1 Conquistador Condominium s Ewing Waterproofing Inspection Report 05 1

2 Monthly Assessment Report Report No: 05 Report Date: Sept 7, 2015 Project Name: Conquistador Condominiums Project Consultant(s): Scott F. Mulholland USBCI Communicated With: Mike Treadway & Justin Randolph Ewing Waterproofing Carol Young Association Manager Consultants Comments/Concerns: Ewing Waterproofing has been contracted to perform full waterproofing restoration of the Conquistador buildings exterior. The scope of work for the restoration repairs has been provided by USBCI. Ewing will be performing waterproofing of the first floor exterior walls and concrete stairs and second floor landings. This includes waterproofing coatings on the first floor exterior walls, concrete stairs and landing areas. Waterproofing sealants will also be used at all first floor wall mounted penetrations, balcony enclosure terminations, and all stairs and landing terminations. Ewing will also be performing concrete repairs at isolated locations on several buildings as it relates to concrete damage and delamination. These locations are isolated and the exact amount of damage is unclear until repairs start. USBCI has created a estimate total for concrete repairs based on the physical evidence. Ewing waterproofing will not be performing the concrete repairs. A General Contractor will be performing all concrete repairs associated with Conquistador. USBCI, the GC and county will coordinate together in documenting the locations and totals for all concrete repairs. Ewing has provided each building with an average cost for the remaining waterproofing repairs. USBCI will provide updates of the progress of all work in relation to the waterproofing repairs and will submit a report with each Pay Application to validate payments owed. Corporate Headquarters: 1722 NW 80th Blvd, Suite 70, Gainesville, Florida OFFICE: (352) Toll Free (888) 44 USBCI FAX: (321) WEBSITE: USBCI@USBUILDINGCONSULTANTS.COM SERVING CLIENTS THROUGH MULTIPLE OFFICES THROUGHOUT FLORIDA, NATIONALLY, AND INTERNATIONALLY 2

3 CONQUISTADOR CONDOMINIUMS WORK SUMMARY REPORT FOR PERIOD INCLUDED WITHIN July August BILLINGS Week 1-2 7/13/15 7/24/15 1. Completed the second coat of the AllGuard coating on the exterior walls of building 73 in Navarra Court. 2. Completed the second coat of the AllGuard coating on the exterior walls of buildings in Talavara Court. 3. Finished waterproofing sealants to the perimeter of the balcony screens on buildings in Navarra Court. 4. Finished waterproofing sealants to the perimeter of the balcony screens on buildings in Talavara Court. 5. Waterproofing sealants applied to the exterior of buildings in Talavara Court. Week 3-4 7/27/15 8/7/15 1. Completed the second coat of the AllGuard coating on the exterior walls of buildings in Talavara Court. 2. Completed the second coat of the AllGuard coating on the exterior walls of buildings in Aledo Court. 3. Finished waterproofing sealants to the perimeter of the balcony screens on buildings in Aledo Court. 4. Waterproofing sealants applied to the exterior of buildings in Aledo Court. 5. Painted underside of stairs and building in Catalonia Court. 6. Pressure washed buildings in Santiago Court and in Aledo Court. 7. Applied the base coat, aggregate and top coat to the stairs and landings on buildings in Catalonia Court. Week 5-6 8/10/15 8/21/15 1. Completed the second coat of the AllGuard coating on the exterior walls of buildings in Santiago Court. 2. Finished waterproofing sealants to the perimeter of the balcony screens on buildings in Santiago Court. 3. Waterproofing sealants applied to the exterior of buildings in Santiago Court. 4. Pressure washed buildings in Santiago Court and in Veronese Court. 5. Applied the base coat, aggregate and top coat to the stairs and landings on buildings in Catalonia Court 3

