KEMKO, INC. METAL BUILDING SYSTEM SPECIFICATIONS

Size: px
Start display at page:

Download "KEMKO, INC. METAL BUILDING SYSTEM SPECIFICATIONS"

Transcription

1 KEMKO, INC. METAL BUILDING SYSTEM SPECIFICATIONS 1. GENERAL 1.1. SCOPE These specifications apply to metal building systems as designed, engineered and fabricated and by Kemko, Inc. ( Kemko ) These specifications describe Kemko s standard metal building systems. In the absence of contract requirements or restrictions to the contrary, these specifications accurately describe the product provided by Kemko. However, these specifications are in no way intended to limit the available options associated with Kemko s metal buildings These specifications are intended for use by architects, engineers, building code officials and Kemko s employees, customers, and vendors Because of a continuing program of research and development these specifications are subject to change without notice BASIC BUILDING TYPES Symmetrical Gable is a continuous frame building with the ridge in the center of the building, consisting of tapered or straight columns and tapered or straight rafters. Sidewall and endwall girts typically by-pass the columns, but they may be flush in the column line. The building may or may not have interior columns Unsymmetrical Gable is a continuous frame building with an off-center ridge, consisting of tapered or straight columns and rafters. Eave height and roof slope may differ on each side of the ridge. Sidewall and endwall girts typically by-pass the columns, but they may be flush in the column line. The building may or may not have interior columns Single Slope is a continuous frame building which does not contain a ridge, but has one continuous roof sloping from side to side. The primary framing consists of straight or tapered columns and rafters. Sidewall and endwall girts typically by-pass the columns, but they may be flush in the column line. The building may or may not have interior columns Lean-to is a building addition which does not contain a ridge, but has one continuous roof slope from side to side. These buildings rely on the frame of another building for partial support BUILDING NOMENCLATURE Primary frames form the backbone of the building. They are constructed from either hot-rolled wide flange beams or built-up welded steel I shaped members. Kemko never uses light gauge steel to construct its primary framing Secondary framing typically consists of purlins, girts and eave struts that are made from 12, 14 and 16 gauge cold-rolled steel. Secondary framing spans between the primary framing and, among other things, supports the wall and roof panels and carries the building loads to the primary framing Roof Slope is expressed as inches of rise for each 12" of horizontal run Building Width is measured from outside face to outside face of sidewall girts Eave Height is the nominal dimension measured from the level of the finished floor to the intersection of the inside of the roof and sidewall sheets.

2 Building Length is measured from outside face to outside face of endwall girts Bay Spacing is the distance between the primary frames measured along the sidewall Auxiliary Loads are the dynamic loads induced by cranes, conveyors, or other material handling systems Collateral Loads are the weights of any non-moving equipment or material, such as ceilings, electrical or mechanical equipment, sprinkler systems, plumbing, or ceilings Dead Load is the actual weight of the building system supported by a given member Floor Live Loads are the loads induced on a floor system by occupants of a building and their furniture, equipment, etc Roof Live Loads are the loads produced by maintenance activities, rain, erection activities, and other movable or moving loads but not including wind, snow, seismic, crane, or dead loads Roof Snow Load is the gravity load induced by the weight of snow or ice on the roof, assumed to act on the horizontal projection of the roof Seismic Loads are the loads acting in any direction on a structural system due to the action of an earthquake Wind Loads are the loads on a structure induced by the forces of wind blowing from any horizontal direction Importance Factors are incorporated into wind, seismic and other load calculations and account for the degree of hazard to human life, damage to property and importance of the structure to the welfare of the community Exposure Categories are based on the upwind ground surface roughness conditions, determined by natural topography, vegetation and adjacent structures. A building constructed in a wide open area will be designed to a higher standard than one totally surrounded by large obstructions. 2. DRAWINGS 2.1. Kemko shall furnish the following drawings with all metal building systems for the proper identification and assembly of building components Anchor Bolt Plan: Shows the diameter, length location and projection of all anchor bolts for the components of the metal building system. Column reactions will also be shown Erection Drawings: Roof and wall erection (framing) drawings that identify individual components and accessories furnished by Kemko in sufficient detail to permit proper erection of the metal building system Certifications: All standard drawings sets will contain summarized engineering data and will bear the seal of a registered professional engineer. Detailed design calculations will be kept on file by Kemko and will be available on request. 3. STRUCTURAL STEEL DESIGN 3.1. GENERAL Kemko shall use standards, specifications, recommendations, findings and/or interpretations of professionally recognized groups such as American Institute of Steel Construction (AISC), American Iron and Steel Institute (AISI), American Welding Society (AWS), ASTM International (formerly the American Society for Testing and Materials, ASTM), Metal Building Manufacturer s Association (MBMA), and the Society for Protective Coatings (SSPC) as the basis for establishing engineering, design, fabrication, and quality criteria, practices, and

