Model no s AVI1832, AVI2440, AVI3240, AVI3255, AVI3270, AVI3855, AVI3870
|
|
- Ruby Price
- 7 years ago
- Views:
Transcription
1 Attention: The Certifier Ref: Certification Letter.docx Date: 9 December 2011 Re: Certification of AVI Pizza Oven Hood Model no s AVI1832, AVI2440, AVI3240, AVI3255, AVI3270, AVI3855, AVI3870 To whom it may concern, As per the requirements of the Building Code of Australia Clause A2.2, I hereby certify as a Chartered Professional Engineer of the Institute of Australia (Mechanical College):- 1) That the eyebrow hoods discussed in this certification comply with the relevant Australian Standards listed in the Building Code of Australia. 2) That the certification method complies with Clause A2.2 3) That the ventilation systems described with the model no s AVI1832, AVI2440, AVI3240, AVI3255, AVI3270, AVI3855, AVI3870 are capable of equivalent performance to that required by the Building Code of Australia and it s relevant referenced standard - Australian Standard AS ) That the same ventilation systems comply with the requirements of the Building Code of Australia, Section F (Health & Amenity). The basis of this certification is as follows:- no alterations to the manufacturer plans portrayed on the WOLFE Certification Drawings 1,2 & 3 without experienced engineering input maintenance of the system components in line with the manufacturer s advice no increases to the equipment heat output in the oven model that aligns with the hood model Attached to this certificate is:- a. the current definition of Evidence of Suitability at the time of provision b. Further Discussion, which highlights the calculation methodology, and the calculation results for the derivation of air quantities. c. Further Discussion which highlights compliance with all of the components of the referenced Australian Standard AS d. Required Maintenance activities on which the certification is based. The motivation for not using a conventional kitchen extraction hood includes:- 1. Greater safety surrounding better containment 2. More efficient ventilation service provision Yours sincerely For and on behalf of SEED Rob Lord MIEAust CPEng Director of SEED Chartered Professional Engineer (Institute of Engineers Australia) Mechanical Licence number: rob@seedengr.com ph: ) The use of mechanical ventilation & air conditioning in buildings Mechanical Ventilation for acceptable indoor-air quality. Registered office 24 Ellesmere Street Yeronga ABN
2 Relevant Components of the Building Code of Australia Volume 1 Clause A2.2 Evidence of suitability The following excerpt is provided from within the BCA Volume 1. The components relevant to this certificate are highlighted in BOLD below:- (a) Subject to A2.3 and A2.4, evidence to support that the use of a material, form of construction or design meets a Performance Requirement or a Deemed-to-Satisfy Provision may be in the form of one or a combination of the following: (i) A report issued by a Registered Testing Authority, showing that the material or form of construction has been submitted to the tests listed in the report, and setting out the results of those tests and any other relevant information that demonstrates its suitability for use in the building. (ii) A current Certificate of Conformity or a current Certificate of Accreditation. (iii) A certificate from a professional engineer or other appropriately qualified person which (A) certifies that a material, design, or form of construction complies with the requirements of the BCA; and (B) sets out the basis on which it is given and the extent to which relevant specifications, rules, codes of practice or other publications have been relied upon. (iv) A current certificate issued by a product certification body that has been accredited by the Joint Accreditation System of Australia and New Zealand (JAS-ANZ). (v) * * * * * (vi) Any other form of documentary evidence that correctly describes the properties and performance of the material, (b) Evidence to support that a calculation method complies with an ABCB protocol may be in the form of one or a combination of the following: (i) A certificate from a professional engineer or other appropriately qualified person which (A) certifies that the calculation method complies with a relevant ABCB protocol; and (B) sets out the basis on which it is given and the extent to which relevant specifications, rules, codes of practice and other publications have been relied upon. (ii) Any other form of documentary evidence that correctly describes how the calculation method complies with a relevant ABCB protocol. Page 2 of 12
