MINKELS WATERCOOLED CABINET. The smart modular cooling solution

Size: px
Start display at page:

Download "MINKELS WATERCOOLED CABINET. The smart modular cooling solution"

Transcription

1 MINKELS WATERCOOLED CABINET The smart modular cooling solution

2 CLOSED LOOP SOLUTIONS In a closed loop setup the unit is integrated in the rack and the scope of the system is the rack. There are basically three types of closed loop installation. Because of the adjustable inlet valves and outlet direction of the EC fan the cooling module can be easily adjusted to the required setup. This results in flexible solutions for multiple scenarios. One cooling module can be installed on one cabinet and so deliver a cooling capacity of 24 kw per rack. This cooling capacity can be divided over two cabinets which results in a cooling capacity of 12 kw per rack. In case of installing two cooling modules on one rack you reach a cooling capacity of 48 kw or a redundant (1+1) solution for 24 kw. Functionality demands imposed on the IP network have continued to expand over recent years. This has increased processing power requirements and resulted in a higher potential impact (costs) of downtime. The IT industry responded to the increased processing requirements with high density computing, which has in turn placed higher demands on cooling. When it comes to cooling & energy efficiency, water cooling has proven to be one of the most (cost) effective methods. The Minkels OPEN LOOP SOLUTIONS In an open loop setup the unit is integrated in it s environment and the scope of the system is the room. The Minkels Watercooled module will be integrated in a traditional hot and cold aisle installation and draws the hot air from the back of the cabinets returning it as cold air to the front side of the cabinet. This hot and cold aisle setup is preferably optimised with a Minkels Cold Corridor. It can also fulfil your requirements in a redundant cooling scenario. Watercooled Cabinet (MWCC) combines the best technology and concepts, which are already accepted in the industry. This smart mix of proven technologies results in a unique and flexible solution. THE FLEXIBLE SOLUTION The cooling module can be installed in two ways: closed loop open loop The closed loop installation minimises the requirements from the room. All critical applications are isolated from the environment and stored in a single cabinet. The heat can be removed direct from the source and the room conditions can be secured less stringently. The cabinet conditions have to be controlled instead of the room conditions. A closed loop solution can be ideal for an SMB type company. All business applications can be centralised in a Minkels Watercooled Cabinet. Some low density applications, for example cabling and patching can be installed in a separated cabling rack. Minkels provides LANRack or Varicon M cabling solutions for this purpose. When you combine these units with today s virtualisation solutions the amount of business applications which can be located in one rack is impressive and will exceed the requirement of SMB type of companies. The Minkels Watercooled Cabinet enables you to standardise on cooling modules due to it s flexibility. The same module can be used in a datacentre and in MER or SER. The savings on maintenance and spare parts are significant especially when considered over time. It is hard to predict the future requirements of your IT environment, but with the Minkels Watercooled Cabinet one can adapt to every scenario. HYBRID LOOP SOLUTION This solution is a combination of a closed loop and an open loop solution. The hot air will be removed from the cabinet in the same way as a closed loop solution. This hot air will be cooled in the cooling module and presented to the Cold Corridor in the same way as an open loop solution. The total system is closed while the Cold Corridor prevents the cold air from mixing with the (warmer) ambient air. This solution doesn t require a raised floor.