3 tolerances. Kemko s engineering, design, fabrication and quality criteria, practices, and tolerances shall govern, unless specifically stated otherwise in the contract documents Structural mill, or welded up plate components shall be designed in accordance with AISC s Specification for Structural Steel for Buildings, latest edition using ASD or LRFD method Cold-formed steel structural members will be designed in accordance with AISI s Specification for the Design of Cold-formed Steel Structural Members, latest edition DESIGN LOADS Design loads shall be as specified on Kemko s drawings and set forth in the contract documents. Design loads typically include dead load, live loads; seismic loads wind loads collateral loads, auxiliary loads, floor loads, and other specified loads. Loads are also affected by importance factors based on the intended use of the building and deflection limits based on materials used in the building DEFLECTION AND DRIFT Kemko s standard design practices incorporate serviceability limits from the applicable building codes and professional standards. Owner requirements that exceed Kemko s standards must be included in the building contract documents. The applicable building code may also provide deflection limitations. Flexible Ceiling schedule will be used for buildings that have suspended or sheet rock ceilings. Flexible Wall schedule will be used for buildings that have some type of flexible exterior wall material (e.g., wood or HardiePlank ). Brittle Ceiling schedule will be used for buildings that have plaster ceilings. Brittle Wall schedule will be used for buildings that have masonry, glass, stucco, EIFS, or similar type materials. See next page.

4 Metal Roof & Wall Panels Endwall Column L/120 Endwall Rafter (live) L/180 Endwall Rafter (wind) L/180 Wall Girt L/90 Roof Purlins (live) L/150 Roof Purlins (wind) L/150 Flexible Walls Endwall Column L/120 Endwall Rafter (live) L/180 Endwall Rafter (wind) L/180 Wall Girt L/120 Roof Purlins (live) L/150 Roof Purlins (wind) L/150 Brittle Walls Endwall Column L/240 Endwall Rafter (live) L/180 Endwall Rafter (wind) L/180 Wall Girt L/240 Roof Purlins (live) L/150 Roof Purlins (wind) L/150 Wall Panel L/60 Wall Panel L/60 Wall Panel L/60* Rigid Frame (horizontal) H/60 Rigid Frame (vertical) L/180 Wind Framing H/60 Flexible Ceilings Endwall Column L/120 Endwall Rafter (live) L/240 Endwall Rafter (wind) L/240 Wall Girt L/90 Roof Purlins (live) L/240 Roof Purlins (wind) L/240 Wall Panel L/60 Rigid Frame (horizontal) H/60 Rigid Frame (vertical) L/240 Wind Framing H/60 Rigid Frame (horizontal) H/60 Rigid Frame (vertical) L/180 Wind Framing H/60 Brittle Ceilings Endwall Column L/120 Endwall Rafter (live) L/360 Endwall Rafter (wind) L/360 Wall Girt L/90 Roof Purlins (live) L/360 Roof Purlins (wind) L/360 Wall Panel L/60 Rigid Frame (horizontal)h/60 Rigid Frame (vertical) L/360 Wind Framing H/60 Rigid Frame (horizontal) H/120 Rigid Frame (vertical) L/180 Wind Framing H/120 * - If EIFS is attaching to metal panels, use L/240.

5 4. BASIC MATERIAL SPECIFICATIONS 4.1. PRIMARY FRAMING STEEL Steel for Wide-Flange Beams shall conform to the requirements of ASTM Specification A992 Grade 50, with a minimum yield of 50 ksi. All other hot-rolled shapes, including Channels and S-Beams, shall conform to ASTM A-36 or A-572, with a minimum yield of 36 ksi Steel for the web and flange portions of built-up sections shall conform to ASTM A-1011, A 529, A 572 or ASTM A-36 as applicable, with minimum yield of from 42 to55 ksi as indicated by the design requirements Pipe shall conform to the requirements of ASTM A 53 Grade B with a minimum yield strength of 35 ksi X-Bracing shall conform to ASTM A 36 for rod bracing and ASTM A 475 for cable bracing SECONDARY FRAMING STEEL Steel for purlins, girts, eave struts, and C sections shall conform to the requirements of ASTM A-1011 Grade 55. Minimum yield shall be 55 ksi Steel used to form galvanized purlins, girts, eave struts, and C sections shall conform to the requirements of ASTM A-653 G90 Grade 55. Minimum yield shall be 55 ksi ROOF AND WALL PANEL MATERIAL Panel material specified as 26 gauge (.0185 min.) shall be Galvalume or Galvalume Plus material conforming to the requirements of ASTM A792 Grade 80. Minimum yield stress shall be 80 ksi (industry standard Grade E.) Panel material specified as 24 gauge (.023 min.) shall be Galvalume or Galvalume Plus material conforming to the requirements of ASTM A792 Grade 50. Minimum yield stress shall be 50 ksi (industry standard Grade D.) Panel material specified as 22 gauge (.029 min.) shall be Galvalume or Galvalume Plus material conforming to the requirements of ASTM A792 Grade 50. Minimum yield stress shall be 50 ksi (industry standard Grade D.). 5. STRUCTURAL FRAMING SPECIFICATIONS 5.1. GENERAL All framing members shall be shop fabricated for field bolted assembly. The surfaces of the bolted connections shall be smooth and free from burrs or distortions All shop-welded connections shall be in accordance with the American Welding Society (AWS) Code for Building Construction All framing members, where necessary, shall have an identifying mark Visual inspection methods will be used for verification of weld quality as outlined by the AWS Structural Steel Welding Code, Visual Inspection Acceptance Criteria, Table PRIMARY FRAMING Rigid Frame: All rigid frames shall be welded built-up sections or mill shapes as required by design specifications. The built-up columns and rafters may be either constant or tapered depth. Flanges shall be connected to webs by means of a continuous fillet weld on one side.

