(Statute, Rule, FBC, Industry) (11)(a) (5)

Size: px
Start display at page:

Download "(Statute, Rule, FBC, Industry) (11)(a) (5)"

Transcription

1 Code Reference NFPA ( ( (New) Florida Specific Amendment Anytime a reference is made to NFPA 1 or NFPA 101 within this Code, it shall be the Florida specific version of NFPA 1 and NFPA 101. The Florida Building Code shall be referred to anytime a reference is made to the building code or to NFPA 220, Standard on Types of Building Construction in this Code or an adopted standard. If deemed necessary by a fire official for a complete, accurate, and thorough firesafety plans review or inspection, the fire official may request assistance from the building, electrical, plumbing, or similar specialty inspector; however, nothing in this rule gives authority or jurisdiction to any person other than a firesafety inspector certified under Section , Florida Statutes, to perform firesafety inspections required by law, rule, ordinance, or code. Reason for Amendment (Statute, Rule, FBC, Industry) Disposition SERC Y/N "Catch all" language to ensure the FBC is referenced as the building code Keeping ( ( ( ( ( ( (2009) 1.7 (2012) Conflicts. When a requirement differs between this Code and a referenced document, the requirement of this Code shall apply. When a conflict between a general requirement and a specific requirement occurs, the specific requirement shall apply. Florida Fire Prevention Code and Florida Building Code Interrelation. The Florida Fire Prevention Code contains several provisions and requirements that may interrelate with the Florida Building Code. It is not the intent of this Code that such interrelation result in duplicate reviews and inspections by either the firesafety authority or the building official. The authority having jurisdiction over firesafety is responsible for enforcement of the Florida Fire Prevention Code hereof, and, in the event that a dispute arises regarding the enforcement of the Florida Fire Prevention Code as related to the enforcement of the Florida Building Code, the authority having jurisdiction over firesafety shall resolve the dispute by the procedure set forth in Chapter 633 and Chapter 553, Florida Statutes, as required by Section (5), Florida Statutes (11)(a) (5) Language from NFPA 1, 2012 ed Language from NFPA 1, 2012 ed Language from NFPA 1, 2012 ed (11)(a) In the event of a conflict between the Florida Building Code and the Florida Fire Prevention Code and the Life Safety Code as applied to a specific project, the conflict shall be resolved by agreement between the local building code enforcement official and the local fire code enforcement official in favor of the requirement of the code which offers the greatest degree of lifesafety or alternatives which would provide an equivalent degree of lifesafety and an equivalent method of construction. Page 1 NFPA 101

2 NFPA 220, Standard on Types of Building Construction, 2009 edition. NFPA 1971, Standard on Protective Ensembles for Structural Fire Fighting and Proximity Fire Fighting, 2007 edition. NFPA 5000, Building Construction and Safety Code, 2006 edition (2) Now only deleting NFPA 220 ASCE 7, Minimum Desing Loads for Buildings and Other Structures, F.S as deletion (2) The State Fire Marshal shall adopt the National Fire Protection Association s Standard 1, Fire Prevention Code but shall not adopt a building, mechanical, or plumbing code. The State Fire Marshal shall adopt the Life Safety Code, Pamphlet 101, current editions, by reference. The State Fire Marshal may modify the selected codes and standards as needed to accommodate the specific needs of the state. 3.1 The definitions contained in this chapter shall apply to the terms used in this Code. Where terms are not included, common usage of the terms shall apply. The following terms, for the purposes of this Code, shall have the meanings given in this chapter, if not otherwise modified by another chapter. Words used in the present tense shall include the future; words used in the masculine gender shall include the feminine and neuter; the singular number shall include the plural, and the plural number shall include the singular. Where terms are not defined in this chapter or within another chapter, they shall be defined using the definition within the Florida Building Code. their ordinarily accepted meanings within the context in which they are used. Webster s Third New International Dictionary of the English Language, Unabridged, shall be a source for ordinarily accepted meaning NFPA 101, 12 ed has similar language. Uses Merriam-Webster's Collegiate Dictionary, 11th edition (New) Where terms are not defined in this chapter, within another chapter, or the Florida Building Code, they shall be defined using their ordinarily accepted meanings within the context in which they are used. Webster s Third New International Dictionary of the English Language, Unabridged, shall be a source for ordinarily accepted meaning. Fireblocking. Barriers installed to resist the movement of flame and gases to other areas of a building through small concealed passages in building components such as floors, walls, and stairs. Fire Code. The Florida Fire Prevention Code as defined in F.S The fire code enforced by the jurisdiciton or agency enforcing this Code using the strikethrough language from 101:3.1 (base code) FBC F.S FIREBLOCKING. Building materials or materials approved for use as fireblocking, installed to resist the free passage of flame to other areas of the building through concealed spaces. New definition in 2012 NFPA 101. Page 2 NFPA 101

3 ( (2012 Open Parking Structure. A parking structure that, at each parking level, has wall FBC 406.3, see also FBC openings open to the atmosphere, for an area of not less than 1.4 ft2 for each linear foot (0.4 m2 for each linear meter) of its exterior perimeter. Such openings are distributed over at least 40 percent of the building perimeter or uniformly over two opposing sides. Interior wall lines and column lines are at least 20 percent open, with openings distributed to provide ventilation. (1) A structure used for the parking or storage of motor vehicles that have: (a) at least 50% of the clear height between floors shall be open to the atmosphere for the full length of at least two exterior walls, excluding required stair and elevator walls and structural columns. Interior wall lines and column lines shall be at least 20% open and uniformly distributed or, (b) the exterior walls of the structure shall have uniformly distributed openings on two or more sides totaling no less than 40% of the building perimeter. The area of such openings in the exterior walls on each level shall be at least 20% of the total perimeter wall area of each level. Interior wall lines and column lines shall be at least 20% open and uniformly distributed. (2) The distance from any point on any floor level to an open exterior wall facing on a street, or to other permanently maintained open space at least 20ft (6096mm) wide extending full width to a street shall not exceed 200ft (61m). (3) Garages within 10 ft (3048mm) of a common property or building line shall be provided with an enclosure wall along the line of not less than 1-hour fire resistance without openings therein, except door openings meeting the requirements of shall be permitted. removing - new 2013 FBC is consistent with 2012 NFPA 101, FBC current language is similar to NFPA 101 base code; renumbered to 101: refers to 101: which uses NFPA 88A: definition language. FBC (2013 ed) states Openings. For natural ventilation purposes, the exterior side of the structure shall have uniformly distributed openings on two or more sides. The area of such openings in exterior walls on a tier shall be not less than 20 percent of the total perimeter wall area of each tier. The aggregate length of the openings considered to be providing natural ventilation shall be not less than 40 percent of the perimeter of the tier. Interior walls shall be not less than 20 percent open with uniformly distributed openings. Exception: Openings are not required to be distributed over 40 percent of the building perimeter where the required openings are uniformly distributed over two opposing sides of the building. (2) 200 ft came from NFPA 88A; (3) 1 hr separation came from FBC; Section Area and height increases. The allowable area and height of open parking garages shall be increased in accordance with the provision of this seciton. Garages with sides open on three-fourths of the building's perimeter are permitted to be increased by 25% in area and one tier in height. Garages with sides open around the entire building's perimeter are permitted to be increased by 50% in area and one tier in height. For a side to be considered open under the above provisions, the total area of openings along the side shall not be less than 50% of the interior area of the side at each tier and such openings shall be equally distributed along the length of the tier. For purposes of calculating the interior area of the side, the height shall not exceed 7 ft. Table (Exception) (New) Exception For one-story or two-story structures that are less than 10,000 square feet, whose occupancy is defined in the Florida Building Code and the Florida Fire Prevention Code as business or mercantile, the authority having jurisdiction shall enforce the wall fire-rating provisions for occupancy separation as defined in the Florida Building Code ; SB (3) Portions of buildings used as accessory offices or for customary nonhazardous uses necessary for transacting the principal business in storage and industrial occupancies need not be separated from the principal use. (4) Industrial occupancies producing, using, or storing low hazard products in accordance with Subdivision need not be separated by fire-resistant construction from the occupancies to which they are accessory. FBC 509 Not change in 101, 12 ed; FBC - limits area not more than 10 % of the building area of the story, no separation required between accessory occupancies and main occupancy Page 3 NFPA 101

