P21 Which one of the following contains indications of cavitation in an operating centrifugal pump? A. Low flow rate with low discharge pressure. B. Low flow rate with high discharge

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

Water valves REFRIGERATION AND AIR CONDITIONING. Fitters notes

Water valves REFRIGERATION AND AIR CONDITIONING. Fitters notes REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Application...3 Identification...3 Installation...5 Setting...6 Maintenance...6 Spare parts...8 Fault location...9 2 RZ4DA202 DKRCC.PF.D00.A1.02

More information

SELECTION, APPLICATION AND MAINTENANCE

SELECTION, APPLICATION AND MAINTENANCE DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine

More information

User's Instructions. Alpha HE CB25/33 and HE SY25

User's Instructions. Alpha HE CB25/33 and HE SY25 User's Instructions Alpha HE CB25/33 and HE SY25 Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Boiler Range For Technical help or for Service call... ALPHA HELPLINE Tel:

More information

Hydraulic control unit series 0086-372-01

Hydraulic control unit series 0086-372-01 Technical Product Information No. 1290 EN Hydraulic control unit series 0086-372-01 Contents Page About this Technical Product Information (TPI) 2 The ORTLINGHAUS numbering system 2 About the product 3

More information

SERVICE SERVICE COMPACT MANUAL. Mod. 3000 92X Mod. 3000 93X Mod. 3000 94X. Part 2

SERVICE SERVICE COMPACT MANUAL. Mod. 3000 92X Mod. 3000 93X Mod. 3000 94X. Part 2 SERVICE COMPACT SERVICE 000 MANUAL Mod. 000 9X Mod. 000 9X Mod. 000 94X Part Forward This Service Handbook is intended to assist with servicing and fault-finding in Caravans and Motor Caravans equipped

More information

Volkswagen B3 Passat General-Engine 4 CYL. 19 Engine - Cooling System (Page GR-19)

Volkswagen B3 Passat General-Engine 4 CYL. 19 Engine - Cooling System (Page GR-19) 19 Engine - Cooling System (Page GR-19) Cooling system draining and filling general information Body components, layout Engine components, layout Radiator fan run-on checking Recommended mixture ratios

More information

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents

More information

PANTHER OPERATING & MAINTENANCE INSTRUCTIONS

PANTHER OPERATING & MAINTENANCE INSTRUCTIONS PANTHER OPERATING & MAINTENANCE INSTRUCTIONS 0503 COMPRESSOR Qty Part No. Qty Part No. SPARES AND SERVICING 1 Screw w/washer 1 FN216HQ0001 2 Screw 4 FN014006024 3 Dipstick compl. 1 FN216HQ0002 4 Plastic

More information

ITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name.

ITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name. ITE Indirect calorifier ITE - 400/500/600/750/1000 0310 117 Installation, User and Service Manual Innovation has a name. Read this manual carefully Warning Read this manual carefully before starting the

More information

Operation & Maintenance Manual

Operation & Maintenance Manual Manual # OMAV2-SUMP1 High Performance Air & Dirt Separators Manual # 9636-1230 Rev. A Operation & Maintenance Manual 340 West 8 th Street Peru, IN 46970 PH: 765 472 3351 FX: 765 472 3968 www.thrushco.com

More information

Rexroth Hydraulic Pump A10VO Series User Manual

Rexroth Hydraulic Pump A10VO Series User Manual Rexroth Hydraulic Pump A10VO Series User Manual Rexroth Hydraulic pump A10VO Series User Manual Revised 5/1/2009 Page 1 of 12 Functional Purpose This pump is preferred over a fixed displacement (gear)

More information

ACCUMULATOR INSTALLATION

ACCUMULATOR INSTALLATION 7001-7 ACCUMULATOR INSTALLATION BRAKE ACCUMULATORS I 308L93 Rae 7-59710 Issued 6-93 Printed in U.S.A 7001-8 Removal ACCUMULATOR VALVE 1. Park the machine on a level surface and lower the. loader bucket

More information

MODEL 300505 INSTALLATION INSTRUCTIONS

MODEL 300505 INSTALLATION INSTRUCTIONS WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 info@burcam.com Your pump has been carefully packaged at the factory to prevent damage during shipping.