4 Overview of the Scope of Repairs Concrete Cracks Grind out all cracks found on the concrete landings greater than 1/16 of an inch. Pressure wash location before applying Sonolastic NP-2 or equal. Landing Perimeter Joint Apply a cant joint around the perimeter of the second level landing at the wood siding to concrete slab decking. The wood siding to concrete decking termination may vary from building to building. If the termination void is less than 3/8 of an inch, apply silicone bond breaker and NP2 sealant directly to the termination. If the termination void ranges from 3/8 to 3/4 of an inch, apply backer rod bond breaker and apply NP2 sealant. All terminations larger than 3/4 of an inch, apply silicone bond breaker and NP2 sealant at the vertical wall to deck termination. Waterproofing Deck Coating System Apply NEOGARD urethane deck coating system to the second floor landing area. Mockups of the coating system will be required as Detailed in the manufacturer specifications. Reference NEOGARD specifications for preparation and application methods. Stucco Cracking Grind out all cracks 1/16 of an inch or larger with crack chaser. Prime (if required) and apply Dow 790 sealant. Apply textured patching compound over all cracks prior to elastomeric coating application. Elastomeric Coating System Two coat application of Dow ALLGUARD to be applied to the exterior stucco cladding system on first floor level. Reference ALLGUARD manufacturer specifications for preparation and application methods. Exterior Cladding Penetrations All exterior cladding penetrations are to be properly sealed with Dow 790. Additional repairs may be required at isolated stucco penetrations as identified in the USBCI Details. This includes all balcony enclosure terminations. Corporate Headquarters: 1722 NW 80th Blvd, Suite 70, Gainesville, Florida OFFICE: (352) Toll Free (888) 44 USBCI FAX: (321) WEBSITE: USBCI@USBUILDINGCONSULTANTS.COM SERVING CLIENTS THROUGH MULTIPLE OFFICES THROUGHOUT FLORIDA, NATIONALLY, AND INTERNATIONALLY 4

5 All first floor exterior walls will have an elastomeric waterproof coating applied. 5

6 All concrete damage will be removed and replaced on the rear elevation of the buildings. These areas are isolated in Phase 1 of the property. All exterior wall penetrations and balcony enclosures will be sealed with waterproof sealants. 6

7 All stairs and 2 nd level landings will have concrete repairs done to damaged and or cracked locations. All stairs and landing terminations have waterproof sealants installed. All open handrail penetrations will be properly filled. All stairs and landings will have a waterproof coating applied. 7

8 All stairs and 2 nd level landings will have concrete repairs done to damaged and or cracked locations. All stairs and landing terminations have waterproof sealants installed. All open handrail penetrations will be properly filled. All stairs and landings will have a waterproof coating applied. 8

Exterior Elevated Elements Inspection Guidelines

Exterior Elevated Elements Inspection Guidelines Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code

More information

Mobile Home Pre-Inspection Checklist

Mobile Home Pre-Inspection Checklist Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING

More information

Stucco and Windows on Wood Frame Construction. Maintaining the Water-shedding Barrier

Stucco and Windows on Wood Frame Construction. Maintaining the Water-shedding Barrier Stucco and Windows on Wood Frame Construction Maintaining the Water-shedding Barrier What is the Water-shedding Barrier? Figure 2-5 Critical barriers of the typical window-wall interface, RESIDENTIAL WINDOW

More information

Williamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, 2013. (68 pages)

Williamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, 2013. (68 pages) INNOVATIVE BUILDING AND ARCHITECTURE CONSULTANTS Mr. Bud Hall Senior Vice President of construction Turnberry Associates 19501 Biscayne Boulevard, Suite 400 Aventura, FL 33180 Subject: The Nashville Hilton

More information

STATE OF FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF FLORIDA LAND SALES, CONDOMINIUMS, AND MOBILE HOMES

STATE OF FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF FLORIDA LAND SALES, CONDOMINIUMS, AND MOBILE HOMES STATE OF FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF FLORIDA LAND SALES, CONDOMINIUMS, AND MOBILE HOMES IN RE: PETITION FOR ARBITRATION THE PRIVATEER SOUTH CONDOMINIUM ASSOCIATION,

More information

Block Lofts Condominiums

Block Lofts Condominiums Block Lofts Condominiums Building Envelope Condition Assessment 747 Ralph McGill Boulevard Atlanta, Georgia Presented to: Block Lofts Condominium Home Owners Association C/o Heritage Property Management