4 Incidental use areas shall be separated as required by Table of the Florida Building Code where Table permits an automatic fire-extinguishing system without a fire barrier, the incidental use area shall be separated by construction capable of resisting the passage of smoke. FBC 509, NFPA 101, 12 ed: (Mixed Occupancies) Each portion of the building shall be classified as to its use in accrdance with Section * The building shall comply with the most restricitve requirements of the occupancies involved, unless seperate safeguards are approved.[new] A Example of uses that might be incidental to another occupancy include... A For example, common path of travel that occurs wholly in a business tenant space, in a multiple ocupancy building containing assembly and business, should not have to meet the assembly occupancy common path of travel limitations. [NEW] The following accessory occupancies shall not be required to be separated from the primary occupancy as required in : (1) A kitchen in an assembly occupancy does not constitute a mixed occupancy. (2) Accessory uses in industrial and storage occupancies as otherwise provided in (1) (3) Rooms or spaces used for customary storage of non-hazardous materials in assembly, business, educational, industrial, mercantile, hotel and dormitory, and apartment occupancies which in aggregate do not exceed one-third of the major floor area in which they are located. Protection from hazards shall be as otherwise provided in the specific occupancy chapter. FBC ; changed one-third to 10% Not in 101, current or 12 ed; FBC - limits area not more than 10 % of the building area of the story, no separation required between accessory occupancies and main occupancy Thresholds at door openings shall not exceed ½ in. (13 mm) in height. Exception: Thresholds at exterior sliding doorways serving dwelling units shall not exceed ¾ inch (19.1mm) in height. FBC ; (9) The provisions of the Life Safety Code shall not apply to newly constructed one-family and two-family dwellings. However, fire sprinkler protection may be permitted by local government in lieu of other fire protectionrelated development requirements for such structures. While local governments may adopt fire sprinkler requirements for one- and twofamily dwellings under this subsection, it is the intent of the Legislature that the economic consequences of the fire sprinkler mandate on home owners be studied before the enactment of such a requirement (6) The door shall be power operated and shall be capable of being operated manually in the event of power failure. (3) Stairways, not a part of the required means of egress, providing access from the outside grade level to the basement in rooming houses, rectories, and parsonages shall be exempt from when the maximum height from the basement finished floor level to grade adjacent to the stair does not exceed 8 ft. (2438mm) and the grade level opening to the stair is covered by hinged doors or other approved means. FBC (1) No provisions in FBC or FS Not change in 101, 12 ed; Horizontal Sliding Doors Not change in 101, 12 ed Page 4 NFPA 101

5 Where the occupant load served does not exceed five three, spiral stairs shall be permitted, provided that the following criteria are met: (6) Handrails shall be provided on both sides of the stairway. Exception: Handrails required on one side within dwelling units, guest rooms and guest suites. FBC & (9) Not change in 101, 12 ed FBC - (1) Occ load does not exceed three & from mezzanines not exceeding 250 sq. ft (2) dwelling units, guest rooms & guest suites occ. load does not exceed five The provisions of the Life Safety Code shall not apply to newly constructed one-family and two-family dwellings. However, fire sprinkler protection may be permitted by local government in lieu of other fire protection-related development requirements for such structures. While local governments may adopt fire sprinkler requirements for one- and two-family dwellings under this subsection, it is the intent of the Legislature that the economic consequences of the fire sprinkler mandate on home owners be studied before the enactment of such a requirement Each stair, platform, and landing, not including handrails and existing stairs, in buildings required in the Florida Building Code to be of Type I or Type II construction and all buildings of assembly occupancy with an occupant load of 1000 or more persons, or of an assembly occupancy with a legitimate stage and an occupant load of 700 or more persons shall be of noncombustible material throughout. Stairways located in a required fire resistant enclosure shall have closed risers. All other stairways shall be permitted to have open risers. Interior stairs constructed of wood shall be fire-blocked in concealed spaces between stair stringers at the top and bottom of the run. Fireblocking shall comply with Subdivision (c). FBC ; See also Section 410, Stages & Platforms FBC - Possible FBC? Not change in 101, 12 ed; FBC - All stairways shall be built of materials consistent with the types permitted for the type of construction of the building, except that wood handrails shall be permitted for all types of construction. Not change in 101, 12 ed; not in 101 Not change in 101, 12 ed; not in 101 Exception: Stairs permitted to have open risers in accordance with Subdivision The underside of interior stairways, if of combustible construction, shall be protected to provide not less than 1-hour fire resistance FBC? Not change in 101, 12 ed; not in Exception: When located within a dwelling unit. If not vertical, risers on other than existing stairs shall be permitted to slope under the tread at an angle not to exceed 30 degrees from vertical, provided that the projection of the nosing does not exceed 11/4 in. (32mm) (38 mm). FBC Not change in 101, 12 ed; not in 101; FBC - Risers shall be solid and vertical or sloped under the tread above from the underside of the nosing above at an angle not more than 30 degrees (0.52 rad) from the vertical. The leading edge (nosings) of treads shall project not more than 11/4 inches (32 mm) beyond the tread below and all projections of the leading edges shall be of uniform size, including the leading edge of the floor at the top of a flight. Page 5 NFPA 101