6 Endwall Frames: All endwall roof beams and endwall columns shall be mill-rolled sections, or built-up I sections depending on design requirements Plates, Stiffeners, etc.: All base plates splice plates, cap plates, and stiffeners shall be factory welded into place on the structural members Bolt Holes: All base plates, splices, and flanges shall be shop fabricated to include bolt connection holes. Webs shall be shop fabricated to include bracing holes SECONDARY FRAMING Minimum decimal equivalent thicknesses for gauges are as follows: 16 Gauge inches 14 Gauge inches 12 Gauge inches Purlins and Girts: Purlins and girts shall be cold-formed Z sections with stiffened flanges. They shall be pre-punched at the factory to provide for field bolting to. They shall be flush or by-pass as required by design and the contract documents. Connection bolts will install through the webs and flanges as necessary Eave Struts: Eave Struts shall be unequal flange cold-formed C sections Base Angle: A base member will be supplied by which the base of the wall covering may be attached to the perimeter of the slab. Base angle shall be secured to the concrete slab with expansion anchors BRACING Diagonal Bracing: Diagonal bracing in the roof and sidewalls shall be used to remove longitudinal loads (wind, crane, etc.) from the structure. This bracing will be furnished to length and equipped with a bevel washer, flat washer, and nut at each end. It may consist of rods threaded at each end or galvanized cable with suitable threaded-end eyebolts. If load requirements so dictate, bracing may be of structural angle and/or pipe, bolted in place Flange Bracing: The compression flange of all primary framing shall be braced laterally with angles connecting to the webs of purlins or girts so that the flange compressive stress is within allowable limits for any combination of loadings Special Bracing: When load requirements or window and door placements do not allow diagonal bracing, a wind bent frame, wind column, or fixed base columns will be used. 6. ROOF AND WALL COVERING 6.1. GENERAL Standard roof and wall panels shall be PBR profile Kemko offers a wide variety of other panel profiles and panel coating systems. For specific details and costs, contact Kemko at STANDARD PANEL DESCRIPTION PBR profile panels shall have major ribs 1 ¼ high spaced 12 on center, with a purlin bearing leg. In the flat area between the major ribs are two smaller ribs. Each panel shall provide 36 net coverage in width. All sidelaps shall be at least one major rib.

7 Panel Length: All wall panels shall be continuous from sill to roofline and all roof panels shall be continuous from eave to ridge except where lengths become prohibitive for handling purposes. All end laps shall be at least 6 on roof, 4 on walls, and 3 on wall lights Endwall Edge Cuts: All endwall panels for buildings with 1:12, or less, roof slope shall be square cut. All endwall panels for buildings with more than a 1:12 roof slope shall be bevel cut in the field by the building erector if necessary. 7. MISCELLANEOUS MATERIAL SPECIFICATIONS 7.1. FASTENERS Structural Bolts: All bolts used in frame splices shall comply with ASTM A325 or A325T. The nuts used shall comply with ASTM 563, and the washers, when specified, shall comply with ASTM A All bolts used in connections of secondary framing to primary framing shall be zinc plated ANSI Grade 2, ASTM A307. The nuts used shall comply with ASTM 563, and the washers, when specified, shall comply with ASTM Fasteners for Roof Panels: All panels shall be attached to the secondary framing members by means of #12-14 x 1-1/4 self-drilling structural carbon steel screws with a long-life zinc-alloy head, with or without paint, assembled with an EPDM washer. These fasteners are applicable for use with fiberglass blanket insulation up to 4 thick. If no roof insulation is present, #12 x 1 self-drilling screws with a long-life zinc alloy head and EPDM washers will be used. All self-drilling lap screws are ¼ -14 x 7/8 with a long-life zinc alloy head and EPDM washer, regardless of structural screw length Fasteners for Wall Panels: Wall panels shall be attached to the secondary framing members by means of a self-drilling fastener made of carbon steel, #12 x 1-1/4 hex washer head with EPDM washers for fiberglass insulation up to 3 thick and #12 x 1-1/2 for fiberglass insulation 4 to 6 thick. If no wall insulation is present, #12 x 3/4 hex washer head screws with EPDM washers will be used. Screws for panel laps shall be with self-drilling ¼ -14 x 7/8 hex washer head with EPDM washers Anchor Bolts: All anchor bolts shall comply with ASTM F SEALANTS AND CLOSURES Closure Strips: The corrugations of the roof and wall panels shall be filled with solid or closed-cell, preformed rubber, neoprene or polyethylene closures where required Sealants: Roof panels shall be installed with a tape sealer. This material shall be a butyl base elastic compound with a minimum solid content of 99%, and shall be Schnee-Morehead #5227 or equal. The sealer shall have good adhesion to metal and be non-staining, non-corrosive, non-shrinking, non-oxidizing, nontoxic and nonvolatile GUTTER, FLASHING & DOWNSPOUTS Gutters and Flashing: Gutters and rake shall be 26 (.0185 min.) gauge Galvalume or Galvalume Plus steel conforming to ASTM A792, with a minimum yield of 50 ksi (industry standards Grade D) Downspouts: All downspouts shall be rectangular in shape and shall be 26 gauge (.0185 min.) Galvalume or Galvalume Plus steel conforming to ASTM A792, with a minimum yield of 50 ksi (industry standards Grade D). 8. PAINTING 8.1. STRUCTURAL PAINTING