More information

Reference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls

Reference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls Reference: BRM-00220488-A0 July 18 th, 2014 Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Re: 1.0 Introduction Exp Services Inc. (exp) was retained by the Toronto

More information

March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202

March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request

More information

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,

More information

Masonry and Concrete Repair and Restoration

Masonry and Concrete Repair and Restoration 2041 W. Carroll Chicago, IL 60612 Tel: 312-666-4646 Fax: 312-666-6066 Email: info@emiusa.net Masonry and Concrete Repair and Restoration Masonry Repair Concrete Repair & Restoration Business Information

More information

StuccoSpec Moisture Testing Inspection

StuccoSpec Moisture Testing Inspection e-mail - stuccospec@juno.com StuccoSpec Moisture Testing Inspection Property Located At: 265 Elm Street, Anywhere, USA 01/27/02 Ordered by: Mr. & Mrs. John Doe #2 Song Sparrow Place, The Woodlands, T 77381281-364-0012

More information

Certification: Building Plans Examiner. Exam ID: B3

Certification: Building Plans Examiner. Exam ID: B3 Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building

More information

Finegan Inspection Services, Inc.

Finegan Inspection Services, Inc. Finegan Inspection Services, Inc. Report Prepared For: Phone 513-683-0733 Fa 513-697-0163 Owners Property Address City, State, ZIP Phone FAX Owners Realtor Realty Company Phone FAX OWNER INFORMATION PROPERTY

More information

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:

More information

FIRESTOPPING & SMOKE SEALS

FIRESTOPPING & SMOKE SEALS SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of

More information

PETERSONS WATERFRONT CONDOMINIUMS

PETERSONS WATERFRONT CONDOMINIUMS CONSULT DESIGN CONSTRUCT PETERSONS WATERFRONT CONDOMINIUMS 103 Park Street Chelan, Washington Findings Summary Report Prepared for: Petersons Waterfront Condominium Association March 21, 2014 J2 Project

More information

Stucco Moisture Inspection Report

Stucco Moisture Inspection Report Stucco Moisture Inspection Report For the Property Located At: Sample Inspection St. Report Prepared Ecusively For: Potential Buyer Pace FL. 32571 >< 850.393.6106 >< ofc- 850-941-8600 > Email: pat@moistureconsultantsinc.com

More information

3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations

3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations 3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations Any penetration through the stucco that is left unsealed will allow entry of moisture. Even an average size home can have an extreme

More information

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,

More information

University of Missouri Hospitals and Clinics. Structural Repair and Protection of Post-tensioned Parking Garage

University of Missouri Hospitals and Clinics. Structural Repair and Protection of Post-tensioned Parking Garage University of Missouri Hospitals and Clinics Structural Repair and Protection of Post-tensioned Parking Garage 1 University of Missouri Project The University of Missouri Health Care Patient and Visitor

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

Building Foundation and Structure

Building Foundation and Structure Building Foundation and Structure Overview The construction of the Hall of Waters building began in 1936, and was constructed over the original site of the Siloam and Sulpho-Saline Springs. The original

More information

USER GUIDE Easier, Safer, Betta! www.gripsetbetta.com WATERPROOFING

USER GUIDE Easier, Safer, Betta! www.gripsetbetta.com WATERPROOFING USER GUIDE Easier, Safer, Betta! www.gripsetbetta.com WATERPROOFING Welcome to Gripset Betta, Over the past 3 decades through the tireless commitment to improve and enhance the way buildings are waterproofed,

More information

Figure 1 The GENERAL CONTRACTOR blames the applicator (if available) for improper installation and

Figure 1 The GENERAL CONTRACTOR blames the applicator (if available) for improper installation and BACKGROUND History The Exterior Insulation and Finish System (EIFS) was originally developed in West Germany in the 1960s. The original market for EIFS was providing an insulation layer to existing masonry

More information

WORK SUMMARY April 17, 2015

WORK SUMMARY April 17, 2015 1 A Roof Damaged condenser fins at CU-1, CU-1A, and CU-2A. Rake all condenser fins at CU-1, CU-1A, and CU-2A. 66 3 units 2 A Roof Unacceptable/damaged paint finish at sheet metal parapet Sand/re-paint

