ADVANCED METHODOLOGIES AND NEW TOOL FOR MULTIPHASE POWER QUALITY ANALYSIS & MITIGATION

Size: px
Start display at page:

Download "ADVANCED METHODOLOGIES AND NEW TOOL FOR MULTIPHASE POWER QUALITY ANALYSIS & MITIGATION"

Transcription

1 ADVANCED METHODOLOGIES AND NEW TOOL FOR MULTIPHASE POWER QUALITY ANALYSIS & MITIGATION Xavier YANG EDF R&D - France Xavier.yang@edf.fr INTRODUCTION For utility network and end-user loads harmonic simulation, a large number of power quality problems show that single phase equivalent circuit and linear model are not suitable to reveal a part of real disturbance events such as unbalance harmonic impedances, asymmetric voltage sag, negative sequence current propagation, and phase to ground harmonic resonance. This paper deals with some particulars aspects of multiphase network harmonic modelling used in ExpertEC, a new and simple power quality analysis tool developed by Electricite de France (EDF). It makes power quality mitigation easier and it can shorten substantially the studying time of a real power quality problem, compared with a more general simulation software. As ExpertEC uses true multiphase matrix models, it can deal with all the above phenomena by means of its simple and useful industrial loads and sources models. For usual end-user loads such as squirrel cage induction motors, power transformers and lines, full multiphase matrix models are employed in order to characterize positive, negative and zero sequence impedances. These modules make it possible to simulate unbalance voltage impact to an induction machine as it draws important negative sequence currents from the power supply when its input voltage is unbalanced. ExpertEC Fig. 1. Part of working screen of ExpertEC The PQ Expert subsystem is a pre-designed element; it can be settled at the point of common coupling of a simulated circuit. Its role is to analyse three-phase power quality problems and give power quality indicators according to the local utility s limits. If there is violation of the limits, PQ Expert subsystem will propose, design and size an appropriate solution. The three-phase Norton unit is another useful element for power quality mitigation. It makes it possible to simplify a complex electric grid system to a three-phase steady state active network in which all the impedances and current sources are modelled according to the harmonic frequencies. Harmonic order can be studied up to 256 or unlimitedly when using input data file. In the end, the processing software gives both harmonic spectrum plots and time domain waveform plots. Other available modules in ExpertEC: user-designed sources, wattmeter, voltage analyser, current analyser, voltage regulator, reactive compensator, protection unit, etc. The input data of all models are based on either equivalent electric circuit values (R, L, C, E, J, M, etc) or technical data sheet from electric equipment. All the calculations have been validated thanks to a number of on-site power quality mitigations. The studied disturbance mitigation methodologies can be used in different power quality analysis domains: power grids, industrial networks, tertiary power supplies, and embedded electric facilities. The following power problems can be treated with a minimized engineer time: 1. On site harmonic analysis (harmonic, inter harmonic, unbalance harmonic, notched voltage), 2. Electric values calculations such as RMS, Thd, powers, cos(ϕ), energy, motor starting, protection, etc, 3. Harmonic impedance calculation, unbalance impedance measurement and automatic resonance identification, 4. Frequency domain analysis of different types of power transformers (independent flux, forced flux, Scott, etc), 5. Harmonic filter design, sizing and validation, capacitor bank sizing. 6. Unbalance investigation and compensation design, 7. Voltage surge and sag analysis, 8. Protection unit verification. This software tool was developed for application in down the meter power quality services offered by EDF group companies. The detailed multiphase modelling functions of this software will be described in the following paragraphs by different real cases. METHODOLOGIES FOR MULTIPHASE POWER QUALITY MITIGATION This part is aimed at describing different methodologies used for multiphase power quality mitigation. As a great part of power grid faults are asymmetrical, the single-phase modelling and symmetrical approaches can t reveal precisely

