Dumping Condensate from High Pressure Mains into adjacent Pumped Condensate Returns to to the Steam Plant Should be Avoided
|
|
- Loreen Boyd
- 7 years ago
- Views:
Transcription
1 Dumping Condensate from High Pressure Mains into adjacent Pumped Condensate Returns to to the Steam Plant Should be Avoided
2 HighTemp Condensate 1. When 338 o F condensate passes through trap to 15 psig, it can t exist as 338oF water at 15 psig. The hottest water can be at 15 psig is 250 o F, so 88 Btu/# is liberated as flash steam. (because 88 Btu s= ( )oF *1.0 Btu/oF per pound for water) Btu Happens to be ~10% of the heat of vaporization of 15 psig steam. ( 88/ 945 = 9.3% actually) Thus, for every 1 pound of condensate passed by the trap, ~1/10th pound of steam will be gener-ated while 9/10 pound will remain condensate. 3. BUT, at 15 psig, steam occupies 800 x the volume of condensate. ( Steam Table ). So even though, by mass there s only 1 part steam to 9 parts condensate, by volume, the ratio is 800 parts to 9 parts water, or ~ 89 to 1. So by volume, 89 times as much steam as condensate enters the pipe. 4. The Point: a lot of 250oF steam is being injected into water that is subcooled down to below 212oF. 100 psig, 338oF Steam 338 o F 100 psi 15 psig 90oF Pumped Condensate 15 psig into Hot condensate flashes to 250oF condensate & 15 psi steam. 250 o F DP accelerating water into collapsing void = 30 psia 9 psia (vapor pressure of 190oF water) = 21 psid IMPERIAL Low Press Pumped Condensate Return 15 psig flash steam (@ 250 o F) bubbling into 190 o F condensate What will Happen?????? The Steam Bubble may collapse with a C.I.W.! So why not avoid them with a dedicated High Pressure CR line?? (next slide) If condensate-flow R T > 1.0, steam continuously condenses as it enters pipe and no bubble can grow, so NO HAMMER. If condensate R T < 1.0, steam bubbles will form and grow, but MAY NOT HAMMER if they re left alone to flow out the system. But the situation is UNSTABLE: Rise To Plant IF cool condensate dumps in downstream so Rt >>1.0,BANG. IF a Pump restarts increasing flow, so Rt >>1.0, BANG. Steam cuts off (e.g. trap closes) so Rt >>0, BANG.
3 The Steam Bubble May Collapse You d like YES,! It depends on the Condensing Ratio Q cond.cap. > Q stm.in IMPERIAL Can We Tell If It Will? m c (T sat T cond ) * 1.0 Btu/# > m stm h fg m c (DT subcooling ) > m stm h fg at Pressure in condensate line at Pressure in condensate line m s #/hr of 250oF Steam 90oF Pumped Condensate 15 psig m c I. If Q cond.cap. > Q stm.in in steady flow, then 250 o F All flash steam entering the pipe will be condensed by the subcooled condensate flow. No steam bubble can grow, so there is no steam bubble to collapse. Things are copasetic. m c (60 of ) > m stm (945 Btu/#) (60 Btu/#)
4 II. Now suppose Q cond.cap. > Q stm.in in steady flow, All flash steam entering the pipe will NOT be condensed. Steam bubbles will grow and travel downstream < IMPERIAL So What? No Problem if steam bubbles make it to the Condensate Receiver BUT, Suppose another branch of Condensate Return tee s into CR Main before the Receiver and brings more subcooled condensate If m s #/hr of 250oF Steam m c (T sat - T c ) > m stm Bubble ( h fg Btu/#) (60oF) (946 m c #/hr of 190oF Cond. mc 15 psig m c 250 o F 200 of 250 o F