6 Projections. Stairs shall be clear of all obstructions except projections not exceeding 4 ½ in. (114mm) at or below handrail height on each side. The design of guards and handrails and the hardware for attaching handrails to guards, balusters, or walls shall be such that there are no projections that might engage loose clothing. Openings in guards shall be designed to prevent loose clothing from becoming wedged in such openings. New handrails on stairs shall be uniform, not less than 34 in. (865 mm), and not more than 38 in. (965 mm), above the surface of the tread, measured vertically to the top of the rail from the leading edge of the tread. New handrails shall be installed to provide a clearance of not less than 1 ½ in (32mm) 2¼ in. (57 mm) between the handrail and the wall to which it is fastened. FBC FBC FBC Differs from 101 existing and 12 ed; FBC - On ramps, the clear width between handrails shall be 36 inches (914 mm) minimum. Projections into the required width of stairways and ramps at each handrail shall not exceed 41/2 inches (114 mm) at or below the handrail height. Projections into the required width shall not be limited above the minimum headroom height required in Section Differs from 101 existing and 12 ed; FBC uses "uniform" Differs from 101 existing and 12 ed; FBC - Clear space between a handrail and a wall or other surface shall be a minimum of 11/2 inches (38 mm). A handrail and a wall or other surface adjacent to the handrail shall be free of any sharp or abrasive elements (Guard Details) (4) Guardrails for individual guest rooms, and in residential board and care occupancies shall be a minimum of 36 in. (914mm). Open guards, other than approved existing open guards, shall have intermediate rails or an ornamental pattern such that a sphere 4 in. (100 mm) in diameter is not able to pass through any opening up to a height of 34 in. (865 mm), and the following also shall apply: (1) The triangular openings formed by the riser, tread, and bottom element of a guardrail at the open side of a stair shall be of such size that a sphere 6 in. (150 mm) in diameter is not able to pass through the triangular opening. (2) In detention and correctional occupancies, in industrial occupancies, and in storage occupancies, and in areas not accessible to the public in storage occupancies, the clear distance between intermediate rails, measured at right angles to the rails, shall not exceed 21 in. (535 mm). Exception No.1 Approved existing open guards. Exception No.2 Mercantile occupancies in accordance with Exception No.3 A bottom rail or curb is not required on guardrails with dwelling units or residential board and care occupancies. Enclosed, usable space shall be permitted under stairs, provided that the following criteria are met: (3) The space is not used for the storage of flammable, or otherwise hazardous materials. FBC FBC , Exception #4 Differs from 101 existing and 12 ed; FBC - guards shall have a height no less than 34 in. & no more than 38 in. The exceptions struck do not appear in 101 existing or 12 ed.; FBC - Required guards shall not have openings which allow passage of a sphere 4 inches (102 mm) in diameter from the walking surface to the required guard height. The High Velocity Hurricane Zone shall comply with Sections and Exception #4-4. In areas that are not open to the public within occupancies in Group I- 3, F, H or S, and for alternating tread devices and ship ladders, guards shall not have openings which allow passage of a sphere 21 inches (533 mm) in diameter No provisions in FBC or FS The modification does not appear in 101 existing or 12 ed (1) (d) Ramps that are part of the required means of egress shall be not less than 44 in.wide. FBC The minimum width of a means of egress ramp shall not be less than that required for corridors by Section The clear width of a ramp between handrails, if provided, or other permissible projections shall be 36 inches (914 mm) minimum. Section The minimum corridor width shall be as determined in Section , but not less than 44 inches (1118 mm). Page 6 NFPA 101

7 Table (a) New Ramps Minimum width clear of all obstructions, except projections not more than 3½ in. (90mm) more than 4½ in. (114 mm) at or below handrail height on each side FBC Requires projections not to exceed 4 1/2 inches Drop-Offs. Ramps and landings with drop-offs shall have curbs, walls, railings, or projecting surfaces that prevent people from traveling off the edge of the ramp. Curbs or barriers shall be not less than 4 in. (100 mm) in height or any other arrangement installed in compliance with the current edition of the Florida Building Code. Guards complying with shall be provided for ramps, unless otherwise provided in Handrails complying with shall be provided along both sides of a ramp segment steeper than 1 in 20. Handrails that are not continuous shall extend at least 18 in. (305mm) beyond the top and bottom of the ramp segment and shall be parallel with the floor or ground surface. The height of handrails and guards shall be measured vertically to the top of the guard or rail from the walking surface adjacent therto. FBC keep base code only Handrails shall be provided along both sides of a ramp run with a rise greater than 6 inches (152 mm) and shall conform to the requirements in Sections If handrails are not continuous, they shall extend at least 18 inches (305 mm) beyond the top and bottom of the ramp segment and shall be parallel with the floor or ground surface. Ends of handrails shall be either rounded or returned smoothly to floor, wall or post. Handrails shall not rotate within their fittings. Top of the handrail gripping surface shall be not less than 34 inches (864 mm) nor more than 38 inches (965 mm) above the ramp surface Extended Floor or Ground Surface. The floor or ground surface of the ramp run or landing shall extend 12 in. (305mm) minimum beyond the inside face of a handrail complying with Curb or Barrier. A curb or barrier shall be provided that prevents the passage of a 4 in. (102mm) diameter sphere, where any portion of the sphere is within 4 in. (102mm) of the floor or ground surface. Alternating tread devices complying with shall be permitted in the means of egress only where providing one of the following: (5) A means of egress from a mezzanine of not more than 250 sq. ft. (23 m2) in industrial, health care, storage, detention and correctional occupancies and within dwelling units of residential occupancies. FBC FBC FBC FBC has similar language. FBC has similar language. Limited to Groups F, H & S not more than 250 sq ft in area & serves not more than 3 occupants Alternating tread devices shall comply with the following: (5) The height of the riser shall not exceed 8 in. (203mm) 9½ in. (240 mm). (6) Treads shall have a projected tread depth of not less than 54/5 in. (145 mm), measured in accordance with 7.2.2, with each tread providing 9½ in. (240 mm) of depth, including tread overlap. (6) Alternating tread stairways shall have a projected tread, exclusive of nosing, of 8 ½ in (216mm) within minimum total tread depth of 10 ½ in (267 mm). (11) A minimum of 12 in (305mm) shall be provided between the stair handrails to adjacent alternating tread stairways FBC ; not sure on (11) Riser hieght shall be a max 9 1/2 inches; Projected tread of 5 inches, min tread depth of 8 1/2 inches, min treadth width of 7 inches. Table Table Note: Day-Care Use before 10/1/ net; net F.S (6) FS (6) - Prior to 1992, 20 sq ft net per child; after 1992, 35 sq ft net per child Page 7 NFPA 101