3 Further Discussion Certification for AVI Pizza Oven Hood What is the ventilation principle behind the AVI Pizza Oven Eyebrow Hood? The prime function of any kitchen canopy is to protect the area surrounding the cooking process from soiled matter and flame to make tolerable and safe the immediate area for people to work in. An air flow is created across the cooking process to capture the fumes created, and the by-products of this vapour shall be collected and contained by means of the filters within the canopy, allowing the cleaner air to be discharged. This is containment. Conveyor pizza ovens allow for the rapid cooking of food products with consistency and ease of operator use. They generally have a large kitchen footprint, a high-input gas burner or electric elements, and a high volume capacity to cook the food at a very high rate. The importance of considering the required ventilation rate as well as the energy input and efficiency for such a powerful appliance cannot be understated. The eye brow hood is also sometimes identified as the pants leg exhaust system. The image below portrays the concept. The entry and exit of the cooking process are each managed by an eyebrow ventilation system and the space in between the two eye brows is provided with an even heat that prevents condensation on any surfaces. Ventilation efficiency is significantly increased with the eyebrow concept as the air quantities required for successful containment are proportional to the area of the eyebrow entry. The eyebrow hood certified in this document has specific features to minimise the eye brow entry area and hence it is capable of significant reduction of exhaust air quantities compared to conventional extraction systems. Page 3 of 12
4 What is the Audit Trail from the Building Code of Australia to the permissible use of this product? The flow chart below is Figure 1.1 General Application of this Standard from AS It establishes that Section 5 and in particular Figure 5.1 is the correct procedure for this application. Page 4 of 12
5 Figure 5.1 of Section 5 allows Local exhaust to be used in lieu for part or all of the general exhaust. It identifies Clause as the legitimate clause for approval and also requires the designer to comply with other elements such as satisfactory discharge of exhaust. Page 5 of 12
6 The clause lists the 5 conditions (a-e) for approval and it is re-presented below:- Page 6 of 12
7 What are the conditions for approval (supplier certification only) and how are they met? Conditions for Approval Effluent shall be collected as close as practicable to the source using special surroundings How are they met? The eyebrow hood style permits the complete surrounding of the cooking process with only the smallest gaps to permit air entry. Local exhaust rates shall be in accordance with relevant Australian Standards or the American Conference of Governmental Industrial Hygienists Industrial Ventilation manual The Australian Standard AS deliberately does not address the airflow rates for local exhaust systems. However, the British Specification for Kitchen Ventilation (HVCA DW/172) does provide for the thermic method and also identifies the use of eyebrow hoods for Conveyor Pizza Ovens. Using the largest oven model XLT , it is derived that an airflow of 420L/s will be required for a 3 bay pizza oven. Certain applicatiosn may require a further 15% increase that is, 483L/s. The exhaust rates specified by the AVI eyebrow hood are 566L/s (i.e. 1200cfm). This airflow rate is the result of Schlieren visualization testing and no reduction in airflows below 566L/s is covered by this certification. Registered office 24 Ellesmere Street Yeronga ABN
8 Conditions for Approval How are they met? The airflow rates from DW/172 is portrayed below. Note that these rates are calculated as per lineal meter :- Local exhaust may be a substitute for general exhaust where the resultant contamination level is equal or less that of general exhaust The schlieren visualization conducted by the Food Service Technology Centre (July 2009) shows no breach of fumes at 1200cfm (566L/s) and hence, it is permissible that this eyebrow hood can replace general exhaust systems. The decision to ventilate the remainder of the kitchen is undertaken by the mechanical designer for the site s installation and is not covered by this certification. Page 8 of 12
9 Conditions for Approval Make-up air openings shall be positioned so as to not be detrimental to capture How are they met? The image below portrays that the hood has clearly defined air intake points. The clearances specified for maintenance (approximately 500mm is nominated in manufacturer s documentation) will permit sufficient air entry without excessive turbulence. Sufficient airflow shall be distributed evenly across the hood The filters within the hood create a self-balancing airflow pattern that stretches across the width of the pizza oven. This criterion is achieved. Page 9 of 12
10 In addition, AS also requires construction related compliance:- Compliance to the kitchen hood references in AS (Appendix C) are valid for the following items:- construction-related items maintenance related items distances between heat sources and grease arresting devices (Continued on the following page) Registered office 24 Ellesmere Street Yeronga ABN