3 Cooling capacity Number of Fans Width Height Depth Weight Electrical connections 24 kw mm 2000 mm 1200 mm 180 kg 230 VAC 50/60 Hz 700 Watt Max. waterflow 54 l/min Water temperature 12-18¼C* (min. 8¼C) Max. operating pressure 5 bar Water hose connection 1 inch Water content heat exchanger per MWCC 10,2 dm3 Max. airflow 5000 m3/h Air inlet temperature 20-25¼C** Recommended humidity on site 40-55%** * Advised water temperatures for 24 kw ** ASHRAE, Class 1,2 HEAT EXCHANGER The heat exchanger unit can be removed as a separate unit. The collector pipes divide the water among three individual heat exchangers, which are connected together. Each heat exchanger has 4 parallel channels among which the flow is divided. The construction is designed to provide a distributed temperature pattern along the heat exchanger. ENERGY EFFICIENCY AND SUSTAINABILITY The Minkels Watercooled Cabinet is designed with energy efficiency as the main criteria. The control unit of the Minkels Watercooled Cabinet is designed to optimise the system continuously. This delta T control results in a focus of cooling energy only where and when needed. The targeted area which requires cooling is especially minimised in a closed loop solution. Water is proven to be one of the most efficient media to transport heat (energy). The Air circulation within the cooling unit and the coil is optimised so minimal fan power is required to pump the air around. The combination of these elements results in an optimal cooling efficiency. The units flexibility can have an even bigger impact when taking the sustainability of your IT environment into consideration as it can follow the growth path of your IT environment. The Minkels Watercooled Cabinet can play a central role in any cooling strategy you apply in the future. This results in a longer lifetime and smaller impact on the environment. COST EFFICIENCY Standardising on the Minkels Watercooled Cabinet is easy considering it s flexibility and ease of integration with all cooling strategies. This results in significant savings on both OPEX and CAPEX. The savings on OPEX are basically on maintenance, spare parts and training of your operational staff. The operation of the equipment and fine tuning of the setting requires only a basic level of knowledge from your staff. Training and updating this knowledge is much easier for one standardised cooling unit than for a mixture of different sub optimised cooling units. Number of coils 3 Height 600 mm Width 250 mm Depth 176 mm Pressure loss heat exchanger per MWCC 19 kpa Number of channels 4 WATERVALVE Type 2-way, NO (Normally Open) Pressure drop 11 kpa* * At maximum recommended water flow

4 FANS Number of Fans 6 Fan type EC fan Air pressure loss in system 150 Pa Max. airflow per fan 830 m3/h Weight fan unit 6 kg In the event of control board failure the fan will automatically run in a safe mode at full speed. Each fan unit can easily be swapped in case of failure. REGULATING MECHANISM The regulating mechanism is simple. The dt over the equipment is derived from the measured values of T in and T out. Based on this value the fan speed is regulated. In order to maintain a correct inlet temperature (T in ) the ON/OFF watervalve is used. With an extra correction factor one is able to choose the relation between the dt and T in regulating mechanism. Fan speed regulation on dt The dt determines the fan speed. POWER BOX AND CONTROL BOX The power and control of the Watercooled Cabinet is located on the top section of the cabinet. The control and power is separately housed and hot swappable. In case the control board fails, the complete box can easily be exchanged without downtime. Power box Control box Fan speed regulation on T in (Optional) The inlet temperature regulates the fan speed. In fact this function helps to compensate for initial temperature differences Voltage 230 VAC 24 VDC Current max 5A 1A Function Switch A and B power supply Power EC fans Safe fan mode in case of control box failure Intelligent control Monitoring via display (on rack) or WIB7000 (online) Watervalve regulation on T in

5 Minkels Netherlands Eisenhowerweg 12 P.O. Box AA Veghel Tel. +31 (0) Fax +31 (0) Minkels Belgium Remysite Remylaan 4C - Bus Wijgmaal (Leuven) Tel. +32 (0) Fax +32 (0) info-be@minkels.com Minkels France Parc d activits de Malnoue 28, Rue Vlad. Jankelevitch Emerainville Tel. +33 (0) Fax +33 (0) info-fr@minkels.com Minkels Switzerland Riedstrasse 3-5 CH-6330 Cham Tel. +41 (0) Fax +41 (0) info-ch@minkels.com Minkels United Kingdom Unit 6, Union Way Hillbottom Road Sands Industrial Estate High Wycombe Bucks, HP12 4HJ Tel. +44 (0) Fax +44 (0) info-uk@minkels.com AN AEGIDE COMPANY MWCC08v02

M O N I T O R I N G S O L U T I O N S INFRASTRUCTURE MANAGEMENT SOLUTIONS. Varicontrol-P. The Integrated Rack Management System

M O N I T O R I N G S O L U T I O N S INFRASTRUCTURE MANAGEMENT SOLUTIONS. Varicontrol-P. The Integrated Rack Management System V RICONTROL M O N I T O R I N G S O L U T I O N S TM INFRASTRUCTURE MANAGEMENT SOLUTIONS Varicontrol-P The Integrated Rack Management System CONTROLLERS Varicontrol-P2, Varicontrol-P4 and Varicontrol-P6

More information

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use

More information

V RICONDITION C OOLING SOLUTIONS. Next Generation Cold Corridor. Takes modular thinking in energy-efficient data centre design to a new level

