1 IT COOLING

2 Range of precision air conditioning units for IN-ROW installation available in the following versions: i. Direct Expansion air cooled: 2 models with nominal cooling capacity 25 & 40 kw. Water cooled version under evaluation ii. Chilled water: 2 models with nominal cooling capacity 50 & 60 kw. The COOL ROW range alongside the actual COOLSIDE EVO increasing the RC Group offer for precision air conditioning units for application in a fast growing market. 2

3 COOL ROW: fan section cold isle side with closed door 3

4 The ENERGY SAVING oriented general / operating characteristics as well as the fitted components allow to fully meet various and sophisticated needs of today Data Halls with hot spots / high concentrated loads: i. Application in installations with hot / cold isle lay-out, with or without containment ii. iii. iv. Installations requiring load sharing working logic, with ALL units in operation at partial load for maximum energy saving Cold isle temperature control through cooling capacity modulation based on supply air temperature Hot isle temperature or differential pressure control through air flow modulation 4

5 COOL ROW DX: main characteristics: i) Single cabinet for both models: 600 x 1200 x 2000(h) mm. ii) iii) iv) Back air return from hot aisle and frontal or side air supply into cold isle Built-in single scroll BLDC inverter compressors (EC compressor) specific for R410A Nr. 4 x Plug Fan Radical type with brushless EC electric motors in compliance with the ERP 2015 norm v) Finned package high efficiency evaporator with copper tubes and aluminum fins vi) Electronic expansion valve BLDC SCROLL COMPRESSOR ELECTRONIC EXPANSION VALVE VENTILATORE PLUG FAN Con motore elettrico di tipo EC 5

6 COOL ROW: fan section cold isle side with open door 6

7 COOL ROW DX: control system: Same advanced microprocessor fitted in NEXT EVO INVERTER for simultaneous control of cold isle temperature and either temperature or differential pressure of hot isle. Two control logic based on cooling capacity and air flow control: LOGIC 1: i. Cold isle temperature control through cooling capacity modulation. The BLDC inverter compressor changes the speed following the supply air temperature (supply air temperature control) ii. Hot isle temperature control through fan speed modulation. The Plug Fan EC type fans change the speed following the return air temperature (return air temperature control) 7

8 COOL ROW DX: control system: LOGIC 2: i. Cold isle temperature control through cooling capacity modulation. The BLDC inverter compressor changes the speed following the supply air temperature (supply air temperature control) ii. Hot isle differential pressure control through fan speed modulation. The Plug Fan EC type fans change the speed following the differential pressure between hot and cold isle (differential pressure control) 8

9 COOL ROW : i. CHW coil ii. electric panel iii. differential pressure sensor hot isle side with open door 9

10 COOL ROW DX: main accessories: i) Additional water coil ( extra-circuit) ii) iii) iv) 3 stage electric heater: 3 x 850 W Adiabatic ultrasonic humidifier: 1.0 kg/h Isotherm electrode humidifier: 2.0 kg/h v) G4 efficiency return air filter vi) Microprocessor accessories: same as NEXT EVO INVERTER 10

11 COOL ROW CW: main characteristics: i) Single cabinet for both models : 600 x 1200 x 2000(h) mm. ii) iii) iv) Back air return from hot aisle and frontal or side air supply into cold isle Nr. 4 x Plug Fan Radical type with brushless EC electric motors in compliance with the ERP 2015 norm Finned package high efficiency CHW coil with copper tubes and aluminum fins v) 2-way CHW valve 11

12 COOL ROW CW: control system: Same advanced microprocessor fitted in NEXT EVO CW for simultaneous control of cold isle temperature and either temperature or differential pressure of hot isle. Two control logic based on cooling capacity and air flow control : LOGIC 1: i. Cold isle temperature control through cooling capacity modulation. The CHW valve opens or closes following the supply air temperature (supply air temperature control) ii. Hot isle temperature control through fan speed modulation. The Plug Fan EC type fans change the speed following the return air temperature (return air temperature control) 12

13 COOL ROW CW: control system: LOGIC 2: i. Cold isle temperature control through cooling capacity modulation. The CHW valve opens or closes following the supply air temperature (supply air temperature control) ii. Hot isle differential pressure control through fan speed modulation. The Plug Fan EC type fans change the speed following the differential pressure between hot and cold isle (differential pressure control) 13