8 Projections within the means of egress of not more than 4 ½ in. (114 mm) on each Exception: Objects projecting from walls with their leading edges between 27 and 80 in. (686 and 2032 mm) above the finished floor shall protrude no more than 4 in. (102 mm) into walks, corridors, passageways, or aisles. Free standing objects mounted on posts or pylons may overhang 12 in. (305 mm) maximum from 27 to 80 in. (686 and 2032 mm) above the ground or finished floor. FBC FBC has similar language The width of exit access that is formed by furniture and movable partitions, that serves not more than six people, and that has a length not exceeding 50 ft (15 m) shall meet both of the following criteria: (3) Hurricane Protection Devices. The temporary installation or closure of storm shutters, panels, and other approved hurricane protection devices shall be permitted on emergency escape and rescue openings in residential occupancies during the threat of a storm. Such devices shall not be required to comply with the operational constraints of While such protection is provided, at least one means of escape from each occupied unit shall be within the first floor of the unit and shall not be located within a garage. Occupants in any part of the unit shall be able to access the means of escape without passing through a lockable door not under their control. Emergency generators providing power to emergency lighting systems shall be installed, tested, and maintained in accordance with NFPA 110, Standard for Emergency and Standby Power Systems and Article 700, Emergency Systems of the National Electric Code. Stored electrical energy systems, where required in this Code, other than battery systems for emergency luminaires in accordance with , shall be installed and tested in accordance with NFPA 111, Standard on Stored Electrical Energy Emergency and Standby Power Systems. FBC Unknown source FBC has similar language Language added; FBC requires NFPA 70 along with NFPA 110 & NFPA 111; NFPA recommends not to have this amendment - too restrictive. Also, NFPA 110 & 111 reference NFPA Where the contents are classified as high hazard, exits shall be provided and arranged to allow all occupants to escape from the building or structure, or from the hazardous area thereof, to the outside or to a place of safety with a travel distance of not more than 75 ft (23 m), measured as required in unless otherwise provided in This has been deleted in its entirety by the State of Florida. The requirement of shall not apply to storage occupancies as otherwise provided in Chapter 42. The Florida Building Code NFPA 220, Standard on Types of Building Construction, shall be used to determine the requirements for the construction classification. FBC 1016 FBC (2) FBC 1016, Exit Access Travel Distance - Hazardous Storage (H-1 thru H-5) travel distance is from 75 ft to 200 ft. Storage (S-1 & S-2) travel distance from 200 ft to 400 ft. See above comment (2) The State Fire Marshal shall adopt the National Fire Protection Association s Standard 1, Fire Prevention Code but shall not adopt a building, mechanical, or plumbing code. The State Fire Marshal shall adopt the Life Safety Code, Pamphlet 101, current editions, by reference. The State Fire Marshal may modify the selected codes and standards as needed to accommodate the specific needs of the state. Page 8 NFPA 101

9 Each new Fire Wall, Fire Barrier, Fire Partition, Smoke Barrier, Smoke Partition, or any other new wall required to have protected openings shall be permanently identified with signs or stenciling above any decorative ceiling and in concealed spaces with the wording, FIRE AND SMOKE BARRIER PROTECT ALL OPENINGS, or similar language. Such signs or stenciling shall be in 4 inch high letters, ½ inch stroke, and not more than 15 feet on-center. FBC 713.6; see also Same language as in FBC except no size of lettering specified The provisions of Section 9.6 shall apply only where specifically required by another section of this Code or where supervision of a new fire sprinkler system or new fire alarm system is required by the Florida Building Code. Unless otherwise provided in through , notification signals for occupants to evacuate shall be audible and visible signals in accordance with NFPA 72, National Fire Alarm Code. and ICC/ANSI A117.1, American National Standard for Accessible and Usable Buildings and Facilities, or other means of notification acceptable to the authority having jurisdiction shall be provided. Unknown source F.S Language added Not change in 101, 12 ed; not in 101; possible reference to a building code 9.8 ( ( ( ( ( ( ( ( ( ( Special Inspections and Tests. F.S. Where required by another section of this Code, special inspections and tests F.S. shall be performed to verify the operation of the fire protection system in its final condition for acceptance by the authority having jurisdiction. The special inspector's relevant experience in the design, installation, and testing F.S of the fire protection systems being tested shall be documented. The design documents shall provide the procedures and methods to be used and F.S. items subject to special inspections and tests. The special inspector shall submit an inspection and test report to the authority having jurisdiction and registered design professional in responsible charge. Minimum construction requirements shall be in accordance with the Florida Building Code applicable occupancy chapter. F.S (2) 9.8 is Carbon Monoxide (CO) in ed 9.9 "Special Inspections and Tests" ibid ibid ibid ibid (2) The State Fire Marshal shall adopt the National Fire Protection Association s Standard 1, Fire Prevention Code but shall not adopt a building, mechanical, or plumbing code. The State Fire Marshal shall adopt the Life Safety Code, Pamphlet 101, current editions, by reference. The State Fire Marshal may modify the selected codes and standards as needed to accommodate the specific needs of the state. Page 9 NFPA 101