More information

City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage

City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage Property Address: Company Name: Contractor Name: Contractor Address: City: State: Zip: License Number: Phone Number

More information

Historic Esmont Virginia Post Office Renovation

Historic Esmont Virginia Post Office Renovation Historic Esmont Virginia Post Office Renovation 2008-03-09 06:00:00 by BeamsPainting Historic Esmont Post Office Beams Painting had the pleasure of planning and implementing the restoration of historic

More information

The AQUAFIN Approach to Concrete Repair

The AQUAFIN Approach to Concrete Repair Concrete Repair Building Product Systems Waterproofing & Concrete Restoration Decorative Coatings Moisture Vapor Remediation & Flooring Injection Grouting The AQUAFIN Approach to Concrete Repair www.aquafin.net

More information

Sample Drawing Package for One and Two Family Dwelling Applications

Sample Drawing Package for One and Two Family Dwelling Applications Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx

More information

Water Damage & Repair

Water Damage & Repair Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below

More information

Dow Corning AllGuard Silicone Elastomeric Coating. Application and Maintenance Guide

Dow Corning AllGuard Silicone Elastomeric Coating. Application and Maintenance Guide Dow Corning AllGuard Silicone Elastomeric Coating Application and Maintenance Guide Contents This document is intended to provide installation and field testing instructions for Dow Corning AllGuard Silicone

More information

ARROWHEAD GENERAL INSURANCE AGENCY RESIDENTIAL EARTHQUAKE INSURANCE PROGRAM UNDERWRITING GUIDELINES & RATE MANUAL

ARROWHEAD GENERAL INSURANCE AGENCY RESIDENTIAL EARTHQUAKE INSURANCE PROGRAM UNDERWRITING GUIDELINES & RATE MANUAL UNDERWRITING GUIDELINES & RATE MANUAL Arrowhead General Insurance Agency, Inc. Page 1 of 8 Producers Manual June 2001 UNDERWRITING GUIDELINES A. BINDING AUTHORITY/ELIGIBILITY Binding and risk approval

More information

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state

More information

EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES

EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES FAILING WATERPROOFING

More information

2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award George Washington University Ross Hall Façade Restoration

2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award George Washington University Ross Hall Façade Restoration 2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award George Washington University Ross Hall Façade Restoration 2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award

More information

DryvitCARE Frequently Asked Questions

DryvitCARE Frequently Asked Questions DryvitCARE Frequently Asked Questions DS702 DC1.0 DC2.0 DC3.0 DC4.0 DC5.0 DC6.0 Frequently Asked Questions General Warranty Technical Third Party Expert Overclad Application Sealant Frequently Asked Questions

More information

STRUCTURAL ASSESSMENT

STRUCTURAL ASSESSMENT STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha

More information

Assessing Curtain Walls

Assessing Curtain Walls Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC pbeers@gciconsultants.com What is a Curtain Wall System? A curtain wall system is an outer covering of a building

More information

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

A. This Section includes rubberized asphalt sheet membrane waterproofing systems. SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: Somewhere, FL CLIENT: GAIA GC ID No: 2015000 DATE: 12/31/2015 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792 FLORIDA

More information

PROPOSAL. Prepared for: Craig Mottram & Family, 118 Rangoon Rd. Prepared by: Carlos Andrade, Owner & Operator. Brandon Andrade, Project Coordinator

PROPOSAL. Prepared for: Craig Mottram & Family, 118 Rangoon Rd. Prepared by: Carlos Andrade, Owner & Operator. Brandon Andrade, Project Coordinator PROPOSAL Prepared for: Craig Mottram & Family, 118 Rangoon Rd. Prepared by: Carlos Andrade, Owner & Operator Brandon Andrade, Project Coordinator t. 416.652.6424 f. 416.652.3234 May 1 st, 2012 Craig Mottram

More information

Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration

Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration DS497 SECTION ONE A. Objective The objective of this guide is to provide owners and general contractors/construction

More information

Facts on Water Intrusion. Water Intrusion Causes Major Problems Before and After Construction. July 1, 2011