8 All uncoated structural steel shall be cleaned and primed as required by the Society for Protective Coatings (SSPC) as follows: Primary framing steel preparation specification shall be SSPC-SP Primary framing will be painted with Kemko s standard red oxide primer Pre-coated cold-form members shall be cleaned according to SSPC-SP 8 or SSPC-SP 6, and then chemically pretreated before being coated with a minimum of.5 mils of polyester based red primer. The primer contains a wax type lubricant to facilitate roll-forming and deter marring during these operations. Hairline crazing, which may occur during forming operations, is considered normal. Special preparation is required before a finish coat can be applied over this wax finish. Note: Primer systems are not intended as finish coat paint systems and do not offer the uniformity of appearance, durability or corrosion resistance of a top coat applied over a primer. Primers are designed to promote the wetting action and adhesion of a top coat and offer only short-term corrosion protection from ordinary atmospheric exposure. Primer is compatible only for top coating with solvent-based alkyd and modified alkyd top coat paints. Abrasions caused by handling after paintings as well as the flaking of tight mill scale are to be expected PAINTED PANELS The painted panel exterior finish shall be either Siliconized Polyester, or Kynar 500 as specified in the contract documents Interior Finish: The painted panel interior finish shall have a white or parchment top coat over epoxy primer or an epoxy base coat, white or parchment, with a clear polyester top coat. 9. ACCESSORIES 9.1. WINDOWS Standard windows shall be self-framing horizontal slide, vertical single hung or fixed narrow lite units. They are available in a variety of sizes PERSONNEL DOORS Personnel door shall be 3 x 7 single leaf, 4 x 7 single leaf or 6 x 7 double leaf manufactured from 20 gauge galvanized steel Door leafs shall have an embossed finish with a white prime coat Door leafs shall be solid, half glass, or side vision (narrow lite) Doors shall be constructed for non-hand installation The standard lockset shall have a lever passage handle OVERHEAD DOORS Doors will be Overhead Door Corporation Model 790 unless otherwise specified Doors shall be designed to resist applicable wind loads and are available in a variety of sizes Door Framing: Overhead door support framing shall be designed to resist applicable wind loads and shall typically consist of cold-formed C jambs with a cold-formed C header at the top of the opening. Cold-formed C framing will be galvanized unless specified otherwise If wind loads are sufficiently high or other factors warrant it, mill-rolled channels will be used in lieu of cold-rolled C sections. Mill-rolled channels will be primer painted unless otherwise specified.

9 9.4. GRAVITY VENTILATORS Gravity ridge ventilators shall be manufactured from Galvalume A792 Grade 50 pre-painted or bare. The ventilator body shall be 26 gauge (.0185 min.) with flat skirts and shall be pre-formed for a 1:12 pitch. Ventilators shall be equipped with birdscreens, dampers, and riveted end caps. Ventilators shall be 10 long and have a 9 throat. Twelve inch throat ventilators are available as an option Round ventilators shall be 24 gauge and shall have an adjustable base for ridge mounting or a pitched base for on-slope mounting LOUVERS Louver frames shall be 18 gauge galvanized steel frame with 20 gauge blades, and shall be self-framing and selfflashing. The color shall be as specified by the customer. They shall be equipped with adjustable or fixed blades as specified LIGHT TRANSMITTING PANELS High Strength light transmitting panels are fiberglass reinforced polyester and shall comply with ASTM D3841, Type CC2, and Grade 2. Standard light transmitting panels will match Kemko s standard PBR roof panels INSULATION Fiberglass Blanket Insulation shall conform to ASTM specification C991 NAIMA 404. Standard insulation shall be 3 and 4 thick. (R-10 and R-13 respectively). Other insulation systems with higher R values are available The standard facing for fiberglass insulation shall be reinforced white vinyl WMP-VR. Other facings are available. 10. ERECTION AND INSTALLATION Building erection and the installation of accessories shall be performed in accordance with erection drawings by a Kemko erection crew, or an otherwise qualified erector using proper tools and equipment. Erection practices shall conform to MBMA s Metal Building Systems Manual, latest edition There shall be no field modifications to primary structural members except as authorized and specified by Kemko. 11. BUILDING ANCHORAGE AND FOUNDATION The building anchor bolts shall be designed to resist the maximum column reactions resulting from the specified combinations of loadings. These designs and sizes shall be specified by Kemko. Anchor bolts typically are supplied by Kemko Foundations shall be adequately designed by a qualified foundation engineer to support the building reactions and other loads that may be imposed by the building use. The design shall be based on the specific soil conditions of the building site. The engineering of the foundation may or may not be provided by Kemko. Kemko assumes no responsibility for the integrity of any foundation designed by others or stamped by an engineer other than one of Kemko s choosing. 11. WARRANTIES Kemko offers a variety of warranties for panel coatings, roof systems, weather tightness, and manufactured materials. For specific warranty details, contact Kemko at