5 But What about Unsteady Flow?
6 Suppose Q cond.cap. > Q stm.in initially so all flash steam is condensed IMPERIAL m s #/hr of 250oF Steam Bang! The trap starts blowing steam bubbles again because m c DT s.c. < m s h fg 190oF m c Then Condensate Flow decreases, say, due to a large condensate pump shutting off So flash steam bubbles again survive in the PCR When the Condensate Pump cycles back on, the condensing Ratio flips back Steam Bubbles Collapse and Watercannon may occur against the check valve Lesson: Better not let Q cond.cap. go below Q stm.in, to allow steam bubbles to persist
7 IMPERIAL Suppose Q cond.cap. < Q stm.in Initially due to a large incoming steam input so steam is not all condensing m s #/hr of Flash Steam Bang! 190oF m c Then Steam input is abruptly cut off, say, due to a large trap cycling off so the condensing Ratio flips to Condensing, then the Steam Bubbles will Collapse, water may run up and and hammer against the check valve
8 IMPERIAL If there were a high point in the system for steam to collect, Q cond.cap. > 1.0 Q stm.in is not enough to prevent steam from persisting at the high point. m s #/hr of Flash Steam Bang! 190oF When Steam input is abruptly cut off The Steam Bubble will Collapse causing Water to run up and and hammer against the check valve The Condensing Ratio was found to have to be as high as 140% to guarantee no waterhammer where high points were built into the PCR.
9 IMPERIAL Affect of Blowing Traps Steam will warm condensate flow so entering steam bubbles will tend to persist Increased Flow Volume due to the space taken up by the flash steam will increase velocity in the PCR line. thereby increasing the DP loss in the line. That will bump up the Line pressure, and most significantly, the force of any waterhammer Incoming Condensate from Building Receivers will still be < 212oF, say about 190oF When 190oF condensate dumps into CR Main, it will have more subcooling relative to the steam, and be more likely to cause the steam bubbles to collapse. I.E. ther will be more Waterhammer. < m s #/hr of Flash Steam From Blowing Trap m c #/hr from Condensate Receiver at 190oF 215 of 25 psig o F m c (60oF) (77oF) (946) m c (T sat - T c ) > m stm Bubble ( h fg Btu/#) 220oF (933) 267 o F
10 Work Arounds to Avoid Separate HP CR Line
11 Sparger in CR to Break Up Flashing Steam Manhole which housed 60 psi Steam Main and CR was at End of Steam Line, Last Building When Building CR Pump was On, there was 60 times the cooling capacity needed to condense all flash steam, so all flash steam exiting sparger was condensed. When CR pump cycled off, local forward flow in CR Main went to zero. If trap cycled on into the 15 psi line, at ( )oF/ 946 Btu/# *800/1, = its condensate entered the CR as 48 parts steam by Volume, compared to 1 part water. When Bulding s CR Tank refilled, Pump re-started oF Bang
12 Separate, Dedicated High Pressure Condensate Return IMPERIAL All the steam traps on the High Pressure Steam Mains Discharge to it. It will be 2-Phase flow. Mostly steam, some small volume of condensate Its Pressure is still dictated by that needed to get the 2-Phase mix back to the Plant To be simple, the Pipe should run downhill all the way to the Plant because It s easy for the steam to go up hill, not so condensate. it will pool before a rise until it almost blocks the pipe, then Blurp up in slug flow when the pressure behind it builds enough to lift it over the rise. This CAN (but might not) result in Severe Slug Flow So if the 2- Phase fluid needs to go uphill, it needs special treatment to not be sluggy 100 psig Steam 50 psig Steam 190oF Cond 338 o F 100 psi 15 psig 15 psig 89 x vol of 15 psi steam to 250oF condensate 250 o F steam 300 o F 50 psi 15 psig 40 x vol of 15 psi steam to 250 of condensate 250 o F steam 250 o F Condensate Which Brings up the Question: How do you get the liquid condensate up to the Plant? How about a pumping it from a Separator Tank, Route the steam to LP Steam, the Condensate to a Receiver, flashing it, then pumping it psig + How Do Have Trouble Run line uphill Dump Subcooled Water into it (i.e. water at less than 15 psi saturation temp of 250oF) Say some Building s Condensate receiver at 190oF. slope Enough water head so Pump doesn t cvitate
13
Heating Water by Direct Steam Injection
Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space
More informationSteam System Efficiency. Bill Lumsden Leidos Engineering
Steam System Efficiency Bill Lumsden Leidos Engineering Steam System Efficiency Steam System Efficiency Key Take-aways: Review of the properties of ice, water, and steam Learn the basics of steam trap
More informationC. starting positive displacement pumps with the discharge valve closed.
KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the
More informationSpecific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.
Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of
More informationEquivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409
Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam
More informationRefrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
More informationDIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING
By Philip Sutter Pick Heaters, Inc. DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING INTRODUCTION Many process plants currently use steam or hot water to heat jacketed devices such as tanks,
More informationThermodynamics - Example Problems Problems and Solutions
Thermodynamics - Example Problems Problems and Solutions 1 Examining a Power Plant Consider a power plant. At point 1 the working gas has a temperature of T = 25 C. The pressure is 1bar and the mass flow
More informationChokes. Types Reasons Basics of Operations Application
Chokes Types Reasons Basics of Operations Application Most Common Chokes Positive: Fixed orifice Disassemble to change bean Adjustable Provides variable orifice size through external adjustment Schematic
More informationRusty Walker, Corporate Trainer Hill PHOENIX
Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat
More informationUNDERSTANDING REFRIGERANT TABLES
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,
More informationA basic introduction to steam
A basic introduction to steam FOR HOT, COLD, MOIST AND DRY, FOUR CHAMPIONS FIERCE. STRIVE HERE FOR MASTERY Milton 1666 Steam Wonderful Steam Very high heat content Recyclable Clean, non toxic Biodegradable
More informationSteam System Safety Operation and Maintenance
A Short Refresher on Water Hammer as related to Steam System Safety Operation and Maintenance 21st IDEA Distribution Workshop Miami, FL February 21, 2011 Mark Vogler Superintendent Thermal Engineering
More informationOpen Cycle Refrigeration System
Chapter 9 Open Cycle Refrigeration System Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved An open cycle refrigeration system is that the system is without a traditional evaporator.
More informationSteam System Best Practices Condensate System Piping
Steam System Best Practices Condensate System Piping Summary The best method for improving steam system energy efficiency, reducing chemical costs, and reducing make-up water costs is to return the maximum
More informationQUESTIONS THERMODYNAMICS PRACTICE PROBLEMS FOR NON-TECHNICAL MAJORS. Thermodynamic Properties
QUESTIONS THERMODYNAMICS PRACTICE PROBLEMS FOR NON-TECHNICAL MAJORS Thermodynamic Properties 1. If an object has a weight of 10 lbf on the moon, what would the same object weigh on Jupiter? ft ft -ft g
More informationChapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service
BP Lower 48 Onshore Operations Safety Manual Page 4.19 1 Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service I. General Requirements A. After motor vehicle accidents and underground excavation
More informationTOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?
KNOWLEDGE: K1.01 [3.3/3.5] P21 Which one of the following contains indications of cavitation in an operating centrifugal pump? A. Low flow rate with low discharge pressure. B. Low flow rate with high discharge
More informationHow To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
More informationOverview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
More informationSTEAM HEATING SYSTEM TROUBLESHOOTING GUIDE
Page 1 of 9 PURPOSE Steam is the most commonly used heating medium for maintaining process temperatures. Compared to other heating media, steam contains a significant amount of heat energy, and this heat
More informationCharacteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
More informationGeothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls
Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &
More informationHow does solar air conditioning work?
How does solar air conditioning work? In a conventional air conditioning system; The working fluid arrives at the compressor as a cool, low-pressure gas. The compressor is powered by electricity to squeeze
More informationTroubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
More informationEvaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle
INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication
More informationSteam System Design and Best Practices Related to Kiln Drying
Steam System Design and Best Practices Related to Kiln Drying New England Kiln Drying Association Steam Design and Best Practices HerLine Technologies What is Steam? Like other substances water can exist
More informationACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation
ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation Ohio Medical Corporation 1111 Lakeside Drive Gurnee, IL 60031 Phone: (800) 448-0770 Fax: (847) 855-6304 info@ohiomedical.com
More informationVACUUM REFRIGERATION SYSTEMS
VACUUM REFRIGERATION SYSTEMS CHILL VACTOR The Croll-Reynolds CHILL-VACTOR is a chiller that uses a vapor flashing process. Water has a pressure-temperature relationship which is its boiling point. If its
More informationUnsteady State Relief Valve Evaluation. External Pool Fire Scenario
Unsteady State Relief Valve Evaluation External Pool Fire Scenario By Rame Sulaiman Process Engineer Process Engineering Associates, LLC Copyright 2009 Process Engineering Associates, LLC. All rights reserved.
More informationEngineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
More informationHeat Recovery In Retail Refrigeration
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
More informationGround-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29
Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 A refrigerant retrofit project, involving the conversion of a large Data Room cooling system from R22 to R422D (DuPont
More informationAir Conditioning 101. STN Presentation AC101
Air Conditioning 101 What is Refrigeration? Refrigeration is Cooling by the Removal of Heat Heat is Measured In BTU s A BTU is a British Thermal Unit It is the Amount of Heat to Raise One Pound of Water,
More informationChapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from
More informationWhy and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
More informationSteam Generation Efficiency Module Blowdown Losses Section
Steam End User Training Steam Generation Efficiency Module Blowdown Losses Section Slide 1 Blowdown Losses Module This section will discuss blowdown loss and its affect on boiler efficiency. [Slide Visual
More informationVogt Valves The Connection Bulletin for Forged Steel Flow Control Valves CB 15
The Connection Bulletin for Forged Steel Flow Control Valves CB 15 Flow Control Division Forged Steel Flow Control Valves GRADUATED DIAL AND INDICATOR FULLY GUIDED V-PORT THROTTLING DISC AND INTEGRAL HARD
More informationHow To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
More informationENERGY RETROFIT PROGRAM
ENERGY RETROFIT PROGRAM An innovative but simple retrofit for existing hot water and chilled water piping systems that will help you save money. REDUCE FLOW BY 50% REDUCE PUMP HEAD BY 75% REDUCE PUMP POWER
More informationHOW TO SELECT A LOW VOLUME (L.V ) BOILER
HOW TO SELECT A LOW VOLUME (L.V ) BOILER FREQUENTLY ASKED QUESTIONS OR COMMENTS ON BOILERS Dear Potential Customer: Low Volume Operator Exempt boilers have been marketed in Ontario to eliminate the requirement
More informationCommercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:
PART 1: CO 2 Commercial refrigeration has been in the environmental spotlight for more than a decade, especially as leakage studies have revealed the true effects of hydrofluorocarbon (HFC) emissions.
More informationUniversity of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012
University of Maryland College Park District Energy System IDEA Campus Energy Conference February 9, 2012 UMCP District Energy System The University of Maryland district energy system consists of a well
More informationC H A P T E R T W O. Fundamentals of Steam Power
35 C H A P T E R T W O Fundamentals of Steam Power 2.1 Introduction Much of the electricity used in the United States is produced in steam power plants. Despite efforts to develop alternative energy converters,
More informationEnergy Saving Ideas for Your Box Plant
General Session Energy Saving Ideas for Your Box Plant Moderator: Jeff Pallini Fosber America, Inc. Program Overview: Immediate Ideas: Jim Simko of Simtek Systems, Inc. Mid-Term Ideas: John Donahue of
More informationChemical versus Physical Changes
Chemical versus Physical Changes Permission to Copy - This document may be reproduced for non-commercial educational purposes Copyright 2009 General Electric Company What are physical and chemical changes?
More informationVAD. Variable Area Desuperheaters
Desuperheater overview Steam used in process plants can be superheated, that is, heated to a temperature above saturation. The excess of temperature above its saturation is called 'superheat'. Desuperheated
More informationPressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves
Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves CRANE Energy Flow Solutions TM Donald H. Johnson Crane Energy Flow Solutions 1 Crane Co. Resolution Made By Richard Teller
More informationOverview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank
Overview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank Unbiased, Third-Party, Water & Energy Management Consulting Firm: - Not affiliated
More informationSome Criteria for Choosing a Steam Boiler for a Microbrewery
Some Criteria for Choosing a Steam Boiler for a Microbrewery Jack Coe Rite Engineering and Manufacturing Corporation Breweries rely on steam heating for a number of functions, primarily to heat the brew
More informationFlashing and Cavitation
As seen in the Summer 2015 issue of MAGAZINE BACK TO BASICS A high-power boiler burner in a co-generation plant Flashing and Cavitation Some of the following questions may seem unrelated, but they all
More informationScroll Compressor Development for Air-Source Heat Pump Water Heater Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
More informationBPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap
1263050/6 IM-P126-07 ST Issue 6 BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation
More informationCompressors Buying Guide
Compressors Buying Guide Below is a copy of a booklet which will help you make a compressor purchase! Included is information on... Horse Power (HP) Pressure (PSI) Cubic Feet Per Minute (CFM) Tank Sizes
More information= water horsepower WHP brake horsepower QH WHP = (222) ( 33,000 ft-lbs/min-hp)( 7.481 gal/ft ) 1 HP=0.746 kw
Lecture 11 Pumps & System Curves I. Pump Efficiency and Power Pump efficiency, E pump E pump = water horsepower WHP brake horsepower = BHP (221) where brake horsepower refers to the input power needed
More informationThermoSorb Desiccant Dryers
ThermoSorb Desiccant Dryers Sierra Why dry compressed air? Contamination reduces efficiency The air we breathe contains contamination in the form of water vapour and airborne particles. During the compression
More informationEJECTOR AIR REMOVAL SYSTEMS ENGINEERING DATA BULLETIN # PVS-80025201-ARS PAGE 1 OF 5
BULLETIN # PVS-80050-ARS PAGE OF 5 GENERAL Air Removal Systems generally consist of dual 00% (twin-element) ejecrs, single 00% surface-type inter- & aftercondensers, suction & discharge isolation valves
More informationUNIT 2 REFRIGERATION CYCLE
UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression
More informationME 201 Thermodynamics
ME 0 Thermodynamics Second Law Practice Problems. Ideally, which fluid can do more work: air at 600 psia and 600 F or steam at 600 psia and 600 F The maximum work a substance can do is given by its availablity.