2 disturbance behaviour in real power system. Particularly voltage sags propagation analysis must be studied by true three phase models at different voltage levels. However, the development of three-phase models of all power system equipment was restricted by computer resource. Fortunately, the recent development in computer makes it more and more possible to cope with power quality problem by true threephase models in a single personal computer. Asymmetrical components modelling Induction motor. As well known, two thirds of industrial loads is composed of electric motors. Induction motor is a typical asymmetrical load in power quality analysis, because in which the negative sequence impedance is much lower than that of its positive sequence. Based on nodal equations, we can model a passive n-terminal electrical linear load into an admittance matrix referred to nodal equation: [In] = [Gn] [Vn] [Gn] In: vector of nodal current injection Vn: nodal voltage vector Gn: load admittance matrix g11 g12. g1n g21 g22. g2n gn1 gn2. gnn If the positive sequence impedance is equal to the negative sequence impedance, all up and down triangles elements of G is symmetrical, that is: gij = gji, i.e. transposable. For asynchronous motor, gij gji, we can t use a transposable admittance matrix to simulate its harmonic behaviour, and we need to take into account of the asymmetry in the admittance matrix. The same way, the relationships between nodal voltages and currents vectors at motor s input can be written: V1 I1 [V] = [Z] [I] with [V] = V2 [I] = I2 [Z] = V3 I3 Z1 Z2 Z3 Vp Vn = [A] [V] Ip In = [A] [I] [A] = 1 a a² 1 a² a The relationships between voltages and currents of an AC motor become: Vp Vn Ip = [Zd] In With [Zd] = We obtain [A][V]=[Zd][A][I], or [V] = [A -1 ][Zd][A][I] with [Z]=[ A -1 ][Zd][A]. We define the motor s admittance matrix [G]=[Z -1 ]. The nodal voltage matrix equation can be written in current nodal current equation matrix [I]=[G][V]. For an asynchronous motor, G is not transposable because the negative impedance is bigger than the positive sequence. It is impossible to represent G by passive components as R, L, C, etc. That is why ExpertEC utilizes a matrix model in order to study motor s behaviour. The fig.2 shows an unbalance problem studied for a plastic product manufactory. In this site, the asymmetrical geometric arrangement of LV cable has caused serious current unbalance at workshop s feeder that powers over 100 induction machines. The following figure shows the simulation circuit to study the behaviour of a induction motor powered by asymmetrical LV cable. Ep: symmetrical voltage source (400V), Zc: unbalanced cable, M: induction motor (375kW). The negative sequence voltage is about 4V at the motor s input (1%). The three-phase matrix model simulation shows that the induction machine can amplify voltage unbalance δv: the current unbalance δi has reached about 7%. This phenomenon can t be studied in a symmetrical model. The following simulation curve reproduces the relation between δi/δv and slip of a low voltage 3-phase squirrel-cage induction machine. 1 3 Power supply V I Motor s impedance Z δi/δv 12 Unbalance amplification by an AC motor If we decompose three-phase values into positive sequence (Vp, Ip, ), negative sequence (Vn, In, ) and zero sequence (,, ), the above schema can be drawn as the sum of following equivalent circuits: Vp (0 ) Vn (0 ) slip Fig. 2. Unbalance amplification curve Vp (-120 ) Vn (120 ) Vp (-240 ) Vn (240 ) All these values are in complex, with a = e j(120 ) : The above figure shows that an induction machine amplifies greatly unbalance voltage particularly when its slip is lower. The current unbalance may be important even if the voltage unbalance is small. If an end-user load contains a number of induction machines without adjustable speed driver, current unbalance problem caused by voltage unbalance may become critical for thresholds setting of feeder s protection.