VALOR STEEL BUILDINGS STANDARD SPECIFICATIONS

VALOR STEEL BUILDINGS STANDARD SPECIFICATIONS VALOR STEEL BUILDINGS STANDARD SPECIFICATIONS For Rigid/I- Beam Construction as designed, engineered, and fabricated by Valor Steel Buildings. General 1.1) Valor shall use standards, specifications, recommendations,

More information

Preformed Metal Roofing and Siding

Preformed Metal Roofing and Siding Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision

More information

Specifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023

Specifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023 Specifications Preformed Metal Wall and Roof Panels Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023 Section 07410 Preformed Metal Wall and Roof Panels Structural

More information

SECTION 07400 STANDING SEAM METAL ROOF

SECTION 07400 STANDING SEAM METAL ROOF SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and

More information

ATLANTA MODEL SPECIFICATIONS

ATLANTA MODEL SPECIFICATIONS ATLANTA MODEL 50 SPECIFICATIONS Dimensions: Roof Dimensions (point to point) 50-0 Column Dimensions (out to out of columns) 44-0 Eave Height 8-0 Roof Height @ Peak ±21-8⅞ Hip Roof 6:12 pitch Square Feet

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

DENVER MODEL 30 X 30 SPECIFICATIONS

DENVER MODEL 30 X 30 SPECIFICATIONS DENVER MODEL 30 X 30 SPECIFICATIONS Dimensions: Roof Dimensions 30-0 x 30-0 (4) Columns (Center to Center) 25-6½ x 25-6½ Minimum Clearance 8-0 Roof Height @ Peak Dependent on Col. Ht. Hip Roof 4:12 pitch

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

COLORADO MODEL. 35 x 65 SPECIFICATIONS

COLORADO MODEL. 35 x 65 SPECIFICATIONS COLORADO MODEL 35 x 65 SPECIFICATIONS Dimensions: Roof Dimensions 35-0 x 65-0 Column Dimensions (center to center) 31-0 x 30-6 Minimum Clearance 14-0 Roof Height @ Peak ±18-8 Curved Roof ±42-6 radius Square

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

The Olympia Difference

The Olympia Difference The Olympia Difference Valued Customer, Thank you for choosing Olympia Steel Buildings as the solution to your building needs. You can be confident that the Olympia team of professionals will provide you

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

STANDARD PRODUCT Specifications

STANDARD PRODUCT Specifications 1. GENERAL 4. STRUCTURAL FRAMING STANDARD PRODUCT 1.1. SCOPE... 3 4.1. GENERAL... 6 1.1.1. Intent.... 3 4.1.1. Field Bolt Assembly.... 6 1.1.2. Performance... 3 4.1.2. Shop Connections...... 6 1.1.3. Product

More information

INSTALLATION MANUAL For Grand Rib-3 / Multi Purpose / & Classic Rib Roofing Panels

INSTALLATION MANUAL For Grand Rib-3 / Multi Purpose / & Classic Rib Roofing Panels INSTALLATION MANUAL For Grand Rib-3 / Multi Purpose / & Classic Rib Roofing Panels Grand Rib-3 / Multi-Purpose / Classic Rib Grand Rib-3 / Multi-Purpose / & Classic Rib Grand Rib 3 panels are a strong,

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

METAL BUILDING SYSTEMS

METAL BUILDING SYSTEMS BUILDING SYSTEMS The Brand of Choice METAL BUILDING SYSTEMS www.nucorbuildingsystems.com Building Systems The Brand of Choice Nucor Building Systems, a division of Nucor Corporation, is one of the most

More information

SECTION 07 61 13 STANDING SEAM METAL ROOFING

SECTION 07 61 13 STANDING SEAM METAL ROOFING SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced

More information

Holiday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated.

Holiday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standing-seam metal roofing, custom fabricated. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: Show installation

More information

SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK

SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,

More information

Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..

Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers.. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3

More information

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,

More information

Chapter 6 ROOF-CEILING SYSTEMS

Chapter 6 ROOF-CEILING SYSTEMS Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;

More information

March 14, 2007. Installation of Bay, Bow and Garden Windows

March 14, 2007. Installation of Bay, Bow and Garden Windows March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed

More information

GUIDELINE SPECIFICATIONS

GUIDELINE SPECIFICATIONS GUIDELINE SPECIFICATIONS GORDON SOFFIT-SHIELD - An Exterior Metal Soffit System DIVISION 05 5800 or DIVISION 07 7700 Note To Specifier: SOFFIT-SHIELD should be installed by tradesmen that are experienced

More information

- - - - Steel Panel Frame. Exterior Steel Sheeting. Optional Rigid Insulation. Optional Steel Insulation Liner

- - - - Steel Panel Frame. Exterior Steel Sheeting. Optional Rigid Insulation. Optional Steel Insulation Liner The Kelly Klosure pre-framed modular panel has 4 components that are factory finished to create an easy and versatile bolt-together system in the field. Steel Panel Frame Exterior Steel Sheeting Optional

More information

Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions

Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions All questions and concerns please call 904-696-9700 Discount Direct Metal Roofing Plus Rib metal roofing panels are a strong,

More information

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed

More information

Standing Seam Roof Systems

Standing Seam Roof Systems Standing Seam Roof Systems REAL PEOPLE. REAL PRODUCTS. REAL SOLUTIONS. www.a-s.com Building Benefits You Can Expect From A&S Materials Standing Seam roof panels weigh a relatively modest 11/2 pounds per

More information

INSTALLATION OF A BAY WINDOW

INSTALLATION OF A BAY WINDOW INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening

More information

Federal Steel Systems: Metal Building Terminology

Federal Steel Systems: Metal Building Terminology Federal Steel Systems Federal Steel Systems: Metal Building Terminology 925 S. Niagara Street, Suite 250 Denver, Colorado 80224 Toll-Free: 1-855-885-9570 info@federalsteelsystems.com http://federalsteelsystems.com

More information

Chapter 3 - Structural Design

Chapter 3 - Structural Design Chapter 3 - Structural Design 3.0 General 3.0.1 Design Overview Greenhouse buildings are a complete structure including the structural support and enclosure elements. The primary structural system includes:

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS

SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS 1 SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

BRIDGE & SUPPLY COMPANY. Installation Guide. Ultra 2000. Includes:

BRIDGE & SUPPLY COMPANY. Installation Guide. Ultra 2000. Includes: BRIDGE & SUPPLY COMPANY Installation Guide Ultra 2000 Includes: Ultra 2000 Installation Guide Stock Trim Profiles Ultra 2000 Trim Installation Guide Page 2 Table of Contents Ultra 2000 Profile, Colors

More information

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system

More information

Metal Building Systems Installation and Flashings & Details Guide. Table of Contents

Metal Building Systems Installation and Flashings & Details Guide. Table of Contents Table of Contents Section Page Notes to Designer/User..................1-2 Map of Typical Roof Conditions............3 Fastener Placement.......................4 Fastener Selection........................5

More information

Window Installation Instructions

Window Installation Instructions Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for

More information

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel

More information

Commercial And Industrial Steel Buildings

Commercial And Industrial Steel Buildings Commercial And Industrial Steel Buildings Arco Building Systems, Inc. Since 1979 Arco has been providing the highest quality steel buildings to contractors and owners throughout the United States. Leadership

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

SECTION 07410 METAL ROOF SYSTEM

SECTION 07410 METAL ROOF SYSTEM SECTION 07410 METAL ROOF SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and General Provisions of Contract, including General Conditions and other Division 1 Specification Sections, apply to

More information

Sports and High Mast Lighting Poles Phone: (866) 474-7200 Fax: (817) 924-7049

Sports and High Mast Lighting Poles Phone: (866) 474-7200 Fax: (817) 924-7049 Sports and High Mast Lighting Poles 4 High Mast Lighting Poles General American LitePole offers a raising and lowering system that allows for ease of maintaining the lighting system at ground level. Ideal

More information

Section Page Section Page

Section Page Section Page Western States Western Rib Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer / Installers..1 Fastener Placement and Selection.2-3 Key

More information

PANELIZED HOME INSTALLATION GUIDELINE

PANELIZED HOME INSTALLATION GUIDELINE PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

Sapa: SECTION 05520 ARCHITECTURAL ALUMINUM HANDRAILS AND RAILINGS

Sapa: SECTION 05520 ARCHITECTURAL ALUMINUM HANDRAILS AND RAILINGS PART 1 GENERAL Sapa: SECTION 05520 ARCHITECTURAL ALUMINUM HANDRAILS AND RAILINGS 1.1 SECTION INCLUDES A. Aluminum and Glass Handrails B. Aluminum Railings 1.2 RELATED SECTIONS A. Section 05700 - Ornamental

More information

CLEAR-DIVISIONS CENTERFOLD

CLEAR-DIVISIONS CENTERFOLD CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in