More informationEnclosed Football Stadium Design History and Lessons Learned
Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP btowell@cxegroup.com CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention
More informationMC4-50 Feeding System
MC4-50 Feeding System Dry Calcium Hypochlorite For Municipal Applications The smarter way to water quality PATENTED SPRAY TECHNOLOGY DELIVERS UNPARALLELED CONSISTENT RESULTS The Constant Chlor Plus MC4-50
More informationIt will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
More informationTechnical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1
Technical Training Associates Presents Commercial Refrigeration Equipment Servicing Part 1 By Jim Johnson A Practical Approach To The Fundamentals Of Walk-Ins, Reach-In and, Display Cases: Restaurant,
More informationRecover Heat from Boiler Blowdown Water
Prepared for California Energy Commission (CEC) Prepared By: Southern California Gas Company (A Sempra Energy Utility) E3M Inc. May 2012 i Disclaimer The CEC and its contractor, Southern California Gas
More informationHow To Clean Water From An Ammonia Refrigeration System
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can
More informationAn analysis of a thermal power plant working on a Rankine cycle: A theoretical investigation
An analysis of a thermal power plant working on a Rankine cycle: A theoretical investigation R K Kapooria Department of Mechanical Engineering, BRCM College of Engineering & Technology, Bahal (Haryana)
More informationHumidity, Condensation, Clouds, and Fog. Water in the Atmosphere
Humidity, Condensation, Clouds, and Fog or Water in the Atmosphere The Hydrologic Cycle Where the Water Exists on Earth Evaporation From the Oceans and Land The Source of Water Vapor for the Atmosphere
More informationOSHA Tank Venting DEFINITIONS
OSHA Tank Venting DEFINITIONS 1910.106 - Flammable and combustible liquids. 1910.106(a)(2) (a) Definitions. As used in this section: (2) Atmospheric tank shall mean a storage tank which has been designed
More informationPOSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES
POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES M. Bantle 1, I. Tolstorebrov, T. M. Eikevik 2 1 Department of Energy Efficiency, SINTEF Energy Research, Trondheim, Norway,
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
More informationChapter 8: Flow in Pipes
Objectives 1. Have a deeper understanding of laminar and turbulent flow in pipes and the analysis of fully developed flow 2. Calculate the major and minor losses associated with pipe flow in piping networks
More informationAny Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.
I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is
More informationMinor losses include head losses through/past hydrants, couplers, valves,
Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within
More informationHS-901(A) BASIC STEAM HEATING SYSTEMS
HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,
More informationChilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
More informationTheory, Application, and Sizing of Air Valves
Theory, Application, and Sizing of Air Valves VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX. (630) 941-8042 www.valmatic.com 1 THEORY, APPLICATION,
More informationFrequently Asked Questions
Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.
More informationOptimize Pipeline Hydraulics with Multiphase Flow Modeling
Optimize Pipeline Hydraulics with Multiphase Flow Modeling Below are questions asked by attendees during the webinar on February 22, 2012, followed by answers provided by our presenters. Will you also
More informationREGULATING VALVE APPLICATIONS
REGULATING APPLICATIONS GENERAL REGULAR APPLICATION & INSTALLATION NOTES Regulator Application & Installation Notes The following are considerations for all steam regulator installations, as system operation
More informationMechanical Seal Piping Plans
Mechanical Seal Piping Plans Single Seals plans 01, 02, 03, 11, 13, 14, 21, 23, 31, 32, 41 Dual Seals plans 52, 53A, 53B, 53C, 54, 55 Quench Seals plans 62, 65A, 65B, 66A, 66B Gas Seals plans 72, 74, 75,
More informationCPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!