11 Visual inspection of the hoods and review of the workshop drawings confirms construction related compliance with Appendix C:- Compliance with C3.1 is evident. There is a very short stretch of horizontal face adjacent the filter faces but no signs of condensation. This is permissible as Appendix C describes internal surfaces as sloping at 40 0 to the vertical unless the design & performance of hoods prevent the formation of any condensate on such surfaces. Compliance with C3.2 is self-evident. Compliance with C3.3 is evident with the use of the collar or plenum above the hood. Compliance with C3.4.1 is self-evident. As mentioned previously, there is a very short stretch of horizontal face adjacent the filter faces but no signs of condensation. This is permissible as Appendix C describes internal surfaces as sloping at 40 0 to the vertical unless the design & performance of hoods prevent the formation of any condensate on such surfaces. Compliance with C3.4.2 & C3.4.3 is self-evident. Note there are no hood gutters as such there are drains under the filters that are sized to drain captured grease into the removable grease containers. Compliance with C3.4.4 has been demonstrated both on site and with Schlieren visualization testing and thus is self-evident. Compliance with C3.4.5 is self evident. Access is from behind the vapour seal. Page 11 of 12
12 Maintenance & Cleaning Certification for AVI Pizza Oven Hood The following table is provided by the manufacturer s installation manual and this list of activities is the basis of this certification. Note that fire suppression [where installed] will also require maintenance and inspection. Page 12 of 12
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationSafe Method: Gas Safety in Catering Establishments
Safe Method: Gas Safety in Catering Establishments Safety Point Why? What do you do? Gas equipment and services must only be installed, maintained and repaired by a Gas Safe registered installer. Check
More informationKITCHEN HOODS GUIDELINES
KITCHEN HOODS GUIDELINES City of Palo Alto Building Inspection Division 285 Hamilton Ave. Inspection Request: 650 329-2496 Revision Date:6/27/12 General Requirements/Checklist for: Commercial Codes Enforced:
More informationAustralian/New Zealand Standard
Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The
More informationpresents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
More informationCommercial Kitchen Fire Safety
Commercial Kitchen Fire Safety Commercial grade kitchens are a common feature found in many churches today, as religious institutions are providing meals for daycares, soup kitchens, meals on wheels and
More informationPANDA SPRAY BOOTH FILTER INFORMATION
PANDA SPRAY BOOTH FILTER INFORMATION Our Spray Booth has been designed to reduce the risk of potential hazardous situations occurring. You must adhere to the specifications chart listed below when replacing
More informationPart 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery
Part 3 Ancillary technologies Chapter CONTENTS SCOPE Clause Page DESIGN Design standards D1 1 Statutory requirements D2 1 System design D3 1 Building integration D4 2 Noise D5 2 Access and controls D6
More informationPRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133
More informationTR/19 HVCA Guide to Good Practice Internal Cleanliness of Ventilation Systems
TR/19 HVCA Guide to Good Practice Internal Cleanliness of Ventilation Systems SECTION 7 Specific Considerations for Kitchen Extract Systems 7.1 The kitchen extract system presents particular hazards due
More informationAZB 800. Vertical Flue Gas Ducting Ø60/100mm 7 719 001 884
AZB 800 Vertical Flue Gas Ducting Ø60/100mm 7 719 001 884 Ø120 1310 Ø125 50 125 6 720 610 703-00.1O for Gas Condensing Boilers: OSW Contents Contents Safety instructions 2 Symbols 2 1 Use 3 1.1 General
More informationSECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING
SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air
More informationPROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings Version 2006.1 AUSTRALIAN BUILDING CODES BOARD JANUARY 2006 TABLE OF CONTENTS Foreword 1. Scope 2. Purpose and context
More informationThe Basics of Commercial Kitchen Exhaust Cleaning
The Basics of Commercial Kitchen Exhaust Cleaning ANSI/IKECA C 10 ANSI/IKECA C 10: Standard for Cleaning of Commercial Exhaust Systems IKECA Introduces the Kitchen Exhaust Cleaning Industry s First American
More informationcity of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
More informationCIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance
CIBSE Guide M: Maintenance engineering and management compliance legislation and guidance Types of System/Plant Action required Frequency by Type of Fire and Smoke Fire extinguishers Discharge (not CO
More informationNational Heavy Vehicle Accreditation Scheme: Standards and Business Rules - Maintenance Management standards
National Heavy Vehicle Accreditation Scheme: Standards and Business Rules - Maintenance Management standards Version 1.0 February 2014 Maintenance Management standards Maintenance Management Systems 1.