More information

Installation Manual for STANDING SEAM ROOFING

Installation Manual for STANDING SEAM ROOFING Installation Manual for STANDING SEAM ROOFING Absolute Steel Toll Free 877-833-3237 / Phone 480-768-1618 / Fax 480-768-1514 www.metalroofingsource.com Standing Seam features approximately one-inch high

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE

MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE This specification is intended to describe the general requirements applicable to a proper structural mezzanine design. In addition, it is to serve as

More information

Introduction...COMB-2 Design Considerations and Examples...COMB-3

Introduction...COMB-2 Design Considerations and Examples...COMB-3 SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant

More information

CLEAR-DIVISIONS APERTO

CLEAR-DIVISIONS APERTO CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide

Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3

More information

STEEL BUILDINGS RECOMMENDED INSTALLATION GUIDE

STEEL BUILDINGS RECOMMENDED INSTALLATION GUIDE STEEL BUILDINGS RECOMMENDED INSTALLATION GUIDE 3 TO 30 METRE SPAN TILT UP METHOD SUPPLIED BY: Last update 8 December 2010 2010 FBHS (Aust) Pty Limited FBHS (Aust) Pty Limited ABN 83 126 232 504 trading

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................

More information

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035 Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí

More information

INSTALLATION. General. Important Note. Design. Transport

INSTALLATION. General. Important Note. Design. Transport General The roof trusses you are about to install have been manufactured to precise engineering standards. To ensure that the trusses perform as designed, it is essential that they be handled, erected

More information

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3. Pages identified with the NMBS Logo as shown above, have been produced by NMBS to assist specifiers and consumers in the application of New Millennium Building Systems Deck products. Pages identified with

More information

LEGACY REPORT ER-5110. www.icc-es.org. ICC Evaluation Service, Inc. Reissued November 1, 2003. Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER-5110. www.icc-es.org. ICC Evaluation Service, Inc. Reissued November 1, 2003. Legacy report on the 1997 Uniform Building Code LEGACY REPORT Reissued November 1, 2003 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems The Butler MR-24 Standing Seam Roof Difference A comparison between metal roof systems Roof Systems Necessities Weathertight (don t leak!) Low maintenance Weathertightness Roof clips, seams, panel alignment

More information

CLEAR-DIVISIONS VARIOFOLD

CLEAR-DIVISIONS VARIOFOLD CLEAR-DIVISIONS VARIOFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS VARIOFOLD moveable The yellow highlighted areas in the

More information

Prefab Instruction Manual

Prefab Instruction Manual Prefab Instruction Manual http://www.muellerinc.com TABLE OF CONTENTS A. Site and Foundation Preparation 1. General Information 2. Squaring of Foundation 3. Anchor Bolt Settings (Pgs. 3,4) B. Building

More information

Product Catalog. Extreme Roofing, Inc. 2680 Rt. 982 Mammoth, PA 724.838.7695 www.extremeroofinginc.com

Product Catalog. Extreme Roofing, Inc. 2680 Rt. 982 Mammoth, PA 724.838.7695 www.extremeroofinginc.com 2012 Product Catalog Extreme Roofing, Inc. 2680 Rt. 982 Mammoth, PA 724.838.7695 www.extremeroofinginc.com 2 PH. 724.838.7695 Email. sales@extremeroofinginc.com Website. www.extremeroofinginc.com Fax.

More information

Packaged Terminal Air Conditioner Wall Sleeve Installation

Packaged Terminal Air Conditioner Wall Sleeve Installation Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation

More information

FLAT ROOF CARPORT RECOMMENDED INSTRUCTION MANUAL

FLAT ROOF CARPORT RECOMMENDED INSTRUCTION MANUAL FLAT ROOF CARPORT RECOMMENDED INSTRUCTION MANUAL Table of Contents Introduction... 2 Components... 3 Step 1 Marking out the Perimeter of the Carport... 3 Step 2a Footing Set-Out for Concrete Block Pad

More information

EAST LYME HIGH SCHOOL

EAST LYME HIGH SCHOOL Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed

More information

Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin

Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin americancraftsmanwindows.com Project Requirements: Failure to follow these instructions may void product

More information

STANDING SEAM SHEET METAL ROOFING

STANDING SEAM SHEET METAL ROOFING STANDING SEAM SHEET METAL ROOFING GENERAL INFORMATION 1.1 For all standing seam metal roofing work consult Columbia University Facilities Exteriors and Historic Preservation group. 1.2 Fabricator is responsible

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

SECTION 07411 STANDING SEAM METAL ROOFING

SECTION 07411 STANDING SEAM METAL ROOFING PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Standing-seam metal roof. 2. Metal gutters. 1.2 DEFINITIONS A. Metal Roof Panel Assembly: Metal roof panels, waterproofing membrane (underlayment),

More information

Residential Garage Door Terminology

Residential Garage Door Terminology A Air Infiltration: The leakage or passage of air through a door system Anodize: A hard non-corrosive oxide film on the surface of aluminum Astragal: A compressible or deformable seal provided on the bottom