Facts on Water Intrusion. Water Intrusion Causes Major Problems Before and After Construction. July 1, 2011 Water Intrusion Causes Major Problems Before and After Construction By Scott Spiderman Mulholland CGC CDDC CMR CMA CIEC When buildings leak, the environmental, structural and long term performance can

More information

The minimum reinforcement for the stem wall is the placement of:

The minimum reinforcement for the stem wall is the placement of: PolySteel creates an ideal insulated stem wall for concrete slabs that can make this part of your project easier and faster, in addition to making your finished project more energy-efficient. Figures 3.20

More information

Melbourne balcony Assessments

Melbourne balcony Assessments Balcony Assessment Melbourne balcony Assessments Address: SAMPLE Date: Assessor: Luke O Neill Registered Builder DBL-C 31305 Assessment Guidelines This is an assessment of balcony and elements as presented

More information

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Simpson Engineering A state licensed engineering firm F-1607

Simpson Engineering A state licensed engineering firm F-1607 Simpson Engineering A state licensed engineering firm F-1607 4126 Allencrest 13901 Midway Lane, Dallas, Road, Texas Ste.102-136 75244 Telephone: 214-351-1637 Dallas, - Fax: TX 214-351-1639 75244-4388 Telephone:

More information

Repair of Spalling and Leaking Clay Brick Building Walls

Repair of Spalling and Leaking Clay Brick Building Walls B etter buildings Repair of Spalling and Leaking Clay Brick Building Walls Overview A few years after being built in Waterloo in 1980, a condominium of three, six-storey buildings showed severe spalling

More information

D Sample Notices to Property Owners, Sample Affidavits, and Other Material

D Sample Notices to Property Owners, Sample Affidavits, and Other Material D Sample Notices to Property Owners, Sample Affidavits, and Other Material These samples are offered to illustrate specific points in the Desk Reference. States and communities should examine them carefully

More information

ADDENDUM NO. 2. DATE: September 14, 2015 INVITATION FOR BID: IFB J160004535 Fire Station #22 Roof Replacement Project DATED: August 25, 2015

ADDENDUM NO. 2. DATE: September 14, 2015 INVITATION FOR BID: IFB J160004535 Fire Station #22 Roof Replacement Project DATED: August 25, 2015 ADDENDUM NO. 2 DATE: September 14, 2015 INVITATION FOR BID: IFB J160004535 Fire Station #22 Roof Replacement Project DATED: August 25, 2015 RECEIPT DATE: September 30, 2015 (CHANGED) OPENING DATE: October

More information

RDH Building Sciences Inc.

RDH Building Sciences Inc. MAK LTR 2007 03 26 Proposal for Building Enclosure Consulting Services RDH Building Sciences Inc. 509 FAIRVIEW AVENUE N SEATTLE WA 98109-5507 TEL 206 324 2272 FAX 206 324 6339 SEA@RDHBE.COM WWW.RDHBE.COM

More information

Window Installation Instructions

Window Installation Instructions Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for

More information

KWA Engineers, LLC Consulting Structural Engineers

KWA Engineers, LLC Consulting Structural Engineers KWA Engineers, LLC Consulting Structural Engineers October 14, 2014 Ms. Sylvia Dowling, President-Board of Directors Ms. Ray Stoudt, Maintenance Manager Aliki Condominium 2828 North Atlantic Avenue Daytona

More information

The Ultimate in Weathersealing Versatility. Dow Corning 123 Silicone Seal

The Ultimate in Weathersealing Versatility. Dow Corning 123 Silicone Seal The Ultimate in Weathersealing Versatility Dow Corning 123 Silicone Seal Effective and attractive EIFS restoration When urethane sealants fail on EIFS-clad buildings, leaks and interior damage typically

More information

Braselton Bros. Store Redevelopment 5134 HWY 53 BRASELTON, GA 30548 LEVEL 0 - DEMO & NEW PLAN. Room. Room. Room. Room. Room. Room. Room. Room.