More information

Zenith Solar thermal 4.5m pump station Installation manual

Zenith Solar thermal 4.5m pump station Installation manual Zenith Solar thermal 4.5m pump station Installation manual Product code: 20026145 INSTALLATION MANUAL WATER RETURN GROUP This instruction manual is an integral part of the installation and maintenance

More information

Electric Instantaneous. Water Heaters. Service manual

Electric Instantaneous. Water Heaters. Service manual Electric Instantaneous Water Heaters Service manual Before installation quoting stage Work out with the customer what is the right model to install for the application Site assessment 1. The electrician

More information

Laddomat 21-60 Charging unit

Laddomat 21-60 Charging unit Laddomat 21-60 Charging unit User and installation instructions NOTE! Diagrams in this brochure only describe connection principles. Each installation must be measured and carried out according to the

More information

GUERNSEY OIL INSTALLATION GUIDELINES

GUERNSEY OIL INSTALLATION GUIDELINES GUERNSEY OIL INSTALLATION GUIDELINES This guidance relates only to liquid oil. For information on the requirements for associated equipment such as the positioning of boilers and flues please refer to

More information

AMBASSADOR (KITCHEN), COUNTRYMAN (OUTDOOR) & CONSUL (BOILERHOUSE) CONSENSING BOILERS SENATOR (KITCHEN) & COUNTRYMAN (OUTDOOR) COMBI CONSENSING BOILERS

AMBASSADOR (KITCHEN), COUNTRYMAN (OUTDOOR) & CONSUL (BOILERHOUSE) CONSENSING BOILERS SENATOR (KITCHEN) & COUNTRYMAN (OUTDOOR) COMBI CONSENSING BOILERS Page INTRODUCTION/WARRANTY 2 - WHAT IS A CONDENSING BOILER? 2 AMBASSADOR (KITCHEN), COUNTRYMAN (OUTDOOR) & CONSUL (BOILERHOUSE) CONSENSING BOILERS USER INSTRUCTIONS 3 - BOILER OPERATION 3 - SWITCHING THE

More information

Volvo Penta Quality Line Marine Water Heaters. Owners Manual

Volvo Penta Quality Line Marine Water Heaters. Owners Manual Volvo Penta Quality Line Marine Water Heaters Owners Manual Mounting Instructions Congratulations on your choice of a new QL Water Heater. A choice that will help you bring out the best in boating pleasure.

More information

FLEXCON EXPANSION VESSELS. Flamco FLEXCON 2-80. Flexcon. Expansion vessels FLEXCON 110 1000 FLEXCON M. Flamco FLEXCON V-B.

FLEXCON EXPANSION VESSELS. Flamco FLEXCON 2-80. Flexcon. Expansion vessels FLEXCON 110 1000 FLEXCON M. Flamco FLEXCON V-B. FLEXCON EXPANSION VESSELS Flamco 1 Flexcon Expansion vessels FLEXCON 2-80 FLEXCON 110 1000 FLEXCON M Flamco FLEXCON V- 2007 edition / UK Flamco Flexcon the first name in expansion vessels Flamco has over

More information

Operating instructions

Operating instructions 6302 6959 02/2006 GB For the user Operating instructions Logano G215 WS Oil and gas-fired boilers Please read thoroughly before use. Overview Regulations and directives Installation: 90/396/EEC gas appliance

More information

Morco House Riverview Road Beverley HU17 0LD

Morco House Riverview Road Beverley HU17 0LD Morco House Riverview Road Beverley HU17 0LD Morco Products Ltd Tel: 01482 325456 Fax: 01482 212869 Email sales@morcoproducts.co.uk Web www.morcoproducts.co.uk Combi Boilers - Poor Hot Water Delivery Combi

More information

CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual

CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual Goodway Technologies Corporation 420 West Avenue Stamford, CT 06902-6384 (203)359-4708 Sales: 1-800-333-7467 Customer Service: 1-800-370-2855