More informationDRYER VENTING SPECIFICATIONS DRYER SAFETY
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting
More informationFuels Safety Program FS- 072-06 7 DIRECTOR S PUBLIC SAFETY ORDER
Ref. No.: Rev. No.: Fuels Safety Program FS- 072-06 7 DIRECTOR S PUBLIC SAFETY ORDER Date: January 13, 2006 IN THE MATTER OF: THE TECHNICAL STANDARDS AND SAFETY ACT, 2000, S.O. 2000, c. 16 - and - ONTARIO
More informationCOMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET
COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET Colorado Springs Fire Department Division of the Fire Marshal February 2014 Table of Contents PURPOSE... 3 SCOPE... 3 DEFINITIONS... 3 GUIDELINES...
More informationHVAC. Kitchen Exhaust. rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier!
HVAC & Kitchen Exhaust The Heart of Restaurant HVAC rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier! 1 CKV Design: Just not that easy! There is no piece of equipment in the commercial
More informationTechnical Bulletin 005(A) Developed with Communities and Local Government
Technical Bulletin 005(A) Developed with Communities and Local Government Title: Gas cookers in internal kitchens - Ventilation requirements as applied to England, Wales, the le of Man and Guernsey Date
More informationGuidance notes to the CER s recently enacted Gas Works Regulations. These Guidance Notes should be read in conjunction with:
Guidance notes to the CER s recently enacted Gas Works Regulations These Guidance Notes should be read in conjunction with: ELECTRICITY REGULATION ACT 1999 (GAS WORKS) REGULATIONS 2009 Who should read
More informationCHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
More informationHEAVY DUTY STORAGE GAS
Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many
More informationClearing the air A simple guide to buying and using local exhaust ventilation (LEV)
Clearing the air A simple guide to buying and using local exhaust ventilation (LEV) Clearing the air Health and Safety A simple guide to buying and using local exhaust ventilation (LEV) Every year, thousands
More informationFume Cupboard Guidance
Health and Safety Office Fume Cupboard Guidance Document control information Published document name: fume-cupboards-gn.pdf Date issued: Version: 1.0 Previous review dates: December 2013 Next review date:
More informationPLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW
CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,
More informationPre-site Installation Instructions for Aga Electric Cooker Models Electric C Electric E
Electric Cookers Pre-site Installation Instructions for Aga Electric Cooker Models Electric C Electric E PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING YOUR AGA Consumer Protection As responsible manufacturers
More informationCETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory
More informationAmendment: Combustion Appliance Testing Standards Removal. Proponent: Brett Dillon, Chair Standards Development Committee
Amendment: Combustion Appliance Testing Standards Removal Proponent: Brett Dillon, Chair Standards Development Committee Applies to: 2006 Mortgage Industry National Home Energy Rating Systems Standards,
More informationRestaurant & café guide
'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers
More information4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
More informationPLAN SUBMITTAL REQUIREMENTS FOR KITCHEN HOOD AND DUCT EXTINGUISHING SYSTEMS
March 1996 PLAN SUBMITTAL REQUIREMENTS FOR KITCHEN HOOD AND DUCT EXTINGUISHING SYSTEMS PLAN REVIEW 1. Submit a completed permit application and a minimum of three sets of shopquality plans and calculations
More informationFIRE CODE INTERPRETATION