Braselton Bros. Store Redevelopment 5134 HWY 53 BRASELTON, GA 30548 LEVEL 0 - DEMO & NEW PLAN. Room. Room. Room. Room. Room. Room. Room. Room. 1.d 2.d 3.d 4.d 1.d 2.d 3.d 4.d REMOVE, REPAIR, & REPLACE EXISTING STOREFRONT SYSTEMS D.1 D.2 REMOVE, REPAIR, & REPLACE EXISTING STOREFRONT SYSTEMS D.1 D.2 REMOVE STAIR & INFILL WALL C.1 REMOVE DOOR &

More information

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44

More information

Construction Coatings

Construction Coatings Deck Coatings Decorative Rooftop Living Plaza Deck Waterproofing Low Odor Metal and Roof Membrane Restoration Mechanical Room Waterproof Coating POLYTUFF SYSTEMS INTERNATIONAL www.polytuffus.com Decorative

More information

Vista del Cañon Newsletter May 2002

Vista del Cañon Newsletter May 2002 Vista del Cañon Newsletter May 2002 ROOFING SCHEDULE New flat roof installation is now underway for buildings in retrofit Phases 3-8. Phases 1 and 2 have already had new flat roofs installed. Rite-Way

More information

Rehabilitation Strategies for Bonded Concrete Overlays of Asphalt Pavements

Rehabilitation Strategies for Bonded Concrete Overlays of Asphalt Pavements University of Pittsburgh Rehabilitation Strategies for Bonded Concrete Overlays of Asphalt Pavements Authors: J. M Vandenbossche S. Sachs August 2013 1. Introduction Bonded concrete overlays of asphalt

More information

How To Repair A Boat Landing Deck With A Boat Bed

How To Repair A Boat Landing Deck With A Boat Bed RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing

More information

When dealing with a potential moisture problem, time is of the essence. Taking a proactive approach will save you money and headaches down the road.

When dealing with a potential moisture problem, time is of the essence. Taking a proactive approach will save you money and headaches down the road. If you own a house clad in something known as exterior insulated finish systems (EIFS), also known as synthetic stucco, you are probably trying to cope with a small but growing feeling of anxiety. You

More information

Business area System/product family System/product Exterior restore group. Sto restore Advanced Restoration for Building Façades

Business area System/product family System/product Exterior restore group. Sto restore Advanced Restoration for Building Façades Business area System/product family System/product Exterior restore group Sto restore Advanced Restoration for Building Façades Sto restore Restoring building exteriors to protect the value of your investment.

More information

CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS

CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS CCU Engineering Specifications Section 003300 Effective Date: Nov. 1st, 2011 Page 1 of 5 PRECAST CONCRETE PRODUCTS PART 1 - GENERAL The following specification is intended for use for the design, selection

More information

Metropolitan Builders Association Masonry & Concrete Standard

Metropolitan Builders Association Masonry & Concrete Standard Metropolitan Builders Association Masonry & Concrete Standard Background Masonry and concrete work in residential construction often provides the base structure upon which the house is built or as a veneer.

More information

Estimated Cost of Repair

Estimated Cost of Repair 1 Applicant: Property: Home: Business: Assessor: Applicant Number: Type of Loss: Hurricane Date Contacted: 1/18/2014 Date of Loss: 10/29/2012 Date Received: 1/14/2014 Date Inspected: 2/4/2014 Date Entered:

More information

State of Connecticut Department of Public Health RADON PROGRAM

State of Connecticut Department of Public Health RADON PROGRAM State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon

More information

I N T E R N A T I O N A L R E S I D E N T I A L CO D E

I N T E R N A T I O N A L R E S I D E N T I A L CO D E Visual Interpretation Of The I N T E R N A T I O N A L R E S I D E N T I A L CO D E 2006 STAIR BUILDING CODE Portions of this document reproduce sections from the 2006 International Residential Code, International

More information

A0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET

A0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET POYNTZ AVENUE, STE 9 MANHATTAN, KS 0..0..9 FAX WEST th STREET JUNCTION CITY, KS.... FAX 0, Bruce McMillan AIA, Architects, P.A. HERITAGE TRUST FUND GRANT PROJECT NO. 0-0 ROOF REPAIR OF THE 00 LOCUST STREET