More information

Additions and Alterations

Additions and Alterations Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal

More information

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit. Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section

More information

Tundra Series Windows January 2016

Tundra Series Windows January 2016 Tundra Series Windows January 2016 New Construction Installation Instructions Nail Fin, J-Fin and Brickmold Aplications product. ATTENTION! Read and understand all installation instructions before installing

More information

STANDARD OPEN PATIO COVER

STANDARD OPEN PATIO COVER STANDARD OPEN PATIO COVER BUILDING & SAFETY DIVISION 201 E. LA HABRA BLVD. LA HABRA, CA 90631 62-90-9710 Call Before You Dig 1-800-227-2600 PLEASE NOTE: This information Bulletin is made available to assist

More information

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes

More information

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description

More information

Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS.

Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS. Austin City Code - Volume II TITLE 25 LAND DEVELOPMENT\CHAPTER 25-12 TECHNICAL CODES\ARTICLE 1: UNIFORM BUILDING CODE\25-12-3 LOCAL AMENDMENTS TO THE BUILDING CODE Chapter 36 - STRAW BALE CONSTRUCTION

More information

SECTION 15140 - PIPE HANGERS AND SUPPORTS

SECTION 15140 - PIPE HANGERS AND SUPPORTS Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the

More information

4572 N Old US 31, Rochester, IN 46975 Toll Free: 877-889-7802 Fax: 574-223-7846 www.ramcosupply.com DETAIL MANUAL. and guide to Ramco Supply products

4572 N Old US 31, Rochester, IN 46975 Toll Free: 877-889-7802 Fax: 574-223-7846 www.ramcosupply.com DETAIL MANUAL. and guide to Ramco Supply products 4572 N Old US 31, Rochester, IN 46975 DETAIL MANUAL and guide to Ramco Supply products Metal Roofing and Siding Panels & Accessories 1 4572 N Old US 31, Rochester, IN 46975 Ramco Supply s RAM Roofing Panels

More information

James M. Pleasants Company

James M. Pleasants Company James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:

More information

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including general and supplementary conditions and other Division 1

More information

1.02 SYSTEM DESCRIPTION

1.02 SYSTEM DESCRIPTION 1 OF 7 MODULAR MEZZANINES GUIDE SPECIFICATIONS FOR PART 1 - GENERAL 1.01 RELATED WORK A. SECTION 03 30 00: Cast in Place Concrete (and Concrete Finishing) 1. The area where mezzanine is installed shall

More information

CH. 2 LOADS ON BUILDINGS

CH. 2 LOADS ON BUILDINGS CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

VERTICAL LOCK Table of Contents

VERTICAL LOCK Table of Contents Table of Contents TABLE OF CONTENTS Vertical Lock Product Data Sheet... 2 Vertical Lock Engineering Data... 3 General Information... 6 Material Testing... 7 Panel Overview... 8 Handling Material & Storage

More information

Page & Turnbull imagining change in historic environments through design, research, and technology

Page & Turnbull imagining change in historic environments through design, research, and technology DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED

More information

City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures

City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures SECTION 7201 - PURPOSE The purpose of this appendix chapter is to establish minimum prescriptive standards

More information

SECTION 6. Glass Storefront Doors:

SECTION 6. Glass Storefront Doors: SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail

More information

n Three 4 x 4 butt hinges per door - prevents wracking and assures smooth positive operation n Heavy duty 16 gauge steel frame

n Three 4 x 4 butt hinges per door - prevents wracking and assures smooth positive operation n Heavy duty 16 gauge steel frame Weather Fin and bulb help keep bad weather outside and good air inside Windows: n Many light kits are available 1-LU 4 X 48 1-LE 16 X 16 1-LA 20 X 24 1-LI 20 X 24 1-B 22 X 36 1-LW 16 X 16 W/GRID 9-LB 22

More information

H-Stud Area Separation Wall System

H-Stud Area Separation Wall System 12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic

More information

Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows

Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows americancraftsmanwindows.com Project Requirements: Read

More information

HORIZONTAL INSTALLATION

HORIZONTAL INSTALLATION THERMO/SOLAR Žiar s.r.o. MANUAL FOR INSTALLATION PV SUPPORTING FRAMES HORIZONTAL INSTALLATION Technical alternation reserved A1410 1 12/2014 CONTENT ORD.NO. PAGE Mounting information 3 Mounting, flat roof

More information

Materials. Estimating Steel. Players. Materials. Shop Drawings. Detailing Process. Standard shapes. Fabricated members, Built-up sections

Materials. Estimating Steel. Players. Materials. Shop Drawings. Detailing Process. Standard shapes. Fabricated members, Built-up sections Materials Standard shapes W sections, C channels, Structural T, Angles, Pipes, Tubes, Rods and Plates Fabricated members, Built-up sections Adding plates to beam flanges, Stiffeners to beam webs Built

More information