FIRE CODE INTERPRETATION February 2014 FCI-14-02 Page 1 of 6 ISSUE: Fixed Fire Suppression & Exhaust Systems Cooking A number of queries from owners, designers and safety codes officers have been received
More informationNMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
More informationThe risk assessment of fire damper installations
The risk assessment of fire damper installations June 2010 Paul White OVERVIEW OVERVIEW The purpose of this presentation is to highlight that fire dampers form a key part of the passive fire protection
More informationA GUIDE TO WINDOW AND DOOR SELECTION
Australian window association guide series A GUIDE TO WINDOW AND DOOR SELECTION An industry guide to the selection and certification of windows and doors Background Foreword As part of its commitment to
More informationCooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in
More informationSPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE
SPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE CL2 - Pipe and Tank Lagging Warranty Underwriters will not be liable for loss
More informationSTORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders
STORE HAZARDOUS SUBSTANCES SAFELY Suitable containers incompatibles gas cylinders Oxy-Acetylene welding flammable substances 35 36 STORE HAZARDOUS SUBSTANCES SAFELY STORE HAZARDOUS SUBSTANCES SAFELY Storing
More informationUnder sill units. Type FSL-B-ZAS
.1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract
More informationDESIGN OF GREASE FILTER EQUIPPED KITCHEN EXHAUST SYSTEMS
DESIGN OF GREASE FILTER EQUIPPED KITCHEN EXHAUST SYSTEMS CONTENTS PAGE NO. HOODS, WHY? 2 GREASE FILTERS, WHY? 2 TYPES OF HOODS 3 Ventilator Hood 3 Canopy Hood 4 Canopy Slot Hood 5 DESIGNING THE KITCHEN
More informationPART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL
PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL Boiler Manual A. INSTALLING EXHAUST VENT AND INTAKE AIR VENT B. GENERAL n DANGER The Elite Heating Boiler must be vented as detailed in this section.
More informationSPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
More informationVAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
More informationIH 17025 E Sigma Island 90
INSTRUCTIONS FOR USE Kitchen extractor hood Type: IH 17025 E Sigma Island 90 Dear Customer!! You are now a user of the newest generation kitchen extractor hood type IH 17025 E Sigma Island 90. This hood
More informationMemorandum of Understanding between the NSW Ministry of Health and Sydney Water Corporation
Page 1 of 11 Memorandum of Understanding between the NSW Ministry of Health and Sydney Water Corporation This work is copyright. It may be reproduced in whole or in part for study or training purposes
More informationHow To Design A Gas Dryer
Non Domestic Laundry Gas Appliance Installation Code of Practice Introduction This code of practice has been produced with the assistance of all Companies within the OPL sector of SLEAT because of the
More informationOn Site Treatment Systems
On Site Treatment Systems Introduction In cases where houses require to be located in the countryside,(i.e. where no sewerage is available),it is necessary to provide a specific on-site treatment system
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
More informationProperty Inspection. 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT
Property Inspection 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT March 2013 This document has been prepared for the benefit of Clint Marston. No liability is accepted by this company
More informationDrinking Water Quality Management Plan Review and Audit Guideline
Drinking Water Quality Management Plan Review and Audit Guideline This publication has been compiled by Queensland Water Supply Regulator, Department of Energy and Water Supply. State of Queensland, 2013.