More information

BTC. Building Technology Consultants, PC 1845 E. Rand Road, Suite L-100 Arlington Heights, Illinois 60004 Main: (847) 454-8800, Fax: (847) 454-8801

BTC. Building Technology Consultants, PC 1845 E. Rand Road, Suite L-100 Arlington Heights, Illinois 60004 Main: (847) 454-8800, Fax: (847) 454-8801 BTC Structural Engineer Hpreicher@btcpc.com Patrick E. Reicher is a Structural Engineer at Building Technology Consultants, PC. 6BREGISTRATIONS Licensed Structural Engineer (SE), Illinois Certified Construction

More information

Residential Decks. Planning and Development Services Department

Residential Decks. Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Engineering Evaluation

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

How To Prevent Water Damage To A Home

How To Prevent Water Damage To A Home Having inspected about 800 homes in the last four years, I have seen a lot of problems with many homes. Most of these problems are minor; however, there are some problems that are quite serious. One of

More information

etter buildings Lessons learned: Restoring the Quayside Village leaky condo CASE STUDY NUMBER 50 Introduction

etter buildings Lessons learned: Restoring the Quayside Village leaky condo CASE STUDY NUMBER 50 Introduction B etter buildings North Vancouver, B.C. CASE STUDY NUMBER 50 Lessons learned: Restoring the Quayside Village leaky condo Introduction This case study describes how the Quayside Village Co-housing community

More information

Structure Survey Findings:

Structure Survey Findings: Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,

More information

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792

More information

September 1, 2003 CONCRETE MANUAL 5-694.900 CONCRETE PAVEMENT REHABILITATION 5-694.900

September 1, 2003 CONCRETE MANUAL 5-694.900 CONCRETE PAVEMENT REHABILITATION 5-694.900 September 1, 2003 CONCRETE MANUAL 5-694.900 5-694.901 GENERAL CONCRETE PAVEMENT REHABILITATION 5-694.900 Concrete Pavement Rehabilitation is an extremely valuable tool of the Minnesota Department of Transportation

More information

Building Condition Assessment Report

Building Condition Assessment Report Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.

More information

School Construction Authority Architecture & Engineering

School Construction Authority Architecture & Engineering SCOPING GUIDELINES 1.0 GENERAL GUIDELINES 2.0 BUILDING ENVELOPE SCOPING GUIDELINES 3.0 CATEGORIES AND COMPONENTS: The Flood Elimination/Below Grade Capital Category may include some or all of the following

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13

More information

~iffiui ~ Bridge Condition Survey. Inspection Date: 21 May 2003 District: San Angelo County: Tom Green Highway:

~iffiui ~ Bridge Condition Survey. Inspection Date: 21 May 2003 District: San Angelo County: Tom Green Highway: Texas Depadment of Transpo,tation Bridge Condition Survey Inspection Date: 21 May 2003 District: San Angelo County: Tom Green Highway: Irving Street Facility Name: Lone Wolf Bridge Structure Number: B00315-031

More information

How To Use Dow Corning Brand Sealants

How To Use Dow Corning Brand Sealants Dow Corning EIFS Restoration Guide This document is intended to provide installation and field testing instructions for Dow Corning brand sealants, coatings and primers for EIFS applications in order to

More information

Consumer Aid for Post Construction Contracts and Termite Treatments

Consumer Aid for Post Construction Contracts and Termite Treatments State of Florida Department of Agriculture and Consumer Services Consumer Aid for Post Construction Contracts and Termite Treatments A Guide for Residential Homeowners Bureau of Inspection and Incident

More information

SECTION 3 ONM & J STRUCTURAL ANALYSIS

SECTION 3 ONM & J STRUCTURAL ANALYSIS Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION

More information

THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING

THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING DIVISION 7 THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING 07110. MEMBRANE WATERPROOFING: The following are minimum requirements to assure adequately designed waterproofed floors for machine and equipment

More information

ADMINISTRATIVE SERVICES PROVIDED

ADMINISTRATIVE SERVICES PROVIDED ADMINISTRATIVE SERVICES PROVIDED Full Service Contracts Provide 24 hour answering services to receive emergency calls and take approved action as necessary Communicate with various Board, Committee members