3 In the other hand, asynchronous induction machines can compensate slightly upstream unbalanced voltage sags, because its negative impedance is lower than its positive one. Therefore, the main drawback of this kind of load is current unbalanced amplification during voltage sag (Fig.3). When fault direction analysis is performed, this phenomenon must be taken into account because an up-stream voltage sag can also provoke serious over current. Line voltages (V) Motor phase currents (A) combination of 3 single-phase transformers (independent flux). Norton network In order to simplify a simulation task, it is recommended to use equivalent Norton or Thevenin network when coping with a large size electric circuit. Simulated Norton network is a 4-terminal element that can be built by both modelling and site measurement. It contains current sources and impedances. A typical three-phase Norton network is modelled by 7 series data sheet: 1 frequency, 3 currents and 3 impedances. Each phase of Norton network is constructed by frequency f, impedance Z f and current source J f shown in following figure. Fig. 3. Voltage sag and current response at an AC motor s input Three-phase transformer. Three-phase power transformer considered as a balanced device is justified in the majority of practical situations. However, it has an asymmetrical component behaviour, particularly, in fault analysis. We have modelled three-phase transformer in phase coordinates, so no more assumptions are necessary for the global model, even though it is possible to make physical assumption of each phase in order to simplify the three phase-model. We construct a twelve dimensions complex matrix to represent all 6 windings, mutual inductances, and magnetic circuit reluctance. The next flow chart shows the steps of true three phase transformer modelling. Upa Upb U pc [V] Ipb Ipa Ipc 6 windings Three-phase Differential values Isa Isb Isc U sa Usb U sc Set flux type: 3 legged or > 3 legged Set connections data sheet Admittance matrix calculation v1 V2 V3 V4 V5 I1 I2 I3 I4 I5 6 windings Three-phase Nodal values Set connections Fig. 4. Three phase transformer modelling I6 I7 I8 I9 I10 I11 V6 V7 V8 V9 V10 V11 At input side, Set connection matrix bloc converts all threephase Delta or Star connections into six windings phase coordinates. Output Set connection module bloc transforms 12-order coordinate matrix in to 8-order complex admittance matrix by which nodal voltages can be achieved. At Set Flux type unit, we can model 3 types of three-phase transformer construction: 3 legged (forced flux), 4-5 legged (free flux) or [I] Three phase Norton network J 1 (f) Z 1 (f) J 2 (f) Z 2 (f) J 3 (f) Z 3 (f) Fig. 5. Frequency domain Norton network For a given large scale simulated circuit, ExpertEC can build automatically an equivalent steady-state Norton network by frequency scan in two steps at each frequency: short circuit and open circuit simulations in order to define Z f and J f values. Three phase impedance measurement and automatic resonance frequency identification At a point of common coupling of three phase power system, impedance is suggested to be calculated by a three phase current source set by positive, negative and zero sequences components according to scanned frequency. The typical elements that affect three-phase impedance calculation are induction machine, network neutral system, three-legged power transformer, etc. Frequency impedance scans give all phase-phase and phase-neutral impedances represented in magnitude & angle via frequency. The following curves show the impedances calculated at the secondary of two types of transformers simulated by true three-phase model (1 MVA, 50Hz). Z1 is the impedance calculated by a single-phase impedance meter, and Ztr is the phase impedance measured by a three-phase impedance meter. For a three-legged power transformer, the error from single-phase impedance calculation is very important. In this case, a three-phase impedance calculation must be used.

4 Five legged Three legged Fig. 6. harmonic impedance The automatic resonance frequency identification function is a useful tool for harmonic mitigation. The principle of automatical harmonic resonance identification is to analyse dz/df values. If dz/df=0 at f = fr1, there is a harmonic resonance at the measuring point. If the impedance gets maximum value at frequency fr1, the resonance is a parallel harmonic resonance and it will amplify mainly downstream harmonic current at this frequency. If the impedance gets minimum value at fr2, there is a series resonance. In this case, the downstream harmonic current will be filtered. If the resonance elements (R,L,C) are located in front of the analysis point, ie, load side, upstream harmonic voltage of this frequency could provoke downstream harmonic current. Impedance curve Z fr1 fr2 Fig.7. Software resonance identification i1 i2 i3 Fig. 8. Power quality indicators and phase currents at 20 kv busbar Active filter design. The above figure shows that total voltage harmonic distortion exceed the normalized limits. Based on this technical information, PQ Expert subsystem can automatically design an appropriate passive filter or size a suitable active filter. The active filter size takes account of busbar voltage and harmonic currents. For this site, an active filter is sized by the following parameters: - Rated filter power = 810 kva without reactive power compensation or 5.4 MVA with reactive compensation, - Compensated frequencies = 150 to 1500 Hz - Compensation phase current is evaluated and shown in following figure (without reactive power compensation). At each identified resonance frequency, the amplifying coefficient is estimated by impedance module. Power quality indication and PQ expert subsystem Power quality indicators. The power quality indication is one of the power quality expert functions, which gives the levels of power quality parameters compared with local utility standards: - Total voltage harmonic distortion (Thd_V), - Total current harmonic distortion (Thd_I), - Reactive power / active power (Tan), - Voltage unbalance (UnB.V), - Current unbalance (UnB.I). If there is violation of the limits, PQ Expert subsystem will propose, design and size an appropriate solution such as filter, unbalance compensator. The following example shows harmonic mitigation performed by PQ Expert subsystem for a foundry. At the 20 kv feeder, there are two disturbance loads: induction heating ovens equipped with 12-pulse rectifiers. On basis of voltage and current measurements from the site, the whole associated network is modelled and a PQ Expert subsystem is inserted at secondary of the 20 MVA transformer. Fig. 9. Phase current of designed active filter As the high power active filter is still more expensive than the passive filter, especially when the reactive power has to be compensated, a set of passive filters has been adopted for this site. Passive filter design. As the tangent value of this site exceeds the normalized limits, passive filter solution has been selected. PQ Expert sub system automatically designs a set of appropriate passive filters whose roles are to compensate the most important harmonic current and to correct power factor at the point of common coupling. The filter design takes account not only of theoretical calculations but also engineering parameters that can make it easier to contact a filter manufacturer. The automatic filter design is done in the following steps:

5 - Spectrum analysis with site measuring data, - Reactive power compensation at fundamental frequency, - Choice of type of filter, - Calculation of filter elements RLC, - Rated voltages and currents calculation, - Establishment of data sheet for filter manufacturer. According to the analysis of the above site data, the first harmonic current to be filtered is order 11 (550Hz for 50Hz fundamental). In order to avoid low harmonic parallel resonance with network impedance, the filters are designed from 250 Hz with the following engineering restrictions: - Upstream transformer short-circuit power = 130 MVA, - Rated line voltage = 20 kv, - Reactive power compensation = -5.4 MVAr, - Fundamental frequency = 50Hz, - Shunt filter frequencies = 250, 350, 550, 650 Hz, - Quality factor = 30 to 45. The fundamental reactive power and the quality factor are two important aspects to ensure filter stability. When filter power is 50% greater than that of the upstream power transformer, it is recommended to take necessary precautions in order to mitigate over voltage caused by passive filter. If there is important transient load (frequent motor starting), damped filter structure must be used. Based on the above site parameters, 4 shunt passive filters are designed by PQ Expert subsystem: Filter 250 Hz Filter 350 Hz Filter 550Hz Filter 650 Hz R (Ohm) L (mh) C (µf) With these four filters, the impedance at the point of common coupling is modified. They have shifted parallel resonance points to less harmful frequencies. The first parallel resonance frequency is moved to 197 Hz, which is lower than that of the lowest existing harmonic current. Phase-Phase Impedance Phase Impedance Voltages without filters Voltages with filters Fig. 11. Power quality indicators with compensation CONCLUSIONS This paper presents useful approaches for three-phase power quality analysis using full matrix modelling methods, which give truthful results for multi frequency calculation, particularly for power transformers, power lines and induction machines. The harmonic-unbalanced components make it inadequate to use single-phase model for harmonic analysis. Even in voltage dip investigation, symmetric model is insufficient to examine fault attenuation through a threelegged power transformers. For an industrial network harmonic diagnosis, it is recommended to use three-phase impedance calculation in order to reveal unbalance harmonic resonance. A pre-designed power quality expert unit in the software can give directly relative power quality levels compared with local utility standards. This function makes it easy to design and size an appropriate filter, compensator, etc. Frequency domain Norton network can be used for steady state power quality mitigation. It makes possible to simplify a studied complex electric grid system to a three-phase active component. REFERENCES [1] J. Arrillaga, C.P. Arnold, "Computer Analysis of Power System" John Willy & Sons, ISBN , [2] V. Brandwajn, H. W. Dommel, and I. I. Dommel, "Matrix representation of three-phase n-winding transformers for steady state and transient studies, IEEE Transactions on Power Apparatus and system, Vol. PAS-101, No.6 June Fig. 10. Impedance versus frequency at 20 kv busbar (with filters) All the filter components are calculated and verified by both RMS values and arithmetic sum values. With the designed filters, phase currents have been cleaned and complied with utilities power quality standards. After put into service of these four filters, a series of site measurements has shown that the voltage Thd was reduced from 9.8% to 2.1%. [3] X. Yang, B. Coze, "Modeling of power transformer, line and cable", Electricity of France, Clamart, France. Tech. Rep. HR-42/03/052-30, Nov [4] Georges J. Anders, "Rating of Electric Power Cables: Ampacity Computations for Transmission, Distribution, and Industrial Applications" IEEE ISBN , McGraw-Hill ISBN , 1997.

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers Journal Journal of of Emerging Emerging Trends Trends in in Engineering Engineering and and Applied Applied Sciences Sciences (JETEAS) (JETEAS) 1 1 (1): (1): 72-78 72-78 Scholarlink Research Institute

More information

Introduction. Harmonics and IEEE 519 Page 1 of 19

Introduction. Harmonics and IEEE 519 Page 1 of 19 Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES E Bompard*, E Carpaneto*, R Napoli*, P Ribaldone**, C Vercellino** * Dipartimento di Ingegneria Elettrica Industriale,

More information

Three phase circuits

Three phase circuits Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors

More information

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...