More informationSafety Storage Cabinets
Safety Storage Cabinets Safe storage of flammables? The workplace without a fire resistant Safety Storage Cabinet Dangers, risks and your disadvantages... STORAGE ROOM Transport/working time - Increased
More informationRHODE ISLAND. Downloaded 01.15.11
Housekeeping/Laundry/Maintenance Section 35.0 Housekeeping RHODE ISLAND Downloaded 01.15.11 35.1 A full time employee of the facility shall be designated responsible for housekeeping services, supervision
More informationCROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS
CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS WARNING Improper installation, adjustment, alteration, service, or maintenance of this product can cause
More informationArts Revitalisation Projects and the Planning System. January 2010 Guideline
Arts Revitalisation Projects and the Planning System January 2010 Guideline Photography credits: courtesy http://www.flickr.com/groups/renewnewcastle/ Arts Revitalisation Projects and the Planning System
More informationSTARTING A NEW FOOD BUSINESS? GUIDELINES FOR OPENING A CLASS 3 FOOD BUSINESS
STARTING A NEW FOOD BUSINESS? GUIDELINES FOR OPENING A CLASS 3 FOOD BUSINESS Updated: July 2010 Contents Procedure for opening a new Food Business... 2 Basic Records... 3 Summary - Construction and Fitout
More informationSTANDARD PLUMBING AND DRAINAGE REGULATION 2003
Queensland Subordinate Legislation 2003 No. 265 Plumbing and Drainage Act 2002 STANDARD PLUMBING AND DRAINAGE REGULATION 2003 TABLE OF PROVISIONS Section Page PART 1 PRELIMINARY Division 1 Introduction
More informationRC44. for fire risk assessment of catering extract ventilation
Catering extract 17/10/06 15:45 Page 1 RC44 for fire risk assessment of catering extract ventilation IMPORTANT NOTICE This document has been developed through the Insurers Fire Research Strategy scheme
More informationCooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx
More informationAsbestos Storage Facility Plan Examples
Asbestos Storage Facility Plan Examples The purpose of this document This document contains examples of what an operational plan, plans and specification, contingency plan and closure plan should look
More informationCOMMERCIAL KITCHEN HOOD WORKSHEET / CHECKLIST
CITY OF PRESCOTT COMMUNITY DEVELOPMENT DEPARTMENT COMMERCIAL BUILDING PERMIT REVIEW 201 S. CORTEZ STREET PRESCOTT, AZ 86302 (928)777-1207 Licensed Contractor Required License L16 or K16 COMMERCIAL KITCHEN
More informationAutomatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
More informationARMAGH BANBRIDGE AND CRAIGAVON DISTRICT COUNCIL CINEMAS (NORTHERN IRELAND) ORDER 1991
ARMAGH BANBRIDGE AND CRAIGAVON DISTRICT COUNCIL CINEMAS (NORTHERN IRELAND) ORDER 1991 APPLICATION FOR THE GRANT, RENEWAL, TRANSFER OF CINEMA LICENCE / PERMISSION FOR ADDITIONAL HOURS, PERMISSION FOR CHILDRENS
More informationCertification. Kitchen Exhaust Cleaning and Certification Manual 2 ~ Certification. Table of Contents
Certification Table of Contents Phil Ackland Certification Protocol... 2 Preamble... 3 Purpose... 4 Certification Details... 4 Company "Qualification" Steps... 5 Company Qualification Application... 5
More informationFS209E and ISO Cleanroom Standards
FS209E and ISO Cleanroom Standards Terra Universal is the leading expert in the design and fabrication of critical-environment applications. We offer a complete range of equipment, furnishing and supplies
More informationGeismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14 Preparer: Owner: Approver: S/IH Team Leader S/IH Team Leader Manager LA Hub
BASF Corporation Title: LOCAL EXHAUST VENTILATION Individual Unit Function: Industrial Hygiene Procedure No.: IH-3 Page: 1 of 12 Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14
More informationKitchen Planning Guidelines With Access Standards
Kitchen Planning Guidelines With s 1: Door/Entry The clear opening of a doorway should be at least 32 wide. This would require a minimum 2-10 door. The clear opening of a doorway should be at least 34.
More informationGas-Fired, Residential Storage Type Water Heaters
Consulting, Resource, Education, Training, and Support Services for Home Inspectors A candle loses no light when it lights another candle. Gas-Fired, Residential Storage Type Water Heaters Most inspectors
More informationWe hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.