More information

University of California - Santa Barbara West Campus Point Faculty Housing

University of California - Santa Barbara West Campus Point Faculty Housing University of California - Santa Barbara West Campus Point Faculty Housing Reconstruction Guidelines and Considerations to Correct Exterior Building Envelope Weatherproofing Defects and Recommended Upgrades

More information

http://www.iccsafe.org/

http://www.iccsafe.org/ Sections R311 and R312 from the 2006 International Residential Code These sections of Chapter 3 of the 2006 International Residential Code for One and Two Family Dwellings (R311 and R312) including the

More information

Fire Barriers & Fire Stopping

Fire Barriers & Fire Stopping Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire

More information

Important Information for Installer & Homeowner

Important Information for Installer & Homeowner Important Information for Installer & Homeowner Homeowner: Please keep this information for your records, do not discard! Installation Instructions for Wood Frame Construction Replacement (See other side

More information

Hardcoat Stucco Moisture Evaluation

Hardcoat Stucco Moisture Evaluation Hardcoat Stucco Moisture Evaluation For the Property Located At: 217 Glen Haven Ct. Anywhere NJ 08057 Report Prepared For: Mr. Homeowner 786 Garwood Rd Moorestown NJ 08057 Ph: 856-235-0564 Website: www.victoryhomeinspections.com

More information

A and S Property Inspector

A and S Property Inspector Cover Page A and S Property Inspector Property Inspection Report Inspection prepared for: xxxxx xxxxx Real Estate Agent:.. - Date of Inspection: 8/25/2014 Time: 10am Age of Home: 1999 Size: 1841 Weather:

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

Sealant. 30" Model No. 35020. D: 17-7/8" TO 18-3/8" (454 to 466mm) W: 29-3/4" TO 30-1/4" (756 to 768mm) Under Countertop Installation

Sealant. 30 Model No. 35020. D: 17-7/8 TO 18-3/8 (454 to 466mm) W: 29-3/4 TO 30-1/4 (756 to 768mm) Under Countertop Installation INSTALLATION INSTRUCTIONS CARE AND MAINTENANCE London Kitchen Sinks 24" Sink model number 35030 30" Sink model number 35020 36" Sink model number 35040 Thank you for selecting Porcher. To ensure this product

More information

VJ ASSOCIATES 1825 K STREET NW, #1100 WASHINGTON, DC - 20006 TEL: (202) 609-7480 INITIAL PROJECT COST ANALYSIS

VJ ASSOCIATES 1825 K STREET NW, #1100 WASHINGTON, DC - 20006 TEL: (202) 609-7480 INITIAL PROJECT COST ANALYSIS VJ ASSOCIATES 1825 K STREET NW, #1100 WASHINGTON, DC - 20006 TEL: (202) 609-7480 INITIAL PROJECT COST ANALYSIS January 7, 2014 0 BASIS OF ESTIMATE The estimate is based on the drawings and documents received

More information

PERFORMANCE GUIDELINES

PERFORMANCE GUIDELINES 1. Foundation/Basement 17 PERFORMANCE GUIDELINES 1. FOUNDATION/BASEMENT 1.1 Efflorescence on concrete or masonry surfaces Efflorescence is the formation of a white crystalline or powdery deposit on the

More information

Claridge Condominium Association, Inc. 7515 Pelican Bay Blvd. Naples, FL 34108

Claridge Condominium Association, Inc. 7515 Pelican Bay Blvd. Naples, FL 34108 Claridge Condominium Association, Inc. 7515 Pelican Bay Blvd. Naples, FL 34108 APPROVAL OF HURRICANE SHUTTERS PROCEDURES RESOLUTION OF THE BOARD OF DIRECTORS AT THE CLARIDGE WHEREAS, Claridge Condominium

More information

SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)

SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the

More information

SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES

SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES SECTION 33 05 16.13 PRECAST CONCRETE PART 1 - GENERAL 1.01 SECTION INCLUDES A. This item shall consist of the construction of both sanitary and storm sewer precast concrete manholes in accordance with

More information