14 COOL ROW CW: main accessories: i. PICCV type CHW valve, independent from the pressure ii. iii. iv. Additional water coil (extra-circuit) 3 stage electric heater: 3 x 850 W Adiabatic ultrasonic humidifier: 1.0 kg/h v. Isotherm electrode humidifier: 2.0 kg/h vi. vii. G4 efficiency return air filter Microprocessor accessories: same as NEXT EVO CW 14

15 COOL ROW CW: the PICCV chilled water valve: Chilled water valve type PICCV (Pressure Independent Cooling Control Valve) One common body housing: - control valve - balancing valve - stop valve Advantages: - constant water flow when pressure changes - energy consumption optimization - simplified design - No balancing necessary for the plant 15

16 COOL ROW: i. CHW coil ii. PICCV valve iii. IN/OUT CHW pipes hot isle side with open door 16

17 COOL ROW: selling points i. Scroll inverter compressors BLDC (Brushless Direct Current) type (EC compressors) with very high energy efficiencies; higher than the ones of scroll inverter compressors no BLDC ii. iii. iv. Plug Fan EC radical type fans in accordance with the ERP 2015 Norm Large accessories availability, including PICCV type CHW valve Internal components lay-out, design of refrigerant /water pipes to minimize pressure drops on both air & refrigerant/watersides 17

18 Start here! Start with RC Group

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing

More information

CoolTeg Plus Chilled Water (CW) version: AC-TCW

CoolTeg Plus Chilled Water (CW) version: AC-TCW version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings

More information

Chilled Water Precision Air Conditioner For Critical Application

Chilled Water Precision Air Conditioner For Critical Application AIRSYS-P-SC-OPTIMA-HD-E1304V01.2 HD Chilled Water Precision Air Conditioner For Critical Application Cooling capacity: 42.1kW~161.5kW OPTIMA product family is designed for medium to large data center.

More information

STULZ View On DataCenter Cooling

STULZ View On DataCenter Cooling STULZ View On DataCenter Cooling Stulz Was Founded In Hamburg (Germany) In 1947 And Has 5 Production Sites And 14 Subsidiaries In 14 Countries. We Are Represented By Partners In Over 110 Countries. Stulz

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment The Intelligent Data Center Cooling Solution: Liebert CRV Trust the industry leader in Precision Cooling to deliver

More information

News in Data Center Cooling

News in Data Center Cooling News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle

More information

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

AIR SOURCE CHILLERS FOR OUTDOOR INSTALLATION

AIR SOURCE CHILLERS FOR OUTDOOR INSTALLATION AIR SOURCE CHILLERS FOR OUTDOOR INSTALLATION HIGH EFFICIENCY LATEST CONTROL SYSTEM LEED RELEVANT PRODUCT EXTREMELY SILENT OPERATIONS Features High efficiency chiller, air source for outdoor installation

More information

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy LG Air conditioning Company Multi V Water Ⅱ Air Conditioning Academy 1.1 What is Multi V Water II? High Performance Prospect rights Water pipe Refrigerant pipe Indoor unit Beautiful Exterior Convenience

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

IPSIP M series-m Modular Data Center

IPSIP M series-m Modular Data Center IPSIP M series-m Modular Data Center IPSIP MODULAR TECHNOLOGIES. 1 With the rapid development of cloud computing and mobile Internet businesses, the growth of IT density and energy consumption are bringing

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

Why Daikin? 2015 Houston, Texas USA www.daikincomfort.com

Why Daikin? 2015 Houston, Texas USA www.daikincomfort.com Why Daikin? Daikin: The Premium Brand industry leader Daikin is recognized as the world s number one leader in the manufacture of HVAC equipment and refrigerants. For over 90 years, Daikin has grown consistently

More information

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC & hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS

More information

Split units TH with hermetic compressors

Split units TH with hermetic compressors Split units TH with compressors Refrigeration units in split variant. Available with screw or solder terminal. Condensing unit with sound insulated weatherproof housing for outdoor installation. Split

More information

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units

More information

UR...3 URX CF...7 URHE CF...11. Heat recovery unit. Heat recovery unit with refrigerant circuit(442-1947 cfm)