September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify
More informationFIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
More informationChemical Fume Hoods. Environmental Health and Safety 974-5084
Chemical Fume Hoods Environmental Health and Safety 974-5084 Regulatory References Prudent Practices in the Laboratory 2011 (National Research Council of The National Academies): Laboratory chemical hoods
More informationSubpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
More informationALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
More informationProcedures for the Effective Use of Biological Safety Cabinets
Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum
More informationSECTION 15950 - TESTING, ADJUSTING, AND BALANCING
SECTION 15950 - TESTING, ADJUSTING, AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationCity of Langford. Nuisance (Controlled Substance) Bylaw 1009
City of Langford Nuisance (Controlled Substance) Bylaw 1009 : City of Langford Nuisances (Controlled Substance) Bylaw 1009 Table of Contents Page # Part 1 Citation... 1 Part 2 Severability... 1 Part 3
More informationCHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
More informationBUILDING OR RENOVATING
A GUIDE TO BUILDING OR RENOVATING YOUR IDEAL HOME building work? What records should I keep? Is insurance required? W I need approval for? What do I need approval for? How do I obtain building work? How
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationHIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons
Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined
More informationPreventative Maintenance & Statutory Testing
Preventative Maintenance & Statutory Testing Emergency Evacuation Lighting - Inspection and Maintenance It is an Occupational Health and Safety Act requirement that employers have a legal duty of care
More informationMP 5.7 RESIDENTIAL SERVICES BUILDING STANDARD
MP 5.7 RESIDENTIAL SERVICES BUILDING STANDARD Index Purpose... 3 Commencement.3 Application...3 Compliance..3 Associated Requirements... 3 Definitions... 4 Kitchen Facilities... 6 Laundry Facilities...
More informationRestaurant and Café Risk Management Guide. Don t Risk It!
property & liability Restaurant and Café Risk Management Guide Don t Risk It! About Lumley Insurance Lumley Insurance has extensive experience in restaurant insurance and risk management. This experience
More informationSAFETY SIGNAGE PROCEDURE
Page 1 of 10 SAFETY SIGNAGE PROCEDURE 1.0 PURPOSE 1.1 To enable a reference to signage to meet legislative requirements and ensure in cases of emergency appropriate signage is visible. 2.0 SCOPE 2.1 This
More informationTable of Contents. Introduction... 3. 1: Types of Commercial Kitchen Ventilation Hoods... 4. 2: Determining Exhaust Rate... 8
September 2005 Table of Contents SECTION PAGE NUMBER Introduction..................................................................... 3 1: Types of Commercial Kitchen Ventilation Hoods.......................................
More informationHVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
More informationIEQ-15 Air Distribution System
AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA
More informationCooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
More informationGuidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
More informationLOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS
SUBCHAPTER 9 LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS SECTION 150.2 ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS IN EXISTING BUILDINGS
More informationSMOKE ALARMS CLASS 1A BUILDINGS
SMOKE ALARMS CLASS 1A BUILDINGS A smoke alarm is a device that combines both smoke detection and alarm facilities into a single unit. Smoke alarms are required to be installed in all new residential Class
More informationKAWERAU DISTRICT COUNCIL General Bylaw Part 9: On-site Wastewater Disposal Systems (2010)
KAWERAU DISTRICT COUNCIL General Bylaw Part 9: On-site Wastewater Disposal Systems (2010) Kawerau District Council General Bylaw Part 9: On-site Wastewater Disposal Systems (2010) Explanatory Statement
More informationM7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace
TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially
More informationPlumbing for retail food businesses
Plumbing for retail food businesses Every day, thousands of food outlets in Sydney produce waste, such as cooking oil, grease and food solids. If that waste is discharged directly into our sewers, it can
More informationAurora Mall. Aurora (Denver), Colorado
is the largest superregional mall in the city of Aurora, and it s only getting bigger and better. The mall is currently undergoing a significant interior and exterior renovation, scheduled for completion
More informationAustralian Transport Council. National Standard for the Administration of Marine Safety SECTION 4 SURVEYS OF VESSELS
Australian Transport Council National Standard for the Administration of Marine Safety SECTION 4 SURVEYS OF VESSELS Edition 1 Draft for comment issued 20 December 2005 Endorsed by the Australian Transport
More informationCONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
More informationCITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT
Page 1 CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT CIVIC CENTRE 2141 MAJOR MACKENZIE DRIVE MAPLE ONTARIO L6A 1T1 905-832-2281 Page 2 SECTION 1 - GENERAL OBJECTIVES To provide
More information