10 Underground and limited access structures, and all areas and floor levels traversed in traveling to the exit discharge, shall be protected by an approved, supervised automatic sprinkler system in accordance with Section 9.7, unless such structures meet one of the following criteria: (1) They have an occupant load of 50 or fewer persons in new underground or limited access portions of the structure. (1) (2)They have an occupant load of 100 or fewer persons in existing underground or limited access portions of the structure. (2) (3)The structure is a one-story underground or limited access structure that is permitted to have a single exit per Chapters 12 through 42, with a common path of travel not greater than 50 ft (15 m). FBC Not change in 101, 12 ed; FBC has similar language with all 3 criterias. removing the Florida Specific Amendment. This section is not in the 2013 FBC. Now states Automatic sprinkler system. The highest level of exit discharge serving the underground portions of the building and all levels below shall be equipped with an automatic sprinkler system installed in accordance with Section Water-flow switches and control valves shall be supervised in accordance with Section Exits from underground structures with an occupant load of more than 100 persons in the underground portions of the structure and having a floor used for human occupancy located more than 30 ft (9140 mm) below the lowest level of exit discharge, or having more than one level located below the lowest level of exit discharge, shall be provided with outside smoke-venting facilities or other means to prevent the exits from becoming charged with smoke from any fire in the areas served by the exits. Locking devices complying with shall be permitted to be used on a single door or a single pair of doors if both of the following conditions apply: (1) The door or pair of doors serve as the main exit and the assembly occupancy has an occupant load not greater than (2) Any latching devices on such a door(s) from an assembly occupancy having an occupant load of 100 or more are released by panic hardware or fire exit hardware. FBC FBC , #2 Not change in 101, 12 ed; FBC has similar language but no reference to occupant load Not change in 101, 12 ed; FBC reqires occupant load of 300 or less for assembly occupancies The path of travel along the aisle accessway shall not exceed ft ( m) from any seat to the closest aisle or egress doorway. Where the occupant load exceeds 100, the The following assembly occupancies shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with (1): (1) Bars with live entertainment (2) Dance halls (3) Discotheques (4) Nightclubs or similar usage (5) Assembly occupancies with festival seating FBC FBC adding the following language to "Dance Halls" to align with FBC - (serving food or drink) Not change in 101, 12 ed; FBC has identical language with 30 ft requirement. 101, 12 ed: Bars with live enterainment removed; FBC requirements - A-1 & A-3 occupant load > 300; A-2 occupant load > 100 Page 10 NFPA 101

11 Interior corridors and lobbies shall be constructed in accordance with and Section 8.3, unless otherwise permitted by the following: (1) Corridor and lobby protection shall not be required where assembly rooms served by the corridor or lobby have at least 50 percent of their exit capacity discharging directly to the outside, independent of corridors and lobbies. (2) Corridor and lobby protection shall not be required in buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. (3) Lobbies serving only one assembly area that meet the requirements for intervening rooms (see ) shall not be required to have a fire resistance rating. (4) Where the corridor ceiling is an assembly having a 1-hour fire resistance rating where tested as a wall, the corridor walls shall be permitted to terminate at the corridor ceiling. (5) Corridor and lobby protection shall not be required in buildings protected throughout by an approved, total (complete) coverage smoke detection system providing occupant notification and installed in accordance with Section 9.6. Unknown source Not change in 101, 12 ed Where the nature of the special amusement building is such that it operates in reduced lighting levels, the building shall be protected throughout by an approved automatic smoke detection system in accordance with Section 9.6. Exception: In areas where ambient conditions will cause a smoke detection system to alarm, an approved alternative type of automatic detector shall be installed. Where the occupant load exceeds , the following assembly occupancies shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with (1): (1) Bars with live entertainment (1) (2) Dance halls (2) (3) Discotheques (3) (4) Nightclubs or similar usage (4) (5) Assembly occupancies with festival seating FBC FBC ; addressed in adding the following language to "Dance Halls" to align with FBC - (serving food or drink) Not change in 101, 12 ed; FBC - Similar language; In spaces where smoke detectors cannot be utilized due to ambient condition, apporved automatic heat detectors shall be permitted. 101, 12 ed: Bars with live enterainment removed; FBC requirements - A-1 & A-3 occupant load > 300; A-2 occupant load > No dead-end corridor shall exceed 20 ft (6100 mm)., other than in buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7, in which case dead-end corridors shall not exceed 50 ft (15 m). No common path of travel shall exceed 75 ft (23 m). Limitations on common path of travel shall be in accordance with and FBC ; FAC 69A (14)(a) FBC Not change in 101, 12 ed: FBC - Dead-end corridor shall not exceed 20 ft except for fully sprinkler then 50 ft. FAC 69A (14)(a) requires dead-end corridors no more than 20 ft with no exception for sprinklers. Not change in 101, 12 ed; FBC - Common path of travel for E Occupancies shall not exceed 75 ft. No exceptions for sprinkler system. Nothing in FAC 69A-58. Page 11 NFPA 101

12 Common path of travel shall not exceed 100 ft (30 m) in a building protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. Common path of travel shall not exceed 75 ft (23 m) in a building not protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. Lockups. Lockups in educational occupancies shall comply with the requirements of Rule 69A , Florida Administrative Code Lockups. Lockups in educational occupancies, other than approved existing lockups, shall comply with the requirements of Rule 69A , Florida Administrative Code No dead-end corridor shall exceed 20 ft (6100 mm).,other than in buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7, in which case dead-end corridors shall not exceed 50 ft (15 m). No common path of travel shall exceed 75 ft (23 m).,other than for the first 100 ft (30 m) in a building protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. Limitations on common path of travel shall be in accordance with and Common path of travel shall not exceed 100 ft (30 m) in a building protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. Common path of travel shall not exceed 75 ft (23 m) in a building not protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. Lockups. Lockups in day care occupancies shall comply with the requirements of Lockups. Lockups in day care occupancies, other than approved existing lockups, shall comply with the requirements of FBC FBC A A FBC FBC FBC FBC No provisions in FBC or FS No provisions in FBC or FS Not change in 101, 12 ed; Common path of travel for E Occupancies shall not exceed 75 ft. No exceptions for sprinkler system. Nothing in FAC 69A-58. Not change in 101, 12 ed; Common path of travel for E Occupancies shall not exceed 75 ft. No exceptions for sprinkler system. Nothing in FAC 69A-58. Not change in 101, 12 ed Not change in 101, 12 ed Not change in 101, 12 ed; FBC - Dead-end corridors shall not exceed 20 ft, no exception for sprinklers FBC provides exception for sprinklers - 50 ft. Not change in 101, 12 ed ; FBC - Common path of travel shall not exceed 75 ft., no exception for sprinklers Not change in 101, 12 ed; FBC - common path of travel shall not exceed 75 ft, no exceptions for sprinklers Not change in 101, 12 ed; FBC - common path of travel shall not exceed 75 ft, no exceptions for sprinklers Not change in 101, 12 ed Not change in 101, 12 ed Page 12 NFPA 101