More information

SELECTION, APPLICATION & MAINTENANCE

SELECTION, APPLICATION & MAINTENANCE DIESEL PROTECTION SYSTEMS TPZ Engine Air Intake Shut Down Valves (Combined Automatic Overspeed and Air Pressure Operated Shut Down Bendix Types) SELECTION, APPLICATION & MAINTENANCE Valve Numbers TPZ-101

More information

Vertical selfpriming Side-Channel Pumps Type WPV

Vertical selfpriming Side-Channel Pumps Type WPV Vertical selfpriming Side-Channel Pumps Type WPV FIELD OF APPLICATION The side-channel pumps are selfpriming and operate more economically (better efficiency) than normal centrifugal pumps when handling

More information

Not required for most applications Not required for most applications High pressure (12-803 provided) High pressure (12-803 provided)

Not required for most applications Not required for most applications High pressure (12-803 provided) High pressure (12-803 provided) ELECTRIC FUEL PUMPS P/N 12-801-1, 712-801-1, 12-802-1, 712-802-1, 12-815-1, & 712-815-1 FUEL PRESSURE REGULATORS P/N 12-803, 12-501, 12-804, 12-500, & 15812NOS Installation Instructions THESE INSTRUCTIONS

More information

Description of functions

Description of functions Description of functions Laddomat 21 is designed to......allow the boiler to reach a high working temperature soon after firing....to preheat the cold tank water in the bottom of the boiler so that the

More information

SILENT AIR COMPRESSOR

SILENT AIR COMPRESSOR SILENT AIR COMPRESSOR MODEL NO: SHHHAIR 50/24 PART NO: 2320875 OPERATION & MAINTENANCE INSTRUCTIONS LS0309 INTRODUCTION Thank you for purchasing this CLARKE Silent Air Compressor. Before attempting to

More information

A Guide to Trouble-Free Cooling Towers

A Guide to Trouble-Free Cooling Towers A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic

More information

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions. B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary

More information

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual Speedflow Undersink Unvented Water Heater Models SF10K and SF15K Instruction Manual Version 2.0 May 2009 Hyco SpeedFLOW UnVENTED WATER HEATER Models SF10K (10 Litres) and SF15K (15 Litres) 1. Introduction

More information

Float and Thermostatic Traps Series H, C and X

Float and Thermostatic Traps Series H, C and X Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT

More information

Belt Driven Compressors

Belt Driven Compressors Manual Belt Driven Compressors 070708/00004 Table of Contents Page Introduction / Warranty 3 Standard Components 5 Compressor Layout 6 Installation 9 Engine Driven Compressors 11 Maintenance 13 Safety

More information

your water pressure explained

your water pressure explained your water pressure explained water networks your responsibility low pressure Our water networks are designed so that a typical home has a plentiful supply of water pressure and flow. There are however

More information

TOBY DVR5 OIL CONTROL & SAFETY VALVE

TOBY DVR5 OIL CONTROL & SAFETY VALVE TOBY DVR5 OIL CONTROL & SAFETY VALVE TECHNICAL HANDBOOK Principle of Operation The Toby DVR5 Oil Control Valve is a multi function unit for maintaining a constant oil level, regulating the oil flow and

More information

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/ CW-5000/ 5200 Contents Cautions ---------------------------------------------------------------- 3 Parts introduction --------------------------------------------------- 4 Installation ------------------------------------------------------------

More information

COMMISSIONING OF HVAC SYSTEMS

COMMISSIONING OF HVAC SYSTEMS FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS

More information

Baxi Combi 80e & 105e

Baxi Combi 80e & 105e Baxi Combi 8e & 15e Please keep these instructions safe. Should you move house, please hand them over to the next occupier. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Natural

More information

Session 2: Hot Water Supply

Session 2: Hot Water Supply MEBS6000 Utility Services http://www.hku.hk/mech/msc-courses/mebs6000/index.html Session 2: Hot Water Supply Dr. Benjamin P.L. Ho Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