More information

7. Reactive energy compensation

7. Reactive energy compensation 593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical

More information

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT by Philip J. A. Ling, P.Eng. Cyril J. Eldridge, B. Sc. POWERSMITHS INTERNATIONAL

More information

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how

More information

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the

More information

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a Harmonics and transformers Harmonic component filter Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Variable Frequency Drives - a Comparison of VSI versus LCI Systems Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been

More information

The design and performance of Static Var Compensators for particle accelerators

The design and performance of Static Var Compensators for particle accelerators CERN-ACC-2015-0104 Karsten.Kahle@cern.ch The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,

More information

FREQUENCY CONTROLLED AC MOTOR DRIVE

FREQUENCY CONTROLLED AC MOTOR DRIVE FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly

More information

Topic Suggested Teaching Suggested Resources

Topic Suggested Teaching Suggested Resources Lesson 1 & 2: DC Networks Learning Outcome: Be able to apply electrical theorems to solve DC network problems Electrical theorems and DC network problems Introduction into the unit contents, aims & objectives

More information

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward

More information

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the

More information

Harmonics in your electrical system

Harmonics in your electrical system Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses

More information

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM E.Babu 1,R.Subramanian 2 1, Department of Electrical and electronics engg 2 Department of Electrical

More information

Scholars Research Library

Scholars Research Library Available online at www.scholarsresearchlibrary.com Scholars Research Library Archives of Applied Science Research, 2010, 2 (2):380-387 (http://scholarsresearchlibrary.com/archive.html) ISSN 0975-508X

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications Copyright Material IEEE Paper No. PCIC-2003-15 Tony Hoevenaars, P. Eng. Kurt LeDoux, P.E. Matt Colosino Member IEEE Member,

More information

INDUCTION REGULATOR. Objective:

INDUCTION REGULATOR. Objective: INDUCTION REGULATOR Objective: Using a wound rotor induction motor an Induction Regulator, study the effect of rotor position on the output voltage of the regulator. Also study its behaviour under load

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS LIST OF CONTENT 1. INTRODUCTION... 1 2. HARMONIC VOLTAGE ASSESSMENT REQUIREMENT IN THE UK... 2 3. THE ASSESSMENT... 2 3.1. SYSTEM MODELLING...3 3.2.

More information

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran A_lashkarara@hotmail.com Seyed Ali NABAVI NIAKI University of Mazandaran

More information

Chapter 24. Three-Phase Voltage Generation

Chapter 24. Three-Phase Voltage Generation Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use

More information

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC 61000-3-2

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC 61000-3-2 Electromagnetic Compatibility (EMC) Low-Frequency Standards Summary IEC 61000-3-2: Limits for harmonic current emissions (equipment input current 16A per phase) IEC 61000-3-4: Limitation of emission of

More information

HARMONICS AND HOW THEY RELATE TO POWER FACTOR. W. Mack Grady The University of Texas at Austin Austin, Texas 78712

HARMONICS AND HOW THEY RELATE TO POWER FACTOR. W. Mack Grady The University of Texas at Austin Austin, Texas 78712 Abstract HARMONICS AND HOW THEY RELATE TO POWER FACTOR W. Mack Grady The University of Texas at Austin Austin, Texas 787 Robert J. Gilleskie San Diego Gas & Electric San Diego, California 93 We are all

More information

Network Theory Question Bank

Network Theory Question Bank Network Theory Question Bank Unit-I JNTU SYLLABUS: Three Phase Circuits Three phase circuits: Phase sequence Star and delta connection Relation between line and phase voltages and currents in balanced

More information

(3 )Three Phase Alternating Voltage and Current

(3 )Three Phase Alternating Voltage and Current EEE 2015 EECTRCS (3) Monophase 1 Three phase Three phase electric power is a common method of alternating current electric power generation, transmission, and distribution. t is a type of polyphase system

More information

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

Power Quality Standards for Electric Service

Power Quality Standards for Electric Service Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as

More information

Harmonic Distortion and Variable Frequency Drives

Harmonic Distortion and Variable Frequency Drives Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation

More information

How To Understand And Understand The Theory Of Electricity

How To Understand And Understand The Theory Of Electricity DIRECT CURRENT AND ALTERNATING CURRENT SYSTEMS N. Rajkumar, Research Fellow, Energy Systems Group, City University Northampton Square, London EC1V 0HB, UK Keywords: Electrical energy, direct current, alternating

More information

High Frequency Modeling for Cable and Induction Motor Over-voltage Studies in Long Cable Drives

High Frequency Modeling for Cable and Induction Motor Over-voltage Studies in Long Cable Drives IEEE Industrial Application Society 36th Annual Meeting Page of 8 Chicago, Illinois, USA, September 3 October 5, High Frequency Modeling for Cable and Induction Motor Over-voltage Studies in Long Cable

More information

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to

More information

Module Title: Electrotechnology for Mech L7

Module Title: Electrotechnology for Mech L7 CORK INSTITUTE OF TECHNOLOGY INSTITIÚID TEICNEOLAÍOCHTA CHORCAÍ Autumn Examinations 2012 Module Title: Electrotechnology for Mech L7 Module Code: ELEC7007 School: School of Mechanical, Electrical and Process

More information

PM734F - Technical Data Sheet Winding 28

PM734F - Technical Data Sheet Winding 28 - Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including

More information

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Power Quality Issues, Impacts, and Mitigation for Industrial Customers Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing

More information

Open Phase Conditions in Transformers Analysis and Protection Algorithm

Open Phase Conditions in Transformers Analysis and Protection Algorithm Open Phase Conditions in Transformers Analysis and Protection Algorithm Amir Norouzi GE Digital Energy Markham, ON amir.norouzi@ge.com Abstract This paper first provides an in-depth analysis of open phase

More information

Power Electronics Testings

Power Electronics Testings Power Electronics Testings PV Inverter Test Solution www.chromaate.com Turnkey Test & Automation Solution Provider w w w.chromaate.com A PV system is an energy system which directly converts energy from

More information

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR INDEX NO. : M-142 TECHNICAL MANUAL FOR NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2000 Certified Company) 212/1, Mansarover Civil

More information

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Mirza Softić*, Amir Tokić**, Ivo Uglešić*** *Kreka - Dubrave e, Dubrave, Bosnia and Herzegovina (e-mail: softic_mirza@yahoo.com).

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit

More information

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction The Facts About Harmonics and Power Factor Power Quality: Harmonics & Power Factor Correction 1 Agenda I. Harmonic Basics II. Harmonic Mitigation Methods III. Active Harmonic Filters IV. Applications V.

More information

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1 Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =

More information

How To Improve Power Quality

How To Improve Power Quality Power Quality Improvement Of Three Phase Four Wire Distribution System Using VSC With A Zig-Zag Transformer Sajith Shaik *, I.Raghavendar ** *(Department of Electrical Engineering, Teegala Krishna Reddy

More information

3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS

3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS 3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS Pierre FRISTOT Olivier CONSTANT Catherine MONCET Omegawatt - France Omegawatt - France SDET - France pierre.fristot@omegawatt.fr

More information

3-Phase AC Calculations Revisited

3-Phase AC Calculations Revisited AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who

More information

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume

More information

Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current

Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current Summary Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current Joachim Härsjö, Massimo Bongiorno and Ola Carlson Chalmers University of Technology Energi och Miljö,

More information

CERN Accelerator School. Electrical Network and Power Converters. Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland

CERN Accelerator School. Electrical Network and Power Converters. Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland CERN Accelerator School Electrical Network and Power Converters Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland 1/ 21 / 17.5.2004 / HU Boksberger Outline Utility Standards

More information

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009 PotashCorp New Brunswick Division Picadilly Potash Project ETAP SIMULATION Prepared by: Carlos Reinel Senior Engineer R&D Department Power Survey International Approved by: Pierre Archambault, PEng. VP

More information

Paralleling Power Sources Which Share a Common Neutral

Paralleling Power Sources Which Share a Common Neutral Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share

More information

WIND TURBINE TECHNOLOGY

WIND TURBINE TECHNOLOGY Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems

More information

FREJA Win Software for FREJA relay testing system

FREJA Win Software for FREJA relay testing system Software for FREJA relay testing system A Megger Group Company Software for FREJA relay testing system In FREJA Win, the all-round General instrument program serves as a convenient, easy to understand,

More information

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka S S B Udugampala, V Vijayarajah, N T L W Vithanawasam, W M S C Weerasinghe, Supervised by: Eng J Karunanayake, Dr. K T M U Hemapala

