LOAD BANK PART NUMBER / OPERATIONS AND MAINTENANCE MANUAL
|
|
- Barbara Pitts
- 7 years ago
- Views:
Transcription
1 LOAD BANK PART NUMBER / OPERATIONS AND MAINTENANCE MANUAL Prepared by: 5455 N River RD W Geneva, OH Phone: TechSupport@get-psi.com HDT 1 TM /
2 TABLE OF CONTENTS 1.0 INTRODUCTION SAFETY CONSIDERATIONS CONNECTION PROCEDURE OPERATING PROCEDURES SPECIFICATION MAINTENANCE PROCEDURES FAULT FINDING 5 HDT 2 TM /
3 1.0 INTRODUCTION The / kw load bank is designed for applying load for testing or to prevent wet-stacking on a Diesel Engine Generator Set (DEG). It is designed to operate on 208VAC at 60Hz. The unit is comprised of pre-set, force air cooled, high powered resistor elements. Safety features include internal fuse protection, fan motor overload protection, and auxiliary circuit protection. The load bank is force air cooled by a three phase powered fan which is internally connected to the 3 phase load circuit, which represents a permanent load while the unit is in use. The enclosure is designed for outdoor use. 2.0 SAFETY CONSIDERATIONS 1. The load bank is designed for indoor or outdoor use. 2. The unit should only be operated by competent electrical engineers who are completely familiar with the operation and specification of the load bank. 3. The equipment is designed for AC operation only. 4. Operators must ensure that interconnecting cables are correctly rated to carry the required load current and adequately insulated to prevent the possibility of electric shock when operating at high voltages. 5. When in use the load bank should be isolated using safety barriers. 6. The load bank should only be operated in an area with adequate ventilation. 7. Care should be taken as the exhaust air outlet will be hot during operation. 8. Cables must be positioned away from the air exhaust. 9. During operation the load bank should not be covered or positioned to restrict air flow. 10. Caution some metal surfaces will be hot during operation 11. At the end of any test the fans should be kept running for 5 10 minutes at no load to remove the residual heat from the load bank case and elements. 12. There is a Power Distribution Block (PDB) located in the unit to permit the load cable to be hardwired to the load bank. 3.0 CONNECTION PROCEDURE 1. Ensure the power source to be tested is compatible with the load bank operating voltage. 2. Ensure the power source is de-engaged. 3. Do not attempt to operate the load bank above the maximum operating voltage. 4. Check that all panel mounted control switches are in the OFF position. 5. Connect phase A, B and C to L1, L2 and L3 respectively and connect the Neutral and Ground to the corresponding positions on the PDB in the load bank. 6. Connect cable to power source. 4.0 OPERATING INSTRUCTIONS HDT 3 TM /
4 Operators should read the SAFETY CONSIDERATIONS and CONNECTION PROCEDURE before carrying out the following operating instructions. 1. Ensure all panels are in place on the load bank. 2. Ensure all panel mounted switches are in the OFF position. 3. Energize the power source from the generator. 4. Switch on the panel mounted toggle switch. 5. Ensure the fan rotates in correct direction with exhaust air being expelled from the exhaust grill. If the fan rotates incorrectly the cables have been connected in the wrong phase rotation and the following procedure should be performed. a) Disconnect and isolated the power source. b) Change over any two phase connections c) Continue the operating procedure from 1 above 6. During running mode the load can be adjusted by moving the toggle switches to on. There is a 10kw load step and a 20kw load step. There is an indicator light that illuminates when the load step is activated. 7. Do not exceed the maximum rating of the load bank. 8. At the end of use switch the load bank to fan only (off load) for between 5 and 10 minutes to cool the resistor elements. 9. Isolate the generator power source. 10. DO NOT remove the power circuit with the load circuit energized. 5.0 SPECIFICATION Part Number: / Max operating voltage: 208V three phase 60 Hz Max current rating: 100A per phase Max power rating: 30 KW Connection: 1 five point PDB for hardwired connection Resistor tolerance: +/-5% Operating ambient temperature: -40 to +55 deg C Storage ambient temperature: -40 to +60 deg C Dimensions Length in Width in Height in 6.0 MAINTENANCE PROCEDURES HDT 4 TM /
5 The load bank should not require any special maintenance; however as with any electrical equipment periodic checks should be carried out to ensure the equipment is in a safe and satisfactory condition. The following periodic checks are recommended on the load bank; 1) Check the inlet and outlet grills are free from obstruction or debris. 2) Check that the controls and terminals are undamaged and secure. 3) Check the fan rotates freely without resistance. 4) Check connection cables are undamaged. 7.0 FAULT FINDING PROCEDURES The following fault finding procedure is intended to identify simple operational errors and has been categorized into possible problem areas as follows; Note: Isolate the load bank from any power source before removing any covers. Testing the load bank with the covers removed is not recommended as high voltages can be present on power resistors or terminals. Repair or replacement should be carried out by the manufacturer or trained personnel at the direction of the manufacturer. Issue/Symptom Cause Solution Cooling Fan not operational Fan contactor faulty. Circuit breaker not closed. Power coming to unit is not proper. Fan is faulty. Fuse is blown. Loose Wire. Check to see that control voltage is coming into the contactor and that all three phases of power are also available. If the contactor engages the problem is elsewhere. If not replace the contactor. Close the Circuit Breaker. If the breaker will not close check for continuity to ground. If continuity exists there is a short, investigate that. If no continuity exists replace the breaker. Ensure the power coming into the unit is 208 VAC 60Hz three phase with at least 100Amps supply. Replace the fan motor. Check and replace the fuse. Inspect the system for a loose wire connection. Issue/Symptom Cause Solution HDT 5 TM /