Building Services Engineering Technician

Building Services Engineering Technician Building Services Engineering Technician A competent Building Services Engineering Technician is expected to be able to demonstrate the following skills and competences: Systems design in the building

More information

3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: sales@kellogg-american.com Website: www.kellogg-american.com

3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: sales@kellogg-american.com Website: www.kellogg-american.com Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor

More information

Domestic Chemical Water Treatment Manufacturers Association

Domestic Chemical Water Treatment Manufacturers Association Domestic Chemical Water Treatment Manufacturers Association Code of Practice for Chemical Cleaning and Inhibiting of Domestic Hot Water Central Heating Systems A Guide for Installers and Specifiers Prepared

More information

High Output Boiler Systems

High Output Boiler Systems High Output Boiler Systems Information for Dual System Link up methods For use in GB & IE (Great Britain and Republic of Ireland). This appliance has been certified for use in countries other than those

More information

OBSERVING BOILER SAFETY RULES

OBSERVING BOILER SAFETY RULES OBSERVING BOILER SAFETY RULES The rules that follow are brief reminders of the possible consequences in a boiler plant of inappropriate operator response or questionable action in maintaining the boiler

More information

INSTRUCTION MANUAL CIRRO MK 3/TYPE 2 MIST GENERATOR

INSTRUCTION MANUAL CIRRO MK 3/TYPE 2 MIST GENERATOR INSTRUCTION MANUAL CIRRO MK 3/TYPE 2 MIST GENERATOR INTRODUCTION The Cirro MK 3 is a fully professional mist generator for producing sufficient airborne reflection particles to enable effect lighting to

More information

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE Page 1 of 9 PURPOSE Steam is the most commonly used heating medium for maintaining process temperatures. Compared to other heating media, steam contains a significant amount of heat energy, and this heat

More information

GRANT. Vortex Condensing Oil Boilers. USER, INSTALLATION and SERVICING INSTRUCTIONS

GRANT. Vortex Condensing Oil Boilers. USER, INSTALLATION and SERVICING INSTRUCTIONS Part No. IRL 003 Rev. 02 May 2010 EFFICIENT HEATING SOLUTIONS GRANT Vortex Condensing Oil Boilers USER, INSTALLATION and SERVICING INSTRUCTIONS Indoor/Utility, System and Boiler House Models with outputs

More information

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

Link-Up. Solid Fuel Association Guide to Central Heating. www.solidfuel.co.uk

Link-Up. Solid Fuel Association Guide to Central Heating. www.solidfuel.co.uk Solid Fuel Association Guide to Central Heating Link-Up Combining solid fuel with other central heating technologies using various methods ranging from a simple link-up to a fully integrated thermal store

More information

ENGINE COOLING SYSTEM

ENGINE COOLING SYSTEM ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,

More information

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Baxi Combi Instant 8e & 15e Gas Fired Wall Mounted Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.

More information

Electric Flow Boiler

Electric Flow Boiler Electric Flow Boiler Installation & technical Manual If you require any further assistance: Telephone: 01698 820533 Fax: 01698 825697 E-mail: info@electric-heatingcompany.co.uk or visit our website www.electric-heatingcompany.co.uk

More information

For installation guide see reverse of book

For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN

More information

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167 PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION

More information

VOYAGER 570G. 744A Sprayer Control

VOYAGER 570G. 744A Sprayer Control VOYAGER 570G 744A Sprayer Control U S E R M A N U A L U S E R M A N U A L Table of Contents CHAPTER 1 - INTRODUCTION...1 SYSTEM CONFIGURATIONS...1 KIT CONTENTS...3 CONTROL HOUSING ASSEMBLY...5 CHAPTER

More information

DANGER DANGER. General Information. Safety Is Your Responsibility. Ordering Parts. Contact Information

DANGER DANGER. General Information. Safety Is Your Responsibility. Ordering Parts. Contact Information Safety Safety Is Your Responsibility DANGER To avoid personal injury or death, carefully read and understand all instructions pertaining to the Anthony Liftgates product. Do not attempt to install, operate,