CPX/HT Series REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM High-performance products. Designed for you! COMPRESSED AIR WATER CONTAMINATION Atmospheric air contains water in vapor form in different
More informationLiquid level measurement using hydrostatic pressure and buoyancy
iquid level measurement using hydrostatic pressure and buoyancy This worksheet and all related files are licensed under the Creative Commons Attribution icense, version 1.0. To view a copy of this license,
More informationLaundry Hot Water Systems
TECHNICAL BULLETIN HE-2020 Laundry Hot Water Systems Commercial/Institutional Applications using Helitherm Heat Exchangers AERCO INTERNATIONAL, INC. 159 PARIS AVE., NORTHVALE, NJ 07647 (201) 768-2400 FAX
More informationValve Sizing. Te chnic al Bulletin. Flow Calculation Principles. Scope. Sizing Valves. Safe Product Selection. www.swagelok.com
www.swagelok.com Valve Sizing Te chnic al Bulletin Scope Valve size often is described by the nominal size of the end connections, but a more important measure is the flow that the valve can provide. And
More informationLECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS 1. Define an accumulator and explain its function A hydraulic accumulator is a device that stores the potential energy of an incompressible fluid
More informationABSTRACT. aspects of potential waste heat recovery systems and the economics of installing them at selected survey factories.
ABSTRACT WASTE HEAT RECOVERY IN THE FOOD PROCESSING INDUSTRY W. L. Lundberg and J. A. Christenson Westinghouse Electric Corporation Advanced Energy Systems Division F. Wojnar H. J. Heinz Company U.S.A.
More informationMaterial taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001
Pressure Control Chapter 3 Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Introduction Pressure control is a key element in the design of any circuit. Used correctly, it can
More informationThat s it, that s what we do: air knife drying. Ray Ralph, President R.E. Morrison Equipment Inc.
Post Shrink Tunnel Drying Air Knife Belt Cleaning Systems Conveyorized Drying Systems Bolt-On Air Knife Systems Air Knife Belt Defrosters Crate and Tote Drying Booster Blowers Vacuum Pumps for Carton Erecting
More informationHow do I measure the amount of water vapor in the air?
How do I measure the amount of water vapor in the air? Materials 2 Centigrade Thermometers Gauze Fan Rubber Band Tape Overview Water vapor is a very important gas in the atmosphere and can influence many
More informationDEFROSTING. Service Engineers Section Technical Bulletin No 3
Service Engineers Section Technical Bulletin No 3 DEFROSTING 1. INTRODUCTION This bulletin is presented to cover the methods used and problems experienced with defrosting of coils for chill and frozen
More informationSulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard
Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain
More informationTYPE E Main Valve Sizes 3 /8 through 12
SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,
More informationModule 9: Basics of Pumps and Hydraulics Instructor Guide
Module 9: Basics of Pumps and Hydraulics Instructor Guide Activities for Unit 1 Basic Hydraulics Activity 1.1: Convert 45 psi to feet of head. 45 psis x 1 ft. = 103.8 ft 0.433 psi Activity 1.2: Determine
More informationFacility Operations Physical Safety Guidance Document
Facility Operations Physical Safety Guidance Document Title: Guide on Pipe Identification Standards (ASME A13.1-1996) Original Date: December 18, 2000 Section: 4.0 Facility Operations Revised Date: Number:
More informationBoiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
More informationThe paper addresses the boil-off in the cryogenic industry and details the specifics of it when applied to vehicle LNG tanks.
What is Boil-off? Scope... 1 Boil-off in the cryogenic industry... 1... 1 Measures for boil-off... 2 LNG vehicle tanks... 2 Boil-off for the vehicle LNG Tank... 2 Heat management and types of fuel delivery
More informationIn-Line Air Separators
Air Elimination & Control In-Line Air Separators The AC models of air separators deliver all the quality and performance you expect from Taco products. They are built to last with shell, heads and ANSI
More informationCHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank
CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS Blank SONNTAG/BORGNAKKE STUDY PROBLEM 7-1 7.1 A car engine and its fuel consumption A car engine produces 136 hp on the output shaft with a thermal efficiency
More informationScreening Reactor S t e a d a t e r Piping Systems for Water Hammer
NUREGCR-6519 Screening Reactor S t e a d a t e r Piping Systems for Water Hammer Manuscript Completed: August 1997 Date Published: September 1997 Massachusettsnstitute of Technoloey 77 MassachusettsAvenue
More informationMAINTENANCE INSTRUCTIONS. Thermia Robust heat pump
MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................
More information