UR...3 URX CF...7 URHE CF...11. Heat recovery unit. Heat recovery unit with refrigerant circuit(442-1947 cfm) UR...3 Heat recovery unit URX CF...7 Heat recovery unit with refrigerant circuit(442-1947 cfm) URHE CF...11 High efficiency heat recovery unit with refrigeration circuit(588-1942 cfm) UR Heat recovery

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

Local Dealer: www.cebrands.com

Local Dealer: www.cebrands.com Local Dealer: C.E. LLC - Miami, FL USA www.cebrands.com Res2012-Rev2 QUALITY YOU CAN FEEL Residential Product Line >TCA7,9 Tempstar SmartComfort TXT + Air Conditioner Featuring The Observer Communication

More information

CHILLED WATER DATA ROOM UNITS

CHILLED WATER DATA ROOM UNITS Critical Infrastructure for the World s Leading Data Centers CHILLED WATER DATA ROOM UNITS Downflow Net Sensible Cooling 79 220kW Upflow Net Sensible Cooling 66 206kW A Nortek Company DATA CENTER COOLING

More information

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Dr. Nguyen Nguyen An, HUST CONTENTS Energy consumption to produce hot water in residential

More information

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel. Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning

More information

60-150kW. For more information on Airedale visit www.barbourproductsearch.info SmartCool. 0-150kW. > SmartCool. www.airedale.com

60-150kW. For more information on Airedale visit www.barbourproductsearch.info SmartCool. 0-150kW. > SmartCool. www.airedale.com 60-150kW 0-150kW > Next generation precision air conditioning Typical applications > Data centres and computer rooms > Telecommunications and ISP facilities > Clean rooms > Switching stations > Laboratories

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for

More information

Commercial Portable Air Conditioners

Commercial Portable Air Conditioners Commercial Portable Air Conditioners Air Rover commercial portable air conditioners provide the environmental stability and comfort required by today s sensitive equipment, allowing your business to avoid

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

TWE+TTA TWE+TWA 6.25-20 T.R.

TWE+TTA TWE+TWA 6.25-20 T.R. TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Commercial Gas Heat Pump - VRF

Commercial Gas Heat Pump - VRF SANYO GHP Introduction Commercial Gas Heat Pump - VRF 01.12.2011 Agenda 1. SANYO GHP History 2. SANYO GHP Range 3. GHP Market Position 4. 2-WAY 5. GHP Power 6. 3-WAY 7. EER/COP 8. Water Heat Exchanger

More information

Technical data. Danfoss DHP-A

Technical data. Danfoss DHP-A Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW - AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2014

European Code of Conduct for Data Centre. Presentation of the Awards 2014 European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency

More information

Fan Coil Units. Fan coil units with brushless DC motor with inverter. your comfort. our world. » Up to 70% energy saving with BLDC motor technology

Fan Coil Units. Fan coil units with brushless DC motor with inverter. your comfort. our world. » Up to 70% energy saving with BLDC motor technology your comfort. our world.» Up to 70% energy saving with BLDC motor technology» Instant adjustment to temperature and relative humidity changes» Low noise levels» Highly flexible solutions Fan Coil Units

More information

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment

More information

PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS

PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS NOR-LAKE, INCORPORATED 727 Second Street P.O. Box 248 Hudson, Wisconsin 54016 800-955-5253 715-386-2323 866-961-5253 Parts 800-388-5253 Service 715-386-4291 FAX www.norlake.com Split-Pak Pre-Assembled

More information

III. Roof Mount AC Mobile Climate Control 19 MCC Reference Manual 2014

III. Roof Mount AC Mobile Climate Control 19 MCC Reference Manual 2014 III. Roof Mount AC Mobile Climate Control 19 MCC Reference Manual 2014 III.1. Large Roof Mount PN: 89-3037 Roof Mount Unit Eco 136 Parallel roof mount Air-conditioning and ventilation systems The Eco 136

More information

White Paper #10. Energy Efficiency in Computer Data Centers

White Paper #10. Energy Efficiency in Computer Data Centers s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular

More information

Appendix - Controllers 179

Appendix - Controllers 179 Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2

More information

"I'm a Daikin Comfort Pro"

I'm a Daikin Comfort Pro www.daikincomfort.com "I'm a Daikin Comfort Pro" Those five simple words can offer you comfort like you ve never experienced. The words mean that the dealer you invited into your home is a highlyqualified

More information

Advances in Gas Cooler Design and the New Gas Cooler Product Selector

Advances in Gas Cooler Design and the New Gas Cooler Product Selector Advances in Gas Cooler Design and the New Gas Cooler Product Selector Simon Jones Engineering Manager Sean Armitage Sales Manager Introduction GEA Searle Over 90 years experience in the design and manufacture

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

EHDC. Cooling system for Data Center and server cabinets.