More information

FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES

FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES 01D351-GB FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES DOLOMIT FLOAT SWITCHES The DOLOMIT float switches find application in liquid level control in tanks and wells; they require connection

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

Plumbing and Electrical Installation Guide

Plumbing and Electrical Installation Guide Plumbing and Electrical Installation Guide For new build only, to commence after installation of the C21t tiles. This guide must be left with the property owner after installation. Issue: 02:December 08

More information

building engineering services association specification for: Domestic Heating www.thebesa.com

building engineering services association specification for: Domestic Heating www.thebesa.com building engineering services association specification for: Domestic central Heating installation www.thebesa.com building engineering services association acknowledgments Guide to good practice: Domestic

More information

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk 1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

INSTALLATION, OPERATION, MAINTENANCE AND PARTS MANUAL 'J' SERIES - GAS FIRED STEAM BOILERS (6J - 60J)

INSTALLATION, OPERATION, MAINTENANCE AND PARTS MANUAL 'J' SERIES - GAS FIRED STEAM BOILERS (6J - 60J) INSTALLATION, OPERATION, MAINTENANCE AND PARTS MANUAL 'J' SERIES - GAS FIRED STEAM BOILERS (6J - 60J) This Manual must be available to the boiler operator at all times. JGAS-E-10 2008 In case of Emergency

More information

ClearView 100. Instruction Manual

ClearView 100. Instruction Manual ClearView 100 Instruction Manual Important Safeguards This appliance is not intended for use by children or infirm persons without supervision. Young children should be supervised to ensure that they do

More information

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw ,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted

More information

SWIMMING POOL HEAT PUMP Owners Manual

SWIMMING POOL HEAT PUMP Owners Manual SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor

More information

www.the Floor Heating Warehouse.co.uk

www.the Floor Heating Warehouse.co.uk www.the Floor Heating Warehouse.co.uk Underfloor Heating Installation Guide (Grundfoss Pump System) General Overview: Our water based underfloor heating system can be installed by your own plumber or heating

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you

More information

Installing a new 928 Motorsports All-Aluminum Radiator

Installing a new 928 Motorsports All-Aluminum Radiator 928 Motorsports Supercharger Installation Copyright 2008, 928 Motorsports, LLC All Rights Reserved Installing a new 928 Motorsports All-Aluminum Radiator Copyright 2008 928 Motorsports, LLC. Toll-Free

More information

ATTENTION This is a general warning that failure to follow instructions could result in poor functioning of the unit.

ATTENTION This is a general warning that failure to follow instructions could result in poor functioning of the unit. 1. Description The macerating system of this unit is installed in a case, specifically designed for horizontal outlet spigots. This macerator is manufactured in a factory which is quality certified to

More information

Technical Guide 08/15/14

Technical Guide 08/15/14 Technical Guide 08/15/14 1 Table of Contents Contact information.3 Identifying your system..4-8 Model Number Serial number location Parts of your fuel system..9-14 Fuel pump diagram Wire harness schematics

More information

Eurovacuum EV Series. Single Stage Oil Sealed Rotary Vane Pump

Eurovacuum EV Series. Single Stage Oil Sealed Rotary Vane Pump Eurovacuum EV Series Single Stage Oil Sealed Rotary Vane Pump Eurovacuum EV Series Single Stage Oil Sealed Rotary Vane Pumps Eurovacuum Company is offering its various products to meet industrial vacuum

More information

Rotary IBC AdBlue Pump

Rotary IBC AdBlue Pump Installation, Operating, Maintenance & Safety Instructions Rotary IBC AdBlue Pump RHP105 Important Information It is important to ensure that this pump is both handled and operated in accordance with the

More information

1. RANGE OF APPLICATION 3. SAFETY INSTRUCTIONS 4 4. DESIGN 4

1. RANGE OF APPLICATION 3. SAFETY INSTRUCTIONS 4 4. DESIGN 4 Henco Snelselectie kaart EN IMPORTANT! Before starting work the fitter must carefully read this installation and operation manual, understand and observe its conditions. The water floor heating control

More information