V RICONDITION C OOLING SOLUTIONS. Next Generation Cold Corridor. Takes modular thinking in energy-efficient data centre design to a new level V RICONDITION C OOLING SOLUTIONS Next Generation Cold Corridor Takes modular thinking in energy-efficient data centre design to a new level In 2006, Minkels became the first data centre supplier in Europe

More information

I N T E G R A T E D D A T A c E N T R E S O L U T I O N S

I N T E G R A T E D D A T A c E N T R E S O L U T I O N S INTEGRATED Data centre SOLUTIONS The Need for Flexibility A growing search for energy-efficiency, security and uptime enhancement, as well as technological developments like virtualization and cloud computing

More information

EHDC. Cooling system for Data Center and server cabinets.

EHDC. Cooling system for Data Center and server cabinets. EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment

More information

RICONPOWER POWER DISTRIBUTION SOLUTIONS. VariconPower. Rack Power Distribution Units

RICONPOWER POWER DISTRIBUTION SOLUTIONS. VariconPower. Rack Power Distribution Units V RICONPOWER POWER DISTRIBUTION SOLUTIONS VariconPower Rack Power Distribution Units Power is a business critical component of every server room and data centre. Any power disruption, even the smallest

More information

by knürr CoolTherm Server cabinet technology with outstanding benefits up to 35kW cooling capacity Blade-Server server optimized! www.knuerr.

by knürr CoolTherm Server cabinet technology with outstanding benefits up to 35kW cooling capacity Blade-Server server optimized! www.knuerr. HIGH DENSITY COOLING SOLUTIONS by knürr CoolTherm Server cabinet technology with outstanding benefits up to 35kW cooling capacity Blade-Server server optimized! optimiert! Setting benchmarks. Being the

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry

More information

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER Your Complete Turnkey Server Room Air Condition UPS THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER AVAILABLE IN WATER AND GAS SYSTEM MODEL AIR-CONDITIONED CABINET EXCELLENT TEMPERATURE CONTROL FOR

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Automation's Modular Containerized Datacenter Solutions

Automation's Modular Containerized Datacenter Solutions SAFE Automation's Modular Containerized Datacenter Solutions Automation's SAFE (Secure, Autonomous, Flexible, Efficient) Modular Containerized Datacenter offers a fast, flexible and efficient solution

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

Knürr DCL Modular Rack Cooling from 6 kw to 60 kw

Knürr DCL Modular Rack Cooling from 6 kw to 60 kw Knürr DCL Modular Rack Cooling from 6 kw to 60 kw Emerson Network Power Business-Critical Continuity so your success continues! Core competencies AC Power Connectivity DC Power Embedded Computing Embedded

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment The Intelligent Data Center Cooling Solution: Liebert CRV Trust the industry leader in Precision Cooling to deliver

More information

Refrigeration Compressed Air Dryer Buran Ultrapulse

Refrigeration Compressed Air Dryer Buran Ultrapulse Refrigeration Compressed Air Dryer Buran Ultrapulse There is more to compressed air than just compressing air Compressed air is an indispensable source of operating and processing power in all areas of

More information

Electric Flow Boiler

Electric Flow Boiler Electric Flow Boiler EHC offer the most comprehensive range of electric boilers in the market and with our wealth of knowledge and technical expertise we have designed the Slim Jim Electric Flow Boiler

More information

Reference Guide: SmartDesign Approach: Common Data Center Challenges:

Reference Guide: SmartDesign Approach: Common Data Center Challenges: Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Server Room Thermal Assessment

Server Room Thermal Assessment PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

30-120 3 Phase Modular Finally the benefits of Modular ups are for all

30-120 3 Phase Modular Finally the benefits of Modular ups are for all MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion

More information

Knürr CoolAdd The universal retrofit solution against overheating in server racks. Rack & Enclosure Systems

Knürr CoolAdd The universal retrofit solution against overheating in server racks. Rack & Enclosure Systems Knürr CoolAdd The universal retrofit solution against overheating in server racks Rack & Enclosure Systems Knürr CoolAdd When cold air is no longer enough! Data centers are subject to constant changes:

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

Rotary screw compressors kw 5,5 7,5 11 15 18,5 22 30 bar 8 10 13 15 MODULO

Rotary screw compressors kw 5,5 7,5 11 15 18,5 22 30 bar 8 10 13 15 MODULO Rotary screw compressors kw 5,5 7,5 11 15 18,5 22 30 bar 8 10 13 15 MODULO The sum of technology TriAB Air ends The BALMA screw compressors are fitted with the unique TriAB air ends that are designed and

More information

Rittal Liquid Cooling Series

Rittal Liquid Cooling Series Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de

More information

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings

More information

Center Thermal Management Can Live Together

Center Thermal Management Can Live Together Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Energy-efficient & scalable data center infrastructure design

Energy-efficient & scalable data center infrastructure design Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable

More information

RiMatrix S Make easy.

RiMatrix S Make easy. RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

INDUSTRIAL AUTOMATION EQUIPMENT EDITION 2016. www.elipse-automation.eu

INDUSTRIAL AUTOMATION EQUIPMENT EDITION 2016. www.elipse-automation.eu INDUSTRIAL AUTOMATION EQUIPMENT EDITION 2016 Your partner in an automated industry Our combination of technical know-how, product responsibility and on-time deliveries guarantees you the best WHY CHOOSE

More information

THE WORLD S MOST EFFICIENT DATA CENTER

THE WORLD S MOST EFFICIENT DATA CENTER THE WORLD S MOST EFFICIENT DATA CENTER HP POD 240a Ed Turkel Manager, WW HPC Marketing Hyperscale Business Unit 2011 Hewlett-Packard Development Company, L.P. The information contained herein is subject

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill

More information

Eight frames in three different sizes provide stylish and practical housing for the Crystal Vision modular product range

Eight frames in three different sizes provide stylish and practical housing for the Crystal Vision modular product range Eight s in three different sizes provide stylish and practical housing for the Crystal Vision modular product range WHICH FRAME DO YOU NEED? Indigo 2AE Indigo 2SE Indigo 1AE Indigo 1SE Indigo 1AE-DP Indigo

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Blade Server & Data Room Cooling Specialists

Blade Server & Data Room Cooling Specialists SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

CoolTeg Plus Chilled Water (CW) version: AC-TCW

CoolTeg Plus Chilled Water (CW) version: AC-TCW version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

The Concept. How Cassettair can benefit you. Applications. Selecting Cassettair

The Concept. How Cassettair can benefit you. Applications. Selecting Cassettair The Concept A Europe-wide research and development programme identified the need for a high performance cassette fan convector, powered by low pressure hot water and compatible with universal suspended

More information

AMTRON E-30 Compact heat and cooling meter

AMTRON E-30 Compact heat and cooling meter AMTRON E-30 Compact heat and cooling meter Application The compact AMTRON E-30 meter is used for energy consumption measurements for heating and cooling applications in small premises such as apartments,

More information

Measure Server delta- T using AUDIT- BUDDY

Measure Server delta- T using AUDIT- BUDDY Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Daikin Altherma hybrid heat pump. The natural combination

Daikin Altherma hybrid heat pump. The natural combination Daikin Altherma hybrid heat pump The natural combination Daikin Altherma hybrid heat pump, the natural combination Why choose Daikin Altherma hybrid heat pump? What the customer wants: more energy efficient

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

CANNON T4 MODULAR DATA CENTRE HALLS

CANNON T4 MODULAR DATA CENTRE HALLS CANNON T4 MODULAR DATA CENTRE HALLS Halve up-front investment, use a Modular fit out approach Highly efficient, Low PUE, Scalable system with reduced Capex and Opex Turnkey solutions available complete,

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

HFE1600 Series 1600W 1U Hot Swap Front End Power Supplies

HFE1600 Series 1600W 1U Hot Swap Front End Power Supplies 25.2W/in 3 power density Internal ORing MOSFET & Current Share Climate Savers Computing efficiency standards Up to 8000W in 1U rack Single and dual output 1U racks PMBus option HFE1600 Series 1600W 1U

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Designed for multi-injector endurance testing, the

Designed for multi-injector endurance testing, the Designed for multi-injector endurance testing, the ETB Test Bench can optionally provide shot-to-shot mass measurement. The injectors are precisely subject to variable controls and hydraulic pressures

More information

(Examples of various colocation sites)

(Examples of various colocation sites) Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company