6 Does not provide sufficient Load Current Thermal Overload tripped Resistive element is open (faulty) Either load bank circuit breaker is off. Check to see if S4 or S5 are open. If there has been an over temperature condition the overload may need to cool before the unit will come back on line. If no over temperature condition exists the overload could be faulty. Isolate the overload and check to see if it is closed at room temperature (70F).It should be closed, if not replace the overload. Isolate the element and check for continuity. If there is no continuity the element is faulty. If there is continuity connect the wires and check at the top of the resistive element to see if the proper voltage is present. Check to see that amperage is present with an Amp Clamp. If amperage is present the element is ok. Engage the circuit breaker for the 10k or 20k. If the circuit breaker will not engage check for a short in the system. If the breaker will not close check for continuity to ground. If continuity exists there is a short, investigate that. If no continuity exists replace the breaker. Indicator light not functional Contactor faulty. Switch is faulty. Loose Wire. The bulb is blown. The fuse is blown. Improper input power. Replace the contactor. Replace the switch. Inspect the system for a loose wire connection. Replace the light. Check and replace the fuse. Restore input power to 208VAC 60Hz three phase. HDT 6 TM /
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
More informationSUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
More informationSingle Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
More informationDRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
More informationINSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI Page 2 / 16 CONTENTS 1 GENERAL... 3 2 SAFETY... 3 2.1 Safety instructions... 3 2.2 Correct use... 3 3 DESCRIPTION
More informationV94 BULK TAPE DEGAUSSER
TECHNICAL MANUAL Operating and Maintenance Instructions for V94 BULK TAPE DEGAUSSER V94 BULK TAPE DEGAUSSER TECHNICAL MANUAL Document No. M000208 Production Standard ZZ 009 415 WARNING To help minimise
More informationIndoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
More information543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
More informationARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
More information8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
More informationSection B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
More informationADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
More informationREFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca
More informationPS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY
PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY 7320 Ashcroft, Suite 104 Houston, Texas 77081 p: 713-772-1404 f: 713-772-7360 e: info@juicegoose.com www.juicegoose.com 06-06 CONGRATULATIONS
More informationUSER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
More informationREB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The
More informationMTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
More informationChromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION
Chromalox Installation, Operation RENEWAL PARTS IDENTIFICATION Portable Industrial Unit Blower Air Type DRA and DIVISION SALES REFERENCE DATE SECTION (Supersedes P-) PF-) NOVEMBER, 00 DRA PF- -0-00 Specifications
More information3000W Power Inverter
3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE
More informationService manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More information2 electrical. electrical. 2010 PulteGroup, Inc. All Rights Reserved.
2 12 2010 PulteGroup, Inc. All Rights Reserved. circuit breakers Circuit breakers protect your home s system from power failure. The wiring in your home is protected by circuit breakers. Circuit breakers,
More informationCONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page 2-7. 3-Phase Simplex Page 8-13
CONTROL PANEL INSTALLATION INSTRUCTIONS Single Phase Simplex Page 2-7 3-Phase Simplex Page 8-13 Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3 Manufactured by SJE-Rhombus Installation Instructions
More informationUHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
More informationChapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams
Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More information6. Diagnostics for A/C System Malfunction
6. A: A/C OR SELF-DIAGNOSIS SYSTEMS DO NOT OPERATE TROUBLE SYMPTOM: Set temperature is not indicated on the display, switch LEDs are faulty or switches do not operate. Self-diagnosis system does not operate.
More informationLG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
More informationLG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
More informationBulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
More informationFailure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
More informationHM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
More informationREGULINE 600VA / 1000VA REGULATOR USER MANUAL
REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate
More informationPSR The compact range Description
Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides
More informationIMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.
THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to
More informationAMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
More informationUSER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
More informationMODEL 300505 INSTALLATION INSTRUCTIONS
WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 info@burcam.com Your pump has been carefully packaged at the factory to prevent damage during shipping.
More informationInstallation Manual Version 7.3 IMPORTANT:
Installation Manual Version 7.3 IMPORTANT: READ ENTIRE MANUAL CAREFULLY, THIS PHASE CONVERTER MUST BE INSTALLED BY A INDUSTRIAL LICENSED ELECTRICIAN 230 VOLTS MODEL ONLY READ FIRST!!!!!! DANGER: HIGH VOLTAGE
More informationAir conditioning, electrical testing
just a test. Air conditioning, electrical testing 01-253 Wire and component test using VAG1598 A test box Special tools and equipment VAG 1598 A test box and VAG 1598/11 adapter cable and VAG 1598/12 VAG1526
More informationPDS-750-TR Touring Power Supply Operator s Manual
PDS-750-TR Touring Power Supply Operator s Manual Rev 1.2 2004 City Theatrical, Inc. Patent Pending 2 CONTENTS The City Theatrical PDS-750-TR...3 Cautions...3 Compliance Certifications...3 Compatibility
More informationOwner's/Installation Manual
Owner's/Installation Manual Power Management Module (PMM) and Starter Kit NOTE: The starter kit must be purchased and installed prior to individual PMM usage. Model Numbers: 00686-0 PMM 00699-0 PMM WITH
More informationMP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
More informationESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
More informationUSER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920
USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920 [This page intentionally left blank] Warning for Your Protection 1. Read these instructions. 2. Keep these
More informationBubble King. User Manual
Bubble King User Manual TABLE OF CONTENTS 1. Before You Begin... 3 What Is Included... 3 Unpacking Instructions... 3 Claims... 3 Text Conventions... 3 Icons... 3 Document Information... 3 Product at a
More informationPortable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
More informationPDS-375-TR Touring CB Power/Data Supply Operator s Manual Rev 1.2
PDS-375-TR Touring CB Power/Data Supply Operator s Manual Rev 1.2 2005 City Theatrical, Inc. Patent Pending The PDS-375 TR Power Supply page 2 CONTENTS The City Theatrical PDS-375 TR...3 Cautions...3 Compliance
More informationFor Models #6-5001, #6-7501, #10-7501 & #10-12K1
EmerGen Switch Manual Transfer Switch Manufactured by CONNECTICUT ELECTRIC SWITCH MFG. CO. 1-800-730-2557 OWNER S MANUAL & INSTALLATION INSTRUCTIONS For Models #6-5001, #6-7501, #10-7501 & #10-12K1 PLEASE
More informationINFRARED QUARTZ WALL HEATER
INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this
More informationST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
More informationhttp://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for
More informationR22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
More informationTECHNICAL MANUAL. Operating and Maintenance Instructions for. Manual Degausser
TECHNICAL MANUAL Operating and Maintenance Instructions for DIGI TAPEMASTER Manual Degausser DIGI TAPEMASTER TECHNICAL MANUAL Document No. M000263 Production Standard ZZ 009 154 ZZ 009 157 WARNING This
More informationHVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC
HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC Page. Basic Diagnostic Procedure.... General Description...3 3. Electrical Components Location...6 4. A/C Control Module I/O Signal...8 5. Self-diagnosis...0 6.
More informationAUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
More informationKESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850
INSTALLATION AND OPERATING INSTRUCTIONS KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850 Product advantages Automatic float switch as water
More informationWhat are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
More informationINSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION When installing or using any high voltage electrical appliance, basic safety precautions
More information3053 Electrical Safety Training Program Course Outline
3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting
More informationSection 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU
Automatic Temperature Control Diagnosis and Repair Diagnosis of Automatic A/C Systems The most common automatic A/C system malfunctions tend to be the result of basic air conditioning problems. These problems
More informationInverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
More informationTECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402
TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE
More informationOWNER S MANUAL BIG BEAR VORTEX FAN MODEL #BB-1 INTRODUCTION OPERATION SAFETY SERVICE WARRANTY CONTACT SPECIFICATIONS TROUBLESHOOTING
OWNER S MANUAL BIG BEAR VORTEX FAN MODEL #BB-1 INTRODUCTION OPERATION SAFETY SERVICE WARRANTY CONTACT SPECIFICATIONS TROUBLESHOOTING PLEASE READ AND SAVE THESE INSTRUCTIONS - 2 - INTRODUCTION TO THE BIG
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationOperating instructions
ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 7938 81-0 Fax +49 (0) 7938 81-110 info1@de.ebmpapst.com www.ebmpapst.com CONTENTS 1. SAFETY REGULATIONS AND S 1.1 Levels of hazard
More informationE2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
More informationUser s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
More information12. Inspection and Maintenance
12. and Maintenance Mandatory Be sure to inspect the inverter regularly and periodically to prevent it from breaking down because of the environment of use, such as temperature, humidity, dust and vibration,
More information2-Stage, 3-phase controller Type 30051/1500051
2-Stage, 3-phase controller Type 30051/1500051 Installation instructions Retain for future use System s for heating, cooling, ventilating ED I012/02/02/5GB Contents Correct and proper use Important information
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationTo suit Daikin FDY "F" Series and FD "F" Series. (and other models incorporating BRC1B62/52 Remote Controller)
OPERATION MANUAL Split System Ducted Air Conditioner To suit Daikin FDY "F" Series and FD "F" Series AIR CONDITIONER A hr o C (and other models incorporating BRC1B62/52 Remote Controller) Dear Owner, Thank
More information14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
More informationCENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit
Instructions CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Catalog Number 2100-SD1 Description The Bulletin 2100 smoke detector unit is a 0.5 space factor unit for use in Bulletin
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationWARMER or COOKER/WARMER
WARMER or COOKER/WARMER Use & Care Manual FW-S500 WARMER 3138365 Conforms to: UL STD: 197 3138365 Conforms to: NSF STD.4 FW-S600 COOKER / WARMER Model Description Size Voltage Hz Wattage FW-S500 Electric
More information*.ppt 11/2/2009 12:48 PM 1
Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers
More informationSAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content
More informationshopinkelowna.com/mr--electric---home- Electrician-West-Kelowna/648681.htm
shopinkelowna.com/mr--electric---home- Electrician-West-Kelowna/.htm Website Visibility: by Search Engine % Keyword Rankings: Summary Search engine Keywords Moved Up/Down - - Keyword Rankings Keyword Affordable
More informationETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
More informationNSI DIGITAL DIMMING SYSTEM DDS 9800 DIMMER PACKS
NSI DIGITAL DIMMING SYSTEM NSI DIGITAL DIMMING SYSTEM DDS 9800 DIMMER PACKS Software Revision 1.41, Version C UL, Mfg Q3/96, and above SPECIFICATIONS Number of Channels: 9800 : 8 channels Output capacity:
More informationOperating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
More informationPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Product description Wide rated operational voltage 208 600 V AC Wide rated control supply voltage 100 250 V, 50/60 Hz Rated operational current 18 to 370 A Wide ambient temperature range, -25 to +60 ºC
More informationLIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
More informationTopvex SX/C, Topvex TX/C. Air Handling Unit
Air Handling Unit Document in original language 131677-EN_GB 23-12-2015 A001 Contents 1 Declaration of Conformity... 1 2 Warnings... 2 3 Product information... 2 3.1 General... 2 3.2 Technical data...
More informationCHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
More informationThermo Top - Troubleshooting Tree
Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may
More informationSERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
More informationBC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC.
BC-5000 BATTERY CAPACITY TESTER OPERATIONS MANUAL COFKO LLC. COPYRIGHT 2010 1 UNPACKING As you unpack your new BC-5000 battery capacity tester, inspect the tester for signs of shipping damage. If shipping
More informationREVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)
SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY
More informationEVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. This Troubleshooting Guide covers the electric coolant valve and control
More informationSi10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
More informationOwner's Manual. Automatic Transfer Switch. This manual should remain with the unit.
Owner's Manual Automatic Transfer Switch REFERENCE THE OWNER'S MANUAL SUPPLIED WITH THE GENERATOR WHEN USING THIS DOCUMENTATION. NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS. THIS PRODUCT
More informationMULTI XS 3600. Battery charger. For lead-acid batteries 1,2-120Ah
MULTI XS 3600 Battery charger For lead-acid batteries 1,2-120Ah User s Manual and a guide to professional battery charging For Starter/Deep Cycle batteries EN INTRODUCTION Congratulations on your purchase
More information5W LED Energy Saver PIR Bulkhead
5W LED Energy Saver PIR Bulkhead Model: LED88PIR Black I n s t a l l a t i o n & Ope r a t i n g I n s t r u c t i o n s 1. General information: The unit utilises passive infrared technology to detect
More informationInstallation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P
Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P Distributed in the U.S.A. and Canada by CHENG USA, INC. Sales (574) 294-8997 Warranty Service (877) 294-8997
More informationTIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More informationNEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL info@tuncmatik.com / www.tuncmatik.com Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3.
More informationELECTRICAL SAFETY. The standard unit for measuring electrical current.
ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety
More information