EHDC. Cooling system for Data Center and server cabinets. EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment

More information

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...

More information

Defining Quality. Building Comfort. Heating and Cooling Coils

Defining Quality. Building Comfort. Heating and Cooling Coils Defining Quality. Building Comfort. Heating and Cooling Coils Heating and Cooling Coils Heating and Cooling Coils For over 20 years, AAON has supplied the coil needs of industrial and commercial HVAC customers.

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

IV. Rear Mount System

IV. Rear Mount System Mobile Climate Control 45 MCC Reference Manual 2014 PN: 89-3069 Rearmount Air Conditioning System Eco RM Capacity, Reliability, and Serviceability MCC Eco RM unit, selected as preferred equipment by leading

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

york airside products Delivering precision air conditioning for critical applications Serie R410A Close control air conditioners

york airside products Delivering precision air conditioning for critical applications Serie R410A Close control air conditioners york airside products Delivering precision air conditioning for critical applications Serie R410A Close control air conditioners Air Conditioners for Close Control and Data Centers High energy efficiency

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

NetApp Data Center Design

NetApp Data Center Design NetApp Data Center Design Presentation for SVLG Data Center Efficiency Summit November 5, 2014 Mark Skiff, PE, CEM, CFM Director, IT Data Center Solutions Data Center Design Evolution Capacity Build Cost

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

HUB RADIATOR HYBRID. Multi-energy hybrid system to produce heating and DHW. Multi-energy hybrid system to produce heating, cooling and DHW

HUB RADIATOR HYBRID. Multi-energy hybrid system to produce heating and DHW. Multi-energy hybrid system to produce heating, cooling and DHW is a multi-energy hybrid system that offers the consumer the ability to heat the house, and if necessary produce DHW also affect the environments. The platform, designed to offer innovative solutions for

More information

Technical Systems. Helen Bedford

Technical Systems. Helen Bedford Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

Mechanical Engineering Technician- Plant Technician

Mechanical Engineering Technician- Plant Technician Mechanical Engineering Technician- Plant Technician A competent Mechanical Engineering Technician- Plant Maintenance is expected to: 1. Ability to plan and execute work in a safe and responsible manner

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

marine/bespoke split applications

marine/bespoke split applications split applications marine/bespoke evaporators, condensers and split air conditioning systems suitable for a multitude of applications such as coastal, extreme high and low ambients, harsh dusty environments

More information

5-60kW. EasiCool Range. - 60kW. www.airedale.com. Typical Applications

5-60kW. EasiCool Range. - 60kW. www.airedale.com. Typical Applications 5-60kW - 60kW > Typical Applications > Telecommunications & ISP facilities > Computer rooms > Clean rooms > Switching stations > Laboratories www.airedale.com Specifications The newly developed EasiCool

More information

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT 48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED

More information

How To Test A Theory Of Power Supply

How To Test A Theory Of Power Supply A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade

More information

Data Centre. Flexible, high efficiency cooling solutions. www.airedale.com CONDITIONING CONDENSING UNITS CONTROLS SERVICE TRAINING

Data Centre. Flexible, high efficiency cooling solutions. www.airedale.com CONDITIONING CONDENSING UNITS CONTROLS SERVICE TRAINING Sector Data Centre Data Centre Flexible, high efficiency cooling solutions IT COOLING PRISION AIR CONDITIONING CHILLERS CONDENSERS & CONDENSING UNITS www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

EasiCool. 6-64kW DX AIR. www.airedale.com. Precision Air Conditioning

EasiCool. 6-64kW DX AIR. www.airedale.com. Precision Air Conditioning Precision Air Conditioning DX / CW EasiCool 6-64kW ENHANCED EASICOOL RANGE: + Up to 37% increase in EER + Up to 8% more cooling kw/m 2 Compared with our previous generation EasiCool units HFC R410A HFC

More information

MP-4000 Alarm List (Software version 2.4.3 or later)

MP-4000 Alarm List (Software version 2.4.3 or later) Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.

More information