More information

QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems

QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems The Professional Choice in Fluid Management QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems The Olaer Group is a global player specialising in innovative, efficient system

More information

Introducing AUDIT- BUDDY

Introducing AUDIT- BUDDY Introducing AUDIT- BUDDY Monitoring Temperature and Humidity for Greater Data Center Efficiency 202 Worcester Street, Unit 5, North Grafton, MA 01536 www.purkaylabs.com info@purkaylabs.com 1.774.261.4444

More information

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings. 1100 & 1400 Energy Controllers Satchwell 1100 & 1400 for energy-efficient temperature control in smaller buildings. 02 1100 & 1400 Energy Controllers Features he 1100 and 1400 Energy Controllers are self-configuring

More information

How To Make A Fronius Cl Power Inverter

How To Make A Fronius Cl Power Inverter Fronius CL PV central inverter with Fronius MIX concept Modular system. Maximum yield. The Fronius CL combines high-yield power electronics with the unique, modular system design of up to 15 identical

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing

More information

Advances in Gas Cooler Design and the New Gas Cooler Product Selector

Advances in Gas Cooler Design and the New Gas Cooler Product Selector Advances in Gas Cooler Design and the New Gas Cooler Product Selector Simon Jones Engineering Manager Sean Armitage Sales Manager Introduction GEA Searle Over 90 years experience in the design and manufacture

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

HYDRUS ULTRASONIC METER

HYDRUS ULTRASONIC METER HYDRUS APPLICATION HYDRUS is a static water meter based on the ultrasonic technology. This technology enables accurate calculation of water consumption and eliminates measuring deviations caused by sand,

More information

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION 1/16 Contents: 1. Introduction: the increasing importance of energy efficiency 1.1 Power consumers in the data

More information

Transmission System Total Cost of Ownership

Transmission System Total Cost of Ownership Transmission System Total Cost of Ownership February 2013 Featuring GatesAir s Geoff Mendenhall Technology Advisor Copyright 2015 GatesAir, Inc. All rights reserved. Transmission System - Total Cost of

More information

Aerona Air Source Heat Pumps

Aerona Air Source Heat Pumps ADDENDUM to INSTALLATION INSTRUCTIONS for Aerona Air Source Heat Pumps DOC.87-05/05 Rev.04 March 2013 ATTENTION INSTALLERS - UPDATED INFORMATION! Your Grant Aerona Air Source Heat Pump has a number of

More information

Advanced Heat Reclaim Systems. Harrison Horning, PE, CEM Delhaize America - Hannaford

Advanced Heat Reclaim Systems. Harrison Horning, PE, CEM Delhaize America - Hannaford Advanced Heat Reclaim Systems Harrison Horning, PE, CEM Delhaize America - Hannaford Outline Basic refrigeration cycle Conventional series heat reclaim Full-condensing parallel heat reclaim Direct Hydronic

More information

Case Study Nottingham Trent University

Case Study Nottingham Trent University Data Centre Solutions...energy efficient by design Case Study Nottingham Trent University Nottingham Trent University deploys Modular Data Centre Technology (MDC) Designed & Manufactured by Workspace Technology

More information

The NEW Greenstar i. intuitive. innovative. improved performance. installation ease

The NEW Greenstar i. intuitive. innovative. improved performance. installation ease The NEW Greenstar i innovative intuitive improved performance installation ease A NEW look, NEW features and a NEW NAME for the UK s best selling boiler, the Greenstar i Junior 1 Introducing the new Greenstar

More information

Data Center Cooling Modules

Data Center Cooling Modules Data Center Cooling Modules www.astmodular.com TABLE OF CONTENTS Executive Summary Worldwide PUEs Comparison Operational Expenditure & ROI Selection Guide & Features Real Projects EXECUTIVE SUMARY Data

More information

Heating, air-conditioning, cooling

Heating, air-conditioning, cooling Series description Design High efficiency, single stage, low pressure, inline centrifugal pump Supplied with EC motor and electronic duty adaptation Available in glanded construction, mechanical shaft

More information

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in

More information

Combi Unit Genius. The energy efficient Building Service Centre

Combi Unit Genius. The energy efficient Building Service Centre Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Combi Unit Genius The energy efficient Building Service Centre systemair Central Building Services

More information

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011 , 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.

More information

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power

More information