13 Emergency egress and relocation drills shall be conducted as follows: (1) Not less than one emergency egress and relocation drill shall be conducted every month the facility is in session, unless both of the following criteria are met: (a) In climates where the weather is severe, the monthly emergency egress and relocation drills shall be permitted to be deferred. (b) The required number of emergency egress and relocation drills shall be conducted, and not less than four shall be conducted before the drills are deferred. (2) All occupants of the building shall participate in the drill. (3) One additional emergency egress and relocation drill, other than for day-care occupancies that are open on a year-round basis, shall be required within the first 30 days of operation. (4) Fire emergency egress and relocation drills conducted must include, at a minimum: (a) One fire emergency egress and relocation drill using the established napping or sleeping times. (b) One fire emergency egress and relocation drill using an alternate evacuation route. Occupants of rooms that are not on the ground level or that have a window for rescue shall be permitted to use the main classroom door to exit and then travel in a different direction from that point. (c) One fire drill in the presence and at the request of the authority having jurisdiction FAC 65C-20(3)(b)4a-c Dead-end corridors shall not exceed ft ( mm). FBC Common path of travel shall not exceed ft (23m 30 m) FBC Arrangement of Means of Egress (See ) See , , & Means of egress shall be arranged in accordance with Section : Dead-end corridors shall not exceed 20 ft. (6.1m). FBC Common path of travel shall not exceed 75 ft. (23m). FBC All new one- and two-family dwellings shall be protected throughout by an approved automatic sprinkler system in accordance with (9) Not change in 101, 12 ed: FAC - The fire drills conducted must include, at a minimum: a. One fire drill during the established napping/sleeping times, b. One fire drill using an alternate evacuation route, and c. One fire drill in the presence and at the request of the licensing authority in coordination with the operator. Not change in 101, 12 ed; FBC requires dead-end corridors not to exceed 20 ft.; no exception for sprinklers Not change in 101, 12 ed; FBC requires common path of travel not to exceed 75 ft., no exception for sprinklers The modification does not appear in 101 existing or 12 ed. The modification does not appear in 101 existing or 12 ed. The modification does not appear in 101 existing or 12 ed.; FBC requires dead-end corridors not to exceed 20 ft., no exceptions for sprinklers The modification does not appear in 101 existing or 12 ed.; FBC requires common path of travel not to exceed 75 ft., no exception for sprinklers. The provisions of the Life Safety Code shall not apply to newly constructed one-family and two-family dwellings. However, fire sprinkler protection may be permitted by local government in lieu of other fire protectionrelated development requirements for such structures. While local governments may adopt fire sprinkler requirements for one- and twofamily dwellings under this subsection, it is the intent of the Legislature that the economic consequences of the fire sprinkler mandate on home owners be studied before the enactment of such a requirement... Page 13 NFPA 101

14 * In buildings not protected throughout by an approved, automatic sprinkler system in accordance with , dead-end corridors shall not exceed ft ( m). In buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with , dead-end corridors shall not exceed ft ( m). Travel distance within a guest room or guest suite to a corridor door shall not exceed ft (23 38 m) in buildings protected by an approved, supervised automatic sprinkler system in accordance with Dead-end corridors shall not exceed ft ( m) in buildings not protected throughout by an approved automatic sprinkler system in accordance with Dead-end corridors shall not exceed ft ( m) in buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Apartment buildings four or more stories in height or with more than 11 dwelling units, other than those meeting the requirements of , shall be provided with a fire alarm system in accordance with Section 9.6, except as modified by through Smoke Alarms. Smoke alarms shall be installed in accordance with in every sleeping area, outside every sleeping area in the immediate vicinity of the bedrooms, and on all levels of the dwelling unit, including basements. Exception: In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. The opening dimensions required by shall not apply where interconnected smoke alarms are installed in the bedroom(s) and in the living area(s). Fire Department Notification shall not be required in existing apartment buildings 4 stories or less in height, when all of the following are provided: (1) An approved sign is provided at each manual fire alarm pull box reading Local Alarm Only - In Case of Fire Call 911. The lettering and numbers on approved signs shall have a minimum height of ½ inch 2 inches, with a minimum 1/8 inch 3/8 inch stroke width, and shall be white red in color on red white background located no higher than 4 inches directly above the manual fire alarm box and; (2) A combination visual and audible notification device is provided at an approved location on the outside wall FBC FBC , exception #2 FBC FBC FBC , exception #2 FBC (3) FBC Unknown source Unknown source Not change in 101, 12 ed; FBC requires dead-end corridors not to exceed 20 ft. Not change in 101, 12 ed; FBC provides exception for sprinklers - dead-end corridors not to exceed 50 ft. Not change in 101, 12 ed; FBC requires for R-1 (Hotels) & for R-2 (Dormitories) a travel distance not to exceed 125 ft. with sprinklers. Not change in 101, 12 ed; FBC requires dead-end corridors not to exceed 20 ft Not change in 101, 12 ed; FBC provides exception for sprinklers - dead-end corridors not to exceed 50 ft. Not change in 101, 12 ed; FBC #3 requires fire alarm to be installed for buildings containing more than 11 dwelling units or sleeping units. Not change in 101, 12 ed; FBC - In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. Not change in 101, 12 ed Page 14 NFPA 101

15 ( (2012 High-Rise Building Sprinklers. All high-rise buildings, other than those meeting or , shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with , not later than December 31, Notwithstanding chapter 633 or of any other code, statute, ordinance, administrative rule, or regulation, or any interpretation of the foregoing, an association, condominium, or unit owner is not obligated to retrofit the common elements, association property, or units of a residential condominium with a fire sprinkler system in a building that has been certified for occupancy by the applicable governmental entity if the unit owners have voted to forego such retrofitting by the affirmative vote of a majority of all voting interests in the affected condominium. The local authority having jurisdiction may not require completion of retrofitting with a fire sprinkler system before the end of By December 31, 2016, an association that is not in compliance with the requirements for a fire sprinkler system and has not voted to forego retrofitting of such a system must initiate an application for a building permit for the required installation with the local government having jurisdiction demonstrating that the association will become compliant by December 31, ( ( * When used to satisfy the requirements of , the term Engineered Life Safety System shall only apply as an alternative to complete automatic fire sprinkler protection in existing high-rise buildings. An Engineered Life Safety System does not apply to existing low-rise buildings. Minimum Construction Requirements. Building construction shall be in accordance with the Florida Building Code. Large board and care facilities shall be limited to the building construction types specified in Table (see 8.2.1), based on the number of stories in height as defined in Declaratory Statement, Case No FM. Renumber to (2) Dead-end corridors shall not exceed ft ( mm). FBC In buildings protected throughout by an approved, supervised automatic sprinkler FBC , exception system in accordance with (1), dead-end corridors shall not exceed #2 ft ( m). Where access to exits is provided by corridors, such corridors shall be separated from use areas by fire barriers in accordance with Section 8.3 having a minimum 1-hour fire resistance rating, except under any of the following conditions: (1) Where exits are available from an open floor area (2) Within a space occupied by a single tenant provided such corridors do not serve an occupant load of 30 or more persons. (3) Within buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with (1) FBC (Table ) (2) The State Fire Marshal shall adopt the National Fire Protection Association s Standard 1, Fire Prevention Code but shall not adopt a building, mechanical, or plumbing code. The State Fire Marshal shall adopt the Life Safety Code, Pamphlet 101, current editions, by reference. The State Fire Marshal may modify the selected codes and standards as needed to accommodate the specific needs of the state. Not change in 101, 12 ed; FBC requires dead-end corridors not to exceed 20 ft. Not change in 101, 12 ed; FBC provides exception for sprinklers - dead-end corridors not to exceed 50 ft In mercantile occupancies classified as ordinary hazard, travel distance shall not exceed 150 ft (46 m). Should be * Not changed in 101, 21 ed; FBC requires corridors to be 1 hour rated if occupant load is > 30 or if sprinkler then no rating Page 15 NFPA 101