More information

UCI274C - Technical Data Sheet

UCI274C - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards

More information

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC

More information

UCI274H - Technical Data Sheet

UCI274H - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors Applied and Computational Mechanics 3 (2009) 331 338 Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors M. Mikhov a, a Faculty of Automatics,

More information

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

Application Note AN- 1095

Application Note AN- 1095 Application Note AN- 1095 Design of the Inverter Output Filter for Motor Drives with IRAMS Power Modules Cesare Bocchiola Table of Contents Page Section 1: Introduction...2 Section 2 : Output Filter Design

More information

Chapter 12: Three Phase Circuits

Chapter 12: Three Phase Circuits Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in

More information

PI734D - Technical Data Sheet

PI734D - Technical Data Sheet PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

PI734B - Technical Data Sheet

PI734B - Technical Data Sheet PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

Electron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution

Electron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution lectron S..L. Design Production & Trading of ducational quipment A29 LCTICAL POW SYSTM TAINS Production Transmission Distribution FAX 9065 980 - -mail: electron@electron.it Web: www.electron.it ev 02 Specifications

More information

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution Nandita Dey, Dr.A.K.Chakraborty Lecturer, Electrical Engineering Department, Tripura University Suryamaninagar

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid

More information

However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.

However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence. Application note for Inrush Current Limiters (ICL) Turning on electrical devices generally cause high inrush currents which can damage electronic components and cause interruption of the line voltage if

More information

Developing a Utility/Customer Partnership To Improve Power Quality and Performance

Developing a Utility/Customer Partnership To Improve Power Quality and Performance Developing a Utility/Customer Partnership To Improve Power Quality and Performance Mark McGranaghan Electrotek Concepts Knoxville, TN Abstract Many industrial and commercial electric customers now require

More information

Survey of Harmonics Measurements in Electrical Distribution Systems

Survey of Harmonics Measurements in Electrical Distribution Systems Survey of Harmonics Measurements in Electrical Distribution Systems Leon M. Tolbert, Member, IEEE Oak Ridge National Laboratory* P.O. Box 28, Bldg Oak Ridge, TN 3783-6334 Alexandria, VA 2235-3862 Phone:

More information

APPLICATION OF IEEE STD 519-1992 HARMONIC LIMITS

APPLICATION OF IEEE STD 519-1992 HARMONIC LIMITS APPLCATON OF EEE STD 519-199 HARMONC LMTS Thomas M. Blooming, P.E. t.blooming@ieee.org Eaton Electrical Asheville, North Carolina Daniel J. Carnovale, P.E. DanielJCarnovale@eaton.com Eaton Electrical Pittsburgh,

More information

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University PURPOSE: The purpose of this lab is to introduce PSS/E. This lab will introduce the following aspects of PSS/E: Introduction to

More information

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY Carrier Corporation Syracuse, New York October 2005 TABLE OF CONTENTS INTRODUCTION..........................2

More information

A project to optimise quality and energy efficiency must include metering

A project to optimise quality and energy efficiency must include metering EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,

More information

Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants

Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants Mariana B. Pereira 1, Einar V. Larsen 2, Sebastian A. Achilles 3 Energy Consulting General Electric 1 Av. Magalhães de Castro 4800,

More information

Power Quality Paper #3

Power Quality Paper #3 The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production

More information

Transformers. Special transformers Reactors products

Transformers. Special transformers Reactors products Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having

More information

Verification of Short Circuit Test Results of Salient Poles Synchronous Generator

Verification of Short Circuit Test Results of Salient Poles Synchronous Generator Verification of Short Circuit Test Results of Salient Poles Synchronous Generator Abdul Jabbar Khan 1, Amjadullah Khattak 2 1 PG Student, University of Engineering and Technology, Peshawar, Department

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique

Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique NKV.Sai Sunil 1, K.Vinod Kumar 2 PG Student, GITAM University, Visakhapatnam, India. Asst.Professor, Department

More information

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321) Lab 4: 3-phase circuits. Objective: to study voltage-current relationships in 3-phase circuits; to learn to make delta and Y connections; to calculate and measure real, apparent, and reactive powers. Equipment:

More information

Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System

Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System W. EL-KHATTAM M. M. A. SALAMA Electrical & Computer Engineering, Waterloo University, Ontario, Canada Abstract: Due

More information