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44

More information

http://www.iccsafe.org/

http://www.iccsafe.org/ Sections R311 and R312 from the 2006 International Residential Code These sections of Chapter 3 of the 2006 International Residential Code for One and Two Family Dwellings (R311 and R312) including the

More information

CHAPTER 9 FIRE PROTECTION SYSTEMS

CHAPTER 9 FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes

More information

The replacement or modification of existing windows shall comply with the following requirements:

The replacement or modification of existing windows shall comply with the following requirements: City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)

More information

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this

More information

Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:

Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 STAIRWAYS 46. LANDINGS. Section R311 IRC 2009 R311.7.5 Landings for stairways. There shall be a floor or

More information

New York City Department of Buildings

New York City Department of Buildings The New NYC Building Code Chapter 10 Means of Egress New York City Department of Buildings Technical Affairs Fatma M. Amer, P.E. Copyright Materials This presentation is protected by US and International

More information

I N T E R N A T I O N A L R E S I D E N T I A L CO D E

I N T E R N A T I O N A L R E S I D E N T I A L CO D E Visual Interpretation Of The I N T E R N A T I O N A L R E S I D E N T I A L CO D E 2006 STAIR BUILDING CODE Portions of this document reproduce sections from the 2006 International Residential Code, International

More information

Number of Sides Required to Have a Handrail

Number of Sides Required to Have a Handrail Excerpt from 2012 B.C. Building Code HANDRAILS & GUARDS 9.8.7. Handrails 9.8.7.1. Required Handrails 1) Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and ramps in accordance

More information

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management

More information

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

Building Codes Update: The 2009 International Fire Code and the Apartment Industry ! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International

More information

BUILDING PERMIT SPECIFICATIONS

BUILDING PERMIT SPECIFICATIONS BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide

More information

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes. 1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310

More information

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE

More information

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013 Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have

More information

9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards.

9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards. Section 9.8. Stairs, Ramps, Handrails and Guards 9.8.1. Application 9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and

More information

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:

More information

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 **Disclaimer: This document is to serve as informational purposes only. This is not a code book or a final interpretation of the

More information

Errata has been identified as follows:

Errata has been identified as follows: 2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level

More information

2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i

2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i 2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i Changes between the 2006 and 2009 Editions of the International Codes account for the vast majority of changes to the 2010 Florida Building Code. In many

More information

5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.

5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness. NFPA 101 Life Safety Code Section 5-8 Illumination of Means of Egress 5-8.1 General. 5-8.1* Illumination of means of egress shall be provided in accordance with this section for every building and structure

More information

NFPA 101 2012 SELECT SIGNIFICANT CHANGES

NFPA 101 2012 SELECT SIGNIFICANT CHANGES NFPA 101 2012 SELECT SIGNIFICANT CHANGES William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire INTRODUCTION NFPA 101 is

More information

Certification: Building Plans Examiner. Exam ID: B3

Certification: Building Plans Examiner. Exam ID: B3 Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

CITY OF TORONTO. BY-LAW No. 349-2008

CITY OF TORONTO. BY-LAW No. 349-2008 Authority: Licensing and Standards Committee Item 12.3, adopted as amended, by City of Toronto Council on April 28 and 29, 2008 Enacted by Council: April 29, 2008 CITY OF TORONTO BY-LAW No. 349-2008 To

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS

FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS CHAPTER 46 FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS SECTION 4601 GENERAL 4601.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to a state building

More information

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM

More information

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us

More information

NFPA 101 2015 20 Frequently Asked Questions

NFPA 101 2015 20 Frequently Asked Questions February 2015 NFPA 101 2015 20 Frequently Asked Questions By Ron Coté, P.E. Ask an NFPA Expert The Technical Questions Service is free with your NFPA Membership. Our Technical Questions Service provides

More information

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

Area of Rescue Assistance Communication System ADA Code Applicable excerpts: Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment

More information

RHODE ISLAND DIVISION OF STATE FIRE MARSHAL

RHODE ISLAND DIVISION OF STATE FIRE MARSHAL RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#

More information

2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions. 1004.1 Design Occupant Load. 1005 - Means of Egress Capacity Determination

2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions. 1004.1 Design Occupant Load. 1005 - Means of Egress Capacity Determination 2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes Clay Aler, P.E. Principal caler@koffel.com Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Questions Submit

More information

Healthcare Engineering. Code Summary Report

Healthcare Engineering. Code Summary Report American Society for Healthcare Engineering Code Summary Report CODE SUMMARY HEALTH CARE NEW BUILDINGS This code summary is based on the following codes: 2000 Edition NFPA 101, The Life Safety Code (LSC),

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION BC 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES

MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012 MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

Walking and Working Surface Checklist:

Walking and Working Surface Checklist: Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:

More information

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional

More information

Life Safety Code Enabling References

Life Safety Code Enabling References SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003

M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003 M E M O R A N D U M To: Partnership for Safer Buildings Date: 21 March 2003 From: Codes Assessment Subcommittee Walter Smittle III, Chairman Re: Building Code Fire Safety Concerns: NFPA 5000, Building

More information

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.

More information

SECTION 903 AUTOMATIC SPRINKLER SYSTEMS

SECTION 903 AUTOMATIC SPRINKLER SYSTEMS Page 25 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information

More information

CHAPTER 10 MEANS OF EGRESS. User Note: See Preface page iv ("marginal markings" for Chapter 10 reorganization information.)

CHAPTER 10 MEANS OF EGRESS. User Note: See Preface page iv (marginal markings for Chapter 10 reorganization information.) CHAPTER 10 MEANS OF EGRESS User Note: See Preface page iv ("marginal markings" for Chapter 10 reorganization information.) SECTION 1001 GENERAL 1001.1 Scope. Buildings or portions thereof shall be provided

More information

Mobile Fire Rescue Department Bureau of Fire Prevention

Mobile Fire Rescue Department Bureau of Fire Prevention 222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This

More information

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the

More information

CHILD CARE CENTER INFORMATION SHEET

CHILD CARE CENTER INFORMATION SHEET CHILD CARE CENTER INFORMATION SHEET SECTION 1 INTRODUCTION This fire safety information sheet is based on the 2007 Minnesota State Fire Code (MSFC) and the 2007 Minnesota State Building Code (MSBC). It

More information

Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.

Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable

More information

TEXT (CO Detection Commercial Buildings Final) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows:

TEXT (CO Detection Commercial Buildings Final) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows: TEXT (CO Detection Commercial Buildings Final) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows: Section 1228.4. Carbon Monoxide Detection in Commercial Buildings

More information

The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services

The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services MITT ROMNEY GOVERNOR KERRY HEALEY LT. GOVERNOR EDWARD A. FLYNN SECRETARY The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services P.O. Box 1025 State Road Stow, Massachusetts

More information

Indiana Building Rehabilitation Standard

Indiana Building Rehabilitation Standard Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

New Ontario Building Code Highlights

New Ontario Building Code Highlights New Ontario Building Code Highlights Part 9 This summary highlights items that are believed to be significant changes to the 2012 OBC and is not intended to include all changes made within this or other

More information

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02

NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 PART A: Project Data and Classification 1. Project name & location Renovation of the Cheerwine Building, 322 East Council St.,

More information

New York City Department of Buildings

New York City Department of Buildings The New NYC Building Code Chapter 11 Accessibility New York City Department of Buildings Technical Affairs Keith Wen, R.A. Copyright Materials This presentation is protected by US and International Copyright

More information

Effective June 27, 2015. TEXT (CO Detection Commercial Buildings)

Effective June 27, 2015. TEXT (CO Detection Commercial Buildings) TEXT (CO Detection Commercial Buildings) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows: Section 1228.4. Carbon Monoxide Detection in Commercial Buildings (a)

More information

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use. Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent

More information

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration

More information

Errata NFPA 1. Fire Code. 2015 Edition

Errata NFPA 1. Fire Code. 2015 Edition Errata NFPA 1 Fire Code 2015 Edition Reference: 2.2, Table 6.1.14.4.1(a) and (b), 13.3.1.6, 13.7.2.13.2.1, 14.11.3.3, 18.5.2, 18.5.3, 20.1.2, 20.1.5.12, 25.1.1, 25.3, 25.4, A.3.3.164.2, and A.13.3.2.9.1

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:

More information

FIRE SAFETY REQUIREMENTS

FIRE SAFETY REQUIREMENTS FIRE SAFETY REQUIREMENTS 156.200 GENERALLY. A. Scope. The provisions of this chapter shall govern the minimum conditions and standards for fire safety relating to structures and exterior premises, including

More information

Fire Alarm Systems Requirements by Occupancy Type

Fire Alarm Systems Requirements by Occupancy Type WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

Florida Advanced Building Code Course# FLBC11

Florida Advanced Building Code Course# FLBC11 Florida Advanced Building Code Course# FLBC11 EZpdh.com All Rights Reserved CHAPTER 1 Administration: Significant Changes Chapter 1 is now split into two parts: Part 1 is Scope and Application, Part 2

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

Residential Decks. Planning and Development Services Department

Residential Decks. Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet

Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet 1. Definitions a. AHJ Authority Having Jurisdiction. The Fire Chief or Fire Marshal of a given Fire District

More information

WINDOW AND DOOR REPLACEMENT REQUIREMENTS

WINDOW AND DOOR REPLACEMENT REQUIREMENTS WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

Common ADA Errors and Omissions in New Construction and Alterations

Common ADA Errors and Omissions in New Construction and Alterations U.S. Department of Justice Civil Rights Division Disability Rights Section Common ADA Errors and Omissions in New Construction and Alterations Introduction The ADA requires that new construction and alterations

More information

Current as of 11/10/08 1 of 1

Current as of 11/10/08 1 of 1 BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009 FIRE ALARM PLAN REVIEW Office of the State Fire Marshal Massachusetts December 2009 SURPRISE QUIZ 1. A fire alarm system is required to be installed by the MSBC, what edition of NFPA 72 do you use? 2.

More information

2012 Changes of the International Building Code Compared to the National Fire Protection Association- 101

2012 Changes of the International Building Code Compared to the National Fire Protection Association- 101 2012 Changes of the International Building Code Compared to the National Fire Protection Association- 101 For the Florida Building Commission And the Fire Code Advisory Council Introduction The scope of

More information

Building Department John Fiedler Construction Official Ext. 211. SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev 4-3-2014

Building Department John Fiedler Construction Official Ext. 211. SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev 4-3-2014 TOWNSHIP OF HILLSBOROUGH COUNTY OF SOMERSET Hillsborough Township Municipal Complex The Peter J. Biondi Building 379 South Branch Road Hillsborough, NJ 08844 P: (908) 369-4313 F: (908) 369-3954 Building

More information

Fire Safety In High Rise Building

Fire Safety In High Rise Building Fire Safety In High Rise Building CLASSIFICATION OF BUILDINGS AS PER NATIONAL BUILDING CODE 1. GROUPING. Group A - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group B Group C - Educational

More information

Single Family Residential Basement Finish

Single Family Residential Basement Finish How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete

More information

Mobile Home Pre-Inspection Checklist

Mobile Home Pre-Inspection Checklist Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

Simplified Steel Stair Design for Commercial and Institutional Buildings

Simplified Steel Stair Design for Commercial and Institutional Buildings Simplified Steel Stair Design for Commercial and Institutional Buildings Collaborating with steel stair fabricators during the design of commercial and institutional buildings promotes integrated practice

More information

Control filling, grading, dredging, and other development which may increase erosion or flood damage; and

Control filling, grading, dredging, and other development which may increase erosion or flood damage; and ARTICLE 16. FLOOD DAMAGE PREVENTION Section 16-1: Findings of Fact The flood hazard areas of the Town of Lillington are subject to periodic inundation which results in loss of life and property, health

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal

MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY Policy #: Subject of Policy: INS-04 (2007) Escape Windows Revised and Approved By: Title: Jerry Rosendahl State Fire

More information

STATE BUILDING CODE 2005 CONNECTICUT SUPPLEMENT 2009 AMENDMENT

STATE BUILDING CODE 2005 CONNECTICUT SUPPLEMENT 2009 AMENDMENT STATE BUILDING CODE 2005 CONNECTICUT SUPPLEMENT 2009 AMENDMENT Sec. 29-252-1d. State Building Code 2009 Amendment to the 2005 Connecticut Supplement The 2003 International Building Code, 2003 International

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations

More information

- 5 - Table1. Maximum Compartment Volumes

- 5 - Table1. Maximum Compartment Volumes - 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,

More information

CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau

CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction

More information